New or existing? Determining scope for healthcare projects

68
Flad Architects Page 1 of 5 Flad Code Forum Notes : DD Month YYYY Flad Code Forum Notes 29 September 2015 1. Code Forums a. Notes of past code forums are posted at : i. Flad Home Page / Resources / Codes / Forums / Year / Date of Forum. b. This Code Forum will Discuss : New or Existing? Determining Scope for Healthcare Projects. c. Additional information is contained in attached power point slides: PP-pages. New or Existing? Determining Scope for Healthcare Projects PP-01 through PP-64 2. References a. NFPA 101 Life Safety Code - 2012 edition = LSC 3. LSC = (5) Major Parts : PP-01 through PP-06 a. General Chapters : Chapters 1-4 & 6-11 b. Performance-Based Option : Chapter 5 c. Occupancy Chapters : Chapters 12-42 d. Building Rehabilitation : Chapter 43 e. Annexes (A, B, & C) 4. General Chapters : PP-07 through PP-13 a. Many of the provisions of these General Chapters are mandatory for all occupancies i. Some provisions are mandated only when referenced by a specific occupancy ii. Others provisions are exempted for specific occupancies iii. Often "where permitted by Chapters 11 through 43" appears (1) (80) instances of “Chapters 11 through 43in the LSC iv. “Permitted” or “Required” or “Specified” v. “Unless prohibited” vi. “Chapter 18 & 19” References 5. LSC Application : PP-14 through PP-19 a. Apply to both new construction and existing buildings/structures b. Specific provisions for existing buildings/structures may differ from those for new i. Example : Doors in Boiler Rooms, Heater Rooms, and Mech Equip Rooms may be held open in EXISTING HC occupancies but not in NEW HC occupancies c. Existing Building. A building erected or officially authorized prior to the effective date of the adoption of this edition of the Code by the agency or jurisdiction. i. Date plans were approved for construction by the appropriate AHJ. ii. Per CMS’s S&C-11-05-LSC : (1) If the facility’s building plans were approved or a building permit was issued or construction started after the effective date, (March 13, 2003), of the final regulation, the building or addition must be surveyed under 2000 NEW LSC. (2) If the facility’s building plans were approved by a State Agency or building permit issued or construction started prior to the effective date, (March 13, 2003), of the final regulation, the building must be surveyed under 2000 EXISTING LSC. d. Major vs. Minor Rehabilitation i. LSC 2003 : establishes when a smoke compartment (SC) needs to be sprinklered as part of a rehabilitation (major - yes, minor - no) (1) Major = 50% or more of SC or more than 4500 SF (2) Minor = Less than 50% of SC and less than 4500 SF 6. Building Rehabilitation : PP-20 i. Ch 43 first appeared in the 2006 LSC.

Transcript of New or existing? Determining scope for healthcare projects

Flad Architects Page 1 of 5 Flad Code Forum Notes : DD Month YYYY

Flad Code Forum Notes 29 September 2015 1. Code Forums

a. Notes of past code forums are posted at : i. Flad Home Page / Resources / Codes / Forums / Year / Date of Forum.

b. This Code Forum will Discuss : New or Existing? Determining Scope for Healthcare Projects.

c. Additional information is contained in attached power point slides: PP-pages. New or Existing? Determining Scope for Healthcare Projects – PP-01 through PP-64 2. References

a. NFPA 101 Life Safety Code - 2012 edition = LSC 3. LSC = (5) Major Parts : PP-01 through PP-06

a. General Chapters : Chapters 1-4 & 6-11 b. Performance-Based Option : Chapter 5 c. Occupancy Chapters : Chapters 12-42 d. Building Rehabilitation : Chapter 43 e. Annexes (A, B, & C)

4. General Chapters : PP-07 through PP-13 a. Many of the provisions of these General Chapters are mandatory for all occupancies

i. Some provisions are mandated only when referenced by a specific occupancy ii. Others provisions are exempted for specific occupancies iii. Often "where permitted by Chapters 11 through 43" appears

(1) (80) instances of “Chapters 11 through 43” in the LSC iv. “Permitted” or “Required” or “Specified” v. “Unless prohibited” vi. “Chapter 18 & 19” References

5. LSC Application : PP-14 through PP-19 a. Apply to both new construction and existing buildings/structures b. Specific provisions for existing buildings/structures may differ from those for new

i. Example : Doors in Boiler Rooms, Heater Rooms, and Mech Equip Rooms may be held open in EXISTING HC occupancies but not in NEW HC occupancies

c. Existing Building. A building erected or officially authorized prior to the effective date of the adoption of this edition of the Code by the agency or jurisdiction. i. Date plans were approved for construction by the appropriate AHJ. ii. Per CMS’s S&C-11-05-LSC :

(1) If the facility’s building plans were approved or a building permit was issued or construction started after the effective date, (March 13, 2003), of the final regulation, the building or addition must be surveyed under 2000 NEW LSC.

(2) If the facility’s building plans were approved by a State Agency or building permit issued or construction started prior to the effective date, (March 13, 2003), of the final regulation, the building must be surveyed under 2000 EXISTING LSC.

d. Major vs. Minor Rehabilitation i. LSC 2003 : establishes when a smoke compartment (SC) needs to be sprinklered as

part of a rehabilitation (major - yes, minor - no) (1) Major = 50% or more of SC or more than 4500 SF (2) Minor = Less than 50% of SC and less than 4500 SF

6. Building Rehabilitation : PP-20 i. Ch 43 first appeared in the 2006 LSC.

Flad Architects Page 2 of 5 Flad Code Forum Notes : DD Month YYYY

(1) It was added to “promote the adaptive reuse of EXISTING buildings without sacrificing needed life safety.”

(2) Prior to that, any alteration to an EXISTING building was required to meet the requirements for NEW construction.

b. Rehabilitation Classifications are a stepped approach to mandate requirements. i. (1) Repair ii. (2) Renovation iii. (3) Modification iv. (4) Reconstruction v. (5) Change of use or occupancy classification vi. (6) Addition

7. Repair : PP-21 a. The patching, restoration, or painting of materials, elements, equipment, or fixtures for

the purpose of maintaining such materials, elements, equipment, or fixtures in good or sound condition.

b. Examples i. Ceiling tiles, damaged by a water leak, are replaced in an existing office. ii. A portion of the original plaster-on-lath wall is patched with a piece of GWB, sanded,

and painted to match the adjacent wall. 8. Renovation : PP-22 & PP-32

a. The replacement in kind, strengthening, or upgrading of building elements, materials, equipment, or fixtures, that does not result in a reconfiguration of the building spaces within.

b. Examples i. Ceiling tiles are replaced with newer ones in an existing office. ii. Existing lavatories and water closets are replaced on a one-to-one basis & in the

same locations for aesthetic reasons. c. Requirements

i. Interior Finish Requirements = NEW ii. All other renovation work = EXISTING

d. Renovation work must not reduce the level of code compliance 9. Modification : PP-23 & PP-33 through PP-34

a. The reconfiguration of any space; the addition, relocation, or elimination of any door or window; the addition or elimination of load-bearing elements; the reconfiguration or extension of any system; or the installation of any additional equipment.

b. Examples i. (2) adjacent offices are combined into a single larger office by removing the wall

between the rooms. All work occurs within the (2) offices. ii. A sprinkler system is voluntarily (not statutorily) added to a warehouse. (See 43.5.2.2

for exclusively Fire Protection work) c. Requirements

i. Newly constructed elements, components, and systems shall comply with NEW construction.

ii. Work must also comply with Renovation iii. Renovation work must not reduce the level of code compliance

d. Extensive Modifications i. Modification work that is exclusively electrical, plumbing, mechanical, fire protection

system, or structural work shall not be considered a reconstruction, regardless of its extent.

10. Reconstruction : PP-24 through PP-26 & PP-35 through PP-39 a. The reconfiguration of a space that affects an exit or a corridor shared by more than one

occupant space; or the reconfiguration of a space such that the rehabilitation work area

Flad Architects Page 3 of 5 Flad Code Forum Notes : DD Month YYYY

is not permitted to be occupied because existing means of egress and fire protection systems, or their equivalent, are not in place or continuously maintained.

b. Examples i. An entire floor of an existing hospital is gutted to the columns and exterior walls. New

patient rooms and staff support areas are added. ii. A portion of an existing hospital floor is closed to occupancy and isolated from the

remainder of the floor by temporary fire-resistance rated barrier. The remainder of the floor remains occupied during the rehabilitation and has independent Means of Egress from the work area.

c. Requirements i. Newly constructed elements, components, and systems shall comply with NEW

construction. ii. Work must also comply with Renovation & Modifications iii. Renovation work must not reduce the level of code compliance iv. Means of Egress

(1) If Recon Area > 50% of Floor, then (3) M of E Components for entire Floor = NEW (a) Illumination of the Means of Egress (M of E) (b) Emergency Lighting (c) Marking the M of E

v. Extinguishing Systems (1) If Recon Area > 50% of Building Area, then Sprinkler Systems (SS) – highest

Recon floor & all floors below per NEW (2) If Recon Area > 50% of Floor Area, then Sprinkler Systems (SS) – entire floor per

NEW vi. Fire Alarm Systems

(1) Smoke Alarms required in any Recon Area to meet the NEW occupant requirements (a) Lodging or Rooming Houses (b) Hotels & Dormitories (c) Apartment Buildings (d) Guest rooms (e) Dwelling Units (f) Residential Board and Care

vii. Elevators (1) In High-Rise Buildings where the Recon Area is 20% or more of the occupied

floor area, all floors must be accessible by at least (1) elevator. 11. Change of Use : PP-27 through PP-28 & PP-40

a. A change in the purpose or level of activity within a structure that involves a change in application of the requirements of the Code.

b. Examples i. A patient room is converted into a storage room that is greater than 100 sf and stores

combustible materials making it a hazardous location. ii. A living area in a small board and care (16 or less residents) is converted to a

resident room requiring it to meet the large board and care requirements (more than 16 residents)

c. Change of Use only = No Change of Occupancy + No change of Hazard Level d. Change of Use only = No Change of Occupancy + Change of Hazard Level

i. Comply w/(1) : (1) Compliance w/the requirements to the new Change of Use in accordance with its

NEW occupancy chapter

Flad Architects Page 4 of 5 Flad Code Forum Notes : DD Month YYYY

(2) Existing HC protected throughout by a supervised automatic sprinkler system & the Change of Use room/space is <250sf, it does not need to meet the NEW occupancy chapter

12. Change of Occupancy (COC) : PP-40 through PP-43 a. Other than a COC to an Assembly occupancy, ALL other occupancies w/in the

same/lesser hazard category & classification must meet : i. EXISTING occupancy chapters ii. NEW occupancy chapters

(1) Automatic Sprinkler & Detection (2) Alarm & Communication Systems (3) Hazardous Areas

iii. Example (1) Hospital (Hazard Category 2) is rehabilitated to an Ambulatory HC (Hazard

Category 3) (2) Must meet EXISTING & NEW

b. Other than a COC to an Assembly occupancy, ALL other occupancies w/in the higher hazard category & classification must meet : i. NEW occupancy chapters ii. Example

(1) Ambulatory HC (Hazard Category 3) is rehabilitated to a Hospital (Hazard Category 2)

(2) Must meet NEW 13. Addition : PP-29 & PP-44

a. An increase in the building area, aggregate floor area, building height, or number of stories of a structure.

b. Additions to an Existing Building must meet NEW occupancy chapter(s) i. Must NOT create or extend any nonconformity that affects fire safety or the Means of

Egress in the Existing Building ii. Examples

(1) Increased travel distance (2) Number of Stories based on Construction Type

c. Existing Building must meet its EXISTING occupancy chapter(s) i. Any rehabilitation work that affects the Existing Bldg must meet those requirements ii. Need separation from Addition or be sprinkled if the combined areas of the Addition

+ Exist Bldg require it per NEW 14. Repair vs Renovation : PP-30 through PP-32

a. Matter of Quantity i. Major Repair = Renovation ii. Minor Renovation = Repair iii. Examples

(1) Replacing a section of corridor carpet = Repair (2) Replacing all corridor carpet = Renovation

b. Matter of Quality i. Repair permits the use of “similar” materials to those existed before the repair work

was done provided the use of that material is not prohibited by other code sections. ii. Renovation requires the use of materials that are permitted by other code sections

for existing or new buildings. 15. History of Hospital Regulation : PP-45

a. 1946 : Hospital Survey and Construction Act i. Hill Burton Act ii. Code : Building Exits Code (pre-NFPA 101 LSC)

b. 1971 : CMS adopts the 1967 NFPA 101 LSC c. 1987 : CMS adopts the 1985 NFPA 101 LSC

Flad Architects Page 5 of 5 Flad Code Forum Notes : DD Month YYYY

d. 1995 : International Code Council formed i. Combined ICBO, BOCA, & SBCI into ICC

e. 2003 (3/11/03) : CMS adopts the 2000 NFPA 101 LSC f. 2011: CMS announces adoption of the 2012 NFPA 101 LSC g. 2012 : CMS issues waivers for 2012 NFPA 101 LSC h. 2016 (?) : CMS adopts the 2012 NFPA 101 LSC

16. Hospital Example : PP-46 through PP-63 a. 1950 Hospital + 1967/1970 Additions b. 2000 Addition c. March 3, 2003 : CMS adopts 2000 NFPA 101 Life Safety Code

i. Surveyors follow CMS's S&C-11-05-LSC which differentiates EXISTING and NEW healthcare occupancies per March 13, 2003. (1) 2000 Addition + 1967/1970/1990 Additions + 1950 Hospital should meet

EXISTING Health Care Occupancy (1985 LSC) (2) 2000 Addition + 1967/1970/1990 Additions + 1950 Hospital must meet

EXISTING Health Care Occupancy (2000 LSC) T:\twyatt\Code\Code Forums\2015 0929\2015 0929 Code Forum Notes.docx

F L A D C O D E F O R U M

New or Existing?

Determining Scope for Healthcare Projects

9/29/2015 Flad Code Forum 1

O U T L I N E

• NFPA 101 Life Safety Code (LSC) Overview

– Chapters 1-11 + 43 vs. Chapters 12-42

• New vs. Existing Health Care Occupancies

• Chapter 43 : Rehabilitation Work

• Example : Hospital

9/29/2015 Flad Code Forum 2

NFPA 101 Life Safety Code (2012)

• LSC is comprised of (5) major parts

– General Chapters : Chapters 1-4 & 6-11

– Performance-Based Option : Chapter 5

– Occupancy Chapters : Chapters 12-42

– Building Rehabilitation : Chapter 43

– Annexes (A, B, & C)

9/29/2015 Flad Code Forum 3

NFPA 101 Life Safety Code (2012)

• (31) Occupancy Chapters – Ch 12/13 Assembly

– Ch 14/15 Education

– Ch 16/17 Day-Care

– Ch 18/19 Health Care

– Ch 20/21 Ambulatory Health Care

– Ch 22/23 Detention and Correctional

– Ch 24 One- and Two-Family Dwellings

– Ch 25 Reserved

– Ch 26 Lodging or Rooming Houses

– Ch 27 Reserved

– Ch 28/29 Hotels and Dormitories

– Ch 30/31 New Apartment

– Ch 32/33 Residential Board and Care

– Ch 34 Reserved

– Ch 36/37 Mercantile

– Ch 34 Reserved

– Ch 38/39 Business

– Ch 40 Industrial

– Ch 41 Reserved

– Ch 42 Storage

• (11) New/Existing + (4) New + (5) Reserved

• (12) General Chapters– Ch 1 Administration

– Ch 2 Referenced Publications

– Ch 3 Definitions

– Ch 4 General

– Ch 5 Performance-Based Option

– Ch 6 Classification of Occupancy and Hazard of Contents

– Ch 7 Means of Egress

– Ch 8 Features of Fire Protection

– Ch 9 Building Service and Fire Protection Equipment

– Ch 10 Interior Finish, Contents, and Furnishings

– Ch 11 Special Structures and Hi-Rise Buildings

– Ch 43 Building Rehabilitation

• Annexes– Annex A Explanatory Material

– Annex B Supplemental Evacuation Equipment

– Annex C Informational References

07/30/2015 Flad Code Forum 4

NFPA 101 Life Safety Code (2012)

• (31) Occupancy Chapters – Ch 12/13 Assembly

– Ch 14/15 Education

– Ch 16/17 Day-Care

– Ch 18/19 Health Care

– Ch 20/21 Ambulatory Health Care

– Ch 22/23 Detention and Correctional

– Ch 24 One- and Two-Family Dwellings

– Ch 25 Reserved

– Ch 26 Lodging or Rooming Houses

– Ch 27 Reserved

– Ch 28/29 Hotels and Dormitories

– Ch 30/31 New Apartment

– Ch 32/33 Residential Board and Care

– Ch 34 Reserved

– Ch 36/37 Mercantile

– Ch 34 Reserved

– Ch 38/39 Business

– Ch 40 Industrial

– Ch 41 Reserved

– Ch 42 Storage

• (12) General Chapters– Ch 1 Administration

– Ch 2 Referenced Publications

– Ch 3 Definitions

– Ch 4 General

– Ch 5 Performance-Based Option

– Ch 6 Classification of Occupancy and Hazard of Contents

– Ch 7 Means of Egress

– Ch 8 Features of Fire Protection

– Ch 9 Building Service and Fire Protection Equipment

– Ch 10 Interior Finish, Contents, and Furnishings

– Ch 11 Special Structures and Hi-Rise Buildings

– Ch 43 Building Rehabilitation

• Annex– Annex A Explanatory Material

– Annex B Supplemental Evacuation Equipment

– Annex C Informational References

07/30/2015 Flad Code Forum 5

NFPA 101 Life Safety Code (2012)

• (4) Occupancy Chapters – Ch 18/19 Health Care

– Ch 20/21 Ambulatory Health Care

• (10) General Chapters– Ch 1 Administration

– Ch 2 Referenced Publications

– Ch 3 Definitions

– Ch 4 General

– Ch 6 Classification of Occupancy and Hazard of Contents

– Ch 7 Means of Egress

– Ch 8 Features of Fire Protection

– Ch 9 Building Service and Fire Protection Equipment

– Ch 10 Interior Finish, Contents, and Furnishings

– Ch 43 Building Rehabilitation

• Annex– Annex A Explanatory Material

07/30/2015 Flad Code Forum 6

(10) General Chapters (1-4, 6-11)

• Building blocks for occupancy chapters (12-42)

• Many of the provisions of these General Chapters are mandatory for all occupancies– Some provisions are mandated only when referenced by a specific

occupancy

– Others provisions are exempted for specific occupancies

– Often "where permitted by Chapters 11 through 43" appears

• 4.3* Assumptions.

– 4.4.2.3 Where specific requirements contained in Chapters 11 through 43 differ from general requirements contained in Chapters 1 through 4, and Chapters 6 through 10, the requirement of Chapters 11 through 43 shall govern

• (80) instances of “Chapters 11 through 43” in the LSC (2012)

9/29/2015 Flad Code Forum 7

“Where Permitted” Example

• 7.2.1.6.1 Delayed-egress locks

– Only allowed when permitted by Chapters 11 through

43. Permission to use the delayed-egress lock is

normally found in the " __ .2.2" subsection of each

occupancy chapter.

– For example, 12.2.2.2.5 specifically permits the use of

delayed-egress locks in New Assembly occupancies.

• If this permission is not found in an occupancy

chapter, the delayed-egress lock cannot be used.

9/29/2015 Flad Code Forum 8

“Permitted” or “Required” or “Specified”

• 4.7 Fire Drills– 4.7.1 Where Required

– 4.7.2 Drill Frequency

• 6.2 Hazard of Contents. – 6.2.1.3 … hazardous areas are separated …

• 7.1.3.1 Exit Access Corridors

• 7.2.1.4.1 Swinging-Type Door Assembly Requirement

• 7.2.1.5.5 Key-Operated Locks

• 7.2.1.5.7 … cannot be removed when the door leaf …

• 7.2.1.5.8 … Re-entry from the stair enclosure

• 7.2.1.6.1 Delayed-Egress Locking Systems

• 7.2.1.6.2 Access-Controlled Egress Door Assemblies

• 7.2.1.6.3 Elevator Lobby Exit Access Door Assemblies Locking

• 7.2.1.10 Revolving Door Assemblies

• 7.2.1.11 Turnstiles

• 7.2.1.15 Inspection of Door Openings

• 7.2.2.2.3 Spiral Stairs

• 7.2.2.2.4 Winders

• 7.2.2.5.5 Exit Stair Path Markings

• 7.2.8 Fire Escape Stairs

• 7.2.10 Slide Escapes

• 7.3.4 Minimum Width

• 7.4 Number of Means of Egress

• 7.5 Arrangement of Means of Egress

• 7.5.3 Exterior Ways of Exit Access

• 7.6.7 Travel distance limitations

• 7.8 Illumination of Means of Egress

• 7.9 Emergency Lighting

• 7.10 Marking of Means of Egress

• 7.13 Normally Unoccupied Building Service Equipment Support Areas

• 8.2 Construction and Compartmentation

• 8.3.4.4 20-minute fire protection-rated door

• 8.3.5 Penetrations

• 8.3.6 Joints

• 8.4.5 Joints

• 8.5.7 Joints

• 8.6.9 Convenience Openings

• 9.6.3 Occupant Notification

9/29/2015 Flad Code Forum 9

“Unless prohibited” Examples

• In other locations in the General Chapters, the

wording "unless prohibited by Chapters 11

through 43" is used.

– (5) examples in LSC (2012)

• In these cases, the provision is permitted in

ALL occupancies, UNLESS specifically

prohibited by an occupancy chapter.

9/29/2015 Flad Code Forum 10

“Unless prohibited” Examples

• 7.2.1.4.1 Swinging-Type Door Assembly Requirement. – (4) Horizontal-sliding door assemblies shall be permitted … unless prohibited by Chapters 11

through 43 …

• 7.8 Illumination of Means of Egress. – 7.8.1.2.2 Unless prohibited by Chapters 11 through 43, automatic, motion sensor-type lighting

switches shall be permitted …

• 7.13 Normally Unoccupied Building Service Equipment Support Areas.– 7.13.1.1 Unless prohibited by Chapters 11 through 43, the provisions of Section 7.13 shall

apply …

• 8.6.6 Communicating Space. – Unless prohibited by Chapters 11 through 43, unenclosed floor openings forming a

communicating space between floor levels shall be permitted …

• 8.6.7 Atriums. – Unless prohibited by Chapters 11 through 43, an atrium shall be permitted …

9/29/2015 Flad Code Forum 11

“Chapter 18 & 19” References

• 7.1.9 Impediments to Egress. Any device or alarm installed to restrict the improper use of a means of egress shall be designed and installed so that it cannot, even in case of failure, impede or prevent emergency use of such means of egress, unless otherwise provided in 7.2.1.6 and Chapters 18, 19, 22, and 23.

• 7.2.1.5 Locks, Latches, and Alarm Devices. – 7.2.1.5.4 The requirements of 7.2.1.5.1 and 7.2.1.5.3 shall not apply

where otherwise provided in Chapters 18 through 23.

• 7.2.4 Horizontal Exits. – 7.2.4.1.3 The requirement of 7.2.4.1.2 shall not apply to the following:

• (1) Health care occupancies as otherwise provided in Chapters 18 and 19

9/29/2015 Flad Code Forum 12

“Chapter 18 & 19” References

• 7.2.4.2 Fire Compartments.– 7.2.4.2.1.1 Any fire compartment not having an exit leading outside shall be considered as

part of an adjoining compartment with an exit leading to the outside.

– 7.2.4.2.1.2 The requirement of 7.2.4.2.1 shall not apply to the following: • (1) Health care occupancies as otherwise provided in Chapters 18 and 19

– 7.2.4.2.4 The floor area on either side of a horizontal exit shall be sufficient to hold the occupants of both floor areas and shall provide at least 3 ft2 (0.28 m2) clear floor area per person, unless otherwise permitted for the following: • (1) Health care occupancies as provided in Chapters 18 and 19

• 7.3.2 Measurement of Means of Egress. – 7.3.2.3 In health care and ambulatory health care occupancies, projections shall be permitted

in corridors in accordance with Chapters 18 through 21.

• 9.6.3 Occupant Notification. – 9.6.3.5.2 Visible-only signals shall be provided where specifically permitted in health care

occupancies in accordance with the provisions of Chapters 18 and 19.

9/29/2015 Flad Code Forum 13

LSC Application

• 1.3 Application. – 1.3.1* New and Existing Buildings and Structures. The

Code shall apply to both new construction and existing buildings and existing structures. • *A.1.3.1 Various chapters contain specific provisions for

existing buildings and structures that might differ from those for new construction.

• EXAMPLE– Doors in Boiler Rooms, Heater Rooms, and Mech

Equip Rooms may be held open in EXISTING HC occupancies but not in NEW HC occupancies.

9/29/2015 Flad Code Forum 14

Suggested Procedure :

Code RequirementsAnnex A Explanatory Material

A.1.1 The following is a suggested procedure for determining the Code requirements for a building or structure:

1. Determine the occupancy classification by referring to the occupancy definitions in Chapter 6 and the occupancy Chapters 12 through 42. (See 6.1.14 for buildings with more than one use.)

2. Determine if the building or structure is new or existing. (See the definitions in Chapter 3.)

3. Determine the occupant load. (See 7.3.1.)

4. Determine the hazard of contents. (See Section 6.2.)

5. Refer to the applicable occupancy chapter of the Code, Chapters 12 through 42. [See Chapters 1 through 4 and Chapters 6 through II, as needed, for general information (such as definitions) or as directed by the occupancy chapters

6. Determine the occupancy subclassification or special use condition, if any.

7. Proceed through the applicable occupancy chapter to verify compliance with each referenced section, subsection, paragraph, subparagraph, and referenced codes, standards, and other documents.

8. Where two or more requirements apply, refer to the occupancy chapter, which generally takes precedence over the base Chapters 1 through 4 and Chapters 6 through 11.

9. Where two or more occupancy chapters apply, such as in a mixed occupancy (see 6.1.14), apply the most restrictive requirements.

9/29/2015 Flad Code Forum 15

Suggested Procedure :

Code Requirements

• Step 1 : Determine the occupancy

classification

– Health Care (Hospital)

• Step 2 : Identify the Approval Dates to

determine if the building or structure is NEW

or EXISTING

– Document investigation

9/29/2015 Flad Code Forum 16

“Existing” Definition

• 3.3.36* Building. Any structure used or intended for supporting or sheltering any use or occupancy.

– 3.3.36.5* Existing Building. A building erected or officially authorized prior to the effective date of the adoption of this edition of the Code by the agency or jurisdiction.

• A.3.3.36.5 Existing Building. With respect to judging whether

a building should be considered existing, the deciding factor

is not when the building was designed or when construction

started but, rather, the date plans were approved for construction

by the appropriate authority having jurisdiction.

– 3.3.79* Existing. That which is already in existence on the date this edition of the Code goes into effect.

9/29/2015 Flad Code Forum 17

Step 2 : Identify Approval Dates

• Per CMS's S&C-11-05-LSC– "Review the date the facility first applied for admission into

the program. The use of the EXISTING or NEW chapters of the LSC depends on the date of plan approval or the date of construction (if there is no plan approval process) for the facility’s building(s). If the facility’s building plans were approved or a building permit was issued or construction started after the effective date, (March 13, 2003), of the final regulation, the building or addition must be surveyed under 2000 NEW LSC. If the facility’s building plans were approved by a State Agency or building permit issued or construction started prior to the effective date, (March 13, 2003), of the final regulation, the building must be surveyed under 2000 EXISTING LSC."

9/29/2015 Flad Code Forum 18

Major vs. Minor Rehabilitation

• 18.1.1.4.3.1. (LSC 2003) New text establishes

threshold for major and minor rehabilitation

for determination of when a smoke

compartment (SC) needs to be sprinklered as

part of a rehabilitation.

– Major

• 50% or more of SC or more than 4500 SF

– Minor

• Less than 50% of SC and less than 4500 SF

9/29/2015 Flad Code Forum 19

Chapter 43 : Building Rehabilitation

• Ch 43 first appeared in the 2006 LSC. It was added to “promote the adaptive reuse of EXISTING buildings without sacrificing needed life safety.”

• Prior to that, any alteration to an EXISTING building was required to meet the requirements for NEW construction.

• Rehabilitation Classifications are a stepped approach to mandate requirements.– (1) Repair

– (2) Renovation

– (3) Modification

– (4) Reconstruction

– (5) Change of use or occupancy classification

– (6) Addition

• Repair is least and Addition is most

• The term “REMODEL” is not found in the LSC

9/29/2015 Flad Code Forum 20

Chapter 43 : REPAIR

• 43.2.2.1.1 Repair. The patching, restoration, or paintingof materials, elements, equipment, or fixtures for the purpose of maintaining such materials, elements, equipment, or fixtures in good or sound condition.

• Examples

– Ceiling tiles, damaged by a water leak, are replaced in an existing office.

– A portion of the original plaster-on-lath wall is patched with a piece of GWB, sanded, and painted to match the adjacent wall.

9/29/2015 Flad Code Forum 21

Chapter 43 : RENOVATION

• 43.2.2.1.2 Renovation. The replacement in kind, strengthening, or upgrading of building elements, materials, equipment, or fixtures, that does not result in a reconfiguration of the building spaces within.

• Examples

– Ceiling tiles are replaced with newer ones in an existing office.

– Existing lavatories and water closets are replaced on a one-to-one basis & in the same locations for aesthetic reasons.

9/29/2015 Flad Code Forum 22

Chapter 43 : MODIFICATION

• 43.2.2.1.3 Modification. The reconfiguration of any space; the addition, relocation, or elimination of any door or window; the addition or elimination of load-bearing elements; the reconfiguration or extension of any system; or the installation of any additional equipment.

• Examples– (2) adjacent offices are combined into a single larger office by

removing the wall between the rooms. All work occurs within the (2) offices .

– A sprinkler system is voluntarily (not statutorily) added to a warehouse. (See 43.5.2.2 for exclusively Fire Protection work)

9/29/2015 Flad Code Forum 23

Chapter 43 : RECONSTRUCTION

• 43.2.2.1.4* Reconstruction. The reconfiguration of a space that affects an exit or a corridor shared by more than one occupant space; or the reconfiguration of a space such that the rehabilitation work area is not permitted to be occupied because existing means of egress and fire protection systems, or their equivalent, are not in place or continuously maintained.

• A.43.2.2.1.4 It is not the intent that a corridor, aisle, or circulation space within a suite be considered as a corridor that is shared by more than one occupant space. The suite should be considered as only one occupant space. The following situations should be considered to involve more than one occupant space: – (1) Work affecting a corridor that is common to multiple guest rooms on a

floor of a hotel occupancy

– (2) Work affecting a corridor that is common to multiple living units on a floor of an apartment building occupancy

– (3) Work affecting a corridor that is common to multiple tenants on a floor of a business occupancy

9/29/2015 Flad Code Forum 24

Chapter 43 : RECONSTRUCTION

• Examples

– An entire floor of an existing hospital is gutted to the columns and exterior walls. New patient rooms and staff support areas are added.

– A portion of an existing hospital floor is closed to occupancy and isolated from the remainder of the floor by temporary fire-resistance rated barrier. The remainder of the floor remains occupied during the rehabilitation and has independent Means of Egress from the work area.

9/29/2015 Flad Code Forum 25

Modification vs. Reconstruction

• Rehabilitation of an entire building or an

entire occupancy within a building :

– Classified as Reconstruction

• Modification of over 50% of the building area :

– Classified as Reconstruction (43.5.2)

9/29/2015 Flad Code Forum 26

Chapter 43 : CHANGE OF USE

• 43.2.2.1.5 Change of Use. A change in the purpose or level of activity within a structure that involves a change in application of the requirements of the Code.

• Examples– A patient room is converted into a storage room that is

greater than 100 sf and stores combustible materials making it a hazardous location.

– A living area in a small board and care (16 or less residents) is converted to a resident room requiring it to meet the large board and care requirements (more than 16 residents)

9/29/2015 Flad Code Forum 27

Chapter 43 : CHANGE OF USE

• 18/19.1.1.4.2 (2012 LSC) exempts some

changes from one health care occupancy

subclassification to another from being

considered a change of use.

9/29/2015 Flad Code Forum 28

Chapter 43 : ADDITION

• 43.2.2.1.7 Addition. An increase in the

building area, aggregate floor area, building

height, or number of stories of a structure.

9/29/2015 Flad Code Forum 29

Repair vs Renovation

• Repair vs Renovation = Matter of Quantity

– Major Repair = Renovation

– Minor Renovation = Repair

• Examples

– Replacing a section of corridor carpet = Repair

– Replacing all corridor carpet = Renovation

9/29/2015 Flad Code Forum 30

Repair vs Renovation

• Repair vs Renovation = Matter of Quality

– Repair permits the use of “similar” materials to

those existed before the repair work was done

provided the use of that material is not prohibited

by other code sections.

– Renovation requires the use of materials that are

permitted by other code sections for existing or

new buildings.

9/29/2015 Flad Code Forum 31

Renovation Requirements

• Interior Finish Requirements = NEW

– All other renovation work = EXISTING

• Renovation work must not reduce the level of

code compliance

• Minor reductions* of clear openings of

replacement doors and windows are allowed.

– *AHJ determines how much deviation is permitted

9/29/2015 Flad Code Forum 32

Modification Requirements

• Newly constructed elements, components,

and systems shall comply with NEW

construction.

• Work must also comply with Renovation

• Renovation work must not reduce the level of

code compliance

• Building must meet the applicable EXISTING

occupancy chapter.

9/29/2015 Flad Code Forum 33

EXTENSIVE Modifications

• 43.5.2 Extensive Modifications.

– 43.5.2.2 Modification work that is exclusivelyelectrical, plumbing, mechanical, fire protection system, or structural work shall not be considered a reconstruction, regardless of its extent.

– 43.5.2.4 Rehabilitation work areas in which the modification work is exclusively plumbing, mechanical, fire protection system, or electrical workshall not be included in the computation of total area of all rehabilitation work areas.

• Note : Structural not included in this scope

9/29/2015 Flad Code Forum 34

Reconstruction

• Newly constructed elements, components, and systems shall comply with NEWconstruction.

• Work must also comply with Renovation & Modifications

• Renovation work must not reduce the level of code compliance

• Building must meet the applicable EXISTINGoccupancy chapter.

9/29/2015 Flad Code Forum 35

Reconstruction : Means of Egress

• EXISTING occupancy requirements that may be more stringent than EXISTING conditions

– Illumination of the Means of Egress (M of E)

– Emergency Lighting

– Marking the M of E

• (3) M of E Components in Recon Area = NEW

• If Recon Area > 50% of Floor

– (3) M of E Components for entire Floor = NEW

9/29/2015 Flad Code Forum 36

Reconstruction : Extinguishing Systems

• If Recon Area > 50% of Building Area

– Sprinkler Systems (SS) – highest Recon floor & all

floors below per NEW

• If Recon Area > 50% of Floor Area

– Sprinkler Systems (SS) – entire floor per NEW

• If EXISTING occupancy chapter requires a

standpipe, one shall be provided up to the

floor of the Recon Area

9/29/2015 Flad Code Forum 37

Reconstruction : Fire Alarm Systems

• Smoke Alarms required in any Recon Area to

meet the NEW occupant requirements

– Lodging or Rooming Houses

– Hotels & Dormitories

– Apartment Buildings

– Guest rooms

– Dwelling Units

– Residential Board and Care

9/29/2015 Flad Code Forum 38

Reconstruction : Elevators

• In High-Rise Buildings where the Recon Area is

20% or more of the occupied floor area, all

floors must be accessible by at least (1)

elevator.

9/29/2015 Flad Code Forum 39

Change of Use - Options

• Change of Use only

– No Change of Occupancy

– No change of Hazard Level

• Change of Use only

– No Change of Occupancy

– Change of Hazard Level - Comply w/(1) :

• Compliance w/the requirements to the new Change of Use in accordance with its NEW occupancy chapter

• Existing HC protected throughout by a supervised automatic sprinkler system & the Change of Use room/space is <250sf, it does not need to meet the NEW occupancy chapter

9/29/2015 Flad Code Forum 40

Change of Occupancy Classification

• Other than a COC to an Assembly occupancy, ALL other occupancies w/in the same/lesser hazard category & classification (T43.7.3) must meet :– EXISTING occupancy chapters

– NEW occupancy chapters• Automatic Sprinkler & Detection

• Alarm & Communication Systems

• Hazardous Areas

• Example – Hospital (Hazard Category 2) is rehabilitated to an

Ambulatory HC (Hazard Category 3)

– Must meet EXISTING & NEW

9/29/2015 Flad Code Forum 41

Change of Occupancy Classification

• Other than a COC to an Assembly occupancy, ALL other occupancies w/in the higher hazard category & classification (T43.7.3) must meet :

– NEW occupancy chapters

• Example

– Ambulatory HC (Hazard Category 3) is rehabilitated to a Hospital (Hazard Category 2)

– Must meet NEW

9/29/2015 Flad Code Forum 42

Hazard Categories and Classifications

9/29/2015 Flad Code Forum 43

Addition

• Additions to an Existing Building :– Must meet NEW occupancy chapter(s)

– Must NOT create or extend any nonconformity that affects fire safety or the Means of Egress in the Existing Building

– Examples• Increased travel distance

• Number of Stories based on Construction Type

• Existing Building :– Must meet its EXISTING occupancy chapter(s)

– Any rehabilitation work that affects the Existing Bldg must meet those requirements

– Need separation from Addition or be sprinkled if the combined areas of the Addition + Exist Bldg require it per NEW

9/29/2015 Flad Code Forum 44

History of Hospital Regulation

• 1946 : Hospital Survey and Construction Act – Hill Burton Act

– Code : Building Exits Code (pre-NFPA 101 LSC)

• 1971 : CMS adopts the 1967 NFPA 101 LSC

• 1987 : CMS adopts the 1985 NFPA 101 LSC

• 1995 : International Code Council formed– Combined ICBO, BOCA, & SBCI into ICC

• 2003 (3/11/03) : CMS adopts the 2000 NFPA 101 LSC

• 2011: CMS announces adoption of the 2012 NFPA 101 LSC

• 2012 : CMS issues waivers for 2012 NFPA 101 LSC

• 2016 (?) : CMS adopts the 2012 NFPA 101 LSC

9/29/2015 Flad Code Forum 45

Code Questions from HC Clients

• Q : What is the maximum allowable "undercut" for hospital corridor doors?

• A : It depends … NEW or EXISTING?

• There are no restrictions for undercuts in non-hazardous doors for EXISTING HC occupancies that are "protected throughout by an approved, supervised automatic sprinkler system."

9/29/2015 Flad Code Forum 46

Code Questions from HC Clients

• Q : What is the required ratings and/or sprinkler requirements for Hazardous Areas?

• A : It depends … must determine which LSC edition the Hazardous Areas were approved.

9/29/2015 Flad Code Forum 47

9/29/2015 Flad Code Forum 48

LSC (2000)

SECTION 1.4 APPLICATION• 1.4.1 * New and Existing Buildings and Structures. The Code shall apply to both

new construction and existing buildings and existing structures.

• *A.1.4 – It is the intent of Section 1.4 that a building, addition, or alteration designed to meet the

requirements of a prior edition of the Code be required to meet those requirements for the life of the building. It is intended that the initial assessment of the building, when new, should be based on new occupancy requirements for the edition of the Code in effect on the date of plan approval.

– Subsequent assessments of the building should be based on new occupancy requirements of that same edition of the Code for the life of the building. Requirements for existing buildings in this edition of the Code apply if those requirements are more restrictive.

– There are some cases where the requirements for new construction are less restrictive, and it might be justified to permit an existing building to use the less restrictive requirement. However, extreme care needs to be exercised when granting such permission, because the less restrictive provision might be the result of a new requirement elsewhere in the Code.

– For example, in editions of the Code prior to 1991, corridors in new health care occupancies were required to have a 1-hour fire resistance rating. Since 1991, these corridors have been required only to resist the passage of smoke. However, this provision is based on the new requirement that all new health care facilities be protected throughout by automatic sprinklers.

9/29/2015 Flad Code Forum 49

9/29/2015 Flad Code Forum 50

• 1950 Hospital + 1967/1970 Additions– All approved prior to adoption of 1967 LSC in 1971

– No (federal) code requirements for this building

– 1970’s Business Addition separated with a 2-Hr FB

– No automatic sprinkler protection throughout

9/29/2015 Flad Code Forum 51

• 1990 Addition– Connected to 1950/1967 Hospital w/o a 2-Hr FB

– NEW Health Care Occupancy (1985 LSC)

• 1950 Hospital + 1967/1970 Addition– Must NOW meet EXISTING Health Care Occupancy (1985 LSC)

9/29/2015 Flad Code Forum 52

• 1950 Hospital + 1967/1970 Additions– EXISTING Health Care Occupancy (1985 LSC)

• Fire Alarm System required - Added

• Smoke Detection System required - Added

• Automatic Sprinkler System required – Not Added – Exception : Type II (111) – 1 Story … Bldg’s “1st Flr” is >50% below grade = 1 Story

• Smoke Compartments - Added

9/29/2015 Flad Code Forum 53

• 2000 Addition– Connected to 1950/1967/1970 Hospital w/o a 2-Hr FB

– Must meet NEW Health Care Occupancy (1985 LSC)

• 1950 Hospital + 1967/1970/1990 Additions– Must STILL meet EXISTING Health Care Occupancy (1985 LSC)

9/29/2015 Flad Code Forum 54

• March 3, 2003 : CMS adopts 2000 NFPA 101 Life Safety Code

• 2000 Addition– SHOULD meet EXISTING Health Care Occupancy (1985 LSC)

• 1950 Hospital + 1967/1970/1990 Additions– SHOULD meet EXISTING Health Care Occupancy (1985 LSC)

9/29/2015 Flad Code Forum 55

Chapter 43 : Building Rehabilitation

9/29/2015 Flad Code Forum 56

CMS's S&C-11-05-LSC

"Review the date the facility first applied for admission into the program. The use of the EXISTING or NEW chapters of the LSC depends on the date of plan approval or the date of construction (if there is no plan approval process) for the facility’s building(s). If the facility’s building plans were approved or a building permit was issued or construction started after the effective date, (March 13, 2003), of the final regulation, the building or addition must be surveyed under 2000 NEW LSC. If the facility’s building plans were approved by a State Agency or building permit issued or construction started prior to the effective date, (March 13, 2003), of the final regulation, the building must be surveyed under 2000 EXISTING LSC."

9/29/2015 Flad Code Forum 57

• March 3, 2003 : CMS adopts 2000 NFPA 101 Life Safety Code

• 2000 Addition– MUST meet EXISTING Health Care Occupancy (2000 LSC)

• 1950 Hospital + 1967/1970/1990 Additions– MUST meet EXISTING Health Care Occupancy (2000 LSC)

9/29/2015 Flad Code Forum 58

Chapter 43 : Building Rehabilitation

9/29/2015 Flad Code Forum 59

• 2000 Addition

– Automatic Sprinkler System required – Not Added?

– Exception : Type II (111) – 1 Story … Bldg’s “1st Flr” is

>50% below grade = 1 Story

9/29/2015 Flad Code Forum 60

S U M M A R Y

• When discussing the adoption of the 2012 LSC

by CMS sometime in 2016-2017 with our HC

clients, stress the following points :

– This adoption will “wipe the slate clean” of

previous “rehabilitation” projects needing to meet

different editions (1967, 1985, 2000) of the LSC.

– All hospitals will be EXISTING Health Care

occupancies and be required to meet Chapter 19.

9/29/2015 Flad Code Forum 61

S U M M A R Y

• Any “rehabilitation” projects should be identified per its classification and a key plan kept up-to-date.

9/29/2015 Flad Code Forum 62

F L A D C O D E F O R U M

T H A N K Y O U F O R

AT T E N D I N G

9/29/2015 Flad Code Forum 63