Strategy Basis
� Sustain our position through commercial action plans (tailor made by geography) with the existing offers
and boost controller retrofits.
� Action plans by geography supported by MVS Category Manager team.
� Training of Recloser champions (by region) to enhance prescription
� Foster our main advantage : ADVC controller by upgrading and developing new features such as:
� Launch ADVC3 –
� New option for front office to translate strings and load their local languages for WSOS and possibly HMI interface
depending on whether the language uses alpha numeric characters
� Advanced protection functions
� Additional communication features –
� Implement our fight back plan on switchgear to be able to come back on the market with a new
offer by end 2017
Page 2Confidential Property of Schneider Electric |
Recloser business remains in the core of Schneider Electric but requires the commitment of everyone to be sustainable.
Confidential Property of Schneider Electric
Key Highlights
Easy Install / Swap
Ease of Use
Switchgear compatible
1
2
3
Reuse existing configuration
Fast and Extensible
Secure
4
5
6
Advance Controller (ADVC 3)
Confidential Property of Schneider Electric
Why ADVC3?
> ADVC 2 has reached End of Life
> Limited processing power and memory
> Inability to support new features
IEC61850, Cyber Security etc..
> Component Obsolesence
> Ethernet Chip
> ADVC 3 has increased memory and processing power.
> Will facilitate new developments
Operation A ADVC 2 ADVC 3
Create file from Controller 41 sec 26 sec
Retrieve 10,000 events 65 sec 5 sec
Application f/w upgrade 550-600 sec 15-20 sec
Compare all settings 49 sec 5 sec
A Measurements under standard office network conditions
>MUCH FASTER
Confidential Property of Schneider Electric
� COMMUNICATIONS PORTS
� PROCESSOR
� MEMORY
� NEW FIRMWARE (not backwards compatible)
Design Element ADVC2 ADVC 3
Memory 32 MB 512 MB
Storage 64 MB 1 GB
File System None UBI
CPU Freq 48 MHz 800 MHz
DSP 64 MHz 168 MHz
Ethernet 10 Base-T 100 Base-T
USB Serial USB 2.0
Port ADVC 2Qty. Speed
ADVC 3Qty. Speed
USB B 1 128000
baud1 Up to 480
mbps
USB A 0 3 Up to 480
mbps
RS-232 4 Up to
57600
baud
2 Up to
115200
baud
RS-485 1 Up to
57600
baud
0 NA
V23 1 1200 baud 0 NA
Ethernet 1 10
Base-T2 100
Base-T
� EVERYTHING ELSE EXACTLY SAME
� PWP Process underway� REPLACEMENT CAPE SPARES WILL BE NEW TYPE
ADVC 3 CHANGES
Confidential Property of Schneider Electric
USB 2.0
WSOS driver
USB 2.0
Native adaptors’ support
Firmware upgrade support *
� FAST
100 BASE-T support
Native SWITCH implementation
Supports communications on separate LANs
* Support for firmware upgrade via USB
memory stick is a part of the roadmap
� SECURE �EXTENSIBLE
COMMS PORTS FEATURES
COMMS PORTS
Confidential Property of Schneider Electric
PHYSICAL FEATURES
Easy Install / Swap
Ease of Use
Switchgear compatible
ADVC 2ADVC 2 ADVC 3ADVC 3
Same Form factor
Same Look and Feel
Same Menu Structures
No additional tools for Installation
Compatible with SetVUE and FlexVUE displays
�EASY INSTALLATION
�PHYSICALLY BACKWARDS COMPATIBLE
� SAME ARRANGEMENT INSIDE THE CUBICLE
Confidential Property of Schneider Electric
FIRMWARE & CONFIGURATION FEATURES
All Existing Features Supported on ADVC3
Compatible with existing version A40+ configuration
Simple upgrade tool in WSOS to re-map communication ports
Preserve existing configuration while migrating
� FEATURE RICH
� ALL EXISTING FEATURES SUPPORTED
� SIMPLE UPGRADE FROM EXISTING PLATFORM � RE-USE EXISTING CONFIGURATION FILE VIA AN ‘UPGRADE TOOL’
Cu
rre
nt
En
han
ce
d
Phase, Earth Time Overcurrent � �
Phase, Earth Instantaneous Overcurrent � �
Sensitive Earth Fault Instantaneous Overcurrent� �
High Current Trip & Lockout (Phase & Earth/) � �
Phase, Earth Directional � �
Negative Sequence Instantaneous, Time
Overcurrent
� �
Negative Sequence Directional � �
Phase Under/Over Voltage � �
U/O Voltage Auto Restoration � �
Under/Over Frequency � �
U/O Frequency Auto Restoration � �
Loss of Phase � �
Live Load Blocking � �
Second Harmonic Inrush � �
Trip / Alarm / Sectionalise configurability � �
Broken conductor � �
Directional Detection � �
Synchrocheck � �
Loop Automation � �
Intelligent Loop Automation(With P2P comms) � �
Custom Logic creation and implementation � �
FLEXVUE � �
SETVUE � �
Trip/Close Isolate/Disable � �
USB (Type B) - WSOS � �
USB (Type A) � 3
RS232 4 2
Ethernet 1 2
Digital I/O for configurable external device
control
� �
Security Secure DNP3 � �
Protection features
Automation
Operator Interface
Communication and
external interface
Confidential Property of Schneider Electric
CONFIGURATION FEATURES
Same WSOS Tool for switchgear configuration
Familiar configuration interface
Same end user process sequence for configuration
WSOS installation comes with all required drivers that are
backwards compatible with ADVC2 and ADVC Lite
� EASY OF USE
� SAME WSOS CONFIGURATION TOOL – FAMILIAR INTERFACE
� COMPLETE COMPATIBILITY WITH EXISTING SWITCHGEAR RANGE
N-series
U-series
W-series
RL-series
Confidential Property of Schneider Electric
ADVC 3
Native support for commonly available USB-RS232 adaptors
Native support for commonly available USB-RS485 adaptors
Configuration similar to native port support
Application usage as before, once the ports are configured
� EASY TO USE CONFIGURATION PAGES FOR ADDITIONAL COMMS PORT
� FLEXIBILITY TO USE USB CONVERTERS
Cu
rre
nt
En
ha
nce
d
Phase, Earth Time Overcurrent � �
Phase, Earth Instantaneous Overcurrent � �
Sensitive Earth Fault Instantaneous Overcurrent� �
High Current Trip & Lockout (Phase & Earth/) � �
Phase, Earth Directional � �
Negative Sequence Instantaneous, Time
Overcurrent
� �
Negative Sequence Directional � �
Phase Under/Over Voltage � �
U/O Voltage Auto Restoration � �
Under/Over Frequency � �
U/O Frequency Auto Restoration � �
Loss of Phase � �
Live Load Blocking � �
Second Harmonic Inrush � �
Trip / Alarm / Sectionalise configurability � �
Broken conductor � �
Directional Detection � �
Synchrocheck � �
Loop Automation � �
Intelligent Loop Automation(With P2P comms) � �
Custom Logic creation and implementation � �
FLEXVUE � �
SETVUE � �
Trip/Close Isolate/Disable � �
USB (Type B) - WSOS � �
USB (Type A) � 3
RS232 4 2
Ethernet 1 2
Digital I/O for configurable external device
control
� �
Security Secure DNP3 � �
Protection features
Automation
Operator Interface
Communication and
external interface
Confidential Property of Schneider Electric
ADVC3 2017 ROADMAP, ADVC2 ramp down
Launch of ADVC 3
- ILA & Directional Protection Compatibility
- French & Spanish
interface
- Real time PLC for
CLT
- IEC 61850
Configuration , reporting
Q1 -2017 Q2 -2017 Q3 -2017 Q4-2017
Software adaptations
- ILA Load shed - SCADA Energy
measurement Analogues
- Harmonics Analogues & revised history
* ADVC2
IEC61850 support for GOOSE
messaging Q2 2018
Confidential Property of Schneider Electric
WINDOWS 10 WSOS SUPPORT
> A Windows 10 compatible version of WSOS will be launched in Q1
> Support for Windows 10 is incompatible with Windows XP> The USB Drivers are incompatible
> Support for Windows XP is withdrawn
> Microsoft ceased support for XP a number of years ago
> Microsoft has also ceased support for Windows 7
ADVC3 Schneider Electric
NEW GENERATION CONTROLLER
Confidential Property of Schneider Electric