NetSure™ RDB SeriesNetSure™ RDB Series
22
NetSure™ RDB Series48V Plug-n-Play Rack DistributionNetSure™ RDB Series48V Plug-n-Play Rack Distribution
Model options by application:• 1-2U Rack Mount Devices
• 6 or 15 outlet (L6 or L15) versions• Larger Rack Mount Devices
• 6 outlet (M6) version• Blade Chassis and High Power Devices
• 2 or 3 outlet (H2 or H3) versions
NetSure™ RDB Series Designed to feed up to 8.6kW from 200A breaker Zero U, rear mount Plug-n-play connectors for tool-less add/move/change
Includes ground plug Breaker trip notification Universal mounting – can be mounted on the left or right in
both top and bottom cable applications
33
Rack Distribution ConceptRack Distribution Concept
Zero UPower Strip
IT Rack
Typical 4/0 Cables
Aside
Bside
Quick Connect Plug
Output Breakers
Blade Server Example(3) 70A inputs / side
20A Load
20A Load
20A Load
Aside
Bside
Rack Mount Server Example(15) 20A inputs / side
No conduit req’din cable tray
DC Power SystemIT Rack
44
Available ModelsAvailable Models
Max Watts
Max
Amps1Max kW
Max
Amps1
420 10 2.5 60 547692630 15 3.8 90 547693840 20 5.0 120 547499
420 10 6.3 150 547694
630 15 8.42 2002 547695840 20 8.42 2002 547615
1,050 25 6.3 150 5476961,260 30 7.6 180 5476971,470 35 8.42 2002 547503
H2 2 3,360 80 6.7 160 547500
2,100 50 6.3 150 5476982,520 60 7.6 180 5476992,940 70 8.42 2002 547501
M6 6
OutletsL6 6
L15 15
Part Number
1 Max Amps rated at end of battery discharge (42V)2 PDU power rating limited to 200A, 8.4 kW eachAll NetSure™ RDB Series PDUs are designed for up to 200A input
H3 3
Power RatingPer Outlet Per PDU
NetSure™ RDB Model
55
NetSure™ RDB L6NetSure™ RDB L6
NetSure™ RDB Model Outlets
Power Rating
Part Number
Per Outlet Per PDU
Max Watts
Max Amps1
Max kW
Max Amps1
L6 6 420 10 2.5 60 547692630 15 3.8 90 547693840 20 5.0 120 547499
1 Max Amps rated at end of battery discharge (42V)2 PDU power rating limited to 200A, 8.4 kW eachAll NetSure™ RDB Series PDUs are designed for up to 200A input
66
NetSure™ RDB L15NetSure™ RDB L15
NetSure™ RDB Model Outlets
Power Rating
Part Number
Per Outlet Per PDU
Max Watts
Max Amps1
Max kW
Max Amps1
L15 15 420 10 6.3 150 547694630 15 8.42 2002 547695840 20 8.42 2002 547615
1 Max Amps rated at end of battery discharge (42V)2 PDU power rating limited to 200A, 8.4 kW eachAll NetSure™ RDB Series PDUs are designed for up to 200A input
77
NetSure™ RDB M6NetSure™ RDB M6
NetSure™ RDB Model Outlets
Power Rating
Part Number
Per Outlet Per PDU
Max Watts
Max Amps1
Max kW
Max Amps1
M6 6 1,050 25 6.3 150 5476961,260 30 7.6 180 5476971,470 35 8.42 2002 547503
1 Max Amps rated at end of battery discharge (42V)2 PDU power rating limited to 200A, 8.4 kW eachAll NetSure™ RDB Series PDUs are designed for up to 200A input
88
NetSure™ RDB H2NetSure™ RDB H2
NetSure™ RDB Model Outlets
Power Rating
Part Number
Per Outlet Per PDU
Max Watts
Max Amps1
Max kW
Max Amps1
H2 2 3,360 80 6.7 160 5475001 Max Amps rated at end of battery discharge (42V)2 PDU power rating limited to 200A, 8.4 kW eachAll NetSure™ RDB Series PDUs are designed for up to 200A input
99
NetSure™ RDB H3NetSure™ RDB H3
NetSure™ RDB Model Outlets
Power Rating
Part Number
Per Outlet Per PDU
Max Watts
Max Amps1
Max kW
Max Amps1
H3 3 2,100 50 6.3 150 5476982,520 60 7.6 180 5476992,940 70 8.42 2002 547501
1 Max Amps rated at end of battery discharge (42V)2 PDU power rating limited to 200A, 8.4 kW eachAll NetSure™ RDB Series PDUs are designed for up to 200A input
1010
Output CablesOutput Cables Quick connect to PDU Un-terminated to IT equipment 2 Models:
• 547613: Power Cord for H2, H3 Models - 4' Long
• 547595: Power Cord for L6, L15, M6 Models - 6' Long
1111
Breaker Trip Alarm SchemeBreaker Trip Alarm Scheme• Alarm scheme for NetSure™ RDB Series
• -48 VDC signal provided to indicate a breaker has tripped
• Signal can be “daisy-chained” to connect to multiple power strips
• Alarm signal can be connected to NetSure™ controller, or• to other monitoring system that accepts -48 VDC signal
• 2 position removable terminal block provides a simple customerconnection point for alarm signal requiring only a stripped wire
1212
PDU Rack Mounting BracketPDU Rack Mounting Bracket
• Mounts in rear of IT rack• Includes bracket and hardware to
mount to one side of rack • Left side or right side mounting• P/N: 547665
1313
Mating Input Quick Connect Kits Mating Input Quick Connect Kits
• Provides mating connector to input of NetSure™ RDB Series• Installs on cables from NetSure™ DC Power System• Includes mating SB350 housing and two contacts• 4 kits to accommodate 1/0 through 4/0 wire• QTY: 1 per distribution strip depending on input wire size
KIT P/N Wire Size
547668 1/0 AWG
547669 2/0 AWG
547670 3/0 AWG
547671 4/0 AWG