Netezza Site Prep Specs
Transcript of Netezza Site Prep Specs
-
IBM Netezza 1000-SeriesSite Preparation and Specifications Revised: June 17, 2011
D20281-18 Rev. 11.0
Note: Before using this information and the product that it supports, read the information in “Notices and Trademarks” on page B-1.
© Copyright IBM Corporation 2001-2011.US Government Users Restricted Rights – Use, duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp.
Contents
Preface
1 IBM Netezza 1000 System Models1000-3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
1000-6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1000-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
1000-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
1000-24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1000-36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
1000-48 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
1000-72 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
1000-84 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
1000-96 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
1000-120 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
2 1000-3 SpecificationsElectrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Space requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
3 1000-6 SpecificationsElectrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Space requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
4 1000-12 SpecificationsElectrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Space requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
iii
5 1000-18 SpecificationsSpace requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
6 1000-24 SpecificationsSpace requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
7 1000-36 SpecificationsSpace requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
8 1000-48 SpecificationsSpace requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
9 1000-72 SpecificationsSpace requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
iv
10 1000-84 SpecificationsSpace requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-4
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-4
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-5
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-5
11 1000-96 SpecificationsSpace requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4
12 1000-120 SpecificationsSpace requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
Electrical Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-4
Environmental Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-4
Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-5
Host Server Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-5
Appendix A: Model Comparison
Appendix B: Notices and TrademarksNotices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Trademarks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Open Source Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Regulatory and Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
v
vi
Tables
Table 2-1: 1000-3 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Table 2-2: 1000-3 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Table 2-3: 1000-3 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Table 2-4: 1000-3 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Table 2-5: IBM x3650 M3 Host Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Table 3-1: 1000-6 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Table 3-2: 1000-6 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Table 3-3: 1000-6 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Table 3-4: 1000-6 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Table 3-5: IBM x3650 M3 Host Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Table 4-1: 1000-12 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Table 4-2: 1000-12 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Table 4-3: 1000-12 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Table 4-4: 1000-12 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . 4-3
Table 4-5: IBM x3650 M3 Host Specifications. . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Table 5-1: 1000-18 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Table 5-2: 1000-18 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Table 5-3: 1000-18 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Table 5-4: 1000-18 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . 5-3
Table 5-5: IBM x3850 X5 Host Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Table 6-1: 1000-24 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Table 6-2: 1000-24 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Table 6-3: 1000-24 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Table 6-4: 1000-24 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . 6-3
Table 6-5: IBM x3850 X5 Host Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Table 7-1: 1000-36 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Table 7-2: 1000-36 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Table 7-3: 1000-36 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Table 7-4: 1000-36 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . 7-3
Table 7-5: IBM x3850 X5 Host Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Table 8-1: 1000-48 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Table 8-2: 1000-48 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Table 8-3: 1000-48 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
vii
Table 8-4: 1000-48 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . 8-3
Table 8-5: IBM x3850 X5 Host Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Table 9-1: 1000-72 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Table 9-2: 1000-72 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
Table 9-3: 1000-72 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4
Table 9-4: 1000-72 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . . 9-5
Table 9-5: IBM x3850 X5 Host Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
Table 10-1: 1000-84 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
Table 10-2: 1000-84 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 10-4
Table 10-3: 1000-84 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . 10-4
Table 10-4: 1000-84 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . 10-5
Table 10-5: IBM x3850 X5 Host Specifications . . . . . . . . . . . . . . . . . . . . . . . . 10-5
Table 11-1: 1000-96 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
Table 11-2: 1000-96 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
Table 11-3: 1000-96 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
Table 11-4: 1000-96 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . . 11-4
Table 11-5: IBM x3850 X5 Host Specifications . . . . . . . . . . . . . . . . . . . . . . . . 11-4
Table 12-1: 1000-120 Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
Table 12-2: 1000-120 Electrical Requirements . . . . . . . . . . . . . . . . . . . . . . . . 12-4
Table 12-3: 1000-120 Operating Environment. . . . . . . . . . . . . . . . . . . . . . . . . 12-4
Table 12-4: 1000-120 Floor Loading Requirements . . . . . . . . . . . . . . . . . . . . . 12-5
Table 12-5: IBM x3850 X5 Host Specifications . . . . . . . . . . . . . . . . . . . . . . . . 12-5
Table A-1: Model Comparison . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
viii
Figures
Figure 1-1: 1000-3 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Figure 1-2: 1000-6 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Figure 1-3: 1000-12 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Figure 1-4: 1000-18 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Figure 1-5: 1000-24 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Figure 1-6: 1000-36 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Figure 1-7: 1000-48 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Figure 1-8: 1000-72 Pod 1 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Figure 1-9: 1000-72 Pod 2 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Figure 1-10: 1000-84 Pod1 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Figure 1-11: 1000-84 Pod 2 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Figure 1-12: 1000-96 Pod1 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Figure 1-13: 1000-96 Pod 2 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Figure 1-14: 1000-120 Pod1 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Figure 1-15: 1000-120 Pod 2 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11
Figure 1-16: 1000-120 Pod 3 (front view) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-12
Figure 2-1: Rack Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Figure 3-1: Rack Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Figure 4-1: Rack Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Figure 5-1: Space Requirements for a 2-Rack Pod . . . . . . . . . . . . . . . . . . . . . . . 5-2
Figure 6-1: Space Requirements for a 2-Rack Pod . . . . . . . . . . . . . . . . . . . . . . . 6-2
Figure 7-1: Space Requirements for a 3-Rack Pod . . . . . . . . . . . . . . . . . . . . . . . 7-2
Figure 8-1: Space Requirements for a 4-Rack Pod . . . . . . . . . . . . . . . . . . . . . . . 8-2
Figure 9-1: Space Requirements for a 4-Rack Pod . . . . . . . . . . . . . . . . . . . . . . . 9-2
Figure 9-2: Space Requirements for a 2-Rack Pod . . . . . . . . . . . . . . . . . . . . . . . 9-3
Figure 9-3: Pod Positioning for Multiple Pods . . . . . . . . . . . . . . . . . . . . . . . . . . 9-3
Figure 10-1: Space Requirements for each 4-Rack Pod . . . . . . . . . . . . . . . . . . . 10-2
Figure 10-2: Space Requirements for each 3-Rack Pod . . . . . . . . . . . . . . . . . . . 10-2
Figure 10-3: Pod Positioning for Multiple Pods . . . . . . . . . . . . . . . . . . . . . . . . . 10-3
Figure 11-1: Space Requirements for each 4-Rack Pod . . . . . . . . . . . . . . . . . . . 11-2
Figure 11-2: Pod Positioning for Multiple Pods . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
Figure 12-1: Space Requirements for each 4-Rack Pod . . . . . . . . . . . . . . . . . . . 12-2
Figure 12-2: Space Requirements for a 2-Rack Pod . . . . . . . . . . . . . . . . . . . . . . 12-3
Figure 12-3: Pod Positioning for Multiple Pods . . . . . . . . . . . . . . . . . . . . . . . . . 12-3
ix
x
PrefaceThe IBM Netezza 1000 system is a high-performance, integrated data warehouse appliance that provides unparalleled performance, extensive scaling, high reliability, and ease of use. The system uses a unique architecture that combines current trends in processor, network, and software technologies to deliver a very high-performance system for large enterprise customers.
About This Guide
IBM Netezza 1000 Series Site Preparation and Specifications is written for those who need to understand the site requirements and specifications of each IBM Netezza 1000 model. This guide assumes that you understand the capabilities and capacities of the physical space in which you are installing a IBM Netezza 1000 system.
The guide describes the hardware components that make up the system, and discusses the following:
Preparing a physical location.
Maintaining a location.
Various IBM Netezza 1000 models.
Hardware specifications.
Included in This Guide
This guide is designed to be used before and during installation of the IBM Netezza 1000 system. It contains important information on preparing and maintaining your site. It specif-ically covers the following topics:
Chapter 1, “IBM Netezza 1000 System Models” — Lists the different system models and describes the location of the major components within the system.
Chapter 2, “1000-3 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM Netezza 1000 3 system.
Chapter 3, “1000-6 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM Netezza 1000 6 system.
Chapter 4, “1000-12 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM Netezza 1000 18 system.
Chapter 5, “1000-18 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM Netezza 1000 12 system.
Chapter 6, “1000-24 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM Netezza 1000 24 system.
Chapter 7, “1000-36 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM Netezza 1000 36 system.
Chapter 8, “1000-48 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM Netezza 1000 48 system.
xi
Chapter 9, “1000-72 Specifications” — Provides the information necessary to prepare your site for the installation of the IBM Netezza 1000 72 system.
Chapter 10, “1000-84 Specifications” — Provides the information necessary to pre-pare your site for the installation of the IBM Netezza 1000 84 system.
Chapter 11, “1000-96 Specifications” — Provides the information necessary to pre-pare your site for the installation of the IBM Netezza 1000 96 system.
Chapter 12, “1000-120 Specifications” — Provides the information necessary to pre-pare your site for the installation of the IBM Netezza 1000 120 system.
Appendix A, “Model Comparison” — Provides a model comparison of the systems in the current IBM Netezza 1000 product line.
xii
Symbols and Conventions
This guide uses the following typographical conventions:
Numbered steps for procedures
Single-step procedures are preceded by the q symbol
Bulleted lists for topics
Italics for terms, and user-defined variables such as filenames
Abbreviations
This guide uses the following abbreviations throughout:
Abbreviation Description
A ampere
ACID Atomicity, Consistency, Isolation, and Durability
GB Gigabyte
HTTP HyperText Transport Protocol
Hz Hertz
in. Inch
kg Kilogram
KVA Kilo Volt-Amps
KVM Keyboard-Video-Mouse
lb Pound
m meter
Mb Megabit
MB Megabyte
ms Milliseconds
MSFI Mustang Snippet Fabric Interface
MSPU Mustang Snippet Processing Unit
NIC Network Interface Card
NPS Netezza Performance Software
PCI Peripheral Component Interconnect
xiii
If You Need Help
If you are having trouble using the IBM® Netezza® appliance, you should:
1. Retry the action, carefully following the instructions given for that task in the documentation.
2. Go to the Netezza Knowledge Base at https://knowledge.netezza.com. Enter your sup-port username and password. You can search the knowledge base or the latest updates to the product documentation. Click Netezza HelpDesk to submit a support request.
3. If you are unable to access the Netezza Knowledge Base, you can also contact Netezza Support at the following telephone numbers:
North American Toll-Free: +1.877.810.4441
United Kingdom Free-Phone: +0.800.032.8382
International Direct: +1.508.620.2281
Refer to your Netezza maintenance agreement for details about your support plan choices and coverage.
PCIe PCI Express
PCIx PCI eXtended
PDU Power Distribution Unit
RAID Redundant Array of Independent Disks
RPC Remote Power Controller
SAS Serial Attached SCSI
SATA Serial Advanced Technology Attachment
SCSI Small Computer System Interface
SFI Snippet Fabric Interface
SNMP Simple Network Management Protocol
SPA Snippet Processing Array
SPU Snippet Processing Unit
TB Terabyte
VAC Volts Alternating Current
Abbreviation Description
xiv
Comments on the Documentation
We welcome any questions, comments, or suggestions that you have for the IBM Netezza documentation. Please send us an e-mail message at [email protected] and include the following information:
The name and version of the manual that you are using
Any comments that you have about the manual
Your name, address, and phone number
We appreciate your comments on the documentation.
D20281-18 Rev.11.0 i-xv
IBM Netezza 1000-Series Site Preparation and Specifications
i-xvi D20281-18 Rev.11.0
C H A P T E R 1
IBM Netezza 1000 System ModelsThis chapter contains the following information:
A description of each system, including the number of racks, S-Blades, and SPAs in the system
An illustration of each system showing the placement of components within each rack.
1000-3
The 1000-3 is a single-rack system containing 3 S-Blades housed in 1 SPA.
Figure 1-1 shows a 1000-3 system.
Note: The switch is only visible from the rear of the rack.
Figure 1-1: 1000-3 (front view)
JBOD
S-Blades
JBOD
Host 1 (x3650)
Host 2 (x3650)
KVM
Mgt Switch
1-1
IBM Netezza 1000-Series Site Preparation and Specifications
1000-6
The 1000-6 is a single-rack system containing 6 S-Blades housed in 1 SPA.
Figure 1-2 shows a 1000-6 system.
Note: The switch is only visible from the rear of the rack.
Figure 1-2: 1000-6 (front view)
JBOD
JBOD
S-Blades
JBOD
JBOD
Host 1 (x3650)
Host 2 (x3650)
KVM
Mgt Switch
1-2 D20281-18 Rev.11.0
1000-12
1000-12
The 1000-12 is a single-rack system containing 12 S-Blades housed in 2 SPAs.
Figure 1-3 shows a 1000-12 system.
Note: The switch is only visible from the rear of the rack.
Figure 1-3: 1000-12 (front view)
JBOD
JBOD
JBOD
JBOD
S-Blades
S-Blades
JBOD
JBOD
JBOD
JBOD
Host 1 (x3650)
Host 2 (x3650)
KVM
Mgt Switch
D20281-18 Rev.11.0 1-3
IBM Netezza 1000-Series Site Preparation and Specifications
1000-18
The 1000-18 is a two-rack system containing 18 S-Blades housed in 3 SPAs.
Note: The racks are bolted together into a single unit and cannot be separated.
Figure 1-3 shows a 1000-18 system.
Note: The switches are only visible from the rear of the rack.
Figure 1-4: 1000-18 (front view)
JBOD
JBOD
JBOD
JBOD
JBOD
JBOD
S-Blades S-Blades
S-Blades
JBOD
JBOD
JBOD
JBOD
JBOD
JBOD
Host 1 (x3850 M2) Host 2 (x3850 M2)
KVM
Mgt Switch
Fabric Switch
Fabric Switch
1-4 D20281-18 Rev.11.0
1000-24
1000-24
The 1000-24 is a two-rack system containing 24 S-Blades housed in 4 SPAs.
Note: The racks are bolted together into a single unit and cannot be separated.
Figure 1-3 shows a 1000-24 system.
Note: The switches are only visible from the rear of the rack.
Figure 1-5: 1000-24 (front view)
JBOD JBOD
JBOD JBOD
JBOD JBOD
JBOD JBOD
S-Blades S-Blades
S-Blades S-Blades
JBOD JBOD
JBOD JBOD
JBOD JBOD
JBOD JBOD
Host 1 (x3850 M2) Host 2 (x3850 M2)
KVMMgt Switch
Fabric Switch
Fabric Switch
D20281-18 Rev.11.0 1-5
IBM Netezza 1000-Series Site Preparation and Specifications
1000-36
The 1000-36 is a three-rack system containing 36 S-Blades housed in 6 SPAs.
Note: The racks are bolted together into a single unit and cannot be separated.
Figure 1-3 shows a 1000-36 system.
Note: The switches are only visible from the rear of the rack.
Figure 1-6: 1000-36 (front view)
JBOD JBODJBOD
JBOD JBODJBOD
JBOD JBODJBOD
JBOD JBODJBOD
S-Blades S-BladesS-Blades
S-Blades S-BladesS-Blades
JBOD JBODJBOD
JBOD JBODJBOD
JBOD JBODJBOD
JBOD JBODJBOD
Host 1 (x3850 M2) Host 2 (x3850 M2)
KVM
Mgt Switch
Fabric Switch
Fabric Switch
1-6 D20281-18 Rev.11.0
1000-48
1000-48
The 1000-48 is a four-rack system containing 48 S-Blades housed in 8 SPAs.
Note: The racks are bolted together into a single unit and cannot be separated.
Figure 1-3 shows a 1000-48 system.
Note: The switches are only visible from the rear of the rack.
Figure 1-7: 1000-48 (front view)
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
S-Blades S-BladesS-Blades S-Blades
S-Blades S-BladesS-Blades S-Blades
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
Host 1 (x3850 M2) Host 2 (x3850 M2)
KVM
Mgt Switch
Fabric Switch
Fabric Switch
D20281-18 Rev.11.0 1-7
IBM Netezza 1000-Series Site Preparation and Specifications
1000-72
The 1000-72 is a six-rack system containing 72 S-Blades housed in 12 SPAs.
Note: The racks are bolted together into two distinct units, known as pods. Pods may be located separately from each other, limited by the length (20 meters) of the inter-pod cables. Pods may not be broken apart into individual racks.
Figure 1-3 shows a 1000-72 system.
Note: The switches are only visible from the rear of the rack.
Figure 1-8: 1000-72 Pod 1 (front view)
Figure 1-9: 1000-72 Pod 2 (front view)
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
S-Blades S-BladesS-Blades S-Blades
S-Blades S-BladesS-Blades S-Blades
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
Host 1 (x3850 M2) Host 2 (x3850 M2)
KVM
Mgt Switch
Fabric Switch
Fabric Switch
JBOD JBOD
JBOD JBOD
JBOD JBOD
JBOD JBOD
S-Blades S-Blades
S-Blades S-Blades
JBOD JBOD
JBOD JBOD
JBOD JBOD
JBOD JBOD
Mgt Switch Fabric Switch
Fabric SwitchKVM
1-8 D20281-18 Rev.11.0
1000-84
1000-84
The 1000-84 is a seven-rack system containing 84 S-Blades housed in 14 SPAs.
Note: The racks are bolted together into two distinct units, known as pods. Pods may be located separately from each other, limited by the length (20 meters) of the inter-pod cables. Pods may not be broken apart into individual racks.
Figure 1-3 shows a 1000-84 system.
Note: The switches are only visible from the rear of the rack.
Figure 1-10: 1000-84 Pod1 (front view)
Figure 1-11: 1000-84 Pod 2 (front view)
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
S-Blades S-BladesS-Blades S-Blades
S-Blades S-BladesS-Blades S-Blades
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
Host 1 (x3850 M2) Host 2 (x3850 M2)
KVM
Mgt Switch
Fabric Switch
Fabric Switch
JBOD JBOD JBOD
JBOD JBOD JBOD
JBOD JBOD JBOD
JBOD JBOD JBOD
S-Blades S-Blades S-Blades
S-Blades S-Blades S-Blades
JBOD JBOD JBOD
JBOD JBOD JBOD
JBOD JBOD JBOD
JBOD JBOD JBOD
Mgt Switch Fabric Switch Fabric Switch
Fabric Switch Fabric SwitchKVM
D20281-18 Rev.11.0 1-9
IBM Netezza 1000-Series Site Preparation and Specifications
1000-96
The 1000-96 is a eight-rack system containing 96 S-Blades housed in 16 SPAs.
Note: The racks are bolted together into two distinct units, known as pods. Pods may be located separately from each other, limited by the length (20 meters) of the inter-pod cables. Pods may not be broken apart into individual racks.
Figure 1-3 shows a 1000-96 system.
Note: The switches are only visible from the rear of the rack.
Figure 1-12: 1000-96 Pod1 (front view)
Figure 1-13: 1000-96 Pod 2 (front view)
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
S-Blades S-BladesS-Blades S-Blades
S-Blades S-BladesS-Blades S-Blades
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
Host 1 (x3850 M2) Host 2 (x3850 M2)
KVM
Mgt Switch
Fabric Switch
Fabric Switch
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
S-Blades S-BladesS-Blades S-Blades
S-Blades S-BladesS-Blades S-Blades
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
Mgt Switch Fabric Switch Fabric Switch
Fabric Switch Fabric SwitchKVM
1-10 D20281-18 Rev.11.0
1000-120
1000-120
The 1000-120 is a ten-rack system containing 120 S-Blades housed in 20 SPAs.
Note: The racks are bolted together into three distinct units, known as pods. Pods may be located separately from each other, limited by the length (20 meters) of the inter-pod cables. Pods may not be broken apart into individual racks.
Figure 1-3 shows a 1000-120 system.
Note: The switches are only visible from the rear of the rack.
Figure 1-14: 1000-120 Pod1 (front view)
Figure 1-15: 1000-120 Pod 2 (front view)
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
S-Blades S-BladesS-Blades S-Blades
S-Blades S-BladesS-Blades S-Blades
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
Host 1 (x3850 M2) Host 2 (x3850 M2)
KVM
Mgt Switch
Fabric Switch
Fabric Switch
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
S-Blades S-BladesS-Blades S-Blades
S-Blades S-BladesS-Blades S-Blades
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
JBOD JBODJBOD JBOD
Mgt Switch Fabric Switch Fabric Switch
Fabric Switch Fabric SwitchKVM
D20281-18 Rev.11.0 1-11
IBM Netezza 1000-Series Site Preparation and Specifications
Figure 1-16: 1000-120 Pod 3 (front view)
JBOD JBOD
JBOD JBOD
JBOD JBOD
JBOD JBOD
S-Blades S-Blades
S-Blades S-Blades
JBOD JBOD
JBOD JBOD
JBOD JBOD
JBOD JBOD
Mgt Switch Fabric Switch
Fabric SwitchKVM
1-12 D20281-18 Rev.11.0
C H A P T E R 2
1000-3 SpecificationsThis chapter explains the following requirements for the 1000-3 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Electrical Power Requirements
Each 1000-3 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 2-1.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
Table 2-1: 1000-3 Electrical Requirements
Specification Value
Circuits 2
Total Plugs (Drops) 2
Voltage 200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit Breaker Rating 20 Amps (Single Phase)
Connector NEMA 30A L6-30 (NA models)IEC 309 32A 2P+G (EU models)
Maximum Power 2,930 W
Power/Area 385 W/ft2
(4,141 W/m2)
2-1
IBM Netezza 1000-Series Site Preparation and Specifications
Space requirements
Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The 1000-series systems are housed in a rack that is 1.5 in. (3.8 cm) wider than previous Netezza systems. This means that the 1000-series system is wider than a stan-dard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
Figure 2-1 shows the space requirements for each rack.
Figure 2-1: Rack Space Requirements
The total space requirements for the 1000-3 system are listed in Table 2-2.
Table 2-2: 1000-3 Space Requirements
Physical Including Clearance
Footprint (WxD) 25.5 in. by 43 in.(64.8 cm x 109.2 cm)
25.5 in. by 130 in.(64.8 cm x 330.2 cm)
25.5 in(64.8 cm)
30 in(76 cm)
40 in(101.6 cm)
60 in(152 cm)
between rows
36 in91.5 cm)
2-2 D20281-18 Rev.11.0
Environmental Requirements
Environmental Requirements
The 1000-3 system is designed to operate within the following temperature, humidity, and altitude ranges:
Floor Loading Requirements
The floor that supports the 1000-3 system must be capable of supporting a minimum of 132 lbs/ft2 (642 kg/m2).
Table 2-3: 1000-3 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 9,998 BTU/hr
Table 2-4: 1000-3 Floor Loading Requirements
Specification Value
Maximum Weight 1,000 lb(453.6 kg)
Maximum Weight/Area 131.3 lb/ft2
(641.1 kg/m2)
D20281-18 Rev.11.0 2-3
IBM Netezza 1000-Series Site Preparation and Specifications
Host Server Specifications
Table 2-5: IBM x3650 M3 Host Specifications
Feature Number Description
Processors two Quad-core Intel Xeon 2.4 GHz, 12MB L3 1066MHz 80w
Memory — 24 GB, PC3-10600 (DDR3) SDRAM
Power supplies two 675W, Redundant, hot-pluggable
Fans three N+1 Redundant, hot-pluggable
NIC four ports (two available)
Four Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port PCIe Gigabit Adapter
NIC one dual port card(one available)
One Dual Port PCIe 10 Gigabit Adapter
IMM port one Integrated Management Module dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots four(two available)
Four PCI-Express x8 (one full length, one half length, two low profile)
USB 2.0 ports five Two front, two rear, one internal
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
Form Factor 2U (3.5”) rack-mountable
Management IMM
2-4 D20281-18 Rev.11.0
C H A P T E R 3
1000-6 SpecificationsThis chapter explains the following requirements for the 1000-6 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Electrical Power Requirements
Each 1000-6 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 3-1.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
Table 3-1: 1000-6 Electrical Requirements
Specification Value
Circuits 2
Total Plugs (Drops) 2
Voltage 200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit Breaker Rating 30 Amps (Single Phase)
Connector NEMA 30A L6-30 (NA models)IEC 309 32A 2P+G (EU models)
Maximum Power 4,120 W
Power/Area 541 W/ft2
(5,822 W/m2)
3-1
IBM Netezza 1000-Series Site Preparation and Specifications
Space requirements
Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The 1000-series system is housed in a rack that is 1.5 in. (3.8 cm) wider than previ-ous Netezza systems. This means that the 1000-series system is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
Figure 3-1 shows the space requirements for each rack.
Figure 3-1: Rack Space Requirements
The total space requirements for the 1000-6 system are listed in Table 3-2.
Table 3-2: 1000-6 Space Requirements
Physical Including Clearance
Footprint (WxD) 25.5 in. by 43 in.(64.8 cm x 109.2 cm)
25.5 in. by 130 in.(64.8 cm x 330.2 cm)
25.5 in(64.8 cm)
30 in(76 cm)
40 in(101.6 cm)
60 in(152 cm)
between rows
36 in91.5 cm)
3-2 D20281-18 Rev.11.0
Environmental Requirements
Environmental Requirements
The 1000-6 system is designed to operate within the following temperature, humidity, and altitude ranges:
Floor Loading Requirements
The floor that supports the 1000-6 system must be capable of supporting a minimum of 171 lbs/ft2 (834 kg/m2).
Table 3-3: 1000-6 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 14,058 BTU/hr
Table 3-4: 1000-6 Floor Loading Requirements
Specification Value
Maximum Weight 1,300 lb(589.7 kg)
Maximum Weight/Area 170.7 lb/ft2
(833.4 kg/m2)
D20281-18 Rev.11.0 3-3
IBM Netezza 1000-Series Site Preparation and Specifications
Host Server Specifications
Table 3-5: IBM x3650 M3 Host Specifications
Feature Number Description
Processors two Quad-core Intel Xeon 2.4 GHz, 12MB L3 1066MHz 80w
Memory — 24 GB, PC3-10600 (DDR3) SDRAM
Power supplies two 675W, Redundant, hot-pluggable
Fans three N+1 Redundant, hot-pluggable
NIC four ports (two available)
Four Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port PCIe Gigabit Adapter
NIC one dual port card(one available)
One Dual Port PCIe 10 Gigabit Adapter
IMM port one Integrated Management Module dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots four(two available)
Four PCI-Express x8 (one full length, one half length, two low profile)
USB 2.0 ports five Two front, two rear, one internal
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
Form Factor 2U (3.5”) rack-mountable
Management IMM
3-4 D20281-18 Rev.11.0
C H A P T E R 4
1000-12 SpecificationsThis chapter explains the following requirements for the 1000-12 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Electrical Power Requirements
Each 1000-12 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 4-1.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
Table 4-1: 1000-12 Electrical Requirements
Specification Value
Circuits 2
Total Plugs (Drops) 2
Voltage 200-240/380-415 VAC, 50 Hz (EU models — 3-Phase Wye)200-208 VAC, 60 Hz (NA models — 3-Phase Delta)
200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit Breaker Rating 30 Amps (EU models — 3-Phase Wye)40 Amps (NA models — 3-Phase Delta)
60 Amps (Single Phase)
Connector IEC 309 32A 3P+N+G (EU models — 3-Phase Wye)IEC 309 60A 3P+G (NA models — 3-Phase Delta)
IEC 309 60A 2P+G (Single Phase)
Maximum Power 7,220 W
Power/Area 948 W/ft2
(10,203 W/m2)
4-1
IBM Netezza 1000-Series Site Preparation and Specifications
Space requirements
Each rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The 1000-series system is housed in a rack that is 1.5 in. (3.8 cm) wider than previ-ous Netezza systems. This means that the 1000-series system is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
Figure 4-1 shows the space requirements for each rack.
Figure 4-1: Rack Space Requirements
The total space requirements for the 1000-12 system are listed in Table 4-2.
Table 4-2: 1000-12 Space Requirements
Physical Including Clearance
Footprint (WxD) 25.5 in. by 43 in.(64.8 cm x 109.2 cm)
25.5 in. by 130 in.(64.8 cm x 330.2 cm)
25.5 in(64.8 cm)
30 in(76 cm)
40 in(101.6 cm)
60 in(152 cm)
between rows
36 in91.5 cm)
4-2 D20281-18 Rev.11.0
Environmental Requirements
Environmental Requirements
The 1000-12 system is designed to operate within the following temperature, humidity, and altitude ranges:
Floor Loading Requirements
The floor that supports the 1000-12 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).
Table 4-3: 1000-12 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 24,636 BTU/hr —
Table 4-4: 1000-12 Floor Loading Requirements
Specification Value
Maximum Weight 2,000 lb(907.2 kg)
Maximum Weight/Area 262.7 lb/ft2
(1,282.6 kg/m2)
D20281-18 Rev.11.0 4-3
IBM Netezza 1000-Series Site Preparation and Specifications
Host Server Specifications
Table 4-5: IBM x3650 M3 Host Specifications
Feature Number Description
Processors two Quad-core Intel Xeon 2.4 GHz, 12MB L3 1066MHz 80w
Memory — 24 GB, PC3-10600 (DDR3) SDRAM
Power supplies two 675W, Redundant, hot-pluggable
Fans three N+1 Redundant, hot-pluggable
NIC four ports (two available)
Four Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port PCIe Gigabit Adapter
NIC one dual port card(one available)
One Dual Port PCIe 10 Gigabit Adapter
IMM port one Integrated Management Module dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots four(two available)
Four PCI-Express x8 (one full length, one half length, two low profile)
USB 2.0 ports five Two front, two rear, one internal
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
Form Factor 2U (3.5”) rack-mountable
Management IMM
4-4 D20281-18 Rev.11.0
C H A P T E R 5
1000-18 SpecificationsThis chapter explains the following requirements for the 1000-18 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Space requirements
The 1000-18 consists of two racks. The racks are bolted together into a group of racks called a pod. In this system there is a single pod of two racks.
RackEach rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The racks that are used for 1000-series systems are 1.5 in. (3.8 cm) wider than those used in previous Netezza systems. This means that each rack in the 1000-series sys-tem is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
PodsThe 1000-18 consists of a pod with two racks. The space requirements for the pod are listed in Table 5-1.
Figure 5-1 shows the space requirements for the pod.
Table 5-1: 1000-18 Space Requirements
Number of RacksFootprint
Physical Including Clearance
2 51 in. by 43 in.(128.6 cm x 109.2 cm)
51 in. by 130 in.(128.6 cm x 330.2 cm)
5-1
IBM Netezza 1000-Series Site Preparation and Specifications
Figure 5-1: Space Requirements for a 2-Rack Pod
Electrical Power Requirements
Each 1000-18 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 5-2.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
51 in(129.6 cm)
Front
Rear
Table 5-2: 1000-18 Electrical Requirements
Specification 2-Rack Pod
Circuits 2
Total Plugs (Drops) 4
Voltage 200-240/380-415 VAC, 50 Hz (EU models — 3-Phase Wye)200-208 VAC, 60 Hz (NA models — 3-Phase Delta)
200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit Breaker Rating 30 Amps (EU models — 3-Phase Wye)40 Amps (NA models — 3-Phase Delta)
60 Amps (Single Phase)
Connector IEC 309 32A 3P+N+G (EU models — 3-Phase Wye)IEC 309 60A 3P+G (NA models — 3-Phase Delta)
IEC 309 60A 2P+G (Single Phase)
Maximum Power 11,060 W
5-2 D20281-18 Rev.11.0
Environmental Requirements
Environmental Requirements
The 1000-18 system is designed to operate within the following temperature, humidity, and altitude ranges:
Floor Loading Requirements
The floor that supports the 1000-18 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).
Power/Area 726 W/ft2
(7,815 W/m2)
Table 5-2: 1000-18 Electrical Requirements
Specification 2-Rack Pod
Table 5-3: 1000-18 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 37,738 BTU/hr —
Table 5-4: 1000-18 Floor Loading Requirements
Specification 2-Rack Pod
Maximum Weight 3,000 lb(1360.8 kg)
Maximum Weight/Area 195.8 lb/ft2
(958.3 kg/m2)
D20281-18 Rev.11.0 5-3
IBM Netezza 1000-Series Site Preparation and Specifications
Host Server Specifications
Table 5-5: IBM x3850 X5 Host Specifications
Feature Number Description
Processors four Six-core Intel Xeon 2.0 GHz, 18MB L3 1066MHz 105w
Memory — 128 GB, PC3-8500 (DDR3-1066) RDIMMs
Power supplies two 1975W, Redundant, hot-pluggable
Fans six N+1 Redundant, hot-pluggable
NIC two ports(two available)
Two Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port 1 Gigabit Adapter
NIC three dual port card(internal use)
Three Dual Port 10 Gigabit Adapter
IMM port one Remote Supervisor Adapter dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots seven(three available)
Seven PCIe (3 available)
USB 2.0 ports four Two front, two rear
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
Form factor 4U (7”) Rack-mountable
Management IMM
5-4 D20281-18 Rev.11.0
C H A P T E R 6
1000-24 SpecificationsThis chapter explains the following requirements for the 1000-24 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Space requirements
The 1000-24 consists of two racks. The racks are bolted together into a group of racks called a pod. In this system there is a single pod of two racks.
RackEach rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The racks that are used for 1000-series systems are 1.5 in. (3.8 cm) wider than those used in previous Netezza systems. This means that each rack in the 1000-series sys-tem is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
PodsThe 1000-24 consists of a pod with two racks. The space requirements for the pod are listed in Table 6-1.
Figure 6-1 shows the space requirements for the pod.
Table 6-1: 1000-24 Space Requirements
Number of RacksFootprint
Physical Including Clearance
2 51 in. by 43 in.(128.6 cm x 109.2 cm)
51 in. by 130 in.(128.6 cm x 330.2 cm)
6-1
IBM Netezza 1000-Series Site Preparation and Specifications
Figure 6-1: Space Requirements for a 2-Rack Pod
Electrical Power Requirements
Each 1000-24 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 6-2.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
51 in(129.6 cm)
Front
Rear
Table 6-2: 1000-24 Electrical Requirements
Specification 2-Rack Pod
Circuits 2
Total Plugs (Drops) 4
Voltage 200-240/380-415 VAC, 50 Hz (EU models — 3-Phase Wye)200-208 VAC, 60 Hz (NA models — 3-Phase Delta)
200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit Breaker Rating 30 Amps (EU models — 3-Phase Wye)40 Amps (NA models — 3-Phase Delta)
60 Amps (Single Phase)
Connector IEC 309 32A 3P+N+G (EU models — 3-Phase Wye)IEC 309 60A 3P+G (NA models — 3-Phase Delta)
IEC 309 60A 2P+G (Single Phase)
Maximum Power 14,160 W
6-2 D20281-18 Rev.11.0
Environmental Requirements
Environmental Requirements
The 1000-24 system is designed to operate within the following temperature, humidity, and altitude ranges:
Floor Loading Requirements
The floor that supports the 1000-24 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).
Power/Area 930 W/ft2
(10,005 W/m2)
Table 6-2: 1000-24 Electrical Requirements
Specification 2-Rack Pod
Table 6-3: 1000-24 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 48,316 BTU/hr —
Table 6-4: 1000-24 Floor Loading Requirements
Specification 2-Rack Pod
Maximum Weight 4,000 lb(1814.4 kg)
Maximum Weight/Area 262.7 lb/ft2
(1,282.6 kg/m2)
D20281-18 Rev.11.0 6-3
IBM Netezza 1000-Series Site Preparation and Specifications
Host Server Specifications
Table 6-5: IBM x3850 X5 Host Specifications
Feature Number Description
Processors four Six-core Intel Xeon 2.0 GHz, 18MB L3 1066MHz 105w
Memory — 128 GB, PC3-8500 (DDR3-1066) RDIMMs
Power supplies two 1975W, Redundant, hot-pluggable
Fans six N+1 Redundant, hot-pluggable
NIC two ports(two available)
Two Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port 1 Gigabit Adapter
NIC three dual port card(internal use)
Three Dual Port 10 Gigabit Adapter
IMM port one Remote Supervisor Adapter dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots seven(three available)
Seven PCIe (3 available)
USB 2.0 ports four Two front, two rear
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
Form factor 4U (7”) Rack-mountable
Management IMM
6-4 D20281-18 Rev.11.0
C H A P T E R 7
1000-36 SpecificationsThis chapter explains the following requirements for the 1000-36 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Space requirements
The 1000-36 consists of three racks. The racks are bolted together into a group of racks called a pod. In this system there is a single pod of three racks.
RackEach rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The racks that are used for 1000-series systems are 1.5 in. (3.8 cm) wider than those used in previous Netezza systems. This means that each rack in the 1000-series sys-tem is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
PodsThe 1000-36 consists of one 3-rack pod. The space requirements for the pod are listed in Table 7-1.
Table 7-1: 1000-36 Space Requirements
Number of RacksFootprint
Physical Including Clearance
3 76.5 in. by 43 in.(194.3 cm x 109.2 cm)
76.5 in. by 130 in.(194.3 cm x 330.2 cm)
7-1
IBM Netezza 1000-Series Site Preparation and Specifications
Figure 7-1 shows the space requirements for the Pod.
Figure 7-1: Space Requirements for a 3-Rack Pod
Electrical Power Requirements
Each 1000-36 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 7-2.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
76.5 in(194.3 cm)
Front
Rear
Table 7-2: 1000-36 Electrical Requirements
Specification 3-Rack Pod
Circuits 2
Total Plugs (Drops) 6
Voltage 200-240/380-415 VAC, 50 Hz (EU models — 3-Phase Wye)200-208 VAC, 60 Hz (NA models — 3-Phase Delta)
200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit/Breaker Rating 30 Amps (EU models — 3-Phase Wye)40 Amps (NA models — 3-Phase Delta)
60 Amps (Single Phase)
Connector IEC 309 32A 3P+N+G (EU models — 3-Phase Wye)IEC 309 60A 3P+G (NA models — 3-Phase Delta)
IEC 309 60A 2P+G (Single Phase)
Maximum Power 20,360 W
7-2 D20281-18 Rev.11.0
Environmental Requirements
Environmental Requirements
The 1000-36 system is designed to operate within the following temperature, humidity, and altitude ranges:
Floor Loading Requirements
The floor that supports the 1000-36 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).
Power/Area 891 W/ft2
(9,591 W/m2)
Table 7-2: 1000-36 Electrical Requirements
Specification 3-Rack Pod
Table 7-3: 1000-36 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 69,471 BTU/hr —
Table 7-4: 1000-36 Floor Loading Requirements
Specification 3-Rack Pod
Maximum Weight 6,000 lb(2721.6 kg)
Maximum Weight/Area 262.7 lb/ft2
(1,282.6 kg/m2)
D20281-18 Rev.11.0 7-3
IBM Netezza 1000-Series Site Preparation and Specifications
Host Server Specifications
Table 7-5: IBM x3850 X5 Host Specifications
Feature Number Description
Processors four Six-core Intel Xeon 2.0 GHz, 18MB L3 1066MHz 105w
Memory — 128 GB, PC3-8500 (DDR3-1066) RDIMMs
Power supplies two 1975W, Redundant, hot-pluggable
Fans six N+1 Redundant, hot-pluggable
NIC two ports(two available)
Two Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port 1 Gigabit Adapter
NIC three dual port card(internal use)
Three Dual Port 10 Gigabit Adapter
IMM port one Remote Supervisor Adapter dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots seven(three available)
Seven PCIe (3 available)
USB 2.0 ports four Two front, two rear
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
Form factor 4U (7”) Rack-mountable
Management IMM
7-4 D20281-18 Rev.11.0
C H A P T E R 8
1000-48 SpecificationsThis chapter explains the following requirements for the 1000-48 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Space requirements
The 1000-48 consists of four racks. The racks are bolted together into a group of racks called a pod. In this system there is a single pod of four racks.
RackEach rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The racks that are used for 1000-series systems are 1.5 in. (3.8 cm) wider than those used in previous Netezza systems. This means that each rack in the 1000-series sys-tem is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
PodsThe 1000-48 consists of one 4-rack pod. The space requirements for the pod are listed in Table 8-1.
Table 8-1: 1000-48 Space Requirements
Number of RacksFootprint
Physical Including Clearance
4 102 in. by 43 in.(259.2 cm x 109.2 cm)
102 in. by 130 in.(259.2 cm x 330.2 cm)
8-1
IBM Netezza 1000-Series Site Preparation and Specifications
Figure 8-1 shows the space requirements for the Pod.
Figure 8-1: Space Requirements for a 4-Rack Pod
Electrical Power Requirements
Each 1000-48 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 8-2.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
102 in(259.1 cm)
Front
Rear
Table 8-2: 1000-48 Electrical Requirements
Specification 4-Rack Pod
Circuits 2
Total Plugs (Drops) 8
Voltage 200-240/380-415 VAC, 50 Hz (EU models — 3-Phase Wye)200-208 VAC, 60 Hz (NA models — 3-Phase Delta)
200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit/Breaker Rating 30 Amps (EU models — 3-Phase Wye)40 Amps (NA models — 3-Phase Delta)
60 Amps (Single Phase)
Connector IEC 309 32A 3P+N+G (EU models — 3-Phase Wye)IEC 309 60A 3P+G (NA models — 3-Phase Delta)
IEC 309 60A 2P+G (Single Phase)
Maximum Power 26,560 W
8-2 D20281-18 Rev.11.0
Environmental Requirements
Environmental Requirements
The 1000-48 system is designed to operate within the following temperature, humidity, and altitude ranges:
Floor Loading Requirements
The floor that supports the 1000-48 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).
Power/Area 872 W/ft2
(9,384 W/m2)
Table 8-2: 1000-48 Electrical Requirements
Specification 4-Rack Pod
Table 8-3: 1000-48 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 90,627 BTU/hr —
Table 8-4: 1000-48 Floor Loading Requirements
Specification 4-Rack Pod
Maximum Weight 8,000 lb(3628.8 kg)
Maximum Weight/Area 262.7 lb/ft2
(1,282.6 kg/m2)
D20281-18 Rev.11.0 8-3
IBM Netezza 1000-Series Site Preparation and Specifications
Host Server Specifications
Table 8-5: IBM x3850 X5 Host Specifications
Feature Number Description
Processors four Six-core Intel Xeon 2.0 GHz, 18MB L3 1066MHz 105w
Memory — 128 GB, PC3-8500 (DDR3-1066) RDIMMs
Power supplies two 1975W, Redundant, hot-pluggable
Fans six N+1 Redundant, hot-pluggable
NIC two ports(two available)
Two Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port 1 Gigabit Adapter
NIC three dual port card(internal use)
Three Dual Port 10 Gigabit Adapter
IMM port one Remote Supervisor Adapter dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots seven(three available)
Seven PCIe (3 available)
USB 2.0 ports four Two front, two rear
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
Form factor 4U (7”) Rack-mountable
Management IMM
8-4 D20281-18 Rev.11.0
C H A P T E R 9
1000-72 SpecificationsThis chapter explains the following requirements for the 1000-72 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Space requirements
The 1000-72 consists of a total of six racks. The racks are bolted together into separate groups called pods. In this system there are a total of two pods; one pod of four racks, and one pod of two racks.
RackEach rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The racks that are used for 1000-series systems are 1.5 in. (3.8 cm) wider than those used in previous Netezza systems. This means that each rack in the 1000-series sys-tem is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
PodsThe 1000-72 consists of two separate pods. The space requirements for each pod are listed in Table 9-1.
Table 9-1: 1000-72 Space Requirements
Number of RacksFootprint
Physical Including Clearance
Pod 1 4 102 in. by 43 in.(259.2 cm x 109.2 cm)
102 in. by 130 in.(259.2 cm x 330.2 cm)
9-1
IBM Netezza 1000-Series Site Preparation and Specifications
Figure 9-1 shows the space requirements for Pod 1.
Figure 9-1: Space Requirements for a 4-Rack Pod
Pod 2 2 51 in. by 43 in.(128.6 cm x 109.2 cm)
51 in. by 130 in.(128.6 cm x 330.2 cm)
Table 9-1: 1000-72 Space Requirements
Number of RacksFootprint
Physical Including Clearance
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
102 in(259.1 cm)
Front
Rear
9-2 D20281-18 Rev.11.0
Space requirements
Figure 9-2 shows the space requirements for Pod 2.
Figure 9-2: Space Requirements for a 2-Rack Pod
When positioning the pods, they may be placed side-by-side, front-to-front, or rear-to-rear. Spacing between pods placed front-to-front or rear-to-rear must be as shown in Figure 9-3.
Figure 9-3: Pod Positioning for Multiple Pods
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
51 in(129.6 cm)
Front
Rear
102 in(152 cm)
D20281-18 Rev.11.0 9-3
IBM Netezza 1000-Series Site Preparation and Specifications
Electrical Power Requirements
Each 1000-72 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 9-2.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
Environmental Requirements
The 1000-72 system is designed to operate within the following temperature, humidity, and altitude ranges:
Table 9-2: 1000-72 Electrical Requirements
Specification Pod 1 Pod 2 Total System
Circuits 2
Total Plugs (Drops) 8 4 12
Voltage 200-240/380-415 VAC, 50 Hz (EU models — 3-Phase Wye)200-208 VAC, 60 Hz (NA models — 3-Phase Delta)
200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit/Breaker Rating 30 Amps (EU models — 3-Phase Wye)40 Amps (NA models — 3-Phase Delta)
60 Amps (Single Phase)
Connector IEC 309 32A 3P+N+G (EU models — 3-Phase Wye)IEC 309 60A 3P+G (NA models — 3-Phase Delta)
IEC 309 60A 2P+G (Single Phase)
Maximum Power 26,560 W 12,960 W 39,520 W
Power/Area 865 W/ft2
(9,308 W/m2)
Table 9-3: 1000-72 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 134,848 BTU/hr —
9-4 D20281-18 Rev.11.0
Floor Loading Requirements
Floor Loading Requirements
The floor that supports the 1000-72 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).
Host Server Specifications
Table 9-4: 1000-72 Floor Loading Requirements
Specification Pod 1 Pod 2
Maximum Weight 8,000 lb(3628.8 kg)
4,000 lb(1814.4 kg)
Maximum Weight/Area 262.7 lb/ft2
(1,282.6 kg/m2)
Table 9-5: IBM x3850 X5 Host Specifications
Feature Number Description
Processors four Six-core Intel Xeon 2.0 GHz, 18MB L3 1066MHz 105w
Memory — 128 GB, PC3-8500 (DDR3-1066) RDIMMs
Power supplies two 1975W, Redundant, hot-pluggable
Fans six N+1 Redundant, hot-pluggable
NIC two ports(two available)
Two Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port 1 Gigabit Adapter
NIC three dual port card(internal use)
Three Dual Port 10 Gigabit Adapter
IMM port one Remote Supervisor Adapter dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots seven(three available)
Seven PCIe (3 available)
USB 2.0 ports four Two front, two rear
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
D20281-18 Rev.11.0 9-5
IBM Netezza 1000-Series Site Preparation and Specifications
Form factor 4U (7”) Rack-mountable
Management IMM
Table 9-5: IBM x3850 X5 Host Specifications
Feature Number Description
9-6 D20281-18 Rev.11.0
C H A P T E R 10
1000-84 SpecificationsThis chapter explains the following requirements for the 1000-84 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Space requirements
The 1000-84 consists of a total of seven racks. The racks are bolted together into separate groups called pods. In this system there are a total of two pods; one pod of four racks and one pod of three racks.
RackEach rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The racks that are used for 1000-series systems are 1.5 in. (3.8 cm) wider than those used in previous Netezza systems. This means that each rack in the 1000-series sys-tem is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
PodsThe 1000-84 consists of two separate pods. The space requirements for each pod are listed in Table 10-1.
Table 10-1: 1000-84 Space Requirements
Number of RacksFootprint
Physical Including Clearance
Pod 1 4 102 in. by 43 in.(259.2 cm x 109.2 cm)
102 in. by 130 in.(259.2 cm x 330.2 cm)
Pod 2 3 76.5 in. by 43 in.(194.3 cm x 109.2 cm)
76.5 in. by 130 in.(194.3 cm x 330.2 cm)
10-1
IBM Netezza 1000-Series Site Preparation and Specifications
Figure 10-1 and Figure 10-2 show the space requirements for each pod.
Figure 10-1: Space Requirements for each 4-Rack Pod
Figure 10-2: Space Requirements for each 3-Rack Pod
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
102 in(259.1 cm)
Front
Rear
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
76.5 in(194.3 cm)
Front
Rear
10-2 D20281-18 Rev.11.0
Space requirements
When positioning the pods, they may be placed side-by-side, front-to-front, or rear-to-rear. Spacing between pods placed front-to-front or rear-to-rear must be as shown in Figure 10-3.
Figure 10-3: Pod Positioning for Multiple Pods
102 in(152 cm)
D20281-18 Rev.11.0 10-3
IBM Netezza 1000-Series Site Preparation and Specifications
Electrical Power Requirements
Each 1000-84 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 10-2.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
Environmental Requirements
The 1000-84 system is designed to operate within the following temperature, humidity, and altitude ranges:
Table 10-2: 1000-84 Electrical Requirements
Specification Pod 1 Pod 2 Total System
Circuits 2
Total Plugs (Drops) 8 6 14
Voltage 200-240/380-415 VAC, 50 Hz (EU models — 3-Phase Wye)200-208 VAC, 60 Hz (NA models — 3-Phase Delta)
200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit/Breaker Rating 30 Amps (EU models — 3-Phase Wye)40 Amps (NA models — 3-Phase Delta)
60 Amps (Single Phase)
Connector IEC 309 32A 3P+N+G (EU models — 3-Phase Wye)IEC 309 60A 3P+G (NA models — 3-Phase Delta)
IEC 309 60A 2P+G (Single Phase)
Maximum Power 26,560 W 19,560 W 46,120 W
Power/Area 865 W/ft2
(9,310 W/m2)
Table 10-3: 1000-84 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 178,523 BTU/hr —
10-4 D20281-18 Rev.11.0
Floor Loading Requirements
Floor Loading Requirements
The floor that supports the 1000-84 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).
Host Server Specifications
Table 10-4: 1000-84 Floor Loading Requirements
Specification Pod 1 Pod 2
Maximum Weight 8,000 lb(3628.8 kg)
6,000 lb(2721.6 kg)
Maximum Weight/Area 262.7 lb/ft2
(1,282.6 kg/m2)
Table 10-5: IBM x3850 X5 Host Specifications
Feature Number Description
Processors four Six-core Intel Xeon 2.0 GHz, 18MB L3 1066MHz 105w
Memory — 128 GB, PC3-8500 (DDR3-1066) RDIMMs
Power supplies two 1975W, Redundant, hot-pluggable
Fans six N+1 Redundant, hot-pluggable
NIC two ports(two available)
Two Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port 1 Gigabit Adapter
NIC three dual port card(internal use)
Three Dual Port 10 Gigabit Adapter
IMM port one Remote Supervisor Adapter dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots seven(three available)
Seven PCIe (3 available)
USB 2.0 ports four Two front, two rear
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
D20281-18 Rev.11.0 10-5
IBM Netezza 1000-Series Site Preparation and Specifications
Form factor 4U (7”) Rack-mountable
Management IMM
Table 10-5: IBM x3850 X5 Host Specifications
Feature Number Description
10-6 D20281-18 Rev.11.0
C H A P T E R 11
1000-96 SpecificationsThis chapter explains the following requirements for the 1000-96 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Space requirements
The 1000-96 consists of a total of eight racks. The racks are bolted together into separate groups called pods. In this system there are a total of two pods of four racks.
RackEach rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The racks that are used for 1000-series systems are 1.5 in. (3.8 cm) wider than those used in previous Netezza systems. This means that each rack in the 1000-series sys-tem is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
PodsThe 1000-96 consists of two separate pods. The space requirements for each pod are listed in Table 11-1.
Table 11-1: 1000-96 Space Requirements
Number of RacksFootprint
Physical Including Clearance
Pod 1 and Pod 2
4 102 in. by 43 in.(259.2 cm x 109.2 cm)
102 in. by 130 in.(259.2 cm x 330.2 cm)
11-1
IBM Netezza 1000-Series Site Preparation and Specifications
Figure 11-1 shows the space requirements for each pod.
Figure 11-1: Space Requirements for each 4-Rack Pod
When positioning the pods, they may be placed side-by-side, front-to-front, or rear-to-rear. Spacing between pods placed front-to-front or rear-to-rear must be as shown in Figure 11-2.
Figure 11-2: Pod Positioning for Multiple Pods
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
102 in(259.1 cm)
Front
Rear
102 in(152 cm)
11-2 D20281-18 Rev.11.0
Electrical Power Requirements
Electrical Power Requirements
Each 1000-96 system requires two separately protected power circuits. The power require-ments for each circuit are listed in Table 11-2.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
Environmental Requirements
The 1000-96 system is designed to operate within the following temperature, humidity, and altitude ranges:
Table 11-2: 1000-96 Electrical Requirements
Specification Pod 1 Pod 2 Total System
Circuits 2
Total Plugs (Drops) 8 8 16
Voltage 200-240/380-415 VAC, 50 Hz (EU models — 3-Phase Wye)200-208 VAC, 60 Hz (NA models — 3-Phase Delta)
200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit/Breaker Rating 30 Amps (EU models — 3-Phase Wye)40 Amps (NA models — 3-Phase Delta)
60 Amps (Single Phase)
Connector IEC 309 32A 3P+N+G (EU models — 3-Phase Wye)IEC 309 60A 3P+G (NA models — 3-Phase Delta)
IEC 309 60A 2P+G (Single Phase)
Maximum Power 26,560 W 25,760 W 52,320 W
Power/Area 859 W/ft2
(9,242 W/m2)
Table 11-3: 1000-96 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 178,523 BTU/hr —
D20281-18 Rev.11.0 11-3
IBM Netezza 1000-Series Site Preparation and Specifications
Floor Loading Requirements
The floor that supports the 1000-96 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).
Host Server Specifications
Table 11-4: 1000-96 Floor Loading Requirements
Specification Pod 1 Pod 2
Maximum Weight 8,000 lb(3628.8 kg)
8,000 lb(3628.8 kg)
Maximum Weight/Area 262.7 lb/ft2
(1,282.6 kg/m2)
Table 11-5: IBM x3850 X5 Host Specifications
Feature Number Description
Processors four Six-core Intel Xeon 2.0 GHz, 18MB L3 1066MHz 105w
Memory — 128 GB, PC3-8500 (DDR3-1066) RDIMMs
Power supplies two 1975W, Redundant, hot-pluggable
Fans six N+1 Redundant, hot-pluggable
NIC two ports(two available)
Two Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port 1 Gigabit Adapter
NIC three dual port card(internal use)
Three Dual Port 10 Gigabit Adapter
IMM port one Remote Supervisor Adapter dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots seven(three available)
Seven PCIe (3 available)
USB 2.0 ports four Two front, two rear
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
11-4 D20281-18 Rev.11.0
Host Server Specifications
Form factor 4U (7”) Rack-mountable
Management IMM
Table 11-5: IBM x3850 X5 Host Specifications
Feature Number Description
D20281-18 Rev.11.0 11-5
IBM Netezza 1000-Series Site Preparation and Specifications
11-6 D20281-18 Rev.11.0
C H A P T E R 12
1000-120 SpecificationsThis chapter explains the following requirements for the 1000-120 system:
Space requirements
Electrical power requirements
Environmental requirements
Floor loading requirements
Space requirements
The 1000-120 consists of a total of ten racks. The racks are bolted together into separate groups called pods. In this system there are a total of three pods; two pods of four racks, and a single pod of two racks.
RackEach rack in the system has a footprint of 25.5 in. (64.8 cm) by 43 in. (109.2 cm). An additional 60 in. (152.4 cm) of clear space is required in front of each rack and 30 in. (76.2 cm) behind the rack. This is to allow unrestricted airflow and access to the system.
Note: The racks that are used for 1000-series systems are 1.5 in. (3.8 cm) wider than those used in previous Netezza systems. This means that each rack in the 1000-series sys-tem is wider than a standard 24 in. (61 cm) data center floor tile. Plan accordingly.
A full height system rack is 87.5 in. (222 cm) tall including its shipping pallet. Without the pallet, the rack stands 79.5 in. (202 cm) tall including casters. Allow for this when plan-ning the movement of the system from the unloading point to its permanent location.
PodsThe 1000-120 consists of three separate pods. The space requirements for each pod are listed in Table 12-1.
Table 12-1: 1000-120 Space Requirements
Number of RacksFootprint
Physical Including Clearance
Pod 1 and Pod 2
4 102 in. by 43 in.(259.2 cm x 109.2 cm)
102 in. by 130 in.(259.2 cm x 330.2 cm)
12-1
IBM Netezza 1000-Series Site Preparation and Specifications
Figure 12-1 shows the space requirements for Pods 1 and 2.
Figure 12-1: Space Requirements for each 4-Rack Pod
Pod 3 2 51 in. by 43 in.(128.6 cm x 109.2 cm)
51 in. by 130 in.(128.6 cm x 330.2 cm)
Table 12-1: 1000-120 Space Requirements
Number of RacksFootprint
Physical Including Clearance
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
102 in(259.1 cm)
Front
Rear
12-2 D20281-18 Rev.11.0
Space requirements
Figure 12-2 shows the space requirements for Pod 3.
Figure 12-2: Space Requirements for a 2-Rack Pod
When positioning the pods, they may be placed side-by-side, front-to-front, or rear-to-rear. Spacing between pods placed front-to-front or rear-to-rear must be as shown in Figure 12-3.
Figure 12-3: Pod Positioning for Multiple Pods
30 in(76 cm)
40 in(101.6 cm)
36 in(91.5 cm)
51 in(129.6 cm)
Front
Rear
102 in(152 cm)
D20281-18 Rev.11.0 12-3
IBM Netezza 1000-Series Site Preparation and Specifications
Electrical Power Requirements
Each 1000-120 system requires two separately protected power circuits. The power requirements for each circuit are listed in Table 12-2.
Note: IBM Netezza recommends that the power supplied to the rack be uninterruptible.
Environmental Requirements
The 1000-120 system is designed to operate within the following temperature, humidity, and altitude ranges:
Table 12-2: 1000-120 Electrical Requirements
Specification Pod 1 Pod 2 Pod 3 Total System
Circuits 2
Total Plugs (Drops) 8 8 4 20
Voltage 200-240/380-415 VAC, 50 Hz (EU models — 3-Phase Wye)200-208 VAC, 60 Hz (NA models — 3-Phase Delta)
200-240 VAC, 50Hz/60 Hz (Single Phase)
Circuit/Breaker Rating 30 Amps (EU models — 3-Phase Wye)40 Amps (NA models — 3-Phase Delta)
60 Amps (Single Phase)
Connector IEC 309 32A 3P+N+G (EU models — 3-Phase Wye)IEC 309 60A 3P+G (NA models — 3-Phase Delta)
IEC 309 60A 2P+G (Single Phase)
Maximum Power 26,560 W 25,760 W 12,960 W 65,280 W
Power/Area 857 W/ft2
(9,225 W/m2)
Table 12-3: 1000-120 Operating Environment
Operating Non-operating
Temperature 10°C to 35°C (50°F to 95°F)
-15°C to 45°C (5°F to 113°F)
Altitude 0 to 3,048 m (0 to 10,000 ft)
0 to 9,144 m (0 to 30,000 ft)
Humidity 20% to 80% non-condensing 10% to 90% non-condensing
Cooling 222,745 BTU/hr —
12-4 D20281-18 Rev.11.0
Floor Loading Requirements
Floor Loading Requirements
The floor that supports the 1000-120 system must be capable of supporting a minimum of 263 lbs/ft2 (1,283 kg/m2).
Host Server Specifications
Table 12-4: 1000-120 Floor Loading Requirements
Specification Pod 1 Pod 2 Pod 3
Maximum Weight 8,000 lb(3628.8 kg)
8,000 lb(3628.8 kg)
4,000 lb(1814.4 kg)
Maximum Weight/Area 262.7 lb/ft2
(1,282.6 kg/m2)
Table 12-5: IBM x3850 X5 Host Specifications
Feature Number Description
Processors four Six-core Intel Xeon 2.0 GHz, 18MB L3 1066MHz 105w
Memory — 128 GB, PC3-8500 (DDR3-1066) RDIMMs
Power supplies two 1975W, Redundant, hot-pluggable
Fans six N+1 Redundant, hot-pluggable
NIC two ports(two available)
Two Gigabit ethernet ports (embedded)
NIC one quad port card(two available)
One Quad Port 1 Gigabit Adapter
NIC three dual port card(internal use)
Three Dual Port 10 Gigabit Adapter
IMM port one Remote Supervisor Adapter dedicated NIC (10/100 Mb)
300 GB SAS drives seven Hot-swappable, in a RAID 10 configuration
PCI slots seven(three available)
Seven PCIe (3 available)
USB 2.0 ports four Two front, two rear
Serial port one
DVD-ROM/CD-RW one 8X / 24X max
Form factor 4U (7”) Rack-mountable
Management IMM
D20281-18 Rev.11.0 12-5
IBM Netezza 1000-Series Site Preparation and Specifications
12-6 D20281-18 Rev.11.0
A P P E N D I X A
Model ComparisonTable A-1 provides a 1000-series model comparison.
Table A-1: Model Comparison
NPS System User DataHost
ProcessorsS-Blades Racks
High Availability
1000-3 8 TB 2 3 1 Yes
1000-6 16 TB 2 6 1 Yes
1000-12 32 TB 2 12 1 Yes
1000-18 48 TB 4 18 2 Yes
1000-24 64 TB 4 24 2 Yes
1000-36 96 TB 4 36 3 Yes
1000-48 128 TB 4 48 4 Yes
1000-72 192 TB 4 72 6 Yes
1000-84 224 TB 4 84 7 Yes
1000-96 256 TB 4 96 8 Yes
1000-120 320 TB 4 120 10 Yes
A-1
IBM Netezza 1000-Series Site Preparation and Specifications
A-2 D20281-18 Rev.11.0
A P P E N D I X B
Notices and TrademarksWhat’s in this appendixNotices
Trademarks
Open Source Notifications
Regulatory and Compliance
This information was developed for products and services offered in the U.S.A.
Notices
IBM may not offer the products, services, or features discussed in this document in other countries. Consult your local IBM representative for information on the products and ser-vices currently available in your area. Any reference to an IBM product, program, or service is not intended to state or imply that only that IBM product, program, or service may be used. Any functionally equivalent product, program, or service that does not infringe any IBM intellectual property right may be used instead. However, it is the user's responsibility to evaluate and verify the operation of any non-IBM product, program, or service.
IBM may have patents or pending patent applications covering subject matter described in this document. The furnishing of this document does not grant you any license to these patents. You can send license inquiries, in writing, to:
IBM Director of LicensingIBM CorporationNorth Castle DriveArmonk, NY 10504-1785 U.S.A.
For license inquiries regarding double-byte character set (DBCS) information, contact the IBM Intellectual Property Department in your country or send inquiries, in writing, to:
Intellectual Property LicensingLegal and Intellectual Property LawIBM Japan Ltd.1623-14, Shimotsuruma, Yamato-shiKanagawa 242-8502 Japan
The following paragraph does not apply to the United Kingdom or any other country where such provisions are inconsistent with local law: INTERNATIONAL BUSINESS MACHINES CORPORATION PROVIDES THIS PUBLICATION "AS IS" WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO, THE
B-1
IBM Netezza 1000-Series Site Preparation and Specifications
IMPLIED WARRANTIES OF NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow disclaimer of express or implied war-ranties in certain transactions, therefore, this statement may not apply to you.
This information could include technical inaccuracies or typographical errors. Changes are periodically made to the information herein; these changes will be incorporated in new edi-tions of the publication. IBM may make improvements and/or changes in the product(s) and/or the program(s) described in this publication at any time without notice.
Any references in this information to non-IBM Web sites are provided for convenience only and do not in any manner serve as an endorsement of those Web sites. The materials at those Web sites are not part of the materials for this IBM product and use of those Web sites is at your own risk.
IBM may use or distribute any of the information you supply in any way it believes appropri-ate without incurring any obligation to you.
Licensees of this program who wish to have information about it for the purpose of enabling: (i) the exchange of information between independently created programs and other programs (including this one) and (ii) the mutual use of the information which has been exchanged, should contact:
IBM Corporation26 Forest StreetMarlborough, MA 01752 U.S.A.
Such information may be available, subject to appropriate terms and conditions, including in some cases, payment of a fee.
The licensed program described in this document and all licensed material available for it are provided by IBM under terms of the IBM Customer Agreement, IBM International Pro-gram License Agreement or any equivalent agreement between us.
Any performance data contained herein was determined in a controlled environment. Therefore, the results obtained in other operating environments may vary significantly. Some measurements may have been made on development-level systems and there is no guarantee that these measurements will be the same on generally available systems. Fur-thermore, some measurements may have been estimated through extrapolation. Actual results may vary. Users of this document should verify the applicable data for their specific environment.
Information concerning non-IBM products was obtained from the suppliers of those prod-ucts, their published announcements or other publicly available sources. IBM has not tested those products and cannot confirm the accuracy of performance, compatibility or any other claims related to non-IBM products. Questions on the capabilities of non-IBM products should be addressed to the suppliers of those products.
All statements regarding IBM's future direction or intent are subject to change or with-drawal without notice, and represent goals and objectives only.
This information is for planning purposes only. The information herein is subject to change before the products described become available.
This information contains examples of data and reports used in daily business operations. To illustrate them as completely as possible, the examples include the names of individu-als, companies, brands, and products. All of these names are fictitious and any similarity to the names and addresses used by an actual business enterprise is entirely coincidental.
B-2 D20281-18 Rev.11.0
Trademarks
COPYRIGHT LICENSE:
This information contains sample application programs in source language, which illustrate programming techniques on various operating platforms. You may copy, modify, and dis-tribute these sample programs in any form without payment to IBM, for the purposes of developing, using, marketing or distributing application programs conforming to the appli-cation programming interface for the operating platform for which the sample programs are written. These examples have not been thoroughly tested under all conditions. IBM, there-fore, cannot guarantee or imply reliability, serviceability, or function of these programs. The sample programs are provided "AS IS", without warranty of any kind. IBM shall not be liable for any damages arising out of your use of the sample programs.
Each copy or any portion of these sample programs or any derivative work, must include a copyright notice as follows:
© (your company name) (year). Portions of this code are derived from IBM Corp. Sample Programs. © Copyright IBM Corp. _enter the year or years_. All rights reserved.
If you are viewing this information softcopy, the photographs and color illustrations may not appear.
Trademarks
IBM, the IBM logo, and ibm.com are trademarks of International Business Machines Corp., registered in many jurisdictions worldwide. Other product and service names might be trademarks of IBM or other companies. A current list of IBM trademarks is available on the Web at www.ibm.com/legal/copytrade.shtml.
Netezza, the Netezza logo, the circle-N logo, TwinFin, Skimmer, Snippet Blades, S-Blades, NPS, Snippet, Snippet Processing Unit, SPU, Snippet Processing Array, SPA, Performance Server, Netezza Performance Server, Asymmetric Massively Parallel Processing, AMPP, Intelligent Query Streaming and other marks are trademarks or registered trademarks of Netezza Corporation, an IBM Company, in the United States and/or other countries. All rights reserved.
The following terms are trademarks or registered trademarks of other companies:
Adobe is a registered trademark of Adobe Systems Incorporated in the United States, and/or other countries.
Linux is a registered trademark of Linus Torvalds in the United States, other countries, or both.
Microsoft, Windows, Windows NT, and the Windows logo are trademarks of Microsoft Corp-pration in the United States, other countries, or both.
NEC is a registered trademark of NEC Corporation.
UNIX is a registered trademark of The Open Group in the United States and other countries.
Java and all Java-based trademarks are trademarks of Sun Microsystems, Inc. in the United States, other countries, or both.
Red Hat is a trademark or registered trademark of Red Hat, Inc. in the United States and/or other countries.
D-CC, D-C++, Diab+, FastJ, pSOS+, SingleStep, Tornado, VxWorks, Wind River, and the Wind River logo are trademarks, registered trademarks, or service marks of Wind River Sys-tems, Inc. Tornado patent pending.
D20281-18 Rev.11.0 B-3
IBM Netezza 1000-Series Site Preparation and Specifications
APC and the APC logo are trademarks or registered trademarks of American Power Conver-sion Corporation.
All document files and software of the above named third-party suppliers are provided "as is" and may contain deficiencies. Netezza and its suppliers disclaim all warranties of any kind, express or implied, including, without limitation, those of merchantability, fitness for a particular purpose, and non infringement.
In no event will Netezza or its suppliers be liable for indirect, incidental, consequential, special, or economic damages (including lost business profits, business interruption, loss or damage of data, and the like), or the use or inability to use the above-named third-party products, even if Netezza or its suppliers have been advised of the possibility of such damages.
Other company, product or service names may be trademarks or service marks of others.
Open Source Notifications
PostgreSQL
Portions of this publication were derived from PostgreSQL documentation. For those por-tions of the documentation that were derived originally from PostgreSQL documentation, and only for those portions, the following applies:
PostgreSQL is copyright © 1996-2001 by the PostgreSQL global development group and is distributed under the terms of the license of the University of California below.
Postgres95 is copyright © 1994-5 by the Regents of the University of California.
Permission to use, copy, modify, and distribute this documentation for any purpose, with-out fee, and without a written agreement is hereby granted, provided that the above copyright notice and this paragraph and the following two paragraphs appear in all copies.
In no event shall the University of California be liable to any party for direct, indirect, spe-cial, incidental, or consequential damages, including lost profits, arising out of the use of this documentation, even if the University of California has been advised of the possibility of such damage.
The University of California specifically disclaims any warranties, including, but not limited to, the implied warranties of merchantability and fitness for a particular purpose. The doc-umentation provided hereunder is on an "as-is" basis, and the University of California has no obligations to provide maintenance, support, updates, enhancements, or modifications.
ICU Library
The Netezza implementation of the ICU library is an adaptation of an open source library Copyright (c) 1995-2003 International Business Machines Corporation and others.
ICU License - ICU 1.8.1 and laterCOPYRIGHT AND PERMISSION NOTICE
Copyright (c) 1995-2003 International Business Machines Corporation and othersAll rights reserved.
Permission is hereby granted, free of charge, to any person obtaining a copy of this software and associated documentation files (the "Software"), to deal in the Software without restric-tion, including without limitation the rights to use, copy, modify, merge, publish, distribute, and/or sell copies of the Software, and to permit persons to whom the Software
B-4 D20281-18 Rev.11.0
Open Source Notifications
is furnished to do so, provided that the above copyright notice(s) and this permission notice appear in all copies of the Software and that both the above copyright notice(s) and this permission notice appear in supporting documentation.
THE SOFTWARE IS PROVIDED "AS IS", WITHOUT WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO THE WARRANTIES OF MERCHANT-ABILITY, FITNESS FOR A PARTICULAR PURPOSE AND NONINFRINGEMENT OF THIRD PARTY RIGHTS. IN NO EVENT SHALL THE COPYRIGHT HOLDER OR HOLDERS INCLUDED IN THIS NOTICE BE LIABLE FOR ANY CLAIM, OR ANY SPECIAL INDIRECT OR CONSEQUENTIAL DAMAGES, OR ANY DAMAGES WHATSOEVER RESULTING FROM LOSS OF USE, DATA OR PROFITS, WHETHER IN AN ACTION OF CONTRACT, NEGLI-GENCE OR OTHER TORTIOUS ACTION, ARISING OUT OF OR IN CONNECTION WITH THE USE OR PERFORMANCE OF THIS SOFTWARE.
Except as contained in this notice, the name of a copyright holder shall not be used in advertising or otherwise to promote the sale, use or other dealings in this Software without prior written authorization of the copyright holder.
ODBC Driver
The Netezza implementation of the ODBC driver is an adaptation of an open source driver, Copyright © 2000, 2001, Great Bridge LLC. The source code for this driver and the object code of any Netezza software that links with it are available upon request to [email protected]
Botan License
Copyright (C) 1999-2008 Jack Lloyd
2001 Peter J Jones2004-2007 Justin Karneges2005 Matthew Gregan2005-2006 Matt Johnston2006 Luca Piccarreta2007 Yves Jerschow2007-2008 FlexSecure GmbH2007-2008 Technische Universitat Darmstadt2007-2008 Falko Strenzke2007-2008 Martin Doering2007 Manuel Hartl2007 Christoph Ludwig2007 Patrick Sona
All rights reserved.
Redistribution and use in source and binary forms, for any use, with or without modifica-tion, of Botan (http://botan.randombit.net/license.html) is permitted provided that the following conditions are met:
1. Redistributions of source code must retain the above copyright notice, this list of condi-tions, and the following disclaimer.
2. Redistributions in binary form must reproduce the above copyright notice, this list of conditions, and the following disclaimer in the documentation and/or other materials pro-vided with the distribution.
THIS SOFTWARE IS PROVIDED BY THE AUTHOR(S) "AS IS" AND ANY EXPRESS OR IMPLIED WARRANTIES, INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRAN-TIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE DISCLAIMED.
D20281-18 Rev.11.0 B-5
IBM Netezza 1000-Series Site Preparation and Specifications
IN NO EVENT SHALL THE AUTHOR(S) OR CONTRIBUTOR(S) BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAM-AGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOW-EVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITYOF SUCH DAMAGE.
Regulatory and Compliance
Regulatory Notices
Install the NPS system in a restricted-access location. Ensure that only those trained to operate or service the equipment have physical access to it. Install each AC power outlet near the NPS rack that plugs into it, and keep it freely accessible.
Provide approved 30A circuit breakers on all power sources.
Product may be powered by redundant power sources. Disconnect ALL power sources before servicing.
High leakage current. Earth connection essential before connecting supply. Courant de fuite élevé. Raccordement à la terre indispensable avant le raccordement au réseau.
Homologation Statement
Attention: This product is not intended to be connected directly or indirectly by any means whatsoever to interfaces of public telecommunications networks, neither to be used in a Public Services Network.
FCC - Industry Canada Statement
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reason-able protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio-frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case users will be required to correct the interference at their own expense.
This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
WEEE
Netezza Corporation is committed to meeting the requirements of the European Union (EU) Waste Electrical and Electronic Equipment (WEEE) Directive. This Directive requires pro-ducers of electrical and electronic equipment to finance the takeback, for reuse or recycling, of their products placed on the EU market after August 13, 2005.
CE Statement (Europe)
This product complies with the European Low Voltage Directive 73/23/EEC and EMC Direc-tive 89/336/EEC as amended by European Directive 93/68/EEC.
B-6 D20281-18 Rev.11.0
Regulatory and Compliance
Warning: This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
VCCI Statement
この装置は、 情報処埋装置等電波障害自主規制協議会 (VCCI) の基準に基づ く ク ラ ス A 情報技術装置です。 この装置を家庭環境で使用する と電波妨害を引き起越す こ と があ り ます。 こ の場合には使用者が適切な対策を講ずる う 要求される こ と があ り ます。
D20281-18 Rev.11.0 B-7
IBM Netezza 1000-Series Site Preparation and Specifications
B-8 D20281-18 Rev.11.0