National Fire Protection Association Report Revision No. 502-NFPA 101-2016 [ Section No. 32.1.9 ]...

23
Second Revision No. 501-NFPA 101-2016 [ Section No. 32.1.1.7 ] 32.1.1.7 Where construction, alteration, or demolition operations are conducted, the provisions of 4.6.10.2 shall apply. Submitter Information Verification Submitter Full Name: SAF-BCF Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Jul 19 11:47:04 EDT 2016 Committee Statement Committee Statement: Adding this section will introduce unintended conflicts. While NFPA 241 addresses means of egress, it doesn't address means of escape. NFPA 241 also requires a fire separation wall which B&C does not require. Response Message: Public Comment No. 83-NFPA 101-2016 [Section No. 32.1.1.7] National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 22 9/20/2016 3:55 PM

Transcript of National Fire Protection Association Report Revision No. 502-NFPA 101-2016 [ Section No. 32.1.9 ]...

Second Revision No. 501-NFPA 101-2016 [ Section No. 32.1.1.7 ]

32.1.1.7

Where construction, alteration, or demolition operations are conducted, the provisions of 4.6.10.2 shall apply.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 11:47:04 EDT 2016

Committee Statement

CommitteeStatement:

Adding this section will introduce unintended conflicts. While NFPA 241 addresses means of egress, it doesn't addressmeans of escape. NFPA 241 also requires a fire separation wall which B&C does not require.

ResponseMessage:

Public Comment No. 83-NFPA 101-2016 [Section No. 32.1.1.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 22 9/20/2016 3:55 PM

Second Revision No. 502-NFPA 101-2016 [ Section No. 32.1.9 ]

32.1.9 Hazardous Materials.

Where hazardous materials are present the provisions of 7.12.2 shall apply.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 11:48:16 EDT 2016

Committee Statement

CommitteeStatement:

There is no "means of egress" in a small board and care occupancy. This chapter uses the concept of "means of escape"instead. While NFPA 30, which was referenced during the First Draft, has specific occupancy requirements, it doesn't haveany board and care occupancy requirements.

ResponseMessage:

Public Comment No. 32-NFPA 101-2016 [New Section after 32.1.8]

Public Comment No. 84-NFPA 101-2016 [Section No. 32.1.9]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 22 9/20/2016 3:55 PM

Second Revision No. 519-NFPA 101-2016 [ Section No. 32.2.2.3.1 ]

32.2.2.3.1

Sleeping rooms, other than those complying with 32.2.2.3.2 or 32.2.2.3.3, and living areas in facilities without a sprinkler systeminstalled in accordance with 32.2.3.5 shall have a second means of escape consisting of one of the following:

(1) Door, stairway, passage, or hall providing a way of unobstructed travel to the outside of the dwelling at street or the finishedground level that is independent of, and remotely located from, the primary means of escape

(2) Passage through an adjacent nonlockable space independent of, and remotely located from, the primary means of escape toany approved means of escape

(3)

(4) Windows having a sill height below the adjacent finished ground level that are provided with a window well meeting the followingcriteria:

(a) The window well has horizontal dimensions that allow the window to be fully opened.

(b) The window well has an accessible net clear opening of not less than 9 ft2 (0.84 m2), with a length and width of not lessthan 36 in. (915 mm).

(c) A window well with a vertical depth of more than 44 in. (1120 mm) is equipped with an approved permanently affixed ladderor with steps meeting the following criteria:

i. The ladder or steps do not encroach more than 6 in. (150 mm) into the required dimensions of the window well.

ii. The ladder or steps are not obstructed by the window.

iii. Ladders or steps that comply with the requirements of 32.2.3.1(c)(i) and (ii) are exempt from the requirements of7.2.2 .

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 15:40:00 EDT 2016

Committee Statement

Committee Statement: Editorial change to match what is included in NFPA 5000.

Response Message:

* Outside window or door operable from the inside, without the use of tools, keys, or special effort, that provides a clear opening

of not less than 5.7 ft2 (0.53 m2), with the width not less than 20 in. (510 mm), the height not less than 24 in. (610 mm), and thebottom of the opening not more than 44 in. (1120 mm) above the floor, with such means of escape acceptable, provided thatone of the following criteria is met:

(a) The window is within 20 ft (6100 mm) of the finished ground level.

(b) The window is directly accessible to fire department rescue apparatus, as approved by the AHJ authority havingjurisdiction .

(c) The window or door opens onto an exterior balcony.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 22 9/20/2016 3:55 PM

Second Revision No. 503-NFPA 101-2016 [ Section No. 32.2.3.2.6 ]

32.2.3.2.6

Where hazardous materials are stored or handled, the provisions of 8.7.3.1 shall apply.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 11:49:30 EDT 2016

Committee Statement

CommitteeStatement:

Adding this requirement will not solve any issues and will create problems. There is no means of egress in a small board andcare as the chapter uses means of escape. While NFPA 30, which is referenced, has specific occupancy requirements, itdoesn't have any board and care occupancy requirements. NFPA 30 also address means of egress requirements which wouldnot be applicable to small board and care occupancies.

ResponseMessage:

Public Comment No. 85-NFPA 101-2016 [Section No. 32.2.3.2.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 22 9/20/2016 3:55 PM

Second Revision No. 504-NFPA 101-2016 [ Section No. 32.2.3.4.1 ]

32.2.3.4.1 General.

A manual fire alarm system shall be provided in accordance with Section 9.6.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 13:35:59 EDT 2016

Committee Statement

CommitteeStatement:

Adding the term "manual" brings the language back to previous edition text. The new language proposed in FR 502created unintended consequences- requiring both manual and automatic detection.

ResponseMessage:

Public Comment No. 86-NFPA 101-2016 [Section No. 32.2.3.4.1]

Public Comment No. 34-NFPA 101-2016 [Section No. 32.2.3.4.2]

Public Comment No. 162-NFPA 101-2016 [Section No. 32.2.3.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 22 9/20/2016 3:55 PM

Second Revision No. 505-NFPA 101-2016 [ Section No. 32.2.3.4.2 ]

32.2.3.4.2 Initiation.

Initiation of the required fire alarm system shall be by one of the following means:

Manual means in accordance with 9.6.2.1(1)

Automatic sprinkler system that complies with 9.6.2.1(3) and provides protection throughout the building

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 13:39:55 EDT 2016

Committee Statement

CommitteeStatement:

Removing these requirements and the action on SR 504 (Section 32.2.3.4.1) brings the language back to previous editiontext. The unintended consequences of the editorial revisions made during First Draft include requiring both manual andautomatic initiation of the fire alarm.

ResponseMessage:

Public Comment No. 87-NFPA 101-2016 [Section No. 32.2.3.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 22 9/20/2016 3:55 PM

Second Revision No. 516-NFPA 101-2016 [ Section No. 32.2.3.5.8 ]

32.2.3.5.8

Systems installed in accordance with NFPA 13D shall be inspected, tested, and maintained in accordance with 32.2.3.5.8.1 through32.2.3.5.8.15, which reference specific sections of NFPA 25. The frequency of the inspection, test, or maintenance shall be inaccordance with this Code, whereas the purpose and procedure shall be from NFPA 25.

32.2.3.5.8.1

Control valves shall be inspected monthly in accordance with 13.3.2 of NFPA 25.

32.2.3.5.8.2

Gages Gauges shall be inspected monthly in accordance with 13.2.7.1.1 of NFPA 25.

32.2.3.5.8.3

Alarm devices shall be inspected quarterly in accordance with 5.2.6 4 of NFPA 25.

32.2.3.5.8.4

Alarm devices shall be tested semiannually in accordance with 5.3.3 2 of NFPA 25.

32.2.3.5.8.5

Valve supervisory switches shall be tested semiannually in accordance with 13.3.3.5 of NFPA 25.

32.2.3.5.8.6

Visible sprinklers shall be inspected annually in accordance with 5.2.1 of NFPA 25.

32.2.3.5.8.7

Visible pipe shall be inspected annually in accordance with 5.2.2 of NFPA 25.

32.2.3.5.8.8

Visible pipe hangers shall be inspected annually in accordance with 5.2.3 of NFPA 25.

32.2.3.5.8.9

Buildings shall be inspected annually prior to the onset of freezing weather to ensure that there is adequate heat wherever water-filled piping is run in accordance with 5.2.5 4.1.2 of NFPA 25.

32.2.3.5.8.10

A representative sample of fast-response sprinklers shall be tested once the sprinklers in the system are 20 years old in accordancewith 5.3.1.1.1.2 3 of NFPA 25.

(A)

If the sample fails the test, all of the sprinklers represented by that sample shall be replaced.

(B)

If the sprinklers pass the test, the test shall be repeated every 10 years thereafter.

32.2.3.5.8.11

A representative sample of dry-pendent sprinklers shall be tested once the sprinklers in the system are 10 years old in accordancewith 5.3.1.1.1.5 6 of NFPA 25.

(A)

If the sample fails the test, all of the sprinklers represented by that sample shall be replaced.

(B)

If the sprinklers pass the test, the test shall be repeated every 10 years thereafter.

32.2.3.5.8.12

Antifreeze solutions shall be tested annually in accordance with 5.3.4 3 of NFPA 25.

32.2.3.5.8.13

Control valves shall be operated through their full range and returned to normal annually in accordance with 13.3.3.1 of NFPA 25.

32.2.3.5.8.14

Operating stems of OS&Y valves shall be lubricated annually in accordance with 13.3.4 of NFPA 25.

32.2.3.5.8.15

Dry-pipe systems that extend into the unheated portions of the building shall be inspected, tested, and maintained in accordancewith 13.4.4 5 of NFPA 25.

Supplemental Information

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 22 9/20/2016 3:55 PM

File Name Description

Chapter_32.2.3.5.8.docx For staff use

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 15:23:55 EDT 2016

Committee Statement

Committee Statement: Editorial changes to update the references to NFPA 25.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 22 9/20/2016 3:55 PM

Second Revision No. 506-NFPA 101-2016 [ Section No. 32.3.3.2.4 ]

32.3.3.2.4

Where hazardous materials are stored or handled, the provisions of 8.7.3.1 shall apply.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 13:44:09 EDT 2016

Committee Statement

CommitteeStatement:

While NFPA 30, which is referenced, has specific occupancy requirements, it doesn't have any board and careoccupancy requirements.

Response Message:

Public Comment No. 88-NFPA 101-2016 [Section No. 32.3.3.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 22 9/20/2016 3:55 PM

Second Revision No. 507-NFPA 101-2016 [ Section No. 32.3.3.6.2 ]

32.3.3.6.2*

Sleeping rooms shall be separated from all spaces, other than adjacent sleeping rooms, adjacent bathrooms, or lounge areas, andbathrooms directly accessible from the sleeping rooms, by walls complying with 32.3.3.6.3 through 32.3.3.6.6.

Supplemental Information

File Name Description

32.3.3.6.2_BCF_separation_living_spaces.docx A.32.3.3.6.2

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 13:45:45 EDT 2016

Committee Statement

CommitteeStatement:

The change incorporates the comments raised during the FR ballot, as raised by the CC Note 37. The annex noteclarifies the intent of this requirement.

ResponseMessage:

Public Comment No. 36-NFPA 101-2016 [Section No. 32.3.3.6.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 22 9/20/2016 3:55 PM

A.32.3.3.6.2 The purpose of this requirement is to protect sleeping rooms from a fire that occurs in an area that is outside of the sleeping room or suite of sleeping rooms such as corridors, Housekeeping Closets, IT Rooms, Electrical/Mechanical Rooms, Libraries, Offices, Conference Rooms, Quiet Rooms and Medication Rooms, Washer/Dryer Rooms, Common Work Rooms, Common Lounges, and Common Bathrooms. Lounges and Bathrooms that can only be accessed directly from the sleeping room or suite of sleeping rooms may be considered part of the sleeping room or suite enclosure and therefore those rooms only should meet the requirements of 32.3.3.6.3 through 32.3.3.6.6 where those room walls either abut a corridor or abut a room other than a sleeping room.

Second Revision No. 508-NFPA 101-2016 [ Section No. 32.3.3.8.2 ]

32.3.3.8.2*

Where residential cooking equipment is used for food warming or limited cooking, or where the equipment has heating elements orburners that have been tested and listed not to allow cooking pan temperature to exceed 662°F (350°C), the equipment shall not berequired to be protected in accordance with 9.2.3, and the presence of the equipment shall not require the area to be protected as ahazardous area where the heating elements or burners have been tested and listed to not allow cooking pan temperatures toexceed 662°F (350°C) .

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 13:50:14 EDT 2016

Committee Statement

CommitteeStatement:

Addresses the range of cooktop temperatures to prevent the overheating of cooking oil. The TC did not have access to UL858 to determine if a reference to that document should be made.

ResponseMessage:

Public Comment No. 89-NFPA 101-2016 [Section No. 32.3.3.8.2]

Public Comment No. 37-NFPA 101-2016 [Section No. 32.3.3.8.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 22 9/20/2016 3:55 PM

Second Revision No. 518-NFPA 101-2016 [ Section No. 32.3.3.8.3 ]

32.3.3.8.3*

Compliance with 9.2.3 shall not be required where all of the following conditions are met:

(1) Residential or commercial cooking equipment in a single kitchen per smoke compartment is used to prepare meals for 30 orfewer persons.

(2) The portion of the board and care facility served by the cooking facility is limited to 30 beds and is separated from other portionsof the board and care facility by a smoke barrier constructed in accordance with 32.3.3.7.9 and with 32.3.3.7.14 through32.3.3.7.22.

(3) The cooktop or range is equipped with a range hood of a width at least equal to the width of the cooking surface, with greasebaffles or other grease-collecting and clean-out capability.

(4)

(5) The hood systems that are not ducted to the exterior additionally have a charcoal filter to remove smoke and odor.

(6) The cooktop or range complies with all of the following:

(a) The cooktop or range is protected with a fire suppression system listed in accordance with ANSI/UL 300, Standard for FireTesting of Fire Extinguishing Systems for Protection of Commercial Cooking Equipment, or is tested and meets allrequirements of UL 300A, Extinguishing System Units for Residential Range Top Cooking Surfaces, in accordance with theapplicable testing document's scope.

(b) A manual release of the extinguishing system is provided in accordance with Section 10.5 of NFPA 96.

(c) An interlock is provided to turn off all sources of fuel and electrical power to the cooktop or range when the suppressionsystem is activated.

(7)

(8)

(9) Portable fire extinguishers in accordance with NFPA 96 are located in all kitchen areas.

(10)

(11) Procedures for the use, inspection, testing, and maintenance of the cooking equipment are in accordance with Chapter 11 ofNFPA 96, and the manufacturer’s instructions are followed.

(12)

(13) The smoke alarms required by 32.3.3.8.3(12) are permitted to be located outside the kitchen area where such placement isnecessary for compliance with the 20 ft (6.1 m) minimum distance criterion.

(14) A single system smoke detector is permitted to be installed in lieu of the smoke alarms required in 32.3.3.8.3(12), provided thefollowing criteria are met:

(a) The detector is located not closer than 20 ft (6.1 m) and not farther than 25 ft (7.6 m) from the cooktop or range.

(b) The detector is permitted to initiate a local audible alarm signal only.

(c) The detector is not required to initiate a buildingwide occupant notification signal.

(d) The detector is not required to notify emergency forces.

(e) The local audible signal initiated by the detector is permitted to be silenced and reset by a button on the detector or by aswitch installed within 10 ft (3.0 m) of the system smoke detector.

(f) System smoke detectors that are required by other sections of the chapter to be installed in corridors or spaces open to thecorridor are not used to meet the requirements of 32.3.3.8.3(12) and are located not closer than 25 ft (7.6 m) to thecooktop or range.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

* The hood systems have a minimum airflow of 500 cfm (14,000 L/min).

* The use of solid fuel for cooking is prohibited.

* Deep-fat frying is prohibited.

* A switch meeting all of the following is provided:

(a) A locked switch, or a switch located in a restricted location, is provided within the cooking facility that deactivates thecooktop or range.

(b) The switch is used to deactivate the cooktop or range whenever the kitchen is not under staff supervision.

(c) The switch is on a timer, not exceeding a 120-minute capacity, that automatically deactivates the cooktop or range,independent of staff action.

* Nofewer Not less than two ac-powered photoelectric smoke alarms, interconnected in accordance with 9.6.2.10.3 andequipped with a silence feature, are located not closer than 20 ft (6.1 m) and not farther than 25 ft (7.6 m) from the cooktop orrange.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 22 9/20/2016 3:55 PM

City:

State:

Zip:

Submittal Date: Tue Jul 19 15:30:12 EDT 2016

Committee Statement

Committee Statement: Editorial change to match 5000.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 22 9/20/2016 3:55 PM

Second Revision No. 509-NFPA 101-2016 [ Section No. 33.1.1.7 ]

33.1.1.7

Where construction, alteration, or demolition operations are conducted, the provisions of 4.6.10.2 shall apply.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 14:01:12 EDT 2016

Committee Statement

Committee Statement: The provisions in NFPA 241 do not apply to board and care occupancies.

Response Message:

Public Comment No. 90-NFPA 101-2016 [Section No. 33.1.1.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 22 9/20/2016 3:55 PM

Second Revision No. 510-NFPA 101-2016 [ Section No. 33.1.9 ]

33.1.9

Where hazardous materials are present the provisions of 7.12.2 shall apply.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 14:13:54 EDT 2016

Committee Statement

CommitteeStatement:

The reference to 7.12.2 has requirements for means of egress. Board and Care facilities do not address means ofegress- only means of escape.

ResponseMessage:

Public Comment No. 91-NFPA 101-2016 [Section No. 33.1.9]

Public Comment No. 33-NFPA 101-2016 [New Section after 33.1.8]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 22 9/20/2016 3:55 PM

Second Revision No. 511-NFPA 101-2016 [ Section No. 33.2.3.2.6 ]

33.2.3.2.6

Where hazardous materials are stored or handled, the provisions of 8.7.3.1 shall apply.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 14:35:36 EDT 2016

Committee Statement

Committee Statement: The reference points to requirements and standards that do not apply to board and care facilities.

Response Message:

Public Comment No. 92-NFPA 101-2016 [Section No. 33.2.3.2.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 22 9/20/2016 3:55 PM

Second Revision No. 512-NFPA 101-2016 [ Section No. 33.2.3.4.1 ]

33.2.3.4.1 Fire Alarm Systems.

A manual fire alarm system shall be provided in accordance with Section 9.6, unless the provisions of 33.2.3.4.1.1 or 33.2.3.4.1.2are met.

33.2.3.4.1.1

A fire alarm system shall not be required where interconnected smoke alarms complying with 33.2.3.4.3 33.2.3.4.4 and not lessthan one manual fire alarm box per floor arranged to continuously sound the smoke detector alarms are provided.

33.2.3.4.1.2

Other manually activated continuously sounding alarms acceptable to the authority having jurisdiction shall be permitted in lieu of afire alarm system.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 14:37:42 EDT 2016

Committee Statement

CommitteeStatement:

This brings the text back to previous edition language. The FR to editorially revise 33.2.3.4.2 created unintendedconsequences.

Response Message:

Public Comment No. 93-NFPA 101-2016 [Section No. 33.2.3.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 22 9/20/2016 3:55 PM

Second Revision No. 513-NFPA 101-2016 [ Section No. 33.2.3.4.2 ]

33.2.3.4.2 Initiation.

Where a fire alarm system is required by 33.2.3.4.1 , initiation shall be by one of the following means:

Manual means in accordance with 9.6.2.1(1)

Automatic sprinkler system that complies with 9.6.2.1(3) and provides protection throughout the building.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 14:49:29 EDT 2016

Committee Statement

CommitteeStatement:

This SR along with SR 512 brings the language back to previous edition text. The FR to editorially revise this sectioncreated unintended consequences.

ResponseMessage:

Public Comment No. 94-NFPA 101-2016 [Section No. 33.2.3.4.2]

Public Comment No. 35-NFPA 101-2016 [Section No. 33.2.3.4.2]

Public Comment No. 165-NFPA 101-2016 [Section No. 33.2.3.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 22 9/20/2016 3:55 PM

Second Revision No. 514-NFPA 101-2016 [ Sections 33.2.3.4.4.6, 33.2.3.4.4.7 ]

33.2.3.4.3.6

Smoke alarms in accordance with 33.2.3.4.3.1 33.2.3.4.4.1 , 33.2.3.4.3.2 , and 33.2.3.4.3.3 shall not be required where buildingsare protected throughout by an approved automatic sprinkler system, in accordance with 33.2.3.5, that uses quick-response orresidential sprinklers, and are protected with approved smoke alarms installed in each sleeping room, in accordance with 9.6.2.10,that are powered by the building electrical system.

33.2.3.4.3.7

Smoke alarms in accordance with 33.2.3.4.3.1 33.2.3.4.4.1 33.2.3.4.3.2 , and 33.2.3.4.3.3 shall not be required where buildingsare protected throughout by an approved automatic sprinkler system, in accordance with 33.2.3.5, that uses quick-response orresidential sprinklers, with existing battery-powered smoke alarms in each sleeping room, and where, in the opinion of the authorityhaving jurisdiction, the facility has demonstrated that testing, maintenance, and a battery replacement program ensure the reliabilityof power to the smoke alarms.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 14:52:28 EDT 2016

Committee Statement

CommitteeStatement:

This change is an editorial change. The exceptions in the 2000 edition applied to the base paragraph that had all threerequirements in it. When the committee removed the exceptions and placed only one requirement per each paragraph, theyincorrectly numbered the paragraphds such that the exception would only apply to one of the three requirements that was in thebase paragraph in the 2000 edition. Adding the paragraph references to 33.2.3.4.3.6 and 7 will fix this editorial mistake.

ResponseMessage:

Public Comment No. 106-NFPA 101-2016 [Sections 33.2.3.4.4.6, 33.2.3.4.4.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 22 9/20/2016 3:55 PM

Second Revision No. 517-NFPA 101-2016 [ Section No. 33.2.3.5.8 ]

33.2.3.5.8

Systems installed in accordance with NFPA 13D shall be inspected, tested, and maintained in accordance with 33.2.3.5.8.1 through33.2.3.5.8.15, which reference specific sections of NFPA 25. The frequency of the inspection, test, or maintenance shall be inaccordance with this Code, whereas the purpose and procedure shall be from NFPA 25.

33.2.3.5.8.1

Control valves shall be inspected monthly in accordance with 13.3.2 of NFPA 25.

33.2.3.5.8.2

Gages Gauges shall be inspected monthly in accordance with 13.2.7.1.1 of NFPA 25.

33.2.3.5.8.3

Alarm devices shall be inspected quarterly in accordance with 5.2.6 4 of NFPA 25.

33.2.3.5.8.4

Alarm devices shall be tested semiannually in accordance with 5.3.3 2 of NFPA 25.

33.2.3.5.8.5

Valve supervisory switches shall be tested semiannually in accordance with 13.3.3.5 of NFPA 25.

33.2.3.5.8.6

Visible sprinklers shall be inspected annually in accordance with 5.2.1 of NFPA 25.

33.2.3.5.8.7

Visible pipe shall be inspected annually in accordance with 5.2.2 of NFPA 25.

33.2.3.5.8.8

Visible pipe hangers shall be inspected annually in accordance with 5.2.3 of NFPA 25.

33.2.3.5.8.9

Buildings shall be inspected annually prior to the onset of freezing weather to ensure that there is adequate heat wherever water-filled piping is run in accordance with 5.2.5 4.1.2 of NFPA 25.

33.2.3.5.8.10

A representative sample of fast-response sprinklers shall be tested once the sprinklers in the system are 20 years old in accordancewith 5.3.1.1.1.2 3 of NFPA 25.

(A)

If the sample fails the test, all of the sprinklers represented by that sample shall be replaced.

(B)

If the sprinklers pass the test, the test shall be repeated every 10 years thereafter.

33.2.3.5.8.11

A representative sample of dry-pendent sprinklers shall be tested once the sprinklers in the system are 10 years old in accordancewith 5.3.1.1.1.5 6 of NFPA 25.

(A)

If the sample fails the test, all of the sprinklers represented by that sample shall be replaced.

(B)

If the sprinklers pass the test, the test shall be repeated every 10 years thereafter.

33.2.3.5.8.12

Antifreeze solutions shall be tested annually in accordance with 5.3.4 3 of NFPA 25.

33.2.3.5.8.13

Control valves shall be operated through their full range and returned to normal annually in accordance with 13.3.3.1 of NFPA 25.

33.2.3.5.8.14

Operating stems of OS&Y valves shall be lubricated annually in accordance with 13.3.4 of NFPA 25.

33.2.3.5.8.15

Dry-pipe systems that extend into the unheated portions of the building shall be inspected, tested, and maintained in accordancewith 13.4.4 5 of NFPA 25.

Supplemental Information

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 22 9/20/2016 3:55 PM

File Name Description

Chapter_33.2.3.5.8.docx For staff use

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 15:27:11 EDT 2016

Committee Statement

Committee Statement: Editorial changes to update the references to NFPA 25.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 22 9/20/2016 3:55 PM

Second Revision No. 515-NFPA 101-2016 [ Section No. 33.3.3.2.4 ]

33.3.3.2.4

Where hazardous materials are stored or handled, the provisions of 8.7.3.1 shall apply.

Submitter Information Verification

Submitter Full Name: SAF-BCF

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 19 14:58:48 EDT 2016

Committee Statement

Committee Statement: Hazardous material requirements should not apply to existing board and care.

Response Message:

Public Comment No. 95-NFPA 101-2016 [Section No. 33.3.3.2.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 22 9/20/2016 3:55 PM