NATIONAL ENERGY CONSERVATION AWARD 2007

32
NATIONAL ENERGY CONSERVATION AWARD 2007

description

NATIONAL ENERGY CONSERVATION AWARD 2007. PRESENTED BY : A.GANESAN EXECUTIVE ENGINEER (E) BSNL ELECTRICAL DIVISION MADURAI. THE BUREAU OF ENERGY EFFICIENCY HAS ANNOUNCED NATIONAL ENERGY CONSERVATION AWARD 2007. CTO BDLG. MADURAI. - PowerPoint PPT Presentation

Transcript of NATIONAL ENERGY CONSERVATION AWARD 2007

Page 1: NATIONAL ENERGY CONSERVATION AWARD  2007

NATIONAL ENERGY CONSERVATION AWARD

2007

Page 2: NATIONAL ENERGY CONSERVATION AWARD  2007

PRESENTED BY :

A.GANESANEXECUTIVE ENGINEER (E)BSNL ELECTRICAL DIVISIONMADURAI

Page 3: NATIONAL ENERGY CONSERVATION AWARD  2007

THE BUREAU OF ENERGY EFFICIENCY HAS ANNOUNCED NATIONAL ENERGY CONSERVATION AWARD 2007

Page 4: NATIONAL ENERGY CONSERVATION AWARD  2007

CTO BDLG. MADURAI

CTO BUILDING

MADURAI IS ONE OF THE TWO BUILDINGS SELECTED BY THE PCE(E) FOR NOMINATION TO THE AWARD

Page 5: NATIONAL ENERGY CONSERVATION AWARD  2007

BUILDING PROFILE

CTO COMPLEX

CTO BUILDING CTMX BUILDING LEVEL IV BUILDING

CTO COMPLEX IS COMPRISING OF THREE BLOCKS

Page 6: NATIONAL ENERGY CONSERVATION AWARD  2007

BUILDING PROFILE

A- CTO BUILDING

G- FLOOR PROPOSED SIGNLE WINDOW CSC

I FLOOR SFMSS EQPT+ ADMN. OFFICE+ IQ

II FLOOR OFFICE + IQ

III FLOOR O/oGM(DEV)+CONFERENCE HALL

Page 7: NATIONAL ENERGY CONSERVATION AWARD  2007

BUILDING PROFILE

B - CTMX BUILDING

G - FLOOR CELL MSC-II + EWSD MDF

I - FLOORSTR EQUIPMENT ( IN PROG ) + INTERNET EXCHANGE

( PROPOSED )

II - FLOOR EWSD EXCHANGE - 10K

III - FLOOR ADMN. OFFICE

Page 8: NATIONAL ENERGY CONSERVATION AWARD  2007

BUILDING PROFILE

C - LEVEL-IV BLDG.

G - FLOOR STR POWER ROOM + OUTDOOR OFFICES

I - FLOOR CELLONE CSC + STR MUX EQUIPMENT

II - FLOOR STR OFFICE + GM (DEV) OFFICE

III - FLOOR CONFERECCE HALL + STR OFFICE

Page 9: NATIONAL ENERGY CONSERVATION AWARD  2007

ENERGY CONSUMPTION CHART

CTO COMPOUND TALLAKULAM, MADURAI Energy Consumption Chart

130000

140000

150000

160000

170000

180000

190000

200000

210000

Jan

Feb

Mar

Apr

May

Jun

Jul

Aug

Sep

Oct

Nov

Dec

Month

No

of

Un

its

co

ns

um

ed

(K

wh

)

2004 2005 2006

Page 10: NATIONAL ENERGY CONSERVATION AWARD  2007

CONSUMPTION PATTERN

Consumption pattern

Window AC,Split AC,

50%

Power plant, 13%

Package AC, 13%

Lighting, 7%

Lift, 6%

Pump, 6%

Fans, 2%

Computers, 2%

Other load, 1%

Window AC,Split AC

Power plant

Package AC

Lighting

Lift

Pump

Fans

Computers

Other load

Page 11: NATIONAL ENERGY CONSERVATION AWARD  2007

REDUCTION IN SPECIFIC ENERGY CONSUMPTION

Connected Load in KW

450

460

470

480

490

500

510

520

530

540

550

2004-05 2005-06 2006-07

Connected Load inKW

SEC (KWh/KW)

34003500

36003700

380039004000

41004200

43004400

2004-05 2005-06 2006-07

SEC (KWh/KW)

AS A RESULT OF VARIOUS ENERGY CONSERVATION MEASURES ADOPTED THE ENERGY EXPENDITURE HAS COME DOWN DESPITE INCREASE IN CONNECTED LOAD

Page 12: NATIONAL ENERGY CONSERVATION AWARD  2007

CTO BUILDING - MADURAI

ON THE BASIS OF THE ACHIEVEMENTS OF VARIOUS ENERGY CONSERVATION MEASURES ADOPTED, THIS BUILDING HAS BEEN SELECTED FOR THE CONTEST

Page 13: NATIONAL ENERGY CONSERVATION AWARD  2007

MAJOR ENERGY SAVING MEASURES ADOPTED

REPLACEMENT OF 54 NOS. OLD W/T A/C UNITS BY 34 NOS. NEW SPLIT A/C UNITS

REPLACEMENT OF CONVENTIONAL TYPE POWER PLANT WITH SMPS POWER PLANT

REPLACEMENT OF ( 6 X 7 TR)OLD PACKAGE A/C PLANT WITH ( 4 X 7 TR ) NEW PACKAGE A/C PLANT

REPLACEMENT OF DEFECTIVE CAPACITORS BY NEW CAPACITORS AND GOOD PF MAINTAINED

Page 14: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF AC UNITS

OLD UNIT REPLACED BY NEW S/T AC UNIT

Page 15: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF AC UNITS

54 NOS. OUTLIVED A/C UNITS UNITS HAVE BEEN REPLACED BY 34 NOS NEW S/T A/C UNITS RESULTING IN A SAVING OF RS.8,99,360/- PER YEAR.

0

10

20

30

40

50

60

OLD NEW

OLD ACUNITS

NEW ACUNITS

Page 16: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF AC UNITS

Energy consumption details for W/T,S/T AC Units

Descriptions Old

After replacement  

New Existing

No. of units 107 34 53

Power consumption (in KW) 2.4 2 2.4

No of working hrs/day 8 8 8

No. of days working 365 365 365

Total Energy consumption in KWh 749856 198560 371424

Total Energy consumption before replacement (for107 AC units) in KWh 749856    

Total Energy consumption after replacement for(34 new units +53 old units) 87 Ac units in KWh 569984    

Savings in energy 179872    

Savings in cost @ Rs.5/- 899360    

Page 17: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF CONVENTIONAL POWER PLANT WITH SMPS POWER

PLANT

Page 18: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF CONVENTIONAL POWER PLANT WITH SMPS POWER

PLANT

THE EXISTING CONVENTIONAL TYPE POWER PLANT HAS BEEN REPLACED WITH SMPS POWER PLANT RESULTING IN A SAVING OF RS.62,550/- PER YEAR

380000390000400000410000420000430000440000450000460000470000480000

EN.COSTCONV

CONV

SMPS

Page 19: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF CONVENTIONAL POWER PLANT WITH SMPS POWER

PLANT

Power saving by replacing conventional power plant by SMPS power plant

DescriptionConventional Power

plant SMPS power plant

Efficiency of power plant 82.64% 95%

Output power ( KW) 7.5 7.5

Input power (KW) 9.08 7.89

Total energy consumption/year (Kwh) 79541 69116

Total cost of the energy (Rs.) 477246 414696

Savings in Energy /year (Kwh)   10425

Savings in cost/year (Rs.)   62550

Page 20: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF DEFECTIVE CAPACITORS

Page 21: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF DEFECTIVE CAPACITORS

THE DEFECTIVE CAPACITORS IN THE POWER FACTOR IMPROVEMENT PANEL HAVE BEEN REPLACED RESULTING IN A SAVING OF RS. 30,799/- PER YEAR.

0.974

0.976

0.978

0.98

0.982

0.984

0.986

0.988

0.99

0.992

Series1

POWER FACTOR ALWAYS > 0.98

Page 22: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF PACKAGE AC UNITS

4+2 X 7 TR REPLACED WITH

3+1 X 7 TR

Page 23: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF PACKAGE AC UNITS

THE EXISTING 4+2 X 7 TR PACKAGE AC PLANT HAS BEEN REPLACED WITH 3+1 X 7 TR PACKAGE AC PLANT RESULTING IN A SAVING OF RS.1028500/- 0

200000

400000

600000

800000

1000000

1200000

1400000

1600000

1800000

OLD NEW

EXPENDITURE

Page 24: NATIONAL ENERGY CONSERVATION AWARD  2007

REPLACEMENT OF PACKAGE AC UNITS

Energy consumption details for PAC units

Description Old New

No. of units 4 3

Power consumption (in KW) 12.6 10

No of working hrs/day 18 18

No. of days working 365 365

Total Energy consumption in KWh 331128 197100

Savings in energy   134028

Cost of Energy @ Rs.5/-unit 1655640 985500

Savings in cost   670140

other savings  

Cost of not providing 2 nos 7TR PAC units @ Rs.3,50,000/unit (A) 700000

Saving in energy for 1 units @18 hrs/day working for 365 days. 65700

Cost of Energy @ Rs.5/-unit (B) 328500

Total savings (A+B) 1028500

Page 25: NATIONAL ENERGY CONSERVATION AWARD  2007

PROPOSED ENERGY SAVING MEASURES IN 2007-08

1. CHANGE OF EB TARIFF OF 21 NOS S/Q

2. REPLACEMENT OF FL. FITTINGS WITH ENERGY EFFICIENT FITTINGS

3.PROVISION OF WATER LEVEL CONTROLLER FOR PUMPS

4. CREATING AWARENESS AMONG STAFF BY CONDUCTING PROGRAMMES & THROUGH SLOGANS

Page 26: NATIONAL ENERGY CONSERVATION AWARD  2007

CHANGE OF EB TARIFF OF S/Q

AT PRESENT 21 NOS S/Q ARE BEING FED FROM SUB STATION & ENERGY COST IS RS.5/- PER UNIT

ALL ELECTRICAL WORKS FOR GETTING SEPARATE SERVICE CONNECTION FOR S/Q ARE COMPLETED

WHEN SERVICE CONNECTION WITH RESIDENTIAL TARIFF IS EFFECTED THERE WILL BE A BI-MONTHLY SAVING OF RS 14,700/-

[ 21 S/Q X (RS 5 - RS 2.8) X 250 UNITS ]

Page 27: NATIONAL ENERGY CONSERVATION AWARD  2007

WATER LEVEL CONTROLLER FOR PUMPS

NEARLY 225 EMPLOYEES ARE WORKING & 13 NOS PUMPS ARE AVAILABLE

ALL THE PUMPS ARE BEING OPERATED MANUALLY

THERE IS A GOOD SAVING POTENTIAL BY PROVIDING WATER LEVEL CONTROLLER FOR THE PUMPS

Page 28: NATIONAL ENERGY CONSERVATION AWARD  2007

INSTALLATION OF ENERGY EFFICIENT LIGHT FITTINGS

598 NOS TWIN FITTINGS & 316 NOS SINGLE FLUORESCENT TUBE LIGHT FITTINGS ARE AVAILABLE

CONNECTED LOAD OF THESE FITTINGS WORKS OUT TO 60 KW

IT HAS BEEN PROPOSED TO REPLACE THE ABOVE WITH ENERGY EFFICIENT FITTINGS IN A PHASED MANNER

ON COMPLETION OF THE TASK THERE WILL BE A REDUCTION OF 18 KW OF LOAD

Page 29: NATIONAL ENERGY CONSERVATION AWARD  2007

AWARENESS PROGRAMME

ENERGY CONSERVATION AWARENESS WILL BE CREATED THROUGH PROGRAMMES AND SLOGAN STICKERS

Page 30: NATIONAL ENERGY CONSERVATION AWARD  2007

APPLICATION SENT

IN VIEW OF THE ABOVE MEASURES & ACHIEVEMENTS & AS PER THE INSTRUCTIONS OF THE PCE(E) & SE(E), APPLICATION FOR THE ENERGY CONSERVATION AWARD HAS BEEN SENT TO BUREAU OF ENERGY EFFICIENCY