Description of item Inspection Quantity Unit Rate Amount Quantity Unit Rate Amount Amount of Supply Item 1 2 3 4 5 6 7 8 9 10 11 1. Supply, erection, testing & commissioning of 3.15 MVA, 33 / 11 KV Delta Star, copper wound, oil immersed, ONAN cooled outdoor type, 3Phase, 50Hz, step down power transformer with OFF load tap changer with taps ranging from +10% to -10% in steps of 2.5% each on HV winding with first filling of EHV grade insulating oil & complete with conservator tank, Buchholz relay, breather, winding & oil temperature meters housed in outdoor panel attached with the transformer complete as per relevant ISS.. 2 No. 2 No. 2. Supply, erection, testing & commissioning of 33 KV, 1000A, 750 MVA rupturing capacity, outdoor Vacuum Circuit Breaker complete with motor operated spring closing (Local / Remote) arrangement with all accessories including lattice support structure,foundation bolts,G.I. nuts & bolts,washers etc. as required and as per relevant ISS complete operative on 110V DC. 33 KV outgoing for Takajala/Incoming at Jampuijala 1 No. 1 No. For Power Transformer 2 No. 2 No. (Amount in Rs.) Erection Sl No. Supply SCHEDULE OF WORK Name of work:- Design,Engineering,Manufacturing,Testing,Supply, installation,Erection & commissioning of 2 X 3.15 MVA, 33 / 11KV Substation complete with construction of Double storied control room cum office building,equipment foundation, boundary wall and Land developement at Jampaijala including Construction of approximately 7.0 CKM. 33 KV "Takarjala-Jampuijala" subTransmission line from Takarjala 33 KV Sub-Station. SCHEDULE - A (Supply , installation & commissioning of Sub-station equipment, control gear and structures) Page 2

Transcript of Name of work:- Design,Engineering,Manufacturing,Testing ... · double break, triple pole Gang...

  • Description of item InspectionQuantity Unit Rate Amount Quantity Unit Rate Amount Amount of Supply Item

    1 2 3 4 5 6 7 8 9 10 111. Supply, erection, testing & commissioning of 3.15 MVA,

    33 / 11 KV Delta Star, copper wound, oil immersed,ONAN cooled outdoor type, 3Phase, 50Hz, step downpower transformer with OFF load tap changer with tapsranging from +10% to -10% in steps of 2.5% each on HVwinding with first filling of EHV grade insulating oil &complete with conservator tank, Buchholz relay,breather, winding & oil temperature meters housed inoutdoor panel attached with the transformer complete asper relevant ISS..

    2 No. 2 No.

    2. Supply, erection, testing & commissioning of 33 KV, 1000A, 750 MVA rupturing capacity, outdoor Vacuum Circuit Breaker complete with motor operated spring closing (Local / Remote) arrangement with all accessories including lattice support structure,foundation bolts,G.I. nuts & bolts,washers etc. as required and as per relevant ISS complete operative on 110V DC.

    33 KV outgoing for Takajala/Incoming at Jampuijala 1 No. 1 No.

    For Power Transformer 2 No. 2 No.

    (Amount in Rs.)

    ErectionSl No.

    Supply

    SCHEDULE OF WORK

    Name of work:- Design,Engineering,Manufacturing,Testing,Supply, installation,Erection & commissioning of 2 X 3.15 MVA, 33 / 11KV Substation complete with construction of Double storied control room cum office building,equipment foundation, boundary wall and Land developement at Jampaijala including Construction of approximately 7.0 CKM. 33 KV "Takarjala-Jampuijala" subTransmission line from Takarjala 33 KV Sub-Station.

    SCHEDULE - A (Supply , installation & commissioning of Sub-station equipment, control gear and structures)

    Page 2

  • Supply, erection, testing & commissioning of 33 KV,800A, manually operated horizontal rotating typedouble break, triple pole Gang operated isolatorcomplete with post insulator, arching horns, mechanicalinterlocking arrangement etc.as per relevant ISS.

    a) With earth switch. 2 No. 2 No.b) Without earth switch. 6 No. 6 No.

    4. Supply, erection, testing & commissioning of 33 KVSingle Phase, outdoor type 3 Core C.T of ratio 100 / 1-1-1 Amp with suitable burden & class of accuracycomplete with associated terminal box connecting linketc. as per relevant ISS and as required(ForTransformer).

    6 No. 6 No.

    5 Supply, erection, testing & commissioning of 33 KVSingle Phase, outdoor type 2 Core C.T of ratio 200 / 1-1Amp with suitable burden & class of accuracy completewith associated terminal box connecting link etc. ( for 33 KV incoming feeder)

    3 No. 3 No.

    6 Supply, erection, testing & commissioning of 33 KVSingle Phase , outdoor type P.T of ratio 33000V / √ 3 /110V / √ 3 having suitable burden & class of accuracyas detailed herein after in technical specification and asper relevant ISS .

    3 No. 3 No.

    7 Supply, erection, testing & commissioning of 10KA, 30 KV,Station Valve type metal oxide heavy duty Lightning SurgeArrestor suitable for operation on 33KV Sytem conforming toISI : 3070 (P-1) / 1974 and amendments thereafter and asrequired.

    12 No. 12 No.

    3.

    Page 3

  • Supply, erection, testing & commissioning of 33 KV control &relay panel, simplex type complete with differential relay, 2-over current and 1- Earth fault combined relay, Auxiliary relay,1- voltmeter, 3- ammeter, CT operated static trivector meter,internal panel wiring, simaphore for Vacuum Circuit breaker &isolator, Mimic bus diagram (Metal size 4mm thick X 10mmwidth).

    a) For 3.15 MVA, 33 / 11 KV Power transformers. 4 No. 4 No.

    b) For 33 KV outgoing/incoming feeder without differential relay..

    4 No. 4 No.

    9 Supply , erection, testing & commisioning of 11 KV vaccumCircuit breaker with Control & relay panel (Incoming) simplextype 800 A contineous current rating,, 350 MVA rupturingcapacity complete with manual and motorised spring closingmechanism ,electrical closing and opening arrangement andinternal panel wiring with provisions of 2- overcurrent & 1-earth fault combined relay, auxilliary relays, 1- volt meter withselector switch, 3- ammeter, C.T. operated static trivector/multi functional energy meter, 1- CT operated static KWHmeter. Breaker capacity800 Amps continuous currentCTR 300/1-1-0.577 Amp with panel top mounted P.T. of PTR 11KV /√3 / 110V / √3 with integral earthing facility and internal arctested for transformer incoming panel as required and as perrelevant ISS.

    2 No. 2 No.

    8

    Page 4

  • 10 11 KV Vaccum Circuit breaker , Control & relay panel simplextype, 800 A continuous current 350 MVA rupturring capacitycomplete with electrical closing mechanism with internalwiring 2- overcurrent & 1- earth fault combined relay,.auxilliary relays,3- ammeter, 1-Volt Meter, C.T. operated statictrivector meter/ Multi functional Energy meter. 1- CT operatedstatic KWH meter with 3 sets of C.T. of Ratio 200 / 1-1 A withintegral earthing facility and internal arc tested for11 KV outgoing feeders as per relevant ISS and as required..

    6 No. 5 No.

    Supply and Erection of Galvanised steel structure and Nuts &Bolts, spring washer etc as required for 33 KV Tower gangtry,Post Insulators and equipments

    a) Steel structure 10.85 MT 10.85 MTb) Nuts & bolts, spring washer and foundation bolts etc. 1.8 MT 1.8 MT

    Supply, erection, testing & commissioning of sub- stationbusbar & stringing materials for 33 KV bus.

    a) ACSR (DOG) 7/1.57/6/4.72 mm (DOG ) conductor. 0.5 KM 0.5 KM

    b) 40mm dia. Al. pipe for equipment bus of current carryingcapacity 400 Amps. 300 Mtr. 300 Mtr.

    c) 7/3.15mm earth wire for substation shielding. 300 Kg 300 Kgd) Ball & socket type 70 KN, 11KV disc Insulator. 72 Nos 72 No.e) Al. tension clamps. 3 -U bolt type, ball& socket type,suitable for70KN Disc Insulator and ACSR DOG conductor. 24 No. 24 No.

    f) 33 KV post insulator 15 No. 15 No.g ) Suspension Clamp suitable for ACSR, DOG Conductor.

    24 No. 24 No.

    h)"T" Clamp suitable for ACSR DOG Conductor. 15 No. 15 No.i)"T" Clamp suitable for ACSR DOG Conductor in one end &40mm dia. Al. tube in other end. 15 No. 15 No.

    12

    11

    Page 5

  • j) Bimetalic clamps suitable for isolator, C.T, P.T., breaker,transformer& L.A. etc. 27 No. 27 No.

    11 / 6.35(E) XLPE power cable a) 240 mm Sq. single core (for 3.15 MVA transformerconnection).

    0.5 Km. 0.5 Km

    b) 185 mm Sq. 3- core(for out going feeder) 0.75 Km. 0.75 KmOutdoor type heat shrink joint kit for 11 KV XLPE cableof size :- a) 240 mm sq. single core 7 No. 7 No.b)185 mm sq. 3- core 7 No. 7 No.Indoor type heat shrink jointing kit for II KV XLPE cableof size :-

    a ) 240 mm sq. single core 7 No. 7 No.b ) 185 mm sq. 3- core 7 No. 7 No.

    16 1100 V grade XLPE insulated & PVC sheathedarmoured Al. cable of size, 70mm sq. 3½ Core cable. 0.2 Km 0..1 Km

    Supply, laying, termination etc. of control cable 1100V,PVC insulated, PVC sheathed 2.5 mm sq copperconductor.a) 12-Core 300 Mtr. 300 Mtr. b) 7-Core 300 Mtr. 300 Mtr. c) 4-Core 400 Mtr. 400 Mtr. d) 2-Core 300 Mtr. 300 Mtr.

    18 Supply of 40mm dia hot Dip perforated Heavy duty G.Ipipe of length 3 mtr and providing earthing as per latestISS: at 33 KV & 11KV switch yard including pair of GIclamps and nuts & bolts as required as per RECspecification, drawing as stipulated herein after .

    18 No. 18 No.

    19 Supply and laying of GI flat 50 X 6 mm size for interconnection of earth electrodes and earthing terminals ofequipments, structures including welding in joints asrequired for mesh earthing.

    300 Mtr. 300 Mtr.

    15

    14

    13

    17

    Page 6

  • 20 Supply & erection of 90 pound lb rail for transformer railtrack. 1.5 MT. 1.5 MT.

    21 Supply,Installation & commissioning of 110V, 240 AHcapacity Sealed & Maintenance Free (SMF) BatteryBank comprising of 55 Nos.'Standby Valve RegulatedLead Acid (VRLA) Cells' of 2 Volt each (Average Discharge Voltage 1.90 VPC) as per specification inthe Bidding / Tender Document.

    1 Unit 1 Unit

    22Battery Charger with ±1% Digitally ControlledRegulation suitable for above 110 Volt VRLA BatteryBank with Float and Boost (FC & BC) chargingarrangement with all Standard protections housed infree Standing Cabinet of 2.0 mm. gauge as perspecification detailed in the Bidding / Tender Document.

    1 Unit 1 Unit

    Supply, erection, testing & commissioning of 110V D.Cdistribution panel made of sheet steel (14 SWG) andsuitable for floor mounting. The distribution panel shallincorporate the following :-

    a) 1-No, 32 Amp. 110V Air break circuit breaker, Doublepole for the battary incomming supply with red & greenindicating lamps.b) 1-No earth leakage indicating lamp.c) 1-No ammeter (range 0-50 A).d) 1-No volt meter (Range 0-150 V).e) 4-Nos 16 Amps 110V double pole miniature Circuit breakerwith over load protection for DC outgoing circuit . The unitwill be complete with necessary internals wiring. Input &outgoing terminals, earthing, points & rating plate.

    Unit Unit1 1

    23

    Page 7

  • Supply, Erection, testing & commissioning of 433/450V, 3 Ph.4 wire 50 Hz, AC distribution board enclosed in sheet steel(14 SWG) floor mounting type (vertical) comprising thefollowing:-

    a) 200 Amp 3-Ph 4-wire , 415 V TPN switch fuse unit (HRCtype) as incomming switch.

    b) 200 Amp 3-Ph. 4-wire , 415 V Al. bus bar having thefollowing outgoing switch facilities.

    i) 100 Amp 415 V 3 ph. 4 wire switch (HRC- type): - 1 No.

    ii) 63 Amp 415 V 3 ph. 4 wire switch (rewireable type): - 2Nos.

    iii) 32Amp 250 V 1 ph.2 wire switch (rewireable type): - 2 Nos.

    iv) 16Amp 250 V 1 ph.2 wire switch (rewireable type): - 3 Nos.

    c) AC voltmeter (Range 0- 500 V) with selector switch (RYB): -1No.

    d) AC Ammeter (Range 0- 300 V) for (RYB) phase : - 3Nos.

    11 KV outgoing bus bar materials

    a) 9 KV, 5 KA, single pole, Metal oxide gapless surgetype LA suitable for nominal system voltage of 11 KV, 3-Ph., 50 Hz AC supply, creepage distance 600 mm.conforming to ISS: 3070 / 1985.

    21 No. 21 No.

    b) 9 Mtr. Long steel tubular pole of designation 410- SP-31 conforming to ISS: 2713 / 1980 with base platecomplete.

    12 No. 12 No.

    c ) Steel materials (Angles & channels). 1.2 MT 1.2 MTd) 45 KN, 11KV disc insulator with 3 U Bolt type discfittings.

    75 No. 75 No.

    e ) 11 KV, 10 KN pin insulator including G.I. pin. 60 No. 60 No.f) 11 KV 3 pole GOS ( Air break type ) -400A. 15 No. 15 No.

    24

    1 Unit1 Unit

    25

    Page 8

  • g) 11KV 3 pole DOF for station transformer 200A. 1 Set 1 Seth) Nuts & bolts assorted size 300 Kg 300 Kgi) 50X6 mm M.S flat for clamp 250 Kg 250 Kgj) ACSR (DOG ) 7/1.57/6/4.72 mm. 0.3 Km 0.3 KmSupply & erection of fire fighting equipment withcomplete accessories . a) G.I bucket - 10 ltrs capacity with wooden / iron stand.

    6 No. 6 No.

    b) Portable fire extinguisher using CO2 with pressureindicator: -5Kg.

    3 No. 3 No.

    c) ABC powder fire extinguisher "Mono Ammoniumphosphate".i) 5- Kg 2 No. 2 No.ii) 2- Kg 2 No. 2 No.

    27 Supply, erection, testing & commissioning of 100 KVA,11/0.43 KV, DY- 11 distribution transformer for stationload.

    1 No. 1 No.

    28 Supply,fabrication,erection including grouting asrequired of 7.5 Mtr long GI support (heavy duty type)having bottom length 4.5 mtr. of dia 65 mm and upperlength of 3 mtr. and 40 mm. dia. For Switchyard lighting.

    16 No. 16 No.

    29 Switchyard lighting complete with 250W, 230V, HPSVluminaries with switchgear complete with the support ofitem 28 including required wiring through the pipe andprovision of control gear( MCB) for individual lantern /lamp as required and per direction of Engineer in charge.

    10 Unit 10 Unit

    30 Shock treatment chart (Laminated ) 2 No.

    31 Artificial respirator 2 No.32 Rubber insulating mat at 15 KV tested of size (1X2)

    mtr. 4 No.

    33 Oill filtration plant of capacity 250 G.P.H. (NIRMALBRAND / John Fowler).

    1 No.

    26

    Page 9

  • 34 a) Hand driven Insulation Tester 5KV (WACO make),10000 M-ohm minimum.

    1 No.

    35 a) Hand driven Insulation Tester 2.5KV (WACO make),10000 M-ohm minimum.

    1 No.

    36 Chain pully block ( 5 ton capacity ) 1 No.

    37 Pulling & lifting machine ( TIRFOR ) 5 ton / capacity. 1 No.

    38 c) Digital clamp meter capable of measuring Variousparameters(RMS values for Voltage & Current):ACCurrent 40/400Amps.AC Voltage: 600V, DC Voltage600V, Resistance 40MegaOhm with LCD Display.DataHold, Audible continuity, Diode Test, Over RangeIndication,Low Battery Indication,etc. shall be avilable inthe meter.etc.as per standard specification andperovisions.

    1 No.

    39 Complete Tool Box with Box Spanner (1 each ofTAPARIA make product no. 1720, 1722, 1725, 1728 and 17301.

    1 Set

    40 15 KV grade hand gloves. 4 Pair

    41 Taparia make Allen key set of 2 different range . 2 Set42 Oil testing set with input volt 230 , 50 Hz single phase

    out put 0-100 KV I/C necessary accessories conformingreleveant IS.

    1 No.

    43 TAPARIA make double ended spanner. 1 Set.

    44 TAPARIA make ring rances. 1 Set.

    45 TAPARIA make insulating screw driver. 1 Set.46 4-Point earth tester. 1 No.47 33 KV discharge Rod of 3 section made of fibre glass

    tube complete with all accessaries as per specification. 2 Set

    48 Crimping tool AAKASH-100 Capacity 6 mmsqr- 400 mmsqr. Weight 5.8 Kg.

    1 No.

    49 Steel Leaning Bench(8'ftX16''inch Long) 2 No

    Page 10

  • 50 Best Quality Plastic Chair with arm. 18 No51 Steel Almirah ( with one locker) 60"x36"x18" 8 No52 Steel Table half Secretariate with Laminated Sheet top

    & with three drawers including automatic locking device to the right side. Storage Unit Size: H. 20"xW.14"xD.21" 8 No

    53 Steel tubulor Chair(with cush-ioned seat and back witharm)(Squire pipe)

    4 No

    SCHEDULE -B(33KV LINE)

    1 Supply and erection of steel tubular pole conforming toISS 2713 (P-I & II) 1980 with base plate direct in earthincluding excavation, refilling and ramming etc. asrequired complete (1 /6th of the length of the pole tobe embedded in earth).

    a) 12 mtr long steel tubular pole 410-SP-44. 198 Nos 198 Nos2

    Supply and erection of painted stay set complete directin earth with 16 mm. dia. 1.8 mtr. long painted stay rod,anchor plate of size 300 X 300 X 8 mm. thick, turnbuckle of length 356 mm. with 300 mm. long threadedadjustable 16 mm. dia. MS rod and thimble includingsupply & erection of 33 KV guy insulator as per ISspecification, hot dip (heavy duty) galvanized staystranded wire of size 7/2.5 mm. grade - IV as perISS:2141/1979 having minimum tensile strength 700Nmmsq. with Zinc coating (heavy type coating conformingto IS:4826/1979, weight 260 Kg. 1 Km.) fastened withstay clamps as required.

    117 set 117 Set3 Supply of 33 KV Stay insulator. 117 Nos4 Supply of galvanized Stay stranded wire of size 7/2.50

    mm 585 Kg

    Page 11

  • 5Supply,Erection, fitting & fixing of 1.8 m long fabricated Cross arm for four pole/two pole structure made up of (100x50x50x6)mm M.S. channel on Pole with 4 machine made holes for its fixing on poles and 3 machine made holes for fixing on it 3 nos.for strings of disc insulator comprising 3 Discs in each string with the support of Back clamp and nuts & Bolts etc. as required and as per design and drawing to be specified by TSECL as per REC Standards.( for 4 Pole Locations & Double pole) for pin.

    82 Nos 82 Nos6 Supply,Erection, fitting & fixing of 1.8m long fabricated

    4 Pole Cross arm made up of (100x50x50x6)mm M.S. channel for pin insulator. 6 Nos 6 Nos

    7 Supply,Erection, fitting & fixing of 1.5m long fabricated 1 Pole Cross arm made up of (100x50x50x6)mm M.S. channel for pin insulator. 116 Nos 116 Nos

    8 Supply,Erection, fitting & fixing of 0.3m long fabricated 1 Pole Cross arm made up of (100x50x50x6)mm M.S. channel for pin insulator. 116 Nos 116 Nos

    9Supply, Erection, fitting & fixing of fabricated Double Pole" / "four pole"Guard bracket made of 2.1 mtr (65x65x6)mm M.S.Angle and machine drilled holes on brackets ( 4 Nos. of holes for double pole bracket) for fixing to poles with Clamp and another 2 holes at both ends of such brackets to hold continued G.I. earth Wire as per design,drawing and engineering requirement of TSECL as per REC Standards as follows:

    41 Nos 41 Nos

    Page 12

  • 10Supply, Erection, fitting & fixing of fabricated Double Pole" / "four pole"Guard bracket made of 1.8 mtr (65x65x6)mm M.S.Angle and machine drilled holes on brackets ( 4 Nos. of holes for double pole bracket) for fixing to poles with Clamp and another 2 holes at both ends of such brackets to hold continued G.I. earth Wire as per design,drawing and engineering requirement of TSECL as per REC Standards as follows:

    41 Nos 41 Nos11

    Supply, Erection, fitting & fixing of fabricated Double Pole" / "four pole"cross basing bracket made of 2.54 mtr (65x65x6)mm M.S.Angle and machine drilled holes on brackets ( 4 Nos. of holes for double pole bracket) for fixing to poles with Clamp and another 2 holes at both ends of such brackets to hold continued G.I. earth Wire as per design,drawing and engineering requirement of TSECL as per REC Standards as follows:

    82 Nos 82 Nos12

    Supply, Erection, fitting & fixing of fabricated Double Pole" / "four pole"cross basing bracket made of 1.8 mtr (65x65x6)mm M.S.Angle and machine drilled holes on brackets ( 4 Nos. of holes for double pole bracket) for fixing to poles with Clamp and another 2 holes at both ends of such brackets to hold continued G.I. earth Wire as per design,drawing and engineering requirement of TSECL as per REC Standards as follows:

    82 Nos 82 Nos13 Supply,fitting & fixing of 70 KN,11 KV ball & socket type

    disc insulator with cap, pin bolt & W clips (phosphor bronze; etc complete as per latest ISS 731-1971 and related latest amendments.(3 nos.Disc Insulator in 1 Set) 228 Nos 228 Nos

    Page 13

  • 14Supply,fitting & fixing of accessories suitable for 11KV Ball & socket type 70KN Disc insulator and ACSR conductor (7/1/6/ 4.73mm) "DOG "as per ISS and latest amendment for tension insulator string comprising following & all other accessories necessary.

    228 set 0 0a Ball Clevis.b Tension clamp 3 U Bolt Type .c Galvanised "U" bolts & nuts. d Galvanised Spring washer. e Flat washer. f Split pin mild steelg Phosphor bronze"U" Clip

    15 Supply & erection of hot dip galvanised MS forged 33 KV pin ( L-230P) suitable for 33 KV pin insulator complete with galvanized hexagonal nuts, G.I flat washer & G.I spring washer conforming to ISS: 2486 (P-II)/1974. The shunk length shall be 100 mm. 348 Nos 348 Nos

    16 Supply & erection of brown glazed porcelain pin insulator for 33 KV system with minimum creeapage 580 mm with mechanical strength 10 KN conforming to ISS: 731 /1971 to mach with 33 KV G.I pin ( L-230P).as per ISS: 2486 (P-II)/1974 348 Nos 348 Nos

    17 Supply,laying,hoisting & stringing of DOG ACSR conductor of size (7/1.57/6/4.72mm.) conforming to IS 398(Part-IV) I974 including binding jumpering etc with P.G.Clamp as required. 21 Km 21 Km

    18 Supply,hoisting, erection & stringing of 8 SWG GI wire(4mm dia) conforming to ISS:280/1978 and latest related amendments with heavy coating Zinc conforming to ISS:4826/1979 i/c laying, hoisting,binding & jumpering etc as reqd. 1610 Kg 14 Km

    Page 14

  • 19 Supply, fitting fixing of fabricated M.S. clamp with necessary machine mads hole for fixing of different type of cross arm with poles /Stay sets made up of 50x6 mm M.S. flate with 2 coats of red oxide primer paint and 1 coat of Al. paint of approved quality 794 Nos 794 Nos

    20Supplyof machine made full threaded M.S. nuts & bolts of assorted size (16x50 mm to 12x300 mm) conforming to ISS 1363 of 1960 and latest amendments.

    320 Kg21 Supply,fitting & fixing of 33 KV Danger plate as per ISS -

    2551 of 1963 and latest amendments with the help of 12 SWG G.I.wire.. 198 Nos 198 Nos

    22 Supply & erection of 12 SWG. G.I barbed wire, 2-ply, 4 points a 3 " part for generating Engineering purpose having zinc contain as per ISS: 4826/1968 396 Kg 64 Nos

    23Providing cradle guards by 8 SWG G.I. wire between earth wire across road crossing,river crossing etc.

    840 Nos24 Grouting of steel tubular poles / stay sets in 1 : 3 : 6 (1

    cement : 3 River Sand : 6 brick aggregate with 20 mm nominal size) i/c. supply of cement ,sand & brick aggregate , excavation, masionry work, back filling of earth,carrying etc. as required along with the cost of centering and shuttering (0.15cum/pole & 0.027cum/stay) 32.859 Cum

    25 Providing spike earthing with GI rod 1.8 mtr. Long and 20 mm dia including connecting clamps,blts etc alongwith drawing of earth wire (8 SWG GI wire ) from earth spike to metals parts pole structure and excavation, refilling, ramming etc. as required as per direction of the Engineer-in-charge. 60 Nos

    Page 15

  • 26 Painting one or more coats with superior ready mixed paint for steel work of approved quality in all shades on new work to give an even shade including priming coat with cross arms. 198 Nos

    27 Providing of Vehicle with valid registration and driver with Licence (MARUTI OMNI) for conveyance of Supervisiory staff/ officers including supply of Fuel & Lubricants as required time to time. 30 Days

    SCHEDULE - CR.C.C FRAMED CONTROL ROOM BUILDING (DOUBLE STORIED)SUBHEAD- EARTHWORKEarth work in excavation over areas (exceeding 30cm in depth, 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed.

    -All kinds of soil

    By manual means 20.00 cum

    Earth work in excavation in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.

    -All kinds of soil

    By manual means 200.00 cum

    Extra for additional lift of 1.5m or part thereof

    -All kinds of soil 17.45 cum

    1

    2

    3

    Page 16

  • Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.

    -All kinds of soil 140.00 cum

    5 Supplying and filling in plinth, under floor, foundations etc. with sand (fine) from local quarry with all lifts including spreading in horizontal layers, watering, grading to required slope, ramming, consolidating and compacting each layer by using plate compactor or by any suitable method complete.

    100.00 cum

    Supplying chemical emulsion in sealed containers including delivery as specified.

    Chlorpyriphos/Lindane emulsifiable concentrate of 20% 28.87 Litre

    Diluting and injecting chemical emulsion for PRE-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) and continuous chemical barrier under and alround the column pits, wall trenches, basement excavation, top surface of plinth filling, junction of wall and floor, along the external perimeter of building, expansion joints, over the top surface of consolidated earth of which apron is to be laid, surroundings of pipes and conduits etc. complete as per specification. The work should be carried out as per IS: 6313 (Part II)- Latest revision [Plinth area of the building at ground floor only shall be measured for payment] :

    With Chlorpyriphos/Lindane E.C. 20% with 1% concentration.

    120.00 sqm

    SUBHEAD-CEMENT CONCRETE WORKS

    4

    6

    7

    Page 17

  • Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering -

    -All work upto plinth level:

    1:4:8 ( 1 Cement: 4 fine sand : 8 graded stone aggregate 40 mm nominal size) 23.00 cum

    1:3:6 ( 1 Cement: 3 fine sand : 6 graded stone aggregate 40 mm nominal size) 38.00 cum

    1:2:4 ( 1 Cement: 2 fine sand : 4 graded stone aggregate 20 mm nominal size) 2.9 cum

    SUBHEAD-R.C.C WORK

    Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centring, shuttering, finishing and reinforcement-

    -All work upto plinth level:

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 39.00 cum

    Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and skirting courses, fillets, columns, pillars, piers, abutments, posts and struts etc. upto floor five level excluding cost of centring, shuttering, finishing and reinforcement-

    In walls (any thickness), including attached pilasters, buttresses, piers, abutments etc.

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 1.50 cum

    In plinth and skirting courses, fillets, columns, pillars, posts and struts

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 38 cum

    8

    10

    9

    Page 18

  • Reinforced cement concrete work in beams, suspended floors, roofs having slope upto 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases upto floor five level excluding the cost of centring, shuttering, finishing and reinforcement-

    RCC work in suspended floors, roofs having slope upto 15° landings, balconies, shelves and chajjas.

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 103 cum

    RCC work in beams, lintels, bands, plain window sills, staircases and spiral staircases excluding precast spiral staircase.

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 70 cum

    Providing and laying upto floor five level reinforced cement concrete work in kerbs, steps and the like excluding the cost of centring, shuttering, finishing and reinforcement-

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 1.50 cum

    13 Providing, hoisting and fixing upto floor five level precast reinforced cement concrete work in shelves including setting in cement mortar 1:3(1cement : 3 fine sand), cost of required centring, shuttering, finishing with neat cement punning on exposed surfaces complete, but excluding cost of reinforcement with cement concrete 1:2:4 (1cement : 2 fine sand : 4 graded stone aggregate 20mm nominal size).

    3.20 cum

    Centering shuttering including struttings, propping etc. and removal of form work for:

    Foundations, footings, bases for columns etc. for mass concrete with timber plank 80.00 sqm

    14

    12

    11

    Page 19

  • Walls (any thickness) including attached pilasters, buttresses, plinth and string courses etc. using shuttering ply

    40.00 sqm

    Suspended floors, roofs, landings, balconies and access platform with 12 mm thick shuttering ply 950.00 sqm

    Lintels, beams, plinth beams, girders, bressumers and cantilevers with shuttering ply 700.00 sqm

    Columns, Pillars, Piers, Abutments, Posts and Struts with shuttering ply 580.00 sqm

    Spiral staircases (including landing) - cast-in-situ with ply

    45.00 sqm

    15 Providing, hoisting and fixing upto floor five level precast reinforced cement concrete work in mouldings as in cornices, windows sills etc. including setting in cement mortar 1:3(1cement : 3 fine sand), cost of required centring, shuttering, finishing smooth with 6mm thick cement plaster 1:3 (1cement : 3 fine sand) on exposed surfaces complete, but excluding cost of reinforcement with cement concrete 1:2:4 (1cement : 2 fine sand : 4 graded stone aggregate 20mm nominal size).

    1.25 cum

    Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto floor five level.

    Thermo-Mechanically Treated bars/ Cold twisted deformed steel bars 26000.00 kg

    SUBHEAD- BRICK WORK

    First class brick work in foundation and plinth including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 51 Cum.

    First class brick work in superstructure above plinth level & upto floor-five level including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 38.50 Cum.

    16

    17

    18

    Page 20

  • 19 Half brick masonry work with first class bricks in foundation and plinth including cost of all materials as required complete:-

    32.00 Sqm.

    Half brick masonry work with first class bricks in superstructure upto floor five level including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 950.00 Sqm.

    Extra for providing & placing in position 2 nos 6mm dia MS bars at every 6th course of full brick masonry work including anchorage in joints of 75mm in each side in superstructure for all level including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 5.00 Cum.

    Extra for providing & placing in position 2 nos 6mm dia MS bars at every 4th course of half brick masonry work including anchorage in joints of 75mm in each side in superstructure for all level including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 5.00 Sqm.

    SUBHEAD- WOOD WORK

    Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position :

    Karai wood 1 CumProviding and fixing ISI marked flush door shutters conforming to IS: 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.

    35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws. 42.00 Sqm

    23

    20

    24

    21

    22

    Page 21

  • Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. all complete.

    Fixed to openings /wooden frames with rawl plugs screws etc.

    1900.00 Kg26 Providing 40 × 5 mm flat iron hold fast 40 cm long including

    fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embedding in cement concrete block 30 × 10 × 15 cm 1:3:6 mix (1 cement : 3 fine sand : 6 graded stone aggregate 20mm nominal size)

    108 No27 Providing and fixing chromium plated brass 100 mm mortice

    latch and lock with 6 levers and a pair of lever handles with necessary screws etc. complete (best make of approved quality).

    32 NoProviding and fixing aluminium sliding door bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with nuts and screws etc. complete :

    300x16 mm 26 NoProviding and fixing aluminium tower bolts ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to required colour or shade with necessary screws etc. complete :

    300x10 mm 120 NoProviding and fixing aluminium handles ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade with necessary screws etc. complete :

    125 mm 65 No

    25

    28

    30

    29

    Page 22

  • Providing and fixing aluminium hanging floor door stopper ISI marked anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour and shade with necessary screws etc. complete.

    Twin rubber stopper 18 No32 Providing and fixing factory made P.V.C. door frame of size

    50x47mm with a wall thickness of 5mm, made out of extruded 5mm rigid PVC foam sheet mitred at corners and joined with 2 Nos. of 150mm long brackets of 15x15mm M.S. square tube, the vertical door profiles to be reinforced with 19×19mm MS square tube of 19 gauge, EPDM rubber gasket weather seal to be provided through out the frame . The door frame to be fixed to the wall usuing MS screws of 65/100 mm size complete as per manufacturers' specification and direction of Engineer-In-Charge.

    70.00 mtr.Providing and fixing to existing door frames.33

    31

    Page 23

  • 30mm thick factory made solid both side prelam panel PVCdoor shutter consisting of frame made out of M.S. tubes of 19gauge thickness and size of 19mm x 19mm for styles, top &bottom rails. M.S. frame shall have a coat of steel primers ofapproved make and manufacture . M.S. frame covered with5mm thick heat moulded prelam PVC ‘C channel of size30mm thickness, 70mm width out of which 50mm shall be flatand 20mm shall be tapered in 45degree angle on either sideforming stiles; and 5mm thick, 95mm wide PVC sheet out ofwhich 75mm shall be flat and 20mm shall be tapered in 45degree on the inner side to form top and bottom rail and115mm wide PVC sheet out of which 75mm shall be flat and20mm shall be tapered on both sides to form lock rail. Top,button and lock rails shall be provided either side of the panel.10mm (5mm x 2 ) thick, 20mm wide cross PVC sheet beprovided as gap insert for top rail & bottom rail, panelling of5mm thick both side Prelam PVC sheet to be fitted in the M.S.frame welded/ sealed to the stiles & rails with 7mm(5mm+2mm) thick x 15mm wide PVC

    sheet beading on inner side, and joined together with solvent cement adhesive. An additional 5mm thick PVC strip of 20mm width is to be stuck on the interior side of the ‘C Channel using PVC solvent adhesive etc. complete as per direction of Engineer-in-charge. manufacturer’s specification & drawing.

    22.00 sqmSUBHEAD- STEEL WORK

    34 Providing structural steel work in single section fixed with or without connecting plate including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete as required.

    350.00 Kg.

    Page 24

  • 35 Providing and fixing in position collapsible steel shutters with vertical channels 20x10x2mm at 100 mm centre to centre and braced with flat iron diagonals 20x5mm size with top and bottom rail of T-iron 40x40x6mm with 40mm dia. steel pulleys & with riveted bolts, nuts, locking arrangement, stoppers, handles, hold fast /anchor bolt including embedding in cement concrete of required grade for fixing in position, all necessary fittings, including applying a priming coat of approved steel primer etc. complete as required.

    42.00 Sqm.

    Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6mm angle iron and 3mm M.S. gusset plates at the junctions and corners, & with cleats with bolts & nuts, rivets, locking arrangement, handles, hooks & eyes, pinlets including embedding in cement concrete of required grade for fixing in position, all necessary fittings, including applying a priming coat of approved steel primer etc. complete as required:-

    Using M.S. angels 40x40x6 mm for diagonal braces. 4.50 Sqm.

    Supplying and fixing rolling shutters of approved make, madeof required size M.S. laths interlocked together through theirentire length and jointed together at the end by end locksmounted on specially designed pipe shaft with brackets, sideguides and arrangements for inside and outside locking withpush and pull operation complete including the cost ofproviding and fixing necessary 275mm long wire springsgrade No.2 and M.S. top cover of required thickness for rollingshutters & with handles, hold fast including embedding incement concrete of required grade required for fixing inposition, all necessary fittings, including applying of approvedsteel primer etc. complete as required:-

    37

    36

    Page 25

  • 80xl.25mm M.S. laths with 1.25 mm thick top cover. 5.40 Sqm.

    38 Providing and fixing ball bearing for rolling shutters ( exceeding 10 sqm area ) of approved make complete as required. 4 Each

    39 Providing and fixing circular/ Hexagonal cast iron or M.S. sheet box for ceiling fan clamp of internal dia 140mm, 73mm height, top lid of 1.5mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/ M.S. sheet box by means of 3.3mm dia. round headed screws, one lock at the corners. Clamp shall be made of 12mm dia M.S. bar bent to shape, including painting the exposed portion as per standard drawing complete as required (provided incase of low ceiling height).

    25 Each

    Steel work welded in built up section/framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using steel etc. complete as required:-

    In grating, frames, guard bar, railing, brackets, gates and similar works, all complete. 450 Kg.

    SUBHEAD-FLOORING WORK

    Providing and laying polished vitrified floor tiles in different sizes ( thickness to be specified by the manufacturer ) with water absorption less than 0.08 % and conforming to IS : 15622 of approved make in all colours, shades over 20 mm thick bed of cement mortar 1 : 4 ( 1 cement : 4 fine sand ) jointed with ordinary cement slurry including pointing with white cement mixed with pigment of matching shade complete.

    Size of tile 60x60 cm 120 sqm

    41

    40

    Page 26

  • Providing and fixing precast chequered cement concrete tiles 22 mm thick, laid in footpath & courtyard, on 20 mm thick bed of cement mortar 1 : 4 ( 1 cement : 4 fine sand ) jointed with neat cement slurry mixed with pigment to match the shade of tiles including rubbing and polishing complete.

    In dark shade using ordinary cement 35.00 sqm

    43 Providing and fixing 1st quality ceramic glazed wall tiles conforming to IS : 15622 ( thickness to be specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-charge in skirting, risers of steps and dados over 12 mm thick bed of cement mortar 1 : 3 ( 1 cement : 3 fine sand ) jointed with ordinary cement slurry including pointing with white cement mixed with pigment of matching shade complete.

    175.00 sqm

    44 Providing and laying 1st quality ceramic glazed floor tiles 300 x 300 mm conforming to IS : 15622 ( thickness to be specified by the manufacturer ) of approved make in colours, shades such as white, ivory, grey, fume red, brown over 20 mm thick bed of cement mortar 1 : 4 ( 1 cement : 4 fine sand ) jointed with ordinary cement slurry including pointing with white cement mixed with pigment of matching shade complete.

    80.00 sqm

    Providing and fixingr Kota stone in floors over 20 mm thick bed of cement mortar 1 : 4 ( 1 cement : 4 fine sand ) jointed with ordinary cement slurry including pointing with ordinary cement mixed with pigment of matching shade, including rubbing and polishing complete.

    Kota stone slab 30mm thick 130.00 sqm

    45

    42

    Page 27

  • Providing and laying 40 mm. thick marble chips flooring rubbed and polished to granolithick finish under layer 34 mm. thick cement concrete 1:2:4 ( 1 ordinary cement: 2 fine sand: 4 graded stone aggregate 12.5 mm.size) and top layer 6 mm. thick with white, black, chocolate , grey, yellow, pink, blue or green marble chips from 1 mm. to 4 mm. nominal size laid in cement marble powder mix 3:1( 1 cement: 1 marble powder) by weight in proportion of 4: 7(4 cement marble powder mix: 7 marble chips) by volume including cement slurry etc. complete

    Using light shade pigment with ordinary cement in top layer160.00 sqm

    Providing and laying 40 mm. marble chips skirting( upto 300 mm. height) rubbed and polished to granolithick finish, top layer 6 mm. thick with white, black, chocolate , grey, yellow, pink, blue or green marble chips of sizes from 1 mm. to 4 mm. nominal sizes laid in cement marble powder mix 3:1( 1 cement: 1 marble powder) by weight in proportion of 4: 7(4 cement marble powder mix: 7 marble chips) by volume including cement slurry etc. complete.

    Using light shade pigment with ordinary cement in top layer

    20.00 sqm.

    SUBHEAD-ALUMINIUM WORK

    46

    47

    Page 28

  • Providing and fixing aluminium work for doors, windows, ventilators, stair railing including hand rail and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS : 1285, fixed with rawl plugs and screws or with fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at top, bottom and sides with required PVC/neoprene felt etc. aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, aluminium snap beading for glazing / paneling, C.P. brass / stainless steel screws, all complete as per architectural drawing and the direction of Engineer-in-charge. (Glazing and paneling to be paid for separately) :-

    For fixed portion of approved quality:-

    Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15). 90.00 Kg.

    49 For shutters/ sliding shutters of doors, windows & ventilators including providing and fixing hinges / pivots / rollers and making provision for fixing fittings wherever required including the cost of PVC / neoprene gasket required of approved quality ( Fittings shall be paid for separately ):-

    Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15). 450 Kg.

    48

    Page 29

  • Providing and fixing glazing of approved quality in aluminium doors, windows, ventilator, shutters and partition frames with PVC / neoprene gasket etc. complete as per architectural drawing and the direction of Engineer-in-charge :-

    With glass/ float glass panes of 5.5 m thickness ( weight not less than 13.50 kg / sqm ) 92.00 Sqm.

    With glass/ float glass panes of 4.0 m thickness ( weight not less than 10.0 kg / sqm ) 17.40 Sqm.

    Providing and fixing double action hydraulic floor spring of approved brand and manufacture ( conforming to IS : 6315 ) for aluminium doors including cost of cutting floors as required, embedding in floors and cover plates etc. complete as per direction of the Engineer-in-charge:-

    With stainless steel cover plate. 1 Each

    Providing and fixing aluminium work consisting of tee / angle sections, of approved make conforming to IS : 733 in frames of false ceiling including aluminium angle cleats with necessary C.P. brass / stainless steel sunk screws, aluminium perimeter angles fixed to wall with rawl plugs @ 450 mm centre to centre and fixing the frame work to 6 mm dia G.I. level adjusting hangers with necessary cadmium plated machine screws all complete as per architectural drawing and the direction of Engineer-in-charge ( level adjusting hangers, ceiling cleats and expansion hold fasteners to be paid for separately ):-

    Anodised aluminium (anodised transparent or dyed to required shade according to IS : 1868 , minimum anodic coating of grade AC 15 ). 8.75 Kg.

    52

    50

    51

    Page 30

  • 53 Providing and filling the gap in between aluminium frame and adjacent RCC / brick work by providing weather silicon sealant over backer rod of approved quality etc. complete as per architectural drawing and direction of the Engineer-in charge:- (i) Upto 5 mm depth and 5 mm width.

    50.00 Metre

    Providing and fixing 12 mm thick prelaminated three layer medium density (exterior grade ) particle board grade-I, type II conforming to IS : 12823 bonded with phenol formaldehyde synthetic resin, of approved brand and manufacture in panelling fixed in aluminium doors, windows, shutters and partition frames with C.P. brass / stainless steel screws all complete as per architectural drawing and the direction of Engineer-in-charge :-

    Prelaminated particle board of approved quality with decorative lamination on both side. 12.00 Sqm.

    Providing and fixing aluminium casement windows fastener of required length for aluminium windows with necessary screws etc. of approved quality complete as per direction of Engineer-in-charge:-

    Anodised aluminium of grade AC 15 ). 10 Each

    Providing and fixing aluminium tubular handle bar of 32 mm outer dia, 3.0 mm thick and 2100 mm long with Stainless Steel screws etc. of approved quality complete as per direction of Engineer-in-charge:-

    Anodised aluminium of grade AC 15 ). 5 Each

    57 Providing and fixing 100 mm brass locks ( best make of approved quality ) with 6 levers without pair of handles for aluminium doors including necessary cutting and making good etc. complete as per direction of Engineer-in-charge.

    5 Each

    SUBHEAD- ROOFING WORK

    56

    54

    55

    Page 31

  • Providing and fixing on wall face unplasticised Rigid PVC rain water pipes (working pressure 4 kg / cm2) conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion:

    Single socketed pipe - 110 mm OD 90.00 m

    Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A including jointing with seal ring conforming to IS : 5382 leaving 10 mm gap for thermal expansion:

    Coupler

    110 mm 15 each

    Bend 87.5°

    110mm 20 each

    Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes by means of 50x50x50mm hard wood plugs, screwed with M.S. screws of required length including cutting brick work and fixing with cement mortar 1 : 4 (1cement : 4 fine sand) making good the wall etc. complete.

    110mm 60 each

    SUBHEAD- FINISHING WORK

    12 mm cement plaster in single layer including cost of materials required and finishing even and smooth and curing complete.

    In cement mortar 1 : 4 ( 1 cement : 4 fine sand ) 1840.00 sqm

    15 mm cement plaster in single layer including cost of materials required and finishing even and smooth and curing complete.

    In cement mortar 1 : 4 ( 1 cement : 4 fine sand ) 950.00 sqm

    62

    60

    61

    58

    59

    Page 32

  • 6 mm cement plaster in single layer including cost of materials required and finishing even and smooth and curing complete.

    In cement mortar 1 : 3 ( 1 cement : 3 fine sand ) 540.00 sqm

    64 Neat cement punning. 280.00 sqm

    65 Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers. 50.00 kg

    66 Providing and applying plaster of paris putty of 2 mm thickness over plastered surface to prepare the surface even and smooth complete. 1210.00 sqm

    67 Applying one coat of cement primer of approved brand and manufacturer on wall surface complete. 1350.00 sqm

    68 Finishing walls with premium acrylic smooth exterior paint of required shade of approved brand and manufacture on new work ( two or more coats applied @ 1.43 kg/10 sqm ) over and including base coat water proofing cement paint applied @ 2.20 kg/10 sqm complete.

    860.00 sqm

    Applying priming coat:

    With ready mixed pink primer of approved brand and manufacture on wood work ( hard & soft wood ). 25.00 sqm

    With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel, galvanised iron / steel work.

    120.00 sqm

    Finishing with epoxy paint ( two or more coats ) of approved brand and manufacture at all locations prepared and applied as per manufacturer's specification on new work including appropriate priming coat, preparation of surface etc. complete.

    On steel work 80.00 sqm

    69

    70

    63

    Page 33

  • 71 Wall painting with plastic emulsion paint ( two or more coats ) of required colour of approved brand and manufacture on new work to give an even shade. 1450.00 sqm

    72 Painting with black anticorrosive bitumastic paint ( two or more coats ) of approved brand and manufacture on new work to give an even shade. 35.40 sqm

    SUBHEAD- SANITARY WORK

    Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete including cutting and making good the walls and floors wherever required :

    White Vitreous china Orrisa pattern W.C. pan of size 580x440 mm with integral type foot rests. 8 eachProviding and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete including cutting and making good the walls and floors wherever required :

    W.C. pan with ISI marked white solid plastic seat and lid 4 eachFixing white vitreous china flat back half stall urinal of size 580x380x350mm with white PVC automatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps (all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P. brass including painting of fittings and cutting and making good the walls and floors wherever required :

    73

    74

    75

    Page 34

  • Single half stall urinal with 5 litre P.V.C. automatic flushing cistern. 8 eachProviding and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps,32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require :

    White Vitreous China Wash basin size 630x450 mm with a single 15 mm C.P. brass pillar taps. 6 each

    77 Providing and fixing white vitreous china pedestal for wash basin completely recessed at the back for the reception of pipes and fittings. 6 eachProviding and fixing P.V.C. waste pipe for sink or wash basin including P.V.C. waste fittings complete.

    Flexible pipe

    32 mm dia 12 each79 Providing and fixing 100 mm sand cast Iron grating for gully

    trap. 6 each80 Providing and fixing 600x450 mm bevelled edge mirror of

    superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.

    8 each81 Providing and fixing 600x120x5mm glass shelf with edges

    round of supported on anodised aluminium angle frame with C.P. brass brackets and guard rail complete fixed with 40 mm long screws, rawl plugs etc., complete.

    8 eachProviding and fixing terminal guard:

    100 mm

    Sand cast iron S&S as per IS - 3989 6 each

    76

    78

    82

    Page 35

  • Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved 450mm long towel rail with total length of 495mm, 78mm wide and effective height quality and colour.

    600mm long towel rail with total length of 645mm, width 78mm and effective height of 88mm, weighing not less than 190gms.

    8 each84 Providing and fixing PTMT liquid soap container 109mm wide,

    125mm high and 112mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colours weighing not less than 105 gms

    8 eachProviding, fixing and laying rigid UPVC pipes conforming to IS :4985 jointing with couplers, of same class conforming to IS : 10124 ( Pt-II ) with solvent cement conforming to IS : 14182 including testing of joints complete ( but excluding the cost of specials like bend, tees etc. which will be paid separately ) as per chapter 20 of CPWD specification and direction of the Engineer - in - charge.

    Class - 3 ( working pressure 6.0 kg / cm2)

    90 mm OD 52.00 Metre110 mm OD 85.00 MetreProviding, fixing and laying fabricated UPVC bend of required degree conforming to IS : 10124 ( part 8 / 9 / 10 / 11 / 12 / 13 ) with solvent cement conforming to IS : 14182 including testing of joints complete as per chapter 20 of CPWD specification and direction of the Engineer - in - charge.

    90 mm OD 20 No110 mm OD 15 No

    85

    86

    83

    Page 36

  • Providing, fixing and laying fabricated UPVC equal tee conforming to IS : 10124 ( Part 5 ) with solvent cement conforming to IS : 14182 including testing of joints complete as per chapter 20 of CPWD specification and direction of the Engineer - in - charge.

    90 x 90 mm dia 7 No110 x 110 mm dia 12 NoProviding, fixing and laying fabricated UPVC end cap conforming toIS : 10124 ( Part 4 ) with solvent cement conforming to IS : 14182 including testing of joints complete as per chapter 20 of CPWD specification and direction of the Engineer - in - charge.

    90 x 90 mm dia 3 No110 x 110 mm dia 2 NoSUBHEAD- WATER SUPPLY INSTALLATION

    Providing and fixing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc.

    Internal work - Exposed on wall.

    15 mm dia. nominal bore 60.00 metre20 mm dia. nominal bore 55.00 metreProviding and fixing G.I. pipes complete with G.I. fittings including trenching and refilling etc.

    External work

    25 mm dia. nominal bore 20.00 metre40 mm dia. nominal bore 50.00 metreMaking connection of G.I. distribution branch with G.I. main of following sizes by providing and fixing tee, including cutting and threading the pipe etc. complete :

    25 to 40 mm nominal bore 2 each92 Making chases upto 7.5x7.5 cm in wails including making

    good and finishing with matching surface after housing G.I. pipe etc. 15.00 metre

    87

    88

    89

    90

    91

    Page 37

  • 93 Providing and placing on terrace (at all floor levels) polyethylene water storage tank ISI : 12701 marked with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank.(1000 litre capacity)x4 nos.

    4000 per litre

    Providing and fixing C.P. brass bib cock of approved quality conforming to IS:8931

    15 mm nominal bore 12 eachProviding and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.

    15mm nominal bore. 8 eachProviding and fixing C.P. brass stop cock (concealed) of standard design and of approved make conforming to IS:8931.

    15 mm nominal bore. 12 eachProviding and fixing ball valve (brass) of approved quality complete :

    15 mm nominal bore 6 each20 mm nominal bore 9 each25 mm nominal bore 3 eachProviding and fixing gun metal gate valve with C.I. wheel of approved quality (screwed end):

    40 mm nominal bore 1 each99 Providing and fixing gun metal non-return valve of approved

    quality (screwed end):

    Vertical

    40 mm nominal bore 2 eachProviding and fixing uplasticised PVC connection pipe with brass unions :

    45 cm length

    15 mm nominal bore 6 each

    101

    100

    94

    95

    96

    98

    97

    Page 38

  • Providing and fixing G.I. Union in G.I. pipe including cutting and threading the pipe and making long screws etc. complete (New work)

    15 mm nominal bore 8 each20 mm nominal bore 8 each25 mm nominal bore 2 each40 mm nominal bore 2 eachProviding and fixing PTMT grating of approved quality and colour.

    Circular type.

    100 mm nominal dia. 6 eachSUBHEAD- SEWERAGE & DRAINAGE WORK

    Constructing brick masonry chamber for underground C.I. inspection chamber and bends with 1st class bricks in cement mortar 1:4 (1 cement : 4 fine sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover with frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) R.C.C. top slab with 1:2:4 mix (1 cement :2 fine sand : 4 graded stone aggregate 20 mm nominal size) foundation concrete 1:5:10 (1 cement: 5 fine sand : 10 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement: 3 fine sand) finished smooth with a floating coat of neat cement on walls and bed concrete etc. complete as per standard design :

    Inside dimensions 455x610 mm and 45 cm deep for single pipe line : 3 No

    Inside dimensions 500x700 mm and 45 cm deep for pipe line with one or two inlets : 1 No

    Supplying and fixing C.I. cover without frame for manholes :105

    104

    102

    103

    Page 39

  • 500 mm diameter C.I. cover (medium duty) the weight of the cover to be not less than 58 kg. 2 No

    SCHEDULE -DR.C.C. FRAMED BOUNDARY WALL

    Total Length of Boumdary Wall = 180.00 Meter.

    Earth work in excavation over areas (exceeding 30cm in depth, 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed.

    -All kinds of soil

    By manual means 100.00 cum

    Earth work in excavation in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.

    -All kinds of soil

    By manual means 137.40 cum

    Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.

    -All kinds of soil 91.60 cum

    4 Supplying and filling in plinth, under floor, foundations etc. with sand (fine) from local quarry with all lifts including spreading in horizontal layers, watering, grading to required slope, ramming, consolidating and compacting each layer by using plate compactor or by any suitable method complete.

    13.50 cum

    1

    2

    3

    Page 40

  • SUBHEAD-CEMENT CONCRETE WORKS

    Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering -

    -All work upto plinth level:

    1:4:8 ( 1 Cement: 4 fine sand : 8 graded stone aggregate 40 mm nominal size) 27.00 cum

    SUBHEAD-R.C.C WORK

    Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centring, shuttering, finishing and reinforcement-

    -All work upto plinth level:

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 19.75 cum

    Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and skirting courses, fillets, columns, pillars, piers, abutments, posts and struts etc. upto floor five level excluding cost of centring, shuttering, finishing and reinforcement-

    In walls (any thickness), including attached pilasters, buttresses, piers, abutments etc.

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 4.75 cum

    In plinth and skirting courses, fillets, columns, pillars, posts and struts

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 15.30 cum

    5

    6

    7

    Page 41

  • Reinforced cement concrete work in beams, suspended floors, roofs having slope upto 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases upto floor five level excluding the cost of centring, shuttering, finishing and reinforcement-

    RCC work in beams, lintels, bands, plain window sills, staircases and spiral staircases excluding precast spiral staircase.

    1:1½:3 ( 1 Cement: 1½ fine sand : 3 graded stone aggregate 20 mm nominal size) 20.435 cum

    Centering shuttering including struttings, propping etc. and removal of form work for:

    Foundations, footings, bases for columns etc. for mass concrete with timber plank 45.00 sqm

    Walls (any thickness) including attached pilasters, buttresses, plinth and string courses etc. using shuttering ply

    36.00 sqm

    Lintels, beams, plinth beams, girders, bressumers and cantilevers with shuttering ply 166.50 sqm

    Columns, Pillars, Piers, Abutments, Posts and Struts with shuttering ply 240.60 sqm

    Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto floor five level.

    Thermo-Mechanically Treated bars/ Cold twisted deformed steel bars 5525.00 kg

    SUBHEAD- BRICK WORK

    First class brick work in foundation and plinth including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 15.35 Cum.

    8

    9

    10

    11

    Page 42

  • Half brick masonry work with first class bricks in superstructure upto floor five level including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 245.00 Sqm.

    Extra for providing & placing in position 2 nos 6mm dia MS bars at every 4th course of half brick masonry work including anchorage in joints of 75mm in each side in superstructure for all level including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 245.00 Sqm.

    SUBHEAD- STEEL WORK

    Steel work welded in built up section/framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using steel etc. complete as required:-

    In grating, frames, guard bar, railing, brackets, gates and similar works, all complete. 765.00 Kg.

    Providing and fixing M.S. grills of required pattern in frames of windows etc. with M.S. flats, square or round bars etc. all complete.

    Fixed to openings /wooden frames with rawl plugs screws etc.2430.00 Kg

    SUBHEAD- FINISHING WORK

    12 mm cement plaster in single layer including cost of materials required and finishing even and smooth and curing complete.

    In cement mortar 1 : 4 ( 1 cement : 4 fine sand ) 405.00 sqm

    15 mm cement plaster in single layer including cost of materials required and finishing even and smooth and curing complete.

    In cement mortar 1 : 4 ( 1 cement : 4 fine sand ) 405.00 sqm

    18 Neat cement punning. 144.00 sqm

    12

    14

    15

    16

    17

    13

    Page 43

  • 19 Applying one coat of cement primer of approved brand and manufacturer on wall surface complete. 810.00 sqm

    Applying priming coat:

    With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel, galvanised iron / steel work.

    135.00 sqm

    21 Finishing walls with acrylic smooth exterior paint of required shade of approved brand and manufacture on new work ( two or more coats applied @ 1.67 kg/10 sqm ) over and including base coat water proofing cement paint applied @ 2.20 kg/10 sqm complete.

    810.00 sqm

    Finishing with epoxy paint ( two or more coats ) of approved brand and manufacture at all locations prepared and applied as per manufacturer's specification on new work including appropriate priming coat, preparation of surface etc. complete.

    On steel work 135.00 sqm

    SCHEDULE -ESWITCH YARD (EQUIPMENT FOUNDATION)

    Earth work in excavation over areas (exceeding 30cm in depth, 1.5m in width as well as 10 sqm on plan) including disposal of excavated earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly dressed.

    -All kinds of soil

    By manual means 1260.00 cum

    Earth work in excavation in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.

    20

    22

    1

    2

    Page 44

  • -All kinds of soil

    By manual means 315.00 cum

    Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.

    -All kinds of soil 185.00 cum

    SUBHEAD-CEMENT CONCRETE WORKS

    Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering -

    -All work upto plinth level:

    1:4:8 ( 1 Cement: 4 fine sand : 8 graded stone aggregate 40 mm nominal size) 88.25 cum

    1:2:4 ( 1 Cement: 2 fine sand : 4 graded well burnt brick aggregate 40 mm nominal size) 65.00 cum

    SUBHEAD-R.C.C WORK

    Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centring, shuttering, finishing and reinforcement-

    -All work upto plinth level:

    1:2:4 ( 1 Cement: 2 fine sand : 4 graded stone aggregate 20 mm nominal size) 105.35 cum

    Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and skirting courses, fillets, columns, pillars, piers, abutments, posts and struts etc. upto floor five level excluding cost of centring, shuttering, finishing and reinforcement-

    In walls (any thickness), including attached pilasters, buttresses, piers, abutments etc.

    3

    4

    5

    6

    Page 45

  • 1:2:4 ( 1 Cement: 2 fine sand : 4 graded stone aggregate 20 mm nominal size) 2.75 cum

    In plinth and skirting courses, fillets, columns, pillars, posts and struts

    1:2:4 ( 1 Cement: 2 fine sand : 4 graded stone aggregate 20 mm nominal size) 1.62 cum

    7 Providing, hoisting and fixing upto floor five level precast reinforced cement concrete work in shelves including setting in cement mortar 1:3(1cement : 3 fine sand), cost of required centring, shuttering, finishing with neat cement punning on exposed surfaces complete, but excluding cost of reinforcement with cement concrete 1:2:4 (1cement : 2 fine sand : 4 graded stone aggregate 20mm nominal size).

    10.50 cum

    Centering shuttering including struttings, propping etc. and removal of form work for:

    Foundations, footings, bases for columns etc. for mass concrete with timber plank 350.85 sqm

    Walls (any thickness) including attached pilasters, buttresses, plinth and string courses etc. using shuttering ply

    23.00 sqm

    Columns, Pillars, Piers, Abutments, Posts and Struts with shuttering ply 21.60 sqm

    Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto floor five level.

    Thermo-Mechanically Treated bars/ Cold twisted deformed steel bars 6725.00 kg

    SUBHEAD- BRICK WORK

    First class brick work in foundation and plinth including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 85.00 Cum.

    10

    9

    8

    Page 46

  • Half brick masonry work with first class bricks in foundation and plinth including cost of all materials as required complete:-

    In cement mortar 1:4 ( 1 cement : 4 fine sand ). 30.00 Sqm.

    SUBHEAD- STEEL WORK

    12 Providing structural steel work in single section fixed with or without connecting plate including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete as required. 400.00 Kg.

    Steel work welded in built up section/framed work including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using steel etc. complete as required:-

    In grating, frames, guard bar, railing, brackets, gates and similar works, all complete. 600.00 Kg.

    14 Providing 1.8 mtr height chain link fenching around sub-station areas with angle post 65 x 65 x 6 mm placed every 2.5 mtr. Apart embeded in cement concrete block of 1:3:6( 1 cement:3 river sand:6 jhama bricks aggrigate 20 mm nominal size) and every 12th post corner post to be shurtted and embeded in cement concrete of 45 x 45 x 60 mm of same mix both post should be fitted with GI stapple of M.S.flat of 50 x 6 mm .Two sutaible gates made of 50 mm dia GI pipe and chain link are to be provided within sub-station fenching (width of gate shall be 4.00 mtr. and height 1.80 mtr. and 2nd gate of 1.20 mtr. width 1.80 mtr height.

    140.00 Mtr.

    SUBHEAD- FINISHING WORK

    12 mm cement plaster in single layer including cost of materials required and finishing even and smooth and curing complete.

    In cement mortar 1 : 4 ( 1 cement : 4 fine sand ) 790.00 sqm

    11

    13

    15

    Page 47

  • 16 Neat cement punning. 790.00 sqm

    17 Applying one coat of cement primer of approved brand and manufacturer on wall surface complete. 19.20 sqm

    Applying priming coat:

    With ready mixed red oxide zinc chromate primer of approved brand and manufacture on steel, galvanised iron / steel work.

    46.08 sqm

    19 Finishing walls with acrylic smooth exterior paint of required shade of approved brand and manufacture on new work ( two or more coats applied @ 1.67 kg/10 sqm ) over and including base coat water proofing cement paint applied @ 2.20 kg/10 sqm complete.

    19.20 sqm

    Finishing with epoxy paint ( two or more coats ) of approved brand and manufacture at all locations prepared and applied as per manufacturer's specification on new work including appropriate priming coat, preparation of surface etc. complete.

    On steel work 46.08 sqm

    SCHEDULE -F (Internal electrification of control room building)

    Supplying and fixing of PVC casing and capping in/c. all accessories as required (Make : - Presto - plast / Precision) a) 25 mm X 10 mm. 180 Mtr. b) 40 mm X 20 mm. 60 Mtr. Supplying and drawing of PVC insulated copper conductor cable in existing PVC casing -capping / conduit in/c. necessary connection as required. (Make: - Havell's / National / Plaza.) a) 2 X 1.5 Sq. mm. 400 Mtr. b) 2 X 4 Sq. mm. 150 Mtr. c) 2 X 6 Sq. mm. 70 Mtr.

    20

    1

    2

    18

    Page 48

  • Supplying and fixing of accessories for PVC casing and capping in/c. necessary connection as required. Make: - Anchor / Precision / Cona (Nice) / SSK / J.J. Deluxe (Fancy). a) Ceiling rose. 62 No. b) Angle lamp holder. 24 No. c) 5/6 Amp. piano switch. 102 No. d) 5/6 Amp. socket. 16 No. e) 15/16 Amp.piano switch. 8 No. f) 15/16 Amp. 5 pin socket. 8 No.

    g) Ding dong call bell. 3 No.

    4

    Supplying and fixing of 415 volt, 63 amp. TPN main switch (Rewireable) front handle in/c. drilling holes on wooden board and connection as required. (Make: - Havells / HPL / Standard).

    2 No.

    5

    Supplying and fixing of 6 ways metal enclosure for 240/415 Volts MCB (SP/SPN/DP/FP) complete with necessary bus bar, earth bar, neutral link etc. including connection as required. (Make: - Havells / HPL / Standard).

    2 No.

    6

    Supplying and fixing of 5 to 32 Amps. rating 240 Volts 'G' Series MCB of single pole in the existing MCB DB complete with connection etc. as required. (Make: - Havells / HPL / Standard).

    10 No.

    7 Providing earthing with 40 mm dia. GI perforated pipe of 4.5 mtr. long with masonary enclosure on top etc. as required.

    2 No.

    8 Extra for using salt and charcoal for pipe earth elctrode as required.

    2 Set.

    9 Providing and fixing 8 swg GI wire on surface or in conduit pipe for loop earthing.

    20 Mtr.

    3

    Page 49

  • 10 Providing and laying earth connection from earth electrode with 8 swg GI wire / copper wire in 15 mm dia. G.I. pipe from earth electrode as required.

    24 Mtr.

    11 Supplying and drawing of 4 sq. mm. aluminium conductor wire for loop earthing including connection as required.

    300 Mtr.

    12

    Supplying and fixing of single box type FTL fittings complete with 1 no. 40 / 36 watt copper ballast, 40/36 watt flurosent tube, starter, holder, pf improving capacitor etc. in/c. connection as required. (Make: - Phillips / Crompton / Bajaj).

    20 No.

    13

    Supplying and fixing of double box type T 5 rated energy efficent FTL fittings complete with 2 nos. 40 / 36 watt copper ballast, 2 nos. 40/36 watt flurosent tube, starter, holder, pf improving capacitor etc. in/c. connection as required. (Make: - Phillips / Crompton / Bajaj).

    8 No.

    14 Supplying and fixing of ceilling luminaries with 2 nos. PLS 11 Watt lamp and mirror optics including necessary connection as required. (Make: - Phillips, Cat no.-FCS - 31 / 211).

    2 No.

    Supplying and fixing of accessories for PVC casing and capping in/c. necessary connection as required.

    a) 102 mm X 102 mm, size wooden formica board with bakelite cover.

    30 No.

    b) 102 mm X 178 mm, size wooden formica board with 8 No. c) 152 mm X 203 mm, size wooden formica board with bakelite cover.

    4 No.

    d) 203 mm X 300 mm, size wooden formica board with bakelite cover.

    6 No.

    e) 254 mm X 300 mm, size wooden formica board with bakelite cover.

    4 No.

    15

    Page 50

  • 16 Supplying and fixing of 300 mm sweep exhaust fan including necessary connection as required. (Make: - Crompton / Khaitan / USHA / Orient).

    8 No.

    17 Supplying and fixing of necessary shutter for 300 mm exhaust fan in the existing whole including necessary painting etc. as required.

    8 No.

    18

    Supplying and fixing of 1200 mm sweep ceilling fan including fixing of regulator and wiring in down rod of standard length etc. as required. (Make: - Crompton / Khaitan / Orient / USHA).

    24 No.

    19 Supplying and fixing of 18 watt CFL in the existing angle holder. (Make: - Phillips / Bajaj / Orpat.

    24 No.

    Page 51

    Schedule

    SCHEDULE OF WORK

    Name of work:- Design,Engineering,Manufacturing,Testing,Supply, installation,Erection & commissioning of 2 X 3.15 MVA, 33 / 11KV Substation complete with construction of Double storied control room cum office building,equipment foundation, boundary wall and Land developement at Jampaijala including Construction of approximately 7.0 CKM. 33 KV "Takarjala-Jampuijala" subTransmission line from Takarjala 33 KV Sub-Station.

    SCHEDULE - A (Supply , installation & commissioning of Sub-station equipment, control gear and structures)

    (Amount in Rs.)

    Sl No.Description of itemSupplyErectionInspection

    QuantityUnitRateAmountQuantityUnitRateAmountAmount of Supply Item

    1234567891011

    1.Supply, erection, testing & commissioning of 3.15 MVA, 33 / 11 KV Delta Star, copper wound, oil immersed, ONAN cooled outdoor type, 3Phase, 50Hz, step down power transformer with OFF load tap changer with taps ranging from +10% to -10% in steps of 2.5% each on HV winding with first filling of EHV grade insulating oil & complete with conservator tank, Buchholz relay, breather, winding & oil temperature meters housed in outdoor panel attached with the transformer complete as per relevant ISS..2No.2No.

    2.Supply, erection, testing & commissioning of 33 KV, 1000A, 750 MVA rupturing capacity, outdoor Vacuum Circuit Breaker complete with motor operated spring closing (Local / Remote) arrangement with all accessories including lattice support structure,foundation bolts,G.I. nuts & bolts,washers etc. as required and as per relevant ISS complete operative on 110V DC.

    33 KV outgoing for Takajala/Incoming at Jampuijala1No.1No.

    For Power Transformer2No.2No.

    3.Supply, erection, testing & commissioning of 33 KV, 800A, manually operated horizontal rotating type double break, triple pole Gang operated isolator complete with post insulator, arching horns, mechanical interlocking arrangement etc.as per relevant ISS.

    a) With earth switch.2No.2No.

    b) Without earth switch.6No.6No.

    4.Supply, erection, testing & commissioning of 33 KV Single Phase, outdoor type 3 Core C.T of ratio 100 / 1-1-1 Amp with suitable burden & class of accuracy complete with associated terminal box connecting link etc. as per relevant ISS and as required(For Transformer).6No.6No.

    5Supply, erection, testing & commissioning of 33 KV Single Phase, outdoor type 2 Core C.T of ratio 200 / 1-1 Amp with suitable burden & class of accuracy complete with associated terminal box connecting link etc. ( for 33 KV incoming feeder)3No.3No.

    6Supply, erection, testing & commissioning of 33 KV Single Phase , outdoor type P.T of ratio 33000V / √ 3 / 110V / √ 3 having suitable burden & class of accuracy as detailed herein after in technical specification and as per relevant ISS .3No.3No.

    7Supply, erection, testing & commissioning of 10KA, 30 KV, Station Valve type metal oxide heavy duty Lightning Surge Arrestor suitable for operation on 33KV Sytem conforming to ISI : 3070 (P-1) / 1974 and amendments thereafter and as required.12No.12No.

    8Supply, erection, testing & commissioning of 33 KV control & relay panel, simplex type complete with differential relay, 2-over current and 1- Earth fault combined relay, Auxiliary relay, 1- voltmeter, 3- ammeter, CT operated static trivector meter, internal panel wiring, simaphore for Vacuum Circuit breaker & isolator, Mimic bus diagram (Metal size 4mm thick X 10mm width).

    a) For 3.15 MVA, 33 / 11 KV Power transformers.4No.4No.

    b) For 33 KV outgoing/incoming feeder without differential relay..4No.4No.

    9Supply , erection, testing & commisioning of 11 KV vaccum Circuit breaker with Control & relay panel (Incoming) simplex type 800 A contineous current rating,, 350 MVA rupturing capacity complete with manual and motorised spring closing mechanism ,electrical closing and opening arrangement and internal panel wiring with provisions of 2- overcurrent & 1- earth fault combined relay, auxilliary relays, 1- volt meter with selector switch, 3- ammeter, C.T. operated static trivector/ multi functional energy meter, 1- CT operated static KWH meter. Breaker capacity800 Amps continuous currentCTR 300 /1-1-0.577 Amp with panel top mounted P.T. of PTR 11KV / √3 / 110V / √3 with integral earthing facility and internal arc tested for transformer incoming panel as required and as per relevant ISS.2No.2No.

    1011 KV Vaccum Circuit breaker , Control & relay panel simplex type, 800 A continuous current 350 MVA rupturring capacity complete with electrical closing mechanism with internal wiring 2- overcurrent & 1- earth fault combined relay,. auxilliary relays,3- ammeter, 1-Volt Meter, C.T. operated static trivector meter/ Multi functional Energy meter. 1- CT operated static KWH meter with 3 sets of C.T. of Ratio 200 / 1-1 A with integral earthing facility and internal arc tested for11 KV out going feeders as per relevant ISS and as required..6No.5No.

    11Supply and Erection of Galvanised steel structure and Nuts & Bolts, spring washer etc as required for 33 KV Tower gangtry, Post Insulators and equipments

    a) Steel structure10.85MT10.85MT

    b) Nuts & bolts, spring washer and foundation bolts etc.1.8MT1.8MT

    12Supply, erection, testing & commissioning of sub- station busbar & stringing materials for 33 KV bus.

    a) ACSR (DOG) 7/1.57/6/4.72 mm (DOG ) conductor.0.5KM0.5KM

    b) 40mm dia. Al. pipe for equipment bus of current carrying capacity 400 Amps.300Mtr.300Mtr.

    c) 7/3.15mm earth wire for substation shielding.300Kg300Kg

    d) Ball & socket type 70 KN, 11KV disc Insulator.72Nos72No.

    e) Al. tension clamps. 3 -U bolt type, ball& socket type, suitable for70KN Disc Insulator and ACSR DOG conductor.24No.24No.

    f) 33 KV post insulator15No.15No.

    g ) Suspension Clamp suitable for ACSR, DOG Conductor.24No.24No.

    h)"T" Clamp suitable for ACSR DOG Conductor.15No.15No.

    i)"T" Clamp suitable for ACSR DOG Conductor in one end & 40mm dia. Al. tube in other end.15No.15No.

    j) Bimetalic clamps suitable for isolator, C.T, P.T., breaker, transformer& L.A. etc.27No.27No.

    1311 / 6.35(E) XLPE power cable

    a) 240 mm Sq. single core (for 3.15 MVA transformer connection).0.5Km.0.5Km

    b) 185 mm Sq. 3- core(for out going feeder)0.75Km.0.75Km

    14Outdoor type heat shrink joint kit for 11 KV XLPE cable of size :-

    a) 240 mm sq. single core7No.7No.

    b)185 mm sq. 3- core7No.7No.

    15Indoor type heat shrink jointing kit for II KV XLPE cable of size :-

    a ) 240 mm sq. single core7No.7No.

    b ) 185 mm sq. 3- core7No.7No.

    161100 V grade XLPE insulated & PVC sheathed armoured Al. cable of size, 70mm sq. 3½ Core cable.0.2Km0..1Km

    17Supply, laying, termination etc. of control cable 1100V, PVC insulated, PVC sheathed 2.5 mm sq copper conductor.

    a) 12-Core300Mtr.300Mtr.

    b) 7-Core300Mtr.300Mtr.

    c) 4-Core400Mtr.400Mtr.

    d) 2-Core300Mtr.300Mtr.

    18Supply of 40mm dia hot Dip perforated Heavy duty G.I pipe of length 3 mtr and providing earthing as per latest ISS: at 33 KV & 11KV switch yard including pair of GI clamps and nuts & bolts as required as per REC specification, drawing as stipulated herein after .18No.18No.

    19Supply and laying of GI flat 50 X 6 mm size for inter connection of earth electrodes and earthing terminals of equipments, structures including welding in joints as required for mesh earthing.300Mtr.300Mtr.

    20Supply & erection of 90 pound lb rail for transformer rail track.1.5MT.1.5MT.

    21Supply,Installation & commissioning of 110V, 240 AH capacity Sealed & Maintenance Free (SMF) Battery Bank comprising of 55 Nos.'Standby Valve Regulated Lead Acid (VRLA) Cells' of 2 Volt each (Average Discharge Voltage 1.90 VPC) as per specification in the Bidding / Tender Document.1Unit1Unit

    22Battery Charger with ±1% Digitally Controlled Regulation suitable for above 110 Volt VRLA Battery Bank with Float and Boost (FC & BC) charging arrangement with all Standard protections housed in free Standing Cabinet of 2.0 mm. gauge as per specification detailed in the Bidding / Tender Document.1Unit1Unit

    23Supply, erection, testing & commissioning of 110V D.C distribution panel made of sheet steel (14 SWG) and suitable for floor mounting. The distribution panel shall incorporate the following :-

    a) 1-No, 32 Amp. 110V Air break circuit breaker, Double pole for the battary incomming supply with red & green indicating lamps.1Unit1Unit

    b) 1-No earth leakage indicating lamp.

    c) 1-No ammeter (range 0-50 A).

    d) 1-No volt meter (Range 0-150 V).

    e) 4-Nos 16 Amps 110V double pole miniature Circuit breaker with over load protection for DC outgoing circuit . The unit will be complete with necessary internals wiring. Input & outgoing terminals, earthing, points & rating plate.

    24Supply, Erection, testing & commissioning of 433/450V, 3 Ph. 4 wire 50 Hz, AC distribution board enclosed in sheet steel (14 SWG) floor mounting type (vertical) comprising the following:-

    a) 200 Amp 3-Ph 4-wire , 415 V TPN switch fuse unit (HRC type) as incomming switch.1Unit1Unit

    b) 200 Amp 3-Ph. 4-wire , 415 V Al. bus bar having the following outgoing switch facilities.

    i) 100 Amp 415 V 3 ph. 4 wire switch (HRC- type): - 1 No.

    ii) 63 Amp 415 V 3 ph. 4 wire switch (rewireable type): - 2 Nos.

    iii) 32Amp 250 V 1 ph.2 wire switch (rewireable type): - 2 Nos.

    iv) 16Amp 250 V 1 ph.2 wire switch (rewireable type): - 3 Nos.

    c) AC voltmeter (Range 0- 500 V) with selector switch (RYB): - 1No.

    d) AC Ammeter (Range 0- 300 V) for (RYB) phase : - 3Nos.

    2511 KV outgoing bus bar materials

    a) 9 KV, 5 KA, single pole, Metal oxide gapless surge type LA suitable for nominal system voltage of 11 KV, 3-Ph., 50 Hz AC supply, creepage distance 600 mm. conforming to ISS: 3070 / 1985.21No.21No.

    b) 9 Mtr. Long steel tubular pole of designation 410- SP-31 conforming to ISS: 2713 / 1980 with base plate complete.12No.12No.

    c ) Steel materials (Angles & channels).1.2MT1.2MT

    d) 45 KN, 11KV disc insulator with 3 U Bolt type disc fittings.75No.75No.

    e ) 11 KV, 10 KN pin insulator including G.I. pin.60No.60No.

    f) 11 KV 3 pole GOS ( Air break type ) -400A.15No.15No.

    g) 11KV 3 pole DOF for station transformer 200A.1Set1Set

    h) Nuts & bolts assorted size300Kg300Kg

    i) 50X6 mm M.S flat for clamp250Kg250Kg

    j) ACSR (DOG ) 7/1.57/6/4.72 mm.0.3Km0.3Km

    26Supply & erection of fire fighting equipment with complete accessories .

    a) G.I bucket - 10 ltrs capacity with wooden / iron stand.6No.6No.

    b) Portable fire extinguisher using CO2 with pressure indicator: -5Kg.3No.3No.

    c) ABC powder fire extinguisher "Mono Ammonium phosphate".

    i) 5- Kg2No.2No.

    ii) 2- Kg2No.2No.

    27Supply, erection, testing & commissioning of 100 KVA, 11/0.43 KV, DY- 11 distribution transformer for station load.1No.1No.

    28Supply,fabrication,erection including grouting as required of 7.5 Mtr long GI support (heavy duty type) having bottom length 4.5 mtr. of dia 65 mm and upper length of 3 mtr. and 40 mm. dia. For Switchyard lighting.16No.16No.

    29Switchyard lighting complete with 250W, 230V, HPSV luminaries with switchgear complete with the support of item 28 including required wiring through the pipe and provision of control gear( MCB) for individual lantern / lamp as required and per direction of Engineer in charge .10Unit10Unit

    30Shock treatment chart (Laminated )2No.

    31Artificial respirator2No.

    32Rubber insulating mat at 15 KV tested of size (1X2) mtr.4No.

    33Oill filtration plant of capacity 250 G.P.H. (NIRMAL BRAND / John Fowler).1No.

    34a) Hand driven Insulation Tester 5KV (WACO make),10000 M-ohm minimum.1No.

    35a) Hand driven Insulation Tester 2.5KV (WACO make),10000 M-ohm minimum.1No.

    36Chain pully block ( 5 ton capacity )1No.

    37Pulling & lifting machine ( TIRFOR ) 5 ton / capacity.1No.

    38c) Digital clamp meter capable of measuring Various parameters(RMS values for Voltage & Current):AC Current 40/400Amps.AC Voltage: 600V, DC Voltage 600V, Resistance 40MegaOhm with LCD Display.Data Hold, Audible continuity, Diode Test, Over Range Indication,Low Battery Indication,etc. shall be avilable in the meter.etc.as per standard specification and perovisions.1No.

    39Complete Tool Box with Box Spanner (1 each of TAPARIA make product no. 1720, 1722, 1725, 1728 and 17301.1Set

    4015 KV grade hand gloves.4Pair

    41Taparia make Allen key set of 2 different range .2Set

    42Oil testing set with input volt 230 , 50 Hz single phase out put 0-100 KV I/C necessary accessories conforming releveant IS.1No.

    43TAPARIA make double ended spanner.1Set.

    44TAPARIA make ring rances.1Set.

    45TAPARIA make insulating screw driver.1Set.

    464-Point earth tester.1No.

    4733 KV discharge Rod of 3 section made of fibre glass tube complete with all accessaries as per specification.2Set

    48Crimping tool AAKASH-100