NDM1 SeriesNDB2 Series
Shanghai Liangxin Electrical CO.,LTDAddress: No. 668 Heng An Road, Pu Dong New District, Shanghai Post code: 200137Tel: 86-21-50412789Fax: 86-21-50410355E-mail: [email protected]
As standards, specifications and designs changefrom time to time, please ask for confirmationof the information given in this publication.
Be printed on ecological paper.
2010
- L
iang
xin
Elec
tric
al -
All
righ
ts r
eser
ved
Miniature Circuit Breaker
-
NDM1-63 Series Miniature Circuit BreakerNDM1-125 Series Miniature Circuit BreakerNDM1L Series Residual Current ModularNDM1LG Series Over Voltage Residual Current ModularNDB1 Series Miniature Circuit Breaker (1P+N)NDB1L Series Residual Current Circuit Breaker With Overload ProtectionNDB1LG Series Residual Current Circuit Breaker With Overload/Overvoltage ProtectionNDB2-63 Series Miniature Circuit Breaker NDB2T-63 Series Miniature Circuit Breaker NDB2-63K Series Miniature Circuit Breaker (1P+N)NDB2Z-63 Series DC Miniature Circuit Breaker NDB2LE Series Residual Current ModularNDG1 Series Disconnect Switch Tripping CurveTemperature DeratingNDA1 Series Modular SocketNDH1 Series BusbarNDH2 Series Busbar
030609121517192124272932363840414345
NDM1 SeriesNDB2 Series
Leading Low-voltage Electrical Component Manufacturer
Miniature Circuit Breaker
-
NDM1-63 Series Miniature Circuit Breaker
ND M 1 63
03 04
M Miniature Circuit Breaker
NDM1-63
1
63B, C, D
1, 2, 3, 4, 5, 6, 10, 16, 20, 25, 32, 40, 50, 63
1, 2, 3, 4
Model and Implication
IEC 60898-1, GB 10963.1;
TV, CE and CCC.
Application
Working Condition
DimensionCurve B: Non-inductive or micro-inductive loadsCurve C: Usual inductive loads
Curve D: Highly inductive loads
Overload and short circuit protection
Ambient temperature: -35+70
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Wiring Capacity
25mm2
Specifications
Rated working voltage: AC230/400V, DC60V
Rated working current: 1A - 63A
Mechanical life: 10000 times
Tripping characteristic: B: 3-5In; C: 5-10In; D: 10-14In
Breaking capacity:
Rated current(A) Voltage(V) Breaking capacity(kA)
BC: 1-40 AC230/400 6
5063 AC230/400 4.5
D : 1-40 AC230/400 4.5Product Features
Modularized
Screw clamp, shock-proof wiring terminals
Numerous accessories available
Standard 35mm Din Rail mounting
RoHS complied
Standards and Certificates
7
18 26.
5
18max
36max
54max
72max
1P
2P3P
4P
5.5
45.5
80.5
max
60
45
72.5max
Brand code
Product code
Design code
Frame rating (A)
Instantaneous tripping characteristic
Rated current (A)
Number of poles
No. Implication
-
05 06
1P
1
2
Number of PolesRated
Current(A)
1234561016202532405063123456101620253240506312345610162025324050631234561016202532405063
2P
1 3
2 4
Part No.
NDM1-63 1/1NDM1-63 2/1NDM1-63 3/1NDM1-63 4/1NDM1-63 5/1NDM1-63 6/1NDM1-63 10/1NDM1-63 16/1NDM1-63 20/1NDM1-63 25/1NDM1-63 32/1NDM1-63 40/1NDM1-63 50/1NDM1-63 63/1NDM1-63 1/2NDM1-63 2/2NDM1-63 3/2NDM1-63 4/2NDM1-63 5/2NDM1-63 6/2NDM1-63 10/2NDM1-63 16/2NDM1-63 20/2NDM1-63 25/2NDM1-63 32/2NDM1-63 40/2NDM1-63 50/2NDM1-63 63/2NDM1-63 1/3NDM1-63 2/3NDM1-63 3/3NDM1-63 4/3NDM1-63 5/3NDM1-63 6/3NDM1-63 10/3NDM1-63 16/3NDM1-63 20/3NDM1-63 25/3NDM1-63 32/3NDM1-63 40/3NDM1-63 50/3NDM1-63 63/3NDM1-63 1/4NDM1-63 2/4NDM1-63 3/4NDM1-63 4/4NDM1-63 5/4NDM1-63 6/4NDM1-63 10/4NDM1-63 16/4NDM1-63 20/4NDM1-63 25/4NDM1-63 32/4NDM1-63 40/4NDM1-63 50/4NDM1-63 63/4
Curve
B, C, D
B, C
B, C, D
B, C
B, C, D
B, C
B, C, D
B, C
Width(mm)
18
36
54
72
2 4 6
1 3
3P
5
1 3 5
4P
2
4 6 8
7
NDM1-125 Series Miniature Circuit Breaker
UL1077, IEC 60947-2, GB 14048.2;
UL, TV, CE, CCC.
Application
Curve C: Usual inductive loads
Curve D: Highly inductive loads
Overload and short circuit protection
Only Curve C available for 125A
Standards and Certificates
Working Condition
Ambient temperature: -35+70
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Specifications
Rated working voltage: AC230/400V, DC60V
Rated working current: 50A - 125A
Mechanical life: 10000 times
Rated impulse withstand voltage: 6kV
Tripping characteristic
C: 8In (20%) D: 12In (20%)
Breaking capacity:
Product Features
Modularized
Screw clamp, shock-proof wiring terminals
Numerous accessories available
Standard 35mm Din Rail mounting
RoHS complied
Wiring capacity
50mm2
ND M 1
M Miniature Circuit Breaker
NDM1-125
1
125
C, D
50, 63, 80, 100, 125
1, 2, 3, 4
Model and Implication
Brand code
Product code
Design code
Frame rating (A)
Instantaneous tripping characteristic
Rated current (A)
Number of poles
1257
50~125
50~125
Rated current(A)
1P
2~4P
Pole number
AC 230
AC230/400
Voltage (V)
10
10
Breakingcapacity(kA)
No. Implication
-
07 08
Number of Poles Width(mm)
27
54
81
108
Curve
C, D
C
C, D
C
C, D
C
C, D
C
Rated Current(A)
50
63
80
100
125
50
63
80
100
125
50
63
80
100
125
50
63
80
100
125
Part No.
NDM1-125 50/1
NDM1-125 63/1
NDM1-125 80/1
NDM1-125 100/1
NDM1-125 125/1
NDM1-125 50/2
NDM1-125 63/2
NDM1-125 80/2
NDM1-125 100/2
NDM1-125 125/2
NDM1-125 50/3
NDM1-125 63/3
NDM1-125 80/3
NDM1-125 100/3
NDM1-125 125/3
NDM1-125 50/4
NDM1-125 63/4
NDM1-125 80/4
NDM1-125 100/4
NDM1-125 125/4
DC Application
Wiring Schematics
Dimension
MCB rated current decided by the power of DC control circuit
According to DC rated voltage, there are several kinds of MCB cascade below
Revised feeding of line power is permitted
The estimated short circuit current can not exceed rated service short-circuit breaking capacity
1P
1
2
2P
1 3
2 4
Specification Rated Current (A)
3P
1 3 5
2 4 6
4P
1 3 5 7
2 4 6 8
DC60V One pole
DC125V Two poles
DC250V Four poles
DC rated service short-circuit breaking capacity (kA)
250V
NDM1-63
NDM1-125
1A~63A
50A~125A
60V
10 (1P)
20 (1P)
125V
20 (2P)
20 (2P)
50 (4P)
15 (4P)
NDM1-63
NDM1-125
1P
NDM1-63
NDM1-125
2P
NDM1-63
NDM1-125
4P
+ +- 60V - 125V
+- 250V
Load Load Load
108max
27max54max
81max
1P
16.5
26.5
5.549.5
60
45
85m
ax
74.5max2P3P4P
-
Brand code
Product code
Design code
Residual current protection
Frame rating (A)
Number of poles
Rated residual operating current (mA)
NDM1L Series Residual Current Modular
ND M 1 L
09 10
M Miniature Circuit Breaker
NDM1L
1
L
32, 50, 100
1PN, 2P, 3P, 3PN, 4P
30, 100
Model and Implication
NDM1L-32, NDM1L-50: IEC 61009-1, GB 16917.1; CCC.
NDM1L-100: IEC60947-2, GB14048.2; CCC.
Application
Working Condition
NDM1L-32 (50) Residual Current Modular
Dimension
Specifications
Clip onto the right side of NDM1 series MCB
Protection against earth leakage faults
Ambient temperature: -5 ~+40
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Wiring Capacity
NDM1L-32: 50mm2
NDM1L-50: 50mm2
NDM1L-100: 50mm2
Rated working voltage: AC230/400V (1PN2P)
AC400V (3P3PN4P)
Rated residual operating current: 30mA, 100mA
Release type: AC, electronic
Standards and Certificates
65 7
NDM1L-32, 50 NDM1L-100
Number of Poles Part No.
NDM1L-32/1PN
NDM1L-50/1PN
NDM1L-32/2
NDM1L-50/2
NDM1L-32/3
NDM1L-50/3
NDM1L-32/3PN
NDM1L-50/3PN
NDM1L-32/4
NDM1L-50/4
Frame Rating(A)
32
50
32
50
32
50
32
50
32
50
Rated ResidualOperating Current (mA)
30
30
30
30
30
30
30
30
30
30
Width (mm)
27
37
27
37
36
51
45
64
45
64
45
4060
5.5
69.5max
94m
ax
L
1PN2 N
N
1
3P2 4 6
1 3 5
3PN1 3 5
1 3 5 N
4P1 3 5 7
2 4 5 8
2P1 3
2 4
No. Implication
-
Brand code
Product code
Design code
Residual current protection
Over voltage protection
Frame rating (A)
Number of poles
Rated residual operating current (mA)
11 12
Release should be released before MCB dielectric test.
NDM1L-100 Series Residual Current Modular
Number of Poles Part No.
NDM1L-100/1PN
NDM1L-100/2
NDM1L-100/3
NDM1L-100/3PN
NDM1L-100/4
100
100
100
100
100
Frame Rating(A)
30, 100
30, 100
30, 100
30, 100
30, 100
Rated ResidualOperating Current (mA)
54
54
73
90
90
Width(mm)
1PN
3P
3PN
4P
2P1 3
2 4
NDM1LG Series Over Voltage Residual Modular
ND M 1 L G
8
M Miniature Circuit Breaker
NDM1LG
1
LG
32, 50
1PN, 2P
30, 100
Model and Implication
IEC 61009-1, GB 16917.1; CCC
Application
Clip onto the right side of NDM1 series MCB
Protection against earth leakage faults and overload
Standards and Certificates
7 8
Working Condition Dimension
Specifications
Ambient temperature: -5 ~+40
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Wiring Capacity
NDM1L-32: 10mm2
NDM1L-50: 25mm2
Rated working voltage: AC230/400V(1PN, 2P)
Over voltage limits: AC280V5%
Release type: AC, electronic
NDM1LG-32, 50
L
94m
ax
69.5max
5.5
6040
45
Rated residual operating current can be customized upon request, such as 6mA, 10mA, 100mA, etc.
Release should be used and ordered together with Nader MCB.
No. Implication
-
13 14
Release should be released before MCB dielectric test
NDM1LG-32 (50) Series Over Voltage Residual Current Modular
Match Principle
Number of Poles Part No.
NDM1LG-32/1PN
NDM1LG-50/1PN
NDM1LG-32/2
NDM1LG-50/2
Frame Rating(A)
32
50
32
50
Rated ResidualOperating Current (mA)
30
30
30
30
Width (mm)
27
37
27
37
1PN2 N
N
1
2P1 3
2 4
OF Auxiliary Switch
NDM1 Series MCB
NDM1-63
NDM1-125
1P
2P
3P
4P
NDM1L Series Residual Current Modular
1PN
2P
3P, 3PN
4P
NDM1L (G)-32 (1A-32A)
NDM1L (G)-50 (40A, 50A)
NDM1L-100 (50A, 63A, 80A, 100A)
Frame rating
Number of poles
ApplicationLinked to the left side of NDM1 seires MCB, to indicate the OPEN or CLOSED status of the associated breaker
Specifications
Current
AC
DC
DC
Voltage
230V
24V
125V
Current
6A
6A
1A
AC
DC
DC
Voltage
400V
48V
250V
3A
2A
0.4A
SD Alarm Switch
Wiring Capacity
Application Linked to the left side of NDM1 series MCB, to indicate the tripping status of the associated breaker
Specifications
AC
DC
DC
Voltage
230V
24V
125V
Current
6A
6A
1A
AC
DC
DC
Voltage
400V
48V
250V
Current
3A
2A
0.4A
Single line: 2.5mm2 Double line: 1.5mm2
IEC 60947-5, GB 14048.5;TV, CE, CCC.
Standards and Certificates
11
12 14
91
92 94
Rated residual operating current can be customized upon request, such as 6mA, 10mA, 100mA, etc.
Release should be used and ordered together with Nader MCB.
Width (mm): 9Notes:After clipping on to NDM1 series MCB,Point 11 and 14 are connected when circuit is closed;Point 11 and 12 are connected when circuit is open.May be used in conjunction with a SD alarm switch or another OF auxiliary switch.
Width (mm): 9
Notes:After clipping on to NDM1 series MCB,Point 91 and 92 are connected when circuit is closed;Point 91 and 94 are connected when the breaker trips due to fault;Point 91 and 92 are connected when the breaker trips by manual operation. Meanwhile, point 91 and 94 are disconnected.May be used in conjunction with a OF auxiliary switch or another SD alarm switch.
MX+OF Shunt ReleaseApplicationLinked to the right side of NDM1A series MCB.
Remote control
Specifications
Control voltage AC 230V/400V DC 24V/48V
Width (mm): 18
Active transfer contact
Note: At DC24V, above design of shunt control circuit is recommended
ZJ: DC24V intermediate relay
N or -
MCB closedMCB open
L or +
C2C1
14
12
SB
L1 L2 ZJ
DC24VA1 A2
Power input
ZJ
MX+OF K
-
16
Brand code
Product code
Design code
Frame rating (A)
Instantaneous tripping characteristic
Rated current (A)
NDB1 Series Miniature Circuit Breaker (1P+N)
ND B C1 32
15
B Miniature Circuit Breaker
NDB1-32
1
32
C
6, 10, 16, 20, 25, 32
Model and Implication
IEC 60898-1, GB 10963.1; CCC.
Application
Working Condition
Dimension
Specifications
TT/TN-S grounding system
Phase and neutral protection against short circuit and overload
Ambient temperature: -35+70
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration Wiring Capacity
10mm2
Product Features
Phase and neutral are both switched when circuit opens or trips because of failure
Phase connected early and disconnected late
Screw clamp, shock-proof wiring terminals
Standard 35mm Din Rail mounting
RoHS complied.
Rated working voltage: AC230V
Mechanical life: 10000 times
Tripping characteristic: C: 5-10In
Breaking capacity: 4.5kA
Standards and Certificates
Number of Poles Part No.
NDB1-32
NDB1-32
NDB1-32
NDB1-32
NDB1-32
NDB1-32
6
10
16
20
25
32
18
Width (mm)
C
Curve
6
10
16
20
25
32
Rated Current (A)
1P+N
6040
80m
ax
5.5
45
70.5max
18max
No. Implication
-
18
Brand code
Product code
Design code
Residual current protection
Frame rating
Instantaneous tripping characteristic
Rated current (A)
NDB1L Series Residual Current Circuit Breaker with Overload Protection
ND B C1 L 32
17
Model and Implication
UL1053, IEC61009-1, GB16917.1;
UL1053 (for NDB1L C10 30mA), TV, CE, CCC.
Application
Working Condition
Dimension
Specifications
TT/TN-S grounding system
Phase and neutral protection against short circuit, overload and earth leakage
Ambient temperature: -5+40
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Wiring Capacity
10mm2
Product Features
Phase and neutral are both switched when circuit opens or trips because of failure
Phase connected early and disconnected late
Screw clamp, shock-proof wiring terminals
Standard 35mm Din Rail mounting
RoHS complied
Rated working voltage: AC230
Mechanical life: 10000 times
Tripping characteristic: C: 5-10In
Rated residual operating current: 30mA
Breaking capacity: 4.5kA
Release type: AC, electronic type
Standards and Certificates
Number of Poles Part No.
NDB1L-32
NDB1L-32
NDB1L-32
NDB1L-32
NDB1L-32
NDB1L-32
6
10
16
20
25
32
36
Width (mm)
C
Curve
30
Rated ResidualOperating Current (A)
6
10
16
20
25
32
Rated Current(A)
7
B Miniature Circuit Breaker
NDB1L-32
1
L
32
C
6, 10, 16, 20, 25, 32
1P+N
T
36max40
45
78m
ax
N
NLOAD
LINE
68.5
70.3max
5.5
No. Implication
Rated residual operating current can be customized upon request, such as 6mA, 10mA, 100mA, etc.
-
20
Brand code
Product code
Design code
Residual current protection
Overvoltage protection
Frame rating (A)
Instantaneous tripping characteristic
Rated current (A)
NDB1LG Series Residual Current Circuit Breaker with Overload and Overvoltage Protection
ND B C1 L 32
19
Model and Implication
IEC 61009-1, GB 16917.1; CCC.
Application
Working Condition
Dimension
Specifications
TT/TN-S grounding system
Phase and neutral protection against short circuit, overload, earth leakage and overvoltage
Ambient temperature: -5+40
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Wiring Capacity
10mm2
Product Features
Phase and neutral are both switched when circuit opens or trips because of failure
Phase connected early and disconnected late
Screw clamp, shock-proof wiring terminals
Standard 35mm Din Rail mounting
RoHS complied
Rated working voltage: AC230
Mechanical life: 10000 times
Tripping characteristic: C: 5-10In
Rated residual operating current: 30mA
Breaking capacity: 4.5kA
Overvoltage: AC280V5%
Release type: AC, electronic type
Standards and Certificates
Number of Poles
36
Width (mm)
C
Curve
30
Rated ResidualOperating Current (A)
6
10
16
20
25
32
Rated Current(A)
8765
8
1P+N
T
36max40
45
78m
ax
N
NLOAD
LINE
68.5
70.3max
5.5
G Part No.
NDB1LG-32
NDB1LG-32
NDB1LG-32
NDB1LG-32
NDB1LG-32
NDB1LG-32
6
10
16
20
25
32
B Miniature Circuit Breaker
NDB1LG-32
1
L
G
32C
6, 10, 16, 20, 25, 32
No. Implication
Rated residual operating current can be customized upon request, such as 6mA, 10mA, 100mA, etc.
-
22
Brand code
Product code
Design code
Frame rating (A)
Instantaneous tripping characteristic
Rated current (A)
Number of poles
NDB2-63 Series Miniature Circuit Breaker
ND B 2 63
21
Model and Implication
UL1077, IEC60898-1, GB 10963.1;
UL1077, TV, CE, CB, CCC.
Application
Working Condition
Dimension
Specifications
Curve B: Non-inductive or micro-inductive loads
Curve C: Usual inductive loads
Curve D: Highly inductive loads
Overload and short circuit protection
Ambient temperature: -35+70
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Wiring Capacity
35mm2
Product Features
High breaking capacity
Modularized
Visual indicator
Screw clamp, shock-proof wiring terminals
Numerous accessories available
Standard 35mm Din Rail mounting
RoHS complied
Rated working voltage: AC230/400V, DC60V
Rated working current: 1A - 63A
Mechanical life: 20000 times
Tripping characteristic: B: 3-5In; C: 5-10In; D: 10-14In
Breaking capacity:
Standards and Certificates
Number of Poles
18
Width (mm)
BCD
Curve
1
2
4
6
10
16
20
25
32
40
50
63
B Miniature Circuit Breaker
NDB2-63
2
63
B, C, D
1, 2, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63
1, 2, 3, 4
7 Part No.
1/1
2/1
4/1
6/1
10/1
16/1
20/1
25/1
32/1
40/1
50/1
63/1
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
1P
2
1
18max
36max
54max
72max4P
3P
2P
1P
21
45
60
74max
5.5
45
81.5
1~63
Rated current(A)
Voltage (V) Breakingcapacity(kA)
AC230/400 10
No. Implication
RatedCurrent (A)
-
Brand code
Product code
Design code
Frame rating (A)
Instantaneous tripping characteristic
Rated current (A)
Number of poles
2423
Number of Poles Curve
B, C, D
B, C, D
B, C, D
Width(mm)
54
72
36
Part No.
1/2
2/2
4/2
6/2
10/2
16/2
20/2
25/2
32/2
40/2
50/2
63/2
1/3
2/3
4/3
6/3
10/3
16/3
20/3
25/3
32/3
40/3
50/3
63/3
1/4
2/4
4/4
6/4
10/4
16/4
20/4
25/4
32/4
40/4
50/4
63/4
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
NDB2-63
RatedCurrent (A)
1
2
4
6
10
16
20
25
32
40
50
63
1
2
4
6
10
16
20
25
32
40
50
63
1
2
4
6
10
16
20
25
32
40
50
63
1 3 5
2
3P
4 6
2P
2 4
1 3
NDB2T-63 Series Miniature Circuit Breaker
ND B 2T 63
Model and Implication
IEC60947-2, GB 14048.2; CCC
Application
Curve B: Non-inductive or micro-inductive loads
Curve C: Usual inductive loads
Curve D: Highly inductive loads
Overload and short circuit protection
Standards and Certificates
B Miniature Circuit Breaker
NDB2T-63
2T
63
B, C, D
1, 2, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63
1, 2, 3, 4
7
Working Condition Specifications
Ambient temperature: -35+70
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Wiring Capacity
35mm2
Product Features
High breaking capacity
Modularized
Visual indicator
Screw clamp, shock-proof wiring terminals
Numerous accessories available
Standard 35mm Din Rail mounting
RoHS complied
Rated working voltage: AC230/400V, DC60V
Rated working current: 1A - 63A
Mechanical life: 20000 times
Rated impulse withstand voltage: 6kV
Tripping characteristic:
B: 4In20%; C: 8In20%; D: 12In20%
Breaking capacity
1~63
Rated current(A)
Voltage (V) Breakingcapacity(kA)
AC230/400 10
4P
1 3 5 7
2 4 6 8
No. Implication
-
2625
Dimension
Number of Poles
18
Width(mm)
B, C, D
Curve
1
2
4
6
10
16
20
25
32
40
50
63
Rated Current(A) Part No.
1/1
2/1
4/1
6/1
10/1
16/1
20/1
25/1
32/1
40/1
50/1
63/1
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
1P
2
1
Number of Poles Curve
B, C, D
B, C, D
B, C, D
Width (mm)
36
54
72
Part No.
1/2
2/2
4/2
6/2
10/2
16/2
20/2
25/2
32/2
40/2
50/2
63/2
1/3
2/3
4/3
6/3
10/3
16/3
20/3
25/3
32/3
40/3
50/3
63/3
1/4
2/4
4/4
6/4
10/4
16/4
20/4
25/4
32/4
40/4
50/4
63/4
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
NDB2T-63
Rated Current (A)
1
2
4
6
10
16
20
25
32
40
50
63
1
2
4
6
10
16
20
25
32
40
50
63
1
2
4
6
10
16
20
25
32
40
50
63
1 3 5
2
3P
4 6
4P
1 3 5 7
2 4 6 8
2P
2 4
1 3
18max
36max
54max
72max4P
3P
2P
1P
21
4560
74max
5.5
45
81.5
-
28
Brand code
Product code
Design code
Frame rating (A)
Instantaneous tripping characteristic
Rated current (A)
Number of poles
NDB2-63K Series Miniature Circuit Breaker (1P+N)
ND B K C2 63
27
B Miniature Circuit Breaker
NDB2-63K
2
63
K
6, 10, 16, 20, 25, 32, 40, 50, 63
C
Model and Implication
IEC 60898-1, GB 10963.1; CCC
Application
Working Condition
Dimension
Specifications
TT/TN-S grounding system
Phase and neutral protection against short circuit and overload
Ambient temperature: -35+70
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibrationWiring Capacity
35mm2
Product Features
Phase and neutral are both switched when circuit opens or trips because of failure
Phase connected early and disconnected late
Screw clamp, shock-proof wiring terminals
Standard 35mm Din Rail mounting
Rated working voltage: AC230V
Mechanical life: 20000 times
Trip characteristic: C: 5-10In
Breaking capacity: 6kA
Standards and Certificates
Number of Poles Part No.
NDB2-63K
NDB2-63K
NDB2-63K
NDB2-63K
NDB2-63K
NDB2-63K
NDB2-63K
NDB2-63K
NDB2-63K
6
10
16
20
25
32
40
50
63
36
Width (mm)
C
Curve
6
10
16
20
25
32
40
50
63
Rated Current (A)
36max
74max
60
45
45
21
5.5
81.5
71P+N
No. Implication
-
30
Brand code
Product code
Design code
DC
Frame rating (A)
Instantaneous tripping characteristic
Rated current (A)
Number of poles
No.
NDB2Z-63 Series DC Miniature Circuit Breaker
ND B 2 Z 63
29
Model and Implication
UL1077, IEC60898-2, GB 10963.2;
UL1077, TV, CE, CB, CCC.
Application
Working Condition
Dimension
Specifications
Curve B: DC non-inductive or micro-inductive loads
Curve C: DC usual inductive loads
Overload and short circuit protection
Ambient temperature: -35~+70
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Wiring Capacity
35mm2
Product Features
High breaking capacity
Modularized
Visual indicator
Screw clamp, shock-proof wiring terminals
Numerous accessories available
Standard 35mm Din Rail mounting
RoHS complied
Mechanical life: 20000 times
Tripping characteristic: B: 4-7In; C: 7-15In
Standards and Certificates
Number of Poles
18
Width (mm)
B, C
Curve
7 8
8
B Miniature Circuit Breaker
NDB2Z-63
2
Z
63
B, C
1, 2, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63
1, 2
Pole number
1P
2P, 3P, 4P
1P
2P, 3P, 4P
1~63A
1~63A
Rated current(A)
DC125V
DC250V
DC220V
DC440V
Voltage (V)
10kA
6kA
Breakingcapacity (kA)
Part No.
NDB2Z-63 1/1
NDB2Z-63 2/1
NDB2Z-63 4/1
NDB2Z-63 6/1
NDB2Z-63 10/1
NDB2Z-63 16/1
NDB2Z-63 20/1
NDB2Z-63 25/1
NDB2Z-63 32/1
NDB2Z-63 40/1
NDB2Z-63 50/1
NDB2Z-63 63/1
Rated Current (A)
1
2
4
6
10
16
20
25
32
40
50
63
1P
1
2
36max
74max
60
45
45
21
5.5
81.5
Implication
-
Brand code
Product code
Design code
Residual current release
Electronic type
Frame rating (A)
Instantaneous tripping characteristic
Rated current (A)
Number of poles
32
NDB2LE Series Residual Current Modular
ND B 2 L
Model and Implication
IEC 61009-1, GB 16917.1;
TV, CE, CCC.
Application
Protection against earth leakage faults
Standards and Certificates
Dimension (With MCB)
E 63
89
B Miniature Circuit Breaker
NDB2LE
2
L
E
63
B, C, D
1, 2, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63
1PN, 2P, 3P, 3PN, 4P
987
Working Condition
1PN, 2P
Specifications
Ambient temperature: -5+40
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
RoHS complied
Wiring Capacity
35mm2
Rated working voltage: AC230V (1PN, 2P)
AC400V (3P, 3PN, 4P)
Rated residual operating current: 30mA(6mA, 10mA, 100mA, 300mA can be customized)
Release type: AC, electronic
31
Number of Poles Width (mm)
36
Part No.
Wiring Schametics
NDB2Z-63 1/2
NDB2Z-63 2/2
NDB2Z-63 4/2
NDB2Z-63 6/2
NDB2Z-63 10/2
NDB2Z-63 16/2
NDB2Z-63 20/2
NDB2Z-63 25/2
NDB2Z-63 32/2
NDB2Z-63 40/2
NDB2Z-63 50/2
NDB2Z-63 63/2
Rated Current (A)
1
2
4
6
10
16
20
25
32
40
50
63
2P
1 3
2 4
7254
2P
7560
45
45 90.5
1PN
1
2
L- L+
+-
L- L+
1 3
2
+ -
L+ L-
1 3
L- L+
L-L+
1 3
1
2
-+
+ 4
3
+-
L- L+M
1
2 + 4
3
L+ L- M
-+
+-
1P (A)
2P (D)
2P (B) 2P (C)
1 3
Load
Top Leading-in Top Leading-in Bottom Leading-in Top Leading-in Bottom Leading-in
Top Leading-in Bottom Leading-in
Notes:
1) L+: Positive pole of power
L-: Negative pole of power
2) Positive pole of breaker Negative pole of breaker3) Normally Lgrounds in DC power system
while neutral line Mgrounds in AC power system.
+
For 3-pole and 4-pole NDB2Z-63 series MCB can be ordered upon special request.
No. Implication
-
34
3P, 3PN, 4P
33
2P
2 4
1 3
Number of Poles Curve
B, C, D
B, C, D
Width(mm)
54
72
Rated Current(A)
1
2
4
6
10
16
20
25
32
40
50
63
1
2
4
6
10
16
20
25
32
40
50
63
1PNN
N 2
1
Part No.
NDB2LE-63 1/1PN
NDB2LE-63 2/1PN
NDB2LE-63 4/1PN
NDB2LE-63 6/1PN
NDB2LE-63 10/1PN
NDB2LE-63 16/1PN
NDB2LE-63 20/1PN
NDB2LE-63 25/1PN
NDB2LE-63 32/1PN
NDB2LE-63 40/1PN
NDB2LE-63 50/1PN
NDB2LE-63 63/1PN
NDB2LE-63 1/2
NDB2LE-63 2/2
NDB2LE-63 4/2
NDB2LE-63 6/2
NDB2LE-63 10/2
NDB2LE-63 16/2
NDB2LE-63 20/2
NDB2LE-63 25/2
NDB2LE-63 32/2
NDB2LE-63 40/2
NDB2LE-63 50/2
NDB2LE-63 63/2
Release should be released first during MCB dielectric test
NDB2LE-63 3PN can be ordered upon special request
Number of Poles Width (mm)
117
135
135
Curve
B, C, D
B, C, D
B, C, D
Rated Current(A)
1
2
4
6
10
16
20
25
32
40
50
63
1
2
4
6
10
16
20
25
32
40
50
63
1
2
4
6
10
16
20
25
32
40
50
63
3PN
N 1 3 5
N 2 4 6
4P
1 3 5 7
2 4 6 8
3P
1 3 5
2 4 6
Part No.
NDB2LE-63 1/3
NDB2LE-63 2/3
NDB2LE-63 4/3
NDB2LE-63 6/3
NDB2LE-63 10/3
NDB2LE-63 16/3
NDB2LE-63 20/3
NDB2LE-63 25/3
NDB2LE-63 32/3
NDB2LE-63 40/3
NDB2LE-63 50/3
NDB2LE-63 63/3
NDB2LE-63 1/3PN
NDB2LE-63 2/3PN
NDB2LE-63 4/3PN
NDB2LE-63 6/3PN
NDB2LE-63 10/3PN
NDB2LE-63 16/3PN
NDB2LE-63 20/3PN
NDB2LE-63 25/3PN
NDB2LE-63 32/3PN
NDB2LE-63 40/3PN
NDB2LE-63 50/3PN
NDB2LE-63 63/3PN
NDB2LE-63 1/4
NDB2LE-63 2/4
NDB2LE-63 4/4
NDB2LE-63 6/4
NDB2LE-63 10/4
NDB2LE-63 16/4
NDB2LE-63 20/4
NDB2LE-63 25/4
NDB2LE-63 32/4
NDB2LE-63 40/4
NDB2LE-63 50/4
NDB2LE-63 63/4
75135
1173PN, 4P
3P
60
45
45 90.5
Dimension
-
Brand code
Product code
Design code
Frame rating (A)
Rated current (A)
Number of poles
3635
OF2 Auxiliary Switch
Application
Linked to the left side of NDB2 series MCB, to indicate the OPEN or CLOSED status of the associated breaker
Specifications
Width (mm): 9
AC
DC
DC
Voltage
415V
130V
24V
Current
3A
1A
6A
AC
DC
Voltage
240V
48V
Current
6A
2A
SD2 Alarm Switch
Wiring Capacity
Application
Linked to the left side of NDB2 series MCB, to indicate the tripping status of the associated breaker
Specifications
Width (mm): 9
AC
DC
DC
Voltage
415V
130V
24V
Current
3A
1A
6A
AC
DC
Voltage
240V
48V
Current
6A
2A
Single line: 2.5mm2 Double line: 1.5mm2
11
12 14
949291
NDG1 Series Disconnect Switch
ND G 1 100
G Switch Disconector
NDG1-100
1
100
32, 63, 100
1, 2, 3, 4
Model and Implication
IEC 60947-3, GB 14048.3;
TV, CE, CCC.
Application
Close, open or disconnect the circuit
Standards and Certificates
Working Condition
Ambient temperature: -35+70
Air humidity: 95%
Altitude: 2000m
Pollution degree:
No significant shock or vibration
Wiring Capacity
4mm2 , 50 4mm2 (Minimum 4mm2 for BV)
Specifications
Rated working voltage: AC230/400V
Mechanical life: 10000 times
Switching capacity:3InA(400V, cos=0.65)
Rated short current making capacity:2000A(400V, cos=0.9)
Rated short-time withstand current2000A(400V, 1s)
IEC 60947-5, GB 14048.5;
TV, CE, CCC.
Standards and Certificates
Notes: After clipping on to NDB2 series MCB, Point 11 and 14 are connected when circuit is closed; Point 11 and 12 are connected when circuit is open. May be used in conjunction with a SD2 alarm switch or another OF2 auxiliary switch.
Notes: After clipping on to NDM1 series MCB,Point 91 and 92 are connected when circuit is closed;Point 91 and 94 are connected when the breaker trips due to fault;Point 91 and 92 are connected when the breaker trips by manual operation. Meanwhile, point 91 and 94 are disconnected.May be used in conjunction with a OF2 auxiliary switch or another SD2 alarm switch.
No. Implication
-
3837
Number of Poles Width (mm)
18
18
18
36
36
36
54
54
54
72
72
72
Part No.
32/1
63/1
100/1
32/2
63/2
100/2
32/3
63/3
100/3
32/4
63/4
100/4
NDG1-100
NDG1-100
NDG1-100
NDG1-100
NDG1-100
NDG1-100
NDG1-100
NDG1-100
NDG1-100
NDG1-100
NDG1-100
NDG1-100
Rated Current (A)
32
63
100
32
63
100
32
63
100
32
63
100
AC 250V 6A
AC 415V 3A
11
1214
OF3 Auxiliary Switch
Application
Linked to the left side of NDG1-100 series disconnect switch to indicate the OPEN or CLOSED status
Specification
Standards and Certificates
Width (mm): 18
Note: Clip onto NDG1-100 switch disconnector.
Point 11 and 14 is connected when circuit is closed;
Point 11 and 12 is connected when circuit is opened.
IEC 60947-5, GB 14048.5;
TV, CE, CCC
Wiring Capacity
Tripping Curve
5
21
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
Curve B (3~5In)
NDM1-63, NDB2-63, NDB2LE-63
5
21
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
Curve C (5~10In)
NDM1-63, NDB2-63, NDB2LE-63NDB1-32, NDB1LG-32
10mm2
Curve D (10~14In)
NDM1-63, NDB2-63, NDB2LE-63
5
21
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
-
4039
Tripping Curve Temperature Derating
Curve C 8In (120%)
NDM1-125
5
21
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
Curve D 12In (120%)
NDM1-125
5
21
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
Curve B (4~7In)
NDB2Z-63
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
Curve C (7~15In)
NDB2Z-63
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
(A)
()
1
3
6
10
16
20
25
32
40
50
63
80
100
125
1.25
3.83
7.58
13.62
20.43
25.28
31.72
40.46
50.86
63.97
82.06
130
155
265
-30
1.27
3.89
7.70
13.89
20.78
25.67
32.21
41.04
51.63
64.92
83.48
135
160
275
-35
1.23
3.76
7.46
13.35
20.08
24.88
31.22
39.82
50.04
62.92
80.64
126
150
255
-25
1.21
3.70
7.34
13.07
19.75
24.47
30.70
39.17
40.21
61.86
79.19
122
146
245
-20
1.19
3.64
7.21
12.81
19.40
24.06
30.18
38.51
48.37
60.77
77.72
118
142
235
-15
1.17
3.57
7.09
12.53
19.05
23.64
29.65
37.84
47.51
59.67
76.22
115
137
225
-10
1.15
3.50
6.96
12.23
18.70
23.22
29.10
37.15
46.63
58.54
74.70
112
133
215
-5
1.13
3.44
6.83
11.93
18.33
22.78
28.55
36.47
45.74
57.40
73.14
108
129
205
0
1.10
3.37
6.70
11.63
17.96
22.34
27.98
35.75
44.83
56.23
71.54
104
125
195
5
1.08
3.30
6.56
11.33
17.58
21.89
27.41
35.03
43.90
55.05
69.91
99
122
185
10 15
1.06
3.22
6.42
11.01
17.20
21.43
26.82
34.30
42.95
53.81
68.24
95
118
175
1
3
6
10
16
20
25
32
40
50
63
80
100
125
20
1.05
3.14
6.27
10.67
16.80
20.96
26.22
33.54
41.98
52.56
66.53
91
114
165
25
1.02
3.06
6.14
10.34
16.40
20.47
25.61
32.77
40.99
51.28
64.78
88
111
155
30
1.00
3.00
6.00
10.00
16.00
20.00
25.00
32.00
40.00
50.00
63.00
85
108
145
35
0.97
2.92
5.84
9.63
15.55
19.47
24.33
31.17
38.93
47.82
60.11
82
103
135
40
0.94
2.84
5.68
9.24
15.11
18.95
23.67
30.34
37.85
46.24
58.19
80
100
125
45
0.91
2.76
5.52
8.85
14.66
18.42
23.00
29.48
36.75
44.81
56.21
75.5
94
115
50
0.89
2.67
5.36
8.45
14.20
17.87
22.28
28.60
35.61
43.33
54.16
72.5
88
105
55
0.86
2.58
5.19
8.01
13.71
17.30
21.56
27.69
34.43
41.81
52.03
68
82
95
60
0.83
2.49
5.01
7.55
13.21
16.71
20.80
26.75
33.21
40.23
49.81
64.5
75
85
65
0.80
2.38
4.83
7.06
12.70
16.10
20.02
25.78
31.95
38.58
47.50
58
68
75
70
0.77
2.27
4.64
6.55
12.75
15.47
19.21
24.77
30.63
35.77
43.05
52.5
58
65
Note: Ambient temperature refers to the temperature inside the distribution board or switchgear where breakers are
mounted. For breakers below 63A, the reference number is 30, while 40 for breakers from 80A to 125A.
5
21
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
Curve B 4In (120%)
NDB2T-63
5
21
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
Curve C 8In (120%)
NDB2T-63
Curve D 12In (120%)
NDB2T-63
5
21
10000 5000
1h20001000
500
200100
50
2010
0.5
0.20.1
0.05
0.020.01
0.005
0.0020.001
0.5 1 2 3 4 5 7 10 20 30 5070100200 l/ln
Rated current
Ambienttemperature
(A)
()Rated current
Ambienttemperature
Correcting current (A)
Correcting current (A)
-
42
Brand code
Product code
Design code
Rated current (A)
Number of holes
Width modular
NDA1 Series Modular Socket
ND A 1
41
A Modular Socket
NDA1
1
10, 16, 25
2, 3, 4
2, 4, 6, 8
Model and Implication
IEC 60884-1, GB 2099.1; CCC.
Standards and Certificates
Connect electric equipment
Modularization
Standard TH35mm mounting
RoHS complied
Product Features
Schematic Part No.
NDA1-10/22
NDA1-16/34
NDA1-16/46
Specification
Single phase,
two holes
Single phase,
three holes
Three phase,
four holes
Three phase,
four holesNDA1-25/48
18
36
Width (mm)
54
72
10
16
Rated Current(A)
16
25
250
250
440
440
Rated WorkingVoltage (V)
2: Single phase, two holes
3: Single phase, three holes
4: Three phase, four holes
Rated current
Number of Holes
Width modular One modular width: 9mm
25A
4
8
16A
4
4 6
3
10A
2
2
No. Implication
-
44
Brand code
Product code
Design code
Frame rating (A)
Number of p ooles
Width (mm)
NDH1 Series Busbar
ND H 1
H Busbar
NDH1
1
63, 100
43
1P, 2P, 3P
Model and Implication
Consist of comb copper bar and insulated cover.
Use T2 pure copper plate for copper bar and enhanced flame retardant PVC for insulated cover.
Compact and simple usage.
IP20 Protection degree
Product Features
By pole number: 1-Pole, 2-Pole, 3-Pole
By length: Multiple of 18mm, also can be customized, and 60 kits at most (1080 mm).
By kit number: the poles that are linked.
Product Type
Specification
Rated insulation voltage: 500V
Rated current: up to 100A
Conventional thermal current: 100A
Impulse voltage withstand: 6kV
Short-time withstand current: 25kA/0.5s
Power frequency voltage withstand: 2500V (AC 50Hz); No breakdown and flashover within 1 minutes.
Application
NDH1 series busbar is used to link MCB line terminals of the same phase. It can also be used to link terminal apparatus in the same way.
No. Implication
-
46
Brand code
Product code
Design code
Frame rating (A)
Number of poles
Width (mm)
NDH2 Series Busbar
45
Application
NDH2-63 series busbar is used to link MCB line terminals of the same phase. It can also be used to link
terminal apparatus in the same way.
ND H 2
H Busbar
NDH2
2
63
1P, 3P
Model and Implication
63
Consist of comb copper bar and insulated cover.
Use T2 pure copper plate for copper bar and enhanced flame retardant PVC for insulated cover.
Compact and simple usage.
IP20 Protection degree
Product Features
By pole number: 1-Pole, 3-Pole
By length: Multiple of 18mm, also can be customized, and 60 kits at most (1080 mm).
By kit number: the poles that are linked.
Product Type
Specification
Rated insulation voltage: 500V
Rated current: up to 100A
Conventional thermal current: 63A
Impulse voltage withstand: 6kV
Short-time withstand current: 25kA/0.5s
Power frequency voltage withstand: 2500V (AC 50Hz); No breakdown and flashover within 1 minutes
No. Implication
MCB P01-02MCB P03-04MCB P05-06MCB P07-08MCB P09-10MCB P11-12MCB P13-14MCB P15-16MCB P17-18MCB P19-20MCB P21-22MCB P23-24MCB P25-26MCB P27-28MCB P29-30MCB P31-32MCB P33-34MCB P35-36MCB P37-38MCB P39-40MCB P41-42MCB P43-44MCB P45-46MCB P47-48