7/29/2019 NA11637A http://slidepdf.com/reader/full/na11637a 1/9 A I R C O M P A C T Air handling units 1 HEATPUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.637 A D ESCRIPTION Casing Double-wall casing with 25 mm glass wool insulation. External panelwork made from painted galvanised steel (RAL 9006 and 7024). Galvanised sheet metal interior. Hinged doors for easy access (1 or 2 lift-off doors) Hydraulic connection On the left: L or on the right: R (specify on order) The units are available in the following models: ceiling mount HC , floor mount HF , or Vertical wall V , easily secured using angle brackets equipped with antivibration mounts Angle brackets of the same type can be used to interconnect the air-handling units and additional units from the outside. Angl e brac ket cove rs give the produ ct a perf ect fina l appearance. 4 standard unit lengths mean that various configurations are possible The lengths are 610, 830, 1100, 1400 mm; models will be determined by the selection software. RA damper Intake-side or discharge-side dampers, whether for air intake, frost protection or insulation purposes, are easily secured to the air-handling unit or additional unit. The guide markings for dampers are identical on both the unit and the duct. The dampers are class 1 or class 3 in accordance with standard EN 1751. Their thickness in the direction of airflow is 110 mm Height is 310 mm. They are fitted with both motorisable and manual control (spindle length: 80 mm). The solution for installation in confined spaces . The CTA ultra slim range offers all the essential functions for quality air handling . U SE The Air Compact air-handling unit is especially suitable for decentralised air-conditioning applications. It can be CEILING MOUNTED or incorporated into a FALSE CEILING with access from below, in RAISED FLOORING or directly in the FLOOR itself with access from above. It can also be installed vertically against a WALL: Upward discharge only with cooling coil (max 4 rows) Upward or downward discharge for the other configurations. R ANGE The Air Compact range consists of 3 sizes ranging from 1500 m 3 /hr to 6000 m 3 /hr. Thickness 400 mm, 4 standardised box lengths determined by the selection software depending on the different configurations. Air Compact 25: 750 mm Air Compact 40: 1310 mm Air Compact 60: 1880 mm Air flow rates: from 1500 to 6000 m 3 /h in 3 sizes. Available pressure: from 100 to 1000 Pa (high performance and reduced sound level) A I R C O M P A C T 1

Transcript of NA11637A

Page 1: NA11637A

7/29/2019 NA11637A

http://slidepdf.com/reader/full/na11637a 1/9

A I R C O M P A C T

Air handling units

1HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.637 A

DESCRIPTION

■ Casing

Double-wall casing with 25 mm glass wool insulation. Externalpanelwork made from painted galvanised steel (RAL 9006 and7024). Galvanised sheet metal interior.Hinged doors for easy access (1 or 2 lift-off doors)

■ Hydraulic connectionOn the left: L or on the right: R (specify on order)The units are available in the following models: ceiling mountHC , floor mount HF , or Vertical wall V , easily secured usingangle brackets equipped with antivibration mounts

Angle brackets of the same type can be used to interconnectthe air-handling units and additional units from the outside.

Angle bracket covers give the product a perfect finalappearance.4 standard unit lengths mean that various configurations arepossible The lengths are 610, 830, 1100, 1400 mm; models willbe determined by the selection software.

■ RA damper

Intake-side or discharge-side dampers, whether for air intake,frost protection or insulation purposes, are easily secured tothe air-handling unit or additional unit.The guide markings for dampers are identical on both the unitand the duct.The dampers are class 1 or class 3 in accordance withstandard EN 1751.Their thickness in the direction of airflow is 110 mmHeight is 310 mm.They are fitted with both motorisable and manual control(spindle length: 80 mm).

The solution for installation in confined spaces .The CTA ultra slim range offers all the essential

functions for quality air handling .

USE

The Air Compact air-handling unit is especially suitable for decentralised air-conditioning applications.

It can be CEILING MOUNTED or incorporated into a FALSECEILING with access from below, in RAISED FLOORING or

directly in the FLOOR itself with access from above.

It can also be installed vertically against a WALL:Upward discharge only with cooling coil (max 4 rows)Upward or downward discharge for the other configurations.

RANGE

The Air Compact range consists of 3 sizes ranging from1500 m 3 /hr to 6000 m 3/hr.Thickness 400 mm, 4 standardised box lengths determined bythe selection software depending on the differentconfigurations.

Air Compact 25: 750 mm Air Compact 40: 1310 mm Air Compact 60: 1880 mm

Air flow rates: from 1500 to 6000 m 3 /h in 3 sizes.

Available pressure: from 100 to 1000 Pa(high performance and reduced sound level)

A I R C O M P A C T

1

Page 2: NA11637A

7/29/2019 NA11637A

http://slidepdf.com/reader/full/na11637a 2/9HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.637 A

AIR COMPACT

2

Air handling units

■ Hydraulic or evaporator coil in the AHU orvertical unit. CFV

The coils are totally DRAINABLE. Piping is fitted with threadedends with purge and drain plugs (Ø 1/8’’).- In heating mode:

Size 25: 1, 2, and 3-row coils are available,Size 40 and 60: 1, 2, and 4-row coils are available, A frost protection thermostat with automatic reset canbe installed on the coil.

- In refrigeration mode:For each size there are 3, 4, and 6-row chilled water coils and3, 6 rows of direct expansion coils.The section is fitted with an eliminator, maximum face velocity:3.1 m/s and a stainless steel condensate container.Container isolation option using closed-cell foam.

For vertical applications, max 4 rows in the CFV unit.

■ 3-way mixing box: CM3

Box enabling removal of extracted air, introduction of fresh air andair recycling via the intermediary of two moving vanes ensuringflow metering and distribution.

Manual and motorisation control possible.

■ Straight or Curved Plenums: PLD PRS

Can be mounted on either intake or discharge.

2 plenum types:- intake or direct discharge: frame with double deflectiongrille, length 25 mm.- intake or discharge at RIGHT ANGLE: fitted with a doubledeflection grille, length 330 mm.

■ Filtration

In addition to a full section G4 filter base assembly,

the following solutions are available: G4, F5 pleated, F6-F7-F8-F9 rigid pockets in universal sizes, with a compressionsystem starting at filtration efficiency class F6.

- Pressure taps mounted as standard on each stage.- Optional liquid filled pressure gauge.

PLD PRS

HI HS SI

■ 2-way mixing box: CM2

Box enabling fresh air and return air to be mixed by a moving vane ensuring flow metering and distribution.Manual and motorisable control.

Page 3: NA11637A

7/29/2019 NA11637A

http://slidepdf.com/reader/full/na11637a 3/9

A I R C O M P A C T

Air handling units

3HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.637 A

■ Electric heater

The electric heater can be installed in the AHU (Power module1) or in an additional BEC unit (Power module 1 or module 2).

It is fitted with 2 safety devices: 1 thermostat with automaticreset and 1 Klixon with manual reset.

Depending on the nature of elements adjacent to the electricheater, (filter or motor, for example), a radiation shield may beinstalled upstream or downstream.

Air Compact 25: fitted with 1 fan Air Compact 40: fitted with a choice of 1 or 2 fans depending on flowrate

Air Compact 60: fitted with 2 fans

Fan without scroll (FREEWHEEL), with motor at shaft end,pressure range 100Pa min to 1000Pa max.

Three-phase 400-Volt configurations are available

VENTILATION

Plug fan, direct drive. Selected for its excellent performance and sound level, as shown below:

Fresh Air

ALI GNE D

Extracted Air Fresh Air

Return air DischargedAir Return

air

ALI GNE D

OFFSET(view from above)

Air flow rate (m 3/hr)

■ Sound attenuator

Fitted with a horizontal sound attenuator, height 200 mm, length 600 mm.

■ Plate recuperator

Plate recuperator, aligned arrangement 25, 40, 60 size or offset arrangement 25 and 40 size: available in 2008.

Air Compact 25

T o

t a l p r e s s u r e

( P a

)

Air Compact 40/1

Air Compact 40/2

Air Compact 60

Page 4: NA11637A

7/29/2019 NA11637A

http://slidepdf.com/reader/full/na11637a 4/9HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.637 A

AIR COMPACT

4

Air handling units

■ Designations and lengths of additional units

4 motor capacities are defined and cover the entire operating range:0.25 kW 4-pole; 0.55 kW 4-pole; 0.75 kW 2-pole; 1.50 kW 2-pole

The frequency inverter is needed to reach the desired operatingpoint.If there are 2 fan motor units, 1 single frequency inverter controlsboth motors.The frequency inverters are connected to a SINGLE PHASE230 V power supply and supply the motors with three-phase current.Optional frequency inverters with THREE PHASE 400 V supply

RA110 mm

PLD25 mm

CFA610 mm

BEC610 mm

CFR610 mm PLJ

25 : 830 mm40 : 1400 mm

CFV610 mm

PLA1110 mm

PRS330 mm

PAS610 mm

CM2400 mm

CM3800 mm

Motor (Kw)Frequency inverter type

SK 1-PH/230 V SK 3-PH/400 V

0.25 0.5M 1T0.55 or 2x0.25 1.2M 1.2T

0.75 1.5M 1.5T

2x0.55 2M/TL 2T

1.5 or 2x0.75 2.5M/TL 2.5T

2x1.5 4.5M/TL 4.5T

AIR COMPACT 25 40 60

Nominal air flowrate (m3 /hr)(speed: 3.1 m/s on coil) 2000 4000 6000

Plug fan TE 280 and TE 200 1 1 2 2Electric motor 1 1 2 2

Available power 0.25 kW 4 pole; 0.55 kW 4 pole; 0.75 kW 2 pole; 1.5 kW 2 pole

Number of frequency inverters 1 1 1 1

Pleated filters G4/F5

Rigid dihedral opacimetric filters F6/F7/F8/F9

Heating coil 1/2/3 rows 1/2/4 rows 1/2/4 rows

Chilled water refrigeration coil 3/4/6 rows

Direct expansion coil 3/6 rows

Electric heater module 1 15 kW 24 kW 36 kW

Plate recuperator: aligned arrangement Yes Yes Yes

Plate recuperator: offset arrangement Yes Yes No

TECHNICAL SPECIFICATIONS

Page 5: NA11637A

7/29/2019 NA11637A

http://slidepdf.com/reader/full/na11637a 5/9

A I R C O M P A C T

Air handling units

5HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.637 A

AHU size In the AHU Additional BEC unit

Module: 2-stage Module 1: 2-stage Module 2: 4-stage

25 6x2.5 kW = 15 kW 6x2.5 kW = 15 kW 12x2.5 kW = 30 kW

40 6x2.5 kW = 24 kW 6x4 kW = 24 kW 12x4 kW = 48 kW

60 6x6 kW = 36 kW 6x6 kW = 36 kW 12x6 kW = 72 kW

P OWER PROVIDED BY COILS (WATTS )

DIMENSIONAL SPECIFICATIONS

Air Compact 25 40 60

External dimensionssection (mm) 750 x 400 1310 x 400 1800 x 400

Length unit available in (mm) 610-830-1100-1400 : 4 standard lengths assembled for all configurations (LST selection)

Length 610 mm

Length 1100 mm

Length 830 mm

Length 1400 mm

DIMENSIONS / F OOTPRINTS

Page 6: NA11637A

7/29/2019 NA11637A

http://slidepdf.com/reader/full/na11637a 6/9HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.637 A

AIR COMPACT

6

Air handling units

■ Plate recuperator unit

Aligned arrangement

Offset arrangement

AIR COMPACT Length Height Width Ø Condensate (D) Condensate drain position // Origin of unit (B)

Condensate drain position:Height // Bottom of unit (A)

25 1100 490 750 16 500 40

40 1100 490 1310 16 500 40

60 1100 490 1880 16 500 40

AIRCOMPACT Length Height Width D A B

25 830 400 1630 16 40 295

40 1400 400 2750 16 40 440

Fresh Air

ALIG NED

Extracted Air Fresh Air

Return air DischargedAir Return

air

ALIG NED

OFFSET(view from above)

B

Ø DExtracted Air

Fresh Air

A

Page 7: NA11637A

7/29/2019 NA11637A

http://slidepdf.com/reader/full/na11637a 7/9

A I R C O M P A C T

Air handling units

7HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.637 A

S ECTION B-B

SECTION D-D

SCREW HØ 8X80

PLASTIC COVER

DAMPING BLOCK

SECTION B-B

SECTION D-D

AIR CONNECTIONS

A B C D

Air Compact 25 750 690 3 238

Air Compact 40 1310 1250 6 212.3

Air Compact 60 1880 1820 8 230.5

■ Air connection

■ Mixing box air connection

Ceiling mounting Floor mounting

AHU intake - AHU discharge air connection - Mixing box and plate recuperator

Page 8: NA11637A

7/29/2019 NA11637A

http://slidepdf.com/reader/full/na11637a 8/9HEAT PUMPS - AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - NA 11.637 A

AIR COMPACT

8

Air handling units

S ECTION E-ESECTION E-E

Plate Code JH 27600

Screw CHC M12 x 30Code 7168187

Flat washer M12 UCode Z440005

Nut M12Code Z438002

Connection coverCode JA 78700

PVC Seal 25 x 5Code Z222017

UNIT CONNECTION S

Assembly between blocks

Position of drill holes for fixing

Page 9: NA11637A

7/29/2019 NA11637A

http://slidepdf.com/reader/full/na11637a 9/9

A I R C O M P A C T

Air handling units

This document is non-contractual. As part of its policy of continual product improvement, CIAT reserves the right to make any technical modification it feels appropriate without pr ior notification.

Head office Avenue Jean Falconnier - B.P. 14

01350 - Culoz - FranceTel.: +33 (0)4 79 42 42 42Fax: +33 (0)4 79 42 42 [email protected] - www.ciat.com

C ompagnie I ndustrielle d’ A pplications T hermiques - S.A. with a registered capital of 26 728 480 € - R.C.S. Bourg-en-Bresse B 545 620 114

CIAT ServiceTel. : 08 11 65 98 98(0,15 € / mn)

Fax : 08 26 10 13 63(0,15 € / mn)