MYDAX, INC. INSTRUCTION/OPERATIONS MANUAL 1M9W...

33
advanced temperature control technology MYDAX, INC. INSTRUCTION/OPERATIONS MANUAL 1M9W-S WATER COOLED CHILLER Serial Number 120-07XX MYDAX, INC. 12260 Shale Ridge Road Auburn, CA 95602 (530) 888-6662 FAX: (530) 888-0962 March 2001

Transcript of MYDAX, INC. INSTRUCTION/OPERATIONS MANUAL 1M9W...

advanced temperature control technology

MYDAX, INC.

INSTRUCTION/OPERATIONS MANUAL

1M9W-S WATER COOLED CHILLER

Serial Number 120-07XX

MYDAX, INC.

12260 Shale Ridge Road

Auburn, CA 95602

(530) 888-6662

FAX: (530) 888-0962

March 2001

Lawrence Berkeley Laboratory

TABLE OF CONTENTS

I. SPECIFICATIONS ....................................................................................................... 1

II. SYSTEM OVERVIEW ................................................................................................. 2

III. INSTALLATION ......................................................................................................... 4

IV. FRONT PANEL CONTROLS ..................................................................................…… 5

V. ERROR MESSAGES ................................................................................................... 7

VI. DIAGNOSTIC DISPLAYS .......................................................................................... 8

VII. SERVICE & WARRANTY .......................................................................................…. 11

VIII. RESHIPPING & LONG-TERM STORAGE PREPARATION ............................ ..................… 12

IX. APPENDIX A: RS-232C SERIAL INTERFACE OPERATION

X. APPENDIX B: DRAWINGS

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 1

SPECIFICATIONS

SYSTEM CAPACITIES

Cooling Capacity @ +20°C 2500 Watts

Coolant Temperature Setpoint Range +15°C to +25°C

Coolant Output Temperature Stability ± 0.05°C

Polypropylene Reservoir Volume 10 Gallons

Recirculating Coolant Low Conductivity Water

Coolant Flow/Pressure 10 Gpm @ 100 Psi (Bypass Provided)

Recirculating Supply/Return Fittings 1" Stainless Steel FPT

Condenser Water @ 75°F 1.5 Gpm Required (∆P = 20 Psi)

Condenser Water Connections 1/2" Stainless Steel FPT

Electrical Service 208/230 volt, 60 Hz, 3 phase, 20 ampWith 10' line cord and L15-30P plug.

Physical Parameters 42"H x 24"W x 33"D, 450 lbs.

STANDARD FEATURES

System is complete with microprocessor-controlled low-stress refrigeration circuit, recirculating pump and fluidreservoir. R-22 refrigeration circuit uses all-brazed construction for extra strength. The heavy-duty frame isconstructed of welded steel tubing equipped with locking casters.

The microprocessor-based control system includes an extensive monitoring capability including comprehensivecontrols, error messages and diagnostics. System status is indicated via a two-row (40 characters each)alphanumeric LCD (liquid crystal display) and with red light-emitting diodes (LED's). The control keyboardemploys membrane switches with a sealed polycarbonate overlay for protection from liquid spills. This chilleris complete with a liquid-filled panel mounted pressure gauge, an internal pressure bypass circuit, a full-flow10 micron particulate filter and an RS-232C Interface for remote control and monitoring.

SAFETY FEATURES

1. Warning & Error Messages: including coolant over-temperature warning & shutdown, low tank level warning& shutdown and others (see ERROR MESSAGES section).

2. System Diagnostics: including coolant & freon temperatures, valve and heater drives and others (seeDIAGNOSTIC DISPLAYS section).

3. Integral compressor refrigerant high pressure protection. 4. Circuit breaker & contactor. 5. Interlock loop, including reset switch. 6. Thermal protection of pump and compressor motors. 7. Manufactured and wired in accordance with IBM Non-Product Safety Design Standards.

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 2

SYSTEM OVERVIEW

System Fluid Schematic

Refer to drawing #B2343, the fluid schematic. The heart of the design is the evaporator valve. This is a thermal-electricexpansion valve, controlled directly by the system's embedded microprocessor. Hermetically sealed, it consists of aspring-loaded needle valve in contact with a bimetallic plate. The plate is wound by a coil of wire connected to terminalson top of the valve. The curvature of the plate, and therefore the position of the needle valve, varies with its temperaturewhich is controlled by electrical current flow through the coil. So by controlling the duration of electrical pulses appliedto the valve terminals, the microprocessor opens the valve to a precisely determined point. This passes a preciselydetermined flow of freon to the evaporator, allowing for exceptionally stable recirculating temperatures. This systemis designed to control the recirculating output temperature to ±0.05°C across the system operating range.

The microprocessor sets the exact position of the valve based upon the system heat load. If the load increases, theevaporator valve is opened slightly, passing more refrigerant. If the load decreases, the valve is closed slightly, passingless refrigerant. During normal operation, the position of this valve stays nearly constant. Only major changes in heatload or system-wide power cycling cause large changes in the valve opening. In the case of a step-wise change in heatload, the microprocessor quickly drives the valve to the new setting and refrigerant flow soon settles at the proper level.

The valve drive setting is based primarily upon data received from RTD's (resistance temperature devices) located aboutthe circuit. The drawing shows RTD's at the evaporator valve, at the discharge line from the pump, at the reservoir andbetween the condenser and receiver. The microprocessor "reads" these and other sensors constantly and sets therefrigerant valve accordingly.

Thus refrigerant flow is truly proportioned, through a valve which only rarely cycles all the way open or shut. Besidesprecise temperature control, this allows continuous compressor operation without the normal addition of cycling, andtherefore failure-prone, pressure-actuated hot gas bypass valves. All other refrigeration circuit components are used asin conventional systems. All permanent copper joints in the refrigeration circuit are brazed for extra strength. Much ofthe circuitry is insulated to eliminate cooling capacity loss and unpredictable operation due to drafts or fluctuatingambient air conditions.

This system is designed to recirculate water. It is not designed to recirculate solutions of automotive antifreeze. Approximately 10 gallons are required to fill the polypropylene reservoir. The heating elements are stainless steelcartridge heaters. The freon evaporator is a coaxial heat exchanger, located in the recirculating return line leading to thereservoir.

The reservoir is fitted with two level sensors. One level sensor drives a FILL TANK alarm at the main panel, indicatingcoolant level has dropped somewhat. The second sensor, the TANK EMPTY sensor, is connected to the safety interlockloop and shuts the system down if tripped. Note that "empty" is a relative term only. The real function of this sensoris to prevent the coolant level from dropping so low as to expose the pump suction line.

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 3

System Electrical Diagram

Refer to drawing #B2344, the system electrical diagram. The central component of the electrical system is the M1001controller. It is microprocessor-based and communicates with and/or controls various other circuit boards andcomponents. Most controller circuitry is laid out on circuit boards mounted in the main control cabinet. The controlleris powered as long as the system circuit breaker is set, receiving 24 VAC power from a bulkhead-mounted transformer.

The controller "reads" the RTD's in the system via board M1002. RTD's are included for the recirculating outputtemperature and the reservoir, as well as for the freon circuit. Also routed through this board are the 100 and 120 •precision RTD calibration resistor circuits. The evaporator valve drive signal is routed through board M1004, as is thephase detector circuit.

The system interlock loop is controlled by the M1002 circuit board. In this application the interlock loop consists of thefreon high pressure switch, the tank over-temperature switch, the TANK EMPTY level sensor, the RESET momentaryswitch, one power relay coil and a relay pole (1R 5-8). The RESET switch serves to feed power to the relay, whichenergizes the contactor. When energized, the contactor feeds power back to the relay so the RESET switch may openup without cutting off power to the relay. If the freon pressure switch, the over-temperature switch or the level sensortrips, power to the loop is interrupted. The microprocessor senses this via the M1002 board. Provided the system haspower, if the loop trips out, the controller drives the PUSH RESET error message. The loop must be reset when the faultcondition is resolved.

The M1002 board also routes signals for the FILL TANK level sensor. If this sensor trips, the microprocessor drivesthe FILL TANK error message.

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 4

INSTALLATION

POWER CONNECTION

This chiller requires a 20 amp or larger circuit, 208/230 volt, 60 Hz, 3 phase and is equipped with a line cordand twist-lock L15-30P electrical plug.

PLUMBING INTERFACE CONNECTIONS

The chiller's 1" female pipe thread (FPT) fitting labeled "TANK OUT" must be plumbed to the inlet of thedevice to be cooled. The outlet of the device to be cooled must be plumbed to the chiller's 1" FPT fittinglabeled "TANK IN". This system is equipped with a ½" FPT fitting labeled "DRAIN". It may be desirable toinstall a valve at this location prior to the initial filling of the reservoir, for the convenience of future drainingprocedures.

The condenser cooling water supply must be plumbed to the chiller's ½" FPT fitting labeled "CONDENSERIN". The chiller's ½" FPT fitting labeled "CONDENSER OUT" must be plumbed to either a drain or the returnpath of the condenser cooling water circuit. Verify that condenser cooling water into and out of the chiller isunobstructed. Obstructions may cause loss of cooling capacity and eventual overheating.

Both the recirculating loop and the condenser cooling water loop are under pressure when the system isoperating. Check all fluid interface connections now to ensure against leaks.

CIRCUIT BREAKER

Set the circuit breaker mounted on the front of the system. Upon setting the circuit breaker, a message similarto the following appears on the 2 by 40-character main display:

This display indicates that the system's phase monitor circuit is checking for correct electrical power phaserelationship. Should a live and ground line be reversed, the phase detector reads PHASE MISSING. Correctthe error and the controller no longer indicates PHASE MISSING. If the display reads PHASE REVERSED,disconnect and switch two of the three phases.

WARNING

The system should be powered for a period of ½ hour before starting, toallow the crankcase heater to separate the refrigerant from the oil.

FILL RESERVOIR

To fill the system's reservoir, unscrew the fill plug on the top of the vertical stand-pipe for the tank and pourin the recirculating fluid. If the system is powered before the tank is filled, the "FILL TANK" error messageis displayed at the main panel, the alarm LED is lighted and the audible alarm sounds. Filling the tankeliminates the alarms. Replace the plug.

PUSH RESET BUTTON

The Reset button, located below the main panel, must be pushed upon powering the system. This resets thepower safety interlock loop, which protects the operator and electrical circuitry.

Output --- Warmup Delay --- Local Set 20.02°C 20.0°C

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 5

FRONT PANEL CONTROLS

All Mydax chillers are controlled by a microprocessor which is accessed via the system control panel. System controlsare simple, yet powerful and in concert with built-in diagnostics and error messages, are exceptionally comprehensive.

POWER LED: Indicates unit is powered (the circuit breaker is set).

RESET: Must be pressed prior to system start-up to energize the interlock loop.

START: Starts compressor and pump and turns on LED's. Once the start-up routine is complete thedisplay changes to the MAIN DISPLAY:

Shows the actual Output Temperature and Setpoint Temperature in °C. Also indicates thatthe local SET TEMPERATURE MODE can be enabled.

STOP: Stops both the compressor and pump and blanks the display.

MUTE ALARM: May be used to deactivate audible alarm for 10 minutes, leaving alarm LED on. Pressing theCLEAR key reactivates the alarm, which sounds until the fault condition is eliminated or theMUTE ALARM switch is depressed again. Pressing MUTE ALARM when no alarm isactive causes the alarm to sound once and the TEST ALARM display to appear.

SET: Enables SET TEMPERATURE MODE. SET MODE is disabled from panel if an alarm isactive or if the unit is in REMOTE. To set, depress:

SET: "Set Mode" appears at the right of the display. Cursor flashes at"units" digit of the temperature display.

ARROWS KEYS: Changes temperature setting in one degree increments unless "."(decimal) key is depressed.

"." (DECIMAL): Moves cursor to the "tenths" digit of the temperature display andcauses arrow keys to change setting in tenths of a degree.

KEYPAD: Changes temperature setting by entering numbers directly.

CLEAR: Erases an incorrect entry.

ENTER: Selects temperature setting and deselects SET mode.

TEST: Initiates Test Mode. See description under DIAGNOSTIC DISPLAYS section of this manual.

ENTER: Enters temperature selections while in the SET mode.

CLEAR: Erases incorrect temperature selections; exits Test Mode; clears Mute Alarm selection.

MODE: Toggles between the RS-232C remote control mode and Local Set mode.

ARROW KEYS: Changes temperature setpoint by 0.1° or 1°C increments/decrements; toggles tank

Output --- MYDAX --- Local Set 20.02°C 20.0°C

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 6

temperature, setpoint temperature and evaporator data view modes for multiple channelsystems.

"." (DECIMAL): Display shows model number and software revision date and copyright:

RUN PUMP: Inactive in this system.

X & Y: For future use.

Z: See Test Panel 9 in the Diagnostic Displays Section.

EMO SWITCH: This is a large red emergency off switch mounted on the left of the main panel. It shuts downthe entire system, excluding the controller.

1M9W-S 2001.01.18Copyright 2001 Mydax, Inc.

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 7

ERROR MESSAGES

A unique feature of Mydax systems is the error messages displayed on the 2 by 40-character liquid crystal display (LCD). The microprocessor constantly checks various points and parameters throughout the system and automatically displaysmessages when error conditions are sensed. Many displays are announced by an audible alarm and LED indicator. Theerror message persists until the fault condition is resolved, provided that the fault condition was not fatal, resulting ina system shutdown.

Condenser Hot Indicates high discharge pressure condition with temperature over +50°C. This is a warning messageonly. A separate mechanical overpressure switch, part of the safety interlock loop, shuts the systemdown in case of an overpressure condition. The purpose of this message is to allow maintenanceworkers to correct the problem at an early stage. (Caused by a clogged filter, low or warm condensercooling water flow or condenser scale build-up.)

Fill Tank Indicates low tank liquid level.

Tank Too Hot Indicates that the reservoir temperature is more than 10°C above the highest allowable set point.Microprocessor shuts down the system.

Push Reset Indicates that the reset button has not been pushed since the last system power-up or that the systeminterlock loop has a fault condition.

A series-wired safety interlock loop protects all Mydax systems, disconnecting AC power from nearlyall circuitry. The loop consists of the freon pressure switch, tank "hot" sensor and low level switch. If any link in the loop is opened, the "Push Reset" error message is displayed. Once the fault iscorrected, the Reset button must be used to re-establish loop integrity. The reset button must also bepushed at system power up.

Phase Missing Indicates that one or more electrical phases are missing.

Phase Reversed Indicates that electrical phases are incorrectly connected. Reverse any two legs.

Low AC Line Indicates a low voltage condition exists on the input AC line.

Open RTD Indicates that an RTD connected to the M1002 Input Board has failed and that the system has shutdown to prevent damage due to lack of data. The RTD at fault may be located by accessing Test Panel#8. The RTD must be replaced for the system to operate again.

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 8

DIAGNOSTIC DISPLAYS

Mydax chillers are provided with a computerized self-diagnostic capability. This system is equipped with 9 differenttest panels, which are accessed by pressing the TEST key, followed by the test panel number. Diagnostic mode isterminated by pressing the CLEAR key, and results in a display similar to that below:

MAIN DISPLAY

Diagnostic messages are displayed on the main 2 by 40-character LCD. Display #5 automatically appears when theTEST key is first depressed. Once in diagnostic mode, other displays can be selected by depressing number keys 1through 9. The following describes each of the test displays:

TEST PANEL #1:

Numbers represent the drive signals for the evaporator valve and tank heater. The range is 0 (minimum) to 20(maximum drive). Each digit represents 5% of the available 24VDC drive voltage. Avg Valve shows a 32second running average of the valve's drive, displayed above it.

TEST PANEL #2:

This display shows the refrigerant circuit RTD temperatures in °C. The display reads:

Limit = Max Evaporator Temp Suct = Suction Temp Psig = Suction PressureSup.Ht = Superheat Temp SHavg = Avg Super Ht Temp Cond = Condenser Temp

The condenser reading is a direct indicator of condenser temperature and pressure. The microprocessor sendsthe CONDENSER HOT error message if the condenser temperature exceeds +54°C.

TEST PANEL #3:

The first 3 sets of 4-digit numbers are hexadecimal. They represent correction values for the slow gain servosfor up to 3 reservoirs. The function of this servo is to dynamically adjust the main temperature control servoto near zero error and thereby maintain temperature stability.

The first 2 digits in each set of 4 show the gain offset. Each increment equals 0.05°C, so 14 Hex = 20 decimal= 1.0°C. This value is internally subtracted from the operator-entered temperature setpoint if the actualtemperature is above the setpoint, thus reducing the coolant temperature. When the actual coolant temperatureis below setpoint, the main servo is driving a heater and no adjustment is made to the setpoint. The setpointoffset is continuously monitored by the controller and adjusted according to current conditions.

The second 2 digits in each set of 4 show the time prescaler. This is a counter which increments or decrementsonce a second and times the next update of the setpoint offset. A typical value is 20 seconds per offset change. When the count reaches "00", the offset may or may not be changed and the count resets to "0A" Hex (10decimal). Together these numbers show that the controller is internally changing the control setpoint tomaintain temperature stability, and give the magnitude and timing of the change.

Output --- MYDAX --- Local Set20.02°C 20.0°C

Valve 7 Htr 8 Avg Valve 5 Htr 6

4.0 -4.8 48.2 35.0Limit Suct Psig Sup.Ht SHavg Condr

302B 0000 091F Z 0.00 G 51.95 14.4SS-1 SS-2 SS-3 RTD Reference SH Avg

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 9

The center of the display shows readings for the RTD "Zero" and "Gain" calibration resistors. Precisionresistors 100Ω and 120Ω (0.1% tolerance or better, representing ideal nominal RTD's) are used as a reference. Typical readings are shown.

TEST PANEL #4:

This display shows auxiliary voltmeter readings of Ext 1, Ext 2 and Ext 3. These are not used in this system. VAC is the 24 VAC internal control voltage; a typical value is in the range of 22 to 28. To the right of thisvalue is a 0. At the far right of this display is a time indicator in seconds. The timer stops at 255 seconds andis used internally for turn on routine procedures.

TEST PANEL #5:

This diagnostic shows the Output RTD (coolant) temperature in °C, the Output Setpoint temperature andOutput temperature slope. Slope is a measure of the direction and amount of the output temperature changeper 60 seconds.

TEST PANEL #6:

This diagnostic shows the Tank temperature with resolutions of 0.05°C and 0.01°C, and the Output temperaturewith resolutions of 0.05°C and 0.01°C.

TEST PANEL #7:

This display shows voltmeter readings for up to 3 optional water resistivity monitor interface raw data outputs. Each resistance monitor channel has a positive and a negative voltage reading. These readings areapproximately equal, but are of opposite polarity.

The refrigerant type that the control system is calibrated for is shown. For example: R22

The two numbers at the top, far right-hand side of this display represent the internally computed maximumevaporator temperature and a counter ranging from 0 to 99, which are used to adjust the valve drives andregulate the superheat temperature.

The second line of the right side of this display indicates the status of the lithium battery, mounted on theM1001 circuit board, used to run the system's elapsed run-time clock depicted in Test Panel 8 and the run/eventrecorder depicted in Test Panel 9. A "Bat. OK" message indicates that the battery is operational, while a "NoBat." message indicates that the battery is dead and should be replaced.

TEST PANEL #8:

The top left side of this display shows the alarm (error message) history. If there have been no alarms since the

-5.294 -1.292 -1.308 +26.46 0 255 Ext 1 Ext 2 Ext 3 VAC Secs

20.00 20.0 0.0 Tank Set DgMin

19.80 19.79 20.00 20.02

+ 0.000 + 0.000 + 0.000 R22 6.00 0- 0.000 - 0.000 - 0.000 Bat. OK

Alarms: Fill Tank ! KEY Run 356d 11:31:25

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 10

last history reset, the display reads "No Alarms". If alarms have occurred, the display shows them in sequence,like the main display. The history can be cleared 3 ways:

1. Power Off/On2. Press START Key when unit is stopped3. Press 0 Key when viewing Test Panel 8

The second line of the display can be read when the chiller is stopped. It indicates the reason that the chillerwas last stopped: KEY, FATAL, RS232 or EXT. The right side of the second line indicates the elapsed runtime on the system in days (from 0 to 9999), hours, minutes and seconds. This system is equipped with abattery which, if operational, saves the elapsed run time value when the system is stopped and restarted. Theelapsed run time is reset each time the system is restarted.

TEST PANEL #9:

This display provides run/event recorder data. The run/event recorder continuously records importantinformation into a non-volatile memory while the system is operating. Data is stored at one-second intervalsfor the last 120 seconds of run time and it is also stored at two-minute intervals for the last 240 minutes of runtime.

The first line of this display indicates the run time in hours, minutes and seconds prior to the last systemshutdown, the output and setpoint temperatures of whichever recirculating channel was last selected at the MainDisplay and the system-wide alarm history. The second line indicates which recirculating channel was lastselected at the Main Display, the evaporator, bypass, condenser and superheat RTD temperatures in °C, theaverage superheat temperature from Test Panel 3 and the flow rate. Both the evaporator temperature and theflow rate are specific to the recirculating channel being viewed. All freon circuit RTD temperatures aretruncated to the nearest 1°C for this display.

After the system is stopped and Test Panel 9 is selected, the memory is displayed at the last or most recentsecond (T- 0: 0: 0). The downward arrow key can be used to decrement time into the past. There are 120 "1-second slots" and 120 "2-minute slots". If the downward arrow key is held down, the time slots decrement atthe rate of two slots per second. The upward arrow key increments to more recent time slots. If the "Z" keyis depressed, the display goes to the oldest 1-second slot (T- 0: 1:59 if the actual run time was of at least thatduration). If the "9" key is depressed while viewing Test Panel 9, the display reverts back to "T- 0: 0: 0", thestop time.

The alarm messages are accurate for the slot that is current. If the display is on the minutes slot, then the alarmsindicated are any which have occurred during that 2-minute interval. Alarm messages cycle or flash in anidentical fashion to those appearing in either the Main Display or in Test Panel

T- 0: 0: 0 20.02 20.0 No Alarms.....Tank 1 4Ev 0By 37Cd 13Sh 14SA Gpm

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 11

SERVICE & WARRANTY

If a unit malfunctions, please contact the Mydax Service Department as soon as possible. Many small problems can leadto large problems if not dealt with immediately. Please have the serial number and model number on hand when calling.

Mydax Service Department: (530) 888-6662FAX: (530) 888-0962

RETURN OF UNIT FOR SERVICE

Many problems may be repaired by field exchanges of a module, pump, controller, etc. If return is required,please obtain a return authorization number from the Mydax Service Department or the unit may not beaccepted at our receiving dock.

Please refer to the shipping instructions which follow.

SERVICE OF REFRIGERATION UNIT

Nearly all repairs to the refrigeration unit involve brazing or silver soldering. This should only be done by aperson trained in refrigeration service and familiar with the Mydax system.

NOTE: Before servicing any refrigeration unit involving brazing, remove all freon from the system. Evacuateto a 400 micron vacuum to remove freon residues, then open all service valves to dry air or drynitrogen before use of a torch.

In particular, service of Mydax refrigeration circuits requires attention to the following:

1) Use caution to protect components from heat damage.

2) Prevent any moisture from entering the circuit, as Mydax proportional valves do not function with moisturepresent. Once moisture has entered the system it cannot be removed.

3) Remove insulation and instrumentation wiring or use heat shields to protect them from torch heat during work.

4) Before recharging the circuit, evacuate it to 200 microns at a minimum room temperature of 75°F for threehours.

ONE YEAR WARRANTY

Mydax, Inc. warrants that its temperature control system, and the component parts thereof, will be free from defects inworkmanship and materials for a period of one year from the date of delivery. In the event that warranty service isrequired, the customer is requested to send the equipment freight prepaid to the factory for service. Mydax will thenperform the appropriate service and will return the equipment freight prepaid.

If field service is required during the warranty period, the customer will be responsible for all travel expenses includingmileage. The customer will not be invoiced for any warranty service performed, with regard to either labor or materials,during a field service visit.

Mydax, Inc. 1M9W-S Water Cooled Chiller

Lawrence Berkeley Laboratory 12

RESHIPPING & LONG-TERM STORAGE PREPARATION

Reshipped systems should be protected from freezing temperatures in shipment or serious damage may occur. Freezingtemperatures can be encountered in air and over-mountain surface shipments in any month of the year. In-transit freeze-up can occur in the recirculating coolant loop and in a water-cooled condenser's cooling loop. To protect againstfreezing, all water must be removed from these circuits, or ethylene glycol must be added.

This system has a water-cooled refrigeration condenser. The following instructions apply to shipment or storagepreparation:

1. Feed in a charge of water-glycol mix into the condenser through the "Condenser In" connection. This can bedone by pump or gravity flow.

2. Feed water-glycol until mixture is visibly flowing out of the "Condenser Out" connection.

3. Plug the "Condenser In" and "Condenser Out" fittings to avoid leakage in shipment.

4. Since the system has been run with water, remove it from the reservoir via the "Drain" fitting. As much wateras possible should be drained from the system before shipment. Water adds significant shipping weight andmay damage electrical parts if it sloshes out of the tank.

5. Continue to remove as much water as possible with a wet/dry vacuum to prevent ice-up in the small "nooks &crannies" of the plumbing.

6. Plug the "Tank In", "Tank Out" and "Drain fittings.

Call Mydax for any helpneeded at (530) 888-6662

Mydax, Inc.

Appendix A RS-232 Page A-1

-Appendix A -RS-232 Serial Interface Operation

RS-232C INTERFACING

The use of an embedded microprocessor allows Mydax to offer an RS-232C (remote)interfacing capability. Mydax systems can be controlled from a computer with either theMYDAX REMOTE Window's ™ software package or any control software of the user's choice. Full control and monitoring is possible, allowing complete system operation from anyconvenient location.

Cable connection is via a rear panel DB-25S connector. Connector pin-out is as follows:

Pin 1 ShieldPin 2 Transmit DataPin 3 Receive DataPin 7 Common

A typical interconnect cable for an IBM-PC COM port should be wired as follows:

IBM-PC MYDAX

DB-25S Female Connector DB-25P Male Connector

1 12 23 34 45 56 67 7

20 20

Mydax, Inc.

Appendix A RS-232 Page A-2

RS-232C COMMANDS

The following ASCII commands can be transmitted to the system MPU via the RS-232C link:

RO Enables RS-232C control.

RF Disables RS-232C control. With remote disabled, system onlyresponds to RO.

GO Starts the compressor and pump.HA Stops the compressor and pump.

RP Run Pump only, active only on selected systems.

S?xy.z Sets fluid temperature (x, y and z are any numbers) of tank A,B or C. Settings outside the range default to the nearest limit. Entering a decimal point is optional, as the last digit is assumed to bethe tenths digit. For example: "SA180" selects +18.0°C for tank A,"SA245", "SA24.5" & "SA+24.5" all select +24.5°C for tank A,"SA93.2" selects +30.0°C for tank A.

TE1 Sends a transmission of abbreviated status including system on/offstatus, actual tank temperature and the set point temperature.

TE2 Causes transmission of flow and resistance, if the options exist. Forexample:

TE3 Transmits the contents of the 2 by 40-character main display over theRS-232 line.

TE4 Same output as TE1 plus RTD temperatures and valve & heater drivesignals.

TR or TR0 Turns off repeat transmission mode.

TRx Enables automatic periodic repeat transmission (x= 1-60 andrepresents the number of seconds between transmissions). Theinstructions which follow the TRx command are repeated at thetransmission rate that was set by the TRx command. TE1, TE2, TE3and TE4 are commands that can be repeated in all or anycombination.

TPx Changes the 2 by 40-character display at the main control panel toTest Panel "x" "0" = normal main display; "1" - "8" = diagnosticdisplays. See section on DIAGNOSTIC DISPLAYS. Does NOT causetransmission of the display over the RS-232C line (see command TE3)

ID Causes transmission of the model number and software revision date. For example:

"ID: 1VLH14W 1-24-2000"

Mydax, Inc.

Appendix A RS-232 Page A-3

AL Causes transmission of the alarm status. For example:

"ALARM: 0" denotes no alarm condition.

AH Causes transmission of the alarm history status. For example:"ALHIS: 13" denotes one alarm.

This history is the same as the Test 8 display. The history representsall alarms that have occurred since the last "Start" command.

CH Clears alarm history. This can also be cleared with the "Start" key orwith the "0" key when viewing Test Panel 8.

A delimiter between command strings can be a carriage return (CR), a semi-colon (;) or a comma (,). If a command is understood, a (>) is returned foracknowledgment. If a command is not understood or ignored then a (?) isreturned.

RS-232C STATUS MESSAGES

TE1 status messages include the following:

ON 19.95 20.0 (CR)(LF) A B C

Key: A) System is ON or OFFB) Actual Tank Temperature in °CC) Set point Temperature in °C

A TE4 status message consists of TE1/TE3 data plus RTD temperatures and valve & heaterdrives:

ON 19.9 20 -63 -8 41.5 34.5 102 0 2 2 0 4 10 8 2 11 (CR)(LF) A B C D E F G H I J K L M N O P Q

An alarm status message is transmitted whenever there is an alarm that occurs for the firsttime and whenever the alarm status changes:

ALARM: 4 13 (CR)(LF) R S T

A halt indication is transmitted when the system is stopped for any reason:

STOP: KEY (CR)(LF) U V

Key: A) System is ON or OFF

B) Actual Tank Temperature in °C, as sensed by the Output RTD

Mydax, Inc.

Appendix A RS-232 Page A-4

C) Set point Temperature in °C

D) Calculated temperature in °C of the refrigerant line at the suction pressuretransducer

E) Pressure in PSIg of the refrigerant line at the suction pressure transducer

F & G) Temperature in °C in the refrigerant line at the Superheat and CondenserRTDs

H) Temperature in °C in the refrigerant line at the Discharge RTD (2-stage designonly)

I ) Temperature in °C in the refrigerant line at the Subcooler RTD (inactive)

J & K) Valve drives of evaporator valves 1 and 2; valve 2 is inactive in singlechannel systems (See "DIAGNOSTIC DISPLAYS, Test Panel 1" for explanation of drivesignals.)

L, M & N) Bypass, Superheat, and Desuperheat valve drives. Desuperheat is notavailable in all designs.

O & P) Heater drive signals; Heater 2 is inactive in single channel systems (See"DIAGNOSTIC DISPLAYS, Test Panel 1" for explanation of drive signals.)

Q) Flow rate in gallons-per-minute(GPM) of recirculation fluid. On systems without aflow meter, this number has no meaning.

R) Any active alarms, by code # (See the next section for a description of alarmcodes.)

S & T) Actual code # for the alarm

U) Stop is displayed whenever the system is halted

V) Indicates the origin of the Stop Command (status message "S") whether it isfrom the system front panel (KEY), the external stop line (EXT.), an RS-232Ccommand (RS232) or it originated from a fatal alarm (FATAL).

Mydax, Inc.

Appendix A RS-232 Page A-5

RS-232C ALARM CODES

The following alarm codes may be transmitted in an AL or AH status message. Not all ofthese codes are possible in every system:

1 CONDENSER HOT: The reading from the condenser RTD indicates atemperature in excess of +50°C. The system microprocessor incrementallyreduces the evaporator valve drive to reduce the flow of refrigerant into theevaporator. This effectively reduces the heat-rejecting capacity of thesystem, which keeps the temperature in the condenser at acceptable levels.

2 LOW FREON: Indicates pressure of refrigerant is low. Have unit serviced byMydax or a qualified service center.

3 RTD OPEN: Indicates that one of the system RTD's has failed and thesystem has shut down to protect itself. The main display shows which RTD isfaulty by giving its pin number location on the M1002 or M1005 circuit board.

4 PUSH RESET: The interlock loop has been broken and the reset switch mustbe depressed to re-establish it.

5 FILL TANK #1: The tank 1 low level sensor has tripped. If coolant is notadded "soon", the "empty" sensor trips and the system shuts down.

6 Inactive in this system.

7 FILL TANK #2: The tank 2 low level sensor has tripped. If coolant is notadded "soon", the "empty" sensor trips and the system shuts down.

8 LOW FLOW: Indicates that a low flow condition exists in one of therecirculating channels.

9 Inactive.

10 PHASE MISSING: Indicates one or two of the three electrical power phasesis missing. Inactive on single-phase units.

11 PHASE REVERSED: Indicates incorrect electrical power phase relationship. May be corrected by reversing any 2 phases. Inactive on single-phase units.

12 Inactive in this system.

13 LOW AC LINE: Indicates a low voltage condition exists on the input AC line.

14 RESISTANCE LOW: Indicates that the deionized water resistivity hasdropped below the programmed limit.

15 TANKx TOO HOT / EXTREME TEMP: Indicates that the tank temperature iseither more than +10.0°C above its upper maximum set point, or too close tofreezing and that the system has shut down.

This page is intentionally left blank.

Rick Pugel
Rick Pugel

sheet 1 of 1 DWG. B2343, Rev 3

Mydax, Inc . Auburn, CA

1M9W-S Chi l ler F lu id Schemat ic

January 25, 2001Water Coo led

HighPressure

Swi tch

FilterDrier

Condenser

Water F low Control Valve

Capi l lary Tubes

Drain

Condenser RTD

CondenserCool ing Water

1 .5 Gpm @ 75°F, P = 20 Psi

Evaporator

R-2

2C

om

pre

sso

rW

ith

Suc

tion

Acc

umul

ator

P ressureRel iefValveSet at

110 Psi

10 M

icro

nP

arti

cula

te

Filt

er

P ressure Gauge

Coolant Supply

+15°C to +25°C

10 Gpm @ 100 Ps i

Coolant Return

HeatExchanger

Evaporator Valve

Sight Glass

Ref

rige

rant

Liq

uid

Tank RTD (Instal led Through Side)

TankHeaters

Level Swi tches

TankBaff le

10 Gal lonPolypropylene Reservoir

1 Hp Mult i -StageCentr i fugal Pump

Output RTD

* Refr igerant control valves are set cont inuously by the system microprocessor.

* Al l RTD's are read cont inuously by the system microprocessor.

#4,742,689#4,918,931#4,934,155

This circui t is coveredby one or more of thefol lowing U.S. Patents:

Rec

eive

r

L inearPressureSensor

HP160

PSIG

3/4" Copper 90 's

1/4" Ball Valve

1/2"

1"

1"

Power

20A #12 AWG

24VAC / Inter lock Loop isRed #18AWGRefr ig valves are wired in Yel low

High Vol tage Wir ing Chart : (Al l HV wire is Black)

Low-Vol tage Wir ing Chart :

DC / Logic wir ing is B lue #18 AWG

Power

Evaporator

Reset

6 9

RL1,C

RL1

A

B

W h

Red

HighPressure Swi tch

Red

C O N 1T1

T2

T3

Keyboard

J1

56

56

50

50

23 Reset

M1004 Power Supply , Phase Detector & Output Drivers

50 +5V

20 Comp

EV1

3+

4

2

1

S S R 1

L3L2L1

Red

M10

02 I

nput

s &

RT

D's

LCD Display

8

5RL1,B

J2

J1

J3

RS-232Connector

J2

M1001 Contro l ler

Power

24 VACOut

Gnd In

Gnd

24

VA

C40

VA

C O N 1

20 Amp

D2402

4

7

RL1,A

L3

L2

L1

Compressor

Crankcase Heater

Grn

P u m p

53

TankEmpty

FillTank

22 Tank1 Lo

+5V 49

HTR1 23

sheet 1 of 1DWG. B2344, Rev 3

Mydax, Inc. Auburn, CA

1M9W-S Chi l ler Electr ica l Diagram

Water Coo led January 25, 2001

D2440

23+ 10

00

W

S S R 4

14

23+ 10

00

W

D2440

D2440

S S R 2

S S R 3

1

1

2

4

3+

4

Tank Heaters

10

00

W

208/230 VAC, 3 phase

Grn

Tan

k

RT10

Con

d.O

utpu

t

RT3

RT4

RT7

Tri

m_0

1

RTD's

1

2

M1007LED PS

M1010 Inter faceLinear

PressureSensor

4

5

67

J4 J4

Blue

Gnd

13' of 12/4 Cable with L-15-30 Plug

5455

E M O

Over Temp

13' of 12/4 Cable with L-15-30 Plug

sheet 1 of 6 DWG. B2240

Mydax Inc. Auburn, CA.

Mydax Controller M1001

'CPU'

D0

D1

D3

D2

D6

D7

D5

D4

A14

A13

+5V

2627 28 1 28 26

A0

A1

A8

A4

A11

A12

A10

A9

A7

A6

A5

A3

A2

CE OE

A15 WRN

U22 U16

27C256

EPROM

6264

Read/Write Memory

20 22 14 20 22 27 14

11

12

13

15

16

17

18

19

10

9

8

7

6

5

4

3

25

24

21

23

2

D4

D5

D7

D6

D2

D3

D1

D0

A0

A1

+5v

1

2

3

4

5

6

7

8

11

9

14

15

16

18

20 19 24

22 23 21 14

RDN

WRN

8254AN

U17

82C54

CounterTimer

100 Hz

200 KHz

Baud Clock

10

13

17

A12

A13

A14

MREQN

A15

U14

8251N

KEYN

Nov 10, 1997

0.1uf

+5V

ResetN

In4

ResetN

+5V

U21

Max690

8

7

6

54

3

2

1

2

3

41

1kWaitNJ7

R110k

0.1uf8.0MHz

D0

D1

D3

D2

D6

D7

D5

D4

26

27

20

19

22

21

14

15

12

8

7

9

10

29

17

16

13

30

31

32

33

34

35

36

37

38

39

40

1

2

3

4

51125

6

24 "CPU"

Z84C0008

U9

M1N

IOREQN

MREQN

WRN

RDN

A0

A1

A3

A2

A6

A7

A5

A4

A8

A9

A11

A10

A14

A15

A13

A12

+5V

8.0 MhzOsc. U15

+5V

NMIJ7

IntJ7

10K

10K

1K

1K

U7 U12

1

2

13

12

3 4

8255N

8254BN

CPr

Q11

10

12

13

Qn 8ClD

U8

9

+5V

RTC

In3

CPr

Q3

4

2

1

QnClD

U8

5

U77

45

3RxRdy

TxRdy fromsheet 2

4 MHzto sheet 2

Bat.

LithiumBattery

U449

10

8

74

HC

13

8

A

B

C

1

2

3

456

15

14

13

12

11

10

9

7

sheet 2 of 6 DWG. B2240-2

Mydax Inc. Auburn, CA.

Mydax Controller M1001

IOREQN

A7

RDNWRN

U13

U12

A0

A1

A2

A2

A3

A4

IN 1

IN 0

IN 2

IN 3

IN 7

IN 6

IN 4

IN 5

OUT 8

OUT 4

OUT 0

OUT 12

OUT 16

OUT 20

13 12

D1

D0

D2

D3

D7

D6

D4

D5

+5V

SeikoL4042

LCDDISPLAYMODULE

124

5

6

14

13

12

11

10

9

8

7

10K 10K10K10K10K 10K

A0

A1

A2

+5V

KEYNU42

5 ea.1N914

10K10K10K10K 10K 10K

KEYN

SIP

D7D6D0 D5D1D0 D2 D3

74HC240

U41

KEY MATRIX(26 Keys)

11 8 13 6 15 4 17 21

19

9 12 7 14 5 16 3 18

D2

D3

D4

D5

D6

U10

82C51A

A0

PCLR

RDN

WRN

BAUDCLOCK

8251N

4.0MHz

+5V

26 4

12

21

13

10

8

7

6

5

2

1

28

27

925

11 20

Rd

CTS

Td

RTS

U4MAX232

15

14

3

17

19

23

12

9

11

10 7

14

8

13

RS-232Interface

0.1uf

0.1uf

Jan. 15, 1996

U31Out 24

Out 28

RTC

SIP

+5VVLC

3

10K

LCD R/W

LCD RS

LCD EN

37

38

39

40

1

2

3

4

U11

8255

"A"Section

D7 27

28D6

D5 29

30D4

D3 31

32D2

D1 33

34D0

5 36

RDN

WRN

8255N

6 7

35 26

ResetN

TxRdy

RxRdy

+5V+

+

+

+

+

10

10

10

10

10

6

2

16

1

3

4

5

15

J3

11

12

13

14

15

654

3

2

1

C

B

A

74

HC

13

8

to sheet 1

74

HC

13

8

A

B

C

1

2

3

456

15

14

13

12

11

10

9

7

74

HC

13

8

A

B

C

1

2

3

456

15

14

13

12

11

10

9

7

sheet 3 of 6 DWG. B2240-3

Mydax Inc. Auburn, CA.

Mydax Controller M1001

Input-Output

11

12

13

17

16

15

14

D0

D1

D2

D3

D4

D5

D6

D7

IN 5

U3

74

HC

24

4

18

3

16

5

14

7

12

9

191

11

8

13

6

15

4

17

2

T2 Low

Interlock

T1 Low

Reset Rly

Freon Lo

Ext Stop

Ext Start

J1-17

J1-18

J1-15

J1-13

J1-14

J1-11

J1-14

J1-16

J1-6

J1-5

J2-4

J2-3

J1-8

J1-7

J1-10

J1-9

T3 Low

Miss Ph.

Rev Ph.

Key Sw.

RemoteDig/Ana

24

23

22

21

20

19

18

2

17

4

15

6

13

8

11

1 19

9

12

7

14

5

16

3

18

74

HC

24

4

U1

10k

+5V

IN 7

D7

D6

D5

D4

D3

D2

D1

D0

2

17

4

15

6

13

8

11

1 19

9

12

7

14

5

16

3

18

74

HC

24

4

U2

10k

+5V

IN 6

D7

D6

D5

D4

D3

D2

D1

D0

Res On/Off

On=Remote

On=extvirtual

On=VoltSet En.

On=noFudge

Baud

Dip Switch

PCLRN

74

HC

27

3

U18

9

6

5

2111

3

4

7

8D3

D2

D1

D0

Out 28

April 24, 1996

Switch 2

Switch 3

+5V

10k

100K

+5V

10k

100k25 10

100k

10k

+5V

U1182C55 "B

U1182C55 "C

D4

D5

13

14 15

12

16

1918

17

D7

D6

LCD R/W

LCD EN

LCD RS

EV1J2-20

EV2J2-19

EV3J2-18

EV4J2-17

EV5J2-15

U24ULN2003A

+5V9

8

1

2

3

4

5

6

7 10

11

12

13

14

sheet 4 of 6 DWG. B2240-4

Mydax Inc. Auburn, CA.

Mydax Controller M1001

Output Dec 20, 1995

U197

4H

C2

73

19

16

15

12

9

6

5

2

111

3

4

7

8

13

14

17

18

PCLRN

Out 8

D0

D1

D2

D3

D4

D5

D6

D7

ULN2003A

9

16

15

14

13

12

11

810

7

6

5

4

3

2

1

U16

+5V

Beep

220

220

220

220

+5V

Compr.J2-13

PumpJ2-16

"Alarm"J2-14

LED

LED

LED

J8-1

J8-2

J8-6

"Power"

D7

D6

D5

D4

D3

D2

D1

D0

U32

74

HC

27

3

19

16

15

12

9

6

5

2

111

3

4

7

8

13

14

17

18

U28

74

HC

27

3

19

16

15

12

9

6

5

2

111

3

4

7

8

13

14

17

18

Out 4+5V +5V

DVB

DVA

High R J4-4

POS R J4-3

DIB J4-6

DIA J4-5

LED

+5V

+15V

Run DVM

DVC

1K

1K

1K

1K

DVMRDY

+5V+5VOut 0

14

13

11

6

4

3

9 1

2

5

7

10

12

15

74

HC

17

4

U5

14

13

11

6

4

3

9 1

2

5

7

10

12

15

74

HC

17

4

U6

D5

D4

D3

D2

D1

D0

1K

1K

1K

1KRA J1-3

RB J1-4

RC J1-1

RD J1-218

17

14

13

8

7

4

3

11 1

2

5

6

9

12

15

16

19

74

HC

27

3

U20

PCLRN

Out 12

D0

D1

D2

D3

D4

D5

D6

D7 SpareJ2-6

FAN 3J2-5

FAN 2J2-8

FAN 1J2-7

HTR 3J2-10

HTR 2J2-9

HTR 1J2-12

U26 ULN2003A

9

16

15

14

13

12

11

810

7

6

5

4

3

2

1

+5V

sheet 5 of 6 DWG. B2240-5B

Mydax Inc. Auburn, CA.

Mydax Controller M1001

Analog March 20, 2000

U38

4

5

6

7

12

11

10

9

8

14 13 3

1

16

15

2

10.0K*

10.0K*

RTD OutJ1-24

Set 1J4-16

Set 2J4-15

AC Det.J2-1

T1 Ext.J4-14

T2 Ext.J4-12

T3 Ext.J4-13

U35

DG

50

8C

J

-15V

DVA

DVB

DVC

+5V

D0

D5

D4

D3

D2

D1

D0

D7

D6

D5

D4

D3

D2

D1

+5V

IN 0

IN1

1

20

19

18

17

16

15

14

13

12

11

10

9

40

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

8

7

6

5

4

3

2

+5V

Run DVM

-15V U4379L05

-5V

1 uf+0.1uf

200K*

0.1uf

.056uf

200kHz

+1uf

200K*

.0047uf

47

+5V

1uf+

DVMRDYU27

1 2

U36

ICL7109

74HC14

+15V

3

2

8

1

7

6

5

U38

TL032CP

+10.24V

-10.24V

10

.0k

0.1

%

10.0K 0.1%

20.0K*

10

.0K

*

D0

14

13

D1

D2

12

11

D3

D4

10

9D

5

D6

8 7D

7

U40U39

AD7528KN

U40

+5V

A0

Out 16

17

6

16

15

5 4 18

Ref A Ref B

12

3

76

5

32

19

20

1

TL032CP

Gain DacJ1-230 to -5.1V

VFanJ2-20 to +10.0V

DI AmpJ4-11

40.2K 0.1%

10.0K 0.1%

10.0K 0.1%

40.2K 0.1%

10.0K 0.1%

30.1K 0.1%

10.0K 0.1%

10.0K 0.1%

10K*

10.0K 0.1%

10.0K 0.1%

10.0K 0.1%30.1K 0.1%

30.1K 0.1%

+15V

+5.12VJ4-8

Test Point Aadjust to +1.024V

Note:1. Resistors with *are 1/4W 1% metal film

2

Ref-02CP U37

6

54

"Adj"

20

.0K

0.1

%

10

.0K

0.1

%

10

.0K

0.1

%

10

K

10.0K 0.1%

10.0K 0.1%

10.0K 0.1%

20.0K 0.1%20.0K 0.1%10.0K 0.1%

RTD X5

sheet 6 of 6 DWG. B2240-6

Mydax Inc. Auburn, CA.

Mydax Controller M1001

Optional Jan. 15, 1996

10

K

10

K

10

K

10

K

10

K

+5V

2K

2K

2K

2K

2K1K

1K

Ctr1J5

Ctr0J5

+5V

0.1uf

13

10

CounterTimer

82C54

U23

8254BN

WRN

RDN

14212322

241920

18

16

15

14

9

11

8

7

6

5

4

3

2

1

A1

A0

D4

D5

D7

D6

D2

D3

D1

D0

FlwSw3J5

FlwSw2J5

FlwSw1J5

200KHz

U30U30

(optional)

Tank1J4-9

TL032CP

10.0K 0.1%

20.0K 0.1%

20.0K0.1%

0.1uf0.1uf

+15V-15V

84 5

67

3

21

16

1

2

3456711101289

13

1415

A1

+5V

++

+10.24V

+5.12V PinJumpers

EDCBA

Out20

AD7542KN

U29

D3

D2

D1

D0

A0

A0

D0

D1

D2

D3

U33

AD7542KN

Out24

A B C D E

PinJumpers

+5.12V

+10.24V

+ +

+5V

A1

1514

13

98 12 10 11 7 6 5 4 3

2

1

16

12

3

76

54 8

-15V +15V

0.1uf 0.1uf

20.0K0.1%

20.0K 0.1%

10.0K 0.1%

TL032CP

Tank2J4-7

(optional)

U34 U34

Range A B C D E

+5.12V on - - on -

+10.24V - on - on -

+-5.12V on - on - on

+-10.24V - on on - on

PinJumpers

sheet 1 of 1 DWG. B2242

Mydax Inc. Auburn, CA.

RTD and Inputs M1002

Dec 28, 1995

100

100

100

100

100

100

100

RT12

RT11

RT10

T3 Evap

T3 Out

T2 Evap

T2 Out

T1 Evap

T1 Out

Condr.

Sup Ht.

Bypass

100

100

Gain DACJ1-23

5VRTD

120 0.1%

100 0.1%

100K*

1.27K 0.1%

100+

10K 0.01uf

62

U1

-15V +15V

43 7

19 S1

S220

21 S3

S422

23 S5

S624

25 S7

S826

11 S9

S1010

9 S11

S128

7 S13

S146

5 S15

S164

A0 A1 A2

A3

17 16 15

14

14

151617

A3

A2A1A0

4 S16

S155

6 S14

S137

8 S12

S119

10 S10

S911

26 S8

S725

24 S6

S523

22 S4

S321

20 S2

S119

U5DG506A

U6DG506A

18

1

27+15V

+5V

-15V

28

28

-15V

+5V

+15V27

1

18

100K

100K

100K

100K

100K

100K

100K

100K

RA J1-3

RB J1-4

RC J1-1

RD J1-2

U3+

+U2

10K 0.001 uf

1.00K0.1%

9.09K 0.1%

76

5 4

672

3 4

LT1001

TL032

-15V

-15V

+15V

5.12VJ1-8 +

U2

+15V

5VRTD

10K

10K

12

3 8

LT1001

RTD's 0.1uf

+

Bridge

24VAC

24VAC

Ext 4

Stop

Start

Com.

+

U8

U8

U7

PS2501-2

PS2501-2

toAna. En. -28-

toStop-26-

toStart-27-

2K

2K

2K

10K

47uf

1N914

6

54

3

8

7

1

2

1

2

4

3

7

58

6

LT1001

RTD OutJ1-240.001

uf2

34

7

6

+15V

U4+

-15V

12.1K 0.1%

10.0K 0.1%

A

B

C

1. Resistor with *are 1/4W 1% metal film

PS2501-2

40.2K 0.1%

50.0k 0.1%

100k 0.1%

"Gain"

"Zero"

0.1uf

0.1uf

0.1uf

0.1uf

0.1uf

0.1uf

0.1uf

0.1uf

0.1uf

0.1uf

0.1uf

U3+

sheet 1 of 2 DWG. B2244

Mydax Inc. Auburn, CA.

Power Supply M1004

24 VAC

GND

47

vo

ltV

ari

ste

r

V

1N4002

4700uf 50V

June 19, 1996

Fuse

In

Out

Out

Out

Out

Out

511*4

76

5 30

.1K

0.1

%1

0.0

K 0

.1%

1.0

K*

750*

U4+

0.1 10uf+

+15V100mA

U2LM317T

+U4

9.76K*

1.0K*

1.0

K*

10

.0K

0.1

%1

0.0

K 0

.1%

3

21511*

1

0.1

U3LM317T

+

15.1 2W

2.0K*

++5V200mA

10uf

10uf

-15V100mA

+

20 1W 1

+

U1LM337T

0.11000uf 50V 500

2.49K*

249*

Q2

00

4L

3

220 6

4

2

1 47

1K 1EV1

Q1MOC3032

U6EV1J2-20

EV2J2-19

U7MOC3032

Q2

EV2 11K

471

2

4

6220

Q2

00

4L

3Q

20

04

L3

220 6

4

2

1 47

1K 1EV3

Q3MOC3032

U8EV3J2-18

EV4J2-17

U9MOC3032

Q4

EV4 11K

471

2

4

6220

Q2

00

4L

3Q

20

04

L3

220 6

4

2

1 47

1K 1EV5

Q5MOC3032

U10EV5J2-15

Freon Control Valves

1N4002

ACDetJ2-1

+

+U5

U5

1

2

3

76

5

1uf

1N914

200K*

200K*4.02K*

511*10M

LM358A

PowerConnectors

TL032

8

4

+15V

-15VU18

AL

Run

43 +

45 +

42 -

44 -

1K

1K

PS2501-2

6

5

8

7

1

2

3

4

10K

Q8

2N222210K

10K

2N2222

Q7

10K

+5V

20 Comp.

21 Pump

22 Alarm

23 Htr1

24 Htr2

25 Htr3

26 Fan1

27 Fan2

28 Fan3

29 BeepJ2-1110K

10KJ2-5

J2-810K

10KJ2-7

J2-1010K

10KJ2-9

J2-1210K

10KJ2-14

J2-1610K

10KJ2-13

+5V

50 +5V

49 +5V

48 +5V

47 +5V

46 +5V

41 VFAN

+5V

J2-2

0.1uf

sheet 2 of 2 DWG. B2244-2

Mydax Inc. Auburn, CA.

Phase Detector M1004

April2 4, 1996

Note:1. Resistors marked with are1% 1/4W, all other resistors are 5% 1/4W.

4

4

8

-15V

+15V

4

8

84

+15V

Loop40

Gnd39

0.1uf

1M

2

Jumpers

"VAC"220210200190180

1N914 0.1uf

1.5

8K

*

1.5

0K

*

1.4

3K

*

1.3

3K

*

1.2

7K

*

0.1uf

U11+

6

5

7

7

5

6

+U14

0.001uf

+5V

1.00M

1.00M 1.00M

0.001uf

1.00M

1.00M

0.001uf0.001uf

1.00M1.00M

1.00M

1.00M

1.00M 1.00M

0.001uf 0.001uf

1.00M

470K

470K

74HC14

+5V

8

InterlockLoop

RelayQ1BS170

1N

40

02

1K

+5V

"OK"

GreenLED

121

13

U16

Miss Ph.J2-4

Rev Ph.J2-3

1.0uf

10M 896

54

3

U17U16

74HC27

11

10

98

U161K Red

LED

"REV."

+5V

RedLED

+5V

+5V

"UNBAL"

RedLED

1KU17U17

LM358A

LM358A

U17

1.0

M

1213

1N914

0.1

uf

2

1.0

M

0.1

uf

11N914

LM393A

LM393A

5

4.7K

4.7K

4.7K

10

K

470K

1

10

K2

3+U14

U12+

5

6 10

K

+5V

7

1

470K

+5V

10

K

2

3+U12

65

4.7K

3

2

U11+

1

U13+

10K*

10K*

7

6

5

3

2

1

10K*

10K*

+U13

10K*

10K*

74HC74

2 6

4

3

1

U15

Cl

Pr

Qn

Q

D

C

12

11

C

D

Q

Qn

Pr

Cl

U15

10

131K

"LOWAC"

11 10U17

"Scale"JumpersX2X1

8.6

6K

*

18

.7K

*

-15V

L1

L2

L3

Input Range190-480VAC

0.1uf

0.1uf

sheet 1 of 1 DWG. D2729

Mydax Inc. Auburn, CA.

M1007 LED Power Supply

Sept 24, 1997

0.1

5.11 watt

1000uf50V

24 VAC

Common

Polyswitch

LM317T

1.0Positive

Negative

250 mA @4.1 voltto Display LED backlight

Heat Sinked

In Out

Ref

1N4002

sheet 1 of 1 DWG. D2616

M y d a x I n c . Auburn, CA.

Inter face M1010

Jan 25, 2000

15.0K 0.1%10.0K 0.1%

+U3

1

2

3 TL032

4

3

2

1

0.110K

Rt

Ct

10uf U1LM2907-8

Note:1. Resistors with *are 1/4W 1% metal f i lm.

2. For Proteus 500C-highCt=0.0047uf, Rt=69.8K*Rp=50K , 100Hz=0.714V

3. For Proteus 550CCt=0.01uf, Rt=49.9K*Rp=50K , 100Hz=0.97V

4. For Gems 1/2" Lo range, Rp= 20k, Rt=30.1k, Ct= 0.01uf100 Hz=0.595 V

Rp

8

7

6

5

1

2

3

Flow In

C o m m o n

Shield

+15V

To J4-14 T1 Ext

To J4-12 T2 Ext

8 9 10

Flow Gnd Press.

U2

+10 Ref.

+ Pres.

- Pres.

C o m m o n

1.02K *

21

8

3

4

5

6

7

-15 V

+15 V

7

45

6

INA114

Opt ional

0.10.1

-15 V

1 M

10K

Pressure Zero

10.0K 0.1%J4-11 DI Amp

J6

10.0K 0.1%15.0K 0.1%

+U3

6

5 TL032

Opt ional

7

4

8

Alarm

C o m m o n

Alarm NC

Alarm NO

Relay

11

12

13

14

200K 0.1%

Optional forGems F lowmeters

0.0047 100k

2k

J4-16 Set1

Us ing Sensym STImV300G1A sensor :0 psig= 1.125 vol t , 300 psig= 8.625 vol t

Us ing Sensym STImV300A1A sensor :0 psia= 1.125 vol t , 300 psia= 8.625 vol tSea level mean pressure= 14.7 psia = 1.4925 vol t

+5V