MYDAX, INC. INSTRUCTION/OPERATIONS MANUAL 1M9W...
Transcript of MYDAX, INC. INSTRUCTION/OPERATIONS MANUAL 1M9W...
advanced temperature control technology
MYDAX, INC.
INSTRUCTION/OPERATIONS MANUAL
1M9W-S WATER COOLED CHILLER
Serial Number 120-07XX
MYDAX, INC.
12260 Shale Ridge Road
Auburn, CA 95602
(530) 888-6662
FAX: (530) 888-0962
March 2001
Lawrence Berkeley Laboratory
TABLE OF CONTENTS
I. SPECIFICATIONS ....................................................................................................... 1
II. SYSTEM OVERVIEW ................................................................................................. 2
III. INSTALLATION ......................................................................................................... 4
IV. FRONT PANEL CONTROLS ..................................................................................…… 5
V. ERROR MESSAGES ................................................................................................... 7
VI. DIAGNOSTIC DISPLAYS .......................................................................................... 8
VII. SERVICE & WARRANTY .......................................................................................…. 11
VIII. RESHIPPING & LONG-TERM STORAGE PREPARATION ............................ ..................… 12
IX. APPENDIX A: RS-232C SERIAL INTERFACE OPERATION
X. APPENDIX B: DRAWINGS
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 1
SPECIFICATIONS
SYSTEM CAPACITIES
Cooling Capacity @ +20°C 2500 Watts
Coolant Temperature Setpoint Range +15°C to +25°C
Coolant Output Temperature Stability ± 0.05°C
Polypropylene Reservoir Volume 10 Gallons
Recirculating Coolant Low Conductivity Water
Coolant Flow/Pressure 10 Gpm @ 100 Psi (Bypass Provided)
Recirculating Supply/Return Fittings 1" Stainless Steel FPT
Condenser Water @ 75°F 1.5 Gpm Required (∆P = 20 Psi)
Condenser Water Connections 1/2" Stainless Steel FPT
Electrical Service 208/230 volt, 60 Hz, 3 phase, 20 ampWith 10' line cord and L15-30P plug.
Physical Parameters 42"H x 24"W x 33"D, 450 lbs.
STANDARD FEATURES
System is complete with microprocessor-controlled low-stress refrigeration circuit, recirculating pump and fluidreservoir. R-22 refrigeration circuit uses all-brazed construction for extra strength. The heavy-duty frame isconstructed of welded steel tubing equipped with locking casters.
The microprocessor-based control system includes an extensive monitoring capability including comprehensivecontrols, error messages and diagnostics. System status is indicated via a two-row (40 characters each)alphanumeric LCD (liquid crystal display) and with red light-emitting diodes (LED's). The control keyboardemploys membrane switches with a sealed polycarbonate overlay for protection from liquid spills. This chilleris complete with a liquid-filled panel mounted pressure gauge, an internal pressure bypass circuit, a full-flow10 micron particulate filter and an RS-232C Interface for remote control and monitoring.
SAFETY FEATURES
1. Warning & Error Messages: including coolant over-temperature warning & shutdown, low tank level warning& shutdown and others (see ERROR MESSAGES section).
2. System Diagnostics: including coolant & freon temperatures, valve and heater drives and others (seeDIAGNOSTIC DISPLAYS section).
3. Integral compressor refrigerant high pressure protection. 4. Circuit breaker & contactor. 5. Interlock loop, including reset switch. 6. Thermal protection of pump and compressor motors. 7. Manufactured and wired in accordance with IBM Non-Product Safety Design Standards.
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 2
SYSTEM OVERVIEW
System Fluid Schematic
Refer to drawing #B2343, the fluid schematic. The heart of the design is the evaporator valve. This is a thermal-electricexpansion valve, controlled directly by the system's embedded microprocessor. Hermetically sealed, it consists of aspring-loaded needle valve in contact with a bimetallic plate. The plate is wound by a coil of wire connected to terminalson top of the valve. The curvature of the plate, and therefore the position of the needle valve, varies with its temperaturewhich is controlled by electrical current flow through the coil. So by controlling the duration of electrical pulses appliedto the valve terminals, the microprocessor opens the valve to a precisely determined point. This passes a preciselydetermined flow of freon to the evaporator, allowing for exceptionally stable recirculating temperatures. This systemis designed to control the recirculating output temperature to ±0.05°C across the system operating range.
The microprocessor sets the exact position of the valve based upon the system heat load. If the load increases, theevaporator valve is opened slightly, passing more refrigerant. If the load decreases, the valve is closed slightly, passingless refrigerant. During normal operation, the position of this valve stays nearly constant. Only major changes in heatload or system-wide power cycling cause large changes in the valve opening. In the case of a step-wise change in heatload, the microprocessor quickly drives the valve to the new setting and refrigerant flow soon settles at the proper level.
The valve drive setting is based primarily upon data received from RTD's (resistance temperature devices) located aboutthe circuit. The drawing shows RTD's at the evaporator valve, at the discharge line from the pump, at the reservoir andbetween the condenser and receiver. The microprocessor "reads" these and other sensors constantly and sets therefrigerant valve accordingly.
Thus refrigerant flow is truly proportioned, through a valve which only rarely cycles all the way open or shut. Besidesprecise temperature control, this allows continuous compressor operation without the normal addition of cycling, andtherefore failure-prone, pressure-actuated hot gas bypass valves. All other refrigeration circuit components are used asin conventional systems. All permanent copper joints in the refrigeration circuit are brazed for extra strength. Much ofthe circuitry is insulated to eliminate cooling capacity loss and unpredictable operation due to drafts or fluctuatingambient air conditions.
This system is designed to recirculate water. It is not designed to recirculate solutions of automotive antifreeze. Approximately 10 gallons are required to fill the polypropylene reservoir. The heating elements are stainless steelcartridge heaters. The freon evaporator is a coaxial heat exchanger, located in the recirculating return line leading to thereservoir.
The reservoir is fitted with two level sensors. One level sensor drives a FILL TANK alarm at the main panel, indicatingcoolant level has dropped somewhat. The second sensor, the TANK EMPTY sensor, is connected to the safety interlockloop and shuts the system down if tripped. Note that "empty" is a relative term only. The real function of this sensoris to prevent the coolant level from dropping so low as to expose the pump suction line.
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 3
System Electrical Diagram
Refer to drawing #B2344, the system electrical diagram. The central component of the electrical system is the M1001controller. It is microprocessor-based and communicates with and/or controls various other circuit boards andcomponents. Most controller circuitry is laid out on circuit boards mounted in the main control cabinet. The controlleris powered as long as the system circuit breaker is set, receiving 24 VAC power from a bulkhead-mounted transformer.
The controller "reads" the RTD's in the system via board M1002. RTD's are included for the recirculating outputtemperature and the reservoir, as well as for the freon circuit. Also routed through this board are the 100 and 120 •precision RTD calibration resistor circuits. The evaporator valve drive signal is routed through board M1004, as is thephase detector circuit.
The system interlock loop is controlled by the M1002 circuit board. In this application the interlock loop consists of thefreon high pressure switch, the tank over-temperature switch, the TANK EMPTY level sensor, the RESET momentaryswitch, one power relay coil and a relay pole (1R 5-8). The RESET switch serves to feed power to the relay, whichenergizes the contactor. When energized, the contactor feeds power back to the relay so the RESET switch may openup without cutting off power to the relay. If the freon pressure switch, the over-temperature switch or the level sensortrips, power to the loop is interrupted. The microprocessor senses this via the M1002 board. Provided the system haspower, if the loop trips out, the controller drives the PUSH RESET error message. The loop must be reset when the faultcondition is resolved.
The M1002 board also routes signals for the FILL TANK level sensor. If this sensor trips, the microprocessor drivesthe FILL TANK error message.
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 4
INSTALLATION
POWER CONNECTION
This chiller requires a 20 amp or larger circuit, 208/230 volt, 60 Hz, 3 phase and is equipped with a line cordand twist-lock L15-30P electrical plug.
PLUMBING INTERFACE CONNECTIONS
The chiller's 1" female pipe thread (FPT) fitting labeled "TANK OUT" must be plumbed to the inlet of thedevice to be cooled. The outlet of the device to be cooled must be plumbed to the chiller's 1" FPT fittinglabeled "TANK IN". This system is equipped with a ½" FPT fitting labeled "DRAIN". It may be desirable toinstall a valve at this location prior to the initial filling of the reservoir, for the convenience of future drainingprocedures.
The condenser cooling water supply must be plumbed to the chiller's ½" FPT fitting labeled "CONDENSERIN". The chiller's ½" FPT fitting labeled "CONDENSER OUT" must be plumbed to either a drain or the returnpath of the condenser cooling water circuit. Verify that condenser cooling water into and out of the chiller isunobstructed. Obstructions may cause loss of cooling capacity and eventual overheating.
Both the recirculating loop and the condenser cooling water loop are under pressure when the system isoperating. Check all fluid interface connections now to ensure against leaks.
CIRCUIT BREAKER
Set the circuit breaker mounted on the front of the system. Upon setting the circuit breaker, a message similarto the following appears on the 2 by 40-character main display:
This display indicates that the system's phase monitor circuit is checking for correct electrical power phaserelationship. Should a live and ground line be reversed, the phase detector reads PHASE MISSING. Correctthe error and the controller no longer indicates PHASE MISSING. If the display reads PHASE REVERSED,disconnect and switch two of the three phases.
WARNING
The system should be powered for a period of ½ hour before starting, toallow the crankcase heater to separate the refrigerant from the oil.
FILL RESERVOIR
To fill the system's reservoir, unscrew the fill plug on the top of the vertical stand-pipe for the tank and pourin the recirculating fluid. If the system is powered before the tank is filled, the "FILL TANK" error messageis displayed at the main panel, the alarm LED is lighted and the audible alarm sounds. Filling the tankeliminates the alarms. Replace the plug.
PUSH RESET BUTTON
The Reset button, located below the main panel, must be pushed upon powering the system. This resets thepower safety interlock loop, which protects the operator and electrical circuitry.
Output --- Warmup Delay --- Local Set 20.02°C 20.0°C
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 5
FRONT PANEL CONTROLS
All Mydax chillers are controlled by a microprocessor which is accessed via the system control panel. System controlsare simple, yet powerful and in concert with built-in diagnostics and error messages, are exceptionally comprehensive.
POWER LED: Indicates unit is powered (the circuit breaker is set).
RESET: Must be pressed prior to system start-up to energize the interlock loop.
START: Starts compressor and pump and turns on LED's. Once the start-up routine is complete thedisplay changes to the MAIN DISPLAY:
Shows the actual Output Temperature and Setpoint Temperature in °C. Also indicates thatthe local SET TEMPERATURE MODE can be enabled.
STOP: Stops both the compressor and pump and blanks the display.
MUTE ALARM: May be used to deactivate audible alarm for 10 minutes, leaving alarm LED on. Pressing theCLEAR key reactivates the alarm, which sounds until the fault condition is eliminated or theMUTE ALARM switch is depressed again. Pressing MUTE ALARM when no alarm isactive causes the alarm to sound once and the TEST ALARM display to appear.
SET: Enables SET TEMPERATURE MODE. SET MODE is disabled from panel if an alarm isactive or if the unit is in REMOTE. To set, depress:
SET: "Set Mode" appears at the right of the display. Cursor flashes at"units" digit of the temperature display.
ARROWS KEYS: Changes temperature setting in one degree increments unless "."(decimal) key is depressed.
"." (DECIMAL): Moves cursor to the "tenths" digit of the temperature display andcauses arrow keys to change setting in tenths of a degree.
KEYPAD: Changes temperature setting by entering numbers directly.
CLEAR: Erases an incorrect entry.
ENTER: Selects temperature setting and deselects SET mode.
TEST: Initiates Test Mode. See description under DIAGNOSTIC DISPLAYS section of this manual.
ENTER: Enters temperature selections while in the SET mode.
CLEAR: Erases incorrect temperature selections; exits Test Mode; clears Mute Alarm selection.
MODE: Toggles between the RS-232C remote control mode and Local Set mode.
ARROW KEYS: Changes temperature setpoint by 0.1° or 1°C increments/decrements; toggles tank
Output --- MYDAX --- Local Set 20.02°C 20.0°C
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 6
temperature, setpoint temperature and evaporator data view modes for multiple channelsystems.
"." (DECIMAL): Display shows model number and software revision date and copyright:
RUN PUMP: Inactive in this system.
X & Y: For future use.
Z: See Test Panel 9 in the Diagnostic Displays Section.
EMO SWITCH: This is a large red emergency off switch mounted on the left of the main panel. It shuts downthe entire system, excluding the controller.
1M9W-S 2001.01.18Copyright 2001 Mydax, Inc.
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 7
ERROR MESSAGES
A unique feature of Mydax systems is the error messages displayed on the 2 by 40-character liquid crystal display (LCD). The microprocessor constantly checks various points and parameters throughout the system and automatically displaysmessages when error conditions are sensed. Many displays are announced by an audible alarm and LED indicator. Theerror message persists until the fault condition is resolved, provided that the fault condition was not fatal, resulting ina system shutdown.
Condenser Hot Indicates high discharge pressure condition with temperature over +50°C. This is a warning messageonly. A separate mechanical overpressure switch, part of the safety interlock loop, shuts the systemdown in case of an overpressure condition. The purpose of this message is to allow maintenanceworkers to correct the problem at an early stage. (Caused by a clogged filter, low or warm condensercooling water flow or condenser scale build-up.)
Fill Tank Indicates low tank liquid level.
Tank Too Hot Indicates that the reservoir temperature is more than 10°C above the highest allowable set point.Microprocessor shuts down the system.
Push Reset Indicates that the reset button has not been pushed since the last system power-up or that the systeminterlock loop has a fault condition.
A series-wired safety interlock loop protects all Mydax systems, disconnecting AC power from nearlyall circuitry. The loop consists of the freon pressure switch, tank "hot" sensor and low level switch. If any link in the loop is opened, the "Push Reset" error message is displayed. Once the fault iscorrected, the Reset button must be used to re-establish loop integrity. The reset button must also bepushed at system power up.
Phase Missing Indicates that one or more electrical phases are missing.
Phase Reversed Indicates that electrical phases are incorrectly connected. Reverse any two legs.
Low AC Line Indicates a low voltage condition exists on the input AC line.
Open RTD Indicates that an RTD connected to the M1002 Input Board has failed and that the system has shutdown to prevent damage due to lack of data. The RTD at fault may be located by accessing Test Panel#8. The RTD must be replaced for the system to operate again.
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 8
DIAGNOSTIC DISPLAYS
Mydax chillers are provided with a computerized self-diagnostic capability. This system is equipped with 9 differenttest panels, which are accessed by pressing the TEST key, followed by the test panel number. Diagnostic mode isterminated by pressing the CLEAR key, and results in a display similar to that below:
MAIN DISPLAY
Diagnostic messages are displayed on the main 2 by 40-character LCD. Display #5 automatically appears when theTEST key is first depressed. Once in diagnostic mode, other displays can be selected by depressing number keys 1through 9. The following describes each of the test displays:
TEST PANEL #1:
Numbers represent the drive signals for the evaporator valve and tank heater. The range is 0 (minimum) to 20(maximum drive). Each digit represents 5% of the available 24VDC drive voltage. Avg Valve shows a 32second running average of the valve's drive, displayed above it.
TEST PANEL #2:
This display shows the refrigerant circuit RTD temperatures in °C. The display reads:
Limit = Max Evaporator Temp Suct = Suction Temp Psig = Suction PressureSup.Ht = Superheat Temp SHavg = Avg Super Ht Temp Cond = Condenser Temp
The condenser reading is a direct indicator of condenser temperature and pressure. The microprocessor sendsthe CONDENSER HOT error message if the condenser temperature exceeds +54°C.
TEST PANEL #3:
The first 3 sets of 4-digit numbers are hexadecimal. They represent correction values for the slow gain servosfor up to 3 reservoirs. The function of this servo is to dynamically adjust the main temperature control servoto near zero error and thereby maintain temperature stability.
The first 2 digits in each set of 4 show the gain offset. Each increment equals 0.05°C, so 14 Hex = 20 decimal= 1.0°C. This value is internally subtracted from the operator-entered temperature setpoint if the actualtemperature is above the setpoint, thus reducing the coolant temperature. When the actual coolant temperatureis below setpoint, the main servo is driving a heater and no adjustment is made to the setpoint. The setpointoffset is continuously monitored by the controller and adjusted according to current conditions.
The second 2 digits in each set of 4 show the time prescaler. This is a counter which increments or decrementsonce a second and times the next update of the setpoint offset. A typical value is 20 seconds per offset change. When the count reaches "00", the offset may or may not be changed and the count resets to "0A" Hex (10decimal). Together these numbers show that the controller is internally changing the control setpoint tomaintain temperature stability, and give the magnitude and timing of the change.
Output --- MYDAX --- Local Set20.02°C 20.0°C
Valve 7 Htr 8 Avg Valve 5 Htr 6
4.0 -4.8 48.2 35.0Limit Suct Psig Sup.Ht SHavg Condr
302B 0000 091F Z 0.00 G 51.95 14.4SS-1 SS-2 SS-3 RTD Reference SH Avg
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 9
The center of the display shows readings for the RTD "Zero" and "Gain" calibration resistors. Precisionresistors 100Ω and 120Ω (0.1% tolerance or better, representing ideal nominal RTD's) are used as a reference. Typical readings are shown.
TEST PANEL #4:
This display shows auxiliary voltmeter readings of Ext 1, Ext 2 and Ext 3. These are not used in this system. VAC is the 24 VAC internal control voltage; a typical value is in the range of 22 to 28. To the right of thisvalue is a 0. At the far right of this display is a time indicator in seconds. The timer stops at 255 seconds andis used internally for turn on routine procedures.
TEST PANEL #5:
This diagnostic shows the Output RTD (coolant) temperature in °C, the Output Setpoint temperature andOutput temperature slope. Slope is a measure of the direction and amount of the output temperature changeper 60 seconds.
TEST PANEL #6:
This diagnostic shows the Tank temperature with resolutions of 0.05°C and 0.01°C, and the Output temperaturewith resolutions of 0.05°C and 0.01°C.
TEST PANEL #7:
This display shows voltmeter readings for up to 3 optional water resistivity monitor interface raw data outputs. Each resistance monitor channel has a positive and a negative voltage reading. These readings areapproximately equal, but are of opposite polarity.
The refrigerant type that the control system is calibrated for is shown. For example: R22
The two numbers at the top, far right-hand side of this display represent the internally computed maximumevaporator temperature and a counter ranging from 0 to 99, which are used to adjust the valve drives andregulate the superheat temperature.
The second line of the right side of this display indicates the status of the lithium battery, mounted on theM1001 circuit board, used to run the system's elapsed run-time clock depicted in Test Panel 8 and the run/eventrecorder depicted in Test Panel 9. A "Bat. OK" message indicates that the battery is operational, while a "NoBat." message indicates that the battery is dead and should be replaced.
TEST PANEL #8:
The top left side of this display shows the alarm (error message) history. If there have been no alarms since the
-5.294 -1.292 -1.308 +26.46 0 255 Ext 1 Ext 2 Ext 3 VAC Secs
20.00 20.0 0.0 Tank Set DgMin
19.80 19.79 20.00 20.02
+ 0.000 + 0.000 + 0.000 R22 6.00 0- 0.000 - 0.000 - 0.000 Bat. OK
Alarms: Fill Tank ! KEY Run 356d 11:31:25
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 10
last history reset, the display reads "No Alarms". If alarms have occurred, the display shows them in sequence,like the main display. The history can be cleared 3 ways:
1. Power Off/On2. Press START Key when unit is stopped3. Press 0 Key when viewing Test Panel 8
The second line of the display can be read when the chiller is stopped. It indicates the reason that the chillerwas last stopped: KEY, FATAL, RS232 or EXT. The right side of the second line indicates the elapsed runtime on the system in days (from 0 to 9999), hours, minutes and seconds. This system is equipped with abattery which, if operational, saves the elapsed run time value when the system is stopped and restarted. Theelapsed run time is reset each time the system is restarted.
TEST PANEL #9:
This display provides run/event recorder data. The run/event recorder continuously records importantinformation into a non-volatile memory while the system is operating. Data is stored at one-second intervalsfor the last 120 seconds of run time and it is also stored at two-minute intervals for the last 240 minutes of runtime.
The first line of this display indicates the run time in hours, minutes and seconds prior to the last systemshutdown, the output and setpoint temperatures of whichever recirculating channel was last selected at the MainDisplay and the system-wide alarm history. The second line indicates which recirculating channel was lastselected at the Main Display, the evaporator, bypass, condenser and superheat RTD temperatures in °C, theaverage superheat temperature from Test Panel 3 and the flow rate. Both the evaporator temperature and theflow rate are specific to the recirculating channel being viewed. All freon circuit RTD temperatures aretruncated to the nearest 1°C for this display.
After the system is stopped and Test Panel 9 is selected, the memory is displayed at the last or most recentsecond (T- 0: 0: 0). The downward arrow key can be used to decrement time into the past. There are 120 "1-second slots" and 120 "2-minute slots". If the downward arrow key is held down, the time slots decrement atthe rate of two slots per second. The upward arrow key increments to more recent time slots. If the "Z" keyis depressed, the display goes to the oldest 1-second slot (T- 0: 1:59 if the actual run time was of at least thatduration). If the "9" key is depressed while viewing Test Panel 9, the display reverts back to "T- 0: 0: 0", thestop time.
The alarm messages are accurate for the slot that is current. If the display is on the minutes slot, then the alarmsindicated are any which have occurred during that 2-minute interval. Alarm messages cycle or flash in anidentical fashion to those appearing in either the Main Display or in Test Panel
T- 0: 0: 0 20.02 20.0 No Alarms.....Tank 1 4Ev 0By 37Cd 13Sh 14SA Gpm
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 11
SERVICE & WARRANTY
If a unit malfunctions, please contact the Mydax Service Department as soon as possible. Many small problems can leadto large problems if not dealt with immediately. Please have the serial number and model number on hand when calling.
Mydax Service Department: (530) 888-6662FAX: (530) 888-0962
RETURN OF UNIT FOR SERVICE
Many problems may be repaired by field exchanges of a module, pump, controller, etc. If return is required,please obtain a return authorization number from the Mydax Service Department or the unit may not beaccepted at our receiving dock.
Please refer to the shipping instructions which follow.
SERVICE OF REFRIGERATION UNIT
Nearly all repairs to the refrigeration unit involve brazing or silver soldering. This should only be done by aperson trained in refrigeration service and familiar with the Mydax system.
NOTE: Before servicing any refrigeration unit involving brazing, remove all freon from the system. Evacuateto a 400 micron vacuum to remove freon residues, then open all service valves to dry air or drynitrogen before use of a torch.
In particular, service of Mydax refrigeration circuits requires attention to the following:
1) Use caution to protect components from heat damage.
2) Prevent any moisture from entering the circuit, as Mydax proportional valves do not function with moisturepresent. Once moisture has entered the system it cannot be removed.
3) Remove insulation and instrumentation wiring or use heat shields to protect them from torch heat during work.
4) Before recharging the circuit, evacuate it to 200 microns at a minimum room temperature of 75°F for threehours.
ONE YEAR WARRANTY
Mydax, Inc. warrants that its temperature control system, and the component parts thereof, will be free from defects inworkmanship and materials for a period of one year from the date of delivery. In the event that warranty service isrequired, the customer is requested to send the equipment freight prepaid to the factory for service. Mydax will thenperform the appropriate service and will return the equipment freight prepaid.
If field service is required during the warranty period, the customer will be responsible for all travel expenses includingmileage. The customer will not be invoiced for any warranty service performed, with regard to either labor or materials,during a field service visit.
Mydax, Inc. 1M9W-S Water Cooled Chiller
Lawrence Berkeley Laboratory 12
RESHIPPING & LONG-TERM STORAGE PREPARATION
Reshipped systems should be protected from freezing temperatures in shipment or serious damage may occur. Freezingtemperatures can be encountered in air and over-mountain surface shipments in any month of the year. In-transit freeze-up can occur in the recirculating coolant loop and in a water-cooled condenser's cooling loop. To protect againstfreezing, all water must be removed from these circuits, or ethylene glycol must be added.
This system has a water-cooled refrigeration condenser. The following instructions apply to shipment or storagepreparation:
1. Feed in a charge of water-glycol mix into the condenser through the "Condenser In" connection. This can bedone by pump or gravity flow.
2. Feed water-glycol until mixture is visibly flowing out of the "Condenser Out" connection.
3. Plug the "Condenser In" and "Condenser Out" fittings to avoid leakage in shipment.
4. Since the system has been run with water, remove it from the reservoir via the "Drain" fitting. As much wateras possible should be drained from the system before shipment. Water adds significant shipping weight andmay damage electrical parts if it sloshes out of the tank.
5. Continue to remove as much water as possible with a wet/dry vacuum to prevent ice-up in the small "nooks &crannies" of the plumbing.
6. Plug the "Tank In", "Tank Out" and "Drain fittings.
Call Mydax for any helpneeded at (530) 888-6662
Mydax, Inc.
Appendix A RS-232 Page A-1
-Appendix A -RS-232 Serial Interface Operation
RS-232C INTERFACING
The use of an embedded microprocessor allows Mydax to offer an RS-232C (remote)interfacing capability. Mydax systems can be controlled from a computer with either theMYDAX REMOTE Window's ™ software package or any control software of the user's choice. Full control and monitoring is possible, allowing complete system operation from anyconvenient location.
Cable connection is via a rear panel DB-25S connector. Connector pin-out is as follows:
Pin 1 ShieldPin 2 Transmit DataPin 3 Receive DataPin 7 Common
A typical interconnect cable for an IBM-PC COM port should be wired as follows:
IBM-PC MYDAX
DB-25S Female Connector DB-25P Male Connector
1 12 23 34 45 56 67 7
20 20
Mydax, Inc.
Appendix A RS-232 Page A-2
RS-232C COMMANDS
The following ASCII commands can be transmitted to the system MPU via the RS-232C link:
RO Enables RS-232C control.
RF Disables RS-232C control. With remote disabled, system onlyresponds to RO.
GO Starts the compressor and pump.HA Stops the compressor and pump.
RP Run Pump only, active only on selected systems.
S?xy.z Sets fluid temperature (x, y and z are any numbers) of tank A,B or C. Settings outside the range default to the nearest limit. Entering a decimal point is optional, as the last digit is assumed to bethe tenths digit. For example: "SA180" selects +18.0°C for tank A,"SA245", "SA24.5" & "SA+24.5" all select +24.5°C for tank A,"SA93.2" selects +30.0°C for tank A.
TE1 Sends a transmission of abbreviated status including system on/offstatus, actual tank temperature and the set point temperature.
TE2 Causes transmission of flow and resistance, if the options exist. Forexample:
TE3 Transmits the contents of the 2 by 40-character main display over theRS-232 line.
TE4 Same output as TE1 plus RTD temperatures and valve & heater drivesignals.
TR or TR0 Turns off repeat transmission mode.
TRx Enables automatic periodic repeat transmission (x= 1-60 andrepresents the number of seconds between transmissions). Theinstructions which follow the TRx command are repeated at thetransmission rate that was set by the TRx command. TE1, TE2, TE3and TE4 are commands that can be repeated in all or anycombination.
TPx Changes the 2 by 40-character display at the main control panel toTest Panel "x" "0" = normal main display; "1" - "8" = diagnosticdisplays. See section on DIAGNOSTIC DISPLAYS. Does NOT causetransmission of the display over the RS-232C line (see command TE3)
ID Causes transmission of the model number and software revision date. For example:
"ID: 1VLH14W 1-24-2000"
Mydax, Inc.
Appendix A RS-232 Page A-3
AL Causes transmission of the alarm status. For example:
"ALARM: 0" denotes no alarm condition.
AH Causes transmission of the alarm history status. For example:"ALHIS: 13" denotes one alarm.
This history is the same as the Test 8 display. The history representsall alarms that have occurred since the last "Start" command.
CH Clears alarm history. This can also be cleared with the "Start" key orwith the "0" key when viewing Test Panel 8.
A delimiter between command strings can be a carriage return (CR), a semi-colon (;) or a comma (,). If a command is understood, a (>) is returned foracknowledgment. If a command is not understood or ignored then a (?) isreturned.
RS-232C STATUS MESSAGES
TE1 status messages include the following:
ON 19.95 20.0 (CR)(LF) A B C
Key: A) System is ON or OFFB) Actual Tank Temperature in °CC) Set point Temperature in °C
A TE4 status message consists of TE1/TE3 data plus RTD temperatures and valve & heaterdrives:
ON 19.9 20 -63 -8 41.5 34.5 102 0 2 2 0 4 10 8 2 11 (CR)(LF) A B C D E F G H I J K L M N O P Q
An alarm status message is transmitted whenever there is an alarm that occurs for the firsttime and whenever the alarm status changes:
ALARM: 4 13 (CR)(LF) R S T
A halt indication is transmitted when the system is stopped for any reason:
STOP: KEY (CR)(LF) U V
Key: A) System is ON or OFF
B) Actual Tank Temperature in °C, as sensed by the Output RTD
Mydax, Inc.
Appendix A RS-232 Page A-4
C) Set point Temperature in °C
D) Calculated temperature in °C of the refrigerant line at the suction pressuretransducer
E) Pressure in PSIg of the refrigerant line at the suction pressure transducer
F & G) Temperature in °C in the refrigerant line at the Superheat and CondenserRTDs
H) Temperature in °C in the refrigerant line at the Discharge RTD (2-stage designonly)
I ) Temperature in °C in the refrigerant line at the Subcooler RTD (inactive)
J & K) Valve drives of evaporator valves 1 and 2; valve 2 is inactive in singlechannel systems (See "DIAGNOSTIC DISPLAYS, Test Panel 1" for explanation of drivesignals.)
L, M & N) Bypass, Superheat, and Desuperheat valve drives. Desuperheat is notavailable in all designs.
O & P) Heater drive signals; Heater 2 is inactive in single channel systems (See"DIAGNOSTIC DISPLAYS, Test Panel 1" for explanation of drive signals.)
Q) Flow rate in gallons-per-minute(GPM) of recirculation fluid. On systems without aflow meter, this number has no meaning.
R) Any active alarms, by code # (See the next section for a description of alarmcodes.)
S & T) Actual code # for the alarm
U) Stop is displayed whenever the system is halted
V) Indicates the origin of the Stop Command (status message "S") whether it isfrom the system front panel (KEY), the external stop line (EXT.), an RS-232Ccommand (RS232) or it originated from a fatal alarm (FATAL).
Mydax, Inc.
Appendix A RS-232 Page A-5
RS-232C ALARM CODES
The following alarm codes may be transmitted in an AL or AH status message. Not all ofthese codes are possible in every system:
1 CONDENSER HOT: The reading from the condenser RTD indicates atemperature in excess of +50°C. The system microprocessor incrementallyreduces the evaporator valve drive to reduce the flow of refrigerant into theevaporator. This effectively reduces the heat-rejecting capacity of thesystem, which keeps the temperature in the condenser at acceptable levels.
2 LOW FREON: Indicates pressure of refrigerant is low. Have unit serviced byMydax or a qualified service center.
3 RTD OPEN: Indicates that one of the system RTD's has failed and thesystem has shut down to protect itself. The main display shows which RTD isfaulty by giving its pin number location on the M1002 or M1005 circuit board.
4 PUSH RESET: The interlock loop has been broken and the reset switch mustbe depressed to re-establish it.
5 FILL TANK #1: The tank 1 low level sensor has tripped. If coolant is notadded "soon", the "empty" sensor trips and the system shuts down.
6 Inactive in this system.
7 FILL TANK #2: The tank 2 low level sensor has tripped. If coolant is notadded "soon", the "empty" sensor trips and the system shuts down.
8 LOW FLOW: Indicates that a low flow condition exists in one of therecirculating channels.
9 Inactive.
10 PHASE MISSING: Indicates one or two of the three electrical power phasesis missing. Inactive on single-phase units.
11 PHASE REVERSED: Indicates incorrect electrical power phase relationship. May be corrected by reversing any 2 phases. Inactive on single-phase units.
12 Inactive in this system.
13 LOW AC LINE: Indicates a low voltage condition exists on the input AC line.
14 RESISTANCE LOW: Indicates that the deionized water resistivity hasdropped below the programmed limit.
15 TANKx TOO HOT / EXTREME TEMP: Indicates that the tank temperature iseither more than +10.0°C above its upper maximum set point, or too close tofreezing and that the system has shut down.
sheet 1 of 1 DWG. B2343, Rev 3
Mydax, Inc . Auburn, CA
1M9W-S Chi l ler F lu id Schemat ic
January 25, 2001Water Coo led
HighPressure
Swi tch
FilterDrier
Condenser
Water F low Control Valve
Capi l lary Tubes
Drain
Condenser RTD
CondenserCool ing Water
1 .5 Gpm @ 75°F, P = 20 Psi
Evaporator
R-2
2C
om
pre
sso
rW
ith
Suc
tion
Acc
umul
ator
P ressureRel iefValveSet at
110 Psi
10 M
icro
nP
arti
cula
te
Filt
er
P ressure Gauge
Coolant Supply
+15°C to +25°C
10 Gpm @ 100 Ps i
Coolant Return
HeatExchanger
Evaporator Valve
Sight Glass
Ref
rige
rant
Liq
uid
Tank RTD (Instal led Through Side)
TankHeaters
Level Swi tches
TankBaff le
10 Gal lonPolypropylene Reservoir
1 Hp Mult i -StageCentr i fugal Pump
Output RTD
* Refr igerant control valves are set cont inuously by the system microprocessor.
* Al l RTD's are read cont inuously by the system microprocessor.
#4,742,689#4,918,931#4,934,155
This circui t is coveredby one or more of thefol lowing U.S. Patents:
Rec
eive
r
L inearPressureSensor
HP160
PSIG
3/4" Copper 90 's
1/4" Ball Valve
1/2"
1"
1"
Power
20A #12 AWG
24VAC / Inter lock Loop isRed #18AWGRefr ig valves are wired in Yel low
High Vol tage Wir ing Chart : (Al l HV wire is Black)
Low-Vol tage Wir ing Chart :
DC / Logic wir ing is B lue #18 AWG
Power
Evaporator
Reset
6 9
RL1,C
RL1
A
B
W h
Red
HighPressure Swi tch
Red
C O N 1T1
T2
T3
Keyboard
J1
56
56
50
50
23 Reset
M1004 Power Supply , Phase Detector & Output Drivers
50 +5V
20 Comp
EV1
3+
4
2
1
S S R 1
L3L2L1
Red
M10
02 I
nput
s &
RT
D's
LCD Display
8
5RL1,B
J2
J1
J3
RS-232Connector
J2
M1001 Contro l ler
Power
24 VACOut
Gnd In
Gnd
24
VA
C40
VA
C O N 1
20 Amp
D2402
4
7
RL1,A
L3
L2
L1
Compressor
Crankcase Heater
Grn
P u m p
53
TankEmpty
FillTank
22 Tank1 Lo
+5V 49
HTR1 23
sheet 1 of 1DWG. B2344, Rev 3
Mydax, Inc. Auburn, CA
1M9W-S Chi l ler Electr ica l Diagram
Water Coo led January 25, 2001
D2440
23+ 10
00
W
S S R 4
14
23+ 10
00
W
D2440
D2440
S S R 2
S S R 3
1
1
2
4
3+
4
Tank Heaters
10
00
W
208/230 VAC, 3 phase
Grn
Tan
k
RT10
Con
d.O
utpu
t
RT3
RT4
RT7
Tri
m_0
1
RTD's
1
2
M1007LED PS
M1010 Inter faceLinear
PressureSensor
4
5
67
J4 J4
Blue
Gnd
13' of 12/4 Cable with L-15-30 Plug
5455
E M O
Over Temp
13' of 12/4 Cable with L-15-30 Plug
sheet 1 of 6 DWG. B2240
Mydax Inc. Auburn, CA.
Mydax Controller M1001
'CPU'
D0
D1
D3
D2
D6
D7
D5
D4
A14
A13
+5V
2627 28 1 28 26
A0
A1
A8
A4
A11
A12
A10
A9
A7
A6
A5
A3
A2
CE OE
A15 WRN
U22 U16
27C256
EPROM
6264
Read/Write Memory
20 22 14 20 22 27 14
11
12
13
15
16
17
18
19
10
9
8
7
6
5
4
3
25
24
21
23
2
D4
D5
D7
D6
D2
D3
D1
D0
A0
A1
+5v
1
2
3
4
5
6
7
8
11
9
14
15
16
18
20 19 24
22 23 21 14
RDN
WRN
8254AN
U17
82C54
CounterTimer
100 Hz
200 KHz
Baud Clock
10
13
17
A12
A13
A14
MREQN
A15
U14
8251N
KEYN
Nov 10, 1997
0.1uf
+5V
ResetN
In4
ResetN
+5V
U21
Max690
8
7
6
54
3
2
1
2
3
41
1kWaitNJ7
R110k
0.1uf8.0MHz
D0
D1
D3
D2
D6
D7
D5
D4
26
27
20
19
22
21
14
15
12
8
7
9
10
29
17
16
13
30
31
32
33
34
35
36
37
38
39
40
1
2
3
4
51125
6
24 "CPU"
Z84C0008
U9
M1N
IOREQN
MREQN
WRN
RDN
A0
A1
A3
A2
A6
A7
A5
A4
A8
A9
A11
A10
A14
A15
A13
A12
+5V
8.0 MhzOsc. U15
+5V
NMIJ7
IntJ7
10K
10K
1K
1K
U7 U12
1
2
13
12
3 4
8255N
8254BN
CPr
Q11
10
12
13
Qn 8ClD
U8
9
+5V
RTC
In3
CPr
Q3
4
2
1
QnClD
U8
5
U77
45
3RxRdy
TxRdy fromsheet 2
4 MHzto sheet 2
Bat.
LithiumBattery
U449
10
8
74
HC
13
8
A
B
C
1
2
3
456
15
14
13
12
11
10
9
7
sheet 2 of 6 DWG. B2240-2
Mydax Inc. Auburn, CA.
Mydax Controller M1001
IOREQN
A7
RDNWRN
U13
U12
A0
A1
A2
A2
A3
A4
IN 1
IN 0
IN 2
IN 3
IN 7
IN 6
IN 4
IN 5
OUT 8
OUT 4
OUT 0
OUT 12
OUT 16
OUT 20
13 12
D1
D0
D2
D3
D7
D6
D4
D5
+5V
SeikoL4042
LCDDISPLAYMODULE
124
5
6
14
13
12
11
10
9
8
7
10K 10K10K10K10K 10K
A0
A1
A2
+5V
KEYNU42
5 ea.1N914
10K10K10K10K 10K 10K
KEYN
SIP
D7D6D0 D5D1D0 D2 D3
74HC240
U41
KEY MATRIX(26 Keys)
11 8 13 6 15 4 17 21
19
9 12 7 14 5 16 3 18
D2
D3
D4
D5
D6
U10
82C51A
A0
PCLR
RDN
WRN
BAUDCLOCK
8251N
4.0MHz
+5V
26 4
12
21
13
10
8
7
6
5
2
1
28
27
925
11 20
Rd
CTS
Td
RTS
U4MAX232
15
14
3
17
19
23
12
9
11
10 7
14
8
13
RS-232Interface
0.1uf
0.1uf
Jan. 15, 1996
U31Out 24
Out 28
RTC
SIP
+5VVLC
3
10K
LCD R/W
LCD RS
LCD EN
37
38
39
40
1
2
3
4
U11
8255
"A"Section
D7 27
28D6
D5 29
30D4
D3 31
32D2
D1 33
34D0
5 36
RDN
WRN
8255N
6 7
35 26
ResetN
TxRdy
RxRdy
+5V+
+
+
+
+
10
10
10
10
10
6
2
16
1
3
4
5
15
J3
11
12
13
14
15
654
3
2
1
C
B
A
74
HC
13
8
to sheet 1
74
HC
13
8
A
B
C
1
2
3
456
15
14
13
12
11
10
9
7
74
HC
13
8
A
B
C
1
2
3
456
15
14
13
12
11
10
9
7
sheet 3 of 6 DWG. B2240-3
Mydax Inc. Auburn, CA.
Mydax Controller M1001
Input-Output
11
12
13
17
16
15
14
D0
D1
D2
D3
D4
D5
D6
D7
IN 5
U3
74
HC
24
4
18
3
16
5
14
7
12
9
191
11
8
13
6
15
4
17
2
T2 Low
Interlock
T1 Low
Reset Rly
Freon Lo
Ext Stop
Ext Start
J1-17
J1-18
J1-15
J1-13
J1-14
J1-11
J1-14
J1-16
J1-6
J1-5
J2-4
J2-3
J1-8
J1-7
J1-10
J1-9
T3 Low
Miss Ph.
Rev Ph.
Key Sw.
RemoteDig/Ana
24
23
22
21
20
19
18
2
17
4
15
6
13
8
11
1 19
9
12
7
14
5
16
3
18
74
HC
24
4
U1
10k
+5V
IN 7
D7
D6
D5
D4
D3
D2
D1
D0
2
17
4
15
6
13
8
11
1 19
9
12
7
14
5
16
3
18
74
HC
24
4
U2
10k
+5V
IN 6
D7
D6
D5
D4
D3
D2
D1
D0
Res On/Off
On=Remote
On=extvirtual
On=VoltSet En.
On=noFudge
Baud
Dip Switch
PCLRN
74
HC
27
3
U18
9
6
5
2111
3
4
7
8D3
D2
D1
D0
Out 28
April 24, 1996
Switch 2
Switch 3
+5V
10k
100K
+5V
10k
100k25 10
100k
10k
+5V
U1182C55 "B
U1182C55 "C
D4
D5
13
14 15
12
16
1918
17
D7
D6
LCD R/W
LCD EN
LCD RS
EV1J2-20
EV2J2-19
EV3J2-18
EV4J2-17
EV5J2-15
U24ULN2003A
+5V9
8
1
2
3
4
5
6
7 10
11
12
13
14
sheet 4 of 6 DWG. B2240-4
Mydax Inc. Auburn, CA.
Mydax Controller M1001
Output Dec 20, 1995
U197
4H
C2
73
19
16
15
12
9
6
5
2
111
3
4
7
8
13
14
17
18
PCLRN
Out 8
D0
D1
D2
D3
D4
D5
D6
D7
ULN2003A
9
16
15
14
13
12
11
810
7
6
5
4
3
2
1
U16
+5V
Beep
220
220
220
220
+5V
Compr.J2-13
PumpJ2-16
"Alarm"J2-14
LED
LED
LED
J8-1
J8-2
J8-6
"Power"
D7
D6
D5
D4
D3
D2
D1
D0
U32
74
HC
27
3
19
16
15
12
9
6
5
2
111
3
4
7
8
13
14
17
18
U28
74
HC
27
3
19
16
15
12
9
6
5
2
111
3
4
7
8
13
14
17
18
Out 4+5V +5V
DVB
DVA
High R J4-4
POS R J4-3
DIB J4-6
DIA J4-5
LED
+5V
+15V
Run DVM
DVC
1K
1K
1K
1K
DVMRDY
+5V+5VOut 0
14
13
11
6
4
3
9 1
2
5
7
10
12
15
74
HC
17
4
U5
14
13
11
6
4
3
9 1
2
5
7
10
12
15
74
HC
17
4
U6
D5
D4
D3
D2
D1
D0
1K
1K
1K
1KRA J1-3
RB J1-4
RC J1-1
RD J1-218
17
14
13
8
7
4
3
11 1
2
5
6
9
12
15
16
19
74
HC
27
3
U20
PCLRN
Out 12
D0
D1
D2
D3
D4
D5
D6
D7 SpareJ2-6
FAN 3J2-5
FAN 2J2-8
FAN 1J2-7
HTR 3J2-10
HTR 2J2-9
HTR 1J2-12
U26 ULN2003A
9
16
15
14
13
12
11
810
7
6
5
4
3
2
1
+5V
sheet 5 of 6 DWG. B2240-5B
Mydax Inc. Auburn, CA.
Mydax Controller M1001
Analog March 20, 2000
U38
4
5
6
7
12
11
10
9
8
14 13 3
1
16
15
2
10.0K*
10.0K*
RTD OutJ1-24
Set 1J4-16
Set 2J4-15
AC Det.J2-1
T1 Ext.J4-14
T2 Ext.J4-12
T3 Ext.J4-13
U35
DG
50
8C
J
-15V
DVA
DVB
DVC
+5V
D0
D5
D4
D3
D2
D1
D0
D7
D6
D5
D4
D3
D2
D1
+5V
IN 0
IN1
1
20
19
18
17
16
15
14
13
12
11
10
9
40
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
8
7
6
5
4
3
2
+5V
Run DVM
-15V U4379L05
-5V
1 uf+0.1uf
200K*
0.1uf
.056uf
200kHz
+1uf
200K*
.0047uf
47
+5V
1uf+
DVMRDYU27
1 2
U36
ICL7109
74HC14
+15V
3
2
8
1
7
6
5
U38
TL032CP
+10.24V
-10.24V
10
.0k
0.1
%
10.0K 0.1%
20.0K*
10
.0K
*
D0
14
13
D1
D2
12
11
D3
D4
10
9D
5
D6
8 7D
7
U40U39
AD7528KN
U40
+5V
A0
Out 16
17
6
16
15
5 4 18
Ref A Ref B
12
3
76
5
32
19
20
1
TL032CP
Gain DacJ1-230 to -5.1V
VFanJ2-20 to +10.0V
DI AmpJ4-11
40.2K 0.1%
10.0K 0.1%
10.0K 0.1%
40.2K 0.1%
10.0K 0.1%
30.1K 0.1%
10.0K 0.1%
10.0K 0.1%
10K*
10.0K 0.1%
10.0K 0.1%
10.0K 0.1%30.1K 0.1%
30.1K 0.1%
+15V
+5.12VJ4-8
Test Point Aadjust to +1.024V
Note:1. Resistors with *are 1/4W 1% metal film
2
Ref-02CP U37
6
54
"Adj"
20
.0K
0.1
%
10
.0K
0.1
%
10
.0K
0.1
%
10
K
10.0K 0.1%
10.0K 0.1%
10.0K 0.1%
20.0K 0.1%20.0K 0.1%10.0K 0.1%
RTD X5
sheet 6 of 6 DWG. B2240-6
Mydax Inc. Auburn, CA.
Mydax Controller M1001
Optional Jan. 15, 1996
10
K
10
K
10
K
10
K
10
K
+5V
2K
2K
2K
2K
2K1K
1K
Ctr1J5
Ctr0J5
+5V
0.1uf
13
10
CounterTimer
82C54
U23
8254BN
WRN
RDN
14212322
241920
18
16
15
14
9
11
8
7
6
5
4
3
2
1
A1
A0
D4
D5
D7
D6
D2
D3
D1
D0
FlwSw3J5
FlwSw2J5
FlwSw1J5
200KHz
U30U30
(optional)
Tank1J4-9
TL032CP
10.0K 0.1%
20.0K 0.1%
20.0K0.1%
0.1uf0.1uf
+15V-15V
84 5
67
3
21
16
1
2
3456711101289
13
1415
A1
+5V
++
+10.24V
+5.12V PinJumpers
EDCBA
Out20
AD7542KN
U29
D3
D2
D1
D0
A0
A0
D0
D1
D2
D3
U33
AD7542KN
Out24
A B C D E
PinJumpers
+5.12V
+10.24V
+ +
+5V
A1
1514
13
98 12 10 11 7 6 5 4 3
2
1
16
12
3
76
54 8
-15V +15V
0.1uf 0.1uf
20.0K0.1%
20.0K 0.1%
10.0K 0.1%
TL032CP
Tank2J4-7
(optional)
U34 U34
Range A B C D E
+5.12V on - - on -
+10.24V - on - on -
+-5.12V on - on - on
+-10.24V - on on - on
PinJumpers
sheet 1 of 1 DWG. B2242
Mydax Inc. Auburn, CA.
RTD and Inputs M1002
Dec 28, 1995
100
100
100
100
100
100
100
RT12
RT11
RT10
T3 Evap
T3 Out
T2 Evap
T2 Out
T1 Evap
T1 Out
Condr.
Sup Ht.
Bypass
100
100
Gain DACJ1-23
5VRTD
120 0.1%
100 0.1%
100K*
1.27K 0.1%
100+
10K 0.01uf
62
U1
-15V +15V
43 7
19 S1
S220
21 S3
S422
23 S5
S624
25 S7
S826
11 S9
S1010
9 S11
S128
7 S13
S146
5 S15
S164
A0 A1 A2
A3
17 16 15
14
14
151617
A3
A2A1A0
4 S16
S155
6 S14
S137
8 S12
S119
10 S10
S911
26 S8
S725
24 S6
S523
22 S4
S321
20 S2
S119
U5DG506A
U6DG506A
18
1
27+15V
+5V
-15V
28
28
-15V
+5V
+15V27
1
18
100K
100K
100K
100K
100K
100K
100K
100K
RA J1-3
RB J1-4
RC J1-1
RD J1-2
U3+
+U2
10K 0.001 uf
1.00K0.1%
9.09K 0.1%
76
5 4
672
3 4
LT1001
TL032
-15V
-15V
+15V
5.12VJ1-8 +
U2
+15V
5VRTD
10K
10K
12
3 8
LT1001
RTD's 0.1uf
+
Bridge
24VAC
24VAC
Ext 4
Stop
Start
Com.
+
U8
U8
U7
PS2501-2
PS2501-2
toAna. En. -28-
toStop-26-
toStart-27-
2K
2K
2K
10K
47uf
1N914
6
54
3
8
7
1
2
1
2
4
3
7
58
6
LT1001
RTD OutJ1-240.001
uf2
34
7
6
+15V
U4+
-15V
12.1K 0.1%
10.0K 0.1%
A
B
C
1. Resistor with *are 1/4W 1% metal film
PS2501-2
40.2K 0.1%
50.0k 0.1%
100k 0.1%
"Gain"
"Zero"
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
0.1uf
U3+
sheet 1 of 2 DWG. B2244
Mydax Inc. Auburn, CA.
Power Supply M1004
24 VAC
GND
47
vo
ltV
ari
ste
r
V
1N4002
4700uf 50V
June 19, 1996
Fuse
In
Out
Out
Out
Out
Out
511*4
76
5 30
.1K
0.1
%1
0.0
K 0
.1%
1.0
K*
750*
U4+
0.1 10uf+
+15V100mA
U2LM317T
+U4
9.76K*
1.0K*
1.0
K*
10
.0K
0.1
%1
0.0
K 0
.1%
3
21511*
1
0.1
U3LM317T
+
15.1 2W
2.0K*
++5V200mA
10uf
10uf
-15V100mA
+
20 1W 1
+
U1LM337T
0.11000uf 50V 500
2.49K*
249*
Q2
00
4L
3
220 6
4
2
1 47
1K 1EV1
Q1MOC3032
U6EV1J2-20
EV2J2-19
U7MOC3032
Q2
EV2 11K
471
2
4
6220
Q2
00
4L
3Q
20
04
L3
220 6
4
2
1 47
1K 1EV3
Q3MOC3032
U8EV3J2-18
EV4J2-17
U9MOC3032
Q4
EV4 11K
471
2
4
6220
Q2
00
4L
3Q
20
04
L3
220 6
4
2
1 47
1K 1EV5
Q5MOC3032
U10EV5J2-15
Freon Control Valves
1N4002
ACDetJ2-1
+
+U5
U5
1
2
3
76
5
1uf
1N914
200K*
200K*4.02K*
511*10M
LM358A
PowerConnectors
TL032
8
4
+15V
-15VU18
AL
Run
43 +
45 +
42 -
44 -
1K
1K
PS2501-2
6
5
8
7
1
2
3
4
10K
Q8
2N222210K
10K
2N2222
Q7
10K
+5V
20 Comp.
21 Pump
22 Alarm
23 Htr1
24 Htr2
25 Htr3
26 Fan1
27 Fan2
28 Fan3
29 BeepJ2-1110K
10KJ2-5
J2-810K
10KJ2-7
J2-1010K
10KJ2-9
J2-1210K
10KJ2-14
J2-1610K
10KJ2-13
+5V
50 +5V
49 +5V
48 +5V
47 +5V
46 +5V
41 VFAN
+5V
J2-2
0.1uf
sheet 2 of 2 DWG. B2244-2
Mydax Inc. Auburn, CA.
Phase Detector M1004
April2 4, 1996
Note:1. Resistors marked with are1% 1/4W, all other resistors are 5% 1/4W.
4
4
8
-15V
+15V
4
8
84
+15V
Loop40
Gnd39
0.1uf
1M
2
Jumpers
"VAC"220210200190180
1N914 0.1uf
1.5
8K
*
1.5
0K
*
1.4
3K
*
1.3
3K
*
1.2
7K
*
0.1uf
U11+
6
5
7
7
5
6
+U14
0.001uf
+5V
1.00M
1.00M 1.00M
0.001uf
1.00M
1.00M
0.001uf0.001uf
1.00M1.00M
1.00M
1.00M
1.00M 1.00M
0.001uf 0.001uf
1.00M
470K
470K
74HC14
+5V
8
InterlockLoop
RelayQ1BS170
1N
40
02
1K
+5V
"OK"
GreenLED
121
13
U16
Miss Ph.J2-4
Rev Ph.J2-3
1.0uf
10M 896
54
3
U17U16
74HC27
11
10
98
U161K Red
LED
"REV."
+5V
RedLED
+5V
+5V
"UNBAL"
RedLED
1KU17U17
LM358A
LM358A
U17
1.0
M
1213
1N914
0.1
uf
2
1.0
M
0.1
uf
11N914
LM393A
LM393A
5
4.7K
4.7K
4.7K
10
K
470K
1
10
K2
3+U14
U12+
5
6 10
K
+5V
7
1
470K
+5V
10
K
2
3+U12
65
4.7K
3
2
U11+
1
U13+
10K*
10K*
7
6
5
3
2
1
10K*
10K*
+U13
10K*
10K*
74HC74
2 6
4
3
1
U15
Cl
Pr
Qn
Q
D
C
12
11
C
D
Q
Qn
Pr
Cl
U15
10
131K
"LOWAC"
11 10U17
"Scale"JumpersX2X1
8.6
6K
*
18
.7K
*
-15V
L1
L2
L3
Input Range190-480VAC
0.1uf
0.1uf
sheet 1 of 1 DWG. D2729
Mydax Inc. Auburn, CA.
M1007 LED Power Supply
Sept 24, 1997
0.1
5.11 watt
1000uf50V
24 VAC
Common
Polyswitch
LM317T
1.0Positive
Negative
250 mA @4.1 voltto Display LED backlight
Heat Sinked
In Out
Ref
1N4002
sheet 1 of 1 DWG. D2616
M y d a x I n c . Auburn, CA.
Inter face M1010
Jan 25, 2000
15.0K 0.1%10.0K 0.1%
+U3
1
2
3 TL032
4
3
2
1
0.110K
Rt
Ct
10uf U1LM2907-8
Note:1. Resistors with *are 1/4W 1% metal f i lm.
2. For Proteus 500C-highCt=0.0047uf, Rt=69.8K*Rp=50K , 100Hz=0.714V
3. For Proteus 550CCt=0.01uf, Rt=49.9K*Rp=50K , 100Hz=0.97V
4. For Gems 1/2" Lo range, Rp= 20k, Rt=30.1k, Ct= 0.01uf100 Hz=0.595 V
Rp
8
7
6
5
1
2
3
Flow In
C o m m o n
Shield
+15V
To J4-14 T1 Ext
To J4-12 T2 Ext
8 9 10
Flow Gnd Press.
U2
+10 Ref.
+ Pres.
- Pres.
C o m m o n
1.02K *
21
8
3
4
5
6
7
-15 V
+15 V
7
45
6
INA114
Opt ional
0.10.1
-15 V
1 M
10K
Pressure Zero
10.0K 0.1%J4-11 DI Amp
J6
10.0K 0.1%15.0K 0.1%
+U3
6
5 TL032
Opt ional
7
4
8
Alarm
C o m m o n
Alarm NC
Alarm NO
Relay
11
12
13
14
200K 0.1%
Optional forGems F lowmeters
0.0047 100k
2k
J4-16 Set1
Us ing Sensym STImV300G1A sensor :0 psig= 1.125 vol t , 300 psig= 8.625 vol t
Us ing Sensym STImV300A1A sensor :0 psia= 1.125 vol t , 300 psia= 8.625 vol tSea level mean pressure= 14.7 psia = 1.4925 vol t
+5V