MV SMC-Flex OEM Components - Rockwell Automation

61
MV SMC-Flex OEM Components Bulletin 1503E Installation Instructions

Transcript of MV SMC-Flex OEM Components - Rockwell Automation

Page 1: MV SMC-Flex OEM Components - Rockwell Automation

MV SMC-Flex OEM ComponentsBulletin 1503E

Installation Instructions

Page 2: MV SMC-Flex OEM Components - Rockwell Automation

Important User Information

Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

Labels may also be on or inside the equipment to provide specific precautions.

Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

Page 3: MV SMC-Flex OEM Components - Rockwell Automation

Table of Contents

1503E-IN001E-EN-P – June 2013

Chapter 1 Introduction Scope ....................................................................................... 1-1

Additional Publications .......................................................... 1-2

Chapter 2 Receiving ............................................................................... 2-1

Handling Procedures for Electrostatic Sensitive Devices ....... 2-1

Standards and Codes ............................................................... 2-2

Chapter 3 Identification .......................................................................... 3-1

Specifications .......................................................................... 3-2

Sizing the Enclosure ............................................................... 3-3

Dimensions ............................................................................. 3-3

Frame Layout .......................................................................... 3-4

Anchoring ............................................................................... 3-5

Torque Requirements .............................................................. 3-5

Power Connections ................................................................. 3-6

Grounding ............................................................................... 3-7

Current Loop Gate Drive Power Assembly ............................ 3-7

Chapter 4 Identification ........................................................................... 4-1

Sizing the Enclosure ................................................................ 4-2

Specifications .......................................................................... 4-3

Dimensions ............................................................................. 4-3

Torque Requirements .............................................................. 4-4

Power Stack Mounting ........................................................... 4-4

Power Stack Dimensions

1000/2300V, 180/360 A ................................................ 4-5

2300V, 600 A ................................................................ 4-6

3300/4160V, 180/360 A ................................................ 4-7

3300/4160V, 600 A ........................................................ 4-8

6900V, 180/360 A ......................................................... 4-9

6900V, 600 A .............................................................. 4-10

Power Connections ............................................................... 4-11

Grounding ............................................................................. 4-12

Power Stack Operating Restrictions ..................................... 4-12

Voltage Sensing Board Dimensions ..................................... 4-13

Mounting and Connecting the Voltage Board ...................... 4-13

Current Loop Gate Drive Power Assembly .......................... 4-15

Chapter 5 Interface Board Installation .................................................... 5-1

Interface Board Layout ............................................................ 5-2

Interface Board Connections .................................................. 5-3

SMC Flex Control Module ..................................................... 5-3

Connecting Interface Board to Voltage Sensing Board .......... 5-4

Connecting Interface Board to Gate Driver Board ................. 5-4

Additional Control Components ............................................. 5-5

Receiving and General Information

Power Stack Frame Installation

Power Stack Installation

Control Component Installation

Page 4: MV SMC-Flex OEM Components - Rockwell Automation

ii Table of Contents

1503E-IN001E-EN-P – June 2013

Chapter 6 Introduction .............................................................................. 6-1

Main and Bypass Contactors ................................................... 6-1

Bypass Contactor .................................................................... 6-1

Main and Bypass Contactor Wiring Configuration ................ 6-2

Bypass Contactor Control Panel ............................................. 6-3

IntelliVAC Control Module .................................................... 6-4

Chapter 7 Wiring Diagrams ..................................................................... 7-1

180/360A, 800 to 1449V ................................................ 7-2

180/360A, 1450 to 2499V ............................................. 7-3

600A, 1450 to 2499V .................................................... 7-4

180/360/600A, 2500 to 4799V ..................................... 7-5

180/360/600A, 4800 to 6900V ..................................... 7-6

Chapter 8 Final Test Procedures .............................................................. 8-1

Dielectric Test ................................................................ 8-2

Additional Tests ...................................................................... 8-4

Spare Parts .............................................................................. 8-4

Appendix A Component Deratings Component Derating Table .................................................... A-1

Appendix B Typical MV SMC Flex Schematic Diagrams 3300/4160V (1 of 2) ..................................................... B-1

3300/4160V (2 of 2) ..................................................... B-3

Appendix B Typical MV SMC Flex Schematic Diagrams SMC Flex OEM Power Stack Kit Chart ................................. C-1

Contactor Installation

Typical Wiring Diagrams

Final Test Procedures

Page 5: MV SMC-Flex OEM Components - Rockwell Automation

Chapter 1

1503E-IN001E-EN-P – June 2013

Introduction Scope This document pertains to the Bulletin 1503E MV SMC Flex OEM

components.

Most of the components described herein are provided in various

1503E kits; however, some of the devices described are not provided.

These must be acquired separately.

The power stack frame is a complete three-phase power system used in

solid-state reduced voltage motor controllers (refer to Figure 3.1).

Power stacks are also available as a set of loose three-phase components

(refer to Figure 4.1). Each form of power stack assembly (frame, loose)

is applied with other Bulletin 1503E control components and power

devices, in forming a complete solution.

Additional Publications Please refer to the following publications for additional information

about the Bulletin 1503E products:

1560E-SR022_-EN-P Medium Voltage Smart Motor

Controller (SMC) • Specification Guide

1560E-UM051_-EN-P Medium Voltage SMC Flex Motor

Controller, Bulletin 1503E, 1560E,

1562E • User Manual

This document contains the following

information for the MV SMC Flex:

• Commissioning

• Maintenance and Troubleshooting

• Parameter List

• Spare Parts List

Order additional copies of instruction manuals for all Allen-Bradley

medium voltage products from the Rockwell Automation on-line

ordering system at http://www.rockwellautomationdox.com.

Page 6: MV SMC-Flex OEM Components - Rockwell Automation

1-2 Introduction

1503E-IN001E-EN-P – June 2013

Page 7: MV SMC-Flex OEM Components - Rockwell Automation

Chapter 2

1503E-IN001E-EN-P – June 2013

Receiving and General Information Receiving Refer to Getting Started, General Handling Procedures for Medium

Voltage Controllers - Publication MVB-5.0. This document is

included with your shipment and contains information regarding

receiving, unpacking, initial inspection, handling, storage, and site

preparation.

A T T E N T I O NA T T E N T I O N

Printed circuit boards contain components that

can be damaged by electrostatic charges that

build up on personnel during normal activities.

Exercise the following precautions when

handling electrostatic sensitive devices. Failure

to do so may damage the device and render it

inoperable.

To guard against electrostatic damage (ESD) to equipment, the

following precautions should be observed when handling electrostatic

sensitive devices.

1) Use a grounding wrist strap to minimize the build up of static

charges on personnel.

2) Handle the module by the edges and avoid touching components or

printed circuit paths.

3) Store devices with sensitive components in the conductive

packaging that the module is shipped in.

These precautions are the minimum requirements for guarding against

ESD. For more information refer to Guarding Against Electrostatic

Damage - Publication ICCG-4.3. See the Additional Publications

section for information on obtaining this document.

Handling Procedures for Electrostatic Sensitive Devices

Page 8: MV SMC-Flex OEM Components - Rockwell Automation

2-2 Receiving and General Information

1503E-IN001E-EN-P – June 2013

Standards and Codes Important: It is recommended that the user be familiar with the

following safety and design standards and codes, and any additional

local codes that a medium voltage controller must comply with:

• CEC (Canadian Electrical Code)

• CSA 22.2 No. 14 (Canadian Standards Association) - Industrial

Control Equipment

• NEC (National Electrical Code)

• NEMA ICS Standards (National Electrical Manufacturers’

Association)

• OSHA (Occupational Safety and Health Administration)

• UL 50 (Underwriters Laboratories) - Enclosures for Electrical

Equipment

• UL 347 (Underwriters Laboratories) - High Voltage Industrial

Control Equipment

• UL 508 (Underwriters Laboratories) - Industrial Control Equipment

• IEC 60204-1 - Safety of Machinery - Electrical Equipment of

Machines, Part 1: General Requirements

• IEC 62271-200 - AC Metal Enclosed Switchgear and Control Gear

for Rated Voltages Above 1kV and up to 52 kV (formerly IEC

60298)

• IEC 60470 - High Voltage Alternating Current Contactors

• IEC 60529 - Degrees of Protection Provided by Enclosures (IP Code)

• IEC 60694 - Common Clauses for High Voltage Switchgear and

Control Gear Standards

• ICS1- Industrial Control and Systems General Requirements

• ICS3 Part 2 - Industrial Control and Systems - Medium Voltage

Controllers Rated 2001-7200V AC

Page 9: MV SMC-Flex OEM Components - Rockwell Automation

Chapter 3

1503E-IN001E-EN-P – June 2013

Power Stack Frame Installation Identification A power stack frame is shown below in Figure 3.1 (3300/4160 V frame

shown).

Figure 3.1 – MV SMC Flex OEM Power Stack Frame

Verify the voltage and current rating of the OEM frame using the

information located on the nameplate at the front of the frame

(see Figure 3.2).

Refer to Table 3.A for the frame description and catalog numbers.

Figure 3.2 – MV SMC Flex OEM Frame Nameplate Data

Page 10: MV SMC-Flex OEM Components - Rockwell Automation

3-2 Power Stack Frame Installation

1503E-IN001E-EN-P – June 2013

Description of Frame Options Catalog Number Part Number

1000V, 180 A, 3 phase, 50/60 Hz 1503E-FRZ1T 80187-547-51

1000V, 360 A, 3 phase, 50/60 Hz 1503E-FRZ1A 80187-547-52

2300V, 180 A, 3 phase, 50/60 Hz 1503E-FRAT 80187-547-53

2300V, 360 A, 3 phase, 50/60 Hz 1503E-FRAA 80187-547-54

3300V, 180 A, 3 phase, 50/60 Hz 1503E-FRCT 80187-547-55

3300V, 360 A, 3 phase, 50/60 Hz 1503E-FRCA 80187-547-56

4160V, 180 A, 3 phase, 50/60 Hz 1503E-FRET 80187-547-57

4160V, 360 A, 3 phase, 50/60 Hz 1503E-FREA 80187-547-58

Voltage ranges : 1000 = 800 to 1449 V 2300 = 1450 to 2499 V 3300/4160 = 2500 to 4799 V

Table 3.B – Power Stack Frame Specifications Description 180 A 360 A

Input Voltages

(50/60 Hz)

1000 volts AC, 3 phase, +10% -15%

2300 volts AC, 3 phase, +10% -15%

3300 volts AC, 3 phase, +10% -15%

4160 volts AC, 3 phase, +10% -15%

Ambient Temperature 0°C to 40°C (32°F to 104°F)

Power Section 6 SCR at 1000 volts 12 SCR at 3300 volts

6 SCR at 2400 volts 12 SCR at 4160 volts

Repetitive Peak Inverse Voltage Rating

1000 volts – 4500 PIV 3300 volts – 13000 PIV

2300 volts – 6500 PIV 4160 volts – 13000 PIV

Thermal Capacity 600% of FLA, 10 seconds (2 starts per hour, 5 minutes between starts)

450% of FLA, 30 seconds (2 starts per hour, 5 minutes between starts)

dv/dt Protection R.C. Snubber Network

Maximum Heat Dissipation (kW)

Start or Stop Cycle (@ 450% FLA) Continuous

180 A 360 A

800 to 2499 V 7 13 .25

2500 to 4799 V 14 26 .25

Altitude 0 to 1000 m (0 to 3,300 ft)

(See Controller Deratings Table A-1 in Appendix A)

Net Weight (Shipping)

1000 to 2300 V – 116 kg (255 lbs)

3300 to 4160 V – 125 kg (276 lbs)

Refer to Table 3.A for acceptable input voltage ranges.

For higher ambient conditions, contact Factory.

Specifications

Page 11: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Frame Installation 3-3

1503E-IN001E-EN-P – June 2013

A T T E N T I O NA T T E N T I O N

The enclosure for the power stack frame assembly must be adequately sized to provide sufficient airflow to cool the units. Failure to provide adequate cooling may result in reduced duty cycles or component failure.

Use the information included in Table 3.B to assist in determining the

enclosure size.

Dimensions The power stack frame dimensions are shown in Figure 3.3 below.

The dimensions are the same for all frame catalog numbers.

900 [35.42] 640 [25.19]

890

[35.04]

Front View Side View

Approximate dimensions in millimeters [inches]

900 [35.42] 640 [25.19]

890

[35.04]

Front View Side View

Approximate dimensions in millimeters [inches]

Figure 3.3 – Power Stack Frame Dimensions (4160V, 360A shown)

Sizing the Enclosure

Page 12: MV SMC-Flex OEM Components - Rockwell Automation

3-4 Power Stack Frame Installation

1503E-IN001E-EN-P – June 2013

Frame Layout Refer to Figure 3.4 for the main components of the OEM SMC

frame.

Voltage Sensing Board located

on underside of mounting panel

Lifting Clip

Heatsink Assembly

Current Loop

Gate Driver Board

Current Loop

Gate Driver Power Assembly

Voltage Sensing Board located

on underside of mounting panel

Lifting Clip

Heatsink Assembly

Current Loop

Gate Driver Board

Current Loop

Gate Driver Power Assembly

PowerPhase

A

PowerPhase

B

PowerPhase

C

Front View

PowerPhase

A

PowerPhase

B

PowerPhase

C

Front View

Figure 3.4 - Frame Layout

Page 13: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Frame Installation 3-5

1503E-IN001E-EN-P – June 2013

Anchoring Mounting holes are provided in the frame and are suitable for 0.5 in.

(M12) diameter anchor bolts (refer to Figure 3.5).

A T T E N T I O NA T T E N T I O N

The frame is designed to be anchored in the upright position and on a level surface. Do not attempt to mount the frame upside down or at any angle that is not level. Improper anchoring may cause injury to personnel and/or damage to the equipment.

640[25.2]

521[20.5]

778[30.6]

900[35.4]

(All dimensions in millimeters [inches])

Front

Figure 3.5 – Frame Mounting Hole Locations (Bottom View)

Torque Requirements All electrical connections must be torqued to the specifications shown

in Table 3.C.

A T T E N T I O NA T T E N T I O N

Ensure that all electrical connections are torqued to the correct specification. Failure to do so may result in damage to the equipment and/or injury to personnel.

Table 3.C – Torque Requirements

Hardware Recommended Torque

1/4 in. 6 ft·lb (8 N·m)

5/16 in. 11 ft·lb (15 N·m)

3/8 in. 20 ft·lb (27 N·m)

1/2 in. 48 ft·lb (65 N·m)

Control Wire Terminals 2.0 – 3.3 in·lb (0.2 – 0.4 N·m)

CLGD Power Assembly Terminals 50 in·lb (5.6 N·m)

SMC Flex Control Module Terminals 5 in·lb (0.6 N·m)

Page 14: MV SMC-Flex OEM Components - Rockwell Automation

3-6 Power Stack Frame Installation

1503E-IN001E-EN-P – June 2013

A T T E N T I O NA T T E N T I O N

To avoid shock hazard, lock out incoming power to power cables when completing connections. Failure to do so may result in severe burns, injury or death.

It is the responsibility of the OEM to ensure that suitable line and load cables are used to satisfy the requirements of the equipment and meet local electrical codes.

1) Use appropriate cable lugs to attach suitable line cables to the

line cable terminal (upper power terminal) of the heatsink

assembly. The terminal is predrilled with a mounting hole with a

diameter of 10.3 mm (0.406 in.). The holes are suitable for M10

(3/8 in.) hardware. Refer to Figure 3.6 for the terminal location.

Torque the fastening hardware to the specifications shown in

Table 3.C.

2) Use cable lugs to attach suitable load cables to the load cable

terminal (lower power terminal) of the heatsink assembly. Refer

to Figure 3.6 for the terminal location. Torque the fastening

hardware to the specifications shown in Table 3.C.

3) Refer to Chapters 6 and 7 for a typical wiring diagram to

determine the required connections. Appendix B includes a

typical schematic for a complete soft starter unit.

Line Cable Terminal

10.3 mm (0.406 in.) diameter

(All stacks in SMC frame have similar configuration)

Right Side View

Load Cable Terminal

10.3 mm (0.406 in.) diameter

Line Cable Terminal

10.3 mm (0.406 in.) diameter

(All stacks in SMC frame have similar configuration)

Right Side View

Load Cable Terminal

10.3 mm (0.406 in.) diameter

Figure 3.6 - Heatsink Assembly Power Connections (4160V, 360A heatsink shown)

Power Connections

I M P O R T A N TI M P O R T A N T

Page 15: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Frame Installation 3-7

1503E-IN001E-EN-P – June 2013

A T T E N T I O NA T T E N T I O N

It is the responsibility of the OEM to ensure that the final enclosure is suitably bonded to ground, and that provisions for grounding are made according to local electrical codes and standards.

The CLGD power assembly is mounted on the front bottom of the

frame (refer to Figure 3.4). All secondary connections are pre-wired

for the power stack frame. It requires a 110/120 or 220/240 VAC

(50/60 Hz), 50 VA, primary source of power. Refer to Chapter 7 for

typical wiring diagrams.

NOTE: There are three individual cable loops (one for each

phase) connected in series. The cable length must be 6.4

metres (21 feet). Do not cut the extra length from these

cables, as they represent the load for the transformer in

the above power assembly. If they are shortened, the

loop current will be incorrect, and the CLGD boards

may not function properly during stop maneuvers.

Grounding

Current Loop Gate Drive Power Assembly (CLGD)

Page 16: MV SMC-Flex OEM Components - Rockwell Automation

3-8 Power Stack Frame Installation

1503E-IN001E-EN-P – June 2013

Page 17: MV SMC-Flex OEM Components - Rockwell Automation

Chapter 4

1503E-IN001E-EN-P – June 2013

Power Stack Installation

Identification A power stack (single phase, 3300/4160V) power stack is shown below

in Figure 4.1.

Figure 4.1 – Single-phase Power Stack

Verify the voltage and current rating of the OEM power stacks by

examining the label and referencing it to the information in Table 4.A.

Table 4.A – Power Stack Options and Catalog Numbers

Voltage Current (Amps) Catalog Number Part Number

1000 V, 3 phase, 50/60 Hz 180 1503E-PPZ1T 80258-011-51

360 1503E-PPZ1A 80258-011-52

2300 V, 3 phase, 50/60 Hz

180 1503E-PPAT 80258-011-53

360 1503E-PPAA 80258-011-54

600 1503E-PPAC 80258-011-55

3300 V, 3 phase, 50/60 Hz

180 1503E-PPCT 80258-011-56

360 1503E-PPCA 80258-011-57

600 1503E-PPCC 80258-011-58

4160 V, 3 phase, 50/60 Hz

180 1503E-PPET 80258-011-59

360 1503E-PPEA 80258-011-60

600 1503E-PPEC 80258-011-61

6900 V, 3 phase, 50/60 Hz

180 1503E-PPKT 80258-011-62

360 1503E-PPKA 80258-011-63

360 1503E-PPKC 80258-011-64

Voltage ranges: 1000 = 800 to 1449V 2300 = 1450 to 2499V 3300/4160 = 2500 to 4799V 6900 = 4800 to 7200V

Page 18: MV SMC-Flex OEM Components - Rockwell Automation

4-2 Power Stack Installation

1503E-IN001E-EN-P – June 2013

Identification (cont.) In addition to the power stacks, a voltage sensing board is to be

connected in the power circuit. Table 4.B lists the voltage sensing

board part number, which is used for all power stacks.

Table 4.B – Voltage Sensing Board Catalog Number

Description Line Voltage (3 phase, 50/60 Hz) Catalog Number Part Number

Voltage Sensing Board

800 to 1500V 1503E-VSZ1 80258-016-52

1501-2500V 1503E-VSA 80258-016-53

2501-4800V 1503-VSE 80258-016-54

4801-7200V 1503E-VSK 80258-016-55

A T T E N T I O NA T T E N T I O N

The enclosure for the power stack assemblies must be adequately sized to provide sufficient airflow to cool the units. Failure to provide adequate cooling may result in reduced duty cycles or component failure.

Use the data in Table 4.C to assist in calculating the enclosure size.

Sizing the Enclosure

Page 19: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Installation 4-3

1503E-IN001E-EN-P – June 2013

Table 4.C – Power Stack Specifications

Description 180 A, 360 A, 600 A

Input Voltages

(50/60 Hz)

1000 volts AC, 3 phase, +10%, -15% 2300 volts AC, 3 phase, +10%, -15% 3300 volts AC, 3 phase, +10%, -15% 4160 volts AC, 3 phase, +10%, -15% 6900 volts AC, 3 phase, +10%, -15%

Ambient Temperature

0°C to 40°C (32°F to 104°F)

Power Section (for 3 phases)

6 SCR at 1000/2300 volts 12 SCR at 4160 volts 12 SCR at 3300 volts 18 SCR at 6900 volts

Repetitive Peak Inverse Voltage Rating

1000 volts – 4500 PIV 3300/4160 volts – 13000 PIV 2400 volts – 6500 PIV 6900 volts – 19500 PIV

Thermal Capacity 600% of FLA, 10 seconds 450% of FLA, 30 seconds

dv/dt Protection R.C. Snubber Network

Maximum Heat Dissipation (kW)

Start or Stop Cycle (@ 450% FLA) Continuous

180 A 360 A 600 A

0 to 2499 V 7 13 22 .25

2401 to 4799 V 14 26 44 .25

4800 to 7200 V 21 39 66 .25

Altitude 0 to 1000 m (0 to 3,300 ft.)

(See Controller Deratings Table A-1 in Appendix A)

Net Shipping Weight

(3 phases)

Rating 1000 / 2300 V 3300 / 4160 V 6900 V

180A / 360A 105 kg (231 lb) 113 kg (249 lb) 126 kg (278 lb)

600 A 132 kg (290 lb) 154 kg (339 lb) 170 kg (374 lb)

Refer to Table 4.A for acceptable input voltage ranges.

180 A and 360 A ratings only for 1000 V power stack

For other ambient ranges, refer to Factory.

Dimensions Refer to Figures 4.2 through 4.7 for the dimensions of the power

stacks.

Specifications

Page 20: MV SMC-Flex OEM Components - Rockwell Automation

4-4 Power Stack Installation

1503E-IN001E-EN-P – June 2013

Torque Requirements All electrical connections must be torqued to the specifications shown

in Table 4.D.

A T T E N T I O NA T T E N T I O N

Ensure that all electrical connections are torqued to the correct specification. Failure to do so may result in damage to the equipment and/or injury to personnel.

Table 4.D – Torque Requirements

Hardware Recommended Torque

1/4 in. 6 ft·lb (8 N·m)

5/16 in. 11 ft·lb (15 N·m)

3/8 in. 20 ft·lb (27 N·m)

1/2 in. 48 ft·lb (65 N·m)

Control Wire Terminals 2.0 – 3.3 in·lb (0.2 – 0.4 N·m)

CLGD Power Assembly Terminals 50 in·lb (5.6 N·m)

SMC Flex Control Module Terminals 5 in·lb (0.6 N·m)

Power Stack Mounting Power stacks are to be mounted in a vertical orientation in order to

provide adequate component cooling. Mount the heatsink in a

suitable location using the mounting holes provided in the assembly.

Use M10 (3/8”) or similar hardware for the mounting hole dimensions

of 10.7 mm x 15.9 mm (0.421in. x 0.625 inches).

Power stacks rated 180/360A, up to 4799V, are provided with

mounting brackets (as shown in Figures 4.2 and 4.4). The mounting

brackets should be affixed to a horizontal surface, and the power stacks

slide into and bolt to the mounting brackets.

A T T E N T I O NA T T E N T I O N

Maintain sufficient clearance between the power

phases and between phases and grounded

surfaces. Refer to local electrical codes to

determine the required clearance. Failure to do

so may result in injury to personnel or damage to

the equipment.

Page 21: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Installation 4-5

1503E-IN001E-EN-P – June 2013

OVERALL DIMENSIONS:

WIDTH: 186.4 [7.34]

HEIGHT: 426.7 [16.80]

DEPTH: 457.7 [18.02]

WEIGHT: 35 kg [77 lbs.]

Front View

Dimensions in millimeters [inches] Mounting Holes for

M10 (3/8”) hardware

(4 places)

Side View

Bottom View

Note: All dimensions

include mounting bracket.

186.4 [7.34]

426.7[16.80]

446.9 [17.60]

457.7 [18.02]

457.7 [18.02]

214.4 [8.44] 12.7 [0.50]

139.7 [5.50]

OVERALL DIMENSIONS:

WIDTH: 186.4 [7.34]

HEIGHT: 426.7 [16.80]

DEPTH: 457.7 [18.02]

WEIGHT: 35 kg [77 lbs.]

Front View

Dimensions in millimeters [inches] Mounting Holes for

M10 (3/8”) hardware

(4 places)

Side View

Bottom View

Note: All dimensions

include mounting bracket.

186.4 [7.34]

426.7[16.80]

446.9 [17.60]

457.7 [18.02]

457.7 [18.02]

214.4 [8.44] 12.7 [0.50]

139.7 [5.50]

Figure 4.2 – Power Stack Dimensions – 1000/2300V, 180/360A

Page 22: MV SMC-Flex OEM Components - Rockwell Automation

4-6 Power Stack Installation

1503E-IN001E-EN-P – June 2013

OVERALL DIMENSIONS:

WIDTH: 501.2 [14.73]

HEIGHT: 444.1 [17.49]

DEPTH: 461.5 [18.17]

WEIGHT: 44 kg [97 lbs]

Dimensions in millimeters [inches]

Front View

501.2 [19.73]

309.8 [12.20]

88.9[3.50]

125.3[4.93]

98.6[3.88]

50.8[2.00]

102.6[4.04]

50.8[2.00]

203.3 [8.01]

461.4 [18.17]

444.1[17.49]

414.2[16.31]

Mounting Holes for

M10 (3/8”) hardware

(4 places)

Side View

OVERALL DIMENSIONS:

WIDTH: 501.2 [14.73]

HEIGHT: 444.1 [17.49]

DEPTH: 461.5 [18.17]

WEIGHT: 44 kg [97 lbs]

OVERALL DIMENSIONS:

WIDTH: 501.2 [14.73]

HEIGHT: 444.1 [17.49]

DEPTH: 461.5 [18.17]

WEIGHT: 44 kg [97 lbs]

Dimensions in millimeters [inches]

Front View

501.2 [19.73]

309.8 [12.20]

88.9[3.50]

125.3[4.93]

98.6[3.88]

50.8[2.00]

102.6[4.04]

50.8[2.00]

203.3 [8.01]

461.4 [18.17]

444.1[17.49]

414.2[16.31]

Mounting Holes for

M10 (3/8”) hardware

(4 places)

Side View

Figure 4.3 – Power Stack Dimensions – 2300V, 600A

Page 23: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Installation 4-7

1503E-IN001E-EN-P – June 2013

OVERALL DIMENSIONS:

WIDTH: 186.7 [7.35]

HEIGHT: 582.2 [22.92]

DEPTH: 454.4 [17.89]

WEIGHT: 38 kg [83 lbs]

Front View

Dimensions in millimeters [inches]Mounting Holes for

M10 (3/8”) hardware

(4 places)

Side View

Bottom View

Note: All dimensions

include mounting bracket.

186.7 [7.35]

582.2[22.92]

443.5 [17.46]

454.4 [17.89]

454.4 [17.89]

214.4 [8.44] 12.7 [0.50]

139.7[5.50]

OVERALL DIMENSIONS:

WIDTH: 186.7 [7.35]

HEIGHT: 582.2 [22.92]

DEPTH: 454.4 [17.89]

WEIGHT: 38 kg [83 lbs]

Front View

Dimensions in millimeters [inches]Mounting Holes for

M10 (3/8”) hardware

(4 places)

Side View

Bottom View

Note: All dimensions

include mounting bracket.

186.7 [7.35]

582.2[22.92]

443.5 [17.46]

454.4 [17.89]

454.4 [17.89]

214.4 [8.44] 12.7 [0.50]

139.7[5.50]

Figure 4.4 – Power Stack Dimensions – 3300/4160V, 180/360A

Page 24: MV SMC-Flex OEM Components - Rockwell Automation

4-8 Power Stack Installation

1503E-IN001E-EN-P – June 2013

Power Stack Mounting (cont.)

OVERALL DIMENSIONS:

WIDTH: 394.7 [15.54]

HEIGHT: 611.2 [24.06]

DEPTH: 461.4 [18.17]

WEIGHT: 51 kg [113 lbs.]

Dimensions in millimeters [inches]

Front View

394.7 [15.54]

203.3 [8.01]

189.8[7.47]

50.8[2.00]

611.2[24.06]

581.3[22.88]

205.2[8.08]

50.8[2.00]

461.4 [18.17]88.9[3.50]

98.6[3.88]

Mounting holes for

M10 (3/8”) hardware

(4 places)

Side View

OVERALL DIMENSIONS:

WIDTH: 394.7 [15.54]

HEIGHT: 611.2 [24.06]

DEPTH: 461.4 [18.17]

WEIGHT: 51 kg [113 lbs.]

Dimensions in millimeters [inches]

OVERALL DIMENSIONS:

WIDTH: 394.7 [15.54]

HEIGHT: 611.2 [24.06]

DEPTH: 461.4 [18.17]

WEIGHT: 51 kg [113 lbs.]

Dimensions in millimeters [inches]

Front View

394.7 [15.54]

203.3 [8.01]

189.8[7.47]

50.8[2.00]

611.2[24.06]

581.3[22.88]

205.2[8.08]

50.8[2.00]

461.4 [18.17]88.9[3.50]

98.6[3.88]

394.7 [15.54]

203.3 [8.01]

189.8[7.47]

50.8[2.00]

611.2[24.06]

581.3[22.88]

205.2[8.08]

50.8[2.00]

461.4 [18.17]88.9[3.50]

98.6[3.88]

Mounting holes for

M10 (3/8”) hardware

(4 places)

Side View

Figure 4.5 – Power Stack Dimensions – 3300/4160V, 600A

Page 25: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Installation 4-9

1503E-IN001E-EN-P – June 2013

OVERALL DIMENSIONS:

WIDTH: 451.9 [17.79]

HEIGHT: 617.0 [24.29]

DEPTH: 399.3 [15.72]

WEIGHT: 42 kg [93 lbs]

Dimensions in millimeters [inches]

Front View

Side View

451.9 [17.79]

260.5 [10.26]88.9[3.50]

101.8[4.01]

212.6[8.37]

193.5[7.62]

617.0[24.29]

587.123.11]

50.8[2.00]

50.8[2.00]

399.3 [15.72]

Mounting holes for

M10 (3/8”) hardware

(4 places)

OVERALL DIMENSIONS:

WIDTH: 451.9 [17.79]

HEIGHT: 617.0 [24.29]

DEPTH: 399.3 [15.72]

WEIGHT: 42 kg [93 lbs]

OVERALL DIMENSIONS:

WIDTH: 451.9 [17.79]

HEIGHT: 617.0 [24.29]

DEPTH: 399.3 [15.72]

WEIGHT: 42 kg [93 lbs]

Dimensions in millimeters [inches]

Front View

Side View

451.9 [17.79]

260.5 [10.26]88.9[3.50]

101.8[4.01]

212.6[8.37]

193.5[7.62]

617.0[24.29]

587.123.11]

50.8[2.00]

50.8[2.00]

399.3 [15.72]

Mounting holes for

M10 (3/8”) hardware

(4 places)

Figure 4.6 – Power Stack Dimensions – 6900V, 180/360A

Page 26: MV SMC-Flex OEM Components - Rockwell Automation

4-10 Power Stack Installation

1503E-IN001E-EN-P – June 2013

Power Stack Mounting (cont.)

Front View

OVERALL DIMENSIONS:

WIDTH: 394.6 [15.54]

HEIGHT: 625.9 [24.64]

DEPTH: 461.4 [18.17]

WEIGHT: 57 kg [125 lbs]

Dimensions in millimeters [inches]

394.6 [15.54]

235.3[9.26]

88.9[3.50]

98.6[3.88]

203.2 [8.00]

50.8[2.00]595.9

[23.46]

625.9[24.64]

193.5[7.52]

50.8[2.00]

461.4 [18.17]

Side ViewMounting holes for

M10 (3/8”) hardware

(4 places)

Front View

OVERALL DIMENSIONS:

WIDTH: 394.6 [15.54]

HEIGHT: 625.9 [24.64]

DEPTH: 461.4 [18.17]

WEIGHT: 57 kg [125 lbs]

Dimensions in millimeters [inches]

394.6 [15.54]

235.3[9.26]

88.9[3.50]

98.6[3.88]

203.2 [8.00]

50.8[2.00]595.9

[23.46]

625.9[24.64]

193.5[7.52]

50.8[2.00]

461.4 [18.17]

394.6 [15.54]

235.3[9.26]

88.9[3.50]

98.6[3.88]

203.2 [8.00]

50.8[2.00]595.9

[23.46]

625.9[24.64]

193.5[7.52]

50.8[2.00]

461.4 [18.17]

Side ViewMounting holes for

M10 (3/8”) hardware

(4 places)

Figure 4.7 – Power Stack Dimensions – 6900V, 600A

Page 27: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Installation 4-11

1503E-IN001E-EN-P – June 2013

A T T E N T I O NA T T E N T I O N

To avoid shock hazard, lock out incoming power to power cables when completing connections. Failure to do so may result in severe burns, injury or death.

It is the responsibility of the OEM to ensure that suitable line and load cables are used to satisfy the requirements of the equipment and meet local electrical codes.

1) Use appropriate cable lugs to attach suitable line cables to the

line cable terminal (upper power terminal) of the heatsink

assembly. The terminal is predrilled with a mounting hole with a

diameter of 10.3 mm (0.406 in.). The holes are suitable for M10

(3/8 in.) hardware. Refer to Figure 4.8 for the terminal location.

Torque the fastening hardware to the specifications shown in

Table 4.D.

2) Use cable lugs to attach suitable load cables to the load cable

terminal (lower power terminal) of the heatsink assembly. Refer

to Figure 4.8 for the terminal location. Torque the fastening

hardware to the specifications shown in Table 4.D.

3) Refer to Chapters 6 and 7 for a typical wiring diagram to

determine the required connections. Appendix B includes a

typical schematic for a complete soft starter unit.

Line Cable Terminal

10.3 mm (0.406 in.) diameter

(All stacks in SMC frame have similar configuration)

Right Side View

Load Cable Terminal

10.3 mm (0.406 in.) diameter

Line Cable Terminal

10.3 mm (0.406 in.) diameter

(All stacks in SMC frame have similar configuration)

Right Side View

Load Cable Terminal

10.3 mm (0.406 in.) diameter

Figure 4.8 - Heatsink Assembly Power Connections (4160V, 360A heatsink shown)

I M P O R T A N TI M P O R T A N T

Power Connections

Page 28: MV SMC-Flex OEM Components - Rockwell Automation

4-12 Power Stack Installation

1503E-IN001E-EN-P – June 2013

A T T E N T I O NA T T E N T I O N

It is the responsibility of the OEM to ensure that the final enclosure is suitably bonded to ground, and that provisions for grounding are made according to local electrical codes and standards.

The SCRs in the power stacks are not intended for continuous

operation. Observe the following operating restrictions for the SMC

when operating at 450% FLC and maximum ambient (40°C).

• Power stacks must be bypassed using a separate contactor when

motor is up to speed.

• Do not operate the power stacks for more than 60 seconds per hour.

• Do not exceed 30 seconds for any individual duty cycle of the power

stacks.

• Do not operate the power stacks for at least five minutes between a

start or a stop cycle.

Note: It may be possible to exceed some of the above restrictions if

all maximum ratings are not attained. For example, higher

ambient conditions can be supported when the % FLC and/or

start time are reduced. Please consult factory for details.

A T T E N T I O NA T T E N T I O N

The operating restrictions for the SMC must be

adhered to. Failure to observe the recommended

precautions may result in injury to personnel or

damage to the equipment.

Power Stack Operating Restrictions

Grounding

Page 29: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Installation 4-13

1503E-IN001E-EN-P – June 2013

Voltage Sensing Board Dimensions

290.0 [11.42]

345.

0 [1

3.58

]

270.2 [10.64]38

5.0

[15.

16]

79.5[3.13]

11.5 [0.45]

290.0 [11.42]

345.

0 [1

3.58

]

270.2 [10.64]38

5.0

[15.

16]

79.5[3.13]

11.5 [0.45]

Figure 4.9 – Voltage Sensing Board Dimension Diagram

The voltage sensing board (VSB) should be mounted adjacent to the

power stacks (refer to Figure 4.9 for dimensions). All connection

points are to be made accessible. The same VSB is used regardless of

the system voltage.

Connect the voltage sensing board to the L1 to L3 and T1 to T3

terminals of the power stack (refer to Chapter 7). Observe the

connection points at the voltage sensing board per Table 4.E and

Figure 4.10.

Specifications for wire used on medium voltage connections:

UL style 3239, #18AWG, 40 KVDC silicone rubber insulated wire.

Table 4.E – Voltage Sensing Board Connections

System Voltage (VLL) VSB Taps

800 – 1500 D

1501 – 2500 C

2501 – 4800 B

4801 – 7200 A

Mounting and Connecting the Voltage Sensing Board

Page 30: MV SMC-Flex OEM Components - Rockwell Automation

4-14 Power Stack Installation

1503E-IN001E-EN-P – June 2013

Figure 4.10 – Voltage Sensing Board

Page 31: MV SMC-Flex OEM Components - Rockwell Automation

Power Stack Installation 4-15

1503E-IN001E-EN-P – June 2013

The CLGD power assembly is provided as a loose component with the

power stacks. It should be mounted adjacent to the power stacks in a

manner that allows the secondary cable assembly to be correctly

installed (see below). The CLGD power assembly requires a 110/120

or 220/240 VAC (50/60 Hz), 50 VA, primary source of power.

Use the supplied three-phase cable assembly to make the secondary

connections. Route the cable through the CLGD board CTs, as shown

in Figure 4.11. Refer to Chapter 7 for typical wiring diagram.

Figure 4.11 – Installation of Cable through CLGD CTs

The supplied cable comes with a protective sheath that should also be

installed. It protects the cable and enhances the system insulation

level.

NOTE: There are three individual cable loops (one for each

phase) connected in series. The cable length must be 6.4

metres (21 feet). Do not cut the extra length from these

cables, as they represent the load for the transformer in

the above power assembly. If they are shortened, the

loop current will be incorrect, and the CLGD boards

may not function properly during stop maneuvers.

Current Loop Gate Drive Power Assembly (CLGD)

Page 32: MV SMC-Flex OEM Components - Rockwell Automation

4-16 Power Stack Installation

1503E-IN001E-EN-P – June 2013

Page 33: MV SMC-Flex OEM Components - Rockwell Automation

Chapter 5

1503E-IN001E-EN-P – June 2013

Control Component Installation Interface Board Installation Mount the Interface Board in a suitable location within a low voltage

compartment, using the appropriate hardware. Use the interface board

mounting bracket (refer to Figure 5.1).

A T T E N T I O NA T T E N T I O N

Do not mount the interface board in the same

compartment as high voltage components.

Ensure that barriers are provided in the final

application to prevent access to any live high-

voltage parts, including insulated conductors

located in enclosures with low voltage parts and

wiring. Failure to do so may result in severe

burns, injury or death.

Figure 5.1 – Mounting the Interface Board

Page 34: MV SMC-Flex OEM Components - Rockwell Automation

5-2 Control Component Installation

1503E-IN001E-EN-P – June 2013

A T T E N T I O NA T T E N T I O N

Do not touch or bend the connectors on the

Interface Board when handling it. Damage to the

connectors may result in loss of communication

signals from the MV SMC Flex to other

components.

Figure 5.2 – Interface Board Layout

Interface Board Installation (cont.)

Page 35: MV SMC-Flex OEM Components - Rockwell Automation

Control Component Installation 5-3

1503E-IN001E-EN-P – June 2013

I M P O R T A N TI M P O R T A N T

• 800-2499V – Two fiber optic transmitters per

phase are used.

• 2500-4799V – Four fiber optic transmitters

per phase are used.

• 4800-6900V – Six fiber optic transmitters per

phase are used.

Connect control power to the interface board. Use a grounded supply

source from 110 to 240 +10, -15% VAC, 50/60 Hz, 15 VA.

Connect 5A current transformer (CT) secondary signals to the interface

board, noting the required CT polarity. Three-phase CTs are required.

Connect the interface board module common (upper right) to a suitable

ground location in the control compartment, as required.

NOTES:

1. Only ground the module common connection if the power

system is solidly or resistively connected to ground. If the

power system is ungrounded, do not do so.

2. Ensure that Ground Instruction Tag (part number 80006-346-01)

is affixed to the ground connection to alert the final customer

of this requirement.

SMC Flex Control Module 1) Connect the ribbon cables (5) to the back of the SMC Flex control

module.

2) Align the ribbon cables (5) from the SMC Flex Control Module

with the connectors on the Interface Board. Push the ribbon

connectors into the mating connectors on the interface board.

3) Use the supplied screws to securely fasten the module to the board

mounting bracket.

4) Supply power to the SMC Flex control module and make the

required control connections.

Refer to User Manual, MV SMC Flex Motor Controller Bulletin

1503E, 1560E,1562E – Publication 1560E-UM051_-EN-P for

detailed instructions on wiring and programming the unit.

Interface Board Connections

Page 36: MV SMC-Flex OEM Components - Rockwell Automation

5-4 Control Component Installation

1503E-IN001E-EN-P – June 2013

Use the wire harness provided to connect the Voltage Sensing Board

and the Interface Board. Refer to Figure 5.2 for the location of the

connector on the interface board, and Figure 4.8 for the connector on

the voltage sensing board.

1) Use the fiber optic cables (Cat. No. 1503E-XXFOXX) to connect

each fiber optic receiver from the gate driver boards to the

interface board (refer to Figure 5.2). Ensure that the gate driver

boards of each power phase are connected to the correct terminals

on the Interface Board. Observe the minimum bend radius of at

least 45 mm (1.75 in.) for the fiber optic cables.

A T T E N T I O NA T T E N T I O N

Do not sharply bend or strike the fiber optic

cables when handling them. A minimum bend

radius of at least 45 mm (1.75 in.) should be

maintained throughout the system. Damaging

the cables may result in signal loss to the

components and improper functioning of the

unit.

Fiber optic components are color coded for

easier connections. Receiver terminals are dark

blue, and transmitter terminals are grey or black.

The cables have a grey connector at one end and

a blue one at the other. When connecting to the

gate driver boards, the dark blue connector must

plug into the dark blue receiver and the grey

connector must plug into the black transmitter

Refer to the appropriate wiring diagram in Chapter 7.

It is acceptable to connect the fiber optic

transmitter cables to any port within a particular

power phase. Note that the cables for the

temperature feedback ports should be connected

to the correct phase. Refer to Figure 5.2 for the

Interface Board layout.

2) Connect the temperature feedback fiber optic receivers for each

phase to the appropriate gate driver board. Refer to Chapter 7 for

the appropriate diagram for the temperature feedback fiber optic

connections.

Connecting Interface Board to Voltage Sensing Board

Connecting Interface Board to Gate Driver Board

I M P O R T A N TI M P O R T A N T

I M P O R T A N TI M P O R T A N T

Page 37: MV SMC-Flex OEM Components - Rockwell Automation

Control Component Installation 5-5

1503E-IN001E-EN-P – June 2013

Additional control components are required to complete the circuit,

depending on the application. Some of these control components are

outlined in Chapter 6 and Appendix B.

It is the responsibility of the OEM to ensure that all required control

components are supplied and functional.

Additional Control Components

Page 38: MV SMC-Flex OEM Components - Rockwell Automation

5-6 Control Component Installation

1503E-IN001E-EN-P – June 2013

Page 39: MV SMC-Flex OEM Components - Rockwell Automation

Chapter 6

1503E-IN001E-EN-P – June 2013

Contactor Installation Introduction The MV SMC Flex components are designed for intermittent starting

duty. A bypass contactor must be used to bypass the power stacks

once the motor is at full speed.

A line contactor is also required in order to isolate the power stacks

from line voltage. A suitable medium voltage circuit breaker may be

substituted for the line contactor.

Main and Bypass Contactors Refer to Table 6.A for the required installation for contactors.

Table 6.A – Required Installation Instructions for OEM Components Component Required Installation Documents

Isolation Contactor • User Manual – OEM Frame and Components, Bulletin 1503, Publication 1503-5.0

• User Manual – Medium Voltage Contactor, Series E, Bulletin 1502, 400 Amp, Publication 1502-UM052_-EN-P or Series D, Publication 1502-UM050_-EN-P or Medium Voltage Contactor, Series D & E, Bulletin 1502, 800 Amp, Publication 1502-UM051_-EN-P

Bypass Contactor • User Manual – Medium Voltage Contactor, Series E, Bulletin 1502, 400 Amp, Publication 1502-UM052_-EN-P or Series D, Publication 1502-UM050_-EN-P or Medium Voltage Contactor, Series D & E, Bulletin 1502, 800 Amp, Publication 1502-UM051_-EN-P

Bypass Contactor A bypass contactor must be used in the SMC configuration to bypass

the SCRs once the motor is up to speed.

Refer to User Manual, MV SMC Flex™ Motor Controller, Bulletin

1503E, 1560E, 1562E, Publication 1560E-UM051_-EN-P for more

information on the bypass contactor and the duty cycle. This

publication was included with your shipment.

A T T E N T I O NA T T E N T I O N

A bypass contactor must be installed to complete the SMC configuration. SCRs are not rated for continuous duty. The duty cycle is limited to 60 seconds per hour. This can be a combination of starting and stopping cycles that does not exceed 30 seconds per cycle. Failure to install a bypass contactor may result in damage to components from overheating.

Page 40: MV SMC-Flex OEM Components - Rockwell Automation

6-2 Vacuum Contactor Installation

1503E-IN001E-EN-P – June 2013

Bypass Contactor (cont.) A typical schematic diagram for the main and bypass contactors is

shown in Figure B.1, Appendix B. Figure 6.1 below, shows the point-

to-point connections for the main and bypass contactors.

I M P O R T A N TI M P O R T A N T

It is the responsibility of the OEM to ensure that

suitable line and load cables are used that satisfy

the requirements of the equipment and meet

local electrical codes.

Incoming power from fused power source

Main Contactor(Rear View)

Bypass

Contactor

(Rear View)

Power Stacks

To load CTs

Incoming power from fused power source

Main Contactor(Rear View)

Bypass

Contactor

(Rear View)

Power Stacks

To load CTs

Figure 6.1 – Main and Bypass Contactor Wiring Configuration

Page 41: MV SMC-Flex OEM Components - Rockwell Automation

Vacuum Contactor Installation 6-3

1503E-IN001E-EN-P – June 2013

Four (4) clearance holes are provided in the control panel for

mounting. The holes are 5.5 mm (0.219 in.) in diameter and are

suitable for M6 (1/4-20) self-tapping fasteners. See Figure 6.2 for the

control panel dimensions.

1) Mount the control panel in a suitable location that is isolated from

medium voltage components. Be aware that the control plug wiring

harness is 10 ft. (3 meters) in length. Ensure that the wiring harness

route still allows for a proper connection to the contactor control

plug.

A T T E N T I O NA T T E N T I O N

Do not mount the control panel in the same

compartment as high voltage components. Low

voltage components must be electrically isolated

from high voltage components to ensure access

is available when the unit is energized. Failure to

do so may result in severe burns, injury or death.

All dimensions in millimeters [inches]

Clearance holes (4)5.5 mm [0.2 in.]

229 [9.00]

213 [8.38]

224

[8.83]

240

[9.46]

All dimensions in millimeters [inches]

Clearance holes (4)5.5 mm [0.2 in.]

229 [9.00]

213 [8.38]

224

[8.83]

240

[9.46]

Figure 6.2 – Bypass Contactor Control Panel Dimensions

Bypass Contactor Control Panel

Page 42: MV SMC-Flex OEM Components - Rockwell Automation

6-4 Vacuum Contactor Installation

1503E-IN001E-EN-P – June 2013

2) Connect the control panel harness to the contactor control wire

plug on the lower left side of the contactor (see Figure 6.3. Each

control wire plug is designed to only connect to a contactor that

has a matching voltage and current rating.

3) Use the terminal blocks on the control panel to connect the unit to

a 120 or 230 volt grounded power source (whichever is applicable

to the control panel) and to other remote devices. See Appendix B

for a typical SMC schematic diagram.

Contactor Control

Wire Plug

Contactor Control

Wire Plug

Figure 6.3 – 120V and 230V Control Wire Plug Location (400A contactor shown)

IntelliVAC Control Module An IntelliVAC control module can be substituted for the control panel

to control the main and bypass vacuum contactors (Series E contactors

only).

Refer to publications 1560E-UM051_-EN-P and 1503-UM051_-EN-P

(IntelliVAC Series A or B) or 1503-UM052_EN-P (IntelliVAC Series C)

for instructions on wiring and set-up of the IntelliVAC control module.

Bypass Contactor Control Panel (cont.)

Page 43: MV SMC-Flex OEM Components - Rockwell Automation

Chapter 7

1503E-IN001E-EN-P – June 2013

Typical Wiring Diagrams

Wiring Diagrams The following wiring diagrams illustrate the connections between the

main components of the MV SMC Flex OEM kits. Some of the

connections are pre-made by Rockwell Automation, depending on the

type of OEM kit being used. It is the responsibility of the OEM to

correctly identify the OEM kit utilized and the connections they must

make.

Additional components are typically required to complete the MV

SMC. Refer to Appendix B for examples of how these additional

components can be implemented to form a complete solution.

A T T E N T I O NA T T E N T I O N

Wires used for connecting the components must

be sufficiently insulated to withstand system

voltage. Refer to the appropriate wiring diagram

for the wire insulation requirements. Failure to

use adequately insulated wiring may cause

injury to personnel and/or damage to the

equipment.

Page 44: MV SMC-Flex OEM Components - Rockwell Automation

7-2 Schematic and Wiring

1503E-IN001E-EN-P – June 2013

G

L2/N

L1TB

1J3

VO

LTA

GE

SE

NS

ING

BO

AR

D

6A5A

4A3A

2A1A

6B5B

4B3B

2B1B

6D6C

5D4D

5C4C

3D3C

2D2C

1D1C

J1G

ND

1G

ND

2

T3

L3T

2L2

T1

L1

CU

RR

EN

T L

OO

P C

T

RS

0V2

CS

GD

2

C2

G2

0V1

S C

GD

1

C1

G1

TH

ER

MIS

TO

R

T

GA

TE

DR

IVE

R B

OA

RD

S

LOA

D

TH

ER

MIS

TO

R

RR

1

HS

3

HS

2

C2

G2

LIN

E

C1

G1

HS

1C

S

TB

6

U16

TX

17

TX

18

U18

U20

TX

10

TX

12

TX

11

TX

13

TX

14

TX

15

TX

16

TX

6

TX

5

TX

9

TX

8

TX

7

TX

4

GD

PS

C+

A-

A+

B+B-

TB

5

C-

TX

2

TX

1

TX

3

VS

B

TB

21

Vco

m

SM

C-F

LEX

INT

ER

FA

CE

BO

AR

D

PH

AS

E B

PH

AS

E C

TX

1R

X1

S1

L1 S2

C1 0V

1

0V2

C2

CU

RR

EN

T L

OO

P

TR

AN

SF

OR

ME

R

H1

H3

H2

H4

X1

X2

FIB

RE

OP

TIC

CA

BLE

S

RX

1T

X1

C1

115/230V AC

50/60Hz

T1

C2

115/230V AC

PHASE A PHASE C TEMP.

CT INPUTS

GATE TRANSMITTERS

PHASE B

TO C.T.'S

TO SMC FLEXMODULE

POWERIN

POWEROUT

G

G DO NOT CONNECT IF POWERSYSTEM IS NOT GROUNDED

Figure 7.1 – Power Circuit Wiring Diagram (180/360A, 800 to 1449V)

Page 45: MV SMC-Flex OEM Components - Rockwell Automation

Schematic and Wiring 7-3

1503E-IN001E-EN-P – June 2013

VO

LTA

GE

SE

NS

ING

BO

AR

D

6A5A

4A3A

2A1A

6B5B

4B3B

2B1B

6D6C

5D4D

5C4C

3D3C

2D2C

1D1C

J1G

ND

1G

ND

2

T3

L3T

2L2

T1

L1

CU

RR

EN

T L

OO

P C

T

RS

0V2

CS

GD

2

C2

G2

0V1

S C

GD

1

C1

G1

TH

ER

MIS

TO

R

T

GA

TE

DR

IVE

R B

OA

RD

S

LOA

D

TH

ER

MIS

TO

R

RR

1

HS

3

HS

2

C2

G2

LIN

E

C1

G1

HS

1C

S

TB

6

PHASE A PHASE C

U16

TX

17

TX

18

U18

U20

TEMP.

CT INPUTS

TX

10

GATE TRANSMITTERS

PHASE B

TX

12

TX

11

TX

13

TX

14

TX

15

TX

16

TX

6

TX

5

TX

9

TX

8

TX

7

TX

4

GD

PS

C+

A-

A+

B+B-

TB

5

C-

TX

2

TX

1

TX

3

VS

B

TB

21

Vco

m

TO C.T.'S

SM

C-F

LEX

INT

ER

FA

CE

BO

AR

D

PH

AS

E B

PH

AS

E C

TX

1R

X1

S1

L1 S2

C1 0V

1

0V2

C2

CU

RR

EN

T L

OO

P

TR

AN

SF

OR

ME

R

H1

H3

H2

H4

X1

X2

FIB

RE

OP

TIC

CA

BLE

S

RX

1T

X1

C1

115/230V AC

50/60Hz

T1

C2

TO SMC FLEXMODULE

G

L2/N

L1

POWERIN

POWEROUT

TB

1J3

115/230V AC

G

DO NOT CONNECT IF POWERSYSTEM IS NOT GROUNDED

G

Figure 7.2 – Power Circuit Wiring Diagram (180/360A, 1450 to 2499V)

Page 46: MV SMC-Flex OEM Components - Rockwell Automation

7-4 Schematic and Wiring

1503E-IN001E-EN-P – June 2013

VO

LTA

GE

SE

NS

ING

BO

AR

D

6A5A

4A3A

2A1A

6B5B

4B3B

2B1B

6D6C

5D4D

5C4C

3D3C

2D2C

1D1C

J1G

ND

1G

ND

2

T3

L3T

2L2

T1

L1

CU

RR

EN

T L

OO

P C

T

RS

0V2

CS

GD

2

C2

G2

0V1

S C

GD

1

C1

G1

TH

ER

MIS

TO

R

T

GA

TE

DR

IVE

R B

OA

RD

S

LOA

D

TH

ER

MIS

TO

R

RR

1

HS

3

HS

2

C2

G2

LIN

E

C1

G1

HS

1C

S

TB

6

U16

TX

17

TX

18

U18

U20

TX

10

GATE TRANSMITTERS

TX

12

TX

11

TX

13

TX

14

TX

15

TX

16

TX

6

TX

5

TX

9

TX

8

TX

7

TX

4

GD

PS

C+

A-

A+

B+B-

TB

5

C-

TX

2

TX

1

TX

3

VS

B

TB

21

Vco

m

SM

C-F

LEX

INT

ER

FA

CE

BO

AR

D

PH

AS

E B

PH

AS

E C

TX

1R

X1

S1

L1 S2

C1 0V

1

0V2

C2

CU

RR

EN

T L

OO

P

TR

AN

SF

OR

ME

R

H1

H3

H2

H4

X1

X2

FIB

RE

OP

TIC

CA

BLE

S

RX

1T

X1

C1

115/230V AC

50/60Hz

T1

C2

G

L2/N

L1TB

1J3

115/230V AC

PHASE A PHASE C TEMP.

CT INPUTS

GATE TRANSMITTERS

PHASE B

TO C.T.'S

TO SMC FLEXMODULE

POWERIN

POWEROUT

G

DO NOT CONNECT IF POWERSYSTEM IS NOT GROUNDED

G

Figure 7.3 - Power Circuit Wiring Diagram (600A, 1450 to 2499V)

Page 47: MV SMC-Flex OEM Components - Rockwell Automation

Schematic and Wiring 7-5

1503E-IN001E-EN-P – June 2013

G

L2/N

L1TB

1J3

VO

LTA

GE

SE

NS

ING

BO

AR

D

6A5A

4A3A

2A1A

6B5B

4B3B

2B1B

6D6C

5D4D

5C4C

3D3C

2D2C

1D1C

J1G

ND

1G

ND

2

T3

L3T

2L2

T1

L1

CU

RR

EN

T L

OO

P C

T

0V4

0V3

CSCS

GD

4

C4

G4

GD

3

C3

G3

RS

1

0V2

CS

GD

2

C2

G2

0V1

S C

GD

1

C1

G1

TH

ER

MIS

TO

R

T

GA

TE

DR

IVE

R B

OA

RD

S

C3

RR

1

C4

HS

5

LOA

D

G4

HS

4

TH

ER

MIS

TO

R

RR

2

G3

HS

3

HS

2

C2

G2

LIN

E

C1

G1

HS

1

CS

1

TB

6

U16

TX

17

TX

18

U18

U20

TX

10

TX

12

TX

11

TX

13

TX

14

TX

15

TX

16

TX

6

TX

5

TX

9

TX

8

TX

7

TX

4

GD

PS

C+

A-

A+

B+B-

TB

5

C-

TX

2

TX

1

TX

3

VS

B

TB

21

Vco

m

SM

C-F

LEX

INT

ER

FA

CE

BO

AR

D

PH

AS

E B

PH

AS

E C

TX

1R

X1

S1

L1 S2

S4

C3

S3

0V3

0V4

C4

C1 0V

1

0V2

C2

CU

RR

EN

T L

OO

P

TR

AN

SF

OR

ME

R

H1

H3

H2

H4

X1

X2

FIB

RE

OP

TIC

CA

BLE

S

RX

1T

X1

TX

1R

X1

RX

1T

X1

C1

115/230V AC

50/60Hz

CS

2

RS

2

C2

C2

T1

C4

115/230V AC

PHASE A PHASE C TEMP.

CT INPUTS

GATE TRANSMITTERS

PHASE B

TO C.T.'S

TO SMC FLEXMODULE

POWERIN

POWEROUT

G

G DO NOT CONNECT IF POWERSYSTEM IS NOT GROUNDED

Figure 7.4 – Power Circuit Wiring Diagram (180/360/600A, 2500 to 4799V)

Page 48: MV SMC-Flex OEM Components - Rockwell Automation

7-6 Schematic and Wiring

1503E-IN001E-EN-P – June 2013

115/230V AC

G

L2/N

L1TB

1J3

VO

LTA

GE

SE

NS

ING

BO

AR

D

6A5A

4A3A

2A1A

6B5B

4B3B

2B1B

6D6C

5D4D

5C4C

3D3C

2D2C

1D1C

J1G

ND

1G

ND

2

T3

L3T

2L2

T1

L1

CU

RR

EN

T L

OO

P C

T

0V6

S C

GD

6

C6

G6

0V5

0V4

CSCS

GD

5

C5

G5

GD

4

C4

G4

RS

2

0V3

CS

GD

3

C3

G3

0V2

S C

GD

2

C2

G2

TH

ER

MIS

TO

R

T

GA

TE

DR

IVE

R B

OA

RD

S

0V1

CSG

D1

G1

C1

C4

RR

3

HS

7

C5

G6

C6

HS

6LO

AD

G5

HS

5

TH

ER

MIS

TO

R

RR

2

RR

1

G3

G4

HS

4

C3

HS

3

C2

G2

LIN

E

HS

2

C1

G1

HS

1

CS

2

RS

1

CS

1

RS

3

CS

3

TB

6

U16

TX

17

TX

18

U18

U20

TX

10

TX

12

TX

11

TX

13

TX

14

TX

15

TX

16

TX

6

TX

5

TX

9

TX

8

TX

7

TX

4

GD

PS

C+

A-

A+

B+B-

TB

5

C-

TX

2

TX

1

TX

3

VS

B

TB

21

Vco

m

SM

C-F

LEX

INT

ER

FA

CE

BO

AR

D

PH

AS

E B

PH

AS

E C

TX

1R

X1

S2

L1 S3

C3

S1

C1

C5

C5

S5

C4

S4

S6

T1

C5 0V

5

0V6

C6

C1 0V

1

0V4

C2 0V

2

0V3

C3

C4

CU

RR

EN

T L

OO

P

TR

AN

SF

OR

ME

R

H1

H3

H2

H4

X1

X2

FIB

RE

OP

TIC

CA

BLE

S

RX

1T

X1

RX

1T

X1

TX

1R

X1

RX

1T

X1

RX

1T

X1

C2

C6

115/230V AC

50/60Hz

PHASE A PHASE C TEMP.

CT INPUTS

GATE TRANSMITTERS

PHASE B

TO C.T.'S

TO SMC FLEXMODULE

POWERIN

POWEROUT

G

DO NOT CONNECT IF POWERSYSTEM IS NOT GROUNDED

G

Figure 7.5 - Power Circuit Wiring Diagram (180/360/600A, 4800 to 6900V)

Page 49: MV SMC-Flex OEM Components - Rockwell Automation

Chapter 8

1503E-IN001E-EN-P – June 2013

Final Test Procedures Final Test Procedures • Verify that the enclosure is properly grounded.

• Verify that phase-to-phase and phase-to-ground clearances meet

the requirements of the local electrical code.

• Visually check for sufficient electrical clearances, creepage

allowances and bend radii. Refer to the applicable local electrical

codes.

• Check the tightness of all power and control connections. Refer to

Table 8.A for recommended torque values. Gently tug on all wires

to ensure that they are properly connected.

Table 8.A – Recommended Torque Values

Hardware Recommended Torque

1/4 in. 6 ft·lb (8 N·m)

5/16 in. 11 ft·lb (15 N·m)

3/8 in. 20 ft·lb (27 N·m)

1/2 in. 48 ft·lb (65 N·m)

Control Wire Terminals 3 in·lb (0.3 N·m)

CLGD Power Assembly Terminals 50 in·lb (5.6 N·m)

SMC Flex Control Module Terminals 5 in·lb (0.6 N·m)

A T T E N T I O NA T T E N T I O N

All hardware for electrical connections must be

torqued to the above specifications. Failure to do

so may result in electrical faults causing

personal injury or damage to the equipment.

• Check for cross-threaded hardware. In addition to the regular

power connections, check the connections and wiring to the

voltage sensing board.

• The high voltage silicone-insulated wires must be identified with

tube markers. Avoid routing the wires over any components. If the

wires are routed across two heatsinks, there must be enough slack

in the wire to allow at least 10 centimeters (four inches) of creepage

between the heatsinks. Tie wraps must not tightly squeeze the high

voltage wires, and must not be put on with a tie-wrap gun.

Page 50: MV SMC-Flex OEM Components - Rockwell Automation

8-2 Final Test Procedures

1503E-IN001E-EN-P – June 2013

• Do not remove the plastic plugs from unused fiber optic

transmitters on the circuit boards.

• Verify that the fiber optic cables between the interface board and

the gate driver boards are connected to the correct power phase.

• Check the routing of the twisted pair of red and white cathode and

gate wires from the SCRs. They can safely touch the heatsink on

the side of the SCR that they are exiting; however, they must not

touch the heatsink on the other side of the SCR. The wires must be

properly supported to ensure this condition is met. The gate leads

must be arranged in the same sequence - top to bottom – as

connected to the gate driver boards. See wiring diagrams in

Chapter 7 for the sequences.

• Verify ground wire connection (if required) at the interface board

(refer to page 5-3).

• Wiring to the voltage sensing board from the power stacks must be

rated for the line voltage. Rockwell Automation recommends UL

style 3239, #18 AWG, 40 kVDC silicone rubber insulated wire for

this application.

• If the bypass vacuum contactor (and capacitor contactor if

applicable) is Series D or earlier, then the contactor must have a

fast drop-out time (typically 50 milliseconds or less) When using

Series E or later vacuum contactors, the drop-out delay is

controlled by the IntelliVAC module (set for minimum delay of 50

milliseconds).

Dielectric Test

1. Remove the six high voltage wires from the voltage sensing board,

and isolate the ends to prepare for the Hi-Pot test.

2. Jumper the heatsinks together within each phase as shown in Table

8.B. See Figure 8.1 for the jumper positioning on the 4160V,

360A heatsink. Table 8.B – Jumper Configuration for Hi-Pot Testing

800 – 2400 V Power Stacks

3300/4160 V Power Stacks

6900 V Power Stacks

Jumper 1, 2 Jumper 1, 2, 4 Jumper 1, 2, 3, 6

Final Test Procedures (cont.)

Page 51: MV SMC-Flex OEM Components - Rockwell Automation

Final Test Procedures 8-3

1503E-IN001E-EN-P – June 2013

Test-jumper positionfor heatsinks 1 and 2

Test-jumper position for heatsinks 2 and 4

HS1

HS2

HS3

HS4

HS5

Heatsinks are numberedfrom top to bottom.

Test-jumper positionfor heatsinks 1 and 2

Test-jumper position for heatsinks 2 and 4

HS1

HS2

HS3

HS4

HS5

Heatsinks are numberedfrom top to bottom.

Figure 8.1 – Example of Jumper Positioning for Hi-pot Test - 4160V, 360A Heatsink shown

3. Measure the resistance between the line and load sides of each

phase to make sure there is zero resistance. This indicates that the

jumpers are properly set on the cathodes.

4. Perform a Hi-Pot test as required by the applicable local codes and

standards.

5. After the Hi-Pot remove the heatsink jumpers. Re-connect the six

feedback board wires.

6. Perform a resistance check for each SCR. The SCR resistance can be

checked directly at the device or at the leads on the gate driver board.

a) The gate-to-cathode resistance should range from 10 to 40

ohms for all styles.

b) The cathode-to-cathode resistance can also be checked and

compared to the results shown on Table 8.C. See Figure 8.2 for

the testing points on the gate driver boards.

Table 8.C – Power Circuit Resistance Measurements

Location of Probes 1000 V 2300 V 3300 V 4160 V 5500 V 6900 V

Cathode to Cathode (KOhms) – – 22-30 23-31 21-29 24-32

Cathode to Cathode (KOhms) 17-23 21-29 40-53 43-57 60-80

64-84

Cathode to Gate (Ohms) 10-40 10-40 10-40 10-40 10-40 10-40

Measured between terminals “Cathode” on CL Boards, upper two or bottom two within a phase.

Measured between terminals “Cathode” on CL Boards, top to bottom within a phase.

Measured between line and load terminals within a phase.

Page 52: MV SMC-Flex OEM Components - Rockwell Automation

8-4 Final Test Procedures

1503E-IN001E-EN-P – June 2013

Snubber

terminal

Temperature signal

fiber-optic transmitter

Current loop CTPlug-in test

power supply

Gate signal

fibre-optic receiver

Cathode

terminal

Common

test point+20V test point Overvoltage

sense terminal

+5V test point

Yellow LED

Thermistor

connector

Gate signal

test point

J2

TP1

TP2

J6

RX1 TX1

TP3 TP4

J1

J4

J3

J5

Gate/Cathode

connector

Snubber

terminal

Temperature signal

fiber-optic transmitter

Current loop CTPlug-in test

power supply

Gate signal

fibre-optic receiver

Cathode

terminal

Common

test point+20V test point Overvoltage

sense terminal

+5V test point

Yellow LED

Thermistor

connector

Gate signal

test point

J2

TP1

TP2

J6

RX1 TX1

TP3 TP4

J1

J4

J3

J5

Gate/Cathode

connector

Figure 8.2 –Current Loop Gate Driver (CLGD) Board Test Points

7. Check all line and load resistances to ground at the interface board.

The measurement for all voltages should be within 11 k ohms to 13

k ohms.

Additional Tests Perform additional tests, as outlined in Chapter 3 of User Manual,

SMC Flex Motor Controller, Bulletin 1503E, 1560E, 1562E,

Publication 1560E-UM051_-EN-P.

Spare Parts For a complete listing of spare parts, refer to User Manual, SMC Flex

Motor Controller, Bulletin 1503E, 1560E, 1562E, Publication

1560E-UM051_-EN-P.

Page 53: MV SMC-Flex OEM Components - Rockwell Automation

Appendix A

1503E-IN001E-EN-P – June 2013

Component Deratings

The components described in this publication may be applied in a wide

variety of situations. Some applications may require component

derating. For example, at altitudes above 1000 m (3300 ft.), the

maximum current and basic impulse level (BIL) are reduced as shown

in Table A.1.

Table A.1 – Component Derating Table

Altitude Rating

Reduce Max. Continuous Current Rating

by : Reduce B.I.L.

Withstand Rating by:

180 A 360 A 600 A

0 to 1,000 m (0 to 3,300 ft)

— — — —

1,001 to 2,000 m (3,301 to 6,600 ft)

10 A 10 A 15 A 6.0 kV

2,001 to 3,000 m (6,601 to 9,900 ft)

20 A 20 A 30 A 12.0 kV

3,001 to 4,000 m (9,901 to 13,200 ft)

30 A 30 A 45 A 18.0 kV

4,001 to 5,000 m (13,201 to 16,500 ft)

40 A 40 A 60 A 24.0 kV

Page 54: MV SMC-Flex OEM Components - Rockwell Automation

A-2 Component Deratings

1503E-IN001E-EN-P – June 2013

Page 55: MV SMC-Flex OEM Components - Rockwell Automation

Appendix B

1503E-IN001E-EN-P – June 2013

Typical MV SMC Flex Schematic Diagrams

Introduction This Appendix contains a typical schematic for a complete MV SMC

Flex controller (refer to Figure B.1).

Refer to publication 1560E-UM051_-EN-P for additional samples of

MV SMC Flex wiring configuration. The examples shown are not a

recommendation for the correct wiring configurations, nor is the OEM

required to design the SMC Flex exactly as shown.

The OEM must ensure that all wiring for the SMC Flex unit meets all

performance and safety requirements, including any applicable laws,

regulations, codes and standards.

Rockwell Automation does not assume any responsibility or liability

for loss or damages caused by failures in the unit manufactured by the

OEM.

For more information, see the Warranty section in General Terms and

Conditions of Sale, Publication 6500-CO001_-EN-P.

Page 56: MV SMC-Flex OEM Components - Rockwell Automation

B-2 Typical MV SMC Flex Wiring Diagrams

1503E-IN001E-EN-P – June 2013

CURRENT LIMITINGPOWER FUSES

L1 ISOLATING SWITCH

DOOR INTERLOCK

GRDL2 L3

MAXIMUM TWO STARTS PER HOUR WITH AMINIMUM OF FIVE MINUTES BETWEEN STARTS.

CAUTION:

WIRE CONNECTIONS FOR PHASE A

REMOTE EQUIPMENT

CONNECTIONS SHOWN FOR PHASE C

WIRE CONNECTIONS FOR PHASE B

TO SMC-FLEX

TO CONTROL CIRCUIT

CURRENT LIMITINGPRIMARY FUSES

500CPT

H1 H2

X1 X2

VA

VOLTAGE SENSING BOARDSMC-FLEX INTERFACE BOARD

24C

4160V AC, 3Ø, 60Hz

4200V

120V

CURRENT LOOP CONDUCTORS PASS THROUGH THE C.T.'SON THE GATE DRIVER BOARDS (CLGD)

C

A

B

C

A

B

A

B

G

CL

CONNECT TO GROUND ONLY IF POWER SYSTEM IS GROUNDEDG

VSB

1B

2B

3B

4B

5B

6BGND2GND1

A: 4800-7200VB: 2500-4799VC: 1450-2499VD: 800-1449V

J1

IS

ISa

M

B

CT3

CT2

CT1T1

T2

T3

MTR

2

OV1

1

RS1S1

OV2

RR1

CS1S2

4

S4

3

OV4

S3

OV3

RR2

RS2 CS2

C1 C2 C3 C4

TX1RX1 G C

TEST

CT

CLGD

-+ OV S

T

C

CLGDCLGD

CRX1 TX1 G

TEST

CT

RX1T TX1 G

CT

TEST

S+ OV- C -+ OV

C T TX1RX1 G

CT

TEST

C T

CLGD

OVS C + - S C

SMCFLEXIB

TB6

PH

AS

E A

PH

AS

E C

U16

TX17

TX18

U18

U20

TE

MP

.

CT

INP

UT

S

TX10

GA

TE

TR

AN

SM

ITT

ER

S

PH

AS

E B

TX12

TX11

TX13

TX14

TX15

TX16

TX6

TX5

TX9

TX8

TX7

TX4

GDPS

C+

A-

A+

B+

B-

TB5

C-

TX2

TX1

TX3

VSB

TB21

Vcom

T3

T1

T2

L3

L2

L1

L1

L2

L3

FROM CLT

GFCT100:1

(OPTIONAL)

G

L2/N

L1

PO

WE

RIN

PO

WE

RO

UT

TB1 J3FROM

CONTROLCIRCUIT

TO SMC-FLEX(11, 12)

(27, 28)

Figure B.1 – Typical MV SMC Flex Schematic Diagram, 3300/4160V (1 of 2)

Page 57: MV SMC-Flex OEM Components - Rockwell Automation

Typical MV SMC Flex Wiring Diagrams B-3

1503E-IN001E-EN-P – June 2013

TEST SUPPLY POINT

FROMCPT TEST SUPPLY POINT

TS

ØA

#6 AWG 50kV

#6 AWG 600V

ØB ØC

CURRENT LOOP TRANSFORMER

TO

BYPASS CONTACTORAUXILIARY RELAY

AUXILIARY RELAYMAIN CONTACTOR

FROM GFCT

SMC-FLEX TO BEPROGRAMMED BYTHE CUSTOMERBEFORE START-UP

BYPASS CONTACTOR

MAIN CONTACTOR

CL

29 3028272524 2623 33 34

201918171514 161311 12

TMSMC-FLEX

DPI

21 22

31 32

CONTROL TERMINALS AUX.1UP-TO-SPEED

AUX.4NORMAL

GROUNDFAULT

TACHINPUT

PTCINPUT

M

MOV

B

MOV

SMCFLEXIBINPUT POWER

X

CLT

H1 H3 H2 H4

X1 X2

120V

0.6V

M-IV

32

1EC

-

+

4TCO

12

11AUX CCO

5

6

L1 G

MCX

BCX CR

STOP

NB BA

B-IV

32

1EC

-

+

4TCO

12

11AUX CCO

5

6

L1 G

CR

START

A BM N

ISb

X60Hz120V

MCX

M

C

BCX

CR

M

C

NORMAL

OFF

TEST

X

X

L2/N

L2/N

SS

SS

SMCFLEXIB-TB6 R

B-IV

9 10

CLOSE

+ -

B-IV

15 16CONTACTOR

STATUS

M-IV

9 10

CLOSE

+ -

M-IV

13 14MODULESTATUS

B-IV

13 14MODULESTATUS

M-IV

15 16CONTACTOR

STATUS

CONTROL RELAY

AUX.2FAULT

AUX.3ALARM

FROMSMCFLEXIB-J3

(OPTIONAL)

Figure B.1 – Typical MV SMC Flex Schematic Diagram, 3300/4160V (2 of 2)

Page 58: MV SMC-Flex OEM Components - Rockwell Automation

B-4 Typical MV SMC Flex Wiring Diagrams

1503E-IN001E-EN-P – June 2013

Page 59: MV SMC-Flex OEM Components - Rockwell Automation

Appendix C

1503E-IN001E-EN-P – June 2013

SMC Flex OEM Power Stack Kit Chart

Table C.1 – SMC Flex OEM Power Stack Kit Chart

Final Part Number Description RA Internal

Part Number Parts supplied in

the RA part number Qty

1503E-PPZ1T SMC Flex Power Stack; 1000V, 180 A,

3 Phase, 50/60Hz 80258-011-51

80187-513-56 3

80190-519-01 6

80013-183-01 24

80187-595-52 1

80018-247-51 1

80157-846-51 3

1503E-PPZ1A SMC Flex Power Stack; 1000V, 360 A,

3 Phase, 50/60Hz 80258-011-52

80187-513-55 3

80190-519-01 6

80013-183-01 24

80187-595-52 1

80018-247-51 1

80157-846-51 3

1503E-PPAT SMC Flex Power Stack; 2300V, 180 A,

3 Phase, 50/60Hz 80258-011-53

80187-513-54 3

80190-519-01 6

80013-183-01 24

80187-595-52 1

80018-247-51 1

80157-846-51 3

1503E-PPAA SMC Flex Power Stack; 2300V, 360 A,

3 Phase, 50/60Hz 80258-011-54

80187-516-51 3

80190-519-01 6

80013-183-01 24

80187-595-52 1

80018-247-51 1

80157-846-51 3

1503E-PPAC SMC Flex Power Stack; 2300V, 600 A,

3 Phase, 50/60HZ 80258-011-55

80187-516-51 3

80190-519-01 6

90013-183-01 24

80187-595-52 1

80018-247-51 1

1503E-PPCT SMC Flex Power Stack; 3300V, 180 A,

3 Phase, 50/60Hz 80258-011-56

80187-514-53 3

80190-519-01 12

80013-183-01 48

80187-595-52 1

80018-247-51 1

80157-846-51 3

1503E-PPCA SMC Flex Power Stack; 3300V, 360 A,

3 Phase, 50/60Hz 80258-011-57

80187-514-54 3

80190-519-01 12

80013-183-01 48

80187-595-52 1

80018-247-51 1

80157-846-51 3

1503E-PPCC SMC Flex Power Stack; 3300 V, 600 A,

3 Phase, 50/60Hz 80258-011-58

80187-517-51 3

80190-519-01 12

80013-183-01 48

80187-595-52 1

80018-247-51 1

1503E-PPET SMC Flex Power Stack; 4160V, 360 A,

3 Phase, 50/60Hz 80258-011-59

80187-514-53 3

80190-519-01 12

80013-183-01 48

80187-595-52 1

80018-247-51 1

80157-846-51 3

Page 60: MV SMC-Flex OEM Components - Rockwell Automation

C-2 SMC Flex OEM Power Stack Kit Chart

1503E-IN00E-EN-P – June 2013

Table C.1 – SMC Flex OEM Power Stack Kit Chart (cont.)

Final Part Number Description RA Internal

Part Number Parts supplied in

the RA part number Qty

1503E-PPEA SMC Flex Power Stack; 4160V, 360 A,

3 Phase, 50/60Hz 80258-011-60

80187-514-54 3

80190-519-01 12

80013-183-01 48

80187-595-52 1

80018-247-51 1

80157-846-51 3

1503E-PPEC SMC Flex Power Stack; 4160V, 600 A,

3 Phase, 50/60Hz 80258-011-61

80187-517-51 3

80187-625-52 1

80190-519-01 12

80013-183-01 48

80187-595-52 1

80018-247-51 1

1503E-PPKT SMC Flex Power Stack; 6900V, 180 A,

3 Phase, 50/60Hz 80258-011-62

80187-515-53 3

80187-625-52 1

80190-519-01 18

80013-183-01 72

80187-595-52 1

80018-247-51 1

1503E-PPKA SMC Flex Power Stack; 6900V, 360 A,

3 Phase, 50/60Hz 80258-011-63

80187-515-54 3

80190-519-01 18

80013-183-01 72

80187-595-52 1

80018-247-51 1

1503E-PPKC SMC Flex Power Stack; 6900V, 600 A,

3 Phase, 50/60Hz 80258-011-64

80187-515-51 3

80190-519-01 18

80013-183-01 72

80187-595-52 1

80018-247-51 1

Page 61: MV SMC-Flex OEM Components - Rockwell Automation

Medium Voltage Products, 135 Dundas Street, Cambridge, ON, N1R 5X1 Canada, Tel: (1) 519.740.4100, Fax: (1) 519.623.8930, www.ab.com/mvb

Publication 1503E-IN001E-EN-P – June 2013 Supersedes Publication 1503E-IN001D-EN-P – September 2009 Copyright © 2013 Rockwell Automation, Inc. All rights reserved. Printed in Canada.