Murphy Oil Petro Chemical Lab State Fire Marshal Review

download Murphy Oil Petro Chemical Lab State Fire Marshal Review

of 13

Transcript of Murphy Oil Petro Chemical Lab State Fire Marshal Review

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    1/13

    1St. Bern:ard Fi1:e DepartmentFire Prevention Bureau

    Murphy Oil USAOwner/Contractor name1615 E Judge PerezOwner/Contractor addressChalmette, LA 70043City, State, ZipGibbs Const.Contact person504-733-4336To whom it may concern:

    Plan Review

    8201 West Judge Perez DriveChalmette, LA _70043Phone (504) 278-4477Fax (504) 278-1583

    8/19/2009

    New ConstructionP0364701Murphy LabProject Name2305 E St. Bernard HwyProject LocationChalmette, LAProject CityIndustrial

    ._ ..-.._Ihis is to advise you that we have reviewed the"dlawillgsand/or: -specifiCations for the subject proposed constructionand--.have determined that they appear to satisfactorily comply with the adopted laws, codes, rules and regulations of the S1.Bernard FirEDepartment subject to the following requirements marked below:1.) Installation of U.L. rated electrically wired smoke detector.2.) Provide a minimum of one 10lb ABC rated fire extinguisher for every 2500 sq. ft. of area.3.) Certification/Recertification of the sprinkler system. This shall be provided by a registered certification company tothe Fire Departm ent in written form.

    IYYl 4.) Certif ication/Recertification of the smoke/heat detection system. This shall be provided by a registered certificationcompany to the Fire Department in written form. .5.) Certification/Recertification of the suppression/hood system. This shall be provided by a registered certificationD company to the Fire Department in written form.D 6.) Const.ruct and ihstaTlJ

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    2/13

    PERMIT APPLICATIONIIBUilDING PERMIT o MOBILE HOME WITH PERMANENT FOUNDATIONCERTIFICATE OF OCCUPANCYibbs Construction LLC Date: 7-29-20092305 St. Bernard Highway, Chalmette, LA 70043Lot: Z-1-A and Z-1-B James Place! M-1 and M-2 Myrtle Grove

    "",", Phone (504) 2714141Contractor: Gibbs Construction LLC Phone: (504) 733-4336736 Citrus Boulevard, Harahan, LA 70123fmw~.1ij DADDITIONEXISTING STRUCTURE

    e and/or lot wil l be:_ ..--, - -, oNeighborhood Commercial

    ~eneral CommercialLight IndustrialHeavy IndustrialLegal' non-conforming useI!.I " \J~\L Height: 30'-0"',' I,. ,,.._- DSUBSURFACE PILINGFOOTING.SCONCRETE SLAB,*:p&Ni IltflLiNG (WO()D) PIER-.. orSEPTIC/MECHANICAL

    ~~\sq\(}) 0J (I)

    Date

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    3/13

    H "BUTCH" BROWNINGFIRE MARSHAL

    NEW CONSTRUCTION

    "/g, '". STATE OF LOUISIANA '!jl/h.

    . C,"", Department of Public Safety and Corrections r:>. J .> . \ Baton Rouge, Louisiana 70806(J> ,.:.;. el'l! 225-925-4920"l>\~ C)A.l ,"'J / t,) /(0 !~C-)~/":~!=~:~~~:::'~>/RONNIE BABINWINK DESIGN GROUP1100 POYDRAS STSTE 1360NEW ORLEANS, LA 70163-0000

    RE: P0364701MURPHY OIL USA INC- LABORATORY BLDG2305 E ST BERNARD HWYCHALMETTE, LA 70044NFPA 101,2006INDUSTRIAL

    Dear ApplicantThis is to advise that we have reviewed the drawings and specifications for the subject proposed construction andhave determined that they appear to satisfactorily comply with the adopted laws, codes, rules and regulations of TheState Fire Marshal subject to the following requirements:1. Scope of Work: This 15000 sq. ft. facility is being reviewed as a high hazard industrial occupancy.

    The POR has indicated on the construction documents that this facility will have a sprinkler systemand a fire alarm system. Both systems are required.

    2. REVIEW FOR COMPLIANCE WITH THE REQUIREMENTS OF THE LOUISIANA STATEUNIFORM CONSTRUCTION CODE, in accordance with Act 12 of the 2005 First ExtraordinarySession of the Louisiana Legislature, IS NOT INCLUDED IN THIS REVIEW. Contact the buildingofficial of the applicable political subdivision to coordinate compliance with these requirements. LRS40: 1730.23 mandates the enforcement of building codes by municipalities and parishes in Louisiana,as described by LRS 40: 1730.28.Note: In accordance with LRS 40: 1730.39.A, this office may establish contract agreements withmunicipalities and parishes in order to provide code enforcement on their behalf, as provided in LRS40: 1730.24. Please visit our web site at http://www.dps.state.la.us/sfm/index.htm for a current list ofjurisdictions requesting plan review by this office, a fee schedule, and a checklist of informationrequired for review.

    3. This exception is intended to apply to the storage and industrial portions of the building only.After consultation with the Office of Rehabilitation Services, it has been determined that this office

    will not req uire the storage/industrial area(s) and associated toileUbath portions of this facility tocomply with any of the ADA-AG or LSC requirements for individuals with disabilities, with thefollowing stipulations:

    Jul 31. 2009P0364701 - PAGE I

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    4/13

    1. No floor plan modifications are permitted. Office additions and spaces created which constitutea change in use will require the upgrading of all existing non-complying features to conform with theprovisions for new construction.2. Provide features of accessibility for the public and administrative areas.

    3. Visual alarm notification shall be provided if a fire alarm system is required by Code.4. If a complaint is received about discrimination in hiring of handicapped individuals orconcerning handicapped accessibility to any part of the facility, then this office shall reserve the rightto investigate the complaint and, if justified, shall reserve the right to require the facility or a portionthereof to be upgraded to comply with the accessibility requirements enforced by this office.

    4.

    5. Please note that this document indicates specific compliance with state regulations and does not

    rJ ep,rft\e[1Q ....w c;r~u.ljJl~t~ .. ~. . . .. V~ with federal law.: t p\!r i IVILl~i:U' .. . 7"i:)"ElDrJii~'E lMPOSED" -The Professional of Record, if applicable, otherwise theowner, shall furnish documentation addressing item(s) number 7,8,9,11,12,14,15,16 of this letter tothis office within 21 days of the date on this l~ter,or this r,eview may be rescinded and found "Not InCompliance". Construction shall NOT be authorized for alLareas which may be affected by theitem(s) listed in this paragraph. The state inspector shall verify that written documentation has beenreceived and acknowledged by the Plan Review Section of this office prior to allowing occupancy.

    NOTE: THE COMMENTS LISTED BELOW IDENTIFY APPARENT DEFICIENCIES DETECTED IN OURREVIEW OFTHE DOCUMENTS SUBMITTED. .5. LRS 37:152.A Prior to construction, all drawings and specifications shall be stamped by the

    professional of record. Refer to sheet G002.

    6. NFPA 45:6.6.3.1 Plans for laboratory emergencies shall be developed, which shall include thefollowing: See section 45:6.6.3.1(Compliance with 2-6wasn't indicated on the submitted documents.)

    7. NFPA 30:6.3.2 The number of storage cabinets located in the chemical storage area shall not exceed6. (Seven cabinets were indicated on the floor plan on sheet A201.) Provide documentation showingcompliance.

    8. NFPA 30:6.4.2.3 Exterior walls shall be constructed to provide ready access for fire-fightingoperations by means of access openings, windows, or lightweight noncombustible wall panels. Adeficiency was detected at the northeast wall of the chemical storage room. Refer to sheet A201.Provide documentation showing compliance.

    9. NFPA 30:6.4.2.4* Where Class IA liquids or unstable liquids are dispensed or stored in containerslarger than 1 L (1 gal), rooms shall be designed to direct flame, combustion gases and pressuresresulting from a deflagration away from important buildings or occupied areas through the use ofdamage-limiting construction. The damage-limiting construction design shall be in accordance withrecognized engineering standards and shall be acceptable to the authority having jurisdiction.(Compliance with this provision wasn't indicated on the submitted documents.) Providedocumentation showing compliance.

    10. NFPA 30:6.9.1 Portable fire extinguishers shall meet the following requirements:Jui31,2009

    P0364701 - PAGE 2

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    5/13

    (I) At least one portable fire extinguisher having a capability of not less than 40: B shall be locatedoutside of, but not more than 3 m (10ft) from, the door opening into an inside liquid storage area.(2) At least one portable fire extinguisher having a capability of not less than 40:B shall be locatedwithin 9 m (30 ft) of any Class I or Class II liquid storage area that is located outside of an insideliquid storage area or liquid warehouse. (What type of fire extinguishers this facility will havewasn't indicated on the submitted documents.)

    Additional fire extinguisher requirements:

    LAC 55:V:303.D Provide listed portable fire extinguishers in accordance with NFP A 10. (Refer toAppendix E for distribution information.)a) NFP A 10.3.3.4 Classifications for fires:Class A fires-fires in ordinary combustible materials, such as wood, cloth, paper, rubber and manyplastics. ..Class B fiJ:'~s-fir~sinflammable liquids, combustible liquids, petroleumgrea'~e, tars. oil~, QH-basedpaints, 'solvents, lacquers, alcohols and flammable gases.Class C fires-fires that involve energized electrical equipment.Class D fires-fires in combustible metals.Class K fires-fires in cooking appliances that involve combustible cooking media (vegetable or animaloils and fats.) (FOR USE ONLY AFTER ASSOCIATED FIRE SUPPRESSION SYSTEM HASACTIVATED AND'ELECTRICAL POWER TO THE COOKING APPLIANCES "HAS SHUNTED)b) NFPA 10:5 Travel distance to a fire extinguisher shall not exceed 75 feet for Class A, C and Dfires. Table 10:5.2.1 and 10:5.5 and 10:5.6.c) NFPA 10:5 Travel distance to a fire extinguisher shall not exceed 30 feet for Class B fires(liquids). (May be increased to 50 feet for Light (low) Hazard fires with 10-8 extinguisher, forOrdinary (moderate) Hazard fires with 20-B extinguisher, and for Extra (high) Hazard firs with 80B extinguisher.) Table 10:5.3.1.For classification of Hazards see 10: 1.4.1 (Light/Low), ]0:1 .4.2 (Ordinary/Moderate): 10:1 .4.3

    (Extra/High)d) NFPA 10:1.5.6 Fire extinguishers shall not be obstructed or obscured from view.e) NFPA 10:1.5.3 Fire extinguishers shall be conspicuously located where they will be readilyaccessible and immediately available in the event of fire. Preferably they shall be located alongnormal paths of travel, including exits from areas.f) NFPA 10: 1.5.10 Top of fire extinguisher, having a gross weight less than 40 lb, shall be not morethan 5 feet above the floor; ifgross weight 40 Ibs or greater, 3-1/2 feet above the floor.

    Jul 31,2009P036470J -PAGE3

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    6/13

    11.

    12.

    13.

    14.

    15.

    16.

    17.

    NFPA 30:6.7.1.4 Where total quantity stored does not exceed 50 percent of the maximum per pilegiven in Table 6.7.1, the distances to a property line that is or can be built upon and to streets, alleys,or public ways shall be permitted to be reduced by 50 percent but not to less than 0.9 m (3 1). (Thedistance from the outside storage area to the property line is less than the minimum allowed by6.7.1.4. The separation distance shall not be less than 25 feet. Refer to sheet CI03.) Providedocumentation showing compliance.NFPA 30:6.7.2 A maximum of 4160 L (1100 gal) of liquids in closed containers, intermediate bulkcontainers, and portable tanks shall be permitted to be stored adjacent to a building under the samemanagement provided the following conditions apply:(1) The adjacent building wall has an exterior fire resistance rating of2 hours.(2) There are no openings to areas at grade or above grade that are within 3 m (10 1) horizontallyof the storage.(3) There are no openings directly above the storage.(4) There are no openings to areas below grade within 15m (50 ft) horizontally of the storage.

    (The outside storage area doesn't comply with items 1 and 2 of section 6.7.2. The portion of theexterior wall that is directly behind the outside_stor.age area shall provide a fire resistance ratingof2hr_ Also a wing wall 5' long shall be installed on each side of the outside storage area and shallterminate at the same height of the exterior wall to which it is connected. ) This will satisfy items 1and 2 of section 6.7.2. Refer to sheets A201 and A401 for more in formation. Provide documentationshowing compliance.101:40.7.11.6 Doors serving high hazard contents ,areas with occupant loads in excess of five shall bepermitted to be provided with a latch or lock only if the latch or lock is panic hardware or fire exithardware complying with 7.2.1.7. (The type of hardware that will be used wasn't indicated on thesubmitted documents.)101:40.7.11.1 * Where the contents are classified as high hazard, exits shall be provided andarranged to allow all occupants to escape from the building or structure or from the hazardous areathereof to the outside or to a place of safety with a travel distance of not more than 23 m (75 ft),measured as required in 7.6.1, unless otherwise provided in 7.11.2. (Lab area 117 doesn't complywith this provision.) Provide documentation showing compliance. Refer to sheet E201.NFPA 50A: 3-2.2 The minimum distance in feet from a hydrogen system of indicated capacitylocated either outdoors, in separate buildings, or in special rooms to any specified outdoor exposureshall be in accordance with Table 3-2.2. The distances in numbers 1,3 through 10, and 14 inclusive inTable 3-2.2 shall not apply where protective structures having a minimum fire resistance rating of 2hours are located between the system and the exposure. (The hydrogen system shall be located aminimum of 25' from the exterior of the building.) Refer to sheet A20l.NFPA 50A:4-1.t Where protective walls or roofs are provided, they shall be constructed ofnoncom bustible or limited-combustible materials. (The exterior wall adjacent to the hydrogensystem is constructed with at least one com bustible material.) Refer to the second exterior wall

    ~ section located on sheet A403. Provide documentation showing compliance.LRS 40: 1731 (Effective 8/15/95) Provide handicapped accessibility in accordance with ADA-AG(Accessibility Guidelines - September 1994). This does not include a review for compliance with theFederal Americans with Disabilities (Civil Rights) Act of 1990. Compliance with state regulationsand requirements does not guarantee compliance with federal law."PARTICULAR APPARENT DEFICIENCIES" and paragraph references are noted as follo)"s:a) 4.9.4(2) Handrails at stairs shall extend at least 12" beyond the top riser and at least 12" plus thewidth of one tread beyond the bottom riser (See Figure 19). Refer to sheet A20I and A505; see stairnearest to office 116.

    Ju131.2009P036470 I - PAGE 4

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    7/13

    b) 4.22.5 Provide at least one accessible urinal with an elongated rim at 17" maximum above thefloor. A deficiency was detected in the Men's restroom 114, refer to sheet 501.c) 4.23 Bathrooms, bathing facilities, and shower rooms shall comply with this section. (The seat andcontrols located in shower 113 don't comply with 4.23. reference fig. 57 of adaag. Refer also to sheetA501@ elevation 20.)

    NOTE: THE FOLLOWING COMMENTS IDENTIFY ISSUES FOR INFORMATIONAL AND CAUTIONARYPURPOSES OR ISSUES THAT COULD NOT BE VERIFIED IN THE SUBMITTED DOCUMENTS.

    18. LRS 40:1730.45 and LAC 55:Y:2601 The documentation provided for the subject facility appears tocomply with The Commercial Building Energy Conservation Code based on ANSI/ASHRAE/IESNA90.1- 2004, or the International Energy Conservation Code, 2006 edition, as applicable.

    19. NFPA 45:5.1.6 All floor openings shallbe sealed or curbed to prevent liq uid leakage to lower floors.20. NFPA 45:5.L9*"Dpenings in fire-rated floor/ceiling and wall assemblies foraire.:-handJing dudworkorair

    movement shall be protected in accordance with NFPA 90A, Standard for the Installation ofAir-Conditioning and Ventilating Systems.

    21. NFPA 45:5.6.1 Electrical receptacles, switches, and controls shall be located so as not to be subject toliquid spills.

    22. NFPA 45:6.1.1 All laboratory units shall be provided with fire protection appropriate to the fifehazard,as follows:(1) Portable fire extinguishers (see Section 6.4)(2) Fire alarm systems (see Section 6.5)(3) Evacuation and emergency plans (see 6.6.3)

    23. NFPA 45:4.3.1 * A laboratory work area shall be considered to contain an explosion hazard if anexplosion of quantities or concentrations of materials, including but not limited to those listedin 4.3.1(1) through 4.3.1(6), could result in serious or fatal injuries to personnel within thatlaboratory work area. (See Annex C.)(1) Storage of materials with a instability hazard rating of 4 (see 8.2.5)Copyright NFP A(2) Use or formation of materials with a instability hazard rating of 4 (see 8.2.5)(3)* Presence of highly exothermic reactions such as polymerizations, oxidations, nitrations,peroxidations, hydrogenations, or organo-metallic reactions(4) Use or formation of materials whose chemical structures indicate a potential hazard, butwhose properties have not been established, such as triple bonds, epoxy radicals, nitroand nitroso compounds, and peroxides(5) Presence of high-pressure reactions (see Figure C.4.5)(6) Other explosion hazards as determined by a qualified person

    (TAKE EXTREME CAUTION FOR ITEM #2.)24. NFPA 45:5.1.4

    systems inTable 5.1.1 shall pertain to laboratory units protected by automatic sprinkler

    Jul 31, 2009P0364701 - PAGE 5

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    8/13

    accordance with NFPA 13, Standard for the Installation of Sprinkler Systems. Where water willcreate a serious fire or personnel hazard, a suitable non water automatic extinguishing systemshall be permitted to be an acceptable substitute for sprinklers.

    25. NFPA 45:6 Requires that this facility be equipped with an automatic sprinkler system and acomplete fire alarm system.

    26. 101:40:3.2 Provide sprinkler system "supervision" in accordance with NFPA 101:9.7.2.27. NFPA 45:6.2.3* The discharge of an automatic fire extinguishing system shall activate an

    audible fire alarm system on the premises.28. NFPA ~5:

    6.5.3 The fire alarm system, where provided, shall be designed so that all personnelendangered by the fire condition or a contingent condition shall be alerted.6.5.4 The fire alarm system shall alert local emergency responders or the public firedepartment.

    ,29. , NFPA 45:8.5.1 * Ducts from chemical fume hoods and from lo,calexhaustsystems shall be constructedentirely of noncombustible materials. Refer to exceptions ..

    30. NFPA 30:6.4.2.7 Mechanical ventilation shall be provided in accordance with this section.31. (Shall comply with the following:)

    NFPA 30:6.8.2* Automatic Sprinkler and Foam-Water Fire Protection Systems. Where automaticsprinklers or low-expansion foam-water sprinkler systems are used, the protection criteria of Table6.8.2(a) through Table 6.8.2(k) shall be followed for the applicable liquid class, container type, andstorage arrangement. Figure 6.8.2(a), Figure 6.8.2(b), and Figure 6.8.2(c) shall be used to specifyprotection criteria for liquid classes, container types, and storage arrangements not specificallycovered in Table 6.8.2(a) through Table 6.8.2(k). All automatic sprinkler and foam-water fireprotection systems shall be wet pipe, deluge, or preaction systems. If preaction systems are used, theyshall be designed so that water or foam solution will immediately discharge from the sprinkler uponsprinkler actuation. Foam-water sprinkler systems that meet the design criteria specified in the watersprinkler tables in this section shall be acceptable.

    32. (This facility shall comply with the following:)NFPA 30:6.4.2.6 In inside storage rooms, electrical wiring and utilization equipment for Class Iliquid storage shall be Class I, Division 2, and electrical wiring and utilization equipment in insidestorage rooms used for the storage of Class II and Class III liquids shall be suitable for generalpurpose.

    33. NFPA 30:6.8.4 Water Supply. Water supplies for automatic sprinklers, other water-based protectionsystems, hose streams, and hydrants shall be capable of supplying the anticipated water flow demandfor a minimum of 2 hours.

    34. NFPA 30:6.10 Precautions shall be taken to prevent the ignition of flammable vapors from sourcesof ignition. Refer to 6.10 for more information.

    35. Notes:Key NFP A standards used for this review:NFPA 452004 editionNFPA 302003 edition

    Jul 3 L 2009P0364701-PAGE6

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    9/13

    36. NFPA 45:8.2.2* Laboratory units and laboratory hoods in which chemicals are present shall becontinuously ventilated under normal operating conditions. The ventilation system shall comply withall applicable sections of NFPA 45:8.

    37. NFPA 45: 11.1.5.2.2 Where the source cylinder is outside of the laboratory, a station regulator andgaugeshall be installed at the point of use. to show outlet pressure.

    38. NFPA 45: 11.2.3* Manual shutoff valves shall be provided near each point of use.39. 101 :7.2.1.5.9 Doors shall be capable of being opened with ONLY one releasing operation. A two

    step release, such as a knob and an independent slide bolt, or an additional exit request button, isNOT acceptable.40. 101 :7.2.1.5 Locks on doors in means of egress shall not require the use of a key, special device or

    special knowledge to open in the direction of egress.Submit a "REQUEST FOR EXEMPTION" for special locking arrangements in accordance withInterpretive Mew.orandum 20G6-03 available on our website at http://www.dpsJouisiana.govLsfm/under the PLAN-REVIEW / FORMS section. Also see Interpretive Memorandum 2006-04 forclarification regarding "magnetic lock releasing devices".NOTE: The "Life Safety and Property Protection Licensing Law" (LRS 40:1664 et seq.) requireslocksmiths to be licensed. Contact the licensing section of this office at 225.925.7047 for guidance andassistance.

    41. 101 :40.3.3 Interior walls and ceilings shall have a flame spread of 0-200 and a smoke developmentrating of 0-450.42. BUILDING SERVICES

    a) 101:40.5.1 Utilities shall comply with the provisions of Section 9.1.b) Compliance with the 2005 NFPA 70, National Electrical Code (NEC), is mandated by RS40:1730.28.A(7). Contact the local Building Official of the applicable local political subdivision or aLouisiana State Uniform Construction Code Council registered third-party provider to verify planreview and inspection requirements of the proposed electrical work.c) HVAC system shall be constructed in accordance with 101 :9.2.d) 101 :9.2.1 Install smoke detectors to automatically stop the fan in HVAC duct systems over 2000cfm in accordance with NFPA 90A:6.4.2(1). Where fire alarm system is required, duct detectorsshall be connected to building alarm system.e) 101 :9.1.1 Install gas piping in accordance with NFPA 54.f) 101:9.2.2 Gas-fired equipment (furnaces, space heaters, water heaters, etc.) shall be U.L. listed forits intended use and shall be installed and vented in accordance with NFP A 54. This type ofequipment shall also comply with the requirements set forth in the interpretive memorandum 2008-1.

    43. LRS 40: I731-(Effective 8/15/95) Provide handicapped accessibilityin accordance with ADA-AG(Accessibility Guidelines - September 1994). This does not include a review for compliance with theFederal Americans with Disabilities (Civil Rights) Act of 1990. Compliance with state regulationsand requirements does not guarantee compliance with federal law."CAUTIONARY/INFORMATIONAL" items and paragraph references are noted as follows:a) 4.15 Provide drinking fountain(s) in compliance with this section.b) 4.1.3(10)(a) In addition to the required accessible wheelchair drinking fountain, provide drinkingaccommodations for those who have difficulty bending and stooping.c) 4.19 Lavatories shall comply with the following:

    Jul 31, 2009P0364701 - PAGE 7

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    10/13

    1. 4.19.2 Lavatories shall be mounted with a clearance of at least 29" from the floor to the bottomof the apron. Knee and toe clearances shall comply with Fig. 31.2.4.19.4 Hot water and drain pipes shall be insulated or covered.3. 4.19.5 and 4.27.4 Faucets shall not require tight grasping, pinching, or twisting of the wrist to

    operate.4.4.19.6 Mirrors shall be mounted with the bottom edge not more than 40" from the floor.

    d) 4.1.3(16) Permanent signage shall comply with 4.30.1. Signage, where provided for permanent rooms and spaces shall provide;

    a. braille and raised lettering as per 4.30.4,b. letter/symbol to background color contrast as per 4.30.5, andc. a 60" height from floor to the centerline of the sign as per 4.30.6.

    2. Other permanent signs which provide direction to or information about functional spaces of thebuilding shall provide;

    a. letter character width to height proportion as per 4.30..2, ....b. character height proportion based 0"" height ofsign from finish floor as per 4.30.3, andc. letter/symbol to background color contrast as per 4.30.5.

    44. NFPA 50A: 6-1 * Caution.Personnel shall be cautioned that hydrogen flames are practically invisible.

    45. NFPA 55:7.1.6.9 Compressed gas containers, cyiinders, and tanks shall not beexposed to corrosive chemicals or fumes that could damage containers, cylinders, tanks, orvalve-protective caps.

    46. NFPA 55:7.3.1.6.1 Venting of gases shall be directed to an approved location.47. NOTE: Please enclose a copy of this letter with future submittals or other correspondence pertaining

    to this projecl.

    Changes to construction in the field which are not consistent with the reviewed documents are not authorized unlessreviewed by this office for compliance with Code. Modifications to reviewed plans must be submitted to this officeby the Architect/Civil Engineer for review prior to final inspection. If an Architect or Civil Engineer is not requiredby RS 37: 155, revisions shall be submitted by the Owner. Submittals shall include plans, completed application, aminimum $55.00 review fee, and a copy ofthe most current plan review letter.Compliance with code requirements for fire protection systems, such as Fire Alarm, Sprinkler and SuppressionSystems, is determined by separate shop drawing submittal and is not included in this review.This review shall in no way permit and/or authorize any omissions or deviations from the specific requirements ofthe adopted codes, rules and regulations in accordance with R.S. 40: 1574.1 (B).This review is valid for 180 days from the date of this letter. Construction permits must be issued and/orconstruction must commence within this time period.This office requires certification of the completed project in accordance with the approved documents (certificateenclosed).

    Jul 31. 2009P0364701 - PAGE 8

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    11/13

    Occupancy of the project will not be permitted until we receive the completed certificate and a satisfactoryinspection of the completed construction has been made by this office.To arrange for inspection of the project, please contact the District Office at the phone number below two (2)to three (3) weeks in advance. The plans stamped reviewed by this office must be available on job site at timeof inspection. Certificate of completion must be provided to the inspecting Deputy for final inspection.Fire Department access and water supplies within the scope of work shall be acceptable to the local firedepartment. Submit to the State Fire Marshal inspector, a review letter from the local fire department,stating that the access and water supply as proposed are acceptable. In lieu of a review letter, where the localfire department does not provide a formal review, the local fire department may indicate review of the accessand water supplies by stating such on the plans bearing the State Fire Marshal review stamp.REVIEWED BY:ANDREW ROSSPLAN REVIEW DEPUTY

    CC:Murphy Oil Usa, JneSt Bernard Parish GovernmentSt Bernard Fire Prevention*New Orleans District* 5042194600

    Ju131,2009P0364701 - PAGE 9

  • 8/14/2019 Murphy Oil Petro Chemical Lab State Fire Marshal Review

    12/13

    STATE OF LOUISIANADepartment of Public Safety and Corrections

    Office of State Fire Marshal Code Enforcement and Building Safety8181 Independence BoulevardBaton Rouge, Louisiana 70806225-925-4920H "BUTCH" BROWNING

    FIRE MARSHAL

    INFORMATION REQUESTNOT FOR PERMITTINGRONNIE BABINWINK DESIGN GROUP1100 POYDRAS ST

    ", ST,E 1360NEW ORLEANS, LA 70163-0000

    Dear Applicant:

    RE: P0364701MURPHY OIL USA INC- LABORATORYBLDG2305.E ST BERNARD HWYCHALJ:' IETT_E,LA 70044NFPA 101,2006INDUSTRIAL

    Additional information is required to perfonn a proper review. The project referenced above is being held pendingsubmission of the following information:1. RS 40:1574 and/or RS 40:1730.39.A Additional drawings and/or specifications are required:

    a) Provide the (complete) MSDS sheets for all chemicals and gases that will be stored and/or used inthis facility as we discussed per our phone conversation on 7/9/2009.b) Also state what specific chemicals and gases will be used and/or stored in each individual room asper our conversation on 7/9/2009. Also provide the amounts of each chemical that will be located ineach of these rooms. Be very specific.c) NOTE: Please enclose a copy of this letter with future submittals or other correspondencepertaining to this project.

    Due to the lack of information, the referenced project has NOT been reviewed. Please direct the requestedinformation to my attention. Processing will continue upon receipt of the infonnation requested above. Enclose acopy of this letter with future submittals and/or other correspondence pertaining to this project.This project will be returned as "NOT IN COMPLIANCE" if the requested infonnation is not received by this officewithin 21 days of the date of this letter, thereby requiring a RESUBMITT AL of the entire project along with a newcompleted appl ication and appropriate review fee.

    Ju19.2009P0364701 - PAGE 1