MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS...

48

Transcript of MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS...

Page 1: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.
Page 2: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

1

                                             

03  10‐2012  D.P. ‐ The sections 5.1, 9.3 and 22.2 have been updated, the change of the heating wire of the antifreezing  kit  is  considered  (it’s  directly  energized  and  equipped with  an  integrated thermostat).   

02  09‐2012  D.P. 

‐ In the section 8.7 we added a table of alarms, descriptions and causes. ‐  In  the  section  13.1  the  number  circuito  f  the  condensor  of  the model  16,  and  we updated the dimensions of the packing of the models 12 and 16. ‐ In the section 15 the curve is updated. ‐ The section 17 is improved with descriptions more clear and tables. ‐ Wiring diagrams are updated (wiring of the manostat).   

01  07‐2012 

00  06‐2012  D.P.  / 

Rev Date Author Descreption of updates Catalogo / Catalogue / Katalog / Catalogue 

MTE14110C5420‐03 Serie / Series / Serie / Serie / Série 

CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS 

D.P.  ‐ Refrigerant charge is changed for the models PACK DUE 12 and 16. 

Page 3: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

2

INDEX 

1 AIM AND CONTENTS OF THIS MANUAL .......................................................................5

1.1 HOW TO KEEP THIS MANUAL.................................................................................................................................................. 5 1.2 GRAPHIC SYMBOLS................................................................................................................................................................. 5

2 SAFETY LAWS ..............................................................................................................5

3 GENERAL SAFETY GUIDELINES .....................................................................................5

3.1 HEALTH AND SAFETY OF WORKERS ........................................................................................................................................ 6 3.2 PERSONAL PROTECTION EQUIPMENTS .................................................................................................................................. 6 3.3 SAFETY SYMBOLS.................................................................................................................................................................... 6 3.4 REFRIGERANT SAFETY DATA SHEET ........................................................................................................................................ 7

4 TECHNICAL CHARACTERISTICS .....................................................................................8

4.1 FRAME.................................................................................................................................................................................... 8 4.2 REFRIGERANT CIRCUIT............................................................................................................................................................ 8 4.3 COMPRESSORS ....................................................................................................................................................................... 8 4.4 AIR SIDE EXCHANGERS............................................................................................................................................................ 8 4.5 FANS ....................................................................................................................................................................................... 8 4.6 USER HEAT EXCHANGERS ....................................................................................................................................................... 8 4.7 ELECTRIC BOX ......................................................................................................................................................................... 8 4.8 MICROPROCESSORS ............................................................................................................................................................... 8 4.9 MONITORING AND PROTECTION DEVICES ............................................................................................................................. 9 4.10 HYDRAULIC CIRCUIT ............................................................................................................................................................... 9 4.11 FAN SPEED CONTROLLER........................................................................................................................................................ 9

5 AVAILABLE VERSIONS ..................................................................................................9

5.1 ACCESSORIES.......................................................................................................................................................................... 9

6 INSTALLATION .............................................................................................................9

6.1 GENERALITY............................................................................................................................................................................ 9 6.2 LIFTING AND HANDLING....................................................................................................................................................... 10 6.2.1 INDOOR UNIT ............................................................................................................................................................... 10 6.2.2 OUTDOOR UNIT............................................................................................................................................................ 10

6.3 LOCATION AND MINIMUM TECHNICAL CLEARANCES .......................................................................................................... 10 6.3.1 INDOOR UNIT ............................................................................................................................................................... 10 6.3.2 OUTDOOR UNIT............................................................................................................................................................ 10

6.4 HYDRAULIC CONNECTIONS .................................................................................................................................................. 10 6.4.1 CONNECTION DIAGRAMS............................................................................................................................................. 10 6.4.2 PLANT LAYOUT DESIGN ................................................................................................................................................ 11 6.4.3 CONNECTIONS POSITIONS ........................................................................................................................................... 12 6.4.4 DRAINAGE CONNECTION ............................................................................................................................................. 12

6.5 REFRIGERANT DIAGRAM ...................................................................................................................................................... 13 6.6 ELECTRICAL CONNECTIONS .................................................................................................................................................. 13 6.6.1 TERMINAL BLOCK CONNECTIONS ................................................................................................................................ 14

7 START UP................................................................................................................... 15

8 INDOOR UNIT CONTROL PANEL ................................................................................. 16

8.1 LED........................................................................................................................................................................................ 16 8.2 FUNCTIONS OF BUTTONS ..................................................................................................................................................... 16 8.2.1 LEVELS OF ACCESS ........................................................................................................................................................ 16

8.3 DESCRIPTION OF THE MAIN DISPLAY.................................................................................................................................... 17 8.3.1 NAVIGATION BETWEEN DISPLAYS................................................................................................................................ 17

Page 4: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

3

8.4 OPERATING MODES.............................................................................................................................................................. 17 8.4.1 OPERATION MODE SETTING......................................................................................................................................... 17

8.5 PROCEDURE.......................................................................................................................................................................... 17 8.5.1 SET‐POINT SELECTION .................................................................................................................................................. 17

8.6 DESCRPTION OF FUNCTIONS ................................................................................................................................................ 17 8.6.1 ACCESS TO THE FUNCTIONS......................................................................................................................................... 17

8.7 ALARMS................................................................................................................................................................................ 18 8.8 ADJUSTMENT OF SANITARY WATER VALVE.......................................................................................................................... 18

9 MICROPROCESSOR USER INTERFACE ......................................................................... 18

9.1 DISPLAY ................................................................................................................................................................................ 19 9.2 LED........................................................................................................................................................................................ 19 9.3 ANTIFREEZE PROTECTION RESISTANCES (IF THE KAS ACCESSORY IS PRESENT) ............................................................................. 19 9.4 ALARMS................................................................................................................................................................................ 19 9.4.1 Sensor alarms ............................................................................................................................................................... 19 9.4.2 Time out inverter.......................................................................................................................................................... 19 9.4.3 High pressure ............................................................................................................................................................... 19 9.4.4 High pressure flow switch (in series with the compressor outlet probe) .................................................................... 19 9.4.5 Low pressure ................................................................................................................................................................ 19

9.5 POWER FAILURE ................................................................................................................................................................... 19 9.6 ALARMS LIST......................................................................................................................................................................... 20

10 SHUTDOWNS FOR LONG PERIODS ............................................................................. 20

11 MAINTENANCE AND PERIODIC CHECKS ..................................................................... 20

11.1 ENVIRONMENTAL PROTECTION ........................................................................................................................................... 21

12 WHEN THE UNIT GOES OUT OF SERVICE .................................................................... 21

13 TECHNICAL DATA....................................................................................................... 22

13.1 OUTDOOR UNITS .................................................................................................................................................................. 22 13.2 INDOOR UNITS...................................................................................................................................................................... 23

14 ELECTRIC DATA .......................................................................................................... 23

15 EFFECTIVE HEAD PRESSURES...................................................................................... 24

16 PERFORMANCES CURVES........................................................................................... 25

16.1 16.2 16.3 16.4

17

17.1 EVAPORATOR WATER FLOW RATE ................................................................................................................................................. 33 17.2 COLD WATER TEMPERATURE (SUMMER OPERATION) ........................................................................................................................ 33 17.3 HOT WATER TEMPERATURE (WINTER OPERATION) ........................................................................................................................... 33 17.4 AMBIENT AIR TEMPERATURE........................................................................................................................................................ 33

18 CORRECTION FACTORS .............................................................................................. 34

18.1 CORRECTION FACTORS: OPERATION WITH GLYCOL ..................................................................................................................... 34

19 DIMENSIONS ............................................................................................................. 34

19.1 INDOOR UNIT ....................................................................................................................................................................... 34 19.2 OUTDOOR UNIT.................................................................................................................................................................... 35

OPERATION LIMITS.................................................................................................... 33

MOD. PACK DUE 9 ................................................................................................................................................................. 27 MOD. PACK DUE 12 ............................................................................................................................................................... 29 MOD. PACK DUE 16 ............................................................................................................................................................... 31

MOD. PACK DUE 7 ................................................................................................................................................................. 25

Page 5: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

4

20 ACCESS PROCEDURE TO INTERNAL PARTS ................................................................. 35

20.1 INDOOR UNIT ....................................................................................................................................................................... 35 20.2 OUTDOOR UNIT.................................................................................................................................................................... 35

21 COMPONENTS OF INDOOR AND OUTDOOR UNITS .................................................... 36

21.1 INDOOR UNIT ....................................................................................................................................................................... 36 21.2 OUTDOOR UNIT.................................................................................................................................................................... 36

22 WIRING DIAGRAMS ................................................................................................... 37

22.1 22.2 22.2.1 22.2.2 22.2.3

23 SOLAR MODULE (OPTIONAL ACCESSORY) .................................................................. 41

23.1 23.2 WIRING DIAGRAM................................................................................................................................................................ 42

 

ASSEMBLY............................................................................................................................................................................. 41

OUTDOOR UNITS .................................................................................................................................................................. 38

Wiring diagram of PACK DUE 12 .................................................................................................................................. 39

INDOOR UNITS...................................................................................................................................................................... 37

Wiring diagram of PACK DUE 9 .................................................................................................................................... 38

Wiring diagram of PACK DUE 16 .................................................................................................................................. 40

Page 6: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

5

the operator thus meeting the requirements listed in the 2006/42/CE Equipment Directive and following amendments. 

1 AIM AND CONTENTS OF THIS MANUAL 

addressed  to machine operators and  it enables  them  to use  the equipment efficiently, even  if  they do not have any previous specific knowledge of it. This manual describes the characteristics of the equipment at the time it is being put on the market; therefore, it may not capture 

ergonomics, safety and functionality of its products. 

1.1 HOW TO KEEP THIS MANUAL 

The manual has to be always kept with the unit it refers to. It has to be stored in a safe place, away from the dust and moisture. It has to be accessible to all users who shall consult it any time they are in doubt on how to operate the equipment. 

 versions of the 

reference material. The customer shall store any updated copy of the manual or parts of  it delivered by the manufacturer as an  attachment to this manual. 

and the maintenance of its own units. 

1.2 GRAPHIC SYMBOLS 

 Indicates operations that can be dangerous for people and/or disrupts the correct operation of the equipment. 

 Indicates prohibited operations. 

 Indicates important information that the operator has to follow in order to guarantee the correct operation of the equipment in complete safety. 

2 SAFETY LAWS 

in force  and with other European and national norms as required by the Council Directive (98/37 and later amendments). 

The equipments meet also the following requirements: • EN ISO 12100 Rule • EN ISO 13857 Rule • EN 378‐1, 378‐2, 378‐3 e 378‐4 Rules • EN 12735‐1 Rule • EN CEI 60204‐1 Rule • EN 1050 Rule • EN CEI 61000‐6‐1 Rule • EN CEI 61000‐6‐3 Rule • 97/23/CE, 2006/95/CE, 2004/108/CE, 2002/95/CE Community Directives 

3 GENERAL SAFETY GUIDELINES 

equipment and its controls and has to have read and understood the information listed in this manual. 

 It’s strictly forbidden to remove and/or tamper with any safety device. 

 

Any  routine or not‐routine maintenance operation  shall be  carried out when  the equipment has been  shut down, disconnected from electric and pneumatic power sources and after its pneumatic system has been discharged. 

 Do not put neither your hands nor insert screwdrivers, spanners or other tools into moving parts of the equipment. 

 

The equipment  supervisor and  the maintenance man has  to  receive  suitable  training  for  the performance of  their tasks in safety. 

 

Operators have to know how to use personal protective devices and have to know the accident‐prevention guidelines contained in national and international laws and norms. 

The  PACK DUE manual contains all the necessary information for the better use of the equipment under safety conditions for 

This manual provides basic information as for the installation, the operation and the maintenance of the  PACK DUE units. It is 

later technological  improvements  introduced by A2B ACCORRONI E.G. as part of  its constant endeavour to enhance the performance, 

A2B ACCORRONI E.G. reserves the right to modify its products and related manuals without necessarily updating previous

A2B ACCORRONI E.G. is available to give any detailed information about this manual and to give information regarding the use 

A2B ACCORRONI E.G.’s equipments and their component parts have been designed in compliance with the harmonised EC norms 

Before  beginning  to  operate  on  PACK DUE  units  every  user  has  to  be  perfectly  knowledgeable  about  the  functions  of  the 

Page 7: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

6

3.1 HEALTH AND SAFETY OF WORKERS 

The  European  Community  has  adopted  a  number  of  directives  on workplace’s  health  and  safety, which  include  89/391/CEE, 89/686/CEE, 89/655/CEE, 86/188/CEE and 77/576/CEE directives. Every employer  shall  implement  such provisions and ensure that workers respect them: 

 

Do  not  tamper with  or  replace  parts  of  the  equipment without  the  specific  consent  of  the manufacturer.  The manufacturer shall have no responsibility whatsoever in case of unauthorised operations. 

 

Using  components,  expendable materials  or  spare  parts  that  do  not  correspond  to  those  recommended  by  the manufacturer and/or listed in this manual may be dangerous for the operators and/or damage the equipment 

 

The  operator’s workplace  has  to  be  kept  clean,  tidy  and  free  from  objects  that may  prevent  free movements. Appropriate  lighting  of  the work  place  shall  be  provided  so  as  to  allow  the  operator  to  carry  out  the  required operations safely. Poor or too strong lighting can cause risks.  

 

Ensure that work places are always adequately ventilated and that aspirators are working, in good condition and in compliance with the requirements of the laws in force. 

3.2 PERSONAL PROTECTION EQUIPMENTS 

 

Protective  clothing: Maintenance men and operators has  to wear protective  clothing  that  complies with  the basic safety requirements currently in force. In case of slippery floors, users have to wear safety shoes with non‐slip soles. 

 Gloves: During maintenance or cleaning operation protection gloves have to be used 

   

Mask  and  goggles:  Respiratory  protection  (mask)  and  eye  protection  (goggles)  should  be  used  during cleaning and maintenance operations. 

3.3 SAFETY SYMBOLS 

The equipment features the following safety signs, which has to be complied with: 

 General hazard 

 Electric shock hazard 

 

When operating and maintaining the PACK DUE units, use the following personal protective equipments. 

Page 8: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

7

3.4 REFRIGERANT SAFETY DATA SHEET 

Name:  R410A (50% Difluoromethane (R32); 50% Pentafluoroethane (R125). 

RISKS IN DICATIONS 

Major risks:  Asphyxia 

Specific risks:  The rapid evaporation can cause freezing. 

FIRST AID 

General informations:  Never give anything by mouth to an unconscious person. 

Inhalation:  Outdoors opens transport. 

  Use oxygen or artificial respiration if necessary. 

  Do not give adrenaline or similar drugs 

Eyes contact:  Rinse carefully with water for at least 15 minutes and consult a doctor. 

Contact with skin:  Wash immediately with plenty of water. 

  Take off immediately the contaminated clothes. 

FIRE PREVENTION 

Extinguishing Media:  Whatever. 

Specifc risks:  Increase in pressure. 

Specifics methods:   Use water spray to cool containers 

MISURE IN CASO DI FUORIUSCITA ACCIDENTALE 

Personal precautions:  Evacuate personnel to safe areas. 

  Provide adequate ventilation. 

  Use personal protective equipment. 

Environmental precautions:  Evaporate. 

Cleaning method:   Evaporate. 

MANIPOLAZIONE E STOCCAGGIO 

Manipulation   

Action/technical precautions:   Provide sufficient air exchange and/or exhaust in work rooms. 

Recommendations for safe use:  Do not breathe vapors or spray mist. 

Storage:  Close tightly and store in a cool, dry and well ventilated place. 

  Store in original container. Incompatible products: explosive, flammable materials, Organic peroxide 

EXPOSURE CONTROL / PERSONAL PROTECTION 

Control parameters:   AEL (8‐h e 12‐h TWA) = 1000 ml/m³ for each of the two components. 

Respiratory protection:  For rescue and maintenance operation in storage tanks use self‐contained respirator apparatus. 

  The vapors are heavier than air and can cause suffocation by reducing oxygen available for breathing. 

Eyes protection:   Safety glasses. 

Protection of hands:   Rubber gloves. 

Hygiene measures:  Do not smoke. 

PHYSICAL AND CHEMICAL PROPERTIES 

Colour:   Colourless. 

Odor:   Light. 

Boiling point:  ‐52.8°C at atmospheric pressure. 

Lighting point:  do not ignite. 

Relative density:  1.08 kg/l at 25°C. 

Solubility in water:  Negligible. 

STABILITY AND REACTIVITY 

Stability:   No reactivity when used with the appropriate instructions. 

Materials to avoid:   Highly oxidizing materials. Incompatible with magnesium, zinc, sodium, potassium and aluminum. 

  The incompatibility is more serious if the metal is present in powerder form or if the surfaces were, recently, unprotected. 

Decomposition products  These products are halogenated compounds, hydrogen fluoride, carbon oxides (CO, CO2), carbonyl halides. 

Risks:   

TOXICOLOGICAL INFORMATION 

Acute toxicity:  (R32) LC50/ inhalation /4 hours/on rat >760 ml/l 

  (R125) LC50/ inhalation /4 hours/on rat >3480 mg/l 

Local effects:  Concentrations substantially above the TLV may cause narcotic effects. 

  Inhalation of decomposed products of high concentrations may cause respiratory failure (pulmonary edema). 

Long term toxicity:  Did not show carcinogenic, teratogenic or mutagenic effects in animal experiments. 

ECOLOGICAL INFORMATION 

Global warming potential  1730 

GWP (R11=1):   

Potential depletion  0 

Ozone ODP (R11=1):   

Disposal considerations:  Usable with reconditioning. 

Page 9: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

8

4 TECHNICAL CHARACTERISTICS 

units are extremely versatile and can operate in heat pump mode with the ability of producing hot water at a temperature of 55°C for environmental heating and  sanitary applications. The  INVERTER  compressor with brushless DC motor  technology, matched with electronic expansion valve, pump and variable speed blower are generally used for optimizing the power consumption and efficient operation of the refrigerating components. 

4.1 FRAME 

ensure the best resistance against atmospheric agents. The frame is self‐supporting with removable panels. All screws and rivets for outdoor installations are in stainless steel. 

4.2 REFRIGERANT CIRCUIT 

The refrigerant gas used in these units is R410A. The refrigerant circuit has been manufactured by means of international primary brands components and according to the UNI EN 13134 rule concerning welding procedures. The refrigerant circuit includes: Safety device on the gas side, 4 way reverse cycle valve, electronic expansion valve,  liquid receiver, valves for maintenance and control, pressure safety device according to PED regulation (high pressure switch), pressure transducers to accurately adjust the evaporating and condensing pressures, filters for throttling valve to avoid its clogging. 

4.3 COMPRESSORS 

used with R410 refrigerant. The compressors are all supplied with crankcase heater and  thermal overload protection. They are mounted on a rubber material acting as a shock absorbers. The  compressors  are mounted  in  a  separate  chamber  in order  to be  separated  from  the  air  stream  to  reduce  the noise. The crankcase heater  is always powered when the compressor  is  in stand‐by. The  inspection  is possible through the frontal panel of the unit that allow the maintenance of the compressors even if the unit is working. 

4.4 AIR SIDE EXCHANGERS 

The air side exchangers are made up of copper pipes and aluminium fins. The diameter of the copper pipes is 3/8” (except for the 

tubes are mechanically expanded into the aluminium fins to improve the heat exchange factor. The geometry of these condensers guarantee  a  low  air  side  pressure  drop  and  then  aerofoil  blades.  They  are  statically  and  dynamically  balanced  and  supplied complete of the safety fan guard according to the EN 60335 Rule. They are mounted on the unit frame by interposition of rubber vibration dampers. The electric motors are all at 6 poles (about 800/900 rpm). The motors are directly driven with an integrated thermal overload protection. The protection class of the motors is IP 54. 

4.5 FANS 

The fans are axial type with aluminium aerofoil blades. They are statically and dynamically balanced and supplied complete of the safety fan guard according to the EN 60335 rule (safety for electrical apparatus of domestic and similar use). They are mounted on the unit  frame by  interposition of  rubber  vibration dampers. The electric motors are  all  at 6 poles  (about 800/900  rpm). The motors are directly driven with an integrated thermal overload protection. The protection class of the motors is IP 54. 

4.6 USER HEAT EXCHANGERS 

The  user  heat  exchangers  are made  up  of  AISI  316  stainless  steel  braze‐welded  plates  type.  The  use  of  these  kind  of  heat exchangers allows a massive reduction of the refrigerant charge of the unit compared to the traditional shell‐in‐tube evaporators and also a reduction of the overall dimensions of the unit. The user heat exchangers are factory insulated with flexible close cell material. Each heat exchanger is provided with a temperature sensor working as antifreeze protection. 

4.7 ELECTRIC BOX 

The  electric  box  is manufactured  according  to  current  European  Union  laws.  The  accessibility  to  the  board  is  possible  after removing the front panel of the unit. The protection degree is IP55. The outdoor unit terminal board is supplied with voltage free contacts for general alarm, outdoor temperature sensor (when expected). The indoor unit terminal board is supplied with sanitary water temperature sensor and handling of 3‐way valve. 

4.8 MICROPROCESSORS 

electronic expansion valve which  is driven by the pressure transducers signals. The microprocessor  is also capable of controlling the  following  functions: water  temperature  regulation, antifreeze protection, compressor’s  time setting, compressor automatic starting sequence, alarm reset, alarm management and operating LED. The control system together with the INVERTER technology 

The  PACK DUE water chillers and heat pumps series are designed for applications  in residential and commercial areas, These 

All PACK DUE units are made up of hot‐galvanised thick sheet metal, painted with polyurethane powder enamels at 180°C to 

The used DC inverter compressors are a rotary hermetic single‐phase type (only for the models PACK DUE 7 and PACK DUE  9) and twin rotary single‐phase (for the model PACK DUE 12), and scroll 3‐phases type (for PACK DUE 16) designed to be 

model PACK DUE 7 in which the diameter of the copper pipes is 5/16”) and the thickness of the aluminium fins is 0,1mm. The 

All PACK DUE units are standard supplied with a microprocessor adopting an overheating control  logic program through the 

Page 10: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

9

and the on board sensors continuously monitor and adapt the performance of the  inverter compressor, of the pump and of the 

conditions requested by the user. 

All  internal units are standard supplied with the  following monitoring and protection devices: return water temperature sensor installed at the return water pipe line from the plant, operating and antifreeze sensor installed at the outlet pipe of the water to the plant and on water side a water  flow switch  is  installed  to protect the evaporator. All  internal units are supplied with high pressure transducer, low pressure transducer, compressor’s inlet and outlet temperature sensors, compressors thermal protection device, fans thermal protection device, high pressure flow switch. 

 

4.10 HYDRAULIC CIRCUIT 

water utilization and directly run by the microprocessor that controls the related start up and proper running. The hydraulic circuit also includes: expansion vessel, safety valve (3 bar) and the automatic air release valve. 

4.11 FAN SPEED CONTROLLER This device is required with the unit running in cooling mode when the outside air temperature is below 20°C, thus reducing the air flow rate of the condensor and adapting the evaporating pressure in order to allow proper running of the unit. This device can also be used to reduce the noise level of the unit when the outside air temperature decreases (e.g. during night operation period). 

5 AVAILABLE VERSIONS 

pump, flow switch, automatic air release valve load/unload valve). 

5.1 ACCESSORIES 

AG – Anti‐vibration rubber pad to be installed in the chassis of the unit for possible shock absorption. KAS ‐ antifreezing kit (this accessory have to be required when the order is placed and have to be factory installed). It is made up of an auto‐heating cable thermostated at 5°C and wrapped around the base of the unit near the condensing coil. 

6 INSTALLATION 

 

WARNING: All the operation described in next chapters MUST BE DONE BY TRAINED PEOPLE ONLY. Before any operation on the unit, be sure that the electric supply is disconnected. 

6.1 GENERALITY 

When  installing  or  servicing  the  unit,  it  is  necessary  to  strictly  follow  the  rules  listed  in  this manual,  to  conform  to  all  the specifications of the labels on the unit, and to take any possible precautions. Not observing the rules reported on this manual can 

fan  (2  fans  as  for  the PACK DUE 16 models)  according  to  the  value of  cooling power  at  any working 

The PACK DUE  INVERTER system  firm  reduces  the plant’s water content  to  the minimum,  that  is  from  the usual value of cooling 12‐15 l/kW to 10 liters (as for the PACK DUE 7 and PACK DUE 9 model types) or to 16 liters (as for the model PACK DUE 12) or to 20 liters (as for the model PACK DUE 16), IN ABSOLUTE, as for the PACK DUE units. Because of the 

appliance’s reduced size, the installation space, heat loss and installation costs. 

4.9 MONITORING AND PROTECTION DEVICES 

reduced water content, the PACK DUE units can be installed in plants without water tank with advantages in terms of the 

DUE 12  and  PACK

up to a value of  10 liters (as for the models PACK DUE  7 and PACK DUE  9), or of 16 liters (as for the model 

absolute value and not to any kW of installed power. 

CAUTION: Having a fixed ∆T(°C), the INVERTER control system  is able to manage plant’s minimum water contents 

PACK DUE 12), and of 20  liters  (as  for  the model PACK DUE 16). This  value makes  reference  to  the  liters’ 

The PACK DUE chillers units are supplied with an integrated hydraulic circuit including the circulating pump, suitable for chilled 

PACK.DUE ‐ reversible heat pump with integrated hydronic system (expansion vessel, safety valve, pressure gauge, circulating 

any eventual damage has to be questioned to the carrier and recorded on the Delivery Note before signing it. A2B ACCORRONI  

severe damage. 

create dangerous situations. After receiving the unit, immediately check its integrity. The unit left the factory in perfect condition; 

E.G. to be  informed, within 8 days, of  the extent of  the damage. The  customer  should prepare a written  statement of any 

Page 11: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

10

6.2 LIFTING AND HANDLING 

6.2.1 INDOOR UNIT 

The handling must be performed by qualified personnel, properly equipped  and with  appropriate  equipments  to  the weight  of  the unit, in compliance with safety regulations. 

 

6.2.2 OUTDOOR UNIT 

When unloading and installing the unit, it is highly recommended to avoid any sudden move  in order to protect the  inner components. Units can be lifted by means of a forklift or, in alternative, of belts, being  sure  not  to  damage  the  lateral  panels  and  the  cover.  It  is important to keep the unit horizontal during these operations. 

 

6.3 LOCATION AND MINIMUM TECHNICAL CLEARANCES 

6.3.1 INDOOR UNIT 

 

  ‐ Place the unit on the wall. 

‐ Drill holes in the marked positions and insert the plugs. ‐ Hook the unit. 

Models. L1 

(mm) L2 

(mm) H1 

(mm) H2 

(mm) 300  300  1500  300 

6.3.2 OUTDOOR UNIT 

partially cover the unit) has to be avoided in order to prevent air recirculation. It is advisable to create a proper basement, with a size similar to unit foot‐print. Unit vibration level is very low: it is advisable however, to fit a rigid rubber band between basement and unit base‐frame. It is also possible to install anti‐vibration supports (springs or rubbers) to keep vibrations at a very low level. Absolute care has to be taken to ensure adequate air volume to the condenser. Re‐circulation of discharge air has to be avoided; failure to observe this point will result  in poor performance or activation of safety controls. For these reasons  it  is necessary to observe the following clearances: 

 

MOD.  A  B*  C  D  E** 1500  500  400  400  500 1500  500  400  400  500 1500  500  400  400  500 1500  500  400  400  500 

* Min.distance recommended for installation and maintenance. ** Min. distance recommended for assistance and maintenance. 

 

 

Both units must be positioned on a  leveled surface, the holders used for  installation must be able to support  its weight. 

6.4 HYDRAULIC CONNECTIONS 

6.4.1 CONNECTION DIAGRAMS The hydraulic connections have to be installed in accordance with national and local regulations; pipes can be made up of steel, galvanized steel or PVC. Pipes have to be designed depending on the nominal water flow and on the hydraulic pressure drops of 

‐ Use the provided template to mark the mounting holes. 

PACK DUE 7‐9‐12‐16 

The all PACK.DUE units are designed  for outdoor  installation: any cover over  the unit and  location near  trees  (even  if  they 

PACK DUE 7 

PACK DUE 16 

PACK DUE 9 PACK DUE 12 

Page 12: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

11

the system. All pipes have to be insulated with closed‐cell material of adequate thickness. Chillers have to be connected to piping by means of flexible joints. Piping should include: • Hole thermometers to monitor the system’s temperature. • Manual shut‐off valves to separate the chiller from the hydraulic circuit. • Y‐shaped metallic filter (to be mounted on the inlet pipe) with a mesh not larger than 1 mm. • Charging group and discharge valve, where necessary. • Anti‐vibration joints. 

T

14

12

13

4

8 9

5

12 10

10

3

7 3

61

11

9*

Connections carried out by manufacturer Connections to be carried out by the installer

System outlet

System inlet

Y

Y

1. Manometer 2. Anti‐vibration joint (recommended for indoor unit joints) 3. Stop valve 4. Air vent valve 5. Flow switch 6. Thermometer 7. Filter 8. Safety valve 9. Expansion vessel 9*    Additiona expansion vessel 10. Discharge valve 11. Load valve/reintegrate 12. Temperature sensor 13. Circulator 14. Heater 

 

Unit water  inlet pipe have to be  in correspondence with the connection  labelled: ”WATER  INLET”, otherwise the evaporator may freeze. It  is  compulsory  to  install on  the WATER  INLET  connection a metallic  filter with a mesh not  larger  than 1 mm. Should the water flow switch be altered or should the filter not be installed, the warranty will no longer be valid. The  filter  have  to  be  kept  clean,  so make  sure  it  is  clean  after  the  unit  has  been  installed,  and  then  check  it periodically. 

  

WARNING  All units are standard supplied with  the water  flow switch  (factory  installed). The water  flow switch HAS TO BE INSTALLED on  the water outlet  connection  (labelled WATER OUTLET). Should  the water  flow  switch be altered, removed, or should the water filter not be  installed on the unit, the warranty will be  invalidated. Please refer to the wiring diagram for the water flow switch electric connections. 

6.4.2 PLANT LAYOUT DESIGN 

 

1. Indoor unit 2. DC inverter moto‐condensing 

(outdoor unit) 3. Sanitary accumulator 4. Plant inertial accumulator 5. Instantaneous prepareracs 6. Solar collector 7. Radiant plant 8. Plant switching over/sanitary 9. Sanitary water inlet 10. Sanitary water outlet 11. Heater for integration 12. Solar central (optional) 

MSI

Page 13: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

12

6.4.3 CONNECTIONS POSITIONS 6.4.3.1 INDOOR UNIT

A. Sytem outlet pipe (1”M) 

B. System inlet pipe (1”M) 

C. Gas line (see Paragraph 13.2) 

D. Liquid line (see Paragraph 13.2) 

E. Power supply 

F. Condensate drain (joint Ø 16 mm) 

 

6.4.3.2 OUTDOOR UNIT

 

A. Power  supply  cover  (access  to  the  terminal 

B. Gas connections cover 

C. Gas connections 

Models  Liquid line  Gas line 

1/4 SAE  1/2 SAE 

3/8 SAE  5/8 SAE   

Units 12 and 16 

 

A. Gas connections cover 

(remove  the  front  side  cover  to  accede  to  the 

terminal) 

Models  Liquid line  Gas line 

3/8 SAE  5/8 SAE 

3/8 SAE  5/8 SAE    

6.4.4 DRAINAGE CONNECTION 6.4.4.1 INDOOR UNIT 

The indoor units are designed so that the base in which there are connections to the same act of the water tray. • Connect a pipe to the predisposed joint on the unit, cfr. Connections position. • Secure it using a hose clamp. • Route the pipe to a suitable draining place. • Maintain a sufficient slope to ensure the smooth flow of the condensate water. 

6.4.4.2 OUTDOOR UNIT 

installed onto the lower part of the unit in the special housing enabling the connection of a drainage pipe. 

B

PACK DUE 7 

block) 

PACK DUE 9 

PACK DUE 12 

B. Access  to  power  supply  and  signal    cables 

PACK DUE 16 

Units 7 and 9 

All PACK DUE units have been designed to use their own base as a drain pan; a plastic pipe fitting  is standard provided to be 

Page 14: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

13

• Locate  the hole at  the base of  the unit between  the  finned coil and fan, A. • Connect to the hole the provided fitting joint, B. • Connect a hose to the nozzle of the supplied fitting joint. • Direct the hose into thedisposal place for condensate water. • Maintain  a  sufficient  slope  to  ensure  the  smooth  flow  of condensate water. 

  

 

6.5 REFRIGERANT DIAGRAM 

SEEEV

LRIN OUT

4WV

DT

LP HP

ST

M

P

C

LS

OS

FL FL

NRV

CLS

Pr

 

C  COMPRESSOR 

CLS COMPRESSOR LIQUID SEPARATOR (only for the models i‐SHWAK/WP 05, 07 e 10) 

OS  OIL SEPARATOR (only for the models i‐SHWAK/WP 10 e 15) ST  COMPRESSOR INLET TEMPERATURE DT  COMPRESSOR OUTLET TEMPERATURE HP  HIGH PRESSURE TRANSDUCER Pr  HIGH PRESSURE FLOW SWITCH LP  LOW PRESSURE TRANSDUCER LS  LIQUID SEPARATOR (only for models i‐SHWAK/WP 10 e 15) 

4WV  VALVE FO INVERTING CYCLE LR  LIQUID RECEIVER EEV  ELECTRONIC EXPANSION VALVE NRV  NO RETURN VALVE (only for the models i‐SHWAK/WP 10 e 15) FL  FILTER M  AXIAL FAN SE  OUTDOOR AIR TEMPERATURE P  CIRCULATOR ON BOARD UNIT IN  WATER INLET TEMPERATURE 

OUT  WATER OUTLET TEMPERATURE 

 WARNING: The unit should be installed so that adequate clearance is available for maintenance and repairation. The warranty does not cover costs related to platforms or handling equipment necessary for any maintenance. 

 All maintenance and testing operations should be carried out only by QUALIFIED PERSONNEL. 

 Before any operation on the unit, make sure the power supply is disconnected. 

 

WARNING: Inside the unit, there are some moving parts. Be especially careful when working near them, even if the unit is off. The temperatures of heads and exhaust piping of the compressor are usually high. Therefore be careful when working near condensing coils. 

  The aluminum fins are very sharp and can cause serious injuries. 

 After the maintenance operations, close the panels tightly with the fastening screws. 

6.6 ELECTRICAL CONNECTIONS 

Check out that the power supply meets the unit’s electric nominal data (tension, phases, frequency) reported on the label in the unit’s  front  panel.  Power  connections  have  to  be made  in  accordance  to  the wiring  diagram  enclosed with  the  unit  and  in accordance  to  the  national  and  international  norms  in  force.  Power  cables  and  line  fuses  have  to  be  sized  according  to  the specifications listed in the wiring diagram enclosed with the unit. 

 WARNING: The supply voltage’s fluctuations can not exceed ±10% of the nominal value. Should these tolerances not be respected, please contact our technical department. 

 

WARNING: The power supply have to respect the listed limits: failing this, warranty will terminate immediately. Before any operation on the unit, be sure that the power supply is disconnected. WARNING: The water  flow switch  (the component number 5  in  the previous  image and  factory  installed) have ALWAYS  to  be  connected  following  the  indications  listed  in  the wiring  diagram. Never  bridge  the water  flow switch connections in the terminal board. Should the water flow switch connections altered or not properly made, the guarantee will be invalidated. 

 WARNING: The  indoor unit can not be  installed  in areas with  strong vibrations,  corrosive gases, and excess of dirtiness or high humidity levels. Comply with the minimum technical installation. 

A

B

Page 15: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

14

6.6.1 TERMINAL BLOCK CONNECTIONS 

 Electrical wiring have to be done only by qualified personnel. 

6.6.1.1 WIRING BETWEEN INDOOR AND OUTDOOR UNITS 

The indoor unit must be connected to the outdoor unit as shown in the below figure. 

 

L N

L N

U-N230V-1Ph-N-50Hz

PE

A

B

QF

P Q E U N

Gnd

R+R-

- +OUTDOORUNIT

INDOORUNIT

X

/ d

 

GF: General differential switch (not included)  A: RS485 connection  B: Power supply connection 

6.6.1.2 INDOOR UNIT 

TERMINALS OF THE ELECTRIC BOX 

 

Single‐phase power supply terminals (ground –phase ‐neutral) max. 4 mm for the units i‐

U‐N For the connection, please use a cable with a maximum section of 4/6mm.Follow the regulations for the section of the cable. 

 the outdoor unit 

P(‐) ‐ Q(+) ‐ E(Gnd) 

For the connection, please use a cable with a minimum section of 1mm for a length not more than 10 m. For length until 100 m a cable with section of1.5mm must be used. 

TERMINALS LOCATED ON THE BOARD A1 

A2  Solar expansion board (optional)  EXPANSION For  the  connection,  please  use  the  cable  supplied  with  the  solar expansion kit fitting. 

A3 Output 230Vac 1A MAX for resistance R2 of contactor control KM2. 

UD0 – N  For the connection, please use a cable with a minimum section of 1,5mm.

YV1  3 way valve for sanitary hot water  UD1 – N  For the connection, please use a cable with a minimum section of 1,5mm.

TH1  Ambient thermostat  ID3 – N For the connection, please use a cable with a minimum section of 1mm for a length not more than 10m. For length more than 10m a cable with section of 1,5mm must be used. 

BT3  Boiler sanitary water sensor  IA2 – G For connection, a cable with minimum section of 0,5mm must be used for  a  length  not more  than  50m.  For  lengh  until  100m,  a  cable with section of 1mm must be used. 

BT4  Outdoor air temperature sensor  IA3 – G For connection, a cable with minimum section of 0,5mm must be used for  a  length  not more  than  50m.  For  lengh  until  100m,  a  cable with section of 1 mm must be used. 

PROTECTION PARTS 

QF  General differential switch (not included)   For the differential switch capcity, please respect the regulations and the 

power supply of unit. 

PACK DUE 7‐9 and 6mm for the units i‐

Terminals RS485 to be connected with those of 

PACK DUE 12 and 16. 

Page 16: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

15

6.6.1.3 OUTDOOR UNIT 

The electrical connections have to be realized by qualified personnel. 

L2 NNO NC R+

R-

L2

NO NC R+

R-N

GND

GNDCO

CO

L1

L1

L3

L3

FUS

E

 GND:   grounding wire; N1:   power supply neutral wire; L1:   power supply live wire; L2:   If it exists, connect the live wire coming from the system L3:  If it exists, connect the live cable coming from the system NO:   generic alarm output (closed when the alarm is not activated); CO:   generic alarm output common terminal; NC:  NO terminal generic alarm output (closed when the alarm is activated); R+:   modbus + signal for connection with indoor unit; R‐:   modbus ‐ signal for connection with indoor unit;  

 

WARNING:  The  grounding  of  the  signal  cable must  not  be  connected  and must  be  protected  from  accidental contact with the sheet: cut it or isolate it with tape. 

7 START UP Before start‐up 

• Ensure the availability of diagrams and manuals of the installed appliance. • Check the availability of diagrams electrical and hydraulic diagrams of the plant where the appliance is connected. • Check if the anti‐vibration couplings exists on hydraulic pipes. • Check if the shut‐off valves of the hydraulic circuits are opened. • Check that the hydraulic circuit has been loaded into required pressure and vented from air. • Check that all the hydraulic connections are carried out correctly and that all information on the labels are  respected. • Ensure that arrangements have been provided to drain condensate. • Ensoure that power cables and all terminals anre well connected. • Check that the electrical connections have been made according to applicable regulations including grounding. • The voltage must be specified on the nameplate of the unit. • Ensure that the voltage is within the tolerance limits of (±10%). • Check that the heating elements of the compressor are powered properly. • Ensure that there are no gas leaks. • Before the start up, check that all shutting panels are positioned and fixed with proper screws. 

The crankcase heaters have to be powered at least 12 hours before start up by switching off the main switch (the heaters are automatically powered when  the main  switch  is  switched off).  The  crankcase heaters are working properly  if,  after  some minutes,  the  temperature  of  crankcase’s  compressor  is  about  10°C  ÷  15°C  higher  than ambient temperature. Never switch off the unit (for a temporary stop) by switching off the main switch: this component should be used to disconnect the unit from the power supply only for lengthy stoppages (e.g. seasonal stoppages). Besides, failing the power  supply,  the  crankcase’s  resistances  are  not  supplied  thus  resulting  in  a  possible  breakdown  of  the compressors once the unit is switched on. 

  

WARNING Do not modify the internal wiring of the unit otherwise the warranty will terminate immediately. WARNING: As for the heat pump models, the summer/winter operating mode have to be selected at the beginning of the related season. Frequent changes of this seasonal operating mode have to be avoided  in order to prevent severe damages to compressors. 

For the models PACK DUE 7 and PACK DUE 9, the terminal block is located under the plastic cover on the right side of the 

the terminal block has to be realized in accordance to the below notes. outdoor unit (for the PACK DUE 12 and PACK DUE 16 models, it is necessary to remove the protective carter). The wiring to 

Page 17: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

16

8 INDOOR UNIT CONTROL PANEL The control panel is composed of a display and buttons for programming. 

ESC

1

PRGMODEON/OFF

4 5 6 7 8

2

3

 

8.1 LED 

1  Heat pump in heating mode 2  Heat pump in cooling mode 3  Circulation pump in sanitary mode 1+3  Circulation pump in cooling mode with sanitary boiler priority 2+3  Heat pump in heating mode with sanitary boiler priority 4  Heat pump compressor is on 5  Hydraulic pump of the heat pump system 6  Electric heater of heating system in heat (winter) mode 7  Sanitary boiler electric heater 8  Hydraulic pump of solar system 

8.2 FUNCTIONS OF BUTTONS 

Esc Alarm reset Menu exit User menu scrolling 

MODE ON/OFF 

Change in heat pump mode To power on and off the heat pump 

Prg To select parameters To store parameters 

▲ Increase the set point To increase the value to be changed Select top item inside the menu 

▼ Decrease the set point Decrease the value to be changed Decrease the bottom item inside the menu 

8.2.1 LEVELS OF ACCESS It has 2 levels of consultation and programming. 

1  Without password for the user  To display the values of parameters, change set point, date and hour. 2  With password for Maintenance and Manufacturer  To display and programmino the parameters of the appliance. 

 

 Please contact our service centre for further details. 

Page 18: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

17

8.3 DESCRIPTION OF THE MAIN DISPLAY 

DISPLAY  VISUALISATION  NOTE MAIN DISPLAY 

Date and time  

Display 1 Return temperature from the heating or cooling system Set point of heating or cooling system 

 

Display 2 Temperature of the sensor of the sanitary sanitary termoaccumulatore Set‐point of sanitary sanitary termoaccumulatore 

 

Display 3  Outdoor air temperature   

Display 4 Temperature of the solar panel collector Temperature of the sanitary thermo‐accumulator 

Screenshot  available  only  in  the  presence  of solar panel 

Display 5  Power output of the solar system Screenshot  available  only  in  the  presence  of solar panel 

8.3.1 NAVIGATION BETWEEN DISPLAYS 

On the control panel 1 Press the ESC button to browse the user’s menu. 

8.4 OPERATING MODES 

MODE  DESCRIPTION OFF  The unit stay in stand‐by Only cooling  Production of chilled water for cooling Cooling and sannitary water  Production of chile water for cooling and  and sanitary hot water Only heating  Production of hot water for heating Heating and sanitary water  Production of hot water for heating and sanitary hot water Only sanitary water  Production of sanitary hot water 

8.4.1 OPERATION MODE SETTING On the control panel 1 Press the “Mode On‐Off” button to select the operating mode. 2 Will be automatically memorized. 

8.5 PROCEDURE 

8.5.1 SET‐POINT SELECTION On the control panel 1 Press the arrows to the set point value. 2 Will be automatically memorized. 

 The operation is the same also for the modification of the sanitary set‐point. 

8.6 DESCRPTION OF FUNCTIONS 

Function  DESCRIPTION 

Timer setting  Setting of the timer on and off for the heat pump according to time slots. 

Set‐point setting  Setting the set‐point of the system and  sanitary of heat pump. 

Pasword setting  Setting the pasword to access into the menu mainyener of  manufacturer. 

Programming  Setting the parameters displayed only by the user (no password) clock (hours and minutes) appears on the main page. 

8.6.1 ACCESS TO THE FUNCTIONS On the control board 1 Press the “PRG” button to enter. 2 Press the arrows buttons to select the function. 3 Press the “PRG” button to accede.  

Page 19: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

18

8.7 ALARMS 

Alarm type  Alarm description  Cause 

Water flows alarm Lack  of  water  circulation  on  the  hydraulic  side  of  the heating/cooling/sanitary boiler system. 

Hydraulic pump is off, burnt, ecc.. the pressure of the water side is zero bar. The  faucet  for  interception of  the  system  are closed.

Outdoor unit link alarm 

A  lose  or  bad  serial  connection  between  indoor  and outdoor moto‐condensing unit. 

Electrical connections reversed or interrupted 

Sensor alarm  Bad detection of the temperature sensor. Cable  of  temperature  sensor  is  interrupted. Temperature sensor error. 

Water antifreeze Temperature  of  the  water  of  cooling/heating/sanitary boiler system is below the set point. 

Hydraulic pump is off, burnt, etc... Pressure on the water side is 0 bar. Faucets for the interception of the system are closed 

8.8 ADJUSTMENT OF SANITARY WATER VALVE 

To activate the sanitary hot water you must: • connect to the terminals IA2 –G a sensor which should be installed inside the tank, • connect the 3‐way switch‐over valve to the terminals UD1‐N (with spring return) If the sanitary hot water temperature is lower than the set‐point of sanitary water (set to 48°C by default) the unit activates the 3‐way switch‐over valve  to deviate  the  flow of water  towards  the water  tank or  to a heat exchanger.  If  the set‐point of sanitary water is reached, the valve returns in rest period. Contact UD1 N‐(3‐way valve): • close: valve energized and water flow deviated to the water tank, • open: valve de‐energized and water flow deviated to the user. Commutating  from winter mode operation  to  sanitary mode operation,  the  compressor  remains on  and works under  the  set frequency. Commutating from summer mode operation, the compressor turns off for safety period. 

NOTES: Using the keyboard on the unit to turn off it does not the sanitary operation The display board on the unit shows: • In sanitary mode: the display shows the temperature measured by the sensor located in the container,    • In heating or cooling mode: the diplay shows the outlet water temperature sensor.    The defrost during heating operation is always performed on the user side, never on the sanitary water tank. 

9 MICROPROCESSOR USER INTERFACE 

  

It is used to reset the manual resetting alarms. During the parameters’ setting, this button can be used to revert BACK to the previous level. 

It allows you to view the setting menu parameters. 

UP button: In the setting mode, this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode.

DOWN button: In the setting mode, this button allows you to shift to a lower menu or to decrease the value of a parameter when you are in the edit mode.

   

Page 20: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

19

9.1 DISPLAY 

In normal view displays the alarm code  if at  least an alarm  is active. In case of multiple alarms activation,  it will display the first alarm, while the second appears when the first is reset. 

9.2 LED 

Compressor LED 

• ON if the compressor is running • OFF if the compressor is off • FLASHING if timings are in progress waiting for compressor’s start up 

Sanitary water LED 

• ON if sanitary water valve is in open position • OFF if the sanitary water valve is in closed position 

Defrosting LED 

• ON in defrost operating mode • OFF if defrosting mode is disabled or completed • FLASHING if defrosting cycle interval’s time is in progress 

Antfreeze resistance LED  • The LED is ON if the antifreeze resistance is active. 

Water pump LED  • The LED is ON if the water pump is running. 

Alarm LED  • The LED is ON if an alarm is activated. 

Heat LED  • The LED is ON if the unit is in the heating mode operation. 

Cool LED  • LED is ON if the unit is in the cooling mode operation. 

9.3 ANTIFREEZE PROTECTION RESISTANCES (if the KAS accessory is present) 

The heating cable placed on the basement of the appliance is equipped with a built‐in thermostat which activates the cable even if the unit is off (but energized) when the outside air temperature decreases below 5°C. 

9.4 ALARMS 

9.4.1 Sensor alarms The alarm will be activated in the case of a short or open circuit of any connected and enabled sensor. The alarm will be activated also when  the  temperature becomes higher  than  the  sensors’ upper  limit  (100°C) or  less  than  the lower limit (‐50°C). 9.4.2 Time out inverter 

Supposing the controller does not communicate with the driver of the compressor, the time out alarm will be activated in order to prevent a system’s control loss. 9.4.3 High pressure 

If the on board pressure transductor detects a pressure higher than 40 bar, the alarm will be activated. In this case the compressor will stop immediately. The alarm will reset when the pressure decreases under 36 bar. 9.4.4 High pressure flow switch (in series with the compressor outlet probe) 

If the pressure switch on the machine detects a pressure higher than 42 bar the alarm will be active. In this case, the compressor will be immediately stopped. The alarm resets when the pressure drops below 32 bar. 9.4.5 Low pressure 

If the on board pressure transductor detects a pressure lower than 2 bars, the alarm will be activated. In this case the compressor will stop immediately. The alarm will reset when the pressure goes over 6 bar. 

9.5 POWER FAILURE 

After power supply reset: 1. The system comes back to the previous state before the power failure. 2. If the system is defrosting, this mode will be cancelled after power supply reset. 3. All the running timings will be cleared and reset again.  

Page 21: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

20

9.6 ALARMS LIST 

Error description  Code  Compressor Pump  Resistances  Fan  

Inverter hardware malfunctioning E75 OFF   OFFCompressor’s tension too high  E76 OFF   OFFPower supply tension out of bounds  E78 OFF   OFFCompressor not power supplied  E79 OFF   OFFInverter time out malfunctioning  E80 OFF   OFFCompressor inlet sensor  E63 OFF OFF OFF  OFFCompressor outlet sensor  E64 OFF OFF OFF  OFFHigh pressure transductor  E65 OFF OFF OFF  OFFLow pressure transductor  E66 OFF OFF OFF  OFFOutdoor air sensor for climate adjust  E67 OFF OFF OFF  OFFHigh pressure  E01 OFF OFF  Low pressure  E02 OFF   OFF

10 SHUTDOWNS FOR LONG PERIODS • Turn off all the indoor terminal units of the users. • Close the water faucet. • Turn off the switch QF general differential to OFF. 

 

If the temperature drops below freezing point (0°C) there  is serious danger of frost: providing a mixture of water and glycol in the system, otherwise drain the water system and the hydraulic circuits of the heat pump. 

11 MAINTENANCE AND PERIODIC CHECKS 

 

WARNING: All the operations described in this chapter HAVE TO BE CARRIED OUT BY TRAINED STAFF ONLY. Before any operation or before entering the inner components of the unit, be sure that the power supply is disconnected. The  compressor’s  heads  and  discharge  piping  are  usually  at  high  temperature  levels.  Be  very  careful  when operating in their surroundings. Aluminium coil fins are very sharp and can cause serious wounds. Be very careful when  operating  in  their  surroundings.  After  servicing  operations,  re‐install  the  cover  panels,  and  fix  them  by means of screws. 

 The refrigerant circuits must not be filled with refrigerant gas other than that indicated on the nameplate. The use of a different refrigerant can cause severe damage to the compressor. 

 It is forbidden to use refrigerant oils other than those specified in this manual. The use of different oil can cause serious damage to the compressor. 

It is a good rule to carry out periodic checks in order to verify the proper operation of the unit. 

OPERATION 1 

month 4 

month6 

month

Filling the water circuit.  x     

Presence of bubbles in the water circuit.  x     

Check out that safety and control devices work correctly (indoor and outdoor units)  x     

Check out possible oil leakage from compressor (outdoor unit).  x     

Check out possible water leakages from the hydraulic circuit (outdoor unit).  x     

Check out the proper working of the flow switches (outdoor unit).  x     

Check out that the crankcase resistances are properly supplied and functioning (outdoor unit).  x     

Clean the metallic filters of the hydraulic circuit.  x     

Clean the finned coil by means of compressed air or water jet (outdoor unit).  x     

Check  out  that  all  the  terminals  on  the  electric  board  as well  as  on  the  terminals  of  the compressor are properly fixed. Clean from time to time the remote control switch’s sliding and fixed contacts (indoor and outdoor units). 

  x   

Tightening of water connections.    x   

Check out the tightening and the balancing of the fan blades (outdoor unit).    x   

Correct voltage.      x 

Correct absorption.      x 

Check the refrigerant charge.      x 

Page 22: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

21

Check the operating pressure, and superheat and subcooling      x 

Check of the efficiency of circulation pump.      x 

Check the expansion tank.      x 

If the unit should be out of service for a long period, discharge water from the piping and from heat  exchanger.  This  operation  is  necessary  if,  during  seasonal  stoppages,  ambient temperature is expected to go down below the freezing point of the employed fluid. 

    x 

11.1 ENVIRONMENTAL PROTECTION 

According to the norms dealing with the use of depleting stratospheric ozone substances,  it  is forbidden to release refrigerants fluids in the atmosphere. They have to be collected and delivered to the seller or to proper gathering points at the end of their operating  life. Refrigerant R410A  is mentioned among controlled  substances and  for  this  reason  it has  to be  subjected  to  the mentioned norms. A particular  care  is  recommended during  service operations  in order  to  reduce as much as possible any refrigerant loss. 

12 WHEN THE UNIT GOES OUT OF SERVICE Once  the  unit  is    arrived  at  the  end  of  its  life  cycle  and  needs  to  be  removed  or  replaced,  the  following  operations  are 

recommended. • the refrigerant has to be recovered by trained people and sent to proper collecting centre; • compressors’ lubricating oil has to be collected and sent to proper collecting centre; • the  frame and  the various components,  if not serviceable any  longer, have  to be dismantled and divided according  to  their nature, particularly copper and aluminium, which are present  in conspicuous quantity  in  the unit. These operations allow easy material recover and recycling process, thus reducing the environmental impact. 

Page 23: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

22

13  TECHNICAL DATA 13.1 OUTDOOR UNITS 

TECHNICAL DATA   Power supply    230V/1/50Hz  230V/1/50Hz  230V/1/50Hz  400V/3/50Hz Max. power input  kW  2.81  3.80  5.47  6.15 Max. starting current  A  7.9  10.0  15.6  8.7 

Electrical data 

Max. current input  A  12.6  17.1  24.5  14.6 Brand    SANYO  HITACHI  MITSUBISHI SIAM  MITSUBISHI SIAM Model    C‐6RVN93H0V  ATL165SD‐C9AU  TNB306FPGM  ANB42FBEMT 

Type   Rotary 

DC Inverter Rotary 

DC Inverter Twin Rotary DC inverter 

Scroll DC inverter 

Number    1  1  1  1 Power input in cooling mode (1)  kW  1.31  1.73  2.43  3.00 Power input in cooling mode (2)  kW  1.40  1.90  2.65  3.21 Power input in heating mode (3)  kW  1.49  2.07  3.25  3.92 Power input in heating mode (4)  kW  1.23  1.72  2.58  3.15 

Compressor 

Refrigerant oil (type, quantity)  mL  FV 50S, 350  68HES‐H, 880  FV50S, 870  MEL 56, 1700 Model    YDK53‐6Y  YDK53‐6Z  YDK100‐6A  YDK100‐6A Type    AC motor  AC motor  AC motor  AC motor Number    1  1  2  2 Rated power input  kW  0.13  0.15  0.19 (×2)  0.19 (×2) Rated running current  A  0.59  0.69  0.87 (×2)  0.87 (×2) Condensator  uF  3uF/450VAC  3uF/450VAC  3uF/450VAC  3uF/450VAC Speed  r/min  770  815  860  860 

Fan motor 

Max. air flow  m3/s  0.71  0.89  1.65  1.67 Number of rows    1.6  2  2.6  2 Tube pitch × row pitch  mm  22×19.05  25.4×22  25.4×22  25.4×22 Fin gap  mm  1.4  1.5  1.5  1.8 Fin type    Hydrophilic aluminiun  Hydrophilic aluminium  Hydrophilic aluminium  Hydrophilic aluminium 

Tube outside diameter and type  mm Ф7.94 Innergroove 

copper tube Ф9.53 Innergroove 

copper tube Ф9.53 Innergroove 

cooper tube Ф9.53 Inner groove 

copper tube 

Length × height × depth (condenser)  mm  778×660×38.1  758×813×44  887×1220×44  887×1220×44 

Condenser 

Number of circuits    2  2  8  8 Type    R410A  R410A  R410A  R410A Refrigerant charge (5)  kg  1.60  1.80  3.30  4.20 Refrigerant 

Pressure design (high/low)  MPa  4.2/2.0  4.2/2.0  4.2/2.0  4.2/2.0 Liquid side / Gas side  mm  6.4/12.7  9.5/15.9  9.5/15.9  9.5/15.9 Max. Refrigerant pipe length  m  25  25  30  30 Max. difference in level (out. unit is up)  m  12  12  20  20 

Refrigerant piping 

Max. difference in level (out. unit is down  m  9  9  12  12 Sound pressure (6)  dB(A)  38÷58  40÷59  41÷61  41÷62 

Noise Sound pressure (7)  dB(A)  46÷67  48÷68  49÷70  49÷71 Dimensions (L×A×P)  mm  842×695×324  895×862×313  940×1245×360  940×1245×360 Packing (L×A×P)  mm  965x752x399  1043×915×395  1080×1285×435  1080×1285×435 

Dimensions and weight 

Net/Gross weight  kg  59/63  73/76  106/114  115/121 

Operating conditions: (1) Cooling: Outdoor air temperature 35°C; inlet/outlet water temperature 12/7°C. (2) Cooling: Outdoor air temperature 35°C; inlet/outlet water temperature 23/18°C. (3) Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet water temperature 40/45°C. (4) Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 30/35°C. (5) Refrigerant charge valide until 5m of distance between  indoor and outdoor units. Above 5m, add 20g/m of  refrigerant  for  the model  i‐SHWAK/WP 07 and 

50g/m of refrigerant for the models i‐SHWAK/WP 09‐12‐16. (6) Sound pressure level measured at 1m from the unit, in free field, according to ISO 3746. (7) Sound pressure levels are measured in free field environment at 1m and 1.5m above the ground, according to DIN 45635. N.B. The performance data shown is indicative and could be subject to change. 

PACK DUE 7 PACK DUE 9 PACK DUE 12  PACK DUE 16

Page 24: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

23

13.2 INDOOR UNITS TECHNICAL DATA  Units Power supply    230V/1/50Hz  230V/1/50Hz  230V/1/50Hz  230V/1/50Hz Max. Power input  kW  3.13  3.13  4.13  4.13 Electrical data 

Max. input current  A  13.68  13.68  17.98  17.98 Cooling capacity (1)  kW  4.71  6.09  9.03  10.82 Input power (1)  kW  1.52  1.96  2.90  3.49 E.E.R. (1)  W/W  3.10  3.11  3.11  3.10 Cooling capacity (2)  kW  6.12  8.12  11.90  14.07 Input power (2)  kW  1.61  2.13  3.12  3.70 

Cooling 

E.E.R. (2)  W/W  3.80  3.81  3.82  3.80 Heating capacity (3)  kW  5.44  7.44  11.98  14.10 Input power (3)  kW  1.70  2.32  3.72  4.35 C.O.P. (3)  W/W  3.20  3.21  3.22  3.24 Heating capacity (4)  kW  5.90  8.01  12.58  14.95 Power consumption (4)  kW  1.44  1.95  3.05  3.64 

Heating 

C.O.P. (4)  W/W  4.10  4.11  4.12  4.10 Water flow (4)  L/s  0.28  0.38  0.60  0.71 Head pressure (4)  kPa  48  45  38  32 Max. input power of water pump  kW  0.13  0.13  0.13  0.13 Max. input current of water pump  A  0.58  0.58  0.58  0.58 Expansion vessel  L  10  10  10  10 Hydraulic connections  inch  1”M  1”M  1”M  1”M Minimum valume of water  L  10  10  16  20 

Hydraulic circuit 

Maximum volume of water  L  350  350  350  350 Liquid side connection  inch  1/4” SAE  3/8” SAE  3/8” SAE  3/8” SAE 

Refrigerant circuit Gas side connection  inch  1/2” SAE  5/8” SAE  5/8” SAE  5/8” SAE Power input  kW  3.0  3.0  4.0  4.0 

Integrative resistance Current input  A  13.10  13.10  17.40  17.40 Dimensions (L×A×P)  mm  515×816×270  515×816×270  515×816×270  515×816×270 Net weight  kg  30  32  34  34 

Dimensions and weight 

Gross weight  kg  33  35  37  37 

Operating conditions: 

(1)  Cooling:  Outdoor air temperatue 35°C; inlet/outlet temperature 12/7°C. (2) Cooling:  Outdoor air temperature 35°C; inlet/outlet temperature 23/18°C. (3) Heating:  Outdoor air temperature 7°C DB 6°C WB.; temp.acqua ing./usc. 40/45°C. (4) Heating:  Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 30/35°C.  N.B. ‐ The performance data are indicative and could be subject to change. ‐The electrical data are shown to scale the size of the circuit breakers and power cables for the indoor unit. 

14 ELECTRIC DATA Power supply of the unit  V/~/Hz  230/1/50*‐400/3/50**  Remote control circuit  V/~/Hz  12 / 1 / 50 Control board circuit  V/~/Hz  12 / 1 / 50  Fans power supply  V/~/Hz  230 / 1 / 50 

Note: Electric data may change  for updating the manual.  It  is therefore necessary to refer always to the wiring diagram of this manual supplied with the unit. 

PACK DUE 7 PACK DUE 9 PACK DUE 12  PACK DUE 16

* For all indoor units and outdoor units PACK DUE 7, PACK DUE 9, PACK DUE 12. ** For the model PACK DUE 16. 

Page 25: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

24

15 EFFECTIVE HEAD PRESSURES 

 Head pressure – water flow characteristics curve net of evaporator pressure drops. 

under the conditions specified at the top (4) of page 23.  

under the conditions specified at the top (4) of page 23.  

under the conditions specified at the top (4) of page page 23.  

under the conditions specified at the top (4) of page page 23.  The plant must be designed so as to ensure the nominal flow rate correspondingly with the working data indicated above. 

0

10

20

30

40

50

60

70

0,6 0,8 1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3

Flow rate [m3/h]

Hea

d Pressure

 [Kp

a]07 

12

09

16 

Optimum  operating  point  for  PACK DUE  7 minichillers  at  compresssor’s  limit  frequency,  at water  pump’s  high  speed 

Optimum  operating  point  for  PACK DUE  9 minichillers  at  compresssor’s  limit  frequency,  at water  pump’s  high  speed 

Optimum  operating  point  for  PACK DUE  12 minichillers  at  compresssor’s  limit  frequency,  at water  pump’s  high  speed 

Optimum  operating  point  for  PACK DUE  16 minichillers  at  compresssor’s  limit  frequency,  at water  pump’s  high  speed 

Page 26: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

25

16 PERFORMANCES CURVES The performances curves reported below are only for indications and could be subjet to modification. 

6

7

8

9

10

11

12

13

14

15

16

17

18

19

4,0 4,2 4,4 4,6 4,8 5,0 5,2 5,4 5,6 5,8 6,0 6,2 6,4 6,6 6,8

Cooling power kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C

6

7

8

9

10

11

12

13

14

15

16

17

18

19

1,3 1,4 1,5 1,6 1,7 1,8 1,9 2,0 2,1 2,2

Input power in cooling operation kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C

6

7

8

9

10

11

12

13

14

15

16

17

18

19

2,0 2,5 3,0 3,5 4,0 4,5

E.E.R. W/W

Wat

er o

utle

t tem

pera

ture

°C

air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C

16.1 Mod. PACK DUE 7 

Page 27: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

26

33

35

37

39

41

43

45

47

49

51

53

55

57

3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 7,5 8,0

Heat capacity yields kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 21°Cair temp. 14°Cair temp. 7°Cair temp. 0°Cair temp. -7°Cair temp. -10°C

33

35

37

39

41

43

45

47

49

51

53

55

57

1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2,0 2,1 2,2 2,3 2,4 2,5

Input power in heating operation kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 21°C

air temp. 14°C

air temp. 7 °C

air temp. 0 °C

air temp. -7°C

air temp. -10°C

33

35

37

39

41

43

45

47

49

51

53

55

57

1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0

Coefficient of performance C.O.P. W/W

Wat

er o

utle

t tem

pera

ture

°C

air temp. 21°Cair temp. 14°Cair temp. 7°Cair temp. 0°Cair temp. -7°Cair temp. -10°C

Page 28: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

27

6

7

8

9

10

11

12

13

14

15

16

17

18

19

5,0 5,5 6,0 6,5 7,0 7,5 8,0 8,5 9,0

Cooling power kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C

6

7

8

9

10

11

12

13

14

15

16

17

18

19

1,8 1,9 2,0 2,1 2,2 2,3 2,4 2,5 2,6 2,7

Input power in cooling operation kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C

6

7

8

9

10

11

12

13

14

15

16

17

18

19

2,2 2,4 2,6 2,8 3,0 3,2 3,4 3,6 3,8 4,0 4,2 4,4 4,6

E.E.R. W/W

Wat

er o

utle

t tem

pera

ture

°C

air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C

16.2 Mod. PACK DUE 9 

Page 29: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

28

33

35

37

39

41

43

45

47

49

51

53

55

57

1,8 1,9 2,0 2,1 2,2 2,3 2,4 2,5 2,6 2,7 2,8 2,9 3,0 3,1

Input power in heating operation kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 21°Cair temp. 14°Cair temp. 7°Cair temp. 0°Cair temp. -7°Cair temp. -10°C

33

35

37

39

41

43

45

47

49

51

53

55

57

1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0Coefficient of performance W/W

Wat

er o

utle

t tem

pera

ture

°C

air temp. 21°Cair temp. 14°Cair temp. 7°Cair temp. 0°Cair temp.-7°Cair temp. -10°C

33353739414345474951535557

4,0 5,0 6,0 7,0 8,0 9,0 10,0 11,0

Heat capacity yields kW

Wat

er o

utle

t tem

pera

ture

°C

air t emp. 21°C

air t emp. 14°C

air t emp. 7°C

air t emp. 0°C

air t emp. -7°C

air t emp. -10°C

Page 30: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

29

6

7

8

9

10

11

12

13

14

15

16

17

18

19

8,0 8,5 9,0 9,5 10,0 10,5 11,0 11,5 12,0 12,5 13,0

Cooling power kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C

6

7

8

9

10

11

12

13

14

15

16

17

18

19

2,6 2,7 2,8 2,9 3,0 3,1 3,2 3,3 3,4 3,5 3,6 3,7 3,8 3,9

Input power in cooling operation kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C

6

7

8

9

10

11

12

13

14

15

16

17

18

19

2,2 2,4 2,6 2,8 3,0 3,2 3,4 3,6 3,8 4,0 4,2 4,4 4,6

E.E.R. W/W

Wat

er o

utle

t tem

pera

ture

°C

air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C

16.3 Mod. PACK DUE 12

Page 31: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

30

33

35

37

39

41

43

45

47

49

51

53

55

57

9,0 9,5 10,0 10,5 11,0 11,5 12,0 12,5 13,0 13,5 14,0 14,5 15,0Heat capacity yields kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. < 27°C

air temp. 20°C

air temp. 13°C

air temp. 7°C

air temp. 2°C

air temp. -2°C

air temp. -7°C

air temp. -10°C

air temp. -12°C

33

35

37

39

41

43

45

47

49

51

53

55

57

2,9 3,3 3,7 4,1 4,5 4,9 5,3 5,7

Input power in heating operation kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. < 27°C

air temp. 20°C

air temp.13°C

air temp. 7°C

air temp. 2°C

air temp.-2°C

air temp. -7°C

air temp. -10°C

air temp. -12°C

33

35

37

39

41

43

45

47

49

51

53

55

57

1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5Coefficient of performance W/W

Wat

er o

utle

t tem

pera

ture

°C

air temp. < 27°C

air temp. 20°C

air temp. 13°C

air temp. 7°C

air temp. 2 °C

air temp. -2°C

air temp. -7°C

air temp. -10°C

air temp. -12°C

Page 32: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

31

6

7

8

9

10

11

12

13

14

15

16

17

18

19

8 9 10 11 12 13 14 15 16Cooling power kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C

6

7

8

9

10

11

12

13

14

15

16

17

18

19

3,1 3,3 3,5 3,7 3,9 4,1 4,3 4,5

Input power in cooling operation kW

Wat

er o

utle

t tem

pera

ture

°C

air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C

6

7

8

9

10

11

12

13

14

15

16

17

18

19

1,9 2,1 2,3 2,5 2,7 2,9 3,1 3,3 3,5 3,7 3,9 4,1 4,3 4,5 4,7

E.E.R. W/W

Wat

er o

utle

t tem

pera

ture

°C

air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C

16.4 Mod. PACK DUE 16 

Page 33: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

32

33

35

37

39

41

43

45

47

49

51

53

55

57

8,0 9,0 10,0 11,0 12,0 13,0 14,0 15,0 16,0 17,0 18,0 19,0

Heat capacity yields kW

Wat

er o

utle

t tem

pera

ture

°Cair temp.< 27°C

air temp. 20°C

air temp. 13°C

air temp. 7°C

air temp. 2°C

air temp. -2°C

air temp. -7°C

air temp. -12°C

air temp. -15°C

33

35

37

39

41

43

45

47

49

51

53

55

57

2,7 3,0 3,3 3,6 3,9 4,2 4,5 4,8 5,1 5,4 5,7 6,0 6,3

Input power in heating operation kW

Wat

er o

utle

t tem

pera

ture

°C

air temp.< 27°C

air temp. 20°C

air temp. 13°C

air temp. 7°C

air temp. 2°C

air temp. -2°C

air temp. -7°C

air temp. -12°C

air temp.-15°C

33

35

37

39

41

43

45

47

49

51

53

55

57

1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5

Coefficient of performance W/W

Wat

er o

utle

t tem

pera

ture

°C

air temp.< 27°C

air temp. 20°C

air temp. 13°C

air temp. 7°C

air temp. 2°C

air temp. -2°C

air temp. -7°C

air temp. -12°C

air temp. -15°C

Page 34: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

33

17  OPERATION LIMITS 17.1 Evaporator water flow rate

The nominal water  flow  rate  is  referred  to  a  ∆T  = 5°C, between  the evaporator’s  inlet  and outlet  temperatures.  The  allowed maximum flow rate is corresponding to ∆T = 3°C; higher values may cause too high pressure drops. The allowed minimum water flow rate  is corresponding to ∆T = 8°C.  Insufficient values may cause too  low evaporating temperatures with the  intervention of safety devices which would stop the unit and,  in some particular cases, the water can freeze  in the evaporator coil causing the refrigeration circuit to break down. We enclosed below a most accurate table showing the minimum flow rates that to ensure for the plate heat exchanger for a the proper operation of unit according  to  the model  (note:  the water  flow  switch  is used  for preventing  the  freezing  sensor  from failure  in the case of  insufficient water flow but  it does not ensure the minimum  flow rate required  in order the unit can work properly) 

Model 

Cooling capacity for reference [kW]  6,12  8,12  11,90  14,07 

Minimum water flow rate that to ensure [L/s]  0,183  0,243  0,356  0,421 As a first approch, and in the absence of other detection systems, the proper flow rate for getting the best performance from your  unit can be found at maximum speed of the circulator, using the pressure gauges for controlling the pressure difference between the return and the delivery water on the outside water connections of the unit and make sure that such value is equal or less than the static pressure indicated on the curves shown in paragraph 16 for the respectives models. 

17.2 Cold water temperature (summer operation)

The allowed minimum temperature at the evaporator’s outlet is 5°C; for more lower temperatures, the unit should undergo some necessaries structural modifications.  In  this case contact our company  for  the  feasibility study and evaluation of changes  to be made according  to your  requests. The maximum  temperature  that  can be maintained at  the outlet of  the evaporator  is 25°C. Higher temperatures (up to a maximum of 40°C) can anyway be tolerated during transitions and start‐up phases of the system. In all cases, the maximum electrical  input occurs for the heat pump operating mode at a water outlet temperature of 55°C and with outdoor temperature of ‐10°C (see the tables in paragraph 17.3). 

17.3 Hot water temperature (winter operation)

Once  the  system  is working at  the  right  temperature,  the  inlet hot water  temperature  should not  to be  lower  than 25°C;  the lowest values that are not related to transitional or start‐up stages may cause compressor’s  incorrect working operation and  its possible  related breakdown. The maximum outlet water  temperature have not  to exceed 55°C. As a  function of  the maximum input  power  and  the  consequent  performance  decrease  in  terms  of  C.O.P.  outlet  temperature  of  the water  up  to  55°C with outdoor  air  temperature  up  to  5°C  are  basically  recommended.  The  water  outlet  temperature  may  be  reduced  for  lower temperatures of the outdoor air temperature, this is according to the conditions of use, taking account of the consumption values indicated in the tables below for the maximum input power as a function of the outdoor temperature and the produced water. For higher temperatures than those pointed out, especially if have a concomitant with the reduction of the water flow rate, it may cause abnormalities to the normal operating of the unit, or the safety devices act in critical cases. 

Temperature of produced water 55°C Model 

Outdoor temp. °C  Input (kW)  Input (kW)  Input (kW)  Input (kW) + 5  2,25  2,95  4,84  5,42 ‐ 10  2,36  3,04  5,65  6,21 

 Temperature of produced water 50°C 

Model Outdoor temp. °C  Input (kW)  Input (kW)  Input (kW)  Input (kW) 

+ 5  2,01  2,68  4,36  4,96 ‐ 10  2,10  2,74  5,31  5,53 

 Temperature of produced water 45°C 

Model Outdoor temp. °C  Input (kW)  Input (kW)  Input (kW) 

+ 5  1,79  2,42  3,98  4,58 ‐ 10  1,88  2,49  4,97  5,24 

17.4 Ambient air temperature

The  units  are  designed  and manufactured  to  operate,  in  summer  operation, with  the  condensate  control, with  outdoor  air temperatures ranging between  ‐10°C and 46°C. While operating as a heat pump,  the admitted outdoor air  temperatures range from ‐15°C to 40°C as a function of the water outlet temperature as indicated in the below table. 

PACK DUE 7  PACK DUE 9  PACK DUE 12  PACK DUE 16 

PACK DUE 7  PACK DUE 9  PACK DUE 12  PACK DUE 16 

PACK DUE 7  PACK DUE 9  PACK DUE 12  PACK DUE 16 

PACK DUE 7  PACK DUE 9 Input (kW) 

PACK DUE 12  PACK DUE 16 

Page 35: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

34

     Operation limits 

Water chiller mode Ambient temperature  Minimum ‐10°C          Maximum +46°C Water outlet temperature  Minimum +5°C           Massima +25°C Heat pump mode Ambient temperature   Minimum ‐15°C          Maximum +30°C Water outelt temperature  Minimum +25°C         Maximum +55°C Heat pump mode for sanitary hot water Ambient temperature with maximum water temp. 48°C  Minimum ‐15°C          Maximum +40°C Ambient temperature with maximum water temp. 55°C  Minimum ‐15°C          Maximum +35°C Water outelt temperature  Minimum +20°C         Maximum +55°C 

18  CORRECTION FACTORS 18.1 CORRECTION FACTORS: operation with glycol 

Glycol %  Freezing point (°C)  CCF  IPCF  WFCF  PDCF 10  ‐3,2 0,985 1 1,02  1,0820  ‐7,8 0,98 0,99 1,05  1,1230  ‐14,1  0,97 0,98 1,10  1,2240  ‐22,3  0,965 0,97 1,14  1,2550  ‐33,8  0,955 0,965 1,2  1,33

CCF:  Capacity correction factor.      IPCF:  Input power correction factor. WFCF:  Water flow rate correction factor.    PDCF:  Pressure drops correction factor. 

The water  flow  rate and pressure drop  correction  factors are  to be applied directly  to  the values given  for operation without glycol.  The water  flow  rate  correction  factor  is  calculated  in  order  to  get  the  same  temperature’s  difference  that would  be obtained without glycol. The pressure drop’s correction factor takes into account the different water flow rate obtained from the application of the water flow rate correction factor. 

19 DIMENSIONS 

19.1 INDOOR UNIT 

 DIMENSIONS (mm)

MODELS A  B  C  D  E  F  G  H  I  L  M  N  O 

91  55  80  40  88  245  56  70  190  93  515  816  270 PACK DUE 7‐9‐12‐16 

Page 36: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

35

19.2 OUTDOOR UNIT 

      

DIMENSIONS (mm) MODELS 

A  B  C  D  E  F  H 

842  560  335  360  312  324  695 895  590  333  355  302  313  862 940  600  376  400  340  360  1245 

20.1 INDOOR UNIT 

 

• Remove the two screws on the bottom of the unit. • Remove the cabinet. 

20.2 OUTDOOR UNIT 

 

• Remove the connection screws connecting the top panel and the front panel. 

• Remove the top panel • Remove the screws connecting the front‐right side panel. 

• Remove the front right side panel. 

Top panel

Front –right side panel

PACK DUE 7 PACK DUE 9 

20 ACCESS PROCEDURE TO INTERNAL PARTS PACK DUE 12‐16 

PACK DUE 7‐9 

PACK DUE 12 ‐ 16 

Page 37: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

36

21 COMPONENTS OF INDOOR AND OUTDOOR UNITS 

21.1 INDOOR UNIT 

1. Electric box 2. User interface 3. Plate heat exchanger 4. Thermostat with manual reset 5. Thermostat with automatic reset 6. Safety valve 7. Flow switch 8. Expansion vessel 9. Pump 10. Heater collector 11. Manual air vent valve 

21.2 OUTDOOR UNIT 

 

1. Condensor coil assy 2. Fan motor support 3. Fan motor 4. Fan 5. Transductor 6. Expansion valve 7. Coil of the expansion valve 8. Compressor 9. 4‐way valve  

purposes. 7 and is included for illustration 

The outdoor units PACK DUE 12 

fans. 

Note: The figure refers to the 

and PACK DUE 16 have two 

outdoor unit model PACK DUE 

Page 38: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

37

22 WIRING DIAGRAMS 

22.1 INDOOR UNITS 

USERCO

NNECTIO

NS

CO

NN

ECTIO

NS

INSID

ETH

E UN

IT

EXPA

NS

ION

ON

-BO

AR

D U

NIT C

ON

NE

CTIO

NU

SE

R C

ON

NE

CTIO

NS

  A1  Electronic controller  FU2  Auxiliary fuse 

A2  Expansion for solar kit (optional)  KM1  Heater integration contactor assembly 

A3  Integration resistance control panel/Sanitary boiler anti‐legionnaires  KM2  Contactor for Integration resistance and sanitary boiler anti‐legionnaires 

A4  Outdoor mono‐condensing unit  QF  General differential switch (not included) 

BT1  Water inlet sensor for the plant  R1  Plant integration resistance 

BT2  Water outlet sensor for the plant  R2  Integration resistance and sanitary boiler anti‐legionnaires 

BT3  Sanitary water sensor for boiler  TH1  Ambient thermostat 

BT4  Outdoor air temperature sensor  THS1  Resistance R1 of safety thermostat action at 80°C reset at 70°C. 

E1  Circulating pump of the plant  THS2  Resistance R1 of manual reset safety thermostat 110°C  

F1  Water flow for the plant  THS3  Resistance R2 of safety thermostat resistance 

FU1  Integration resistance fuse for the plant  YV1  3‐way valve for sanitary hot water 

 

 

WARNING: For connection to outdoor moto‐condensing (A4) see the paragraph 6.5.1.1 The grounding of the signal cable to the moto‐condensing  (E‐GND)  should not be  connected and must be protected  from accidental  contact with  the plate:  cut  it or isolate it with special tape. The terminals to connect on A4 are: R‐ with P / R+ with Q. 

Page 39: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

38

22.2 OUTDOOR UNITS 

 

22.2.1  Wiring diagram of PACK DUE 9 

Page 40: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

39

 

22.2.2  Wiring diagram of PACK DUE 12 

Page 41: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

40

 

22.2.3  Wiring diagram of PACK DUE 16 

Page 42: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

41

23 SOLAR MODULE (OPTIONAL ACCESSORY) 

23.1 ASSEMBLY 

            

A) 

REMOVE THE FOUR SCREWS WITH A SPECIALSCREWDRIVER AND THEN REMOVE THE BOTTOMCOVER OF THE ELECTRIC BOX

B)     

FIXE THE SOLAR EXPANSION BOARD IN THE FOUR HOLES OF THEELECTRIC BOX OF THE INDOOR UNIT AS SHOWN IN THE FRAME

C) 

REMOVE THE FOUR SCREWS OF THE CONTROLPANEL WITH A SPECIAL SCREWDRIVER

D) 

REMOVE THE CONTROL PANEL TOWARDS LEFT SIDEAS SHOWN IN FIGURE TAKING CARE TO THE WIRING

CONNECT THE WIRE OF THE SOLAR EXPANSION BOOARDTO THE WHITE TERMINAL NAMED EXPANSION OF THE CONTROLBOARD AS SHOWN IN THE FIGURE

Page 43: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

 

42

23.2 WIRING DIAGRAM 

8 7 56 4 3 LN

E2

BT6BT5

FU3KA1

QF

L1 N

230V-1Ph-N-50HzU-NPE

B A S E

EXPANSION

A1 WIRING DIAGRAM

A1 Electric box electronic controllerBT5 Solar collector probeBT6 Sanitary boiler probeE2 Solar collector circulation pumpFU3 Fuse of solar collector c irculation pump

( 5x20 T 1.6A )KA1 Relay for collector circulation pumpQF General differenti al switch (not included)

FU3KA1

key

LAY OUT DESIGN

B T6 S an ita ry bo ile r p robeFor the conne ct ion , use a cab le w ith a m in im um sect ion o f 0.5 m m and a leng thno t m ore than 50 m ete rs . For lengh un til 100 m a cab le w ith sec t ion o f 1 m mm ust be used .

U ‐ NS ing le -pha se pow er supp ly te rm ina ls (g roun d - live -n e u tra l)m ax. 1 .5 m m

For the conne ct ion , use a cab le w ith a m ax im um and m in im um sect ion o f 1 .5 m mFo llow the regu la t ions fo r the sec t ion of the cab le .

E 2 S o lla r co llec to r m ic roc ircu la tion pu m p

B T5 S an ita ry co llec to r p robe

PROTECTION PARTS

Q F G ene ra l d iffe ren tia l sw itch (n o t inc luded )

For the conne ct ion , use a cab le w ith a m in im um section o f 1 .5 m m

For conne ction , a cab le w ith m in im um sect ion o f 0 .5 m m m ust be used and a

For the conne ct ion , a cab le w ith m in im um sect ion o f 0 .5 m m m ust be used.

For the brea ker s iz ing p lea se respe c t the regu la t ion s and the po w er o f un it.

leng th o f 50 m . For lengh un til 100 m , a cab le w ith sec t ion o f 1 m m m ust be used .

TERMINALS ON THESOLAR EXPANSIONBOAD A2

5 ‐ 6

A 1 C on tro lle r boa rd BASE For the conne ct ion , use the cab le supp lied w ith the so la r expan s ion k it

3 ‐ 4

7 ‐ 8

              

Page 44: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.
Page 45: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.
Page 46: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.
Page 47: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.
Page 48: MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS D.P.

Tel. 071.723991 - Fax 071.7133153 - Web Site: www.accorroni.it - E-mail: [email protected] Accorroni E.G. S.r.l. - Via d’Ancona, 37 - 60027 Osimo (An)