|RL 49| D.p. ex rel. e.p., d.p. and k.p v. school bd. of broward county
MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS...
Transcript of MTE01110C5420-03 i-SHWAK-WP 07÷16 splittato · Serie / Series / Serie / Serie / Série CHILLERS...
1
03 10‐2012 D.P. ‐ The sections 5.1, 9.3 and 22.2 have been updated, the change of the heating wire of the antifreezing kit is considered (it’s directly energized and equipped with an integrated thermostat).
02 09‐2012 D.P.
‐ In the section 8.7 we added a table of alarms, descriptions and causes. ‐ In the section 13.1 the number circuito f the condensor of the model 16, and we updated the dimensions of the packing of the models 12 and 16. ‐ In the section 15 the curve is updated. ‐ The section 17 is improved with descriptions more clear and tables. ‐ Wiring diagrams are updated (wiring of the manostat).
01 07‐2012
00 06‐2012 D.P. /
Rev Date Author Descreption of updates Catalogo / Catalogue / Katalog / Catalogue
MTE14110C5420‐03 Serie / Series / Serie / Serie / Série
CHILLERS AND INVERTER AIR/WATER HEAT PUMPS WITH AXIAL FANS AND REMOTE CONDENSING UNITS
D.P. ‐ Refrigerant charge is changed for the models PACK DUE 12 and 16.
2
INDEX
1 AIM AND CONTENTS OF THIS MANUAL .......................................................................5
1.1 HOW TO KEEP THIS MANUAL.................................................................................................................................................. 5 1.2 GRAPHIC SYMBOLS................................................................................................................................................................. 5
2 SAFETY LAWS ..............................................................................................................5
3 GENERAL SAFETY GUIDELINES .....................................................................................5
3.1 HEALTH AND SAFETY OF WORKERS ........................................................................................................................................ 6 3.2 PERSONAL PROTECTION EQUIPMENTS .................................................................................................................................. 6 3.3 SAFETY SYMBOLS.................................................................................................................................................................... 6 3.4 REFRIGERANT SAFETY DATA SHEET ........................................................................................................................................ 7
4 TECHNICAL CHARACTERISTICS .....................................................................................8
4.1 FRAME.................................................................................................................................................................................... 8 4.2 REFRIGERANT CIRCUIT............................................................................................................................................................ 8 4.3 COMPRESSORS ....................................................................................................................................................................... 8 4.4 AIR SIDE EXCHANGERS............................................................................................................................................................ 8 4.5 FANS ....................................................................................................................................................................................... 8 4.6 USER HEAT EXCHANGERS ....................................................................................................................................................... 8 4.7 ELECTRIC BOX ......................................................................................................................................................................... 8 4.8 MICROPROCESSORS ............................................................................................................................................................... 8 4.9 MONITORING AND PROTECTION DEVICES ............................................................................................................................. 9 4.10 HYDRAULIC CIRCUIT ............................................................................................................................................................... 9 4.11 FAN SPEED CONTROLLER........................................................................................................................................................ 9
5 AVAILABLE VERSIONS ..................................................................................................9
5.1 ACCESSORIES.......................................................................................................................................................................... 9
6 INSTALLATION .............................................................................................................9
6.1 GENERALITY............................................................................................................................................................................ 9 6.2 LIFTING AND HANDLING....................................................................................................................................................... 10 6.2.1 INDOOR UNIT ............................................................................................................................................................... 10 6.2.2 OUTDOOR UNIT............................................................................................................................................................ 10
6.3 LOCATION AND MINIMUM TECHNICAL CLEARANCES .......................................................................................................... 10 6.3.1 INDOOR UNIT ............................................................................................................................................................... 10 6.3.2 OUTDOOR UNIT............................................................................................................................................................ 10
6.4 HYDRAULIC CONNECTIONS .................................................................................................................................................. 10 6.4.1 CONNECTION DIAGRAMS............................................................................................................................................. 10 6.4.2 PLANT LAYOUT DESIGN ................................................................................................................................................ 11 6.4.3 CONNECTIONS POSITIONS ........................................................................................................................................... 12 6.4.4 DRAINAGE CONNECTION ............................................................................................................................................. 12
6.5 REFRIGERANT DIAGRAM ...................................................................................................................................................... 13 6.6 ELECTRICAL CONNECTIONS .................................................................................................................................................. 13 6.6.1 TERMINAL BLOCK CONNECTIONS ................................................................................................................................ 14
7 START UP................................................................................................................... 15
8 INDOOR UNIT CONTROL PANEL ................................................................................. 16
8.1 LED........................................................................................................................................................................................ 16 8.2 FUNCTIONS OF BUTTONS ..................................................................................................................................................... 16 8.2.1 LEVELS OF ACCESS ........................................................................................................................................................ 16
8.3 DESCRIPTION OF THE MAIN DISPLAY.................................................................................................................................... 17 8.3.1 NAVIGATION BETWEEN DISPLAYS................................................................................................................................ 17
3
8.4 OPERATING MODES.............................................................................................................................................................. 17 8.4.1 OPERATION MODE SETTING......................................................................................................................................... 17
8.5 PROCEDURE.......................................................................................................................................................................... 17 8.5.1 SET‐POINT SELECTION .................................................................................................................................................. 17
8.6 DESCRPTION OF FUNCTIONS ................................................................................................................................................ 17 8.6.1 ACCESS TO THE FUNCTIONS......................................................................................................................................... 17
8.7 ALARMS................................................................................................................................................................................ 18 8.8 ADJUSTMENT OF SANITARY WATER VALVE.......................................................................................................................... 18
9 MICROPROCESSOR USER INTERFACE ......................................................................... 18
9.1 DISPLAY ................................................................................................................................................................................ 19 9.2 LED........................................................................................................................................................................................ 19 9.3 ANTIFREEZE PROTECTION RESISTANCES (IF THE KAS ACCESSORY IS PRESENT) ............................................................................. 19 9.4 ALARMS................................................................................................................................................................................ 19 9.4.1 Sensor alarms ............................................................................................................................................................... 19 9.4.2 Time out inverter.......................................................................................................................................................... 19 9.4.3 High pressure ............................................................................................................................................................... 19 9.4.4 High pressure flow switch (in series with the compressor outlet probe) .................................................................... 19 9.4.5 Low pressure ................................................................................................................................................................ 19
9.5 POWER FAILURE ................................................................................................................................................................... 19 9.6 ALARMS LIST......................................................................................................................................................................... 20
10 SHUTDOWNS FOR LONG PERIODS ............................................................................. 20
11 MAINTENANCE AND PERIODIC CHECKS ..................................................................... 20
11.1 ENVIRONMENTAL PROTECTION ........................................................................................................................................... 21
12 WHEN THE UNIT GOES OUT OF SERVICE .................................................................... 21
13 TECHNICAL DATA....................................................................................................... 22
13.1 OUTDOOR UNITS .................................................................................................................................................................. 22 13.2 INDOOR UNITS...................................................................................................................................................................... 23
14 ELECTRIC DATA .......................................................................................................... 23
15 EFFECTIVE HEAD PRESSURES...................................................................................... 24
16 PERFORMANCES CURVES........................................................................................... 25
16.1 16.2 16.3 16.4
17
17.1 EVAPORATOR WATER FLOW RATE ................................................................................................................................................. 33 17.2 COLD WATER TEMPERATURE (SUMMER OPERATION) ........................................................................................................................ 33 17.3 HOT WATER TEMPERATURE (WINTER OPERATION) ........................................................................................................................... 33 17.4 AMBIENT AIR TEMPERATURE........................................................................................................................................................ 33
18 CORRECTION FACTORS .............................................................................................. 34
18.1 CORRECTION FACTORS: OPERATION WITH GLYCOL ..................................................................................................................... 34
19 DIMENSIONS ............................................................................................................. 34
19.1 INDOOR UNIT ....................................................................................................................................................................... 34 19.2 OUTDOOR UNIT.................................................................................................................................................................... 35
OPERATION LIMITS.................................................................................................... 33
MOD. PACK DUE 9 ................................................................................................................................................................. 27 MOD. PACK DUE 12 ............................................................................................................................................................... 29 MOD. PACK DUE 16 ............................................................................................................................................................... 31
MOD. PACK DUE 7 ................................................................................................................................................................. 25
4
20 ACCESS PROCEDURE TO INTERNAL PARTS ................................................................. 35
20.1 INDOOR UNIT ....................................................................................................................................................................... 35 20.2 OUTDOOR UNIT.................................................................................................................................................................... 35
21 COMPONENTS OF INDOOR AND OUTDOOR UNITS .................................................... 36
21.1 INDOOR UNIT ....................................................................................................................................................................... 36 21.2 OUTDOOR UNIT.................................................................................................................................................................... 36
22 WIRING DIAGRAMS ................................................................................................... 37
22.1 22.2 22.2.1 22.2.2 22.2.3
23 SOLAR MODULE (OPTIONAL ACCESSORY) .................................................................. 41
23.1 23.2 WIRING DIAGRAM................................................................................................................................................................ 42
ASSEMBLY............................................................................................................................................................................. 41
OUTDOOR UNITS .................................................................................................................................................................. 38
Wiring diagram of PACK DUE 12 .................................................................................................................................. 39
INDOOR UNITS...................................................................................................................................................................... 37
Wiring diagram of PACK DUE 9 .................................................................................................................................... 38
Wiring diagram of PACK DUE 16 .................................................................................................................................. 40
5
the operator thus meeting the requirements listed in the 2006/42/CE Equipment Directive and following amendments.
1 AIM AND CONTENTS OF THIS MANUAL
addressed to machine operators and it enables them to use the equipment efficiently, even if they do not have any previous specific knowledge of it. This manual describes the characteristics of the equipment at the time it is being put on the market; therefore, it may not capture
ergonomics, safety and functionality of its products.
1.1 HOW TO KEEP THIS MANUAL
The manual has to be always kept with the unit it refers to. It has to be stored in a safe place, away from the dust and moisture. It has to be accessible to all users who shall consult it any time they are in doubt on how to operate the equipment.
versions of the
reference material. The customer shall store any updated copy of the manual or parts of it delivered by the manufacturer as an attachment to this manual.
and the maintenance of its own units.
1.2 GRAPHIC SYMBOLS
Indicates operations that can be dangerous for people and/or disrupts the correct operation of the equipment.
Indicates prohibited operations.
Indicates important information that the operator has to follow in order to guarantee the correct operation of the equipment in complete safety.
2 SAFETY LAWS
in force and with other European and national norms as required by the Council Directive (98/37 and later amendments).
The equipments meet also the following requirements: • EN ISO 12100 Rule • EN ISO 13857 Rule • EN 378‐1, 378‐2, 378‐3 e 378‐4 Rules • EN 12735‐1 Rule • EN CEI 60204‐1 Rule • EN 1050 Rule • EN CEI 61000‐6‐1 Rule • EN CEI 61000‐6‐3 Rule • 97/23/CE, 2006/95/CE, 2004/108/CE, 2002/95/CE Community Directives
3 GENERAL SAFETY GUIDELINES
equipment and its controls and has to have read and understood the information listed in this manual.
It’s strictly forbidden to remove and/or tamper with any safety device.
Any routine or not‐routine maintenance operation shall be carried out when the equipment has been shut down, disconnected from electric and pneumatic power sources and after its pneumatic system has been discharged.
Do not put neither your hands nor insert screwdrivers, spanners or other tools into moving parts of the equipment.
The equipment supervisor and the maintenance man has to receive suitable training for the performance of their tasks in safety.
Operators have to know how to use personal protective devices and have to know the accident‐prevention guidelines contained in national and international laws and norms.
The PACK DUE manual contains all the necessary information for the better use of the equipment under safety conditions for
This manual provides basic information as for the installation, the operation and the maintenance of the PACK DUE units. It is
later technological improvements introduced by A2B ACCORRONI E.G. as part of its constant endeavour to enhance the performance,
A2B ACCORRONI E.G. reserves the right to modify its products and related manuals without necessarily updating previous
A2B ACCORRONI E.G. is available to give any detailed information about this manual and to give information regarding the use
A2B ACCORRONI E.G.’s equipments and their component parts have been designed in compliance with the harmonised EC norms
Before beginning to operate on PACK DUE units every user has to be perfectly knowledgeable about the functions of the
6
3.1 HEALTH AND SAFETY OF WORKERS
The European Community has adopted a number of directives on workplace’s health and safety, which include 89/391/CEE, 89/686/CEE, 89/655/CEE, 86/188/CEE and 77/576/CEE directives. Every employer shall implement such provisions and ensure that workers respect them:
Do not tamper with or replace parts of the equipment without the specific consent of the manufacturer. The manufacturer shall have no responsibility whatsoever in case of unauthorised operations.
Using components, expendable materials or spare parts that do not correspond to those recommended by the manufacturer and/or listed in this manual may be dangerous for the operators and/or damage the equipment
The operator’s workplace has to be kept clean, tidy and free from objects that may prevent free movements. Appropriate lighting of the work place shall be provided so as to allow the operator to carry out the required operations safely. Poor or too strong lighting can cause risks.
Ensure that work places are always adequately ventilated and that aspirators are working, in good condition and in compliance with the requirements of the laws in force.
3.2 PERSONAL PROTECTION EQUIPMENTS
Protective clothing: Maintenance men and operators has to wear protective clothing that complies with the basic safety requirements currently in force. In case of slippery floors, users have to wear safety shoes with non‐slip soles.
Gloves: During maintenance or cleaning operation protection gloves have to be used
Mask and goggles: Respiratory protection (mask) and eye protection (goggles) should be used during cleaning and maintenance operations.
3.3 SAFETY SYMBOLS
The equipment features the following safety signs, which has to be complied with:
General hazard
Electric shock hazard
When operating and maintaining the PACK DUE units, use the following personal protective equipments.
7
3.4 REFRIGERANT SAFETY DATA SHEET
Name: R410A (50% Difluoromethane (R32); 50% Pentafluoroethane (R125).
RISKS IN DICATIONS
Major risks: Asphyxia
Specific risks: The rapid evaporation can cause freezing.
FIRST AID
General informations: Never give anything by mouth to an unconscious person.
Inhalation: Outdoors opens transport.
Use oxygen or artificial respiration if necessary.
Do not give adrenaline or similar drugs
Eyes contact: Rinse carefully with water for at least 15 minutes and consult a doctor.
Contact with skin: Wash immediately with plenty of water.
Take off immediately the contaminated clothes.
FIRE PREVENTION
Extinguishing Media: Whatever.
Specifc risks: Increase in pressure.
Specifics methods: Use water spray to cool containers
MISURE IN CASO DI FUORIUSCITA ACCIDENTALE
Personal precautions: Evacuate personnel to safe areas.
Provide adequate ventilation.
Use personal protective equipment.
Environmental precautions: Evaporate.
Cleaning method: Evaporate.
MANIPOLAZIONE E STOCCAGGIO
Manipulation
Action/technical precautions: Provide sufficient air exchange and/or exhaust in work rooms.
Recommendations for safe use: Do not breathe vapors or spray mist.
Storage: Close tightly and store in a cool, dry and well ventilated place.
Store in original container. Incompatible products: explosive, flammable materials, Organic peroxide
EXPOSURE CONTROL / PERSONAL PROTECTION
Control parameters: AEL (8‐h e 12‐h TWA) = 1000 ml/m³ for each of the two components.
Respiratory protection: For rescue and maintenance operation in storage tanks use self‐contained respirator apparatus.
The vapors are heavier than air and can cause suffocation by reducing oxygen available for breathing.
Eyes protection: Safety glasses.
Protection of hands: Rubber gloves.
Hygiene measures: Do not smoke.
PHYSICAL AND CHEMICAL PROPERTIES
Colour: Colourless.
Odor: Light.
Boiling point: ‐52.8°C at atmospheric pressure.
Lighting point: do not ignite.
Relative density: 1.08 kg/l at 25°C.
Solubility in water: Negligible.
STABILITY AND REACTIVITY
Stability: No reactivity when used with the appropriate instructions.
Materials to avoid: Highly oxidizing materials. Incompatible with magnesium, zinc, sodium, potassium and aluminum.
The incompatibility is more serious if the metal is present in powerder form or if the surfaces were, recently, unprotected.
Decomposition products These products are halogenated compounds, hydrogen fluoride, carbon oxides (CO, CO2), carbonyl halides.
Risks:
TOXICOLOGICAL INFORMATION
Acute toxicity: (R32) LC50/ inhalation /4 hours/on rat >760 ml/l
(R125) LC50/ inhalation /4 hours/on rat >3480 mg/l
Local effects: Concentrations substantially above the TLV may cause narcotic effects.
Inhalation of decomposed products of high concentrations may cause respiratory failure (pulmonary edema).
Long term toxicity: Did not show carcinogenic, teratogenic or mutagenic effects in animal experiments.
ECOLOGICAL INFORMATION
Global warming potential 1730
GWP (R11=1):
Potential depletion 0
Ozone ODP (R11=1):
Disposal considerations: Usable with reconditioning.
8
4 TECHNICAL CHARACTERISTICS
units are extremely versatile and can operate in heat pump mode with the ability of producing hot water at a temperature of 55°C for environmental heating and sanitary applications. The INVERTER compressor with brushless DC motor technology, matched with electronic expansion valve, pump and variable speed blower are generally used for optimizing the power consumption and efficient operation of the refrigerating components.
4.1 FRAME
ensure the best resistance against atmospheric agents. The frame is self‐supporting with removable panels. All screws and rivets for outdoor installations are in stainless steel.
4.2 REFRIGERANT CIRCUIT
The refrigerant gas used in these units is R410A. The refrigerant circuit has been manufactured by means of international primary brands components and according to the UNI EN 13134 rule concerning welding procedures. The refrigerant circuit includes: Safety device on the gas side, 4 way reverse cycle valve, electronic expansion valve, liquid receiver, valves for maintenance and control, pressure safety device according to PED regulation (high pressure switch), pressure transducers to accurately adjust the evaporating and condensing pressures, filters for throttling valve to avoid its clogging.
4.3 COMPRESSORS
used with R410 refrigerant. The compressors are all supplied with crankcase heater and thermal overload protection. They are mounted on a rubber material acting as a shock absorbers. The compressors are mounted in a separate chamber in order to be separated from the air stream to reduce the noise. The crankcase heater is always powered when the compressor is in stand‐by. The inspection is possible through the frontal panel of the unit that allow the maintenance of the compressors even if the unit is working.
4.4 AIR SIDE EXCHANGERS
The air side exchangers are made up of copper pipes and aluminium fins. The diameter of the copper pipes is 3/8” (except for the
tubes are mechanically expanded into the aluminium fins to improve the heat exchange factor. The geometry of these condensers guarantee a low air side pressure drop and then aerofoil blades. They are statically and dynamically balanced and supplied complete of the safety fan guard according to the EN 60335 Rule. They are mounted on the unit frame by interposition of rubber vibration dampers. The electric motors are all at 6 poles (about 800/900 rpm). The motors are directly driven with an integrated thermal overload protection. The protection class of the motors is IP 54.
4.5 FANS
The fans are axial type with aluminium aerofoil blades. They are statically and dynamically balanced and supplied complete of the safety fan guard according to the EN 60335 rule (safety for electrical apparatus of domestic and similar use). They are mounted on the unit frame by interposition of rubber vibration dampers. The electric motors are all at 6 poles (about 800/900 rpm). The motors are directly driven with an integrated thermal overload protection. The protection class of the motors is IP 54.
4.6 USER HEAT EXCHANGERS
The user heat exchangers are made up of AISI 316 stainless steel braze‐welded plates type. The use of these kind of heat exchangers allows a massive reduction of the refrigerant charge of the unit compared to the traditional shell‐in‐tube evaporators and also a reduction of the overall dimensions of the unit. The user heat exchangers are factory insulated with flexible close cell material. Each heat exchanger is provided with a temperature sensor working as antifreeze protection.
4.7 ELECTRIC BOX
The electric box is manufactured according to current European Union laws. The accessibility to the board is possible after removing the front panel of the unit. The protection degree is IP55. The outdoor unit terminal board is supplied with voltage free contacts for general alarm, outdoor temperature sensor (when expected). The indoor unit terminal board is supplied with sanitary water temperature sensor and handling of 3‐way valve.
4.8 MICROPROCESSORS
electronic expansion valve which is driven by the pressure transducers signals. The microprocessor is also capable of controlling the following functions: water temperature regulation, antifreeze protection, compressor’s time setting, compressor automatic starting sequence, alarm reset, alarm management and operating LED. The control system together with the INVERTER technology
The PACK DUE water chillers and heat pumps series are designed for applications in residential and commercial areas, These
All PACK DUE units are made up of hot‐galvanised thick sheet metal, painted with polyurethane powder enamels at 180°C to
The used DC inverter compressors are a rotary hermetic single‐phase type (only for the models PACK DUE 7 and PACK DUE 9) and twin rotary single‐phase (for the model PACK DUE 12), and scroll 3‐phases type (for PACK DUE 16) designed to be
model PACK DUE 7 in which the diameter of the copper pipes is 5/16”) and the thickness of the aluminium fins is 0,1mm. The
All PACK DUE units are standard supplied with a microprocessor adopting an overheating control logic program through the
9
and the on board sensors continuously monitor and adapt the performance of the inverter compressor, of the pump and of the
conditions requested by the user.
All internal units are standard supplied with the following monitoring and protection devices: return water temperature sensor installed at the return water pipe line from the plant, operating and antifreeze sensor installed at the outlet pipe of the water to the plant and on water side a water flow switch is installed to protect the evaporator. All internal units are supplied with high pressure transducer, low pressure transducer, compressor’s inlet and outlet temperature sensors, compressors thermal protection device, fans thermal protection device, high pressure flow switch.
4.10 HYDRAULIC CIRCUIT
water utilization and directly run by the microprocessor that controls the related start up and proper running. The hydraulic circuit also includes: expansion vessel, safety valve (3 bar) and the automatic air release valve.
4.11 FAN SPEED CONTROLLER This device is required with the unit running in cooling mode when the outside air temperature is below 20°C, thus reducing the air flow rate of the condensor and adapting the evaporating pressure in order to allow proper running of the unit. This device can also be used to reduce the noise level of the unit when the outside air temperature decreases (e.g. during night operation period).
5 AVAILABLE VERSIONS
pump, flow switch, automatic air release valve load/unload valve).
5.1 ACCESSORIES
AG – Anti‐vibration rubber pad to be installed in the chassis of the unit for possible shock absorption. KAS ‐ antifreezing kit (this accessory have to be required when the order is placed and have to be factory installed). It is made up of an auto‐heating cable thermostated at 5°C and wrapped around the base of the unit near the condensing coil.
6 INSTALLATION
WARNING: All the operation described in next chapters MUST BE DONE BY TRAINED PEOPLE ONLY. Before any operation on the unit, be sure that the electric supply is disconnected.
6.1 GENERALITY
When installing or servicing the unit, it is necessary to strictly follow the rules listed in this manual, to conform to all the specifications of the labels on the unit, and to take any possible precautions. Not observing the rules reported on this manual can
fan (2 fans as for the PACK DUE 16 models) according to the value of cooling power at any working
The PACK DUE INVERTER system firm reduces the plant’s water content to the minimum, that is from the usual value of cooling 12‐15 l/kW to 10 liters (as for the PACK DUE 7 and PACK DUE 9 model types) or to 16 liters (as for the model PACK DUE 12) or to 20 liters (as for the model PACK DUE 16), IN ABSOLUTE, as for the PACK DUE units. Because of the
appliance’s reduced size, the installation space, heat loss and installation costs.
4.9 MONITORING AND PROTECTION DEVICES
reduced water content, the PACK DUE units can be installed in plants without water tank with advantages in terms of the
DUE 12 and PACK
up to a value of 10 liters (as for the models PACK DUE 7 and PACK DUE 9), or of 16 liters (as for the model
absolute value and not to any kW of installed power.
CAUTION: Having a fixed ∆T(°C), the INVERTER control system is able to manage plant’s minimum water contents
PACK DUE 12), and of 20 liters (as for the model PACK DUE 16). This value makes reference to the liters’
The PACK DUE chillers units are supplied with an integrated hydraulic circuit including the circulating pump, suitable for chilled
PACK.DUE ‐ reversible heat pump with integrated hydronic system (expansion vessel, safety valve, pressure gauge, circulating
any eventual damage has to be questioned to the carrier and recorded on the Delivery Note before signing it. A2B ACCORRONI
severe damage.
create dangerous situations. After receiving the unit, immediately check its integrity. The unit left the factory in perfect condition;
E.G. to be informed, within 8 days, of the extent of the damage. The customer should prepare a written statement of any
10
6.2 LIFTING AND HANDLING
6.2.1 INDOOR UNIT
The handling must be performed by qualified personnel, properly equipped and with appropriate equipments to the weight of the unit, in compliance with safety regulations.
6.2.2 OUTDOOR UNIT
When unloading and installing the unit, it is highly recommended to avoid any sudden move in order to protect the inner components. Units can be lifted by means of a forklift or, in alternative, of belts, being sure not to damage the lateral panels and the cover. It is important to keep the unit horizontal during these operations.
6.3 LOCATION AND MINIMUM TECHNICAL CLEARANCES
6.3.1 INDOOR UNIT
‐ Place the unit on the wall.
‐ Drill holes in the marked positions and insert the plugs. ‐ Hook the unit.
Models. L1
(mm) L2
(mm) H1
(mm) H2
(mm) 300 300 1500 300
6.3.2 OUTDOOR UNIT
partially cover the unit) has to be avoided in order to prevent air recirculation. It is advisable to create a proper basement, with a size similar to unit foot‐print. Unit vibration level is very low: it is advisable however, to fit a rigid rubber band between basement and unit base‐frame. It is also possible to install anti‐vibration supports (springs or rubbers) to keep vibrations at a very low level. Absolute care has to be taken to ensure adequate air volume to the condenser. Re‐circulation of discharge air has to be avoided; failure to observe this point will result in poor performance or activation of safety controls. For these reasons it is necessary to observe the following clearances:
MOD. A B* C D E** 1500 500 400 400 500 1500 500 400 400 500 1500 500 400 400 500 1500 500 400 400 500
* Min.distance recommended for installation and maintenance. ** Min. distance recommended for assistance and maintenance.
Both units must be positioned on a leveled surface, the holders used for installation must be able to support its weight.
6.4 HYDRAULIC CONNECTIONS
6.4.1 CONNECTION DIAGRAMS The hydraulic connections have to be installed in accordance with national and local regulations; pipes can be made up of steel, galvanized steel or PVC. Pipes have to be designed depending on the nominal water flow and on the hydraulic pressure drops of
‐ Use the provided template to mark the mounting holes.
PACK DUE 7‐9‐12‐16
The all PACK.DUE units are designed for outdoor installation: any cover over the unit and location near trees (even if they
PACK DUE 7
PACK DUE 16
PACK DUE 9 PACK DUE 12
11
the system. All pipes have to be insulated with closed‐cell material of adequate thickness. Chillers have to be connected to piping by means of flexible joints. Piping should include: • Hole thermometers to monitor the system’s temperature. • Manual shut‐off valves to separate the chiller from the hydraulic circuit. • Y‐shaped metallic filter (to be mounted on the inlet pipe) with a mesh not larger than 1 mm. • Charging group and discharge valve, where necessary. • Anti‐vibration joints.
T
14
12
13
4
8 9
5
12 10
10
3
7 3
61
11
9*
Connections carried out by manufacturer Connections to be carried out by the installer
System outlet
System inlet
Y
Y
1. Manometer 2. Anti‐vibration joint (recommended for indoor unit joints) 3. Stop valve 4. Air vent valve 5. Flow switch 6. Thermometer 7. Filter 8. Safety valve 9. Expansion vessel 9* Additiona expansion vessel 10. Discharge valve 11. Load valve/reintegrate 12. Temperature sensor 13. Circulator 14. Heater
Unit water inlet pipe have to be in correspondence with the connection labelled: ”WATER INLET”, otherwise the evaporator may freeze. It is compulsory to install on the WATER INLET connection a metallic filter with a mesh not larger than 1 mm. Should the water flow switch be altered or should the filter not be installed, the warranty will no longer be valid. The filter have to be kept clean, so make sure it is clean after the unit has been installed, and then check it periodically.
WARNING All units are standard supplied with the water flow switch (factory installed). The water flow switch HAS TO BE INSTALLED on the water outlet connection (labelled WATER OUTLET). Should the water flow switch be altered, removed, or should the water filter not be installed on the unit, the warranty will be invalidated. Please refer to the wiring diagram for the water flow switch electric connections.
6.4.2 PLANT LAYOUT DESIGN
1. Indoor unit 2. DC inverter moto‐condensing
(outdoor unit) 3. Sanitary accumulator 4. Plant inertial accumulator 5. Instantaneous prepareracs 6. Solar collector 7. Radiant plant 8. Plant switching over/sanitary 9. Sanitary water inlet 10. Sanitary water outlet 11. Heater for integration 12. Solar central (optional)
MSI
12
6.4.3 CONNECTIONS POSITIONS 6.4.3.1 INDOOR UNIT
A. Sytem outlet pipe (1”M)
B. System inlet pipe (1”M)
C. Gas line (see Paragraph 13.2)
D. Liquid line (see Paragraph 13.2)
E. Power supply
F. Condensate drain (joint Ø 16 mm)
6.4.3.2 OUTDOOR UNIT
A. Power supply cover (access to the terminal
B. Gas connections cover
C. Gas connections
Models Liquid line Gas line
1/4 SAE 1/2 SAE
3/8 SAE 5/8 SAE
Units 12 and 16
A. Gas connections cover
(remove the front side cover to accede to the
terminal)
Models Liquid line Gas line
3/8 SAE 5/8 SAE
3/8 SAE 5/8 SAE
6.4.4 DRAINAGE CONNECTION 6.4.4.1 INDOOR UNIT
The indoor units are designed so that the base in which there are connections to the same act of the water tray. • Connect a pipe to the predisposed joint on the unit, cfr. Connections position. • Secure it using a hose clamp. • Route the pipe to a suitable draining place. • Maintain a sufficient slope to ensure the smooth flow of the condensate water.
6.4.4.2 OUTDOOR UNIT
installed onto the lower part of the unit in the special housing enabling the connection of a drainage pipe.
B
A
C
A
B
PACK DUE 7
block)
PACK DUE 9
PACK DUE 12
B. Access to power supply and signal cables
PACK DUE 16
Units 7 and 9
All PACK DUE units have been designed to use their own base as a drain pan; a plastic pipe fitting is standard provided to be
13
• Locate the hole at the base of the unit between the finned coil and fan, A. • Connect to the hole the provided fitting joint, B. • Connect a hose to the nozzle of the supplied fitting joint. • Direct the hose into thedisposal place for condensate water. • Maintain a sufficient slope to ensure the smooth flow of condensate water.
6.5 REFRIGERANT DIAGRAM
SEEEV
LRIN OUT
4WV
DT
LP HP
ST
M
P
C
LS
OS
FL FL
NRV
CLS
Pr
C COMPRESSOR
CLS COMPRESSOR LIQUID SEPARATOR (only for the models i‐SHWAK/WP 05, 07 e 10)
OS OIL SEPARATOR (only for the models i‐SHWAK/WP 10 e 15) ST COMPRESSOR INLET TEMPERATURE DT COMPRESSOR OUTLET TEMPERATURE HP HIGH PRESSURE TRANSDUCER Pr HIGH PRESSURE FLOW SWITCH LP LOW PRESSURE TRANSDUCER LS LIQUID SEPARATOR (only for models i‐SHWAK/WP 10 e 15)
4WV VALVE FO INVERTING CYCLE LR LIQUID RECEIVER EEV ELECTRONIC EXPANSION VALVE NRV NO RETURN VALVE (only for the models i‐SHWAK/WP 10 e 15) FL FILTER M AXIAL FAN SE OUTDOOR AIR TEMPERATURE P CIRCULATOR ON BOARD UNIT IN WATER INLET TEMPERATURE
OUT WATER OUTLET TEMPERATURE
WARNING: The unit should be installed so that adequate clearance is available for maintenance and repairation. The warranty does not cover costs related to platforms or handling equipment necessary for any maintenance.
All maintenance and testing operations should be carried out only by QUALIFIED PERSONNEL.
Before any operation on the unit, make sure the power supply is disconnected.
WARNING: Inside the unit, there are some moving parts. Be especially careful when working near them, even if the unit is off. The temperatures of heads and exhaust piping of the compressor are usually high. Therefore be careful when working near condensing coils.
The aluminum fins are very sharp and can cause serious injuries.
After the maintenance operations, close the panels tightly with the fastening screws.
6.6 ELECTRICAL CONNECTIONS
Check out that the power supply meets the unit’s electric nominal data (tension, phases, frequency) reported on the label in the unit’s front panel. Power connections have to be made in accordance to the wiring diagram enclosed with the unit and in accordance to the national and international norms in force. Power cables and line fuses have to be sized according to the specifications listed in the wiring diagram enclosed with the unit.
WARNING: The supply voltage’s fluctuations can not exceed ±10% of the nominal value. Should these tolerances not be respected, please contact our technical department.
WARNING: The power supply have to respect the listed limits: failing this, warranty will terminate immediately. Before any operation on the unit, be sure that the power supply is disconnected. WARNING: The water flow switch (the component number 5 in the previous image and factory installed) have ALWAYS to be connected following the indications listed in the wiring diagram. Never bridge the water flow switch connections in the terminal board. Should the water flow switch connections altered or not properly made, the guarantee will be invalidated.
WARNING: The indoor unit can not be installed in areas with strong vibrations, corrosive gases, and excess of dirtiness or high humidity levels. Comply with the minimum technical installation.
A
B
14
6.6.1 TERMINAL BLOCK CONNECTIONS
Electrical wiring have to be done only by qualified personnel.
6.6.1.1 WIRING BETWEEN INDOOR AND OUTDOOR UNITS
The indoor unit must be connected to the outdoor unit as shown in the below figure.
L N
L N
U-N230V-1Ph-N-50Hz
PE
A
B
QF
P Q E U N
Gnd
R+R-
- +OUTDOORUNIT
INDOORUNIT
X
/ d
GF: General differential switch (not included) A: RS485 connection B: Power supply connection
6.6.1.2 INDOOR UNIT
TERMINALS OF THE ELECTRIC BOX
Single‐phase power supply terminals (ground –phase ‐neutral) max. 4 mm for the units i‐
U‐N For the connection, please use a cable with a maximum section of 4/6mm.Follow the regulations for the section of the cable.
the outdoor unit
P(‐) ‐ Q(+) ‐ E(Gnd)
For the connection, please use a cable with a minimum section of 1mm for a length not more than 10 m. For length until 100 m a cable with section of1.5mm must be used.
TERMINALS LOCATED ON THE BOARD A1
A2 Solar expansion board (optional) EXPANSION For the connection, please use the cable supplied with the solar expansion kit fitting.
A3 Output 230Vac 1A MAX for resistance R2 of contactor control KM2.
UD0 – N For the connection, please use a cable with a minimum section of 1,5mm.
YV1 3 way valve for sanitary hot water UD1 – N For the connection, please use a cable with a minimum section of 1,5mm.
TH1 Ambient thermostat ID3 – N For the connection, please use a cable with a minimum section of 1mm for a length not more than 10m. For length more than 10m a cable with section of 1,5mm must be used.
BT3 Boiler sanitary water sensor IA2 – G For connection, a cable with minimum section of 0,5mm must be used for a length not more than 50m. For lengh until 100m, a cable with section of 1mm must be used.
BT4 Outdoor air temperature sensor IA3 – G For connection, a cable with minimum section of 0,5mm must be used for a length not more than 50m. For lengh until 100m, a cable with section of 1 mm must be used.
PROTECTION PARTS
QF General differential switch (not included) For the differential switch capcity, please respect the regulations and the
power supply of unit.
PACK DUE 7‐9 and 6mm for the units i‐
Terminals RS485 to be connected with those of
PACK DUE 12 and 16.
15
6.6.1.3 OUTDOOR UNIT
The electrical connections have to be realized by qualified personnel.
L2 NNO NC R+
R-
L2
NO NC R+
R-N
GND
GNDCO
CO
L1
L1
L3
L3
FUS
E
GND: grounding wire; N1: power supply neutral wire; L1: power supply live wire; L2: If it exists, connect the live wire coming from the system L3: If it exists, connect the live cable coming from the system NO: generic alarm output (closed when the alarm is not activated); CO: generic alarm output common terminal; NC: NO terminal generic alarm output (closed when the alarm is activated); R+: modbus + signal for connection with indoor unit; R‐: modbus ‐ signal for connection with indoor unit;
WARNING: The grounding of the signal cable must not be connected and must be protected from accidental contact with the sheet: cut it or isolate it with tape.
7 START UP Before start‐up
• Ensure the availability of diagrams and manuals of the installed appliance. • Check the availability of diagrams electrical and hydraulic diagrams of the plant where the appliance is connected. • Check if the anti‐vibration couplings exists on hydraulic pipes. • Check if the shut‐off valves of the hydraulic circuits are opened. • Check that the hydraulic circuit has been loaded into required pressure and vented from air. • Check that all the hydraulic connections are carried out correctly and that all information on the labels are respected. • Ensure that arrangements have been provided to drain condensate. • Ensoure that power cables and all terminals anre well connected. • Check that the electrical connections have been made according to applicable regulations including grounding. • The voltage must be specified on the nameplate of the unit. • Ensure that the voltage is within the tolerance limits of (±10%). • Check that the heating elements of the compressor are powered properly. • Ensure that there are no gas leaks. • Before the start up, check that all shutting panels are positioned and fixed with proper screws.
The crankcase heaters have to be powered at least 12 hours before start up by switching off the main switch (the heaters are automatically powered when the main switch is switched off). The crankcase heaters are working properly if, after some minutes, the temperature of crankcase’s compressor is about 10°C ÷ 15°C higher than ambient temperature. Never switch off the unit (for a temporary stop) by switching off the main switch: this component should be used to disconnect the unit from the power supply only for lengthy stoppages (e.g. seasonal stoppages). Besides, failing the power supply, the crankcase’s resistances are not supplied thus resulting in a possible breakdown of the compressors once the unit is switched on.
WARNING Do not modify the internal wiring of the unit otherwise the warranty will terminate immediately. WARNING: As for the heat pump models, the summer/winter operating mode have to be selected at the beginning of the related season. Frequent changes of this seasonal operating mode have to be avoided in order to prevent severe damages to compressors.
For the models PACK DUE 7 and PACK DUE 9, the terminal block is located under the plastic cover on the right side of the
the terminal block has to be realized in accordance to the below notes. outdoor unit (for the PACK DUE 12 and PACK DUE 16 models, it is necessary to remove the protective carter). The wiring to
16
8 INDOOR UNIT CONTROL PANEL The control panel is composed of a display and buttons for programming.
ESC
1
PRGMODEON/OFF
4 5 6 7 8
2
3
8.1 LED
1 Heat pump in heating mode 2 Heat pump in cooling mode 3 Circulation pump in sanitary mode 1+3 Circulation pump in cooling mode with sanitary boiler priority 2+3 Heat pump in heating mode with sanitary boiler priority 4 Heat pump compressor is on 5 Hydraulic pump of the heat pump system 6 Electric heater of heating system in heat (winter) mode 7 Sanitary boiler electric heater 8 Hydraulic pump of solar system
8.2 FUNCTIONS OF BUTTONS
Esc Alarm reset Menu exit User menu scrolling
MODE ON/OFF
Change in heat pump mode To power on and off the heat pump
Prg To select parameters To store parameters
▲ Increase the set point To increase the value to be changed Select top item inside the menu
▼ Decrease the set point Decrease the value to be changed Decrease the bottom item inside the menu
8.2.1 LEVELS OF ACCESS It has 2 levels of consultation and programming.
1 Without password for the user To display the values of parameters, change set point, date and hour. 2 With password for Maintenance and Manufacturer To display and programmino the parameters of the appliance.
Please contact our service centre for further details.
17
8.3 DESCRIPTION OF THE MAIN DISPLAY
DISPLAY VISUALISATION NOTE MAIN DISPLAY
Date and time
Display 1 Return temperature from the heating or cooling system Set point of heating or cooling system
Display 2 Temperature of the sensor of the sanitary sanitary termoaccumulatore Set‐point of sanitary sanitary termoaccumulatore
Display 3 Outdoor air temperature
Display 4 Temperature of the solar panel collector Temperature of the sanitary thermo‐accumulator
Screenshot available only in the presence of solar panel
Display 5 Power output of the solar system Screenshot available only in the presence of solar panel
8.3.1 NAVIGATION BETWEEN DISPLAYS
On the control panel 1 Press the ESC button to browse the user’s menu.
8.4 OPERATING MODES
MODE DESCRIPTION OFF The unit stay in stand‐by Only cooling Production of chilled water for cooling Cooling and sannitary water Production of chile water for cooling and and sanitary hot water Only heating Production of hot water for heating Heating and sanitary water Production of hot water for heating and sanitary hot water Only sanitary water Production of sanitary hot water
8.4.1 OPERATION MODE SETTING On the control panel 1 Press the “Mode On‐Off” button to select the operating mode. 2 Will be automatically memorized.
8.5 PROCEDURE
8.5.1 SET‐POINT SELECTION On the control panel 1 Press the arrows to the set point value. 2 Will be automatically memorized.
The operation is the same also for the modification of the sanitary set‐point.
8.6 DESCRPTION OF FUNCTIONS
Function DESCRIPTION
Timer setting Setting of the timer on and off for the heat pump according to time slots.
Set‐point setting Setting the set‐point of the system and sanitary of heat pump.
Pasword setting Setting the pasword to access into the menu mainyener of manufacturer.
Programming Setting the parameters displayed only by the user (no password) clock (hours and minutes) appears on the main page.
8.6.1 ACCESS TO THE FUNCTIONS On the control board 1 Press the “PRG” button to enter. 2 Press the arrows buttons to select the function. 3 Press the “PRG” button to accede.
18
8.7 ALARMS
Alarm type Alarm description Cause
Water flows alarm Lack of water circulation on the hydraulic side of the heating/cooling/sanitary boiler system.
Hydraulic pump is off, burnt, ecc.. the pressure of the water side is zero bar. The faucet for interception of the system are closed.
Outdoor unit link alarm
A lose or bad serial connection between indoor and outdoor moto‐condensing unit.
Electrical connections reversed or interrupted
Sensor alarm Bad detection of the temperature sensor. Cable of temperature sensor is interrupted. Temperature sensor error.
Water antifreeze Temperature of the water of cooling/heating/sanitary boiler system is below the set point.
Hydraulic pump is off, burnt, etc... Pressure on the water side is 0 bar. Faucets for the interception of the system are closed
8.8 ADJUSTMENT OF SANITARY WATER VALVE
To activate the sanitary hot water you must: • connect to the terminals IA2 –G a sensor which should be installed inside the tank, • connect the 3‐way switch‐over valve to the terminals UD1‐N (with spring return) If the sanitary hot water temperature is lower than the set‐point of sanitary water (set to 48°C by default) the unit activates the 3‐way switch‐over valve to deviate the flow of water towards the water tank or to a heat exchanger. If the set‐point of sanitary water is reached, the valve returns in rest period. Contact UD1 N‐(3‐way valve): • close: valve energized and water flow deviated to the water tank, • open: valve de‐energized and water flow deviated to the user. Commutating from winter mode operation to sanitary mode operation, the compressor remains on and works under the set frequency. Commutating from summer mode operation, the compressor turns off for safety period.
NOTES: Using the keyboard on the unit to turn off it does not the sanitary operation The display board on the unit shows: • In sanitary mode: the display shows the temperature measured by the sensor located in the container, • In heating or cooling mode: the diplay shows the outlet water temperature sensor. The defrost during heating operation is always performed on the user side, never on the sanitary water tank.
9 MICROPROCESSOR USER INTERFACE
It is used to reset the manual resetting alarms. During the parameters’ setting, this button can be used to revert BACK to the previous level.
It allows you to view the setting menu parameters.
UP button: In the setting mode, this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode.
DOWN button: In the setting mode, this button allows you to shift to a lower menu or to decrease the value of a parameter when you are in the edit mode.
19
9.1 DISPLAY
In normal view displays the alarm code if at least an alarm is active. In case of multiple alarms activation, it will display the first alarm, while the second appears when the first is reset.
9.2 LED
Compressor LED
• ON if the compressor is running • OFF if the compressor is off • FLASHING if timings are in progress waiting for compressor’s start up
Sanitary water LED
• ON if sanitary water valve is in open position • OFF if the sanitary water valve is in closed position
Defrosting LED
• ON in defrost operating mode • OFF if defrosting mode is disabled or completed • FLASHING if defrosting cycle interval’s time is in progress
Antfreeze resistance LED • The LED is ON if the antifreeze resistance is active.
Water pump LED • The LED is ON if the water pump is running.
Alarm LED • The LED is ON if an alarm is activated.
Heat LED • The LED is ON if the unit is in the heating mode operation.
Cool LED • LED is ON if the unit is in the cooling mode operation.
9.3 ANTIFREEZE PROTECTION RESISTANCES (if the KAS accessory is present)
The heating cable placed on the basement of the appliance is equipped with a built‐in thermostat which activates the cable even if the unit is off (but energized) when the outside air temperature decreases below 5°C.
9.4 ALARMS
9.4.1 Sensor alarms The alarm will be activated in the case of a short or open circuit of any connected and enabled sensor. The alarm will be activated also when the temperature becomes higher than the sensors’ upper limit (100°C) or less than the lower limit (‐50°C). 9.4.2 Time out inverter
Supposing the controller does not communicate with the driver of the compressor, the time out alarm will be activated in order to prevent a system’s control loss. 9.4.3 High pressure
If the on board pressure transductor detects a pressure higher than 40 bar, the alarm will be activated. In this case the compressor will stop immediately. The alarm will reset when the pressure decreases under 36 bar. 9.4.4 High pressure flow switch (in series with the compressor outlet probe)
If the pressure switch on the machine detects a pressure higher than 42 bar the alarm will be active. In this case, the compressor will be immediately stopped. The alarm resets when the pressure drops below 32 bar. 9.4.5 Low pressure
If the on board pressure transductor detects a pressure lower than 2 bars, the alarm will be activated. In this case the compressor will stop immediately. The alarm will reset when the pressure goes over 6 bar.
9.5 POWER FAILURE
After power supply reset: 1. The system comes back to the previous state before the power failure. 2. If the system is defrosting, this mode will be cancelled after power supply reset. 3. All the running timings will be cleared and reset again.
20
9.6 ALARMS LIST
Error description Code Compressor Pump Resistances Fan
Inverter hardware malfunctioning E75 OFF OFFCompressor’s tension too high E76 OFF OFFPower supply tension out of bounds E78 OFF OFFCompressor not power supplied E79 OFF OFFInverter time out malfunctioning E80 OFF OFFCompressor inlet sensor E63 OFF OFF OFF OFFCompressor outlet sensor E64 OFF OFF OFF OFFHigh pressure transductor E65 OFF OFF OFF OFFLow pressure transductor E66 OFF OFF OFF OFFOutdoor air sensor for climate adjust E67 OFF OFF OFF OFFHigh pressure E01 OFF OFF Low pressure E02 OFF OFF
10 SHUTDOWNS FOR LONG PERIODS • Turn off all the indoor terminal units of the users. • Close the water faucet. • Turn off the switch QF general differential to OFF.
If the temperature drops below freezing point (0°C) there is serious danger of frost: providing a mixture of water and glycol in the system, otherwise drain the water system and the hydraulic circuits of the heat pump.
11 MAINTENANCE AND PERIODIC CHECKS
WARNING: All the operations described in this chapter HAVE TO BE CARRIED OUT BY TRAINED STAFF ONLY. Before any operation or before entering the inner components of the unit, be sure that the power supply is disconnected. The compressor’s heads and discharge piping are usually at high temperature levels. Be very careful when operating in their surroundings. Aluminium coil fins are very sharp and can cause serious wounds. Be very careful when operating in their surroundings. After servicing operations, re‐install the cover panels, and fix them by means of screws.
The refrigerant circuits must not be filled with refrigerant gas other than that indicated on the nameplate. The use of a different refrigerant can cause severe damage to the compressor.
It is forbidden to use refrigerant oils other than those specified in this manual. The use of different oil can cause serious damage to the compressor.
It is a good rule to carry out periodic checks in order to verify the proper operation of the unit.
OPERATION 1
month 4
month6
month
Filling the water circuit. x
Presence of bubbles in the water circuit. x
Check out that safety and control devices work correctly (indoor and outdoor units) x
Check out possible oil leakage from compressor (outdoor unit). x
Check out possible water leakages from the hydraulic circuit (outdoor unit). x
Check out the proper working of the flow switches (outdoor unit). x
Check out that the crankcase resistances are properly supplied and functioning (outdoor unit). x
Clean the metallic filters of the hydraulic circuit. x
Clean the finned coil by means of compressed air or water jet (outdoor unit). x
Check out that all the terminals on the electric board as well as on the terminals of the compressor are properly fixed. Clean from time to time the remote control switch’s sliding and fixed contacts (indoor and outdoor units).
x
Tightening of water connections. x
Check out the tightening and the balancing of the fan blades (outdoor unit). x
Correct voltage. x
Correct absorption. x
Check the refrigerant charge. x
21
Check the operating pressure, and superheat and subcooling x
Check of the efficiency of circulation pump. x
Check the expansion tank. x
If the unit should be out of service for a long period, discharge water from the piping and from heat exchanger. This operation is necessary if, during seasonal stoppages, ambient temperature is expected to go down below the freezing point of the employed fluid.
x
11.1 ENVIRONMENTAL PROTECTION
According to the norms dealing with the use of depleting stratospheric ozone substances, it is forbidden to release refrigerants fluids in the atmosphere. They have to be collected and delivered to the seller or to proper gathering points at the end of their operating life. Refrigerant R410A is mentioned among controlled substances and for this reason it has to be subjected to the mentioned norms. A particular care is recommended during service operations in order to reduce as much as possible any refrigerant loss.
12 WHEN THE UNIT GOES OUT OF SERVICE Once the unit is arrived at the end of its life cycle and needs to be removed or replaced, the following operations are
recommended. • the refrigerant has to be recovered by trained people and sent to proper collecting centre; • compressors’ lubricating oil has to be collected and sent to proper collecting centre; • the frame and the various components, if not serviceable any longer, have to be dismantled and divided according to their nature, particularly copper and aluminium, which are present in conspicuous quantity in the unit. These operations allow easy material recover and recycling process, thus reducing the environmental impact.
22
13 TECHNICAL DATA 13.1 OUTDOOR UNITS
TECHNICAL DATA Power supply 230V/1/50Hz 230V/1/50Hz 230V/1/50Hz 400V/3/50Hz Max. power input kW 2.81 3.80 5.47 6.15 Max. starting current A 7.9 10.0 15.6 8.7
Electrical data
Max. current input A 12.6 17.1 24.5 14.6 Brand SANYO HITACHI MITSUBISHI SIAM MITSUBISHI SIAM Model C‐6RVN93H0V ATL165SD‐C9AU TNB306FPGM ANB42FBEMT
Type Rotary
DC Inverter Rotary
DC Inverter Twin Rotary DC inverter
Scroll DC inverter
Number 1 1 1 1 Power input in cooling mode (1) kW 1.31 1.73 2.43 3.00 Power input in cooling mode (2) kW 1.40 1.90 2.65 3.21 Power input in heating mode (3) kW 1.49 2.07 3.25 3.92 Power input in heating mode (4) kW 1.23 1.72 2.58 3.15
Compressor
Refrigerant oil (type, quantity) mL FV 50S, 350 68HES‐H, 880 FV50S, 870 MEL 56, 1700 Model YDK53‐6Y YDK53‐6Z YDK100‐6A YDK100‐6A Type AC motor AC motor AC motor AC motor Number 1 1 2 2 Rated power input kW 0.13 0.15 0.19 (×2) 0.19 (×2) Rated running current A 0.59 0.69 0.87 (×2) 0.87 (×2) Condensator uF 3uF/450VAC 3uF/450VAC 3uF/450VAC 3uF/450VAC Speed r/min 770 815 860 860
Fan motor
Max. air flow m3/s 0.71 0.89 1.65 1.67 Number of rows 1.6 2 2.6 2 Tube pitch × row pitch mm 22×19.05 25.4×22 25.4×22 25.4×22 Fin gap mm 1.4 1.5 1.5 1.8 Fin type Hydrophilic aluminiun Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Tube outside diameter and type mm Ф7.94 Innergroove
copper tube Ф9.53 Innergroove
copper tube Ф9.53 Innergroove
cooper tube Ф9.53 Inner groove
copper tube
Length × height × depth (condenser) mm 778×660×38.1 758×813×44 887×1220×44 887×1220×44
Condenser
Number of circuits 2 2 8 8 Type R410A R410A R410A R410A Refrigerant charge (5) kg 1.60 1.80 3.30 4.20 Refrigerant
Pressure design (high/low) MPa 4.2/2.0 4.2/2.0 4.2/2.0 4.2/2.0 Liquid side / Gas side mm 6.4/12.7 9.5/15.9 9.5/15.9 9.5/15.9 Max. Refrigerant pipe length m 25 25 30 30 Max. difference in level (out. unit is up) m 12 12 20 20
Refrigerant piping
Max. difference in level (out. unit is down m 9 9 12 12 Sound pressure (6) dB(A) 38÷58 40÷59 41÷61 41÷62
Noise Sound pressure (7) dB(A) 46÷67 48÷68 49÷70 49÷71 Dimensions (L×A×P) mm 842×695×324 895×862×313 940×1245×360 940×1245×360 Packing (L×A×P) mm 965x752x399 1043×915×395 1080×1285×435 1080×1285×435
Dimensions and weight
Net/Gross weight kg 59/63 73/76 106/114 115/121
Operating conditions: (1) Cooling: Outdoor air temperature 35°C; inlet/outlet water temperature 12/7°C. (2) Cooling: Outdoor air temperature 35°C; inlet/outlet water temperature 23/18°C. (3) Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet water temperature 40/45°C. (4) Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 30/35°C. (5) Refrigerant charge valide until 5m of distance between indoor and outdoor units. Above 5m, add 20g/m of refrigerant for the model i‐SHWAK/WP 07 and
50g/m of refrigerant for the models i‐SHWAK/WP 09‐12‐16. (6) Sound pressure level measured at 1m from the unit, in free field, according to ISO 3746. (7) Sound pressure levels are measured in free field environment at 1m and 1.5m above the ground, according to DIN 45635. N.B. The performance data shown is indicative and could be subject to change.
PACK DUE 7 PACK DUE 9 PACK DUE 12 PACK DUE 16
23
13.2 INDOOR UNITS TECHNICAL DATA Units Power supply 230V/1/50Hz 230V/1/50Hz 230V/1/50Hz 230V/1/50Hz Max. Power input kW 3.13 3.13 4.13 4.13 Electrical data
Max. input current A 13.68 13.68 17.98 17.98 Cooling capacity (1) kW 4.71 6.09 9.03 10.82 Input power (1) kW 1.52 1.96 2.90 3.49 E.E.R. (1) W/W 3.10 3.11 3.11 3.10 Cooling capacity (2) kW 6.12 8.12 11.90 14.07 Input power (2) kW 1.61 2.13 3.12 3.70
Cooling
E.E.R. (2) W/W 3.80 3.81 3.82 3.80 Heating capacity (3) kW 5.44 7.44 11.98 14.10 Input power (3) kW 1.70 2.32 3.72 4.35 C.O.P. (3) W/W 3.20 3.21 3.22 3.24 Heating capacity (4) kW 5.90 8.01 12.58 14.95 Power consumption (4) kW 1.44 1.95 3.05 3.64
Heating
C.O.P. (4) W/W 4.10 4.11 4.12 4.10 Water flow (4) L/s 0.28 0.38 0.60 0.71 Head pressure (4) kPa 48 45 38 32 Max. input power of water pump kW 0.13 0.13 0.13 0.13 Max. input current of water pump A 0.58 0.58 0.58 0.58 Expansion vessel L 10 10 10 10 Hydraulic connections inch 1”M 1”M 1”M 1”M Minimum valume of water L 10 10 16 20
Hydraulic circuit
Maximum volume of water L 350 350 350 350 Liquid side connection inch 1/4” SAE 3/8” SAE 3/8” SAE 3/8” SAE
Refrigerant circuit Gas side connection inch 1/2” SAE 5/8” SAE 5/8” SAE 5/8” SAE Power input kW 3.0 3.0 4.0 4.0
Integrative resistance Current input A 13.10 13.10 17.40 17.40 Dimensions (L×A×P) mm 515×816×270 515×816×270 515×816×270 515×816×270 Net weight kg 30 32 34 34
Dimensions and weight
Gross weight kg 33 35 37 37
Operating conditions:
(1) Cooling: Outdoor air temperatue 35°C; inlet/outlet temperature 12/7°C. (2) Cooling: Outdoor air temperature 35°C; inlet/outlet temperature 23/18°C. (3) Heating: Outdoor air temperature 7°C DB 6°C WB.; temp.acqua ing./usc. 40/45°C. (4) Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 30/35°C. N.B. ‐ The performance data are indicative and could be subject to change. ‐The electrical data are shown to scale the size of the circuit breakers and power cables for the indoor unit.
14 ELECTRIC DATA Power supply of the unit V/~/Hz 230/1/50*‐400/3/50** Remote control circuit V/~/Hz 12 / 1 / 50 Control board circuit V/~/Hz 12 / 1 / 50 Fans power supply V/~/Hz 230 / 1 / 50
Note: Electric data may change for updating the manual. It is therefore necessary to refer always to the wiring diagram of this manual supplied with the unit.
PACK DUE 7 PACK DUE 9 PACK DUE 12 PACK DUE 16
* For all indoor units and outdoor units PACK DUE 7, PACK DUE 9, PACK DUE 12. ** For the model PACK DUE 16.
24
15 EFFECTIVE HEAD PRESSURES
Head pressure – water flow characteristics curve net of evaporator pressure drops.
under the conditions specified at the top (4) of page 23.
under the conditions specified at the top (4) of page 23.
under the conditions specified at the top (4) of page page 23.
under the conditions specified at the top (4) of page page 23. The plant must be designed so as to ensure the nominal flow rate correspondingly with the working data indicated above.
0
10
20
30
40
50
60
70
0,6 0,8 1 1,2 1,4 1,6 1,8 2 2,2 2,4 2,6 2,8 3
Flow rate [m3/h]
Hea
d Pressure
[Kp
a]07
12
09
16
Optimum operating point for PACK DUE 7 minichillers at compresssor’s limit frequency, at water pump’s high speed
Optimum operating point for PACK DUE 9 minichillers at compresssor’s limit frequency, at water pump’s high speed
Optimum operating point for PACK DUE 12 minichillers at compresssor’s limit frequency, at water pump’s high speed
Optimum operating point for PACK DUE 16 minichillers at compresssor’s limit frequency, at water pump’s high speed
25
16 PERFORMANCES CURVES The performances curves reported below are only for indications and could be subjet to modification.
6
7
8
9
10
11
12
13
14
15
16
17
18
19
4,0 4,2 4,4 4,6 4,8 5,0 5,2 5,4 5,6 5,8 6,0 6,2 6,4 6,6 6,8
Cooling power kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C
6
7
8
9
10
11
12
13
14
15
16
17
18
19
1,3 1,4 1,5 1,6 1,7 1,8 1,9 2,0 2,1 2,2
Input power in cooling operation kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C
6
7
8
9
10
11
12
13
14
15
16
17
18
19
2,0 2,5 3,0 3,5 4,0 4,5
E.E.R. W/W
Wat
er o
utle
t tem
pera
ture
°C
air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C
16.1 Mod. PACK DUE 7
26
33
35
37
39
41
43
45
47
49
51
53
55
57
3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5 7,0 7,5 8,0
Heat capacity yields kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 21°Cair temp. 14°Cair temp. 7°Cair temp. 0°Cair temp. -7°Cair temp. -10°C
33
35
37
39
41
43
45
47
49
51
53
55
57
1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2,0 2,1 2,2 2,3 2,4 2,5
Input power in heating operation kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 21°C
air temp. 14°C
air temp. 7 °C
air temp. 0 °C
air temp. -7°C
air temp. -10°C
33
35
37
39
41
43
45
47
49
51
53
55
57
1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0
Coefficient of performance C.O.P. W/W
Wat
er o
utle
t tem
pera
ture
°C
air temp. 21°Cair temp. 14°Cair temp. 7°Cair temp. 0°Cair temp. -7°Cair temp. -10°C
27
6
7
8
9
10
11
12
13
14
15
16
17
18
19
5,0 5,5 6,0 6,5 7,0 7,5 8,0 8,5 9,0
Cooling power kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C
6
7
8
9
10
11
12
13
14
15
16
17
18
19
1,8 1,9 2,0 2,1 2,2 2,3 2,4 2,5 2,6 2,7
Input power in cooling operation kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C
6
7
8
9
10
11
12
13
14
15
16
17
18
19
2,2 2,4 2,6 2,8 3,0 3,2 3,4 3,6 3,8 4,0 4,2 4,4 4,6
E.E.R. W/W
Wat
er o
utle
t tem
pera
ture
°C
air temp. 45 °Cair temp. 40 °Cair temp. 35 °Cair temp. 30 °C
16.2 Mod. PACK DUE 9
28
33
35
37
39
41
43
45
47
49
51
53
55
57
1,8 1,9 2,0 2,1 2,2 2,3 2,4 2,5 2,6 2,7 2,8 2,9 3,0 3,1
Input power in heating operation kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 21°Cair temp. 14°Cair temp. 7°Cair temp. 0°Cair temp. -7°Cair temp. -10°C
33
35
37
39
41
43
45
47
49
51
53
55
57
1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0Coefficient of performance W/W
Wat
er o
utle
t tem
pera
ture
°C
air temp. 21°Cair temp. 14°Cair temp. 7°Cair temp. 0°Cair temp.-7°Cair temp. -10°C
33353739414345474951535557
4,0 5,0 6,0 7,0 8,0 9,0 10,0 11,0
Heat capacity yields kW
Wat
er o
utle
t tem
pera
ture
°C
air t emp. 21°C
air t emp. 14°C
air t emp. 7°C
air t emp. 0°C
air t emp. -7°C
air t emp. -10°C
29
6
7
8
9
10
11
12
13
14
15
16
17
18
19
8,0 8,5 9,0 9,5 10,0 10,5 11,0 11,5 12,0 12,5 13,0
Cooling power kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C
6
7
8
9
10
11
12
13
14
15
16
17
18
19
2,6 2,7 2,8 2,9 3,0 3,1 3,2 3,3 3,4 3,5 3,6 3,7 3,8 3,9
Input power in cooling operation kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C
6
7
8
9
10
11
12
13
14
15
16
17
18
19
2,2 2,4 2,6 2,8 3,0 3,2 3,4 3,6 3,8 4,0 4,2 4,4 4,6
E.E.R. W/W
Wat
er o
utle
t tem
pera
ture
°C
air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C
16.3 Mod. PACK DUE 12
30
33
35
37
39
41
43
45
47
49
51
53
55
57
9,0 9,5 10,0 10,5 11,0 11,5 12,0 12,5 13,0 13,5 14,0 14,5 15,0Heat capacity yields kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. < 27°C
air temp. 20°C
air temp. 13°C
air temp. 7°C
air temp. 2°C
air temp. -2°C
air temp. -7°C
air temp. -10°C
air temp. -12°C
33
35
37
39
41
43
45
47
49
51
53
55
57
2,9 3,3 3,7 4,1 4,5 4,9 5,3 5,7
Input power in heating operation kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. < 27°C
air temp. 20°C
air temp.13°C
air temp. 7°C
air temp. 2°C
air temp.-2°C
air temp. -7°C
air temp. -10°C
air temp. -12°C
33
35
37
39
41
43
45
47
49
51
53
55
57
1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5Coefficient of performance W/W
Wat
er o
utle
t tem
pera
ture
°C
air temp. < 27°C
air temp. 20°C
air temp. 13°C
air temp. 7°C
air temp. 2 °C
air temp. -2°C
air temp. -7°C
air temp. -10°C
air temp. -12°C
31
6
7
8
9
10
11
12
13
14
15
16
17
18
19
8 9 10 11 12 13 14 15 16Cooling power kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C
6
7
8
9
10
11
12
13
14
15
16
17
18
19
3,1 3,3 3,5 3,7 3,9 4,1 4,3 4,5
Input power in cooling operation kW
Wat
er o
utle
t tem
pera
ture
°C
air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C
6
7
8
9
10
11
12
13
14
15
16
17
18
19
1,9 2,1 2,3 2,5 2,7 2,9 3,1 3,3 3,5 3,7 3,9 4,1 4,3 4,5 4,7
E.E.R. W/W
Wat
er o
utle
t tem
pera
ture
°C
air temp. 30 °Cair temp. 35 °Cair temp. 40 °Cair temp. 45 °C
16.4 Mod. PACK DUE 16
32
33
35
37
39
41
43
45
47
49
51
53
55
57
8,0 9,0 10,0 11,0 12,0 13,0 14,0 15,0 16,0 17,0 18,0 19,0
Heat capacity yields kW
Wat
er o
utle
t tem
pera
ture
°Cair temp.< 27°C
air temp. 20°C
air temp. 13°C
air temp. 7°C
air temp. 2°C
air temp. -2°C
air temp. -7°C
air temp. -12°C
air temp. -15°C
33
35
37
39
41
43
45
47
49
51
53
55
57
2,7 3,0 3,3 3,6 3,9 4,2 4,5 4,8 5,1 5,4 5,7 6,0 6,3
Input power in heating operation kW
Wat
er o
utle
t tem
pera
ture
°C
air temp.< 27°C
air temp. 20°C
air temp. 13°C
air temp. 7°C
air temp. 2°C
air temp. -2°C
air temp. -7°C
air temp. -12°C
air temp.-15°C
33
35
37
39
41
43
45
47
49
51
53
55
57
1,0 1,5 2,0 2,5 3,0 3,5 4,0 4,5 5,0 5,5 6,0 6,5
Coefficient of performance W/W
Wat
er o
utle
t tem
pera
ture
°C
air temp.< 27°C
air temp. 20°C
air temp. 13°C
air temp. 7°C
air temp. 2°C
air temp. -2°C
air temp. -7°C
air temp. -12°C
air temp. -15°C
33
17 OPERATION LIMITS 17.1 Evaporator water flow rate
The nominal water flow rate is referred to a ∆T = 5°C, between the evaporator’s inlet and outlet temperatures. The allowed maximum flow rate is corresponding to ∆T = 3°C; higher values may cause too high pressure drops. The allowed minimum water flow rate is corresponding to ∆T = 8°C. Insufficient values may cause too low evaporating temperatures with the intervention of safety devices which would stop the unit and, in some particular cases, the water can freeze in the evaporator coil causing the refrigeration circuit to break down. We enclosed below a most accurate table showing the minimum flow rates that to ensure for the plate heat exchanger for a the proper operation of unit according to the model (note: the water flow switch is used for preventing the freezing sensor from failure in the case of insufficient water flow but it does not ensure the minimum flow rate required in order the unit can work properly)
Model
Cooling capacity for reference [kW] 6,12 8,12 11,90 14,07
Minimum water flow rate that to ensure [L/s] 0,183 0,243 0,356 0,421 As a first approch, and in the absence of other detection systems, the proper flow rate for getting the best performance from your unit can be found at maximum speed of the circulator, using the pressure gauges for controlling the pressure difference between the return and the delivery water on the outside water connections of the unit and make sure that such value is equal or less than the static pressure indicated on the curves shown in paragraph 16 for the respectives models.
17.2 Cold water temperature (summer operation)
The allowed minimum temperature at the evaporator’s outlet is 5°C; for more lower temperatures, the unit should undergo some necessaries structural modifications. In this case contact our company for the feasibility study and evaluation of changes to be made according to your requests. The maximum temperature that can be maintained at the outlet of the evaporator is 25°C. Higher temperatures (up to a maximum of 40°C) can anyway be tolerated during transitions and start‐up phases of the system. In all cases, the maximum electrical input occurs for the heat pump operating mode at a water outlet temperature of 55°C and with outdoor temperature of ‐10°C (see the tables in paragraph 17.3).
17.3 Hot water temperature (winter operation)
Once the system is working at the right temperature, the inlet hot water temperature should not to be lower than 25°C; the lowest values that are not related to transitional or start‐up stages may cause compressor’s incorrect working operation and its possible related breakdown. The maximum outlet water temperature have not to exceed 55°C. As a function of the maximum input power and the consequent performance decrease in terms of C.O.P. outlet temperature of the water up to 55°C with outdoor air temperature up to 5°C are basically recommended. The water outlet temperature may be reduced for lower temperatures of the outdoor air temperature, this is according to the conditions of use, taking account of the consumption values indicated in the tables below for the maximum input power as a function of the outdoor temperature and the produced water. For higher temperatures than those pointed out, especially if have a concomitant with the reduction of the water flow rate, it may cause abnormalities to the normal operating of the unit, or the safety devices act in critical cases.
Temperature of produced water 55°C Model
Outdoor temp. °C Input (kW) Input (kW) Input (kW) Input (kW) + 5 2,25 2,95 4,84 5,42 ‐ 10 2,36 3,04 5,65 6,21
Temperature of produced water 50°C
Model Outdoor temp. °C Input (kW) Input (kW) Input (kW) Input (kW)
+ 5 2,01 2,68 4,36 4,96 ‐ 10 2,10 2,74 5,31 5,53
Temperature of produced water 45°C
Model Outdoor temp. °C Input (kW) Input (kW) Input (kW)
+ 5 1,79 2,42 3,98 4,58 ‐ 10 1,88 2,49 4,97 5,24
17.4 Ambient air temperature
The units are designed and manufactured to operate, in summer operation, with the condensate control, with outdoor air temperatures ranging between ‐10°C and 46°C. While operating as a heat pump, the admitted outdoor air temperatures range from ‐15°C to 40°C as a function of the water outlet temperature as indicated in the below table.
PACK DUE 7 PACK DUE 9 PACK DUE 12 PACK DUE 16
PACK DUE 7 PACK DUE 9 PACK DUE 12 PACK DUE 16
PACK DUE 7 PACK DUE 9 PACK DUE 12 PACK DUE 16
PACK DUE 7 PACK DUE 9 Input (kW)
PACK DUE 12 PACK DUE 16
34
Operation limits
Water chiller mode Ambient temperature Minimum ‐10°C Maximum +46°C Water outlet temperature Minimum +5°C Massima +25°C Heat pump mode Ambient temperature Minimum ‐15°C Maximum +30°C Water outelt temperature Minimum +25°C Maximum +55°C Heat pump mode for sanitary hot water Ambient temperature with maximum water temp. 48°C Minimum ‐15°C Maximum +40°C Ambient temperature with maximum water temp. 55°C Minimum ‐15°C Maximum +35°C Water outelt temperature Minimum +20°C Maximum +55°C
18 CORRECTION FACTORS 18.1 CORRECTION FACTORS: operation with glycol
Glycol % Freezing point (°C) CCF IPCF WFCF PDCF 10 ‐3,2 0,985 1 1,02 1,0820 ‐7,8 0,98 0,99 1,05 1,1230 ‐14,1 0,97 0,98 1,10 1,2240 ‐22,3 0,965 0,97 1,14 1,2550 ‐33,8 0,955 0,965 1,2 1,33
CCF: Capacity correction factor. IPCF: Input power correction factor. WFCF: Water flow rate correction factor. PDCF: Pressure drops correction factor.
The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation without glycol. The water flow rate correction factor is calculated in order to get the same temperature’s difference that would be obtained without glycol. The pressure drop’s correction factor takes into account the different water flow rate obtained from the application of the water flow rate correction factor.
19 DIMENSIONS
19.1 INDOOR UNIT
DIMENSIONS (mm)
MODELS A B C D E F G H I L M N O
91 55 80 40 88 245 56 70 190 93 515 816 270 PACK DUE 7‐9‐12‐16
35
19.2 OUTDOOR UNIT
DIMENSIONS (mm) MODELS
A B C D E F H
842 560 335 360 312 324 695 895 590 333 355 302 313 862 940 600 376 400 340 360 1245
20.1 INDOOR UNIT
• Remove the two screws on the bottom of the unit. • Remove the cabinet.
20.2 OUTDOOR UNIT
• Remove the connection screws connecting the top panel and the front panel.
• Remove the top panel • Remove the screws connecting the front‐right side panel.
• Remove the front right side panel.
Top panel
Front –right side panel
PACK DUE 7 PACK DUE 9
20 ACCESS PROCEDURE TO INTERNAL PARTS PACK DUE 12‐16
PACK DUE 7‐9
PACK DUE 12 ‐ 16
36
21 COMPONENTS OF INDOOR AND OUTDOOR UNITS
21.1 INDOOR UNIT
1. Electric box 2. User interface 3. Plate heat exchanger 4. Thermostat with manual reset 5. Thermostat with automatic reset 6. Safety valve 7. Flow switch 8. Expansion vessel 9. Pump 10. Heater collector 11. Manual air vent valve
21.2 OUTDOOR UNIT
1. Condensor coil assy 2. Fan motor support 3. Fan motor 4. Fan 5. Transductor 6. Expansion valve 7. Coil of the expansion valve 8. Compressor 9. 4‐way valve
purposes. 7 and is included for illustration
The outdoor units PACK DUE 12
fans.
Note: The figure refers to the
and PACK DUE 16 have two
outdoor unit model PACK DUE
37
22 WIRING DIAGRAMS
22.1 INDOOR UNITS
USERCO
NNECTIO
NS
CO
NN
ECTIO
NS
INSID
ETH
E UN
IT
EXPA
NS
ION
ON
-BO
AR
D U
NIT C
ON
NE
CTIO
NU
SE
R C
ON
NE
CTIO
NS
A1 Electronic controller FU2 Auxiliary fuse
A2 Expansion for solar kit (optional) KM1 Heater integration contactor assembly
A3 Integration resistance control panel/Sanitary boiler anti‐legionnaires KM2 Contactor for Integration resistance and sanitary boiler anti‐legionnaires
A4 Outdoor mono‐condensing unit QF General differential switch (not included)
BT1 Water inlet sensor for the plant R1 Plant integration resistance
BT2 Water outlet sensor for the plant R2 Integration resistance and sanitary boiler anti‐legionnaires
BT3 Sanitary water sensor for boiler TH1 Ambient thermostat
BT4 Outdoor air temperature sensor THS1 Resistance R1 of safety thermostat action at 80°C reset at 70°C.
E1 Circulating pump of the plant THS2 Resistance R1 of manual reset safety thermostat 110°C
F1 Water flow for the plant THS3 Resistance R2 of safety thermostat resistance
FU1 Integration resistance fuse for the plant YV1 3‐way valve for sanitary hot water
WARNING: For connection to outdoor moto‐condensing (A4) see the paragraph 6.5.1.1 The grounding of the signal cable to the moto‐condensing (E‐GND) should not be connected and must be protected from accidental contact with the plate: cut it or isolate it with special tape. The terminals to connect on A4 are: R‐ with P / R+ with Q.
38
22.2 OUTDOOR UNITS
22.2.1 Wiring diagram of PACK DUE 9
39
22.2.2 Wiring diagram of PACK DUE 12
40
22.2.3 Wiring diagram of PACK DUE 16
41
23 SOLAR MODULE (OPTIONAL ACCESSORY)
23.1 ASSEMBLY
A)
REMOVE THE FOUR SCREWS WITH A SPECIALSCREWDRIVER AND THEN REMOVE THE BOTTOMCOVER OF THE ELECTRIC BOX
B)
FIXE THE SOLAR EXPANSION BOARD IN THE FOUR HOLES OF THEELECTRIC BOX OF THE INDOOR UNIT AS SHOWN IN THE FRAME
C)
REMOVE THE FOUR SCREWS OF THE CONTROLPANEL WITH A SPECIAL SCREWDRIVER
D)
REMOVE THE CONTROL PANEL TOWARDS LEFT SIDEAS SHOWN IN FIGURE TAKING CARE TO THE WIRING
CONNECT THE WIRE OF THE SOLAR EXPANSION BOOARDTO THE WHITE TERMINAL NAMED EXPANSION OF THE CONTROLBOARD AS SHOWN IN THE FIGURE
42
23.2 WIRING DIAGRAM
8 7 56 4 3 LN
E2
BT6BT5
FU3KA1
QF
L1 N
230V-1Ph-N-50HzU-NPE
B A S E
EXPANSION
A1 WIRING DIAGRAM
A1 Electric box electronic controllerBT5 Solar collector probeBT6 Sanitary boiler probeE2 Solar collector circulation pumpFU3 Fuse of solar collector c irculation pump
( 5x20 T 1.6A )KA1 Relay for collector circulation pumpQF General differenti al switch (not included)
FU3KA1
key
LAY OUT DESIGN
B T6 S an ita ry bo ile r p robeFor the conne ct ion , use a cab le w ith a m in im um sect ion o f 0.5 m m and a leng thno t m ore than 50 m ete rs . For lengh un til 100 m a cab le w ith sec t ion o f 1 m mm ust be used .
U ‐ NS ing le -pha se pow er supp ly te rm ina ls (g roun d - live -n e u tra l)m ax. 1 .5 m m
For the conne ct ion , use a cab le w ith a m ax im um and m in im um sect ion o f 1 .5 m mFo llow the regu la t ions fo r the sec t ion of the cab le .
E 2 S o lla r co llec to r m ic roc ircu la tion pu m p
B T5 S an ita ry co llec to r p robe
PROTECTION PARTS
Q F G ene ra l d iffe ren tia l sw itch (n o t inc luded )
For the conne ct ion , use a cab le w ith a m in im um section o f 1 .5 m m
For conne ction , a cab le w ith m in im um sect ion o f 0 .5 m m m ust be used and a
For the conne ct ion , a cab le w ith m in im um sect ion o f 0 .5 m m m ust be used.
For the brea ker s iz ing p lea se respe c t the regu la t ion s and the po w er o f un it.
leng th o f 50 m . For lengh un til 100 m , a cab le w ith sec t ion o f 1 m m m ust be used .
TERMINALS ON THESOLAR EXPANSIONBOAD A2
5 ‐ 6
A 1 C on tro lle r boa rd BASE For the conne ct ion , use the cab le supp lied w ith the so la r expan s ion k it
3 ‐ 4
7 ‐ 8
Tel. 071.723991 - Fax 071.7133153 - Web Site: www.accorroni.it - E-mail: [email protected] Accorroni E.G. S.r.l. - Via d’Ancona, 37 - 60027 Osimo (An)