MPS-C 2000_0000067923.pdf

23
i s 6 .1-2 .8 -1 b Information and Instruction Guide for Type MPSC-2000 El e ctronic Trip Control Uni t ~=~<x M PSC-200 0 ABB Pow e r T&D Co . Inc . Distribution Systems Division AL 11 I N "pup (1)

Transcript of MPS-C 2000_0000067923.pdf

Page 1: MPS-C 2000_0000067923.pdf

i s 6 .1-2 .8 -1 b

Information and Instruction Guide for TypeMPSC-2000 El ectronic Trip Control Uni t

~=~<x

M PSC-2000

ABB Power T&D Co . Inc .Distribution Systems Division

AL 11 IN"pup

(1)

Page 2: MPS-C 2000_0000067923.pdf

C'ONTENT'S PAGE

INTRODUCTION 3

FUNCTIONS 4

SETTINGS 4

RANGE SELECTION 4

LONG TIME FUNCTION 4

SHORT TIME FUNCTION 4

INSTANTANEOUS FUNCTION 5

GROUND FUNCTION 5

CURRENT UNBALANCE 6

CURRENT SENSOR THRESHOLDS 6

INFORMATION FUNCTION 6

TEST FUNCTIONS 7

VOLTAGE INTERFACE MODULE (VIM) 7

SETTINGS 7

MPSC-2000 SETUP INSTRUCTIONS 8

GENERAL INSTRUCTIONS 8

MENULAYOUT 9

METERING SUBMENU 10

SETTINGS Si1BMENiJ 11

CHANGE SETTINGS SUBMENU 1 2

AVAILABLE SETTINGS 13

PASSWORD PROTECTION 13

RECORDS SUBMENU 14

APPENDIX 1 5----------- -

FIELD TESTING 16

TIME VS. CURRENT CURVES 1 8L?Nb ..CS.dad'W.iS .vY.t43147vr.M.4Ae2a45RaaYn~tii .ffiVG2

NOTE : This Instruction hook is provided solely for the convenience of thepurchaser, and does not purport to cover all details or variations in equipment nor toprovide contingency to be met in connection with installation, operation, ormaintenance. Should further information be desired or should particular problemsarise which are not covered sufficiently for the purchaser's purposes, the matter

(2)

Page 3: MPS-C 2000_0000067923.pdf

Al 1111PUMP

INTRODUCT I ON

IB 6 e 1 0 2 .8-1 bPage 3

The electronic trip control unit described in this publication is a solid state, microprocessorcontrolled unit, used in conjunction with a power circuit breaker to protect power systems . Thepower circuits being protected are typically 3-phase, with and without a neutral connection, 50 or60 Hz with AC RMS voltages between 20 8 and 600 volts . The unit will control continuouscurrents as high as 4200 amps, while ground currents may not exceed 1200 amps .

The MPSC-2000 trip control unit measures current to an accuracy of within 1% of the circuitbreaker rating. The Voltage Interface Module (VIM) option measures voltage to an accuracy ofwithin 1 °!o of the circuit breaker rating, and power to within 2% of the circuit breaker rating .

The trip unit is completely self-powered, taking the the tripping energy from the current throughthe breaker without any auxiliary power supply . A battery is supplied for programming the controlunit while the circuit breaker is deenergized .

The complete control of the circuit breaker is achieved by a system comprising :(a) current sensors, (b) an electronic trip control unit, and (c) a magnetic latch trip device .

The sensors , the electronic trip control device and magnetic latch are mounted as an integral partof the circuit breaker to pr ovide complete pro tect ion for overcurrent, short circu it and groundfaults . Internal diagnost ic circuitry is provided to determine and visually identify the cause ofcircuit breake r tripp ing , as overload , short circuit or ground fau lt .

(3)

Page 4: MPS-C 2000_0000067923.pdf

IB 6.1 .2.8-1 bPage 4

/' Of O!PUMP

1 . FUNCTIONS.

The electronic trip control device provides the following four basic functions :

1 .1 Protection Function

Foutbasic trip elements within the unit perform the protective functions :Longtime, short time, instantaneous and ground .

1 .2 Information Fun ct ion

An indicator (target) and an LCD screen display information for the tripping functions . The indicator shows ifthe device has issued a trip command . The LCD can then be polled to determine the type of trip . The LCD andkeypad buttons are used to determine the settings of the unit . Arid LED indicates self -monitoring functions .

1 .3 Test Functions

The unit can be connected to an external test set to check functions and settings .

1 . 4 Communication Functions

The unit can be connected to switchgear mounted devices if they are connected to ABB INCOM Protocol .

2. SETTINGS.

2 . 1 Range Selectio n

The range selector provides the primary amperage used as the base for the unit . It is either set for 1X or 0 .5Xthe breaker rating: Default is 1X .

2 .2 Long Time Function

2 . 2 . 1 Threshold (pickup ) settings- The range of s ettings is : A . SX to 1 . OX in steps of 0 . 1X . Multipliers a re used inconjunction with sensor rati ng and the range selecto r. Mu l tip l iers are selected by keypad i nput and d isplayed onthe LCD . Default i s 1 . 0X .

2 .2 .2 Trip Time -'dime is defined by long time overcurrent curves (graph) and intermediate values between bandlimits . Default is MAX .

2.2.3 Reset Time - Real time is counted up if the current exceeds the function threshold and counted down if the,current drops below the function threshold . Real time is set to zero if the current drops below the power supplythreshold .

2 . 3 . Short Time Functio n

3 .1 Threshold (pickup) settings - 2 3 4 5 6 7 8 9 10 "DISABLED" . The settings are multiples of the sensorstings and the range selector. Settings are selected via the keypad and the LCD display . If the "INST" function i s

disabled, the short time function cannot be disabled . Default is "DISABLED .

(4)

Page 5: MPS-C 2000_0000067923.pdf

/► Of ItPUPIP

!B 6.1 .2.8-lbPage 5

2.3.2 Trip time - Time is defined by the short time overcurrent curves (provided in the appendix of this bulletin) .lat function is selectable . 12t curves are fixed and do not vary with pickup settings . IZt is operational only from 2X to4X. Trip times with I'k out are defined as follows :

Maximum 0.350-0.500 sec

Intermed iate 0 . 200 -0 . 320 sec

Minimum 0 . 080 -0 . 170 sec

Defau lt is maximum with IZt in .

2 .3 .3 Reset time - Real time is counted up if the current exceeds the function threshold and counted down if thecurrent drops below the function threshold .

2 . 4 Instantaneous Functio n

2.4.1 Threshold (pickup) settings - 3 4 5 6 7 8 9 10 11 12 "DISABLED" . The settings are multiples of the rangeselector setting and are made via the keypad and the LCD screen . If the short time unit is disabled, theinstantaneous unit cannot be disabled . Default is 12 .

2 . 4 . 2 Trip time - There is no intentional delay in the instantaneous function .

2 . 4 . 3 The instantaneous unit includes a jumper on the circuit board which eliminates the poss i bility of instantaneousand short time be i ng s imultaneously disabled .

2 .5 G round Function

2.5.1 Threshold (pickup) settings - These settings a re made via the keypad and the LCD screen . Th is function maya l so be disabled . Default is

SENSOR RATINGS (A) SETTINGS (A) 1200 A .

100200 100 , 200 , 300 ,400 600,900, & 1200A600800

1600 30 0,400,600 ,2000 800 , 1000 , & 1200A2500

30003200 500,600,800,4000 900, 1000 , & 1200A4200

(5)

Page 6: MPS-C 2000_0000067923.pdf

1B 6 .1 .2 .8e1 bPage 6

AL ,6 INP%IPIP

2.5.2 Trip time -Thy time is defined by the overcurrent curves (provided in the appendix of this bulletin) . lyt functionis selectable . I2t curves are fixed and do not vary with pickup settings . If the i2t function is out, the trip times aredefined as follows: Default is Maximum with Izt in .

DELAY SENSORSSETTING 100 a 800a4 1600 - 2500A 3000 - 4200A

MAX 5 .2 - 9.5 SEC 0 .59 - 1 . 2 SEC 0 . 35 - 0 . 50 SEC

INT 2 . 1 - 4.2 SEC 0.24 - 0 . 47 SEC 0 . 20 - 0 . 32 SEC

MIN 0 . 68 - 1 . 3 SEC 0.07 - 0 . 18 SEC 0 . 05 - 0 . 17 SEC.v ~

2.5.3 Reset time - Real time is counted up if the current exceeds the function threshold and counted down if thecurrent drops below the function threshold . Real time is set to zero when the current drops below the power pickuppoint.

2 .5 . 4 Residual ground current - In a three phase/ four wire system , the ground fault functions can discriminatebetween a ground fault and a neutral current .

2.55 . Ground fault summing -Thy reset technique used for long-time and short-time function is applied . Real time is-counted up if the current exceeds the function threshold and counted down if the current drops below the functionthreshold . The ground function includes arcing ground summation for tripping . This feature allows arcing groundsoccurring sufficiently close together to be summed so that their magnitude will exceed the threshold setting of theground element .

'. .6 Current Unbalance

2 . 6 .1 Pickup settings [5% to 50%] in increments of 1 % and "DISABLED" . These changes can be made e ither viathe keypad and LCD or the NIM communications un it. Default is "DISABLED" . The current unbalance functi on isonly available for systems with VIM attached .

2.7 Current Sensor Thresholds

2 . 7 . 1 Longtime - 0 . 5X to 1 . QX of sensor rating in increments of OAX .

Short time - 2X to 10X of sensor rating in increments of 1 X.

Instantaneous - 3X to 12X of sensor rating in increments of 1X .

Ground- 100 amps lea 12 00 amps300 amps to 1200 amps500 amps to 1200 amp s

Depending on sensor rafs ng . See section 2 . 5. 1

2 .8 Information Function

' . 8.1 The information function consists of an LCD screen, a mechanical target, a light emitting diode (LED) and sixzypad buttons .

2 . 8 .2 The mechanical target provides indication that the unit has initiated a circuit breaker trip . Further informationabout the function such as the type of trip (LT, ST, INST, GND, I UNB, V UNB, or lli/) and the fault current is

(6)

Page 7: MPS-C 2000_0000067923.pdf

A It OfPUPIP

1B 6 . 1 .2 .8-1 bPage 7

2 . 8 .3 The target resets automatically when the unit is re-energized . Reset occurs within 2 seconds .

2 .8.4 The red LED blinks once per second to indicate that the MPSC-2000 unit is powered upend functioningnormally (self-monitor light) .

2 .8 .5 The red self-monitor light blinks five times per second to indicate long-time pickup and continues to do so untilreset .or. the. breaker trips .

2 . 8 .6 When the unit is powered up and the settings table has timed out, the LCD screen will display meteringinformation provided that the unit has enough line current to power up or is externally powered .

3. TEST FUNCTIONS

3 .1 The unit continuously monitors the condition of the microprocessor. Normal operation is reported by a flashingLED on the front panel . Upon failure, the LED will glow steadily .

4. VOLTAGE INTERFACE MODULE (VIM)

4 . 1 The VIM pe rforms the following functions :

a . Provides the phase voltage for remote d i splay .

b . Houses the electronics for pertorming the power, power factor and frequency processing basedon current data from the MPSC-2000 box .

c . Pe rforms calcu lat ions to determine vo ltage unbalance and und ervo l tage fau l ts .

4 . 2 If a VIM device is i nsta l led , the MPSC-2000 unit must b e connected to a NIM (Network Interface M odule)communications unit ,

4.3 If a VIM is i nstalled in the u n it , a cable connects the unit to the poten tial transformer located on the rear of theMPS -2000 mounting plate and plugs directly into the VIM board .

4 .4 Settings

4.4 . 1 Voltage unbalanc e

4 .4 . 1 .1 Pickup [5% to 50%] i n increments of 1% and "DISABLED" . Set via the front panel or the NIM commun ica tionun i t . Default is "DISABLED" . Connectio n to a NIM is necessa ry for this func t ion to be enabled .

4 .4. 1 . 2 Trip time [0 . 1 to 25.0] seconds in increments of 1 second . Set via the front panel or the NIM communicationsunit . Default i s 25 . 0 seconds .

4.4 .2 Undervoltage trip

4 . 4 . 2 . 1 P ickup [ 1 to 600] volts i n increments of 1 and "D I SAB L ED" . Set v i a the front pane l or the NIM communicationsunit. Defau l t i s "DISABLED" . Connection to a NIM is necessa ry for th is funct i on to be enabled .

4 . 4 . 2 .2 Trip t i me [0 . 1 to 25 . 0 ] seconds in inc rements of 1 second e Set via the front panel or the NIM communicat i onsunit . Default i s 25 . 0 seconds.

(7)

Page 8: MPS-C 2000_0000067923.pdf

I B 6.1 .2.8-1 b AL It ItPage 8

,i

~* .:.'. n• : ; ' X :. : ~ .

5 . MPSC-2000 SETUP INSTRUCTIONS

5 .1 General Instruct i ons

5 .1 . 1 The front panel keypad cons is ts of four directional arrow keys , a cancel key [C], an enter key [E], and an LCDw i ndow .

5 . 1 . 2 When the MPSC-2000 unit i s connected to a power source, an init i al title screen is displayed in the LCDwindow. Th is screen d i splay i s rep l aced after approxima te ly three seconds by a setup screen . Subsequent MainMenu screens are accessed by press ing the °' E" key and the up and down keys (see Section 6) .

5.1 .3 Each Main Menu has a Submenu, used for entering and displaying values . These are accessed by pressingthe "E" key while in the Main Menu . The up and down keys are used in the submenus to display the desired type ofvalues or settings and the "E" key is pressed again to access these . The up and down keys are then used to scrollthrough the settings.

5 .1 .4 Pressing the "C" key in any screen will backup the display to the previous screen .

(8)

Page 9: MPS-C 2000_0000067923.pdf

„ It 11 1B 6 e 1 ,2.8.1b

PUMPPage 9

6 . MENU LAYOUT

6 . 1 The following layout shows the Ma i n Menus and Subm enus accessed by pressing the " E " key and the up anddown arrows . To exit the submenus and return to the Main Menu, the "C" key should be pressed .Far layca uts.of the submenus , refer to sections 6 .2 through 6 . 5 .

INITIAL SCREE N

MPSC-2000Ve rsion 1 . 0

SUBMENUS

Press °'E" (or wait 3 seconds)

la : ## lb : ## "E" =--=11AA l IV MENU== :Metering Men u

"Iwodress "Up and

Ar rows"

METER MENILoad Values

fee sec 6. 2

This screen is displayedwhen unit has power andMPSC-2000 screen has

"timed~p out"====MAIN MENU== :

Show Settings

Press "Up andrrowseeA rrows"

====MAIN MENU=:Change Setting s

Arrows"

====MAIN MENU====Records Menu

=SETTINGS MENU=~ MPS Settings

See sec 6 . 3

••E"' ==ChiA1VGE MENU== MMPS Settings See sec 6.4

••E . . = tECORDS MENU= Seesec 6 . 5

MPS Fau l t Event

(9)

Page 10: MPS-C 2000_0000067923.pdf

1B 6 a 1 .2 ,8-1 b ,,' I* itPage 10

P% 19

6 . 2 METERING SUBMENU

SUBMENU

===METER (VI EPJ U-~= Press ,• E •' ==LOAD VALUES==Load Values la: ###

Press "C ••WIMI lb: #

Ic :In :

an : ###Vbn :Vcn : #

These Vab:###values will Vbc:###not be Vca: #

Press displayed if a KW3p: ###"Up and VIM is not ICi/Ar3p:Down" attached KVA3p: ###A r rows iCVVf-ir3p : ###

KVarHr3p :PF : ###Freq : N/A

===M ETER MENU===M=3 Press ,•E•" =DEMAND VALUES=Demand Values la:

Press. .CIO

0.J . I.7.'f.f."f•I.'

T99PlfIc:These In :

values will ~~p:not be KVAr3p : #

disp l a yed if a KWHr3p :VIM is not KVarHr3p :attached

KEYPAD INPUT SEQUENCE FOR METERING SUBMENU

Press keys in this sequence to access me tering submenus .

la: lb :Ice In: # 8

Defaultscreendisplay

Scroll up and downusing arrow keys

= LO A D VAl6JE5=ass :

==s AAE TER AAE FilJ y=Remand VaMe a

L

(10)

Page 11: MPS-C 2000_0000067923.pdf

Page 11PUMPP

6 .3 SETTINGS SUBMEN U

SUBMEN U

=SETTINGS MENU=MPS Sett ings

Press"Up andDown"Arrows

=SETTINGS MENU=VIM lettings

Press "E"

Press "C"

=SHOW SETTINGS=Rating :

LT Pickup : ####LT Delay : ####ST P ickup : ####ST Delay :ST Curve :INST Pkup : ####GND Pkup :GND Delay :GND Curve: : #Test Crv :Dmnd pn8u l :I Unbal : ####I Unb Dly :PASSWOR D

Press "E" ==SHOW VIM SET==V Unbal :

Press "C"

0/ Unb Idly : #~#UV Pkup : ###UV Delay : ###Dmnd inhr l :

Scroll up and downusing arrow keys

KEYPAD INPUT SEQUENCE FOR SETTINGS SUBMEN U

Press keys in th is sequence to access Settings submenus . =sr,owsemNGS=~e.eng : 00"

Defaul t

iIn: displaysCPe @ n

=SHAW V IRA4/ Unba1: 0

(11)

Page 12: MPS-C 2000_0000067923.pdf

1B 6 .1 .2-8-1 b AL It 16Page 12 PUMP

6 . 4 CHANGE SETTINGS SUBMEN U

SUBMENU

-CHANGE MENMPS Settings

P ress"Up andDown"Arrows

==CHANGE MENVIM Settings

••~`~ =ENTER PASSWOs s a p

Preis °° C"

ENTER PASSWC

~9= w e e A

P ress "C"

V tJnb D i y : 9#UV Pkup: ###UV Delay: ###Dmnd Bntvl : ###

6.4 .1 To change settings PRESS "E", (an asterisk will a ppea r afte r the setting) TOGGL EBETWEEN SETTINGS USING LEFT A ND RIGHT ARROW KEYS, PRESS "E" TO ACCE PT,

THEN PRESS •• C " .

:ESA "E" TO CHANGESETTINGS

trol l up and downusing arrow keys

PRESS " E " TO CHANGESETTING S

Default KEYPAD I NPUT SEQllE NC E

screen -CHANGE SETTINGSd isp l ay Press keys in this sequence to access change settings submenus Rte :

la: lb:1c: on :

--CHANGE MENU—VIM S6lting8

E

See instructions below forchanging setting s

sec. 6 .4 . 1

"E,• =CHANGE SETTINGS PFRating :

IT P ickup : #### LTDelay : ####

ST Pickup :ST Delay : ####ST Curve :INST Pkup : ####CND Pkup : !#GND Delay :GND Curve :Test C ev : ####Dmnd IntvB :I Unbal : ####I Unb Dly: ####PASSWOR D

==CH(VG VIM S~V Unbal :####

E

=C FI NG VIAA SET==

V Ufl baL

(12)

Page 13: MPS-C 2000_0000067923.pdf

A It ItPU. IP6 . 4.2 Available Sett ing

The following i s a l ist of choices for each setting in the "CHANGE SETTINGS" Submenu-,

MPS SETTINGS

I B 6 .' i .2 .8-1bgage 1 3

LT PICKUP- 0 .5X, 0 .6X, 0.7X, 0.8X, 0 .9X, 1 .OX Sensor rating .LT DELAY! MIN, INT, MA XST PICKUP: 2X, 3X, 4X, 5X, 6X, 7X, 8X, 9X, 10X, 11X, 12X Sensor rating, and "DISABLED" .ST DELAY ; MIN, INT, MAXST CURVE : DEF, 117INST PICKUP : 3X, 4X, 5X, 6X, 7X, 8X, 9X, 10X , 11X, 12X Sensor rating, and "DISABLED" (if "INST" disable jumper isnot blocked for certain protection schemes) .GND PICKUP : See ground sensor table, section 2 .5 .1GND DELAY: MIN, INT, MAXGND CURVE : DEF, iITTEST CURVE : LT, ST, INST, CN DDEMAND INTERVAL: 15, 30, and 60 minutesCURRENT UNBALANCE : 5 to 50 percent, in increments of 1 %CURRENT UNBALANCE DELAY: 0.10 to 25 .0 seconds in increments of 0.1% and DISABLED

VIM SETTINGS

VOLTAGE UNBALANCE : 5 to 50 percent, in increments of 1 %VOLTAGE UNBALANCE . DELAY : 0.10 to 25.0 seconds in increments of 0.1% and DISABLEDUNDERVOLTAGE PICKUP : 1 to 600 Volts, in increments of 1 voltUNDERVOLTAGE DELAY: 0.10 to 25 .0 seconds in increments of 0.1% and DISABL EDDEMAND INTERVAL : 15, 30, and 60 minutes

6 . 4 .3 Password Protection

I f a password has not been programmed into the unit, the PASSWORD screen can be bypassed simply by pressing " E ° .

To enter a or change a password follow the steps below :

1 . Scroll down to the PASSWORD screen in the CHANGE SETTINGS Submenu, press "E" .2. Using the UP and DOWN keys, scroll up or down to the desired letter or number, press the RIGHT arrowkey to move to the next space and select the desired letter or number, repeat for the remaining two spacesand then press "E" .3. You will be asked to verify the password change . Retype the password to verify and press " E" .It will be necessary to enter this password to gain access to the CHANGE SETTINGS submenu from this point .4. To change the password just repeat the above instructions . To erase the password, thereby defaulting backto the original unit setting, program blank spaces in the CHANGE PASSWORD screen .

If a password is lost or unknown, call your local service center for further instructions .

(13)

Page 14: MPS-C 2000_0000067923.pdf

I B 6 . 1 .2 .8-1 bPage 14

6 .5 RECORDS SUBMENU

SU B M E N U

=RL I.i0DJ ME eYU- A'" re. s"C"fiAPS ,R u" Even t

Press "Upand Down"

Arrows

=MPS FLT EVENT=Event : #l#

Type :Ticks : #l a :Ib : ###Ic : ###In : ###

=RECORDS MENU= Press "E," ==BREAKER OPER= =Breaker taper. Coun t :~

Press "C"

KSIa :Ka l b :KSIc:

=RECORDS MENU= Press ,• E •• -9/114A FAULT EVENT=VIM Fault Event Type

: Press "C" Vab: ##fi

i/bc : #i/ca :

KEYPAD INPUT SEQUENCE FOR RECORDS SUBMENU

la :In : #~

BREAKER oaExC a urk:

-VIM FAULT EVEMT*Typo: APO

/► it INr9L,PIP

Scroll up and downusing a rrow keys

mo ms FLT saeErmrrt: 0

(14)

Page 15: MPS-C 2000_0000067923.pdf

Al t! ItP%lp,p

APPENDIX

1B 6 .1 .2 .E-1 bPage 1 5

FIELD TESTING

(15)

Page 16: MPS-C 2000_0000067923.pdf

IB 6 . 1 . 2e8-1 bPage 1 6 /, 1! t!

PUMPPROCEDURE FOR FI ELD TESTING THEM PSC-2000 S OL ID STATE TRIP SYSTEM

There are two ways to evaluate the MPSC-2000 solidstate trip system : primary current injection through thebreaker main contacts ; and secondary current injectiondirectly intoAhartrip device. Primary injection has theadvantage of testing the current sensors and magneticlatch also .

The following is a procedure for performing this fieldtesting .Notes :

1 . Refer to time current curves TD-9651, TD-9652 andTD-9653 (also in this appendix) .

2 . When checking calibration, disable the functions notbeing tested, or set them at their highest threshold anddelay values . It is 2SeeC laOly tEportant to disable theGround -function when testfng the other elements toprevent false tripping.

3.3he circuit breaker must be closed before each testbelow.

4 . Following each test, check the MPSC-2000 eventregister , to ensure that the correct element tripped thebreaker , especially if test results appear to be incorrect .

section .5 and 6gin the main 'body of th isinstruction bulletin for instructions on setting the MPSC-2000.

6. These procedures are written for primary injection . Ifthe trip device is being tested by secondary currentinjection, use a special test cable available from AFBand follow the special instructions contained therewith .

Instantaneous or Short Time Threshold Test

1 . Either disable the trip elements not being tested, orset them to their highest threshold value . Set the LongTime Delay to its maximum setting . Set the Short Timedelay to its minimum setting for Short Time tests .

2 . It is recommended that the Range Selection be set toits lowest value to minimize the current required for thistest; however, it may be set to either available value .

3. Set the threshold and delay of the trip element being.ested (again, it is recommended that a low value beused) .

4 . Test for the actual threshold by increasing test currentuntil the breaker trips . It is important to increase thecurrent fast enough so that the breaker will not betripped by the Long Time element prior to completion ofthe test.

5 . The threshold tolerance is +/- 10% on all selectorswitch settings .

Long-Time Threshold Tes t

1 . Either disable the trip elements not being tested or setthem to their highest threshold value .

2 . It is recommended that the Range Selection be set toits lowest value to minimize the current required for thistest ; however, it may be set to either available value .

3. Set the Long Time threshold . Set the delay to itsminimum value .

4. Test for the actual threshold by increasing test currentuntil the pelf Monitor light begins to blink quickly . Thebreaker should trip about 8-13 seconds later.

5 . The threshold tolerance i s +1- 10% on all se lecto r

Long-Time Delay Tes t

1 . Position other trip element selectors at their highestthreshold value .

2. It is recommended that the Range Selection be set toits lowest value to minimize the current required for thistest; however, it may be set to either available value.

3 . Set the Long Time threshold to its maximum setting .

4. Set test current so that it represents three times (3X)the trip system Range Selection setting . Delays shouldbe as follows :

Long-Time Delay Bands

Delay Setting Delay Times (sec . )

iVline 8 - 1 3

--- - - ------------------- - -------

Int. 20 - 33----------------------------------- -

Max. 61 - 100

(16)

Page 17: MPS-C 2000_0000067923.pdf

„ ,! ! IS 6.1 .2.8-l b

~7,li 1 pago,rshort-Tim.Delay Tnt

1 . Position other trip element selectors at the ir highestthreshold value.

2. It is recommended that the Range sel ection be set to, .its lowed va lue to minimize the current required for this,test; howdver, it may be set to either available value.

3. Set the ST Curve to DEF.

4. Set the ST Pickup to its lowest setting.

5. Set test current so that it represents four times (4X)

Short Time Delay Bands (11T)

Delay Setting Delay Times (sec .)

Min . 0. 160 - 0 .250

Int . 0.520 - 0 .780

Max. 0.910 - 1 .350

Restated from 2 .3 .2

Short-lime Delay. Bands (DEF )

Delaysing Delay rimes (sec .)Min. 0.080-0.170

Int. 0.200-0.320

Max. 0.350-0.500

6. Set the ST Curve to IIT. (Note that the lit function ofthe MPSG2000StioitTime e lement is operational onlyfrom twice to four times the Range Selection , and thatthe t rip curve is fixed and does not vary with pickupsettings. ) .::

7. Set test current so that it represents 1 .5 times the STPickup setting . Delays should be as fialbws :

Ground Trip Delay Tests

Ground Trip Delay tests_are performed by injectingcurrent through a single phase of the breaker, whichappears to be a ground fault to the trip device. Onbreakers with 4wire ground . on - double-endedsubstations, a remote neutral sensor must be used fioperform this best.

1 . Disable the other trip elements or set them at theirhighest threshold value.

2. The Range Selector has no influence on groundsettings.

3. -Set the GND PICKUP to the min imum ava ilableg round setting .

4. Set test current so that it represents three times (3X)the GND PICKUP setting. Delays should be as shown inthe chart below.

Restated from 2 .5 .2

Ground Trip Delay Bands (DEF )

De lay Sensor RatingSetting 200A - 800A 1600A - 2000A 3000A - 4000A

M in. 0.68 -1 .3 sec. 0.07 - 0.18 sec. 0.05 - 0.17 sec.

Int. 2.1 - 4.2 sec. 0.24 - 0 .47 sec. 0.20 - 0.32 sec .

Max. 5.2 - 9.5 sec. 0.59 -1 .2 sec. 0.35 - 0.50 sec .

(17)

Page 18: MPS-C 2000_0000067923.pdf

IB 6.1 .2 .$•1 b Figure A-1 a Trip Times with 12t Enabled ("IIT" or "IN ")Page 1 8 See Figure A-1 b for a larger scaled notes section

_ .. a '~Y,j anac tn~v._st cm : .-1 - - -t Trip Y,xn. es ii- M-

_y.'i. . Response W ,4n ,7 1t Pnn~ : Dikf. 4Wa _'DEr or -OUT")MP SC-2000. M P$- g a,.Tl and MAw C- 5f iFlST,Sd .LT 3

_ • ...• NC4C 1~ INS bq la j,100h :a etxcls it+ e 0r7 Iam- ,esyr, ..11 ;wt F't t n7 ~~ ~ .e ~'i _rn-ac :rtriflK . :n enaC feA pr o f w), 'ne n reie c If o y'- d uacl"O m .yie d 11 .A . 11 µ9

+ . ~ . ~ . . _ . . System . IN- .16C fete lp :~rnc •~ : . . ., ti 'D- 9 652 10r i~~~ ry 1 ✓ : n ~v .

NOTE Bne~ curves ore, !9i 5 z s ri1 em II

A t f ~p lUIlGtepll AOl IQO `! .-.n : h a~p ff IFt C O ~i~3 ✓= ~~) ~~^ ^ Y~~f MlR .

;fir, ~ L~^Pd~,-TI M E GU :PV ~9, cd ebrotea for o tc+o6 .ra 6u ~e roe. ;t of J ~~~',; rr.ea¢t aTe Ir am n ~,:~c~N n 50 meAVAll,ABLE S ETTIN GS m ac~m+,m

0. 5 . Q .$ . 0 iQ 8 0 .9,NOTE 3 For bnr I- bond. the I.- -J vCpe . hm~1s ae m . • : ! :me IntrYti err !~~„~qar1~ r 0 7sMES THE whch r ~N

'grrNG CURRENT, o~aur at a gr.en re,. dGple of o(-*q e,,•am, if --,M -,.d, ir . :H ;r tn,vv+Nd Ohal m euAfl .C .trip the brNMp by enea n3 ~ I h0 hyt on l~a c aUS_ Y .G~':. -• z3 111j,, t he

1 'Jx) RlS T tMresho b but areoiv the, 90% w in r. 5T tin . ~ o`-i f , o . p I> irn b.e .x P. ..' S i band hmal . t he n the and e~~l trip t he o r~we to u qn ono i nxi t~.nc nct a c•mem

grrole . thpK the ihe Lt threshold c~f wss tn,~ iox at hx o dyeu t8 ~t ~-(-t - L")N('-7WE BAND the Ioaw et bond 1-4, r" m- ai !-,p

rr UPPER LIMIT5_:-f NOTE lk Use t hg cxcuil Megka o ry r

t'

.• r G^^e!' v'1 u e-t r,IMy jnc e OR tripJCS i SEE N OT E 3) v osue5 oe e ieiecfabw tier Ick tkc Lira a nir ..! y y~ ,swr ,y0eem

NOTE S. The anslonionkous. -e. and q .ou~ I : y. p~nq 1unc' .an< u .r~ I, rdeF,¢n de ntly.tip }n.eahW3s Olt se as of q a,. ~ enro ~

rI! i^~~1G -'~Mk 84P1'J L, cr tb Ox >' Ini f ~s r n /~lE ~ .d CJA h l 01e11 .et ;l flresn NI 1 .14F 111a e (,L) 14`t (i) s . ene .7 t , u. rh.nLOW t'F LIMIT. SOE al~~q at 4Crv 11 ts tn c

PI

=i Q

J iJ

1-J t

L .J

-~`

`1 J..t .-~.

~~ . . .. a ....

Qty I[.-_ A l °7

E E N ',I= E a'e

Ci . + t-t - ~---

~

~~ EE N ~ TF 3)the ih~csro ids ? ,c ~c0~ ~ n~ a d 5C a <s : .c!~vNy . undo a re ; h -01,d mM ;hekn:.w :rq ~w1-n . s ttLr,s n esv : .. rye , difl-

~. I. I ~^ ameM r _ i•x _ .ry Sni r ~

Rol :nq' Cu ~.4r,1 °. s scam . .a t ..~ qT m Go~~ ~~

i~s to~ :eneou s 12 x

Snot-ti n,. q ;(

-~ L-3 _iima 1%. . . . . . .

urauM tL ni m~n ~I.. ._.

J NG?E 8 . A, nlia b i• e~l .ng s al , r3,"'d 7 :10 sYS I<m the 4260 . fkt+M19 •.l %I a :~pSi ewin K-1- C~t~~t• ; ~

Trio R't,j, T,.4 It

cdo 3e c,. u ric- 2 coa. .y is .ond :n ,?n r.860 a a ~ vJ

1 6 9G 3(hO t 6tX'. .

2000 'Co ~ O~cl 3000 i 5 K C 0

:.. . _. 7_0016x. .1 7Qi74000 41)00

4411Y L

LO N G T l p.iED EL?Y 3k n G

1i~N '0.1U P.1

a a LaGLE SET i i :'o . '7 3 4~ . , .~ . i C 71 b:E~ TH ' RA r l p: :-:URR c NI . O R DEFEATED .(SHOWN $0 2,( AND 11,X )

FT- T~

AM EE~ 4v 6AtJ~ S

L9l+.Y 11,1 i: l hi

NT f U UED :a TE

TT

I'

.

~ ;

-- -

04

F ' .TE

--+-

AVa l.AE :E SE'l ; N GS :3, 45 6, 7, 8 3 TO . t i t TIMES THER IN. J R kEn I (S r 4nb+,Iy ~ a t AND i27f )

CLE A RING Tl S9P-_ WITHINSTANTANEOUS TRI P

r 7 '~ -'~ v V If1 .. hW0^~. U . t3 .~ O YJ C~C~Q .- Q O ' Q ".a C3 ~.. N M v J~ „n .~^~ o aa~ c oq3~

::J r'Y ♦ ll118. h1

k is ~ PlrS THRESHOL D_

- M i,L" :PLC OF R A,.jr

IG CIJ4 AEN T

..-•--------

~ -- . .. ._ . .__ . . .!rip t , r S T b t j f ~, ed t "GC or"01-IT"',

TM `, gf ~ h rn ~rA ga r.?S Ire f III vee n~ i w vO7ge b r eok e~ s .

k-Lire Plus . K_. i n g , h bo n . { 1 4 , ~1 P, l.f3v, AAF E Lk L K !) , on~LY4E

~ ru r= ~ ,n c ~aocre

T~! ~ J ~1

'~ . .

(18)

Page 19: MPS-C 2000_0000067923.pdf

IS 6.1 .2 .8-1 b

ANIM111 Pog.,s--~

Figu re A-lb larger scaled notes section from Figure A-1a

Response With ST 12t Behavior Defeated ("DES" or "OUT")MPSC-2000 : M PS-C-3( I NSTIT); MPS-C-4(ST .LT) ; and MPS-C°5(ENST,d7,6T)

1 : This log-ooq~r~ph depicts the short-time response without Izt behavior . It the p`t choracteriis enabled ("I!T" or "IN"), then refer to TD-9653. If a ground function was odded to the tripsystem, then also refer to time-current curve TD-9652 for ground response .

2 : These purr?, are typical of single and three phase power functions for 50 ;'60 Hz systems. Ifa trip function is not available on your unit, then ignore the corresponding curve . Curves werecalibrated for a temperature range of 10-40 'C. The reset time for any trip function is 50 msmaximum .

TE 3: For any time band, the lower and upper limits define the time interval for which tripping willoccur at a given ,multiple of rating current . If current exceeds the INST threshold, then theunit will trip the breaker by means of the instantaneou s-Function . If current less than theINST threshold but greater than 90% of the ST threshold persists for a time up to the lowe rST band limit, then the unit will trip the breaker through the short time lunation . If currentgreater than the the LT threshold but less than 90% of the ST threshold persists unti lthe lower LT band limit, then the unit will trip the breaker through the long time function .

4 : Use the circuit breaker only within its published short circuit current rating . Since, all tripvalues are selectable, they must be chosen to match the requirements of your power system .

5: The instantaneous, short-time, long-time, and ground tripping functions operate independently .Trip thresholds are set as multiples of the rating current . The rating current is e0he r50% or 100% of the trip system rating . EXAMPLE : An 800A K-Line breaker is set at a50 % rating of 400A. If its threshold multipliers are (12) INST, (5) ST, and (0 .8) IT, thenthe thresholds ore 4800 A . 2000 A, and 320 A. respectively . All units are shipped with thefollowing factory settings (unless ordered differently) :

Pmrameter Factory Setting

Rating Current = X 50% of system ratin gTime Bond Minimum

instantaneous 12XShort-Time 4XLong-Time i xGround Minimum

6 : Available ground sett i ngs and trip system compatibility (Note : the 4200 rating is not availablewith K -Line breakers):

Trio 5ylttrn Rating

(Amps)2OQ600800160020003000320040004200

Rating Current

(Amps )100 . 200300, 600400, 800800, 16001000, 20001500, 30001600 . 32002000, 40002100, 4200

Trip System Compatibility

MPSC-2000 V1 .5 and higher

(19)

Page 20: MPS-C 2000_0000067923.pdf

IB 6 .1 .2.8-1 b Figure A-2a Trip Times for ground fault functions ,,LPage 20 See Figure A-2b for a larger scaled notes section

600 05G00

400 0

30b 0

2000

100 0

0 00500,400

30 0

, ::. . . ,. . . . . . . . . . . _ uu

6 0

5^ 40QJ : . . 30L'i

20', L7

t~l

q. . 1Q

4

L . .

ga

7b5

a

. 3

U6

04

03

0 2

IS Current For NpS .C E~cct ronic Trio SystemslsKOUfdD FAULT FUNCTIO N

t1F t, ek . ..i, - $( tNST LT) . AtF5-C-1 ( S7,LT ) . and MPS-C-5(e NS Y. SL. 1,7 )

NOTE 1 'ha x-,eq y opn of ground response supplements TD-9651 and PD-9653,

'na5i. 'e typical of a-n ryleand three p»gsapwwe r (unctions for 56f60~i' B~vzma. 2u,vcs were c olibrated fo r a: temperature range of 1:0 - 40 'C,The mq ., mum rose( time to a ground trip is 50 ms .

NOTE ? : F :f Q~y ; ;m t lb o nl the brier and . upper lirtiits define ine (,'Me intervol for which?•iprKn y ~, .zieca* of a gi ven ground current : It a gcound(oOlt kxtQ!ds thege+•..ns. ?ru ssrc~~ or t~r>yGC than the co rer t ime . bond limit then the unit will'1-0 tti e : tl taYer by me orts 4 the ground function :

NOTE a. U Se the -cmt p, euk er o nly rithin i ts published short -circuit current, rating., .. ao In p rabu es ye se !ectaY l e , they mat be cficxnto makfithe

re ~!'; reme ms at YOU, Power system .

WE 5 A, a aube z g ^ura setGnu s orM trip systam c gmpqt ibe aty {Nate : the 4 ?00 rOting, rpt. .; xdh K- i,Ine bredkers)

,,. .. irro S,r3"• Ra~_~ . . . Are+sbk ]~;;~; nd ,S ej tn~ :Teo S vstekiConiouAitiifi6v. . . . . . .111

rA- ps )

1 00 Yr,O . 3 M HJG . 9G0, 12 0 0rii0 CG. 200 . 300. b CO . 9v0 . i2!Nl v ?1C d 2A06 V t 5 and higher

ya . 2K 300, eao, e00 . i 2ec1 60p ,•'p. 400, 500 . 807 . 090 . 1MrG No. 400 . 6 0+], 300, 1000 . 1290

:~ooc 500 . 600, acc, moo . loon, 12GO3 2C: 4 560 604). X 60 ; 900, i !AC, 1 200 . . . .4 0C0 SCO . bCO. COQ . 900. 100C, 1200

0 5C :7 . E Ch^,. 900 . 900. !OOq . 1200

CF 'V SEt I SHOW Nri n -SSE vT ItACij ra 5OK11 wTH T H

E NA 6 L .J a r " OR iN' ;, SEE ru~1E Sifff

- ` vR OUND =FITTI NG SNGWN SET AT ~~ COa as iTr~ r- 7 CEr~ aTgp

., .~~ T" ~ SEE NOTE S i

~, i i l l I I i t ~ G I

UPrER BAND LIMIT

SEE NOTE i )

TIME QELAY

MAXIMUM

INTERAI FOIATE

~ NINIMUAI.

!.. :-•4gA SAND L.IMiTi j (SEE NOTE, #)

I I H I 1 - 1 1 1 1isakl Ii Lrl II 11, 1 I I f!!I9III iU1 ,.p OM'- tv fq ♦ v++D~mi7*o or 00ob Q .

cD Ci 4 O O „~poN f~9 V in ID hdljO~$ . . .

NM in ~nIXIC I

TPIPPING THRESHOLD MULTIPLES OF GROUND CURRENT

(AMPS X 100 )

-- -i r ~5 y Q h ~epreseirts t he f ii,, x ;i,,~ ~cN v ~l k•~ge '!re:K- - C,ine P lus . K- Line . K - -0 c_r K .',/4 . M 6 . Mt6J 12E ~L K p . No . T L .~ ,y _ 9 {-~ 5 °and LKE 6.=° w

(20)

Page 21: MPS-C 2000_0000067923.pdf

AL t! t!rUrIrIB 6 .7 .2.8-1b

Page 21

Figure A -2b larger scaled notes section from Figure A-2a

GROUND FAULT FUNCTIO N

MPSC-2000 ; MPS-C-3(INST,LT) ; MPS-C-4(ST,LT); and MPS- C -5 (s N ST,51',LT )

t : This log-log graph of ground response supplements TD-9651 and TD-9653 .

2: These curves are typical of single and three phase power functions for 50/60Hz systems . Curves were calibrated for a temperature range of 10-40 'C .The maximum reset time for a ground trip is 50 ms.

3: For any time band, the lower and upper limits define the time interval for whitripping will occur at a given ground current . If a ground fault exceeds theground threshold for longer than the lower time bond limit then the unit willtrip the breaker by means of the ground function .

4: Use the circuit breaker only within its published short-circuit current rating .Since, all trip values are selectable, they must be chosen to match therequirements of your power system .

5 : Available ground settings and trip system compatibility ( Note : the 4200 ratingis not available with K-Line breakers) :

Trip System Rating Available Ground Settings

(Amps) (Amps)200 100, 200, 300, 600, 900, 1200600 100, 200, 300, 600, 900, 1200800 100, 200, 300, 600, 900 , 12001600 300, 400, 600, 800, 1000, 12002000 300, 400, 600, 800, 1000, 12003000 500, 600, 800, 900, 1000, 12003200 500, 600, 800, 900, 1000, 12004000 500, 600, 800, 900, 1000, 12004200 500, 600, 800, 900, 1000, 1200

Trip System Compatibilit y

MPSC-2000 V1 .5 and higher

~ ~

(21)

Page 22: MPS-C 2000_0000067923.pdf

monkIS 6 .1 .2 .8-1 b Figure A-3a Trip Times with ST 12t enabled ("IIT' or, M) 'Page 22 See Figure A-3b for a larger scaled notes sectio n

IE0005Ci49

4000:

3000

2000

1,000

70fr600500

400

200

706050

40

3i)LJ

F- O ;G

L7 L'

6

a

3

q

2

5HU R7 -TIRfE BAN D

1.C'7dE R I. V?{SEE. N G ! :E 1).

Respo nse . ~En ST i7t BMw~ or E~n eeMe CST' a W)MPSr;-20GC ~rS-C-3i WS*.lt)! M VS-C-r(ST :In: and MP5-^' S(tNST.Sf .L' )

iiDte r! n : * i ),wM 1 n m ow s~it-t~.a JV ar~ if in e .?t zerI r,,;e.cedeaN i ~n' a •an•) ~+ ,.~« ~a m-?65' a qro~ ~~:~•~ .m a+aen to

t.p s~ ¢iam . Inm qt, . de . to tav w-tw.MC. swta 1` 0 -Q6SY to, gro -n ratio, :°e

rdfiC 2 t^e . ..re ae tip-1 ~4 a x p. WW he" M ww tia+a 1-6," is 1$0, !4R '+r e,pimsa top sun etan v nW woaot+e m year Wy, Th" q" OF Caneopen0+q cw.e . iu. .es ••cwWxUd la a lirnppal- rongr el 10 410 Y . TM vtad , t +ne 1. pq top fu,!- 5,'. n+a

PO7f }_ Far eny Inno pgidtM bwe KA :gqar "N ts lm IM 6Mf mkaVel inr =;pprrN] i:eai W a grw« muk ipNW rg vq cw pt M cwrenl orcutdtIhep151 (e(h~ 'z

E l . 0 1 U p 1h a Maokw by - cl h vylenleim~u I tlew r Iq~( b . iMnIn e¢M10 #ot yipM then 9f M NST!r e the ST "c'..

5S ppgA NQ. th an ih a :e M w! top It, Dre.* a I Mey(M 11w tvl Lm 1 :tun Y' ~Wetn ig lhqn the tM i f ; NeNt 4 p~,t I., 1" Apx 0 .M S f= l ~ ~fh d0 pt+ r5 1S uM t` !fo.

MMaLi band !.'vi+i 1. lb- tM uMt M a ny IMb MKp lNOwgh IM bn I+n .. tuncuon

NOTE Y Uae MF t +cwl, b*OW oM/r wRho it, puSHMd di/iort, nrtuA' e- ! edk q: S ee., am e. .owSuN a e aN cfdble: They *wfl be cM Un ! a ~A !Ae verypee-6 y Y_ Yo+e ~ syie~.

NOTE 5 7M instant-o0 +M:! irwe . o ^9 'I:.~e xM grauM NpP+W Iw ciiqu W„nl< antlroG^d enis ~1 b ~hiiHMla a e iie1 ~ndi p'n W ur ~ a1m9 ~~ T1K r eiv~9 cw~e e is ptAe.Scx a X00 01 Ine I1r C lem rdM} :Me u YtE An 900 K -lina:.Owe len q ff l of a31.1 rat4 I cxA K i . tnn snow .wpyw « . M. (12) tlvSF . (S) ST . 9qd (O,A{. LL. MENtM 'n. n~ z we 4&W .1 20W h oad 17 J ^ ~s?ac1^~cM M uhf uro iJnewd z*tnErw-a i~irr .<nMgs .(~u',, aa<.~e xwm~y9:' t

,.Rc~~n q C -m . k SW[ of aynem ralmy:

. T~me 8-4 Vi 1-11. . . .. . . : h~Inn- us ' .. 1 7 Y . . . . . . . . . . . . . . . . .. :::

Shc 1 '+- 1 %lAny Ti rrix ' 1 1(

G oand k~ ini~+vm t

NOTE 6 Avp73Dk ybund ftP6ingf Md 16y#/1hNn co. pil !OiliN (Npl~ : the 400 ra iirg .a out a.011o0 0nlh KYi:mi 'Er eoYen) : .. ~ ,

~raierrr Roth+ai tret ine. c~aeni' viie'Sastem . Cortega,CnFl y

7W, 200Got), 300: 5CO iiP5C-1600 v7,5 ono:nlgn,,;6r0 a00, bA

40 0 : '6U0. . . Ztaaq . ' 1000 2000

7oa> >sGo. Sooo321n ,eon, 37W

4000 7000. aooG

4200 2 1 G0. X 200

cH D R? - ' INE CURJFjAvniiAE3L E SE 7?aiG _2 . 3 5, F p 9, AND 10 T iM FS?! t f QTiNU CU RRENT ; OR D EF_n' E0I SHOWN 0 7?~ 4 f JD 4K )

SHOar _ rVF aaN,uM i?

( SEE M OTE 3 )

SHORT TIMEQEILAV BAN D

MAXIMUM

^i TE RME 6i cTE

MINIMU M

ril 'JL~ I tj I I 1 11u a7n~c'"' ~.l . . o u~ •. ~h:00 ~7+ o o G5 ~ . .a moo p p~j

. ~ rl0 a"~ T V1 ~O C~O7Tq N P1 t U: ~O ~ p ~1

+Mq Its ~ h47DJ+~

TPIPFING THRESHOLD -- MULTIPLES OF RATING CURRENT CAMPS?

rWe-cuaRErvt CHARACTERISTIC CURVE STrip Mmes -u e th p it anatia3, o r "Ihf' fThis g rdpn rep r ese n ts t' .e following Pa w vicet oge , b re o ke r5 :K -brie T IY,J ,;:- L~n2 P lus . +~- L ind . K Gun V ~3 1 4 , MEi , MBD , tNB E, LK . LKD . a nd L KE .

(22)

Page 23: MPS-C 2000_0000067923.pdf

Aill IB 6.1 .2.84bPage 23

Figure Alb larger sca led notes section from Figure A -2a

Response with ST ! ' ; EMr~av~or Enabled ("IIl" or "IN")MPSC-2000 ; MPS-C-3(I~dST,LT) ; MPS-~--4(5T,LT) : and MP5-C-5(INST,ST,LT)

1 : This log-log graph depicts the short-lime response with 121 behavior . If the 12t characteristicis defeated ("DEF" or "OUT"), then ~e(er to TD-9651 . It a ground function was added to iretrip system, then also refer to time-current curve TD-9652 for ground respons e

2: These curves are typical of cingle and three phase power functions for 50/60 Hz systems . !fa trip function is not available an your unit, then ignore the corresponding curve . Curves W4rvcalibrated for a temperature range of 10-40 'C. The reset time for any trip function is 5 0 mmaximum .

3: For any time bond, the lower and upper limits define the time interval for which tripping w91!occur at a given multiple of rating current . If current exceeds the INST threshold, then theunit will trip the breaker by means of the in -stantaneoul fun g tign. If current less than theINST threshold but greater than 90of the ST threshold persists for a time up to the lowerST band limit, then the unit will trip the breaker throught the short time function . If currentgreater than the the LT threshold but less than 90% of the ST threshold persists until thelower IT band limit, then the unit will trip ►he breaker through the long time function .

4: Use the circuit breaker only within its published short circuit current rating . Since; all tripvalues are selectable, they must be chosen to match the requirements of your power sysierr, .

5: The in5tantaneou5, short-time, long-time, and ground tripping functions operate independently .Trip thresholds are set as multiples of the rating current . The rating current is eithe r50% or 100% of the trip system rating . EXAMPLE: An 800A K-Line breaker is set at aSOX rating of 400A . If its threshold multipliers are (12) INST, (5) ST, and (0 .8) LT, thenthe thresholds are 4800 A . 2000 A, and 320 A. respectively . All units are shipped w ith thefollowing factory settings (unless ordered differently) :

Pargmeter

Rating Current =Time Bond

InstantaneousShort-TimeLong-Time

Ground

Factory Setting

X 50% of system ratingMinimum

12X4X1 X

Minimum

6: Available ground settings and trip system compatibility (Note : the 4200 rating is not availablewith K-Line breakers) :

Rating Current

(Amps)100, 200300. 600400. 800800, 1600

1000. 20001500. 30001600. 32002000, 40002100 . 4200

Trig System Comqatibili~

MPSC-2000 V1 .5 and h igher

Trip System Rating

(Amps)20060080016002000300032004000420

(23)