Drive Technology \ Drive Automation \ System Integration \ Services Manual Control Cabinet Inverter MOVITRAC ® B Functional Safety Edition 05/2009 16811216 / EN

Transcript of MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2...

Page 1: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

Drive Technology \ Drive Automation \ System Integration \ Services

Manual

Control Cabinet Inverter MOVITRAC® BFunctional Safety

Edition 05/2009 16811216 / EN

Page 2: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

SEW-EURODRIVE—Driving the world

Page 3: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

Functional safety – MOVITRAC® B 3

Content

Content1 General Information ............................................................................................ 4

1.1 About this manual ....................................................................................... 41.2 Structure of the safety notes ....................................................................... 41.3 Rights to claim under limited warranty ........................................................ 51.4 Exclusion of liability..................................................................................... 51.5 Copyright notice .......................................................................................... 51.6 Content of this publication........................................................................... 51.7 Other applicable publications...................................................................... 6

2 Safety Concept .................................................................................................... 72.1 Limitations................................................................................................... 82.2 Representation "Safety concept for MOVITRAC® B / control unit" ............. 92.3 Representation "Safety concept for MOVITRAC® B / size 0" ................... 10

3 Safety-Relevant Conditions ............................................................................. 113.1 Information on the stop categories............................................................ 113.2 Approved devices ..................................................................................... 123.3 Installation requirements........................................................................... 133.4 Requirements on external safety relays.................................................... 143.5 Startup requirements ................................................................................ 163.6 Operation requirements ............................................................................ 16

4 Connection Variants ......................................................................................... 174.1 Disconnection of single drives .................................................................. 174.2 Disconnection of group drives................................................................... 22

5 Technical Data................................................................................................... 25

Index................................................................................................................... 26

Page 4: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

4

1 out this manualeneral Information

1 General Information1.1 About this manual

The manual is part of the product and contains important information about installation,startup, operation and service. The manual is written for everyone installing, starting upor servicing this product.

The manual must be accessible and legible. Make sure that persons responsible for thesystem and its operation, as well as persons who work independently on the unit, haveread through the manual carefully and understood it. If you are unclear about any of theinformation in this documentation, or if you require further information, contact SEW-EURODRIVE.

1.2 Structure of the safety notesThe safety notes in this manual are designed as follows:

Pictogram SIGNAL WORDType and source of danger.

Possible consequence(s) if the safety notes are disregarded.• Measure(s) to prevent the danger.

Pictogram Signal word Meaning Consequences if disregarded

Example:

General danger

Specific danger,e.g. electric shock

DANGER Imminent danger Severe or fatal injuries

WARNING Possible dangerous situation Severe or fatal injuries

CAUTION Possible dangerous situation Minor injuries

STOP Possible damage to property Damage to the drive system or its environ-ment

TIP Useful information or tip.

Simplifies the handling of the drive system.

AbG

Functional safety – MOVITRAC® B

Page 5: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

1Rights to claim under limited warrantyGeneral Information

1.3 Rights to claim under limited warrantyA requirement of fault-free operation and fulfillment of any rights to claim under limitedwarranty is that you adhere to the information in the MOVITRAC® B documentation.Therefore, read the operating instructions before you start working with the unit.

Make sure that the documentation is available to persons responsible for the system andits operation as well as to persons who work independently on the unit. You must alsoensure that the documentation is legible.

1.4 Exclusion of liabilityYou must comply with the information contained in the MOVITRAC® B documentationto ensure safe operation of MOVITRAC® B and to achieve the specified product char-acteristics and performance requirements. SEW-EURODRIVE assumes no liability forinjury to persons or damage to equipment or property resulting from non-observance ofthe documentation. In such cases, any liability for defects is excluded.

1.5 Copyright notice© 2009 – SEW-EURODRIVE. All rights reserved.

Unauthorized duplication, modification, distribution or any other use of the whole or anypart of this documentation is strictly prohibited.

1.6 Content of this publicationThis publication contains conditions and amendments related to MOVITRAC® B insafety-oriented applications.

The system comprises a frequency inverter with asynchronous motor and safety-testedexternal disconnecting device.

Functional safety – MOVITRAC® B

5
Page 6: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

6

1 ther applicable publicationseneral Information

1.7 Other applicable publicationsThis document supplements the MOVITRAC® B operating instructions and limits theapplication notes according to the following information.

It can only be used in conjunction with the following publications:

• The MOVITRAC® B operating instructions must always be observed.

For permitted connection variants, refer to chapter "Connection variants" (see page 17).

OG

Functional safety – MOVITRAC® B

Page 7: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

2Safety Concept

2 Safety Concept

• In case of danger, any potential risk related to a machine must be eliminated asquickly as possible. Standstill with restart prevention is generally the safe conditionfor preventing dangerous movements.

• MOVITRAC® B is characterized by the optional connection of X17 to an external fail-safe, prototype tested safety relay. The safety relay disconnects all active elements(disconnection of the safety oriented 24 V power supply of the output stage control)that generate the pulse trains to the power output stage (IGBT) when a connectedcontrol device (E-STOP button with latching function) is activated.

• Disconnecting the 24 V voltage supply at connector X17 ensures that the supplyvoltages required for operating the frequency inverter and consequently forgenerating a rotating field of pulse patterns (which allow the generation of a rotatingfield) are safely interrupted, preventing automatic restart.

• Instead of separating the drive galvanically from the power supply using contactorsor switches, the disconnection procedure described here prevents the powersemiconductors in the frequency inverter from being activated, thus ensuring safedisconnection. This process disconnects the rotating field generation for therespective motor. The individual motor cannot develop any torque in this state eventhough the mains voltage is still present.

• The requirements for the safety control are clearly defined in the following sectionsand must be observed.

Using a suitable external circuit via a safety control– with approval to at least EN 954-1 category 3enables operation of the MOVITRAC® B frequency inverter with safe disconnec-tion to stop category 0 or 1 according to EN 60204-1, fail-safe protection againstrestart according to EN 1037 and fulfillment of safety category 3 to EN 954-1.

Using a suitable external circuit via a safety control– with approval for EN ISO 13849-1, performance level "d"enables operation of the MOVITRAC® B frequency inverter with safe disconnec-tion according to stop category 0 or 1 to EN 60204-1, fail-safe protection againstrestart according to EN 1037 and fulfillment of performance level "d" to EN ISO13849-1.

Functional safety – MOVITRAC® B

Pi

fkVA

Hz

n

Pi

fkVA

Hz

n

7

Page 8: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

8

2 mitationsfety Concept

2.1 Limitations• Important: The safety concept is only suitable for performing mechanical work

on system/machine components.

• Important: A system/machine-specific risk analysis must always be carried outby the system/machine manufacturer and taken into account for the use of theMOVITRAC® B frequency inverter.

• Danger of fatal injury: When the safety-oriented 24 V voltage supply isdisconnected, the mains supply voltage is still present at the frequencyinverter DC link.

• Danger of fatal injury: When the 24 V voltage supply is disconnected, the DClink voltage is still present at the MOVITRAC® B frequency inverter.

• Important: If work is carried out on the electrical section of the drive system,the DC link voltage must be disconnected.

LiSa

Pi

fkVA

Hz

n

Pi

fkVA

Hz

n

Functional safety – MOVITRAC® B

Page 9: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

2Representation of the "Safety concept for MOVITRAC® B / control unit"

Safety Concept

2.2 Representation of the "Safety concept for MOVITRAC® B / control unit"

[1] Safety relay (external)[2] Low-voltage switch-mode power supply[3] Safety switched-mode power supply (SNT)[4] Voltage supply for controlling the power transistors[5] Feedback to the central processing unit: Voltage supply for output stage control OK (not in safety circuit)[6] Pulse width modulated signals for output stage[7] Power section[8] Motor[9] High-voltage switch-mode power supply

Emergency stop relay(external)

approved for cat. 3acc. to EN 954-1

orPL "d" EN 13849-1

Computercore

Temperaturemeasuring

Power supply

24V externalor

24 V internal

Voltage supply for output stage control O.K.(not in the safety circuit)

Power section

PWM

Ele

ctric

is

olat

ion

Uz-

Uz+

24 V safety disconnected / brake applied (not in safety circuit)

24Vexternal

24V

GND

SNT

Safe

ty c

ircui

t

(5)

(6)

(1)

(3)

(4)

(7) (8)

Voltage supply forcontrol of the

power transistors

SV

I24

S0V

24G

ND

Safe disconnectionwith one pole or

two poles

24V

M

BinaryIN

CANRS485

BinaryOUT

AnalogIN

MOVITRAC® B

(2)

Connection plug for power section

Con

nect

ion

plug

for p

ower

sec

tion

(9)

Uz+Uz-

SNTNV

SNTHV

X17

24Vinternal

Functional safety – MOVITRAC® B

Pi

fkVA

Hz

n

Pi

fkVA

Hz

n

9

Page 10: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

10

2epresentation of the "Safety concept for MOVITRAC® B / size 0"fety Concept

2.3 Representation of the "Safety concept for MOVITRAC® B / size 0"

For units of size 0 in design MC07B...-S0, an external 24 V supply must always beconnected as the control electronics can only be powered in this way.

[1] Safety relay (external) [2] Low-voltage switch-mode power supply[3] Safety switched-mode power supply (SNT)[4] Voltage supply for controlling the power transistors[5] Feedback to the central processing unit: Voltage supply for output stage control OK (not in safety circuit)[6] Pulse width modulated signals for output stage[7] Power section[8] Motor

Emergency stop relay(external)

approved for cat. 3acc. to EN 954-1

orPL "d" EN 13849-1

Computercore

Temperaturemeasuring

SNTNV

Netz

24V external

Voltage supply for output stage control O.K.(not in the safety circuit)

Power section

PWM

Ele

ctric

is

olat

ion

Uz-

Uz+

24 V safety disconnected / brake applied (not in safety circuit)

24Vexternal

24V

GND

SNTSa

fety

circ

uit

(5)

(6)

(1)

(3)

(4)

(7) (8)

Voltage supply forcontrol of the

power transistors

SV

I24

S0V

24G

ND

Safe disconnectionwith one pole or

two poles

24V

M

BinaryIN

CANRS485

BinaryOUT

AnalogIN

MOVITRAC® B (2)X17

RSa

Pi

fkVA

Hz

n

Pi

fkVA

Hz

n

Functional safety – MOVITRAC® B

Page 11: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

3Information on the stop categoriesSafety-Relevant Conditions

3 Safety-Relevant ConditionsThe following conditions are mandatory for the installation and operation ofMOVITRAC® B in applications with safe disconnection of the drive in accordance withcategory 0 or 1 of EN 60204-1 and fail-safe protection against restart according toEN 1037, and conformance with safety category 3 of EN 954-1 or performance level "d"of EN ISO 13849-1. The conditions are divided into the following sections:

• Approved devices

• Installation requirements

• Requirements for external safety relays

• Startup requirements

• Operation requirements

3.1 Information on the stop categories• Stop category 0 means that the safety 24 V voltage supply can be disconnected

independent of the setpoints.

• Observe the following procedure for stop category 1:

– Decelerate the drive using an appropriate brake ramp specified by the setpoint.

– Disconnect the safety-oriented 24 V voltage supply.

Functional safety – MOVITRAC® B

11
Page 12: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

12

3 proved devicesfety-Relevant Conditions

3.2 Approved devicesThe following frequency inverters are permitted for applications with safe disconnectionaccording to stop category 0 or 1 of EN 60204-1, fail-safe protection against restartaccording to EN 1037 and compliance with safety category 3 according to EN 954-1 orperformance level "d" according to EN ISO 13489-1.

3.2.1 MOVITRAC® B for AC 3 × 380 – 500 V / 200 – 240 V supply voltage

Power [kW] 380 – 500 V

Size Type

0.55 0S MC07B0005-5A3-4-S0

0.75 0S MC07B0008-5A3-4-S0

1.1 0S MC07B0011-5A3-4-S0

1.5 0S MC07B0015-5A3-4-S0

2.2 0L MC07B0022-5A3-4-S0

3.0 0L MC07B0030-5A3-4-S0

4.0 0L MC07B0040-5A3-4-S0

5.5 2S MC07B0055-5A3-4-00

7.5 2S MC07B0075-5A3-4-00

11 2 MC07B0110-5A3-4-00

15 3 MC07B0150-503-4-00

22 3 MC07B0220-503-4-00

30 3 MC07B0300-503-4-00

37 4 MC07B0370-503-4-00

45 4 MC07B0450-503-4-00

55 5 MC07B0550-503-4-00

75 5 MC07B0750-503-4-00

Power [kW] 200 – 240 V

Size Type

0.55 0S MC07B0005-2A3-4-S0

0.75 0S MC07B0008-2A3-4-S0

1.1 0L MC07B0011-2A3-4-S0

1.5 0L MC07B0015-2A3-4-S0

2.2 0L MC07B0022-2A3-4-S0

3.7 1 MC07B0037-2A3-4-00

5.5 2 MC07B0055-2A3-4-00

7.5 2 MC07B0075-2A3-4-00

11 3 MC07B0110-203-4-00

15 3 MC07B0150-203-4-00

22 4 MC07B0220-203-4-00

30 4 MC07B0300-203-4-00

ApSa

Functional safety – MOVITRAC® B

Page 13: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

3Installation requirementsSafety-Relevant Conditions

3.2.2 Hazard caused by coasting drive

Note that if the drive does not have a mechanical brake, or if the brake is defective, thedrive may coast to a halt.

Note: If coasting to a halt results in application-dependent hazards, takeadditional protective measures (e.g. movable covers with closure), which coverthe hazardeous area until persons are no longer in danger.The additional protective covers must be designed and integrated in such a way thatthey meet the safety category required for the machine.

After activating the stop command, access to the machine must remain blocked until thedrive has reached standstill, or the access time has to be determined to ensure that anadequate safety distance is maintained.

3.3 Installation requirementsNote the following instructions for applications of MOVITRAC® B with safe disconnec-tion of the drive according to stop category 0 or 1 according to EN 60204-1 and fail-safeprotection against restart according to EN 954-1 safety category 3 or performance level"d" according to EN ISO 13849-1.

• The line between the safety control system (or the safety-oriented tripping device)and MOVITRAC® B terminal X17 is designated as the safety-oriented 24 V voltagesupply.

• Power lines and the safety-oriented 24 V supply voltage must be installed in separatecable ducts.

• The safety-oriented 24 V supply voltage must be routed according to EMC guidelinesand as follows:

– Outside an electrical installation space: Shielded cables must be routedpermanently (fixed) and protected against external damage, or other equivalentmeasures.

– Individual conductors can be routed inside an electrical installation space.

Observe the respective regulations governing the application.

• It must be ensured that parasitic voltages cannot be generated in the safety-oriented24 V supply voltage.

• The total cable length between the safety control system (e.g. safety relay) andMOVITRAC® B is limited to a maximum length of 100 m for EMC reasons.

• The switching capacity of the safety relay and the maximum permissible voltage dropon the 24 V supply cable must be observed during disconnection of group drives.

• Only use terminal connections (terminal blocks) that meet EN 60204-1 and preventshort-circuits.

• Observe the notes in the "MOVITRAC® B" operating instructions on EMC compliantcabling. It is essential that you apply the shielding at both ends on the housing.

• Only use power supplies with safe isolation (SELV/PELV) according to VDE010.According to EN 60950-1, the voltage between the outputs or between any outputand a ground part must not exceed DC 60 V voltage for longer than 0.2 s after onlyone fault. The maximum DC voltage must be 120 V.

Functional safety – MOVITRAC® B

13
Page 14: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

14

3 equirements on external safety relaysfety-Relevant Conditions

• You must remove the jumpers at X17:1 to X17:4 (see following figure) for use inapplications with safe disconnection of the drive according to stop category 0 or 1 inaccordance with EN 60204-1 and fail-safe protection against restart according toEN 954-1 safety category 3 or performance level "d" according to EN ISO 13849-1.

• The shielded lines of the safety-oriented 24 V voltage supply (terminal X17) must beclamped under the signaling electronics shield clamp.

• You must observe the technical data of MOVITRAC® B (see MOVITRAC® Boperating instructions).

Removing jumpers

3.4 Requirements on external safety relays• If the requirements of the standard EN 954-1 are to be met, at least one approval for

safety category 3 according to EN 954-1 must be available.

• If the requirements of the standard EN ISO 13849-1 are to be met, at least oneapproval for performance level "d" according to EN ISO 13849-1 must be available.

• If the DC 24 V voltage supply is safely disconnected at the positive pole only, no testpulses must be applied to this pole in disconnected condition.

• Bipolar disconnection of the DC 24 V supply is permitted.

• The values specified for the safety relays must be adhered to when designing thecircuit.

SV

I

SO

V

24

V

GN

D X17

RSa

Functional safety – MOVITRAC® B

Page 15: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

3Requirements on external safety relaysSafety-Relevant Conditions

• The switching capacity of the safety relays must correspond at least to the maximumpermitted limited output current of the DC 24 V voltage supply. Observe themanufacturer's instructions for the safety relays concerning the permittedcontact loads and fusing that may be required for the safety contacts. Unlessspecified otherwise, the contacts must be protected with 0.6 times the nominalvalue of the maximum contact rating specified by the manufacturer.

• The controller must be designed and connected in such a way that resetting thecontrol device itself will not lead to a restart. A restart may only be carried out afteran additional reset of the controller.

3.4.1 "Safety relay" sample circuitThe following figure shows the basic connection of an external safety relay (accordingto the before mentioned requirements) to MOVITRAC® B.

The information in the respective manufacturer's data sheets must be observed forconnection.

1-pole disconnection of the 24 V supply voltage:

Safety-oriented 24 V supply of the emergency stop relay (e.g. PNOZ....)

Emergency stop relay with certification for at least category 3 according to EN954-1 or performance level "d" according to EN ISO 13849

Fuses in accordance with the manufacturer specifications of the emergency stop relay

24 V

GND

24 V voltage supply

Approved EMERGENCY STOP actuator element

Reset button

Functional safety – MOVITRAC® B

15
Page 16: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

16

3 artup requirementsfety-Relevant Conditions

3.5 Startup requirements• Startup must be documented and the functionality of the safety functions must be

demonstrated.

• Startup checks of the disconnecting device and the correct wiring must be performedand documented for MOVITRAC® B with safe disconnection of the drive accordingto stop category 0 or 1 of EN 60204-1, fail-safe protection against restart accordingto EN 1037 and compliance with safety category 3 according to EN 954-1 orperformance level "d" according to EN ISO 13849-1.

• At startup, the safety-related 24 V control voltage must be included in the functionaltest.

3.6 Operation requirements• Operation is only allowed within the limits specified in the data sheets. This applies

both to the external safety relay as well as MOVITRAC® B.

• The safety functions must be checked at regular intervals to ensure properfunctioning. The period of time between the tests should be specified in accordancewith the risk analysis.

StSa

Functional safety – MOVITRAC® B

Page 17: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

4Disconnection of single drivesConnection Variants

4 Connection VariantsRefer to the publication "Safe Disconnection for MOVITRAC® B - Applications" forexamples of approved connection variants of units listed in the section "Approved Units"for safe disconnection of the drive according to stop category 0 or 1 of EN 60204-1 andfail-safe protection against restart according to EN 1037 and fulfillment of the safetycategory according to EN 954-1 or performance level "d" of EN ISO 13849-1. Thepublication "Safe Disconnection for MOVITRAC® B - Applications" is constantly beingsupplemented by possible applications. The publication includes checklists, which offeradditional assistance in project planning and installation as well as operatingMOVITRAC® B drives in safety-oriented applications. It is essential that you comply withthe publications listed in the section "Safety and warning instructions" for all theconnection variants listed in the publication "Safe Disconnection for MOVITRAC® B -Applications".

4.1 Disconnection of single drives4.1.1 Requirements

The requirements of the manufacturers of safety relays (such as protecting the outputcontacts against welding) or other safety components must be strictly observed. Inaddition, the basic requirements described in the manual "Safe Disconnection forMOVITRAC® B - Conditions" apply for cable routing.

For reasons of EMC, the length of the cable between connection X17 onMOVITRAC® B and the safety components (e.g. safety relay) is limited to a maximumof 100 m. Other instructions by the manufacturer on the use of safety relays for specificapplications must also be observed.

Functional safety – MOVITRAC® B

17
Page 18: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

18

4 isconnection of single drivesonnection Variants

4.1.2 Internal 24 V supply, stop category 0

* external DC 24 V voltage supply. Required for BG0S and BG0L!

Mains connection

®

+24V

Res

et

STARTSTOP

digital input

digital output

PLC

X12

X17

X2

X1 '0'=Ctrl. inhibit'1'=Ctrl. enable'0'=Halt'1'=START CW'0'=Stop'1'=Enable

GND

VO24

SVI24

24VIO

1

2

4

8

L3L2L1

1 2 3

MO

VTR

AC

B

M

4

U V W

5 6

SOV24

Feed

back

EM

ER

GE

NC

Y S

TOP

GND

Safety relay

EMEGENCYSTOP

Safety circuit

} no factory setting

9 GND

GND

+24 V output

Reference + 24 V safe stop input

+24 V safe stop input

* DC24 V

+

DC

Functional safety – MOVITRAC® B

Page 19: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

4Disconnection of single drivesConnection Variants

4.1.3 External 24 V supply, stop category 0

* external DC 24 V supply. Required for BG0S and BG0L!

Mains connection

®

+24V

Res

et

STARTHALT

digital input

digital output

PLC

X12

X17

X2

X1 '0'=Ctrl. inhibit'1'=Ctrl. enable'0'=Halt'1'=START CW'0'=Stop'1'=Enable

1

2

4

L3L2L1

1 2 3

MO

VITR

AC

B

M

4

U V W

5 6

Feed

back

EM

ER

GE

NC

Y S

TOP

GND

Safety relay

EMERGENCYSTOP

Safety circuit

} nofactory setting

GND

VO24

SVI24

24VIO

4

8

SOV24

9 GND

GND

+24 V output

Reference + 24 V safe stop input

+24 V safe stop input

* DC24 V

+

Functional safety – MOVITRAC® B

19
Page 20: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

20

4 isconnection of single drivesonnection Variants

4.1.4 Internal 24 V supply, stop category 1

* external DC 24 V supply. Required for BG0S and BG0L![1] Safety relay with adjustable time delay t1.

Observe the following procedure for stop category 1:

• Decelerate the drive using an appropriate brake ramp specified by the setpoint.

• Disconnect the safety-oriented 24 V voltage supply.

Mains connection

®

+24V

Res

et

STARTHALT

digital input

digital output

PLC

X12

X17

X2

X1 '0'=Ctrl. inhibit'1'=Ctrl. enable'0'=Halt'1'=START SW'0'=Stop'1'=Enable

1

2

4

L3L2L1

1 2 3

MO

VITR

AC

B

M

4

U V W

5 6

Feed

back

EM

ER

GE

NC

Y S

TOP

GND

Safety relay

EMERGENCYSTOP

Safety circuit

t1

[1]

} nofactory setting

GND

VO24

SVI24

24VIO

4

8

SOV24

9 GND

GND

+24 V output

Reference + 24 V safe stop input

+24 V safe stop input

* DC24 V

+

DC

Functional safety – MOVITRAC® B

Page 21: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

4Disconnection of single drivesConnection Variants

4.1.5 External 24 V supply, stop category 1

* external DC 24 V supply. Required for BG0S and BG0L![1] Safety relay with adjustable time delay t1.

Observe the following procedure for stop category 1:

• Decelerate the drive using an appropriate brake ramp specified by the setpoint.

• Disconnect the safety-oriented 24 V voltage supply.

Mains connection

®

+24V

Res

et

STARTHALT

digital input

digital output

PLC

X12

X17

X2

X1 '0'=Ctrl. inhibit'1'=Ctrl. enable'0'=Halt'1'=START SW'0'=Stop'1'=Enable

1

2

4

L3L2L1

1 2 3

MO

VITR

AC

B

M

4

U V W

5 6

Feed

back

EM

ER

GE

NC

Y S

TOP

GND

Safety relay

EMERGENCYSTOP

Safety circuit

t1

[1]

} no factory setting

GND

VO24

SVI24

24VIO

4

8

SOV24

9 GND

GND

+24 V output

Reference + 24 V safe stop input

+24 V safe stop input

* DC24 V

+

Functional safety – MOVITRAC® B

21
Page 22: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

22

4 isconnection of group drivesonnection Variants

4.2 Disconnection of group drives4.2.1 Requirements

For group drives, the 24 V supply of several MOVITRAC® B units can be made availableby a single safety relay. The maximum possible number of units (n units) results fromthe maximum permitted contact load of the safety relay and the maximum permittedvoltage drop of the DC supply for MOVITRAC® B units.

Other requirements of the safety relay manufacturer (such as protecting the outputcontacts against welding) must be strictly observed. In addition, the basic requirementsdescribed in the manual "Safe Disconnection for MOVITRAC® B - Conditions" apply forcable routing.

For reasons of EMC, the length of the cable between connection X17 (MOVITRAC® B)and the safety components (e.g. safety relay) is limited to a maximum of 100 m.

Other instructions by the manufacturer on the safety relay used in the specificapplication must also be observed.

Determining the maximum number of MOVITRAC® B drives for disconnection of group drives

The number (n units) of MOVITRAC® B units that can be connected to a group drive withsafe disconnection is limited by the following points:

1. Switching capacity of the safety relay.

A fuse must be connected in front of the safety contacts according to thespecifications of the safety relay manufacturer to prevent the contacts from stickingor welding.

The project planner is responsible for ensuring that the specifications on theswitching capacity according to EN 60947-4-1, 02/1 and EN 60947-5-1, 11/97 as wellas on contact fuse protection given in the operating instructions of the safety relaymanufacturer are strictly observed.

2. Maximum permitted voltage drop in the 24 V power supply cable.

Values concerning cable lengths and permitted voltage drops must be observedduring project planning for group drives.

3. Maximum cable cross section of 1x1.5 mm2 or 2x0.75 mm2.

A calculation based on the technical data of MOVITRAC® B must be performedseparately for each group drive application.

DC

Pi

fkVA

Hz

n

Functional safety – MOVITRAC® B

Page 23: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

4Disconnection of group drivesConnection Variants

4.2.2 External 24 V supply, stop category 0

* external DC 24 V supply. Required for BG0S and BG0L!

X12

X17

X2

X1 '0'=Ctrl. inhibit'1'=Ctrl. enable'0'=Halt'1'=START CW

1

2

4

®M

OVI

TRAC

B

'0'=Stop'1'=Enable

} nofactory setting

GND

VO24

SVI24

SOV24

24VIO8

9 GND

GND

+24 V output

Reference + 24 V safe stop input

+24 V safe stop input

M

4

U V W

5 6

Mains connection

STARTHALT

digital input

digital output

PLCX12

X17

X2

X1 '0'=Ctrl. inhibit'1'=Ctrl. enable'0'=Halt'1'=START CW

1

2

4

L3L2L1

1 2 3

®M

OVI

TRAC

B

'0'=Stop'1'=Enable

Rese

t

Safety circuit

Feed

back

EM

ERG

ENCY

STO

P

GND

Safety relay

EMERGENCYSTOP

+24V

} no factory setting

GND

VO24

SVI24

SOV24

24VIO8

9 GND

GND

+24 V output

Reference + 24 V safe stop input

+24 V safe stop input

* DC24 V

+

* DC24 V

+

Functional safety – MOVITRAC® B

23
Page 24: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

24

4 isconnection of group drivesonnection Variants

4.2.3 External 24 V supply, stop category 1

* external DC 24 V supply. Required for BG0S and BG0L![1] Safety relay with adjustable time delay t1.

Observe the following procedure for stop category 1:

• Decelerate the drive using an appropriate brake ramp specified by the setpoint.

• Disconnect the safety-oriented 24 V voltage supply.

t1

[1]

X12

X17

X2

X1 '0'=Ctrl. inhibit'1'=Ctrl. enable'0'=Halt'1'=START CW

1

2

4

®M

OVI

TRAC

B

'0'=Stop'1'=Enable

} no factory setting

GND

VO24

SVI24

SOV24

24VIO8

9 GND

GND

+24 V output

Reference + 24 V safe stop input

+24 V safe stop input

M

4

U V W

5 6

Mains connection

STARTHALT

digital input

digital output

PLCX12

X17

X2

X1 '0'=Ctrl. inhibit'1'=Ctrl. enable'0'=Halt'1'=START CW

1

2

4

L3L2L1

1 2 3

®M

OVI

TRAC

B

'0'=Stop'1'=Enable

Rese

t

Safety circuit

Feed

back

EM

ERG

ENCY

STO

P

GND

Safety relay

EMERGENCYSTOP

+24V

} no factory setting

GND

VO24

SVI24

SOV24

24VIO8

9 GND

GND

+24 V output

Reference + 24 V safe stop input

+24 V safe stop input

* DC24 V

+

* DC24 V

+

DC

Functional safety – MOVITRAC® B

Page 25: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

5Technical Data

5 Technical Data

X17 safety input, terminal 4

Voltage / cross-section / duration Min. Typ. Max. Unit

Safety-oriented 24 V supply voltage 19.2 24 30 DC V

Power consumption (size / capacity) BG0S / BG0L / 27 µFBG1 / 270 µF

BG 2/2S / 270 µFBG3 / 270 µFBG4 / 270 µFBG5 / 270 µF

356

7.58

10

W

Cable cross-section of safety-oriented 24 V supply voltage 0.75 1.5 mm2

Time between disconnection of the safety-oriented 24 V supply voltage at MOVITRAC® B until the disconnection of the pulse pattern at output stage tswitch-off.

Size 0Sizes 1 to 5

20100

ms

Functional safety – MOVITRAC® B

Pi

fkVA

Hz

n

25

Page 26: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

26 Functional safety – MOVITRAC® B

Index

Index

AApproved devices ..................................................12

MOVIDRIVE®MDX60B/61B (380 ... 500 VAC)..12

CConnection variants ...............................................17Content of this publication........................................5Copyright..................................................................5

DDisconnection of group drives................................22

Connection variant "external 24 V supply, stop category 1" .................................................24Connection variant "external 24 V supply, stop cat. 0" .........................................................23Determining the maximum number of MDX60B/61B drives...........................................22

Disconnection of single drives................................17Connection variant "external 24 V supply, stop category 0" .................................................19Connection variant "external 24 V supply, stop category 1" .................................................21Connection variant "internal 24 V supply, stop category 0" .................................................18Connection variant "internal 24 V supply, stop category 1" .................................................20Requirements.....................................................17

Documentation, applicable.......................................6Drive coasting (information) ...................................13

EExclusion of liability ..................................................5External safety relays.............................................14

GGroup disconnection

Requirements.....................................................22

IInstallation

Notes on routing control lines ............................13Permitted terminal connections..........................13Requirements.....................................................13

NNotes, general..........................................................4

OOperation, requirements ........................................16

PPublications, applicable ...........................................6

RRequirements

External safety relays ........................................14Installation..........................................................13Operation ...........................................................16Startup ...............................................................16

Rights to claim under limited warranty.....................5

SSafety concept .........................................................7

Limitations............................................................8Schematic representation ..............................9, 10

Safety notesStructure ..............................................................4

Safety relays, external ...........................................14Requirements ....................................................14Sample circuit ....................................................15Switching capacity .............................................15

Safety-relevant conditions .....................................11Startup, requirements ............................................16Stop categories, information ..................................11Structure of the safety notes....................................4

UUse of the manual....................................................4

Page 27: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only
Page 28: MOVITRAC® B - Functional Safety / Manuals / 2009-05 · 8 Functional safety – MOVITRAC® B 2 Limitations Safety Concept 2.1 Limitations • Important: The safety concept is only

SEW-EURODRIVE—Driving the world

SEW-EURODRIVEDriving the world

www.sew-eurodrive.com

SEW-EURODRIVE GmbH & Co KGP.O. Box 3023D-76642 Bruchsal/GermanyPhone +49 7251 75-0Fax +49 7251 [email protected]