IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 1
Installation Instructions - Mounting
IQL11+/xxx/24VAC
Important: Retain these instructions
These instructions shall be used by trained service personnel onlyIf the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.
1 Dimensions
2 Requirements
3 InsTALLATIon
1 Box ConTenTs 2 sToRIng
It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).
ConTenTs1 Box contents ..................................................................12 Storing ...........................................................................13 Installation .....................................................................1
IQL11+/xxx/24VAC Installation Instructions (TG200233)
3.1 Installation - Mounting ...................................................13.2 Installation - configuring ................................................64 Cleaning ......................................................................125 Disposal .......................................................................12
H O2
+50 °C(122 °F) 0-10 °C
(-14 °F) 90 %RH
3.1 Installation - Mounting
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
89 m
m (3
.5”)
75 mm (3”)
185 mm (7.28”)
45 mm (1.77”)
WARnIng: To reduce the risk of electrical shock or fire do not interconnect the output of different Class 2 circuits.
LonMARK® Terminal Unit Controller
cont inued on next page
Note that this product may involve LONWORKS® system integration as referred to in section 3.2 step 4: this procedure should only be performed by an installer with LONWORKS engineering expertise.
152 mm (5.98”)
2 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015
IQL11+/xxx/24VAC Installation Instructions - Mounting
2 Requirements (Continued)
4Lift Hinged Cover
3Mounting
3.1 Installation - Mounting (continued)
H O2
+45 °C(113 °F)
0
0 °C(32 °F)
90 %RH
Protection: IP20, NEMA 1Altitude: <2000 m (6562’)
Avoid locations where corrosive fumes or explosive vapours are present. Avoid electrical noise interference.
DIN rail end stop
!
IQL
IQL
IQL IQ
L
2 holes
∅ 6 mm(0.24”)
107 mm (6.69”)either surface mount
or DIN rail mount
Failure to use a screwdriver to open the cover will cause damage to the unit.
Must be installed in an enclosure rated to at least IP 20 or equivalent. If DIN rail mounted or switch voltage greater than 30 V. If not DIN rail mounted or switch voltage less than 30 V may be mounted out of an enclosure providing it is out of reach (e.g. in a plenum)
/USA/UL/24VAC only: the unit is UL rated as ‘UL916 listed open energy management equipment’.
IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 3
Installation Instructions - Mounting IQL11+/xxx/24VAC
5Connect Power
6 Connect LonWoRKs bus
3.1 Installation - Mounting (continued)
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
100 � F, 50 V min
100 � F, 50 V min
Terminator
e.g.LONTERMINATOR
LonASCN LonB LonASCN LonB
LINC
A
IQLROUTER
B
IQL
x y
A
IQLROUTER
B
zw
IQL
x y zw
T
T T
4 5 6 7 8 9 10 11
4 5 6 7 8 9 10 11
Maximum 64 nodes per LONWORKS segment Maximum 40 IQLs (and LONCs) per virtual Lan
Recommend terminate at LINC or Router.e.g. use IQLRouter integral terminators
Do noT APPLY PoWeR O
I
� � � � � � � � � � � � � � � � � � � �
� � � � � � � � � �
LONWORKS - FTT (free topology)
Star topologyBus topology
Loop topology
*Terminate LONWORKS bus at one end only
LON
L W
network
ON ORKS L W
network
ON ORKS
14 15
polarity independent
* *
*
Do not allow wires to cross on a loop
cont inued on next page
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
IQL consumption <= 15.4 VAC (9.7 VAC + power to triac outputs)
Terminal size 0.14 to 2.5 mm2 (25 to 14 AWG) For the /USA/UL/24 VAC the input power connections must be made using 18 AWG or larger wire rated at least 90 °C.
Clean earths (grounds) consisting of short (<300 mm, 12”) stranded copper wire (>=1.5 mm2, 16 AWG to a substantial earthed (grounded) metal part (e.g. cable tray) are recommended
The 24V supply must include a suitably rated switch in close proximity and be clearly marked as the disconnecting device for the unit.
The earth on this unit is NOT a protective earth, but it is essential that an earth is fitted for functional reasons.24Vac
24V
ac
16 17 18
Earth (ground) 24 Vac supply neutral at transformerUL listed Class 2
24 VAC transformer
4 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015
IQL11+/xxx/24VAC Installation Instructions - Mounting
6Connect LonWoRKs Bus (continued)
7Connect Inputs and outputs
8Connect Inputs
3.1 Installation - Mounting (continued)
If custom strategy, follow special installation instructions and jump to section 3.1 step 11
Custom Strategy Installation Instructions
If used with LPT-10 (powered bus), cable lengths differ - see “Link Power Transceiver User’s Guide (078-0105-01C)”.
LINC
IQ Outstations
L MON ARK
Device
L W busON ORKS
IQ Outstation
LINC
Normal IQ System current loop Lan cable is not recommendedDo not use screened cable
Terminal size 0.14 to 2.5 mm2 (25 to 14 AWG), for USA/UL/24VAC use 22 to 14 AWG
Cable Max bus length Max node to nodeBelden 85102 500 m (545 yds) 500 m (545 yds)IQ systemTP/1/0/16/HF/200 (Belden 8471)
500 m (545 yds) 400 m (430 yds)
UL Level IV, 22 AWG 500 m (545 yds) 400 m (430 yds)
JY(St) Y2 x 2 x 0.8 500 m (545 yds) 320 m (350 yds)TIA5268A Cat. 5, 24 AWG 450 m (490 yds) 250 m (270 yds)
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
3 21 5 4
TB/TS/K /E
9 10
1
11 12 13
3COM C
2
T
TB/TS ü û û û / ûTB/TS/K ü ü û û / ûTB/TS/KE ü ü ü û / ûTB/TS/KEF ü ü ü ü / ûRD/IQL/K üS ü / û / ûRD/IQL/KOS üS ü ü û / û
RD/IQL/KOSF üS ü ü üS / û
∆TPIR
Cable size 0.14 to 2.5 mm2
(25 to 14 AWG), for USA/UL/24VAC use 22 to 14 AWG - Cu only
9 10
1
11 12 13
3COM C
2
Sensors TB/TS, TB/TS/K, TB/TS/KE, TB/TS/KEF recommended; wire as shown below.
Room Display Module (RD-IQL/K, /KOS, /KOSF) provides monitor and control; wired as shown below:
Note that the IQL must be correctly set up to use the RD‑IQL, see section 4 step 13
Note that terminal types COM and C should not be connected together
Note: These terminals provide power to connected RD product that is within the limits described by EN60950‑1 (table 2B)
Input included in TB or RDs Separate input may be used/ Input either cannot be connected, or will be ignored
Connection of separate device to input required- Sensor or Room Display not applicable to IQL11+
Terminal size 0.14 to 2.5 mm2
(25 to 14 AWG)
pola
rity
inde
pend
ent
RD-IQL
12 13
3C
Window/Pushbutton PIR input
Local SetpointAdjust
Potentiometer
Local SpaceTemperature
sensorWIN/Pb/PIR input type selected by configuration parameters W5/W6
IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 5
Installation Instructions - Mounting IQL11+/xxx/24VAC
9Connect Heat/Cool outputs
10Connect Fan outputs
11Close Hinged Cover
12Close enclosure
3.1 Installation - Mounting (continued)
Heat/Cool
Damper
Ra
ise
Lo
we
r
Com
mon
not used
3 4 5 6 7 8
2 3 4 524V 24V
not used
Ra
ise
Lo
we
r
Co
mm
on
Heat or Cool
Valve
~24V
32 4 5
3 4 5 6 7 8
~24V
Rais
e
Lo
we
r
Com
mon
Rais
e
Lo
we
r
Com
mon
Cool ValveHeat Valve
~24V
32 4 5
3 4 5 6 7 8
~24V
Heat or
Cool
Valv
e
not used
~24V
32 4 5
3 4 5 6 7 8
~24V
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
Cool ValveHeat Valve
~24V
32 4 5
3 4 5 6 7 8
~24V
(24 Vac, 400 mA maximum shared between all triac outputs used)
/AR2 /WR2 /WR4 /WT2 /WT4
cable size 0.14 to 2.5 mm2 (25 to 14 AWG),for USA/UL/24VAC use 22 to 14 AWG - Cu only
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
WARnIng: The wires may be connected to hazardous voltages. Disconnect power before attempting any wiring.
5 A maximum @240 Vac resistive or inductive (cosø>=0.4)5A @ 24 Vdc (resistive), 2 A @ 24 Vdc (inductive, T<=30 mS)
Arc suppression (TG200208)
cable size 0.14 to 2.5 mm2 (25 to 14 AWG), for USA/UL/24VAC use 22 to 14 AWG- Cu only
Fan
1
1 2
UL rating applies up to 30V
6 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015
IQL11+/xxx/24VAC Installation Instructions - Mounting
1Tear off Label strip
2 switch on
3Check IQL/LInC on LonWoRKs network
4Install using LonWoRKs network Management Tool
LINC
IQ Outstations
L MON ARK
Device
L W busON ORKS
IQ Outstation
LINC
3.2 Installation-Configuring
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
O
I
(Check LONWORKS network LINCs)
LON OK (green)Flashes every 24 s, ON after 1½ mins
Flashes every 1 s (Deaf IQL. Check LONWORKS network)
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
MAC Addr 00.10.70.00.UD.BBS/No:
Q3B____X73010003
IP Addr Location
‘locate’
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
See LONWORKS network management tool manual. See IQ System LONWORKS Products Engineering Manual (TE200292). LONWORKS System Integrator must have LONWORKS engineering expertise.a). When installing IQL in LONWORKS tool, press service
button when requested.
b). The IQL network image can be obtained from www.lonmark.org, or from www.pnet.trend-controls.com.
c). Set up bindings if required (bind network variables between IQL and LONMARK devices).
If a binding IQLs to LONMARK devicesor b LINCs version <3.23 straddle routeror c other devices have address conflicts with IQ System devicesor d IQLROUTERs used on installed system
SRV PINservice button
LINC
L WnetworkON ORKS
IQL
LONMARKdevice
If one IQ System LONWORKS device is installed, all must be installed.
IQL13+ Data Sheet (TA200113) for LONWORKS network variables (NVs)
O/SLAN
NID
Strategy
Serial No
117 027
00:A0:25:36:51:00
IQL1x WR4 E 06
IQL1xWR4_50100025
IQL1xWR4_50100025
NID
Serial No
00:A0:25:36:51:00
Serial No
IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 7
Installation Instructions - Mounting IQL11+/xxx/24VAC
5Connect software Tool for Commissioning
3.2 Installation-Configuring (continued)
LCI
IQL
if required
IqlTool2 Manual (TE200185)LCI/USB Installation Instructions(TG200817)SET Manual (TE200147)
IqlTool2 (SET)IqlTool2 runs within SETV5.1 (or later)
USB cable supplied with LCI/USB
LONWORKS adaptor cable supplied with LCI/USB Note that a PIN may be required to make
changes. If the PIN has been forgotten the users should contact their supplier (installers contact Technical Support) quoting the generator number and neuron id (both from Address module)
whereupon a default PIN will be supplied. This will only work for three attempts at entering the PIN. After the default PIN is entered a new PIN should be set up and remembered.
7Test Input/output Functionality
6switch on
Custom Strategy Installation Instructions
If custom strategy follow special installation instructions and jump to section 3.2 step 13.
LCI
IQL
If IqlTool2 available
IqlTool2 Manual (TE200185)
Use IqlTool2 to monitor inputs and exercise outputsIqlTool2(SET)
Note that IqlTool2 may also be used for mapping the LONWORKS segment, resolving duplicate addresses on a LONWORKS network, water balancing (/WR2, /WR4, /WT2, /WT4 only), identification via service button, associating with SDU‑LON (for other uses see later)
LONWORKS network
LONWORKS network
8 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015
IQL11+/xxx/24VAC Installation Instructions - Mounting
8Check strategy, sensor/Fan/Heat Cool outputs/electric Heater
/AR2 /WR2 /WR4 /WT2 /WT4
3.2 Installation-Configuring (continued)
�� � �
�� � �
�� � �
� � �
�
heat
� � �
�
cool
OUT2,3damper
OUT2,3damper
OUT2,3
If W2=0(Winter Mode)
heating
OUT2,3If W2=1(Summer Mode)
cooling
OUT2,3
heat valve
OUT4,5
cool valve
OUT2If W2=0(Winter Mode)
heating
OUT2If W2=1(Summer Mode)
cooling
OUT2
heat valve
OUT4
cool valve
�� � �
�� � �
�� � �
�� � �
�� � �
� � �
�
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
S
S
�
In1
oUT1heat
� � �
�
cool
If Fan Speed Auto
IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 9
Installation Instructions - Mounting IQL11+/xxx/24VAC
9 Check operation - Window Contact Input
10Check operation - Pushbutton or PIR Input 11
Check operation- Local sP Adjust
/AR2 /WR2 /WR4 /WT2 /WT4
3.2 Installation-Configuring (continued)
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
Window
fan off
IN3 OUT1
if Window Mode (W5=1)
� � �
�
heat
� � �
�
cool
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
PIR if in standby
Pushbuttonif non-occupied or standby
fan on
24V
acLON
1 2 3 4 5 6 7 8 9 10 14 15 16 17 18
1 2 3 4 5 1
11 12 13
3COM
LON
OK
SRV
PINC
24V 24V 2
Local adjustment can be provided by TB/TS/K, /KE, /KEF or RD-IQL/K, /KOS, /KOSF (see section 3.1 step 8).
If Fan Speed Auto
If Fan Speed Auto
IN4 OUT1OUT1
IN2
Pb/PIR input type selected by configuration parameterW6 - see section 3.2 step 12.
see table section 3.2 step 8
Pushbutton can be provided by TB/TS/KE, /KEF, or RD-IQL/KOS, /KOSF (see section 3.1 step 8)
� � �
�
heat
� � �
�
cool
see table section 3.2 step 8
Wait 6 secs at each end to calibrate potentiometer
�� � �
� � �
�
heat
� � �
�
cool
OUT2,3damper
OUT2,3
valve closes
�� � �
OUT2,3heat valve
�� � �
OUT4,5
cool valve
OUT2 OUT2
damper goes to neutral
�� � �
valve closes
�� � �
heat valve
�� � �
cool valve
OUT4
10 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015
IQL11+/xxx/24VAC Installation Instructions - Mounting
13set up strategy Parameters if required Use IqlTool2 (see section 3.2 step 5) and text
communications
For standard strategies use table below, else refer to custom strategy installation instructions
4 Installation-Configuring (continued)
Parameter Label Function Defaults
/UK/ /USA/UL
K1(V) Remote Setpoint Base setpoint can be adjusted remotely 20 °C 68 °F
K2(V) RemoteSpaceTemp Used if bound to LONWORKS sensor, or if local sensor disconnected 20 °C 68 °F
K3(V) OCC Deadbnd Deadband around setpoint during Occ 1 °C 2 °F
K4(V) Standby Deadbnd Deadband around setpoint during Standby 2 °C 4 °F
K5(V) NOCC Deadbnd Deadband around setpoint during Nocc 12 °C 22 °F
K6(V) Remote Occ Sets state 0=Occ, 1=Nocc, 2=Bypass, 3=Standby 0=Occupied
K8(V) Remote SP Offset Used if bound to a LONWORKS Sensor or if local adjust is disconnected 0 °C 0 °F
K13(V) Pb PIR Run On Time switched into occupancy for PIR or Pb input 1800 s (30 mins)
K15(V) Offset Range Defines range of Local SP adjust pot. 2 °C 2 °F
W1(S) O=4Pipe I=2Pipe Strategy change W1=O(WR4, WT4, AR2) W1=I(WR2, WT2) *
W2(S) Summer Mode Winter (heat only) or Summer (cool only) (only used for /WR2, /WT2) O=Winter
W4(S) O=Water I=Air Strategy change W4=O(WR, WT) W4=I (AR2) *
W5(S) Window Mode Window contact if set to I, PIR or Pb if set to O O=alarm contact
W6(S) O=Pb I=PIR PIR if set to I, Pushbutton if set to O O=pushbutton
W7(S) Frost Condition Overrides heating to 100 % (not /AR2) if unoccupied O=no frost
W8(S) Remote Shutdown Shuts off fan, and sets heat/cool to zero O=no shutdown
L1(G) Heat Loop Gain 20 20
L1(I) Heat Loop Integral 10 mins 10 mins
L2(G) Cool Loop Gain -20 -20
L2(I) Cool Loop Integral 10 mins 10 mins
If required the strategy type may be changed (e.g. /AR2 to /WR2): IQL11+/xxx data sheet (TA200245)
Note that any changes to the strategy parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory
* Default depends on strategy
If used with RD-IQL (see section 3.1 step 8), the following must be configured: Local space Temp Type s9(Y=6), Local sP Adjust Type s10(Y=6), Window Mode W5(s=o) default, o=Pb I=PIR W6(s=o) default followed by R(z=1) to write changestoflashandreset. Configuration for RD-IQL is facilitated by IqlTool2.
If the sensor on IN2 is to be used, leave Local Space Temp Type at default S9(Y=1)
Note that for AR2, WR2, WR4 strategies D2 and D3 full scale drive times should not be greater than 262s.
IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 11
Installation Instructions - Mounting IQL11+/xxx/24VAC
14set up system Core Firmware Module Parameters
15set up Lan system
Using IqlTool2 (see section 4 step 5) and text communications
if required - see conditions
LINC Installation Instructions (TG103062)
LINC
IQ
L WON ORKS
networkIQL
Check Lan
if required
IQ System LONWORKS Products Engineering Manual - (TE200292)
Use SET and terse text communications
SET
4 Installation-Configuring (continued)
Parameter setting Function Condition noteR(..address L - own address device address of IQL if required to rearrange
Lans, address1, 2, 4
N - own LaN Lan number of IQL if required to rearrange Lans, address
1, 2
D - identifier identifier attribute of IQL For alarm ident, text comms, IC comms
1
F - attribute 2 text comms attributes For text comms, IC comms 1G - attribute 3 1A - own Lan alarm address address and Lan of
own Lan alarm targetto report Lan alarms to a supervisor
1R - Own Lan alarm Lan 1E - Internetwork alarm address
address and Lan of Internetwork alarm target
to report internetwork alarms to a supervisor (only for lowest addressed IQ System device on Lan)
1
T - Internetwork alarm Lan 1
r - LONWORKS retry time See IQ System LONWORKS Products Engineering Manual for details
2i - LONWORKS interpacket delay
2
a - LONWORKS service class 2b - router Buffer size buffer size
(bytes) Default = 146
specifies smallest router buffer on system
If routers separate IQLs/LINCs/LONCs and have buffer size smaller that 146 bytes - set to smallest buffer size. (minimum = 66)
2
m - LONWORKS Message code
code number. Default = 64
Code used by IQLs/LINCs/LONCs, all LINCs/LONCs must use same code
If message code being used by other users - must be exclusive to IQ System
2, 5
g - generator number To find PIN if lost (read only)e - Neuron chip id unique identifier
for Neuron®To find PIN if lost; to identify LONWORKS node
(read only)
T(..Time H - Hours Current time To synchronise time for alarms and loggingN - Minutes
D - Day of month Current date To synchronise date for alarms and logging
3M - Month 3Y - Year 3l - Lan of system timemaster IQL timekeeper gets
time sync from IQ at address 11 on this Lan
IQL will be timekeeper If this ‘l’ parameter is non-zero and own address = 11
3, 4
U1(..User P - PIN PIN number in IQ To protect from unauthorised changes
3, 6
l -level authority level of PIN No protection if zero 3
Note 1: IqlTool2 facilitates setting of these parameters across the LONWORKS segmentNote 2: Changing any of these parameters results in a controller reset (clears down time and and sensor logs)Note 3: Any changes to these parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory.Note 4: IqlTool2 facilitates setting to timekeeper (sets up timemaster Lan and changes own address to 11)Note 5: Message code can only be changed by text comms if ‘lonworks managed’ (read only) is set to No.Note 6: If PIN is forgotten see note in section 3.2 step 5
12 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015
IQL11+/xxx/24VAC Installation Instructions - Mounting
Please send any comments about this or any other Trend technical publication to [email protected]
© 2015 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control systems LimitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control systems UsA6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 897-3900 Fax:(425) 869-8445 www.trend-americas.com
16set up IC Comms from IQL
17set up IC Comms from IQ
18set up Communications from supervisor
4 CLeAnIng AnD MAInTenAnCeThere are no serviceable parts inside the unit. Cleaning of the unit should be carried out in order to avoid buildup of dust or other contaminents. Disconnect power before carrying out any cleaning.
5 DIsPosAL
3.2 Installation-Configuring (continued)
Weee Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.
IQL LINC
IQ
Nx
K1
W1
S1
K2
K8
W7
W8
I1
I8
S8
Nx
LCI
IC Comms Module nx(.. - (x=1 to y; y=4 for standard strategies)
if required
Parameter Function
A - Remote device address If zero, ‘global to’ comms. If non-zero specifies target device address for ‘data to’ comms
B - AttributeFor ‘global to’ comms only, attribute of target IQ, references attribute in address module (0 ‘no attribute’, - all IQs on Lan,1 ‘identifier’, 2 ‘attribute 2’, 3 ‘attribute 3’)
N - Remote Lan Target IQ Lan number; if Lan zero, address zero, specifies global global
I - Interval Interval between sending (minutes)S - Significant change Amount analogue must change before sendingM - Source item string Item and parameter being sent (e.g. S1(V))E - Destination module number No. of destination module receiving IC commsT - Destination type Type of destn module receiving comms (e.g. W,K)
Use IqlTool2 (see section 3.2 step 5) and text communications
IQL LINC
IQ
Nx
K1
W1
S1
K2
K8
W7
W8
I1
I8
S8
Nx
IC Comms ‘direction’ in IQ must be: global To, Min, Max, sum, or Average (directions 2 to 6)
see: IQ Configuration Manual (90-1531),IQ3 Configuration Manual (TE200768)
if required
LINC
IQK1
W1
S1
K2
K8
W7
W8
I1
I8
S8
IQL
if required
Note that any changes to the strategy parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory.
e.g. 963 (drag and drop values)
Note that standard strategy pages are available for 963 from Partnernet
Use SET and terse text communications
LONWORKS network
LONWORKS network
LONWORKS networkTerse Text Comms
IC Comms
IC Comms