IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 1 Installation Instructions - Mounting IQL11+/xxx/24VAC Important: Retain these instructions These instructions shall be used by trained service personnel only If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. 1 Dimensions 2 Requirements 3 INSTALLATION 1 BOX CONTENTS 2 STORING It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code). CONTENTS 1 Box contents..................................................................1 2 Storing ...........................................................................1 3 Installation .....................................................................1 IQL11+/xxx/24VAC Installation Instructions (TG200233) 3.1 Installation - Mounting ...................................................1 3.2 Installation - configuring ................................................6 4 Cleaning ......................................................................12 5 Disposal .......................................................................12 HO 2 +50 °C (122 °F) 0 -10 °C (-14 °F) 90 %RH 3.1 Installation - Mounting 24V ac LON 1 2 3 4 5 6 7 8 9 10 14 15 16 17 18 1 2 3 4 5 1 11 12 13 3 LON OK SRV PIN C 2 89 mm (3.5”) 75 mm (3”) 185 mm (7.28”) 45 mm (1.77”) WARNING: To reduce the risk of electrical shock or fire do not interconnect the output of different Class 2 circuits. LONMARK ® Terminal Unit Controller continued on next page Note that this product may involve LONWORKS ® system integration as referred to in section 3.2 step 4: this procedure should only be performed by an installer with LONWORKS engineering expertise. 152 mm (5.98”)

Transcript of - Mounting IQL11+/xxx/24VACproducts.ecc.emea.honeywell.com/europe-historic... · HSE Memorandum of...

IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 1

Installation Instructions - Mounting

IQL11+/xxx/24VAC

Important: Retain these instructions

These instructions shall be used by trained service personnel onlyIf the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired.

1 Dimensions

2 Requirements

3 InsTALLATIon

1 Box ConTenTs 2 sToRIng

It is recommended that the installation should comply with the local electrical safety installation practices (e.g. HSE Memorandum of Guidance on Electricity at Work Regulations 1989, USA National Electric Code).

ConTenTs1 Box contents ..................................................................12 Storing ...........................................................................13 Installation .....................................................................1

IQL11+/xxx/24VAC Installation Instructions (TG200233)

3.1 Installation - Mounting ...................................................13.2 Installation - configuring ................................................64 Cleaning ......................................................................125 Disposal .......................................................................12

H O2

+50 °C(122 °F) 0-10 °C

(-14 °F) 90 %RH

3.1 Installation - Mounting

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

89 m

m (3

.5”)

75 mm (3”)

185 mm (7.28”)

45 mm (1.77”)

WARnIng: To reduce the risk of electrical shock or fire do not interconnect the output of different Class 2 circuits.

LonMARK® Terminal Unit Controller

cont inued on next page

Note that this product may involve LONWORKS® system integration as referred to in section 3.2 step 4: this procedure should only be performed by an installer with LONWORKS engineering expertise.

152 mm (5.98”)

2 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015

IQL11+/xxx/24VAC Installation Instructions - Mounting

2 Requirements (Continued)

4Lift Hinged Cover

3Mounting

3.1 Installation - Mounting (continued)

H O2

+45 °C(113 °F)

0

0 °C(32 °F)

90 %RH

Protection: IP20, NEMA 1Altitude: <2000 m (6562’)

Avoid locations where corrosive fumes or explosive vapours are present. Avoid electrical noise interference.

DIN rail end stop

!

IQL

IQL

IQL IQ

L

2 holes

∅ 6 mm(0.24”)

107 mm (6.69”)either surface mount

or DIN rail mount

Failure to use a screwdriver to open the cover will cause damage to the unit.

Must be installed in an enclosure rated to at least IP 20 or equivalent. If DIN rail mounted or switch voltage greater than 30 V. If not DIN rail mounted or switch voltage less than 30 V may be mounted out of an enclosure providing it is out of reach (e.g. in a plenum)

/USA/UL/24VAC only: the unit is UL rated as ‘UL916 listed open energy management equipment’.

IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 3

Installation Instructions - Mounting IQL11+/xxx/24VAC

5Connect Power

6 Connect LonWoRKs bus

3.1 Installation - Mounting (continued)

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

100 � F, 50 V min

100 � F, 50 V min

Terminator

e.g.LONTERMINATOR

LonASCN LonB LonASCN LonB

LINC

A

IQLROUTER

B

IQL

x y

A

IQLROUTER

B

zw

IQL

x y zw

T

T T

4 5 6 7 8 9 10 11

4 5 6 7 8 9 10 11

Maximum 64 nodes per LONWORKS segment Maximum 40 IQLs (and LONCs) per virtual Lan

Recommend terminate at LINC or Router.e.g. use IQLRouter integral terminators

Do noT APPLY PoWeR O

I

� � � � � � � � � � � � � � � � � � � �

� � � � � � � � � �

LONWORKS - FTT (free topology)

Star topologyBus topology

Loop topology

*Terminate LONWORKS bus at one end only

LON

L W

network

ON ORKS L W

network

ON ORKS

14 15

polarity independent

* *

*

Do not allow wires to cross on a loop

cont inued on next page

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

IQL consumption <= 15.4 VAC (9.7 VAC + power to triac outputs)

Terminal size 0.14 to 2.5 mm2 (25 to 14 AWG) For the /USA/UL/24 VAC the input power connections must be made using 18 AWG or larger wire rated at least 90 °C.

Clean earths (grounds) consisting of short (<300 mm, 12”) stranded copper wire (>=1.5 mm2, 16 AWG to a substantial earthed (grounded) metal part (e.g. cable tray) are recommended

The 24V supply must include a suitably rated switch in close proximity and be clearly marked as the disconnecting device for the unit.

The earth on this unit is NOT a protective earth, but it is essential that an earth is fitted for functional reasons.24Vac

24V

ac

16 17 18

Earth (ground) 24 Vac supply neutral at transformerUL listed Class 2

24 VAC transformer

4 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015

IQL11+/xxx/24VAC Installation Instructions - Mounting

6Connect LonWoRKs Bus (continued)

7Connect Inputs and outputs

8Connect Inputs

3.1 Installation - Mounting (continued)

If custom strategy, follow special installation instructions and jump to section 3.1 step 11

Custom Strategy Installation Instructions

If used with LPT-10 (powered bus), cable lengths differ - see “Link Power Transceiver User’s Guide (078-0105-01C)”.

LINC

IQ Outstations

L MON ARK

Device

L W busON ORKS

IQ Outstation

LINC

Normal IQ System current loop Lan cable is not recommendedDo not use screened cable

Terminal size 0.14 to 2.5 mm2 (25 to 14 AWG), for USA/UL/24VAC use 22 to 14 AWG

Cable Max bus length Max node to nodeBelden 85102 500 m (545 yds) 500 m (545 yds)IQ systemTP/1/0/16/HF/200 (Belden 8471)

500 m (545 yds) 400 m (430 yds)

UL Level IV, 22 AWG 500 m (545 yds) 400 m (430 yds)

JY(St) Y2 x 2 x 0.8 500 m (545 yds) 320 m (350 yds)TIA5268A Cat. 5, 24 AWG 450 m (490 yds) 250 m (270 yds)

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

3 21 5 4

TB/TS/K /E

9 10

1

11 12 13

3COM C

2

T

TB/TS ü û û û / ûTB/TS/K ü ü û û / ûTB/TS/KE ü ü ü û / ûTB/TS/KEF ü ü ü ü / ûRD/IQL/K üS ü / û / ûRD/IQL/KOS üS ü ü û / û

RD/IQL/KOSF üS ü ü üS / û

∆TPIR

Cable size 0.14 to 2.5 mm2

(25 to 14 AWG), for USA/UL/24VAC use 22 to 14 AWG - Cu only

9 10

1

11 12 13

3COM C

2

Sensors TB/TS, TB/TS/K, TB/TS/KE, TB/TS/KEF recommended; wire as shown below.

Room Display Module (RD-IQL/K, /KOS, /KOSF) provides monitor and control; wired as shown below:

Note that the IQL must be correctly set up to use the RD‑IQL, see section 4 step 13

Note that terminal types COM and C should not be connected together

Note: These terminals provide power to connected RD product that is within the limits described by EN60950‑1 (table 2B)

Input included in TB or RDs Separate input may be used/ Input either cannot be connected, or will be ignored

Connection of separate device to input required- Sensor or Room Display not applicable to IQL11+

Terminal size 0.14 to 2.5 mm2

(25 to 14 AWG)

pola

rity

inde

pend

ent

RD-IQL

12 13

3C

Window/Pushbutton PIR input

Local SetpointAdjust

Potentiometer

Local SpaceTemperature

sensorWIN/Pb/PIR input type selected by configuration parameters W5/W6

IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 5

Installation Instructions - Mounting IQL11+/xxx/24VAC

9Connect Heat/Cool outputs

10Connect Fan outputs

11Close Hinged Cover

12Close enclosure

3.1 Installation - Mounting (continued)

Heat/Cool

Damper

Ra

ise

Lo

we

r

Com

mon

not used

3 4 5 6 7 8

2 3 4 524V 24V

not used

Ra

ise

Lo

we

r

Co

mm

on

Heat or Cool

Valve

~24V

32 4 5

3 4 5 6 7 8

~24V

Rais

e

Lo

we

r

Com

mon

Rais

e

Lo

we

r

Com

mon

Cool ValveHeat Valve

~24V

32 4 5

3 4 5 6 7 8

~24V

Heat or

Cool

Valv

e

not used

~24V

32 4 5

3 4 5 6 7 8

~24V

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

Cool ValveHeat Valve

~24V

32 4 5

3 4 5 6 7 8

~24V

(24 Vac, 400 mA maximum shared between all triac outputs used)

/AR2 /WR2 /WR4 /WT2 /WT4

cable size 0.14 to 2.5 mm2 (25 to 14 AWG),for USA/UL/24VAC use 22 to 14 AWG - Cu only

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

WARnIng: The wires may be connected to hazardous voltages. Disconnect power before attempting any wiring.

5 A maximum @240 Vac resistive or inductive (cosø>=0.4)5A @ 24 Vdc (resistive), 2 A @ 24 Vdc (inductive, T<=30 mS)

Arc suppression (TG200208)

cable size 0.14 to 2.5 mm2 (25 to 14 AWG), for USA/UL/24VAC use 22 to 14 AWG- Cu only

Fan

1

1 2

UL rating applies up to 30V

6 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015

IQL11+/xxx/24VAC Installation Instructions - Mounting

1Tear off Label strip

2 switch on

3Check IQL/LInC on LonWoRKs network

4Install using LonWoRKs network Management Tool

LINC

IQ Outstations

L MON ARK

Device

L W busON ORKS

IQ Outstation

LINC

3.2 Installation-Configuring

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

O

I

(Check LONWORKS network LINCs)

LON OK (green)Flashes every 24 s, ON after 1½ mins

Flashes every 1 s (Deaf IQL. Check LONWORKS network)

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

MAC Addr 00.10.70.00.UD.BBS/No:

Q3B____X73010003

IP Addr Location

‘locate’

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

See LONWORKS network management tool manual. See IQ System LONWORKS Products Engineering Manual (TE200292). LONWORKS System Integrator must have LONWORKS engineering expertise.a). When installing IQL in LONWORKS tool, press service

button when requested.

b). The IQL network image can be obtained from www.lonmark.org, or from www.pnet.trend-controls.com.

c). Set up bindings if required (bind network variables between IQL and LONMARK devices).

If a binding IQLs to LONMARK devicesor b LINCs version <3.23 straddle routeror c other devices have address conflicts with IQ System devicesor d IQLROUTERs used on installed system

SRV PINservice button

LINC

L WnetworkON ORKS

IQL

LONMARKdevice

If one IQ System LONWORKS device is installed, all must be installed.

IQL13+ Data Sheet (TA200113) for LONWORKS network variables (NVs)

O/SLAN

NID

Strategy

Serial No

117 027

00:A0:25:36:51:00

IQL1x WR4 E 06

IQL1xWR4_50100025

IQL1xWR4_50100025

NID

Serial No

00:A0:25:36:51:00

Serial No

IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 7

Installation Instructions - Mounting IQL11+/xxx/24VAC

5Connect software Tool for Commissioning

3.2 Installation-Configuring (continued)

LCI

IQL

if required

IqlTool2 Manual (TE200185)LCI/USB Installation Instructions(TG200817)SET Manual (TE200147)

IqlTool2 (SET)IqlTool2 runs within SETV5.1 (or later)

USB cable supplied with LCI/USB

LONWORKS adaptor cable supplied with LCI/USB Note that a PIN may be required to make

changes. If the PIN has been forgotten the users should contact their supplier (installers contact Technical Support) quoting the generator number and neuron id (both from Address module)

whereupon a default PIN will be supplied. This will only work for three attempts at entering the PIN. After the default PIN is entered a new PIN should be set up and remembered.

7Test Input/output Functionality

6switch on

Custom Strategy Installation Instructions

If custom strategy follow special installation instructions and jump to section 3.2 step 13.

LCI

IQL

If IqlTool2 available

IqlTool2 Manual (TE200185)

Use IqlTool2 to monitor inputs and exercise outputsIqlTool2(SET)

Note that IqlTool2 may also be used for mapping the LONWORKS segment, resolving duplicate addresses on a LONWORKS network, water balancing (/WR2, /WR4, /WT2, /WT4 only), identification via service button, associating with SDU‑LON (for other uses see later)

LONWORKS network

LONWORKS network

8 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015

IQL11+/xxx/24VAC Installation Instructions - Mounting

8Check strategy, sensor/Fan/Heat Cool outputs/electric Heater

/AR2 /WR2 /WR4 /WT2 /WT4

3.2 Installation-Configuring (continued)

�� � �

�� � �

�� � �

� � �

heat

� � �

cool

OUT2,3damper

OUT2,3damper

OUT2,3

If W2=0(Winter Mode)

heating

OUT2,3If W2=1(Summer Mode)

cooling

OUT2,3

heat valve

OUT4,5

cool valve

OUT2If W2=0(Winter Mode)

heating

OUT2If W2=1(Summer Mode)

cooling

OUT2

heat valve

OUT4

cool valve

�� � �

�� � �

�� � �

�� � �

�� � �

� � �

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

S

S

In1

oUT1heat

� � �

cool

If Fan Speed Auto

IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 9

Installation Instructions - Mounting IQL11+/xxx/24VAC

9 Check operation - Window Contact Input

10Check operation - Pushbutton or PIR Input 11

Check operation- Local sP Adjust

/AR2 /WR2 /WR4 /WT2 /WT4

3.2 Installation-Configuring (continued)

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

Window

fan off

IN3 OUT1

if Window Mode (W5=1)

� � �

heat

� � �

cool

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

PIR if in standby

Pushbuttonif non-occupied or standby

fan on

24V

acLON

1 2 3 4 5 6 7 8 9 10 14 15 16 17 18

1 2 3 4 5 1

11 12 13

3COM

LON

OK

SRV

PINC

24V 24V 2

Local adjustment can be provided by TB/TS/K, /KE, /KEF or RD-IQL/K, /KOS, /KOSF (see section 3.1 step 8).

If Fan Speed Auto

If Fan Speed Auto

IN4 OUT1OUT1

IN2

Pb/PIR input type selected by configuration parameterW6 - see section 3.2 step 12.

see table section 3.2 step 8

Pushbutton can be provided by TB/TS/KE, /KEF, or RD-IQL/KOS, /KOSF (see section 3.1 step 8)

� � �

heat

� � �

cool

see table section 3.2 step 8

Wait 6 secs at each end to calibrate potentiometer

�� � �

� � �

heat

� � �

cool

OUT2,3damper

OUT2,3

valve closes

�� � �

OUT2,3heat valve

�� � �

OUT4,5

cool valve

OUT2 OUT2

damper goes to neutral

�� � �

valve closes

�� � �

heat valve

�� � �

cool valve

OUT4

10 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015

IQL11+/xxx/24VAC Installation Instructions - Mounting

13set up strategy Parameters if required Use IqlTool2 (see section 3.2 step 5) and text

communications

For standard strategies use table below, else refer to custom strategy installation instructions

4 Installation-Configuring (continued)

Parameter Label Function Defaults

/UK/ /USA/UL

K1(V) Remote Setpoint Base setpoint can be adjusted remotely 20 °C 68 °F

K2(V) RemoteSpaceTemp Used if bound to LONWORKS sensor, or if local sensor disconnected 20 °C 68 °F

K3(V) OCC Deadbnd Deadband around setpoint during Occ 1 °C 2 °F

K4(V) Standby Deadbnd Deadband around setpoint during Standby 2 °C 4 °F

K5(V) NOCC Deadbnd Deadband around setpoint during Nocc 12 °C 22 °F

K6(V) Remote Occ Sets state 0=Occ, 1=Nocc, 2=Bypass, 3=Standby 0=Occupied

K8(V) Remote SP Offset Used if bound to a LONWORKS Sensor or if local adjust is disconnected 0 °C 0 °F

K13(V) Pb PIR Run On Time switched into occupancy for PIR or Pb input 1800 s (30 mins)

K15(V) Offset Range Defines range of Local SP adjust pot. 2 °C 2 °F

W1(S) O=4Pipe I=2Pipe Strategy change W1=O(WR4, WT4, AR2) W1=I(WR2, WT2) *

W2(S) Summer Mode Winter (heat only) or Summer (cool only) (only used for /WR2, /WT2) O=Winter

W4(S) O=Water I=Air Strategy change W4=O(WR, WT) W4=I (AR2) *

W5(S) Window Mode Window contact if set to I, PIR or Pb if set to O O=alarm contact

W6(S) O=Pb I=PIR PIR if set to I, Pushbutton if set to O O=pushbutton

W7(S) Frost Condition Overrides heating to 100 % (not /AR2) if unoccupied O=no frost

W8(S) Remote Shutdown Shuts off fan, and sets heat/cool to zero O=no shutdown

L1(G) Heat Loop Gain 20 20

L1(I) Heat Loop Integral 10 mins 10 mins

L2(G) Cool Loop Gain -20 -20

L2(I) Cool Loop Integral 10 mins 10 mins

If required the strategy type may be changed (e.g. /AR2 to /WR2): IQL11+/xxx data sheet (TA200245)

Note that any changes to the strategy parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory

* Default depends on strategy

If used with RD-IQL (see section 3.1 step 8), the following must be configured: Local space Temp Type s9(Y=6), Local sP Adjust Type s10(Y=6), Window Mode W5(s=o) default, o=Pb I=PIR W6(s=o) default followed by R(z=1) to write changestoflashandreset. Configuration for RD-IQL is facilitated by IqlTool2.

If the sensor on IN2 is to be used, leave Local Space Temp Type at default S9(Y=1)

Note that for AR2, WR2, WR4 strategies D2 and D3 full scale drive times should not be greater than 262s.

IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015 11

Installation Instructions - Mounting IQL11+/xxx/24VAC

14set up system Core Firmware Module Parameters

15set up Lan system

Using IqlTool2 (see section 4 step 5) and text communications

if required - see conditions

LINC Installation Instructions (TG103062)

LINC

IQ

L WON ORKS

networkIQL

Check Lan

if required

IQ System LONWORKS Products Engineering Manual - (TE200292)

Use SET and terse text communications

SET

4 Installation-Configuring (continued)

Parameter setting Function Condition noteR(..address L - own address device address of IQL if required to rearrange

Lans, address1, 2, 4

N - own LaN Lan number of IQL if required to rearrange Lans, address

1, 2

D - identifier identifier attribute of IQL For alarm ident, text comms, IC comms

1

F - attribute 2 text comms attributes For text comms, IC comms 1G - attribute 3 1A - own Lan alarm address address and Lan of

own Lan alarm targetto report Lan alarms to a supervisor

1R - Own Lan alarm Lan 1E - Internetwork alarm address

address and Lan of Internetwork alarm target

to report internetwork alarms to a supervisor (only for lowest addressed IQ System device on Lan)

1

T - Internetwork alarm Lan 1

r - LONWORKS retry time See IQ System LONWORKS Products Engineering Manual for details

2i - LONWORKS interpacket delay

2

a - LONWORKS service class 2b - router Buffer size buffer size

(bytes) Default = 146

specifies smallest router buffer on system

If routers separate IQLs/LINCs/LONCs and have buffer size smaller that 146 bytes - set to smallest buffer size. (minimum = 66)

2

m - LONWORKS Message code

code number. Default = 64

Code used by IQLs/LINCs/LONCs, all LINCs/LONCs must use same code

If message code being used by other users - must be exclusive to IQ System

2, 5

g - generator number To find PIN if lost (read only)e - Neuron chip id unique identifier

for Neuron®To find PIN if lost; to identify LONWORKS node

(read only)

T(..Time H - Hours Current time To synchronise time for alarms and loggingN - Minutes

D - Day of month Current date To synchronise date for alarms and logging

3M - Month 3Y - Year 3l - Lan of system timemaster IQL timekeeper gets

time sync from IQ at address 11 on this Lan

IQL will be timekeeper If this ‘l’ parameter is non-zero and own address = 11

3, 4

U1(..User P - PIN PIN number in IQ To protect from unauthorised changes

3, 6

l -level authority level of PIN No protection if zero 3

Note 1: IqlTool2 facilitates setting of these parameters across the LONWORKS segmentNote 2: Changing any of these parameters results in a controller reset (clears down time and and sensor logs)Note 3: Any changes to these parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory.Note 4: IqlTool2 facilitates setting to timekeeper (sets up timemaster Lan and changes own address to 11)Note 5: Message code can only be changed by text comms if ‘lonworks managed’ (read only) is set to No.Note 6: If PIN is forgotten see note in section 3.2 step 5

12 IQL11+/xxx/24VAC Installation Instructions TG200233 Issue 14, 28-Jan-2015

IQL11+/xxx/24VAC Installation Instructions - Mounting

Please send any comments about this or any other Trend technical publication to [email protected]

© 2015 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control systems LimitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control systems UsA6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 897-3900 Fax:(425) 869-8445 www.trend-americas.com

16set up IC Comms from IQL

17set up IC Comms from IQ

18set up Communications from supervisor

4 CLeAnIng AnD MAInTenAnCeThere are no serviceable parts inside the unit. Cleaning of the unit should be carried out in order to avoid buildup of dust or other contaminents. Disconnect power before carrying out any cleaning.

5 DIsPosAL

3.2 Installation-Configuring (continued)

Weee Directive:At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.

IQL LINC

IQ

Nx

K1

W1

S1

K2

K8

W7

W8

I1

I8

S8

Nx

LCI

IC Comms Module nx(.. - (x=1 to y; y=4 for standard strategies)

if required

Parameter Function

A - Remote device address If zero, ‘global to’ comms. If non-zero specifies target device address for ‘data to’ comms

B - AttributeFor ‘global to’ comms only, attribute of target IQ, references attribute in address module (0 ‘no attribute’, - all IQs on Lan,1 ‘identifier’, 2 ‘attribute 2’, 3 ‘attribute 3’)

N - Remote Lan Target IQ Lan number; if Lan zero, address zero, specifies global global

I - Interval Interval between sending (minutes)S - Significant change Amount analogue must change before sendingM - Source item string Item and parameter being sent (e.g. S1(V))E - Destination module number No. of destination module receiving IC commsT - Destination type Type of destn module receiving comms (e.g. W,K)

Use IqlTool2 (see section 3.2 step 5) and text communications

IQL LINC

IQ

Nx

K1

W1

S1

K2

K8

W7

W8

I1

I8

S8

Nx

IC Comms ‘direction’ in IQ must be: global To, Min, Max, sum, or Average (directions 2 to 6)

see: IQ Configuration Manual (90-1531),IQ3 Configuration Manual (TE200768)

if required

LINC

IQK1

W1

S1

K2

K8

W7

W8

I1

I8

S8

IQL

if required

Note that any changes to the strategy parameters should immediately be followed by a write to the address module, [text comms command, R(z=0), recommended], to commit changes to flash memory.

e.g. 963 (drag and drop values)

Note that standard strategy pages are available for 963 from Partnernet

Use SET and terse text communications

LONWORKS network

LONWORKS network

LONWORKS networkTerse Text Comms

IC Comms