Motor Starters

37
Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any questions. Motor Starters 48 Motor Starters Explosionproof, Dust-Ignitionproof, Watertight CEB Series Bolted Combination & Non-Combination Full Voltage .............................................. 49 Catalog Numbering Logic.................................................. 50 Enclosures Selection Table ............................................... 51 Motor Starter Selection Tables ......................................... 52 Combination Lighting Contactor Selection Tables .......... 62 Enclosure Dimensions ....................................................... 64 Typical Wiring Diagrams .................................................... 73 Modifications ...................................................................... 76 Combination & Non-Combination Full Voltage.................. 77 Selection Tables ................................................................. 78 Dimensions ......................................................................... 80 CSE Series Manual Motor Starters ..................................... 81 Manual Motor Starter Heater Selection Table ................. 82 CESMS Series Manual Motor Starters ............................... 83 Selection Table and Dimensions ...................................... 84

Transcript of Motor Starters

Page 1: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.

Mot

or S

tart

ers

48

Motor StartersExplosionproof, Dust-Ignitionproof, Watertight

CEB Series Bolted Combination & Non-Combination Full Voltage ..............................................49

Catalog Numbering Logic ..................................................50Enclosures Selection Table ...............................................51Motor Starter Selection Tables .........................................52Combination Lighting Contactor Selection Tables ..........62Enclosure Dimensions .......................................................64Typical Wiring Diagrams ....................................................73Modifications ......................................................................76

Combination & Non-Combination Full Voltage ..................77

Selection Tables .................................................................78Dimensions .........................................................................80

CSE Series Manual Motor Starters .....................................81

Manual Motor Starter Heater Selection Table .................82

CESMS Series Manual Motor Starters ...............................83

Selection Table and Dimensions ......................................84

Page 2: Motor Starters

49Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Bolted Combination & Non-Combination Full VoltageExplosionproof, Dust-Ignitionproof, Watertight

These units provide disconnecting means, circuit and motor running protection.

Application• Combination and Non-Combination motor starters are

used in areas where hazardous materials are handled or stored. These units provide disconnecting means, circuit protection, and motor running protection.

Features• 65,000 AIC. Highest interrupt rated enclosure in

the industry.

• Copper-free cast aluminum.

• Precision machined flame path between box and cover.

• Bolt on slotted mounting feet.

• Stainless steel block hinges.

• Stainless steel, captive Quad-Lead cover bolts (disengaged in 1½” turns).

• External stainless steel breaker operating handle.

• Breaker and operator shafts are stainless steel.

• Ground lug package and installation instructions for termination of ground wire enclosed.

• Four point control terminal block, NEMA 1B with wire markers.

• Breaker operators can be locked in the “On” or “Off” position (combination starters only).

• Four plugged ¾” NPSM outlets drilled and tapped for control devices.

• Standard outlets top and bottom.

• Plugged ½” outlets top and bottom for breather/drain.

• Components are mounted on a galvanized steel removable pan.

• Enclosures are designed to accept Cutler-Hammer1, or Square D2 motor starters/circuit breakers. For other manufacturers, consult factory.

• O-ring Gasket insures watertight integrity.

Standard Materials• Bodies and covers: copper-free aluminum.

• Cover bolts: stainless steel.

• O-ring: neoprene.

• Hinges: stainless steel.

Standard Finish• Corrosion resistant grey powder coat epoxy inside & out.

Compliances• UL Standard 1203 and 1604

• CSA Certified - Standard C22.2 No 30

• NEMA 4, 4X, 7BCD, 9EFG

1. Cutler-Hammer® is a trademark of the Eaton Corporation.2. Square D is a trademark of Schneider Electric.

Page 3: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.50

6 Motor Starters

Sample Catalog NumberExample: The part number below depicts a Curlee, Class I, Div. I, Groups B, C & D, NEMA Size 1, Bolted type, Combination Full Voltage Non-Reversing Motor Starter operating at 480 VAC, Cutler-Hammer1 starter w/120 VAC control voltage, and a Cutler-Hammer1 7A MCP. If a breaker is not required, omit last two characters.

CE 1 B B 4 W 1 C 2 * Suffix for Other Options/Features (See Modifi cations on Page 76)

Breaker Trip (MCP) 1 = 3A 4 = 30A 7 = 100A 0 = 400A 2 = 7A 5 = 50A 8 = 150A 3 = 15A 6 = 70A 9 = 250A Breaker Trip (Thermal Mag) A = 15A F = 40A M = 90A S = 200A X = 400A B = 20A G = 50A N = 100A T = 225A C = 25A H = 60A P = 125A U = 250A D = 30A J = 70A Q = 150A V = 300A E = 35A K = 80A R = 175A W = 350A

Breaker Manufacturer C=Cutler-Hammer1 S=Square D2

(Consult factory for other manufacturers)

Control Voltage (120 V coil standard) (1) 1 = 120 V 4 = 480 V 7 = 24 VDC 2 = 240 V 5 = 575 V 8 = 48 VDC 3 = 380 V 6 = 600 V Starter Manufacturer W=Cutler-Hammer1 (A200) S=Square D2 (8536) (Consult factory for other manufacturers)

Operating Voltage 1 = 120 V 4 = 480 V 7 = 24 VDC 2 = 240 V 5 = 575 V 8 = 48 VDC 3 = 380 V 6 = 600 V Starter Function A=FVNR (ATL) G=2S2W B=Comb. FVNR H=Comb. 2S2W C=FVR J=Contactor (3 pole) D=Comb. FVR K=Comb. Contactor (3 pole) E=2S1W M=Lighting Contactor (3-12 pole) F=Comb. 2S1W N=Comb. Lighting Contactor (3-12 pole) (Consult factory for enclosure layouts on starter functions C, D, E, F, G & H) Enclosure Type B Series NEMA Size (0, 1, 2, 3, 4 & 5) (For Size 6, consult factory) Series CE Note: 120 V power must be provided from separate source, or by adding CPT option.

1. Cutler-Hammer® is a trademark of the Eaton Corporation.

2. Square D is a trademark of Schneider Electric.

CEB Series Catalog Numbering Logic

Page 4: Motor Starters

51Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Motor Starter Enclosures Explosionproof, Dust-Ignitionproof, WatertightNon-Reversing Bolted Enclosure

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Selection Tables

Combination Full Voltage Non-Reversing Enclosure Only

NEMA Max Catalog Approx. Standard Mounting Hardware Size HP Number Weight (lbs) Conduit Set Catalog Number

0 3 CE0BB 125 1½” CMH7 1 7½ CE1BB 125 1½” CMH7 2 15 CE2BB 125 1½” CMH7 3 30 CE3BB 195 2½” CMH7 4 50 CE4BB 195 2½” CMH7 5 100 CE5BB 500 4” CMH8

Full Voltage Non-Reversing Enclosure Only

NEMA Max Catalog Approx. Standard Mounting Hardware Size HP Number Weight (lbs) Conduit Set Catalog Number

0 3 CE0BA 80 1½” CMH7 1 7½ CE1BA 80 1½” CMH7 2 15 CE2BA 85 1½” CMH7 3 30 CE3BA 140 2” CMH7 4 50 CE4BA 140 2½” CMH7 5 100 CE5BA 500 4” CMH8

Page 5: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.52

6 Motor Starters

CB Series Full VoltageExplosionproof, Dust-Ignitionproof, Watertight3 Phase, 60 Hz, Non-Reversing (Across-the-Line), 120V Coil Cutler-Hammer®, Bolted Enclosure

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Line NEMA Max Amp Catalog Approx. Standard Mounting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 3 NA CE0BA2W1 80 1½” CMH7 1 7½ NA CE1BA2W1 80 1½” CMH7 240 2 15 NA CE2BA2W1 85 1½” CMH7 3 30 NA CE3BA2W1 140 2” CMH7 4 50 NA CE4BA2W1 140 2½” CMH7 5 100 NA CE5BA2W1 500 4” CMH8

0 5 NA CE0BA4W1 80 1½” CMH7 1 10 NA CE1BA4W1 80 1½” CMH7 480 2 25 NA CE2BA4W1 85 1½” CMH7 3 50 NA CE3BA4W1 140 2” CMH7 4 100 NA CE4BA4W1 140 2½” CMH7 5 200 NA CE5BA4W1 500 4” CMH8

0 5 NA CE0BA6W1 125 1½” CMH7 1 10 NA CE1BA6W1 125 1½” CMH7 600 2 25 NA CE2BA6W1 130 1½” CMH7 3 50 NA CE3BA6W1 195 2” CMH7 4 100 NA CE4BA6W1 195 2½” CMH7 5 200 NA CE5BA6W1 500 4” CMH8

Selection Table

Page 6: Motor Starters

53Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Combination Full Voltage Explosionproof, Dust-Ignitionproof, Watertight3 Phase, 60 Hz, Non-Reversing, 120V Coil Cutler-Hammer®, Bolted Enclosure

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Selection Table

Line NEMA Max Amp Catalog Approx. Standard Mounting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 2 15 CE0BB2W1CA 125 1½” CMH7 0 3 20 CE0BB2W1CB 125 1½” CMH7 1 5 40 CE1BB2W1CF 125 1½” CMH7 1 7½ 50 CE1BB2W1CG 125 1½” CMH7 2 10 50 CE2BB2W1CG 130 1½” CMH7 2 15 100 CE2BB2W1CL 130 1½” CMH7 240 3 20 100 CE3BB2W1CL 195 2½” CMH7 3 30 125 CE3BB2W1CM 195 2½” CMH7 4 40 175 CE4BB2W1CR 195 2½” CMH7 4 50 200 CE4BB2W1CS 195 2½” CMH7 5 60 250 CE5BB2W1CU 500 4” CMH8 5 75 300 CE5BB2W1CV 500 4” CMH8 5 100 400 CE5BB2W1CX 500 4” CMH8

0 3 15 CE0BB4W1CA 125 1½” CMH7 0 5 20 CE0BB4W1CB 125 1½” CMH7 1 7½ 30 CE1BB4W1CD 125 1½” CMH7 1 10 35 CE1BB4W1CE 125 1½” CMH7 2 20 50 CE2BB4W1CG 130 1½” CMH7 2 25 70 CE2BB4W1CJ 130 1½” CMH7 480 3 50 100 CE3BB4W1CN 195 2½” CMH7 3 60 125 CE3BB4W1CP 195 2½” CMH7 4 75 150 CE4BB4W1CQ 195 2½” CMH7 4 100 200 CE4BB4W1CS 195 2½” CMH7 5 125 250 CE5BB4W1CU 500 4” CMH8 5 150 300 CE5BB4W1CV 500 4” CMH8 5 200 400 CE5BB4W1CX 500 4” CMH8

0 5 15 CE0BB6W1CA 125 1½” CMH7 1 7½ 20 CE1BB6W1CB 125 1½” CMH7 1 10 30 CE1BB6W1CD 125 1½” CMH7 2 15 40 CE2BB6W1CF 130 1½” CMH7 2 25 50 CE2BB6W1CG 130 1½” CMH7 600 3 30 70 CE3BB6W1CJ 195 2½” CMH7 3 50 100 CE3BB6W1CN 195 2½” CMH7 4 75 125 CE4BB6W1CP 195 2½” CMH7 4 100 150 CE4BB6W1CQ 195 2½” CMH7 5 150 250 CE5BB6W1CU 500 4” CMH8 5 200 300 CE5BB6W1CV 500 4” CMH8

Page 7: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.54

6 Motor Starters

CEB Series Combination Full Voltage with Motor Circuit Protector3 Phase, 60 Hz, Non-Reversing, 120V Coil Cutler-Hammer®, Bolted Enclosure

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Selection Table

Line NEMA Max Amp Catalog Approx. Standard Mounting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 1 7 CE0BB2W1C2 125 1½” CMH7 0 3 15 CE0BB2W1C3 125 1½” CMH7 1 7 30 CE1BB2W1C4 125 1½” CMH7 240 2 15 50 CE2BB2W1C5 130 1½” CMH7 3 30 100 CE3BB2W1C7 195 2½” CMH7 4 50 150 CE4BB2W1C8 195 2½” CMH7 5 100 400 CE5BB2W1C0 500 4” CMH8

0 1 3 CE0BB4W1C1 125 1½” CMH7 0 3 7 CE0BB4W1C2 125 1½” CMH7 0 5 15 CE0BB4W1C3 125 1½” CMH7 1 7 15 CE1BB4W1C3 125 1½” CMH7 1 10 30 CE1BB4W1C4 130 1½” CMH7 480 2 12 30 CE2BB4W1C4 130 1½” CMH7 2 25 50 CE2BB4W1C5 130 1½” CMH7 3 30 50 CE3BB4W1C5 195 2½” CMH7 3 50 100 CE3BB4W1C7 195 2½” CMH7 4 100 150 CE4BB4W1C8 195 2½” CMH7 5 200 400 CE5BB4W1C0 500 4” CMH8

0 1 3 CE0BB6W1C1 125 1½” CMH7 0 3 7 CE0BB6W1C2 125 1½” CMH7 0 5 15 CE0BB6W1C3 125 1½” CMH7 1 7 15 CE1BB6W1C3 125 1½” CMH7 1 10 30 CE1BB6W1C4 125 1½” CMH7 600 2 20 30 CE2BB6W1C4 130 1½” CMH7 2 25 50 CE2BB6W1C5 130 1½” CMH7 3 40 50 CE3BB6W1C5 195 2½” CMH7 3 50 100 CE3BB6W1C7 195 2½” CMH7 4 60 100 CE4BB6W1C7 195 2½” CMH7 4 100 150 CE4BB6W1C8 195 2½” CMH7 5 200 400 CE5BB6W1C0 500 4” CMH8

Page 8: Motor Starters

55Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Full Voltage3 Phase, 60 Hz, Reversing, 120V Coil Cutler-Hammer®, Bolted Enclosure

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Selection Table

Line NEMA Max Amp Catalog Approx. Standard Mounting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 3 NA CE0BC2W1 115 1½” CMH7 1 7½ NA CE1BC2W1 115 1½” CMH7 240 2 15 NA CE2BC2W1 125 1½” CMH7 3 30 NA CE3BC2W1 300 2” CMH8 4 50 NA CE4BC2W1 300 2½” CMH8

0 5 NA CE0BC4W1 115 1½” CMH7 1 10 NA CE1BC4W1 115 1½” CMH7 480 2 25 NA CE2BC4W1 125 1½” CMH7 3 50 NA CE3BC4W1 300 2” CMH8 4 100 NA CE4BC4W1 300 2½” CMH8

0 5 NA CE0BC6W1 115 1½” CMH7 1 10 NA CE1BC6W1 115 1½” CMH7 600 2 25 NA CE2BC6W1 125 1½” CMH7 3 50 NA CE3BC6W1 300 2” CMH8 4 100 NA CE4BC6W1 300 2½” CMH8

Page 9: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.56

6 Motor Starters

CEB Series Combination Full Voltage with Thermal Magnetic Circuit Breaker3 Phase, 60 Hz, Reversing, 120V Coil Cutler-Hammer® Bolted Enclosure

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Line NEMA Max Amp Catalog Approx. Standard Mounting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 2 15 CE0BD2W1CA 120 1½” CMH7 0 3 20 CE0BD2W1CB 120 1½” CMH7 1 5 35 CE1BD2W1CE 120 1½” CMH7 1 7½ 50 CE1BD2W1CG 120 1½” CMH7 240 2 10 50 CE2BD2W1CG 135 1½” CMH7 2 15 100 CE2BD2W1CN 135 1½” CMH7 3 20 100 CE3BD2W1CN 320 2½” CMH8 3 30 125 CE3BD2W1CP 320 2½” CMH8 4 50 200 CE4BD2W1CS 320 2½” CMH8

0 3 15 CE0BD4W1CA 120 1½” CMH7 0 5 20 CE0BD4W1CB 120 1½” CMH7 1 7½ 30 CE1BD4W1CD 120 1½” CMH7 1 10 35 CE1BD4W1CE 120 1½” CMH7 2 20 50 CE2BD4W1CG 135 1½” CMH7 480 2 25 70 CE2BD4W1CJ 135 1½” CMH7 3 50 100 CE3BD4W1CN 320 2½” CMH8 3 60 125 CE3BD4W1CP 320 2½” CMH8 4 75 150 CE4BD4W1CQ 320 2½” CMH8 4 100 200 CE4BD4W1CS 320 2½” CMH8

0 5 15 CE0BD6W1CA 120 1½” CMH7 1 7½ 20 CE1BD6W1CB 120 1½” CMH7 1 10 30 CE1BD6W1CD 120 1½” CMH7 2 15 40 CE2BD6W1CF 135 1½” CMH7 600 2 25 50 CE2BD6W1CG 135 1½” CMH7 3 30 70 CE3BD6W1CJ 320 2½” CMH8 3 50 100 CE3BD6W1CN 320 2½” CMH8 4 75 125 CE4BD6W1CP 320 2½” CMH8 4 100 150 CE4BD6W1CQ 320 2½” CMH8

Selection Table

Page 10: Motor Starters

57Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Combination Full Voltage with Motor Circuit Protector3 Phase, 60 Hz, Reversing, 120V Coil Cutler-Hammer®, Bolted Enclosure

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Line NEMA Max Amp Catalog Approx. Standard Mounting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 1 7 CE0BD2W1C2 120 1½” CMH7 0 3 15 CE0BD2W1C3 120 1½” CMH7 240 1 7 30 CE1BD2W1C4 120 1½” CMH7 2 15 50 CE2BD2W1C5 135 1½” CMH7 3 30 100 CE3BD2W1C7 320 2½” CMH8 4 50 150 CE4BD2W1C8 320 2½” CMH8 0 1 3 CE0BD4W1C1 120 1½” CMH7 0 3 7 CE0BD4W1C2 120 1½” CMH7 0 5 15 CE0BD4W1C3 120 1½” CMH7 1 7 15 CE1BD4W1C3 120 1½” CMH7 480 1 10 30 CE1BD4W1C4 135 1½” CMH7 2 15 30 CE2BD4W1C4 135 1½” CMH7 2 25 50 CE2BD4W1C5 135 1½” CMH7 3 30 50 CE3BD4W1C5 320 2½” CMH8 3 50 100 CE3BD4W1C7 320 2½” CMH8 4 100 150 CE4BD4W1C8 320 2½” CMH8 0 1 3 CE0BD6W1C1 120 1½” CMH7 0 3 7 CE0BD6W1C2 120 1½” CMH7 0 5 15 CE0BD6W1C3 120 1½” CMH7 1 7 15 CE1BD6W1C3 120 1½” CMH7 1 10 30 CE1BD6W1C4 120 1½” CMH7 600 2 20 30 CE2BD6W1C4 135 1½” CMH7 2 25 50 CE2BD6W1C5 135 1½” CMH7 3 40 50 CE3BD6W1C5 320 2½” CMH8 3 50 100 CE3BD6W1C7 320 2½” CMH8 4 60 100 CE4BD6W1C7 320 2½” CMH8 4 100 150 CE4BD6W1C8 320 2½” CMH8

Selection Table

Page 11: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.58

6 Motor Starters

CEB Series Full VoltageTwo Speed Single Winding, 5 Pole-3 Pole, 3 Phase, 60 Hz, 120V Coil, Cutler-Hammer®.

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Line NEMA Max Amp Catalog Approx. Standard Mouting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 3 NA CE0BE2W1 85 1½” CMH7 1 7½ NA CE1BE2W1 85 1½” CMH7 240 2 15 NA CE2BE2W1 190 1½” CMH7 3 30 NA CE3BE2W1 540 2” CMH8 4 50 NA CE4BE2W1 540 2½” CMH8

0 5 NA CE0BE4W1 85 1½” CMH7 1 10 NA CE1BE4W1 85 1½” CMH7 480 2 25 NA CE2BE4W1 190 1½” CMH7 3 50 NA CE3BE4W1 540 2” CMH8 4 100 NA CE4BE4W1 540 2½” CMH8

0 5 NA CE0BE6W1 85 1½” CMH7 1 10 NA CE1BE6W1 85 1½” CMH7 600 2 25 NA CE2BE6W1 190 1½” CMH7 3 50 NA CE3BE6W1 540 2” CMH8 4 100 NA CE4BE6W1 540 2½” CMH8

With Thermal Magnetic Circuit Breaker Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, G Class III NEMA 4, 4X, 7BCD, 9EFG

Line NEMA Max Amp Catalog Approx. Standard Mtg Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 3 20 CE0BF2W1CB 130 1½” CMH7 1 7½ 50 CE1BF2W1CG 130 1½” CMH7 240 2 15 100 CE2BF2W1CN 195 1½” CMH7 3 30 125 CE3BF2W1CP 545 2½” CMH8 4 50 200 CE4BF2W1CS 545 2½” CMH8

0 5 20 CE0BF4W1CB 130 1½” CMH7 1 10 40 CE1BF4W1CF 130 1½” CMH7 480 2 25 70 CE2BF4W1CJ 195 1½” CMH7 3 50 100 CE3BF4W1CN 545 2½” CMH8 4 100 200 CE3BF4W1CS 545 2½” CMH8

0 5 20 CE0BF6W1CB 130 1½” CMH7 1 10 30 CE1BF6W1CD 130 1½” CMH7 600 2 25 50 CE2BF6W1CG 195 1½” CMH7 3 50 100 CE3BF6W1CN 545 2½” CMH8 4 100 150 CE3BF6W1CQ 545 2½” CMH8

Selection Table

Selection Table

Page 12: Motor Starters

59Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Combination Full Voltagewith MCPTwo Speed Single Winding, 5 Pole - 3 Pole, 3 Phase, 60 Hz,

120V Coil Cutler-Hammer®

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Line NEMA Max Amp Catalog Approx. Standard Mounting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 1 7 CE0BF2W1C2 130 1½” CMH7 0 3 15 CE0BF2W1C3 130 1½” CMH7 240 1 7½ 30 CE1BF2W1C4 130 1½” CMH7 2 15 50 CE2BF2W1C5 195 1½” CMH7 3 30 100 CE3BF2W1C7 545 2½” CMH8 4 50 150 CE4BF2W1C8 545 2½” CMH8

0 1 3 CE0BF4W1C1 130 1½” CMH7 0 3 7 CE0BF4W1C2 130 1½” CMH7 0 5 15 CE0BF4W1C3 125 1½” CMH7 1 7½ 15 CE1BF4W1C3 125 1½” CMH7 480 1 10 30 CE1BF4W1C4 130 1½” CMH7 2 15 30 CE2BF4W1C4 195 1½” CMH7 2 25 50 CE2BF4W1C5 195 1½” CMH7 3 30 50 CE3BF4W1C5 545 2½” CMH8 3 50 100 CE3BF4W1C7 545 2½” CMH8 4 100 150 CE4BF4W1C8 545 2½” CMH8

0 1 3 CE0BF6W1C1 130 1½” CMH7 0 3 7 CE0BF6W1C2 130 1½” CMH7 0 5 15 CE0BF6W1C3 130 1½” CMH7 1 7½ 15 CE1BF6W1C3 130 1½” CMH7 1 10 30 CE1BF6W1C4 130 1½” CMH7 600 2 20 30 CE2BF6W1C4 195 1½” CMH7 2 25 50 CE2BF6W1C5 195 1½” CMH7 3 40 50 CE3BF6W1C5 545 2½” CMH8 3 50 100 CE3BF6W1C7 545 2½” CMH8 4 60 100 CE4BF6W1C7 545 2½” CMH8 4 100 150 CE4BF6W1C8 545 2½” CMH8

Selection Table

Page 13: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.60

6 Motor Starters

CEB Series Full VoltageTwo Speed Two Winding, 3 Pole - 3 Pole, 3 Phase, 60 Hz, 120V Coil, Cutler-Hammer®

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Combination Full Voltage Two Speed Two Winding, 3 Pole - 3 Pole, 3 Phase, 60 Hz,120V Coil, Cutler-Hammer®

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Line NEMA Max Catalog Approx. Standard Mounting Hardware Voltage Size HP Number Weight (lbs) Conduit Set Catalog Number

0 3 CE0BG2W1 85 1½” CMH7 1 7½ CE1BG2W1 85 1½” CMH7 240 2 15 CE2BG2W1 190 1½” CMH7 3 30 CE3BG2W1 540 2” CMH8 4 50 CE4BG2W1 540 2½” CMH8

0 5 CE0BG4W1 85 1½” CMH7 1 10 CE1BG4W1 85 1½” CMH7 480 2 25 CE2BG4W1 190 1½” CMH7 3 50 CE3BG4W1 540 2” CMH8 4 100 CE4BG4W1 540 2½” CMH8

0 5 CE0BG6W1 85 1½” CMH7 1 10 CE1BG6W1 85 1½” CMH7 600 2 25 CE2BG6W1 190 1½” CMH7 3 50 CE3BG6W1 540 2” CMH8 4 100 CE4BG6W1 540 2½” CMH8

Line NEMA Max Amp Catalog Approx. Standard Mounting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 3 20 CE0BH2W1CB 130 1½” CMH7 1 7½ 50 CE1BH2W1CG 130 1½” CMH7 240 2 15 100 CE2BH2W1CN 195 1½” CMH7 3 30 125 CE3BH2W1CP 545 2½” CMH8 4 50 200 CE4BH2W1CS 545 2½” CMH8

0 5 20 CE0BH4W1CB 130 1½” CMH7 1 10 40 CE1BH4W1CF 130 1½” CMH7 480 2 25 70 CE2BH4W1CJ 195 1½” CMH7 3 50 100 CE3BH4W1CN 545 2½” CMH8 4 100 200 CE3BH4W1CS 545 2½” CMH8

0 5 20 CE0BH6W1CB 130 1½” CMH7 1 10 30 CE1BH6W1CD 130 1½” CMH7 600 2 25 50 CE2BH6W1CG 195 1½” CMH7 3 50 100 CE3BH6W1CN 545 2½” CMH8 4 100 150 CE3BH6W1CQ 545 2½” CMH8

Selection Table

Selection Table

Page 14: Motor Starters

61Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

Combination Full Voltage With MCPTwo Speed Two Winding, 3 Pole - 3 Pole, 3 Phase, 60 Hz,

120V Coil Cutler-Hammer®

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Line NEMA Max Amp Catalog Approx. Standard Mounting Hardware Voltage Size HP Trip Number Weight (lbs) Conduit Set Catalog Number

0 1 7 CE0BH2W1C2 130 1½” CMH7 0 3 15 CE0BH2W1C3 130 1½” CMH7 240 1 7½ 30 CE1BH2W1C4 130 1½” CMH7 2 15 50 CE2BH2W1C5 195 1½” CMH7 3 30 100 CE3BH2W1C7 545 2½” CMH8 4 50 150 CE4BH2W1C8 545 2½” CMH8

0 1 3 CE0BH4W1C1 130 1½” CMH7 0 3 7 CE0BH4W1C2 130 1½” CMH7 0 5 15 CE0BH4W1C3 125 1½” CMH7 1 7½ 15 CE1BH4W1C3 125 1½” CMH7 480 1 10 30 CE1BH4W1C4 130 1½” CMH7 2 15 30 CE2BH4W1C4 195 1½” CMH7 2 25 50 CE2BH4W1C5 195 1½” CMH7 3 30 50 CE3BH4W1C5 545 2½” CMH8 3 50 100 CE3BH4W1C7 545 2½” CMH8 4 100 150 CE4BH4W1C8 545 2½” CMH8

0 1 3 CE0BH6W1C1 130 1½” CMH7 0 3 7 CE0BH6W1C2 130 1½” CMH7 0 5 15 CE0BH6W1C3 130 1½” CMH7 1 7½ 15 CE1BH6W1C3 130 1½” CMH7 1 10 30 CE1BH6W1C4 130 1½” CMH7 600 2 20 30 CE2BH6W1C4 195 1½” CMH7 2 25 50 CE2BH6W1C5 195 1½” CMH7 3 40 50 CE3BH6W1C5 545 2½” CMH8 3 50 100 CE3BH6W1C7 545 2½” CMH8 4 60 100 CE4BH6W1C7 545 2½” CMH8 4 100 150 CE4BH6W1C8 545 2½” CMH8

Selection Table

Page 15: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.62

6 Motor Starters

CEB Series Combination Lighting Contactor With Thermal Magnetic Breaker3 Pole, 60 Hz, 120V Coil Cutler-Hammer®

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Line Enclosure Contactor Breaker Catalog Approx. Standard Mounting Hardware Voltage Size Amps Amps Number Weight (lbs) Conduit Set Catalog Number

1 30 40 CE1BN1W1CF 125 1½" CMH7 2 60 70 CE2BN1W1CJ 130 1½" CMH7 120 3 100 125 CE3BN1W1CP 195 2½" CMH7 4 200 225 CE4BN1W1CT 195 2½" CMH7 5 400 450 CE5BN1W1CZ 560 4" CMH8

1 30 40 CE1BN2W1CF 125 1½" CMH7 2 60 70 CE2BN2W1CJ 130 1½" CMH7 240 3 100 125 CE3BN2W1CP 195 2½" CMH7 4 200 225 CE4BN2W1CT 195 2½" CMH7 5 400 450 CE5BN2W1CZ 560 4" CMH8

1 30 40 CE1BN4W1CF 125 1½" CMH7 2 60 70 CE2BN4W1CJ 130 1½" CMH7 480 3 100 125 CE3BN4W1CP 195 2½" CMH7 4 200 225 CE4BN4W1CT 195 2½" CMH7 5 400 450 CE5BN4W1CZ 560 4" CMH8

1 30 40 CE1BN6W1CF 125 1½" CMH7 2 60 70 CE2BN6W1CJ 130 1½" CMH7 600 3 100 125 CE3BN6W1CP 195 2½" CMH7 4 200 225 CE4BN6W1CT 195 2½" CMH7 5 400 450 CE5BN6W1CZ 560 4" CMH8

Selection Table

Page 16: Motor Starters

63Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Lighting Contactor3 Pole, 60 Hz, 120V Coil Cutler-Hammer®

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7BCD, 9EFG

Line Enclosure Contactor Catalog Approx. Standard Mounting Hardware Voltage Size Amps Number Weight (lbs) Conduit Set Catalog Number

1 30 CE1BM1W1 125 1½" CMH7 2 60 CE2BM1W1 130 1½" CMH7 120 3 100 CE3BM1W1 195 2" CMH7 4 200 CE4BM1W1 195 2½" CMH7 5 400 CE5BM1W1 560 4" CMH8

1 30 CE1BM2W1 125 1½" CMH7 2 60 CE2BM2W1 130 1½" CMH7 240 3 100 CE3BM2W1 195 2" CMH7 4 200 CE4BM2W1 195 2½" CMH7 5 400 CE5BM2W1 560 4" CMH8

1 30 CE1BM4W1 125 1½" CMH7 2 60 CE2BM4W1 130 1½" CMH7 480 3 100 CE3BM4W1 195 2" CMH7 4 200 CE4BM4W1 195 2½" CMH7 5 400 CE5BM4W1 560 4" CMH8

1 30 CE1BM6W1 125 1½" CMH7 2 60 CE2BM6W1 130 1½" CMH7 600 3 100 CE3BM6W1 195 2" CMH7 4 200 CE4BM6W1 195 2½" CMH7 5 400 CE5BM6W1 560 4" CMH8

Selection Table

Page 17: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.64

6 Motor Starters

CEB Series Full Voltage Motor Starter EnclosuresDimensions

Enclosure Layout for Sizes 0, 1 & 2

Non-Combination

Enclosure Layout for Size 3

Non-Combination

Page 18: Motor Starters

65Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

Enclosure Layout for Size 4

Non-Combination

Enclosure Layout for Size 5

Non-Combination

CEB Series Full Voltage Motor Starter EnclosuresDimensions

Page 19: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.66

6 Motor Starters

Enclosure Layout for Sizes 0, 1 & 2

Combination

Enclosure Layout for Sizes 3 & 4

Combination

CEB Series Full Voltage Motor Starter EnclosuresDimensions

Page 20: Motor Starters

67Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Full Voltage Motor Starter EnclosuresDimensions

Enclosure Layout for Size 5

Combination

Enclosure Layout for Sizes 0, 1 & 2

Non-Combination - Reversing (Cutler-Hammer®)

Page 21: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.68

6 Motor Starters

Enclosure Layout for Sizes 3 & 4

Non-Combination - Reversing (Cutler-Hammer®)

CEB Series Full Voltage Motor Starter EnclosuresDimensions

Enclosure Layout for Sizes 0, 1 & 2

Combination - Reversing (Cutler-Hammer®)

Page 22: Motor Starters

69Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Full Voltage Motor Starter EnclosuresDimensions

Enclosure Layout for Sizes 3 & 4

Combination - Reversing (Cutler-Hammer®)

Enclosure Layout for Sizes 1 & 2

Combination - Two Speed Single Winding (5 pole - 3 pole)

Page 23: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.70

6 Motor Starters

Enclosure Layout for Sizes 3 & 4

Combination - Multi Speed Single Winding (5 pole - 3 pole)

CEB Series Full Voltage Motor Starter EnclosuresDimensions

Enclosure Layout for Sizes 0, 1 & 2

Non-Combination - Multi Speed Two Winding (3 pole - 3 pole)

Page 24: Motor Starters

71Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEB Series Full Voltage Motor Starter EnclosuresDimensions

Enclosure Layout for Sizes 3 & 4

Non-Combination - Two Speed Two Winding (3 pole - 3 pole)

Enclosure Layout for Sizes 0, 1 & 2

Combination - Two Speed Two Winding (3 pole - 3 pole)

Page 25: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.72

6 Motor Starters

Enclosure Layout for Sizes 3 & 4

Combination - Multi Speed Two Winding (3 pole - 3 pole)

CEB Series Full Voltage Motor Starter EnclosuresDimensions

Page 26: Motor Starters

73Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

For Sizes 5 & 6

CFVNR & FVNR

CEB Series Motor Starter EnclosuresTypical Wiring Diagrams

For Sizes 1 thru 4

CFVNR & FVNR

Page 27: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.74

6 Motor Starters

For Sizes 1 thru 4

Combination & Non-Combination - 2 Speed - Single Winding

CEB Series Motor Starter EnclosuresTypical Wiring Diagrams

For Sizes 1 thru 4

Combination & Non-Combination - Full Voltage Reversing

Page 28: Motor Starters

75Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

For Sizes 1 thru 4

Combination & Non-Combination - 2 Speed - 2 Winding

Combination & Non-Combination - Lighting Contractor - 30 Amp thru 400 Amp

CEB Series Motor Starter EnclosuresTypical Wiring Diagrams

Lighting Contractor - 30 Amp thru 400 Amp

Page 29: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.76

6 Motor Starters

CEB Series Motor StartersModifications

Operators(1)

Suffix Catalog Number Description Factory Installed Field Installed

Start Pushbutton S1X CEPGAStop Pushbutton S2X CEPRC

Start/Stop Dual Pushbutton S3X CEPDGREStop, Lighted PB, Red 120V LP5X CEPTREStart, Lighted PB, Green 120V LP4X CEPTGE3 Position Selector Switch A3X CESS31MN -Specify Legend

2 Position Selector Switch A2X CESS22ML -Specify Legend

Red Pilot Light, 120V L5 CEPL1RGreen Pilot Light, 120V L4 CEPL1GRed Pilot Light, 240V L52 CEPL2RGreen Pilot Light, 240V L42 CEPL2GRed Pilot Light, 480V L54 CEPL4RGreen Pilot Light, 480V L44 CEPL4G

(1) Add “L” to part no. for Size 5 starters.

NEMA 4X Breather/Drain Fittings

Suffix Catalog Number Description Factory Installed Field Installed

Drain Fitting DN DRNB4XBreather Fitting BR BRTB4X

(Drilled & tapped installation included)

Control Power Options (2) (3)

Suffix Catalog Number Description Factory Installed Field Installed

Fused CPT, 50 VA T1 CFCPT050Fused CPT, 100 VA T2 FCPT100Fused CPT, 200 VA T3 CFCPT200Fused CPT, 250 VA T4 CFCPT250Fused CPT, 50 VA T5 CFCPT050Rw/Interposing RelayFused CPT, 150 VA T6 CFCPT150Fused CPT, 300 VA T7 CFCPT300Fused CPT, 500 VA T8 CFCPT500Fused CPT, 750 VSA T9 CFCPT750

Note: CPT includes primary and secondary fuses

Separate Control Fused Circuit S-120V N/ASpecify Starter Coil Voltage S-240V N/A S-480V N/A

(2) Size 1 & 2 150 VA Max. Size 3 & 4 300 VA Max.

(3) Consult factory for other voltages.

Additional Options

Suffix Catalog Number Description Factory Installed Field Installed

Engraved Nameplate, NP N/ABlack letters on white surface, 2” x 4”, 1/8” Letters, 3 Lines Max. Specify Legend

Overload Heater Provide FLA at the time of order.

40W Enclosure 120V O-120V CFA4327X11 Space Heaters 240V O-240V CFA4327X12 480V O-480V CFA4327X13Control Term. Blocks 8 point 8K N/A 20A, 600V 12 point 12K N/ANEMA 1B w/wire markers (Above 12 points, consult factory)

Auxiliary ContactsCutler-Hammer1 Starter Auxiliary Contacts Contact Suffix Catalog Number Description Configuration Factory Installed Field InstalledSize 0-4* 1NO/1NC X11C CJ-11 2NO/2NC X22C CJ-11 (2 ea.)

Size 5** 1NO/1NC X511C C3463D94G18 2NO/2NC X522C C3463D94G18 (2 ea.)

Square D2 Starter Auxiliary Contacts

Contact Suffix Catalog Number Description Configuration Factory Installed Field Installed

Size 0-5 1NO/1NC X11S C999SX8 2NO/2NC X22S C999SX8 (2 ea.)

* 8 Aux. Contacts Max. includes one seal-in and up to seven added. ** 4 Aux. Contacts Max. includes one seal-in and up to three added. Size 0-1 includes one seal-in and up to four added. Size 2-5 includes one seal-in and up to three added.

Notes: 1. Cutler-Hammer® is a trademark of the Eaton Corporation.

2. Square D is a trademark of Schneider Electric.

Page 30: Motor Starters

77Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

Combination and Non-Combination Full VoltageExplosionproof, Dust-Ignitionproof, Watertight

These units provide disconnecting means and undervoltage, circuit and motor running protection.

Applications• “CE” series threaded type combination and

non-combination motor starters are used in areas where hazardous materials are handled or stored. These units provide disconnecting means, under-voltage protection, circuit protection and motor running protection. Full voltage across the line starting and stopping of squirrel cage induction motors. Remote starting and stopping motor as needed.

Features• Enclosures are cast from copper-free aluminum.

• Bolt on slotted mounting foot.

• Ground lug package and installation instructions for termination of ground wires.

• Reset operator with stainless steel shaft.

• Breaker handles can be locked in the “Off” or “On” position (combination starters only).

• Drilled and tapped outlets.

• Standard outlets are determined by motor starter size.

• Outlets for remote control wiring.

• Plugged ½” outlets top and bottom for breather and drain.

• Three plugged ¾” NPSM outlets drilled and tapped for needed lights or switches.

• Ample space is provided for installation and wiring of additional accessories.

• Painted removable pan.

• Enclosures are designed to accept GE, Square D and Cutler-Hammer® motor starters. For other brands, consult factory. Cutler-Hammer® furnished standard unless otherwise specified.

• Motor circuit protectors are available on combination starters.

• Enclosures furnished with or without components.

• Readily accessible circuit breaker mounted outside the center housing.

• Rated for NEMA 4X (grey epoxy-coated inside and outside).

• Acme screw type square threads designed to prevent seizing.

• Bell threads are located inside the housing—protects against damage or contaminants.

Standard Materials• Housings: copper-free aluminum.

• Shaft, bushings and exposed hardware: stainless steel.

Standard Finishes• Housings: epoxy-coated inside and outside.

Compliances• UL Classified

• UL 1203 and 1604

• NEMA 4, 4X, 7CD, 9EFG

• For CSA approvals, please consult factory.

Page 31: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.78

6 Motor Starters

Combination Full Voltage with Thermal Magnetic Breakers Explosionproof, Dust-Ignitionproof, WatertightThreaded Enclosure. 3-Phase, 60 Hz, Non-Reversing

Class I, Div. 1 & 2 Groups C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7CD, 9EFG

Sample Catalog NumberAE0TT-480520- ——

SUFFIX FOR OTHER OPTIONS/FEATURES (SEE MODIFICATIONS ON PAGE 76)

BREAKER TRIP (20 AMP)

MAX. HORSEPOWER (5)

LINE VOLTAGE (480)

BREAKER TYPE (THERMAL MAGNETIC)

ENCLOSURE TYPE (THREADED)

NEMA SIZE (0)

EXPLOSIONPROOF MOTOR STARTER ENCLOSURE

Conduit Sizes Mounting Line Max NEMA Breaker Catalog Weight Loc. A, B, C & D Hardware Voltage H.P. Size Amps Numbers Alum. (lbs) Std. Max Set Catalog Number

2 0 15 CE0TT-240215 70 1¼" 1½" CMH2 3 0 20 CE0TT-240320 70 1¼" 1½" CMH2 5 1 35 CE1TT-240535 70 1¼" 1½" CMH2 7½ 1 50 CE1TT-240750 70 1¼" 1½" CMH2 10 2 50 CE2TT-241050 110 1½" 1½" CMH2 15 2 100 CE2TT-241510 110 1½" 1½" CMH2 240 20 3 100 CE3TT-242010 125 2" 2½" CMH2 30 3 125 CE3TT-243012 125 2" 2½" CMH2 40 4 175 CE4TT-244017 130 2½" 2½" CMH2 50 4 200 CE4TT-245020 130 2½" 2½" CMH2

3 0 15 CE0TT-480315 70 1¼" 1½" CMH2 5 0 20 CE0TT-480520 70 1¼" 1½" CMH2 7½ 1 30 CE1TT-480730 70 1¼" 1½" CMH2 10 1 35 CE1TT-481035 70 1¼" 1½" CMH2 20 2 50 CE2TT-482050 110 1½" 1½" CMH2 25 2 70 CE2TT-482570 110 1½" 1½" CMH2 480 50 3 100 CE3TT-485010 125 2" 2½" CMH2 60 4 125 CE4TT-486012 130 2½" 2½" CMH2 75 4 150 CE4TT-487515 130 2½" 2½" CMH2 100 4 200 CE4TT-481020 130 2½" 2½" CMH5 5 0 15 CE0TT-600515 70 1¼" 1½" CMH2 7½ 1 20 CE1TT-600720 70 1¼" 1½" CMH2 10 1 30 CE1TT-601030 70 1¼" 1½" CMH2 15 2 40 CE2TT-601540 110 1½" 1½" CMH2 25 2 50 CE2TT-602550 110 1½" 1½" CMH2 600 30 3 70 CE3TT-603070 125 2" 2½" CMH2 50 3 100 CE3TT-605010 125 2" 2½" CMH2 75 4 125 CE4TT-607512 130 2½" 2½" CMH2 100 4 150 CE4TT-601015 130 2½" 2½" CMH2

Selection Table

Page 32: Motor Starters

79Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

Sample Catalog NumberCE0TM-480520- ——

SUFFIX FOR OTHER OPTIONS/FEATURES (SEE MODIFICATIONS ON PAGE 76)

BREAKER TRIP (20 AMP)

MAX. HORSEPOWER (5)

LINE VOLTAGE (480)

BREAKER TYPE (MAGNETIC ONLY)

ENCLOSURE TYPE (THREADED)

NEMA SIZE (0)

EXPLOSIONPROOF MOTOR STARTER ENCLOSURE

Combination Full Voltage with Magnetic BreakersExplosionproof, Dust-Ignitionproof, WatertightThreaded Enclosure. 3-Phase, 60 Hz, Non-Reversing

Class I, Div. 1 & 2 Groups C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 4, 4X, 7CD, 9EFG

Selection Table

Conduit Sizes Mounting Line Max NEMA Breaker Catalog Weight Loc. A, B, C & D Hardware Voltage H.P. Size Amps Numbers Alum. (lbs) Std. Max Set Catalog Number 1 0 7 CE0TM-240107 70 1¼" 1½" CMH2 3 0 15 CE0TM-240315 70 1¼" 1½" CMH2 7 1 30 CE1TM-240730 70 1¼" 1½" CMH2 240 15 2 50 CE2TM-241550 110 1½" 1½" CMH2 30 3 100 CE3TM-243010 125 2" 2½" CMH2 50 4 150 CE4TM-245015 125 2½" 2½" CMH2 1 0 3 CE0TM-480103 70 1¼" 1½" CMH2 3 0 7 CE0TM-480307 70 1¼" 1½" CMH2 5 0 15 CE0TM-480515 70 1¼" 1½" CMH2 7 1 15 CE1TM-480715 70 1¼" 1½" CMH2 10 1 30 CE1TM-481030 70 1¼" 1½" CMH2 480 15 2 30 CE2TM-481530 110 1½" 1½" CMH2 25 2 50 CE2TM-482550 110 1½" 1½" CMH2 30 3 50 CE3TM-483050 125 2" 2½" CMH2 50 3 100 CE3TM-485010 125 2" 2½" CMH2 100 4 150 CE4TM-481015 125 2½" 2½" CMH2 1 0 3 CE0TM-600103 70 1¼" 1½" CMH2 3 0 07 CE0TM-600307 70 1¼" 1½" CMH2 5 0 15 CE0TM-600515 70 1¼" 1½" CMH2 7 1 15 CE1TM-600715 70 1¼" 1½" CMH2 10 1 30 CE1TM-601030 70 1¼" 1½" CMH2 20 2 30 CE2TM-602030 110 1½" 1½" CMH2 600 25 2 50 CE2TM-602550 110 1½" 1½" CMH2 40 3 50 CE3TM-604050 125 2" 2½" CMH2 50 3 100 CE3TM-605010 125 2" 2½" CMH2 60 4 100 CE4TM-606010 125 2½" 2½" CMH2 100 4 150 CE4TM-601015 125 2½" 2½" CMH2

Page 33: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.80

6 Motor Starters

Combination Full Voltage Motor StartersDimensions

Enclosure Dimensions (Dimensions are approximate, not for construction)

Enclosure Catalog Number - Dimensions inches (cm) Dim. AES0T AES1T AES2T AES3T AES4T

E 10.63 (26.98) 10.63 (26.98) 13.88 (35.24) 13.38 (33.97) 13.38 (33.97)F 26.00 (66.04) 26.00 (66.04) 30.50 (77.47) 39.50 (100.33) 39.50 (100.33)G 15.25 (38.74) 15.25 (38.74) 19.25 (48.90) 20.25 (51.44) 20.25 (51.44)H 8.00 (20.32) 8.00 (20.32) 8.00 (20.32) 8.00 (20.32) 8.00 (20.32)J 4.75 (12.07) 4.75 (12.07) 4.75 (12.07) 4.75 (12.07) 4.75 (12.07)K 5.38 (13.65) 5.38 (13.65) 5.25 (13.34) 7.50 (19.05) 7.50 (19.05)L 3.75 (9.53) 3.75 (9.53) 3.75 (9.53) 3.75 (9.53) 3.75 (9.53)M 1.06 (2.70) 1.06 (2.70) 1.06 (2.70) — —N 7.50 (19.05) 7.50 (19.05) 7.00 (17.78) 7.75 (19.69) 10.50 (26.67)P 11.00 (27.94) 11.00 (27.94) 18.00 (45.72) 23.00 (58.42) 23.00 (58.42)Q 7.31 (18.57) 7.31 (18.57) 9.38 (23.81) 8.63 (21.91) 8.63 (21.91)R 2.06 (5.29 2.06 (5.29 2.75 (6.99) 3.00 (7.62) 3.00 (7.62)S — — — — — T — — — — —

Approximate Weight lbs (kg)

Enclosure 60 (27.00) 60 (27.00) 100 (45.00) 110 (49.50) 110 (49.50) only

Page 34: Motor Starters

81Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CSE Series ManualExplosionproof

Class I, Div. 1 & 2 Groups C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 3, 3R, 7CD

Applications• Explosionproof across-the-line manual motor starters

for starting single and polyphase AC or DC motors.

Features• Rugged, compact enclosures supplied with Square D or

GE manual motor starters using three overloads.

• Mating surfaces are precision milled to exceed explosion-proof specifications. Covers secure with stainless steel (300 Series) hex-head bolts.

• Bolt on mounting feet.

• Push buttons are positive-operating and can be locked in the Stop position.

Standard Materials• Enclosure: cast aluminum.

• Shaft, bushing and cover bolts: stainless steel (300 Series).

• Mounting feet: aluminum.

Standard Finishes• Housing: Shot blast finish.

* Square D starter provided as standard. For GE starter, change SQD to GE.** Add suffi x for heater. See next page.

Compliances• UL Standard 1203 and 1604

• CSA Certified

Catalog NEMA No. of Motor Maximum Horsepower Number * Size Poles Voltage Single Phase Poly Phase

CSE040805SQD02** 0 2 115 1 ----- 0 2 230 2 -----

CSE040805SQD12** 1 2 115 2 ----- 1 2 230 3 -----

CSE040805SQD03** 0 3 115 ----- ----- 0 3 200 - 230 ----- 3 0 3 380 - 575 ----- 5

CSE040805SQD13** 1 3 115 ----- ----- 1 3 200 - 230 ----- 7½ 1 3 380 - 575 ----- 10

CSE040805SQD02D** 0 2 115 1 - DC 0 2 230 1½ - DC

CSE040805SQD12D** 1 2 115 1½ - DC 1 2 230 2 - DC

Selection Table

Page 35: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.82

6 Motor Starters

CSE Series Manual Starter HeaterSelection Table and Dimensions

1. Select heater elements based on motor nameplate listed Full Load Amps (FLA) 2. Trip rating of elements is 125% of motor minimum FLA listed for the elements. 3. Three heaters required per starter.

.31 - .34 -C036A .35 - .37 -C039A .38 - .42 -C043A .43 - .47 -C048A .48 - .52 -C054A .53 - .57 -C060A .58 - .63 -C066A .64 - .69 -C071A .70 - .77 -C078A .78 - .87 -C087A .88 - .97 -C097A .98 - 1.06 -C109A 1.07 - 1.18 -C131A 1.19 - 1.33 -C131A 1.34 - 1.47 -C148A

Dimensions

.29 - .31 .28 - .29 -B44 .32 - .36 .30 - .33 -B51 .37 - .39 .34 - .36 -B57 .40 - .47 .37 - .44 -B63 .48 - .56 .45 - .52 -B71 .57 - .63 .53 - .59 -B81 .64 - .69 .60 - .64 -B92 .70 - .77 .65 - .71 -B103 .78 - .86 .72 - .80 -B116 .87 - .97 .81 - .90 -B130 .98 - 1.12 .91 - 1.03 -B145 1.13 - 1.24 1.04 - 1.14 -B167 1.25 - 1.39 1.15 - 1.27 -B188 1.40 - 1.57 1.28 - 1.44 -B210 1.58 - 1.78 1.45 - 1.63 -B240 1.79 - 1.96 1.64 - 1.79 -B265 1.97 - 2.20 1.80 - 2.01 -B300 2.21 - 2.41 2.02 - 2.19 -B330

2.42 - 2.75 2.20 - 2.52 -B370 2.76 - 3.25 2.53 - 2.95 -B415 3.26 - 3.50 2.96 - 3.17 -B485 3.51 - 3.87 3.18 - 3.50 -B550 3.88 - 4.13 3.51 - 3.73 -B625 4.14 - 4.69 3.74 - 4.22 -B690 4.70 - 5.20 4.23 - 4.68 -B770 5.21 - 5.53 4.69 - 4.98 -B820 5.54 - 6.23 4.99 - 5.59 -B910 6.24 - 7.18 5.60 - 6.43 -B102 7.19 - 8.20 5.60 - 6.43 -B115 8.21 - 8.98 7.42 - 8.02 -B128 8.99 - 9.63 8.03 - 8.59 -B140 9.64 - 10.6 8.60 - 9.52 -B155 10.7 - 11.8 9.53 - 10.5 -B175 11.9 - 12.7 10.6 - 11.2 -B195 12.8 - 14.3 11.3 - 12.7 -B220 14.4 - 16.1 — — -B250

16.2 - 18.0 — — -B280

For size M-1 and M-1P only

— — 11.3 - 12.7 -B220 — — 12.8 - 14.3 -B250 16.2 - 18.3 14.4 - 16.1 -B280 18.4 - 20.2 16.2 - 17.8 -B320 20.3 - 23.0 17.9 - 20.1 -B360 23.1 - 26.0 20.2 - 22.6 -B400 — — 22.7 - 25.5 -B450 — — 25.6 - 26.0 -B500

For size M-1P only

25.9 - 29.0 — — -B450 29.1 - 30.8 — — -B500 30.9 - 32.7 — — -B560 32.8 - 36.0 — — -B620

Motor FLC (A) Add 1 PH 3 PH Suffix

Motor Full Add Load Amps @ 40°C Suffix

1.48 - 1.66 -C163A 1.67 - 1.78 -C184A 1.79 - 2.00 -C196A 2.01 - 2.18 -C220A 2.19 - 2.45 -C239A 2.46 - 2.76 -C268A 2.77 - 3.00 -C301A 3.01 - 3.27 -C326A 3.28 - 3.49 -C356A 3.50 - 3.86 -C379A 3.87 - 4.30 -C419A 4.31 - 4.88 -C466A 4.89 - 5.49 -C526A 5.50 - 5.85 -C592A 5.86 - 6.45 -C630A

6.46 - 7.22 -C695A 7.23 - 8.05 -C778A 8.06 - 8.88 -C867A 8.89 - 9.66 -C955A 9.67 - 10.5 -C104B 10.6 - 11.6 -C113B 11.7 - 12.7 -C125B 12.8 - 13.2 -C137B 13.3 - 15.1 -C151B 15.2 - 16.6 -C163B 16.7 - 17.6 -C180B 17.7 - 18.0 -C198B 17.7 - 19.8 -C198A 19.9 - 21.1 -C214B 21.2 - 23.1 -C228B 23.2 - 25.2 -C250B

Heater Table for GE

Motor Full Add Load Amps @ 40°C Suffix

Motor Full Add Load Amps @ 40°C Suffix

Heater Table for Square D Motor FLC (A) Add 1 PH 3 PH Suffix

Motor FLC (A) Add 1 PH 3 PH Suffix

Page 36: Motor Starters

83Visit our website at www.egs-curlee.com or

contact Technical Services at (800) 631-6815 with any ques tions.

6Motor Starters

CEXMS Series Manual Motor StartersExplosionproof, Dust-Ignitionproof, Watertight

Class I, Div. 1 & 2 Groups B, C, DClass II, Div. 1 & 2 Groups E, F, GClass III NEMA 3, 3R, 4,4X, 7CD, 9EFG

Applications• Explosionproof across-the-line manual motor starters for

starting polyphase AC motors.

Features• Rugged, compact enclosures supplied with Square D

or Cutler-Hammer® manual motor starters using three overloads.

• Mating surfaces are precision milled to exceed explosion-proof specifications. Covers secure with stainless steel (300 Series) hex-head bolts.

• O-Ring Gasket provides NEMA Type 4 rating.

• Four bolt-on mounting feet allow easy rack or individual mounting. Enclosures have standard conduit openings at top and bottom.

• Operating levers are positive-operating and can be locked in the ON or OFF position.

Standard Materials• Enclosure and handle: cast aluminum.

• Shaft, bushing and cover bolts: stainless steel (300 Series).

• Mounting hardware: stainless steel.

Catalog Number† NEMA Size Number of Poles Motor Starter Series Model Number CEXMS-A† 0 2 Square D 2510 TB01 CEXMS-F† 0 2 C-H/Westinghouse B100 M0B CEXMS-D† 0 3 Square D 2510 TB02 CEXMS-J† 0 3 C-H/Westinghouse B100 M0C CEXMS-B† 1 2 Square D 2510 TC01 CEXMS-G† 1 2 C-H/Westinghouse B100 M1B CEXMS-E† 1 3 Square D 2510 TC03 CEXMS-K† 1 3 C-H/Westinghouse B100 M1C CEXMS-C† 1½ 2 Square D 2510 TC02 CEXMS-H† 1½ 2 C-H/Westinghouse B100 MDB

† Add suffix for heater. See table on next page. Note: Dimensions (in inches) are nominal.

Standard Finishes• Corrosion resistant grey powder coat epoxy standard.

• Stainless steel shaft, bushings and exposed hardware: Passivated.

Compliances• UL Standard 698

Selection Table

Page 37: Motor Starters

Visit our website at www.egs-curlee.com or contact Technical Services at (800) 631-6815 with any ques tions.84

6 Motor Starters

CEXMS Series AC Manual Starter Heater Selection Table and Dimensions

.25 - .26 -FH03 .27 - .29 -FH04 .30 - .32 -FH05 .33 - .35 -FH06 .36 - .39 -FH07 .40 - .44 -FH08 .45 - .49 -FH09 .50 - .55 -FH10 .56 - .61 -FH11 .62 - .68 -FH12 .69 - .75 -FH13 .78 - .83 -FH14 .84 - .91 -FH15

1. Select heater elements based on motor nameplate listed Full Load Amps (FLA). 2. Trip rating of elements is 125% of motor minimum FLA listed for the elements. 3. Three heaters required per starter.

29 - .31 .28 - .29 -B44 .32 - .36 .30 - .33 -B51 .37 - .39 .34 - .36 -B57 .40 - .47 .37 - .44 -B63 .48 - .56 .45 - .52 -B71 .57 - .63 .53 - .59 -B81 .64 - .69 .60 - .64 -B92 .70 - .77 .65 - .71 -B103 .78 - .86 .72 - .80 -B116 .87 - .97 .81 - .90 -B130 .98 - 1.12 .91 - 1.03 -B145 1.13 - 1.24 1.04 - 1.14 -B167 1.25 - 1.39 1.15 - 1.27 -B188 1.40 - 1.57 1.28 - 1.44 -B210 1.58 - 1.78 1.45 - 1.63 -B240 1.79 - 1.96 1.64 - 1.79 -B265 1.97 - 2.20 1.80 - 2.01 -B300 2.21 - 2.41 2.02 - 2.19 -B330

Motor FLC (A) Add 1 PH 3 PH Suffix

Heater Table for Square D

2.42 - 2.75 2.20 - 2.52 -B370 2.76 - 3.25 2.53 - 2.95 -B415 3.26 - 3.50 2.96 - 3.17 -B485 3.51 - 3.87 3.18 - 3.50 -B550 3.88 - 4.13 3.51 - 3.73 -B625 4.14 - 4.69 3.74 - 4.22 -B690 4.70 - 5.20 4.23 - 4.68 -B770 5.21 - 5.53 4.69 - 4.98 -B820 5.54 - 6.23 4.99 - 5.59 -B910 6.24 - 7.18 5.60 - 6.43 -B102 7.19 - 8.20 5.60 - 6.43 -B115 8.21 - 8.98 7.42 - 8.02 -B128 8.99 - 9.63 8.03 - 8.59 -B140 9.64 - 10.6 8.60 - 9.52 -B155 10.7 - 11.8 9.53 - 10.5 -B175 11.9 - 12.7 10.6 - 11.2 -B195 12.8 - 14.3 11.3 - 12.7 -B220 14.4 - 16.1 — — -B250 16.2 - 18.0 — — -B280

For Size M-1 and M-1P only

— — 11.3 - 12.7 -B220 — — 12.8 - 14.3 -B250 16.2 - 18.3 14.4 - 16.1 -B280 18.4 - 20.2 16.2 - 17.8 -B320 20.3 - 23.0 17.9 - 20.1 -B360 23.1 - 26.0 20.2 - 22.6 -B400 — — 22.7 - 25.5 -B450 — — 25.6 - 26.0 -B500

For Size M-1P only

25.9 - 29.0 — — -B450 29.1 - 30.8 — — -B500 30.9 - 32.7 — — -B560 32.8 - 36.0 — — -B620

Heater Table for Cutler-Hammer/Westinghouse

.92 - 1.00 -FH16 1.01 - 1.10 -FH17 1.11 - 1.22 -FH18 1.23 - 1.35 -FH19 1.36 - 1.50 -FH20 1.51 - 1.66 -FH21 1.67 - 1.84 -FH22 1.85 - 2.03 -FH23 2.04 - 2.23 -FH24 2.24 - 2.45 -FH25 2.46 - 2.69 -FH26 2.70 - 2.95 -FH27 2.96 - 3.23 -FH28

3.24 - 3.53 -FH29 3.54 - 3.85 -FH30 3.86 - 4.22 -FH31 4.23 - 4.61 -FH32 4.62 - 5.03 -FH33 5.04 - 5.49 -FH34 5.50 - 5.99 -FH35 6.00 - 6.53 -FH36 6.54 - 7.11 -FH37 7.12 - 7.73 -FH38 7.74 - 8.40 -FH39 8.41 - 9.12 -FH40 9.13 - 9.89 -FH41

9.90 - 10.7 -FH42 10.8 - 11.8 -FH43 11.9 - 13.0 -FH44 13.1 - 14.0 -FH45 14.1 - 15.0 -FH46 15.1 - 16.1 -FH47 16.2 - 17.3 -FH48 17.4 - 18.6 -FH49 18.7 - 20.0 -FH50 20.1 - 21.5 -FH51 21.6 - 23.2 -FH52 23.3 - 25.0 -FH53 25.1 - 26.8 -FH54

Motor Full Add Load Amps @ 40°C Suffix

Dimensions

Motor FLC (A) Add 1 PH 3 PH Suffix

Motor FLC (A) Add 1 PH 3 PH Suffix

Motor Full Add Load Amps @ 40°C Suffix

Motor Full Add Load Amps @ 40°C Suffix

Motor Full Add Load Amps @ 40°C Suffix