Motor Ratings and Qualified Life...

45
30 Gando Drive, New Haven, CT 06513 Motor Ratings and Qualified Life Issues Presented By: Bill Newell Schulz Electric Company

Transcript of Motor Ratings and Qualified Life...

Page 1: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Motor Ratings and Qualified Life Issues

Presented By:Bill NewellSchulz Electric Company

Page 2: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Motor Ratings

Motor Ratings Include:• Voltage• Speed• KVA Code• Full Load Current• Frame• Design• Allowable Ambient Temperature or Full Load

Temperature Rise• Insulation Class

Page 3: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Temperature Rise v. Insulation Class

Motor temperature rise and motor insulation class are two different things

The temperature rise of the motor is dependent on the winding design and the motor’s ability to remove heatThe insulation class is the thermal capability of the insulation systemThe insulation class of a motor’s insulation system can be changed to a higher (or lower) class without affecting the temperature rise of the motor

Page 4: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Establishing Thermal Class

Page 5: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Establishing Thermal Class

Page 6: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Testing Motorettes and Formettes

Codes and Standards• IEEE-117 for Random-Wound Systems• IEEE-275 for Form-Wound Systems• UL 1446 - General Insulation Systems,

can be random, form, motors, solenoids, coils, etc.

Page 7: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Testing Motorettes and Formettes

• Test 3 sets of samples with 10 samples per set

• Test at three separate temperatures at least 20 C apart

• Perform thermal aging, mechanical aging, moisture exposure, voltage testing

• Test until all samples fail

• Graph failures to determine activation energy and develop the Arrhenius curve

Page 8: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Data From IEEE 117 Testing

Page 9: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Log Life Graph of Data

Page 10: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Least Squares Average of Data

Page 11: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Page 12: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Insulation Classifications

• Class A - 105 C• Class B - 130 C• Class F - 155 C• Class H - 180 C

The temperature is the maximum hotspot temperature at which the insulation system can be operated for normal expected service life.

Page 13: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Ambient Temperature and Temperature Rise

Page 14: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Total Winding Temperature

40 C – Ambient

55 C – Class A80 C – Class B Winding Temperature Rise105 C – Class F130 C – Class H

10 C – Hot Spot

Thumbrule: A temperature increase of 10 Cwill reduce the lifetime of the insulation system by one-half.

Page 15: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Qualified Life as a Function of Temperature

Variables needed to determine insulation life:

Page 16: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Qualified Life as a Function of Temperature

Page 17: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Qualified Life as a Function of Temperature

Page 18: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Random-Wound Insulation System

Page 19: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Random-Wound Insulation System

• Magnet Wire: Enamel Coated (MW 36C, MW 15C)

• Fiberglass Support Tape

• Silicone Lead Wire• 15% Silver Solder

• Slot liner: Nomex-Mylar-Nomex

• Slot wedge: Nomex 410

• Phase separator:Nomex 410

• Phase paper: Nomex 411

Page 20: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Random-Wound Insulation System

Page 21: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Random-Wound System(before)

Page 22: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Random-Wound System(before)

Page 23: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Random-Wound System

Page 24: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Random-Wound Post VPI

Page 25: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Form-Wound Insulation System

Page 26: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Form-Wound Insulation System

• Magnet Wire: Square or Rectangular with Enamel Coating, with or without Fiberglass Coating

• Mica Insulating Tape• Fiberglass Support

Tape• 7.5 KV EPDM Lead

Wire

• Slot wedge: Nomex 410

• Filler Strips:Nomex 410

• Slot Wedge: G-200• 15% Silver Solder• Felt Blocking

Page 27: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Form-Wound Insulation System

Page 28: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Page 29: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Trial-Fitting of Coils

Page 30: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Adding Mica Tape

Page 31: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Wrapping with Fiberglass Tape

Page 32: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Connection End

Page 33: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Inserting Last Coils

Page 34: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Post-VPI: Connection End

Page 35: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Factors Affecting the Qualified Life of In-service Motors

• Actual Load vs. Assumed Load• Number of Starts• Maintenance Routine (Required vs.

Actual)• Op-tempo (Hours of Operation)• Actual Ambient Temperature vs. NEMA

Standard • Cleanliness of the Exterior Surfaces• Cleanliness of the Interior Surfaces

Page 36: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Actual Load vs. Assumed Load

The qualified life of an insulation system is based on the temperature rise of the motor’s windings at full load. Since it is unlikely that the motor is actually running at full load during operation, the actual load can be used to extend the qualified life of the motor.

Page 37: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Calculating Temperature Rise for Different Values of Load

IEEE 112 Provides a calculation of temperature rise for varying load conditions for a motor.TRactual = TRtest (Iactual/Itest)2

Where:TRactual = The actual temperature rise of the windings by winding resistance with a load current of Iactual

TRtest = The tested temperature rise of the windings by winding resistance with a load current of Itest

Page 38: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Actual Load vs. Assumed Load

• EPRI NP-3887 “Life Expectancy of Motors in Mild Nuclear Plant Environments” identifies another method that uses “Life Loss Factors” based on the allowable temperature rise of the insulation, the thermal class of the insulation and the percent load of the motor. The result of the calculation can be used to develop the following table:

Page 39: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Actual Load vs. Assumed Load

Page 40: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Rule of Thumb

• In 1930, V. M. Montsinger introduced the 10 degree rule concept which states:

“Thermal life for insulation is halved for each increase of 10 C, or conversely doubled for each decrease of 10 C.”

Page 41: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Number of Starts

Each start introduces both thermal and mechanical stresses on the windings and insulation system that are much higher than that of normal operation.

Page 42: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Thermal Stresses

EPRI NP-3887 “Life Expectancy of Motors in Mild Nuclear Plant Environments” provides a conservative calculation for estimating the loss of operational life that can be expected for each motor start due to thermal stress induced during a motor start from full operating temperature.

This calculation results in approximately 1 hour of lost life per start.

Page 43: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Mechanical Stress

• The mechanical stress of starting causes relative movement between insulation system components which can introduce cracking within the insulation system components.

• Though this is an obvious contributor to reduction in the qualified life, no studies have been performed to quantify this reduction.

Page 44: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Maintenance

• IEEE 323 – 2003 States “…This continued capability is ensured through a program that includes, but is not limited to, design control, quality control, qualification, installation, maintenance, periodic testing, and surveillance…”

• IEEE 334 – 1994 States “…This is accomplished through a program that includes, but is not limited to, design, qualification, production quality control, shipping, storage, installation, operation, maintenance, periodic testing, and surveillance of motors to maintain qualificationof motors throughout their installed life…”

Page 45: Motor Ratings and Qualified Life Issuessite.ieee.org/npec-sc2/files/2017/06/SC-2Mgt04-2_Att16-Newell.pdf · actual TR test = The tested temperature rise of the windings by winding

30 Gando Drive, New Haven, CT 06513

Maintenance Programs

• A subject for another time