    For the world wide use of the Industrial Switchgear in manycountries and for shipboard use national approvals arerequired. The approvals are partly connected with specialtechnical data. This part of the catalogue gives you thenecessary information of the appropriate foreign approvalsfor export. There is also information of which approvals theMoeller products have.

    Page

    Approvals for world markets

    Overview A1/2

    Country-specific approvals A1/4

    Shipping classifications A1/8

    Switchgear for North America

    Approvals A1/13

    Selection of devices A1/14

    Switching duty auxiliary contacts,rating data of AC contactorsaccording to NEMA.

    A1/16

    Selection and usage of fuses A1/17

    Enclosure protection types to NEC(NFPA 70), UL, CSA, NEMA

    A1/18

    Contactor relays

    DILER, DILR contactor relays; DILET,ETR4 timing relays

    A1/19

    Display and operator units, controlcircuit devices

    Operator panels, RMQ16, RMQ-Titan A1/20

    Position switches, pressure switches

    Position switches, proximity switches,pressure switches A1/21

    Contactors

    DILM contactors, complete units A1/22

    DILM/Z motor-starter combinations A1/23

    Overload relays A1/24

    Rotary switches, switch-disconnectors

    Miscellaneous switches withdisconnect function

    A1/25

    Switch-disconnectors A1/26

    Auxiliary contacts A1/28

    Motor-pro

    PKbre

    Coen

    Ac

    Typ

    Typ

    Mocirc

    Se

    Dirsta

    PKbre

    Ac

    FAZ minia

    Su

    CI insulat

    Em

    Pa

    Ind

    CI

    Ca

    Glossary

    For Moeller Electric Sales and Support call KMparts.com (866) 595-961

  • 8/10/2019 Moeller Certificates

    2/44

    Moeller HPL0211-2007/2008

    A1/2

    http://catalog.moeller.net

    pp

    Approvals for world marketsOverview

    The standard versions of most Moeller devicesare approved for use throughout the world,including the USA and Canada.As such, they can be used without restriction asdevices for world markets.

    The standard versions of some devices, such ascircuit-breakers, can be used worldwide except inthe USA and Canada.

    Such devices are available in special UL- and CSA-approved versions for export to these countries.

    Moeller low-voltage switchgear and switchgearassemblies conform to national and internationalspecifications, making it possible to construct controlsystems that will conform to the national internationalspecifications of any country in the world.This, of course, means that due consideration must begiven to the particular national standards of thecountry in question, such as those concerninginstallation, operation, installation materials andmethods, as well as any pertaining to circumstancessuch as severe environmental conditions.The component rating data for 220 240 V, 380 440 V, 500 V, 600 V and 690 V given in this cataloguecover virtually all existing three-phase systemsworldwide.

    Ratings are also given for the supply voltages incommon use in the USA and in Canada.

    In addition to the widely differing system conditions,special installation standards and approvalrequirements also have to be observed for theworldwide use of switchgear:Where screw fuses have to be used in a control system,some European countries such as Denmark, Finland,the Netherlands, Norway and Sweden require gaugescrews. In this case , FORM P fuse bess must beused. Switzerland no longer requires the use of gaugescrews, but they are often still requested by customers.

    The majority of countries permit the import ofswitchgear assemblies and devices on themanufacturers undertaking that they have been

    constructed in accordance with the pertinentspecifications. In some countries, such as the USA andCanada, however, there is a legal obligation to obtainofficial approval.In these countries, devices and enclosures sometimeseven complete control systems are tested andapproved by independent bodies.

    To a certain extent, there also used to be a legalobligation to obtain official approval for low-voltageswitchgear and controlgear in Scandinavia and inSwitzerland. For industrial switchgear, this legalobligation has now been abolished, provided thedevices have been manufactured and tested inaccordance with harmonized European standards(such as IEC/EN 60947). There is then no longer arequirement for them to carry their country's ownaprroval mark. Moeller develops switchgear to

    international standards, such as IEC/EN 60947 andapplies the corresponding marks.

    Since January 1997, all devices must conform to theEuropean Low-Voltage Directive and, where intendedfor sale within the European Union, must carry the CEmark.

    This mark denotes that the device carrying it conformsto all relevant requirements and specifications. Themandatory application of this mark therefore enablesthe unrestricted use of marked devices within theEuropean economic area.

    Since January 1996, all devices sold within theEuropean union must comply with the ElectromagneticCompatibility (EMC) Directive. Moeller has passed therequired tests for all products subject to theseDirectives, and the devices carry the CE mark,demonstrating compliance with the EMC Directive.Because devices bearing the CE mark comply with theharmonized standards, approval and the associatedmarking is no longer required in the following

    countries:

    An exception is equipment for service installations. The

    device group of miniature circuit-breakers andresidual-current circuit-breakers in certain areas is stillsubject to mandatory marking and therefore providedwith the appropriate approval marks:

    Devices for export to the USA and Canada have eitheradditional UL and CSA approval or are available in aseparate version with UL and CSA approval.

    Recently introduced is the mandatory approval ofelectrical products for Slovakia Poland South Africa China Russia Turkey Argentina

    Marking is partly mandatory for these countries. TheIEC rating data is accepted as in other European

    countries.

    Approval is not mandatory in the Czech Republic andHungary. The manufacturers declaration ofconformity is sufficient here.

    Romania requires that components that are to be usedin public buildings must be approved by the Romaniantest authority ICECON.

    RussiaDevices for Russia must bear the appropriate marking.

    South AfricaApproval is mandatory in South Africa for circuit-breakers and busbar trunking systems. These devicesmust bear the appropriate marking.

    ArgentinaIn Argentina, mandatory approval is based onResolution 92/98. From 01/04/2001, miniature circuit-breakers and residual-current circuit-breakers aresubject to mandatory approval. From 01/04/2002,protective switches up to Ie= 63 A and Ue max= 440 Vare subject to mandatory approval and must bear thefollowing markings:

    EuropeConformit Europen(CE)

    BelgiumComit Electro-technique BelgeBelgisch Elektro-technisch Comit(CEBEC)

    DenmarkDanmarks ElektriskeMaterielkontrol(DEMKO)

    Finland(FIMKO)

    FranceUnion Techniquede lElectricit(UTE)

    NetherlandsNaamloze Vennootschaptot Keuring vanElectrotechnischeMaterialien(KEMA)

    NorwayNorges Elektriske

    Materiellkontrol(NEMKO)

    SwedenSvenskaElektriska Materiel-kontrollanstalten(SEMKO)

    SwitzerlandSchweizerischerElektrotechnischerVerein(SEV)

    BelgiumComit Electro-technique BelgeBelgisch Elektro-technisch Comit(CEBEC)

    GermanyVerbandDeutscherElektrotechniker(VDE)

    France

    Union Techniquede lElectricit(UTE)

    Austriasterreichischer Verbandfr Elektrotechnik(VE)

    SwitzerlandSchweizerischer

    ElektrotechnischerVerein(SEV)

    USAUnderwriters Laboratories(UL) Listing Recognition

    CanadaCanadianStandardsAssociation(CSA)

    RussiaGoststandart(GOST-R)

    South AfricaZASABS

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    3/44

    A1/3

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Approvals for world marketsOverview

    Selection of devices

    Selection appropriate for export does not meanmerely meeting the requisite approvals and conformityto relevant specifications. The meaning of the termgoes a great deal further by even including thatequipment and installations must be designed to aconcept with export in mind.The following are important criteria for selectingswitchgear suitable for export:

    For motor-protective circuit-breakersUse inherently short-circuit proof switches capable ofcontrolling the highest prospective fault levels at thepoint of installation without the need for back-upprotection.Advantage: No restrictions whatsoever for installation Complete independence from the on-site protective

    system No problems getting spare parts

    For circuit-breakersUse types with visible contacts, quick-make andquick-break operation as standard. Use current-limit-ing circuit-breakers for high short-circuit levels. Selec-tive switches are recommended for the selectivegraduation of networks.Advantage: Independence from local accident prevention regu-

    lations requiring visible contacts, and safety frofaults caused by inexperienced operating person-nel.

    The effects of short-circuits are kept to a minimum. Fuseless installations offer greater safety and relia-

    bility in plant operation. In the event of a fault, onlythe faulty section of the system is isolated.

    For contactorsUse contactors whose entire range provides consist-ently reliable operation in the event of voltage drops(80% Unshould be aimed for) and whose contact sys-tem will not assume an indeterminate position eitheron closing or on opening in such conditions.Advantage: During the electrification work in areas such as Afri-

    ca and the Middle East, an insufficient voltage sta-bility is at least for a certain time likely in manyapplications (for example due to long spur lines orsmall local generators). The use of devices that full-fill the above requirements will eliminate one of themaim failure causes related to contactors.

    For enclosuresUse insulated enclosures with transparent covers (i.e.totally insulated enclosures).Advantage: Total insulation is the best possible protective meas-

    ure from the users point of view, avoiding, relianceon the possibly doubtful skills of unknown installa-tion personnel. Furthermore, protective measuresbased on earthing are often extremely difficult, ifnot impossible (in the Middle East, for example, dueto the dryness of the ground).

    Insulated enclosures completely eliminate the need

    for any additional protection against corrosion. Thetransparent covers contribute significantly to thecorrect operation of a system, because switchgearoperation can be monitored even with the doors orcovers closed, thus virtually eliminating the possibil-ity of these being left open through carelessness.The transparent cover is an important contributionto safety, especially where exports to areas of un-certain skills are concerned.

    For overcurrent protective devicesAlways use circuit-breakers and motor-protective cir-cuit-breakers. Avoid fuses as far as possible.Advantage: The operational reliability of a system is especially

    important for export contracts. Circuit-breakers andmotor-protective circuit-breakers provide this relia-bility in full measure since they can be immediately

    reclosed once a fault has been cleared, they discon-nect all poles, they have ideal protection throughhigh tripping accuracy and they can be used for se-lective operation. Because they have no fuses orother consumables, they also greatly reduce theproblem of obtaining replacement parts. The ad-vantages of fuseless design for export are especiallyevident in this case. No complicated investigation isneeded to find out which fusing system is used inthe respective location and which specificationshave to be followed to select the correct fuses. Of-ten several different fuse systems with widely vary-ing characteristics are used side-by-side in the samecountry. For the uninitiated, it may be almost im-possible to find the right fuse in these circumstanc-es. These problems do not arise where a circuit-breaker is used.

    For main switchesand safety switches

    Use devices with positive contact separation andclear switch position indication.Advantage: The mechanical coupling of the actuating element

    with the contacts ensues that the Off position is in-dicated only when all main contacts are separatedby the prescribed distance, and only in this positioncan the switch be padlocked. This ensures safetywhen carrying out maintenance and repair work onthe installation or machinery.

    Test authorities

    Moeller devices have the approvals required for use inthe following countries;For details afrom Page A1/4

    Shipping classifications

    Moeller devices have been approved by the followingshipping classification societies:For details afrom Page A1/8

    USAUL

    SlovakiaSKSKTC

    GermanyGermanischerLloydGL

    CanadaCDNCSA

    PolandPLBBJ-SEP

    United KingdomLloyds Register ofShippingLR

    RomaniaROICECON

    ML PAT TurkeyTRTSE

    FranceBureauVeritasBV

    RussiaRUSGOST-R

    ChinaPRCCCC

    RussiaRussian MaritimeRegister of ShippingRS

    South AfricaZASABS

    UkraineUAUkrain-GOST

    ItalyRegistro ItalianoNavaleRINA

    NorwayDet Norske VeritasDNV

    PolandPolski RejestrStatkowPRS

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    4/44

    Moeller HPL0211-2007/2008

    A1/4

    http://catalog.moeller.net

    pp

    Approvals for world marketsCountry-specific approvals

    CountryTest authorities

    USA CDN AUS RUS ZA PRC UA

    UL CSA C-Tick GOST-R SABS CCC Ukrain-GOST

    Control Circuit Devices

    RMQ16 K K K N K

    RMQ-Titan K K K N K KFAK.../I K K K N K K

    SL signal towers K K K N K

    Position switch

    LS... K K K N K

    LS-...-...-ZB, LS-...-...-ZBZ/... K K K N K

    Pressure switches

    MCS..., MCSN... K1) N N K

    easy Relay

    EASY512-AB-RC(X) K K K K N N K

    EASY512-AC-R K K K K N N K

    EASY512-AC-RC(X) K K K K N N K

    EASY512-DA-RC(X) K K K K N N K

    EASY512-DC-R K K K K N N K

    EASY512-DC-RC(X) K K K K N N K

    EASY512-DC-TC(X) K K K K N N K

    EASY719-AB-RC(X) K K K K N N K

    EASY719-AC-RC(X) K K K K N N K

    EASY719-DA-RC(X) K K K K N N K

    EASY719-DC-RC(X) K K K K N N K

    EASY721-DC-TC(X) K K K K N N K

    EASY819-AC-RC(X) K K K K N N K

    EASY819-DC-RC(X) K K K K N N K

    EASY820-DC-RC(X) K K K K N N K

    EASY821-DC-TC(X) K K K K N N K

    EASY822-DC-TC(X) K K K K

    N N K

    easy Control

    EC4P-221-MTXD1 k k k k N N k

    EC4P-221-MTXX1 k k k k N N k

    EC4P-221-MRXD1 k k k k N N k

    EC4P-221-MRXX1 k k k k N N k

    EC4P-221-MTAD1 k k k k N N k

    EC4P-221-MTAX1 k k k k N N k

    EC4P-221-MRAD1 k k k k N N k

    EC4P-221-MRAX1 k k k k N N k

    EC4P-222-MTXD1 k k k k N N k

    EC4P-222-MTXX1 k k k k N N k

    EC4P-222-MRXD1 k k k k N N k

    EC4P-222-MRXX1 k k k k N N kEC4P-222-MTAD1 k k k k N N k

    EC4P-222-MTAX1 k k k k N N k

    EC4P-222-MRAD1 k k k k N N k

    EC4P-222-MRAX1 k k k k N N k

    Input/output expansion

    EASY618-AC-RE K K K K N N K

    EASY618-DC-RE K K K K N N K

    EASY620-DC-TE K K K K N N K

    EASY202-RE K K K K N N K

    Coupling module

    EASY200-EASY K K K K N N K

    Notes K Approved or acceptedk Approval applied for

    N Approval or acceptance notrequired

    Not approved or accepted1) Form CDN

    RMQ, SL, MSC(N), EASY, EC4P

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    5/44

    A1/5

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Approvals for world marketsCountry-specific approvals

    CountryTest authorities

    USA CDN OFF RUS ZA PRC UA

    UL CSA C-Tick GOST-R SABS CCC Ukrain-GOST

    Gateways

    EASY204-DP K K K K N N K

    EASY205-ASI K K K K N N KEASY221-CO K K K K N N K

    EASY222-DN K K K K N N K

    EASY223-SWIRE k k k k N N k

    K KEthernet module

    EASY209-SE K K k k N N k

    easy MFD

    MFD-80-B K K K K N N K

    MFD-80-B-X K K K K N N K

    MFD-80 K K K K N N K

    MFD-80-X K K K K N N K

    MFD-AC-CP8-ME K K K K N N K

    MFD-AC-CP8-NT K K K K N N KMFD-CP8-ME K K K K N N K

    MFD-CP8-NT K K K K N N K

    MFD-CP4 K K K K N N K

    MFD-CP4-500 K K K K N N K

    MFD-CP4-800 K K K K N N K

    MFD-AC-CP4 K K K K N N K

    MFD-AC-CP4-500 K K K K N N K

    MFD-AC-CP4-800 K K K K N N K

    MFD-R16 K K K K N N K

    MFD-T16 K K K K N N K

    MFD-RA17 K K K K N N K

    MFD-TA17 K K K K N N KMFD-AC-R16 K K K K N N K

    MFD-TP12-PT-A k k k k N N k

    MFD-TP12-PT-B k k k k N N k

    MFD-TP12-NI-A k k k k N N k

    MFD-TAP13-PT-A k k k k N N k

    MFD-TAP13-PT-B k k k k N N k

    MFD-TAP13-NI-A k k k k N N k

    Accessories

    EASY200-POW K K K K N N K

    EASY400-POW K K K K N N K

    EASY256-HCI K K K K N N K

    Contactor relaysDILER K K N K N K

    DILA K K N k k k k

    DILA-XHI K K N k k k k

    Electronic timing relays

    ETR 4-... K K K N K K

    DIL ET K K N K

    Safety relay

    ESR... K K N K K

    Measuring and MonitoringRelays

    EMR4... K K N

    Notes K Approved or acceptedk Approval applied for N Approval or acceptance notrequired Not approved or accepted

    EASY, MFD, DIL, ETR, ESR, EMR

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    6/44

    Moeller HPL0211-2007/2008

    A1/6

    http://catalog.moeller.net

    pp

    Approvals for world marketsCountry-specific approvals

    CountryTest authorities

    USA CDN OFF RUS ZA PRC UA

    UL CSA C-Tick GOST-R SABS CCC Ukrain-GOST

    Contactors

    DILM7, DILM9, DILM12, DILM15 K K N K K K K

    DILM17, DILM25, DILM32 K K K K K K K

    DILM40, DILM50, DILM65 K K K K K K K

    DILM80, DILM95, DILM115, DILM150 K K K K K K K

    DILMP20 K K N K K K K

    DILM-XHI K K N K K K K

    DILM-XMV K K N K K K K

    DILM...-XVB K K N K K K K

    DILM...-XSP K K K K K K K

    DILM...-XS1 K K N K K K K

    DILM...-XP1 K K N K K K K

    DILM...-XSP K K K K K K K

    DILEM(-G) K K N K K K K

    DILM185, DILM225, DILM250 K K K K K K K

    DILM300, DILM400, DILM500 K K K K K K K

    DILM580, DILM650, DILM750, DILM820,DILM1000, DILM1600

    K K K K K K

    DILH1400, DILH2000 K K K N K KDILL K K N N

    DILMF K K N

    DILK12 DILK50 K K N N

    Overload relays

    ZB12 K K N K K K K

    ZB32 K K N K K K K

    ZB65 K K N K k K K

    ZB150 K K N K k k K

    ZE-... K K N K N K K

    Z5-.../FF250 K K N K K K K

    ZW7-... K K N K N K

    ZW7-630 N K N K

    ZEV K K K N K K

    Thermistor relay for machine protection

    EMT 6 K K K N K

    Motor-protective circuit-breakers

    PKZM01 K K N K K K K

    PKZM0... K K N K K K K

    PKZM0-T K K N N K

    PKZ2.../ZM... K K N K K K K

    PKZ2/.../S-SP... K1) K1) N N N K

    PKZM4-... K K N K K K

    Circuit-breaker, Switch-disconnectorP1, P3 K3) K3) N K K 2)

    P5 K K N 2) 2) 2)

    NZM1 K1) K1) K K K 2)

    NZM2 K1) K1) K K K 2)

    NZM3 K1) K1) K K K 2)

    NZM4 K1) K1) K K K 2)

    PN1 K 2)

    PN2 K 2)

    PN3 K 2)

    N1 K1) K1) K K 2)

    N2 K1) K1) K K 2)

    N3 K1) K1) K K 2)

    N4 K1) K1) K K 2)

    Notes K Approved or acceptedk Approval applied for1) Switchgear for North America2) On request3) Switchgear for North America In surface

    mounting enclosure

    N Approval or acceptance notrequired

    Not approved or accepted

    DIL, Z, EMT, PKZ, NZM, (P)N

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    7/44

    A1/7

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Approvals for world marketsCountry-specific approvals

    CountryTest authorities

    USA CDN OFF RUS ZA PRC UA

    UL CSA C-Tick GOST-R SABS CCC Ukrain-GOST

    Rotary switches

    T0-..., T3-..., T5-... K K K K K

    Circuit-breakersIZMB(N)(H)2(4)...-800 K K1) K

    IZMB(N)(H)2(4)...-1000 K K1) K

    IZMB(N)(H)2(4)...-1250 K K1) K

    IZMB(N)(H)2(4)...-1600 K K1) K

    IZMB(N)(H)2(4)...-2000 K K1) K

    IZMB(N)(H)2(4)...-2500 K K1) K

    IZMB(N)(H)2(4)...-3200 K K1) K

    IZMH3(4)...-4000 K K1) K

    IZMH3(4)...-5000 K K1) K

    IZMH3(4)...-6300 K K1) K

    Supplementary Protectors2)

    FAZB..., FAZC..., FAZR..., FAZS... K K

    Miniature circuit-breakers

    FAZ, B characteristic K K K K K

    FAZ, C characteristic K K K K K

    FAZ, D characteristic K K K K K

    FAZ-HK K K K K

    FI... k k

    FI-HK... k

    ASA, USA K K

    Transformers

    STI/STZ K K N N N K

    DTI/DTZ K K N N N K

    UTI K K N N N

    CI insulated enclosuresCI..-...-NA, CI..-.../(2)T-NA K K N3) on request K3)

    CI..X-...-NA, CI..X-.../T-NA K K N3) on request K3)

    D...-CI..-NA, T-CI...-NA K K N3) on request K3)

    STB...ZOLL K K N3) on request K3)

    FL...-X-NA K K N3) on request K3)

    ZRF3-NA K K N3) on request K3)

    CI-K small enclosure

    CI-K...-NA K K N3) K3)

    DrivesSoft starters and accessories

    DM4-340 K K

    DS4-340 K K k

    DS6-340 K K k

    DE4-KEY-2 K K

    DE4-COM-2X K K

    DE4-NET-DP2 K K

    Frequency inverters and accessories

    DF51-320 K K

    DF51-322 K K

    DF51-340 K K

    DV51-320 K K

    DV51-322 K K

    DV51-340 K

    DF6-340 K K

    DV6-340 K K Notes K Approved or accepted

    k Approval applied for1) IN switch-disconnectors also have approvals2) As supplementary protectors up to 40 A only3) Applies only for standard CI types; not for NA

    (North America) versions

    N Approval or acceptance notrequired

    Not approved or accepted

    T, IZM, FAZ, CI, DM, DS, DE, DF, DV

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    8/44

    Moeller HPL0211-2007/2008

    A1/8

    http://catalog.moeller.net

    pp

    Approvals for world marketsShipping classifications

    Classification body

    GB D N F I RUS PL

    LloydsRegisterof Shipping

    LR

    German.Lloyd

    GL

    DetNorskeVeritas

    DNV

    Bureau Veritas

    BV

    RegistroItalianoNavale

    RINA

    RussianMaritimeRegisterof Shipping

    RS

    PolskiRejestrStatkw

    PRS

    Control Circuit DevicesRMQ16 K K K K K K K

    RMQ-Titan K K K K K k K

    FAK/I K K

    SL signal towers K K k k N k K

    Position switch

    LS K K K K

    LS-ZB K

    Control relays

    EASY512-AB-RC(X) K K K K

    EASY512-AC-R K K K K

    EASY512-AC-RC(X) K K K K

    EASY512-DA-RC(X) K K K K

    EASY512-DC-R K K K K

    EASY512-DC-RC(X) K K K K

    EASY512-DC-TC(X) K K K K

    EASY719-AB-RC(X) K K K K

    EASY719-AC-RC(X) K K K K

    EASY719-DA-RC(X) K K K K

    EASY719-DC-RC(X) K K K K

    EASY721-DC-TC(X) K K K K

    EASY819-AC-RC(X) K K K K

    EASY819-DC-RC(X) K K K K

    EASY820-DC-RC(X) K K K K

    EASY821-DC-TC(X) K K K K

    EASY822-DC-TC(X) K K K K

    Programmable logic controller

    EC4P-221-MTXD1 k k k k

    EC4P-221-MTXX1 k k k k

    EC4P-221-MRXD1 k k k k

    EC4P-221-MRXX1 k k k k

    EC4P-221-MTAD1 k k k k

    EC4P-221-MTAX1 k k k k

    EC4P-221-MRAD1 k k k k

    EC4P-221-MRAX1 k k k k

    EC4P-222-MTXD1 k k k k

    EC4P-222-MTXX1 k k k k

    EC4P-222-MRXD1 k k k k

    EC4P-222-MRXX1 k k k k EC4P-222-MTAD1 k k k k

    EC4P-222-MTAX1 k k k k

    EC4P-222-MRAD1 k k k k

    EC4P-222-MRAX1 k k k k

    Input/output expansion

    EASY618-AC-RE K K K K K

    EASY618-DC-RE K K K K K

    EASY620-DC-TE K K K

    EASY202-RE

    Coupling device

    EASY200-EASY

    GatewaysEASY204-DP

    EASY205-ASI

    EASY221-CO K

    EASY222-DN

    EASY223-SWIRE

    RMQ, FAK, SL, EASY, EC4P

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    9/44

    A1/9

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Approvals for world marketsShipping classifications

    Classification body

    GB D N F I RUS PL

    LloydsRegisterof Shipping

    LR

    German.Lloyd

    GL

    DetNorskeVeritas

    DNV

    BureauVeritas

    BV

    RegistroItalianoNavale

    RINA

    RussianMaritimeRegisterof Shipping

    RS

    PolskiRejestrStatkw

    PRS

    Ethernet moduleEASY209-SE

    Multi-function-Display

    MFD-80-B K K K K

    MFD-80-B-X K K K K

    MFD-80 K K K K

    MFD-80-X K K K K

    MFD-AC-CP8-ME

    MFD-AC-CP8-NT

    MFD-CP8-ME K K K K

    MFD-CP8-NT K K K K

    MFD-CP4

    MFD-CP4-500

    MFD-CP4-800 MFD-AC-CP4

    MFD-AC-CP4-500

    MFD-AC-CP4-800

    MFD-R16 K K K K

    MFD-T16 K K K K

    MFD-RA17 K K K K

    MFD-TA17 K K K K

    MFD-AC-R16

    MFD-TP12-PT-A

    MFD-TP12-PT-B

    MFD-TP12-NI-A

    MFD-TAP13-PT-A

    MFD-TAP13-PT-B

    MFD-TAP13-NI-A Accessories

    EASY200-POW

    EASY400-POW

    EASY256-HCI

    Contactor relays1)

    DILER K K K K K K K

    DILA, DILA-XHI k k k k

    Electronic timing relays

    ETR4- K

    EMR4-

    Contactors2)

    DILM7 DILM15 K K K k DILM17 DILM32 K K K k

    DILM40 DILM65 K K K k

    DILM80 DILM150 K K K k

    DILMP20 K K K k

    DILEM(-G) K K K K K K K

    DILM185, DILM225, DILM2503) K K K K K K K

    DILM300, DILM400, DILM5003) K K K K K K K

    DILM580, DILM650, DILM750, DILM820,DILM10003)

    K K K K

    DILM1600, DILH1400, DILH2000 K K K k

    Thermistor relay for machineprotection

    EMT6 K

    Notes 1) Switchgear for North America2) The approvals also cover the relevant product accessories.3) RA 110, RA 250

    K Approved or acceptedk Approval applied forN Approval or acceptance not required Not approved or accepted

    EASY, MFD, DIL, ETR, EMR, EMT

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    10/44

    Moeller HPL0211-2007/2008

    A1/10

    http://catalog.moeller.net

    pp

    Approvals for world marketsShipping classifications

    Classification body

    GB D N F I RUS PL

    LloydsRegisterof Shipping

    LR

    German.Lloyd

    GL

    DetNorskeVeritas

    DNV

    Bureau Veritas

    BV

    RegistroItalianoNavale

    RINA

    RussianMaritimeRegisterof Shipping

    RS

    PolskiRejestrStatkw

    PRS

    Overload relays1)

    ZB12 K K k k

    ZB32 K K k k

    ZB65 k K k k

    ZB150 k K k k

    ZE-... K K K K K K K

    Z5-... K K K K K K K

    ZW7-..., ZW7-630 K K K

    Rotary switches1)

    T0..., T3 K K K K

    T 5..., T5B K K

    Motor-protective circuit-breakers1)

    PKZM01 K K k k k k k

    PKZM0..., PKZ2.../ZM... K K K K K K K

    PKZM4-... K K K k k k K

    Circuit-breakers, switch-disconnectors1)

    NZM1, NZM2, NZM3, NZM4 K K K k

    PN1, PN2, PN3 k

    N1, N2, N3, N4 K k

    P1, P3 K K K K

    P5 2) 2) 2) 2)

    Circuit-breakers1)

    IZMB(N)1(-4)--630 K K K

    IZMB(N)1(-4)--800 K K K IZMB(N)1(-4)--1000 K K K

    IZMB(N)1(-4)--1250 K K K

    IZMB(N)1(-4)--1600 K K K

    IZMB(N)(H)2(-4)--800 K K K

    IZMB(N)(H)2(-4)--1000 K K K

    IZMB(N)(H)2(-4)--1250 K K K

    IZMB(N)(H)2(-4)--1600 K K K

    IZMB(N)(H)2(-4)--2000 K K K

    IZMB(N)(H)2(-4)--2500 K K K

    IZMB(N)(H)2(-4)--3200 K K K

    IZMH3(-4)--4000 K K K

    IZMH3(-4)--5000 K K K

    IZMH3(-4)--6300 K K K

    Switch-disconnectors1)

    IN... K

    Miniature circuit-breakers1)

    FAZ, B characteristic K k K K K

    FAZ, C characteristic K k K K K

    FAZ, D characteristic K k K K K

    FIM K

    CI distribution boards

    ID K

    Notes K Approved or acceptedk Approval applied for

    Not approved or acceptedN Approval or acceptance not required

    1)

    The approvals also cover the relevant product accessories.2) On request

    ZB, T, PKZ, NZM, (P)N, IZM, FAZ, CI

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    11/44

    A1/11

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Approvals for world marketsShipping classifications

    Classification body

    GB D N F I RUS PL

    LloydsRegisterof Shipping

    LR

    German.Lloyd

    GL

    Det NorskeVeritas

    DNV1)

    Bureau Veritas

    BV

    RegistroItalianoNavale

    RINA

    RussianMaritimeRegisterof Shipping

    RS

    PolskiRejestrStatkw

    PRS

    Envi-ron-ment

    Volt-age

    Unin-ter-ruptedcurrent

    Envi-ron-ment

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    V A V A V A V A V A V A V A

    Control CircuitDevices

    RMQ16 1, 2, 3 C

    Contact elements

    E10, E01 250 4 250 4 250 4 250 4 250 4 250 4 250 4

    Indicator lights,illuminatedpushbuttons,illuminated selectorswitch actuators

    Q18(25)L... 24 1 W C 24 1 W 24 1 W 24 1 W 24 1 W 24 1 W 24 1 W

    RMQ-Titan 1, 2, 3 C on request on request on request on request on request

    Contact elements

    M22-(C)K(C)... 500 6 500 6 500 6 500 6 500 6 500 6 500 6

    LED elements

    M22-(C)LED... 24 0.26 W 24 0.26 W 24 0.26 W 24 0.26 W 24 0.26 W 24 0.26 W 24 0.26 W

    230 0.33 W 230 0.33 W 230 0.33 W 230 0.33 W 230 0.33 W 230 0.33 W 230 0.33 W

    Position switches

    LS...LS-ZB

    C 500 10

    Contactor relays

    DILA... 1,2,3 500 10 C 500 10 500 10 500 10 DILER...(-G) 1,2,3 600 10 C 500 10 500 10 500 10 600 10 500 10 500 10

    DILR...(-G)TP... 1,2,3 500 10 C 500 10 500 10 500 10 500 10 500 10 500 10

    Timing andmonitoring relays

    EMT6 A 400 3

    EMR4 D

    ETR4 A 440

    Circuit-breakers,switch-disconnectors

    NZM1 1,2,3 690 1602) C 690 1602) 630 125 3) 3)

    NZM2 1,2,3 690 2502) C 690 2502) 690 250 3) 3)

    NZM3 1,2,3 690 6302) C 690 6302) 690 630 3) 3) NZM4 1,2,3 690 16002) C 690 16002) 690 1600 3) 3)

    PN1 1,2,3 690 1602) C 690 1602) 690 125 3) 3)

    PN2 1,2,3 690 2502) C 690 2502) 690 250 3) 3)

    PN3 1,2,3 690 6302) C 690 6302) 690 630 3) 3)

    N1 1,2,3 690 1602) C 690 1602) 690 125 3) 3)

    N2 1,2,3 690 2502) C 690 2502) 690 250 3) 3)

    N3 1,2,3 690 6302) C 690 6302) 690 630 3) 3)

    N4 1,2,3 690 16002) C 690 16002) 690 1600 3) 3)

    Miniature circuit-breakers

    FAZ, B, C, Dcharacteristic

    1,2,3 440 63 C 440 63 440 63 440 63 400 63

    Notes 1) For installations inside switchboards/enclosures onboard ships and offshore unit2) 50 C Ambient temperature3) On request

    RMQ, LS, DIL, ETR, EMR, NZM, (P)N, FAZ

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    12/44

    Moeller HPL0211-2007/2008

    A1/12

    http://catalog.moeller.net

    pp

    Approvals for world marketsShipping classifications

    Classification body

    GB D N F I RUS PL

    LloydsRegisterof Shipping

    LR

    German.Lloyd

    GL

    Det NorskeVeritas

    DNV1)

    Bureau Veritas

    BV

    RegistroItalianoNavale

    RINA

    RussianMaritimeRegisterof Shipping

    RS

    PolskiRejestrStatkw

    PRS

    Envi-ron-ment

    Volt-age

    Unin-ter-ruptedcurrent

    Envi-ron-ment

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    Volt-age

    Unin-ter-ruptedcurrent

    V A V A V A V A V A V A V A

    Contactors

    DILEM...(-G) 1,2,3 690 20 C 690 20 690 20 690 20 690 20 690 20 690 16

    DILM7-12 1,2,3 690 20 C 690 20 690 20 690 20

    DILM17 1,2,3 690 35 C 690 35 690 35 690 35

    DILM25, 32 1,2,3 690 40 C 690 40 690 40 690 40

    DILM40 1,2,3 690 50 C 690 50 690 50 690 50

    DILM50 1,2,3 690 65 C 690 65 690 65 690 65

    DILM65 1,2,3 690 80 C 690 80 690 80 690 80

    DILM80() 1,2,3 690 90 C 690 90 690 90 690 90

    DILM95 1,2,3 690 110 C 690 110 690 110 690 110

    DILM115 1,2,3 690 130 C 690 130 690 130 690 130

    DILM150 1,2,3 690 160 C 690 160 690 160 690 160

    DILM185 1,2,3 1000 225 C 1000 225 1000 225 1000 225 1000 225 1000 225 1000 225

    DILM225 1,2,3 1000 250 C 1000 250 1000 250 1000 250 1000 250 1000 250 1000 250

    DILM250 1,2,3 1000 300 C 1000 300 1000 300 1000 300 1000 300 1000 300 1000 300

    DILM300 1,2,3 1000 350 C 1000 350 1000 350 1000 350 1000 350 1000 350 1000 350

    DILM400 1,2,3 1000 450 C 1000 450 1000 450 1000 450 1000 450 1000 450 1000 450

    DILM500 1,2,3 1000 550 C 1000 550 1000 550 1000 550 1000 550 1000 550 1000 550

    DILM580 1,2,3 1000 800 C 1000 800 1000 800 1000 800

    DILM650 1,2,3 1000 850 C 1000 850 1000 850 1000 850

    DILM750 1,2,3 1000 900 C 1000 900 1000 900 1000 900

    DILM820 1,2,3 1000 1000 C 1000 1000 1000 1000 1000 1000

    DILM1000 1,2,3 1000 1000 C 1000 1000 1000 1000 1000 1000

    DILH1400 1,2,3 1000 1400 C 1000 1400 1000 1400 1000 1400

    DILH2000 1,2,3 1000 2000 C 1000 2000 1000 2000 1000 2000

    Motor protection relay

    ZB12 1,2 690 12 A 690 12 690 12 690 12

    ZB32 1,2 690 32 A 690 32 690 32 690 32

    ZB65 1,2 690 65 A 690 65 690 65 690 65

    ZB150 1,2 690 150 A 690 150 690 150 690 150

    ZE-... 1,2 690 9 A 690 9 690 9 690 9 690 9 690 9 690 9

    Z5-... A 1000 220

    ZW7-... A 750 630 690 630 690 630T rotary switches, with "disconnect function"

    T0-... 1,2,3 690 20 A 660 20 690 20 660 20

    T3-... 1,2,3 690 32 A 660 32 690 32 660 32

    T5-... 690 100

    P switch-disconnector (Miscellaneous switches) with "disconnect function"

    P1-... 1,2,3,4 690 32 C 690 32 690 32 690 32

    P3-... 1,2,3,4 690 100 C 690 100 690 100 690 100

    Motor-protective circuit-breakers

    PKZM01 1,2,3 690 12 A 690 12 690 12 690 12

    PKZM0-...S(E)00... 1,2,3 690 10 A 690 10 690 10 690 10 690 10 690 10 690 10

    PKZ 2... 1,2 690 40 A 690 40 660 40 690 40 690 40 690 40 690 40

    PKZM4-... 1,2,3 690 63 A 690 63 690 63 690 63 690 63 690 63 690 63

    Notes 1)For installations inside switchboards/enclosures onboards ships and offshore units

    DIL, Z, T, P, PKZ,

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    13/44

    A1/13

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Switchgear for North AmericaApprovals

    In the USA, the legally established OSHA (OccupationalSafety and Health Act) and the NEC (National ElectricalCode) require the use of approved devices andsystems.

    In Canada, all electrical apparatus must comply withthe CEC (Canadian Electrical Code), which requiresthat all equipment and installations have CSAapproval.

    In view of these requirements, and because US andCanadian standards deviate widely from those of otherindustrial countries and the IEC, Moeller has, untilrecently, modified product series to bring them in linewith North American standards.

    New developments are designed as devices for worldmarkets from the outset, which means that they meetall requirements including those of the USA andCanada without the need for any additionalequipment or modifications.

    In addition to the normal UL and CSA approvals, thetrade regulations originating from the NAFTAagreements allow the application for a joint UL andCSA approval. The devices then carry a logo that isrecognized in both countries.

    Because market acceptance of the joint approval is stillquite low, Moeller has not made use of this facility untilnow. Some local inspectors and end users still refuse toaccept the joint listing. This section of the Cataloguecontains two group of switching devices for NorthAmerica:

    They have all required approvals including the UL andCSA approval (UL = Underwriters Laboratories,CSA = Canadian Standards Association) and can beused throughout the world.

    They have ratings plates with all important data forworldwide use as well as their use in the USA and inCanada.

    For unrestricted sale in European Union memberstates, the devices contain the CE mark.

    They are UL- and/or CSA-approved and can be usedin the USA, in Canada and in any country in whichUL- and CSA-approval or conformance with NorthAmerican standards are required.

    They have ratings plates containing all importantdata for use in the USA and in Canada.

    Except for occasional differences in their designdetail required for approval, they are largelyidentical with the normal devices of the sameseries.

    Approvals for the USA and for Canada areindicated by a suffix in the devices typedesignation. The type of approval for a device isindicated on the ratings plates by the followingtype suffixes and approval marks:

    As a rule, devices for North America also carry IECor CE-..., for example NZM...-NA circuit-breakers.

    In Canada and the USA, a distinction is made betweendistribution equipment and industrial controlequipment:

    This includes, for example Circuit-breakers

    Disconnectors Switch-disconnector: Fuses Fused interrupters

    These devices are of a rugged design and have largerinsulating clearances than other switching devices (for301 600 V: 1 inch = 25.4 mm clearance and2 inches = 50.8 mm creepage distance).In power distribution switchgear (switchgear,switchboards, panelboards), only these devices mustbe used for power supply and tap-off. In addition, theyare also used as main switches or circuit-breakers inmotor and other load circuits in industrial control.

    Testing of these devices is especially stringent, withrunning production being subject to regular checks bytest authority inspectors. The type tests for circuit-

    breakers with UL- and CSA-approval are among theworlds strictest tests.

    Circuit-breakers from Moeller have passed all of thesetests.

    This includes, for example Contactors Contactor relays Overload relays Motor-protective circuit-breakers Rotary switches Control circuit devices Electronic devices and systems User-programmable controllers

    These devices have smaller physical dimensions andthe insulating clearances are not as great as those ofthe devices for power distribution. Running productionis also monitored by test authority inspectors, but theinspection requirements are not as extensive as thosefor circuit-breakers.

    This industrial control equipment is used mainly inelectrical controllers, motor circuits and consumer

    circuits of all types, in motor control centres (MCC) andin power distribution systems. In controllers, they canbe combined directly with devices for powerdistribution, for example with circuit-breakers as mainswitches or in a motor feeder.

    Similar to the utilization categories for low-voltageswitchgear of the IEC and other national standards,duty types for the various types of switched loadshave been defined for industrial control equipment inCanada and the USA. The type of load for each dutytype is indicated on the devices ratings plate or in itstechnical specifications and defines is applicationpurpose. The table below provides an overview of thisassignment.

    1) Devices for world markets with the followingmain characteristics:

    2) Devices for North America with the followingmain characteristics:

    Typesuffix

    Type of approval Approval mark

    -NA The device is UL-and CSA-approvedas discrete device.

    FORMCDN

    The device is CSA-approved as discretedevice.

    FORMUSA

    The device is ULapproved as discretedevice.

    -CNA The device containsUL-approvedcomponents; itsapproval conditionsmust be maintainedin use. The device isCSA-approved as

    discrete device.

    Device types in North America

    Distribution equipment

    Industrial control equipment

    Performance data for industrial control

    Duty type

    Load typeindicated on theratings plate

    1) Motors Horsepower(HP)

    2) Coils

    (in auxiliary andcontrol circuits)

    Code Designation,Voltampere, StandardPilot Duty or Heavy PilotDuty

    3) Resistance (heating) Amperes, resistance only

    4) Incandescent lamps Amperes or Watts,tungstenAmperes or Watts,tungsten

    5) Ballast (electricdischarge lamps)

    Amperes, ballast

    6) General Use1) Amperes(A)

    1)The General Use group corresponds with IECCategory AC-1.

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    14/44

    Moeller HPL0211-2007/2008

    A1/14

    http://catalog.moeller.net

    pp

    Switchgear for North AmericaSelection of devices

    In North America, these devices are industrial controlequipment according to UL 508 and CSA-C 22-2No. 14). For the North American market, contactorsmust have so-called NEMA-sizes, unless they areused for switching motors, for which orders will specifyratings in HP.

    NEMA=National Electrical Manufacturers Association(USA).

    This part of the Main Catalogue lists the contactorswith the HP ratings approved for North America.

    The table on aPage A1/16 provides an overview ofthe NEMA sizes in relation to the HP ratings andcontinuous currents.

    First of all, it is important to know that when NorthAmerican customers speak of non-combination motorstarters they mean what in Europe is referred to as acontactor and overcurrent relay and will give thesame ordering information as for contactors. Complete

    contactor and overcurrent relay combinations can beassembled as per aPage A1/23.

    Motor starters, which in Europe combine all devices forshort-circuit protection, overload protection andoperational switching of the motor (such as circuit-breaker, contactor and overcurrent relay), are termedcombination motor starter in North America. Thistype of motor starter must be configured like a smallcontrol system complete with all relevant individualdevices. Contactor and overcurrent relay are selectedas previously described.

    According to UL 508 and CSA C 22.2 No. 14, approvedmotor starters must be short-circuit-protected with UL-or CSA-approved circuit-breakers or fuses. This short-circuit protection is fitted separately.

    According to a supplement to UL 508, motor starterscan now also be tested as combination motorcontroller type E for which an additional short-circuitprotection is not required (self-protected starter). Thistest is also accepted by CSA.

    All components for a complete motor starter, includingfull short-circuit protection, are contained in a singledevice. This reduces the required space and eliminatesthe wiring between the components. These devices

    are used in motor control centres (MCC), in controllersand as discrete starters in separate enclosures. Up tothe specified switching capacity, these devices do notneed additional short-circuit protection.

    In the PKZ2 system, these devices are available withtype designation PKZ2/ZM-../S-SP.

    In addition, the type E combination motorcontrollers comprise the manual self-protectedstarters, which require larger clearances andcreepage distances according to UL 508 or CSA-C 22.2No. 5.2 if no upstream short-circuit protective devicesare to be used. These devices are suitable for manualswitching of motors.

    The manual self-protected starters are implementedwith a PKZM0 or PKZM4 with an additional, specialBK25/3-PKZ0-E or BK50/3-PKZ4-E incoming terminal.On the PKZM4, the HB-PKZ4 terminal shroud can beused instead of the incoming terminal. For use inCanada, these devices must also be lockable, meaningthat starters must be fitted with the AK-PKZ0 rotaryhandle.aPage A1/32

    From the combination of a manual type E starterwith a contactor, you can build type F combinationmotor controllers. These, too do not need anadditional short-circuit protection device.

    Type F starters can be combined and used as peraPage A1/33.

    In North America, these devices are industrial controlequipment to UL 508 and CSA-C 22.2 No. 14) and areused as manually operated motor starters in controllersor separately as discrete devices. They are rated in HPand if they are equipped with auxiliary contacts

    they contain duty type information (pilot duties,aPage A1/16). The devices have fixed or adjustablemagnetic short-circuit releases for short-circuitprotection and adjustable overload relays for motoroverload protection. They can be used for switchingmotor circuits, and their auxiliary contacts forswitching control circuits.

    In combination with a downstream contactor, theybecome a motor starter combination, in which thecontactor, acting as motor controller switches andregulates the motor current and the PKZM providesprotection. Although PKZM motor-protective circuit-breakers have an inherent short-circuit withstandcapability, they must, according to North Americanstandards, always be operated with an upstream short-circuit protection device. With most devices, thespecified short-circuit protection device can also beused for protecting a group of PKZMs. This property isreferred to as group-protection in North America.Some devices can be used only for individualprotection.

    In North America, these devices are industrial controlequipment to UL 508 and CSA-C 22.2 No. 14) and areused mainly in controllers and motor control centres(MCC). They are rated in HP, their short-circuit s trengthis given in kA and if they are equipped with auxiliarycontacts contain duty type information (pilot duties,aPage A1/16).

    The devices have adjustable magnetic short-circuitreleases for short-circuit protection and adjustable

    overload relays for motor overload protection. Theycan be used for switching motor circuits, and theirauxiliary contacts for switching control circuits.

    In combination with a downstream contactor, theybecome a motor starter combination, in which thecontactor, acting as motor controller switches andregulates the motor current and the NZM providesprotection.

    NZM motor-protective circuit-breakers can be used inmotor circuits up to the specified short-circuit rating,whereby the inclusion of a short-circuit protectivedevice in the main incoming supply (for example amotor control centre) is assumed.

    In North America, these devices are circuit-breakers(molded case circuit breakers according to UL 489 orservice entrance branch circuit breakers according toCSA-C 22.2 No.5.1) and are used mainly in motorcontrol centres (MCC), controllers and encloseddiscrete equipment. They are rated in A and if theyare equipped with auxiliary contacts contain duty

    type information (pilot duties,a

    Page A1/16).The devices have adjustable magnetic short-circuitreleases for short-circuit protection. They can be usedfor switching motor circuits and other main circuits,and their auxiliary contacts for switching controlcircuits.

    NZM...OBI circuit-breakers are not used as discretedevices; they are always combined to a combinationmotor starter with a downstream contactor andoverload relay, in which the contactor performsoperational switching and regulation of the motorcurrent, the overload relay acts as overload protectivedevice and the motor-protective circuit-breaker actingas short-circuit protection device. This combinationallows a separate indication of trips caused byoverload and by short-circuits through the auxiliary

    contact of the overload relay and the motor-protectivecircuit-breaker. In North America, combinations of thistype are used in motor control centres (MCC) and asdiscrete starters in separate enclosures.

    At locations with short-circuit currents up to theswitching capacity specified for the completecombination motor starter, they can be usedwithout upstream short-circuit protection device.

    In motor starter outputs, they can be used as mainswitches.

    These devices are circuit-breakers (molded case circuitbreakers according to UL 489, service entrance branchcircuit breakers according to CSA-C 22.2 No. 5.1) inNorth America, where they are the normal switches forpower distribution systems, but can also be used inmotor control centres (MCC) and controllers. They arerated in A, their short-circuit switching capacity isgiven in kA and if they are equipped with auxiliarycontacts contain duty type information (pilot duties,aPage A1/16).

    These devices have adjustable magnetic short-circuitreleases for short-circuit protection and fixed-currentor adjustable overload relays for overload protectionfor non-motor-driven outgoing circuits. They can beused as short-circuit protection devices and forswitching motor circuits, and their auxiliary contactsfor switching control circuits. At mounting locationswith short-circuit currents up to their switchingcapacity, they can be used without upstream short-

    circuit protection device.In main current outgoing and incoming lines, they canbe used as main switches.

    In North America, these devices are industrial controlequipment to UL 508 and CSA-C 22.2 No. 14) and areused mainly in controllers and as discrete devices inmotor circuits. They are rated in HP, their rated currentis given in A and if they are equipped with auxiliarycontacts they contain duty type information (pilotduties, aPage A1/16).

    The devices can be used for switching motor circuitsand other main circuits, and their auxiliary contacts forswitching control circuits.

    Contactors

    Contactor and overcurrent relay combinations(non-combination motor starters)

    Motor starters(Combination motor starter)

    Motor starters without additional short-circuit

    protectionType E starters

    Manual type E starters

    Type F starters

    PKZM motor-protective circuit-breakers

    NZM motor-protective circuit-breakers

    NZM...OBI circuit-breakers

    NZM...A circuit-breakers

    T rotary switches, P 1 and P 3 switch-disconnectors

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    15/44

    A1/15

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Switchgear for North AmericaSelection of devices

    P 1 and P 3 can be used as main switches in motorcircuits and in controllers. The required line fuses aredetailed on the devices ratings plates.

    In North America, these devices are industrial controlequipment to UL 508 and CSA-C 22.2 No. 14) and areused mainly in controllers and motor control centres

    (MCC). They are rated in HP, their rated current is givenin A and if they are equipped with auxiliary contacts they contain duty type information (pilot duties,aPage A1/16).

    The devices can be used for switching motor circuitsand other main circuits, and their auxiliary contacts forswitching control circuits.

    N switch-disconnectors require an upstream short-circuit protection device.

    In main current outgoing and incoming lines, bothdevices can be used as main switches.

    1) Avoid the use of fuses by using fuseless devices,

    such as motor-protective circuit-breakers,observing the selection criteria (aPage A1/17).The reasons for this are as follows:

    a) Fuse bases for North American fuses are verylarge and take up a lot of space.

    b) NZM circuit-breakers provide current isolation,short-circuit protection and overload protectionin a single device and are much less expensiveand smaller than a combination of fuse base,fuses and overload relay.

    c) In the USA and in Canada, many different fusesystems are in use. For non-American vendors, itmay be almost impossible to find out the fusesystem used by the end customer (who may notbe known at all to the vendor).

    d) The plant or machine becomes independent ofthe locally used fuse system.

    2) Because no replacement fuses are needed, spareparts management is simplified. If the use of fusesis unavoidable, we recommend that you observe thefollowing points:

    a) North American fuses are classified according tophysical size, switching capacity and currenttime characteristics. The table on Seite 17/18(Enclosure protection types...) provides a roughoverview. It is best, however, to always ask theend customer about the required fuse types.

    b) Motor circuits:Where slow fuses (dual element time delayfuses or time delay fuses) are used:Rated current of max. line fuse F1.75 ratedmotor current or next-higher fuse rated current(max. 2.25 rated motor current).

    Where fast fuses (non-time delay fuses) areused:Rated current of max. line fuseF 3 ratedmotor current or next-higher rated fuse current(max. 4 rated motor current).

    c) Circuits with non-motor loads: Select the linefuse specified by the manufacturer.

    d) Switchgear:For switchgear requiring line fuses for their ownshort-circuit protection, select fuses accordingto the information in the devices technical dataor on the ratings plate. For short-circuitprotection of the combination of Moellercontactor and overcurrent relay,see aPage A1/23for the max. line fuses.

    To ensure both trouble-free motor starting and short-circuit protection of all devices within a circuit, selectthe smallest fuse required according to criteria 2b), 2c)and 2d).

    In North America, these devices are industrial controlequipment and protectors (supplementary protectors

    according to UL 1077 and CSA-C22.2 No. 235). Theyare used mainly in controllers. They can also be usedas additional protective device in electrical deviceswhose incomer is already short-circuit protected ordoes not need short-circuit protection.

    These devices rated current is given in A. They havenon-adjustable magnetic short-circuit releases forshort-circuit protection and fixed-current or adjustableoverload relays for overload protection for non-motor-driven outgoing circuits.

    They can be used as overload and short-circuitprotection devices in single-phase control circuits withor without additional neutral pole. They must inaddition be fitted with an upstream short-circuitprotection device as per device specifications(technical data aPage A1/38).

    FAZ supplementary protectors are especially wellsuited for fuseless protection of control circuits on thesecondary side of transformers whose primary side isalready short-circuit protected or does not need short-circuit protection.

    For the practice common in Europe of making itpossible for customers to retrofit devices with auxiliarycontacts, undervoltage releases, shunt releases andother accessories, the corresponding UL and CSAapprovals can now be issued.The modular method makes it possible to extend therange of applications of contactors, circuit-breakers,the PKZ2 system and control circuit devices by fitting

    add-on modules. For detailed information, see thedevice data.

    Continuous currents and switching duties for auxiliaryswitches according to the tables for auxiliary switcheson aPage A1/16 are assigned to the codedesignations and switching duty types indicated in thedevices technical specifications and on their ratingsplates. The auxiliary contacts of Moeller devicesapproved mainly for heavy pilot duty, and on somedevices for standard pilot duty. For detailedinformation, see the technical data for the devices. Theratings plate for some auxiliary switches containsinformation such as 600 V, same polarity. Thismeans that adjacent auxiliary contacts of the sameauxiliary switch or switch block must be connectedonly to the same control voltage source.

    Requirements:1) In North America, enclosures are often classified

    and ordered by NEMA type, and in Canada byEEMAC type, even though the binding design,ingress protection, etc. requirements of enclosuresare today contained in NEC NFPA 70, UL 508 andUL 50 for the USA, and in CSA-22.2 No. 14 andCSA-C 22.2 No. 94 for Canada.

    2) The enclosures used by Moeller are accepted foruse in North America, since they are UL- and CSA-approved and meet the most important NEMArequirements regarding contact protection,corrosion protection and ingress protection againstsolids and liquids.

    3) To some extent, the requirement for NEMA typesalso covers design details, such as hinged doors orcovers that can be opened and locks only with atool, external fixing strips for wall-mountingenclosures, etc. To fulfill the NEMA requirement,consult Moeller about the intended application.

    4) Degrees of protection:The IEC standards define the ingress protection ofenclosures against solids and water. The

    comparable standards in Canada and the USA gofurther, also covering protection against ingress ofoil and coolant, and corrosion protection of theenclosure; they also define its place ofinstallation. The table on aPage A1/18providesan overview of the requirements in Canada andthe USA and a comparison with the IP ratings.

    5) Sheet steel enclosures:Sheet steel enclosures can be used for all types ofcontrollers. In North America, cables are still laidmainly in metal conduits that act as continuousearth conductor at the same time. They areconnected to the enclosure flanges with suitablemetal screwed glands, while flanged enclosuresensure continuous conductivity between incomingand outgoing conduits. All enclosures used musttherefore contain metal flanges, and are includedin the protective earthing. Sheet steel enclosureswith metal flanges are also suitable for connectingplastic conduits and cables, which are connectedwith commercial glands. In this configuration, anearth conductor routed with the cabling providesthe protective earthing. The metal flanges can betaken off for drilling the holes for the glands.

    Insulated enclosures:The CI enclosures fulfill the North Americanstatutory design and ingress protectionrequirements (laid out by UL 508 and NEMA 250for the USA, in CSA 22.2 No.14 for Canada), andare therefore suitable for the assembly of motorstarters and miniature and small control systemsfor plants and machines. Their absolute corrosionresistance makes them ideal for use in humid orcorrosive environments. The enclosures are

    suitable for the connection of both metal conduitsand plastic conduits and cables, which areconnected with commercial screwed glands.Because total insulation is usually notrecognized for insulated enclosures in the USA andCanada, protective earthing must be implementedwhen these conduits and cables are connected tothem. The earth conductor must be routed throughthe enclosures as described in the attachedinstallation instructions.The CI-...-NA enclosures are approved both withand without insulated flanges. For a full selectionof UL/CSA-approved CI enclosure types, contactyour regional Moeller sales office. The table onaPage A1/18provides an overview of ingressprotection to NEC (National Electrical Code), UL,NEMA and CSA.

    N switch-disconnectors

    Fuse bases and fuses

    Supplementary Protectors FAZ

    Auxiliary contacts, voltage releases

    Enclosures

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    16/44

    Moeller HPL0211-2007/2008

    A1/16

    http://catalog.moeller.net

    pp

    Switchgear for North AmericaSwitching capacities of auxiliary switches, ratings of 3-phase contactors to NEMA

    CodeDesignation1)

    Conventionalfree air thermalcurrentIth

    Max. switching duty

    120 V AC 240 V AC 480 V AC 600 V AC 600 V AC

    A

    On

    A

    Off

    A

    On

    A

    Off

    A

    On

    A

    Off

    A

    On

    A

    Off

    A

    On

    VA

    Off

    VA

    Auxiliary switches inAC control circuits

    Heavypilotduty2)

    A 150 10 60 6 7200 720

    A 300 10 60 6 30 3 7200 720

    A 600 10 60 6 30 3 15 1.5 12 1.2 7200 720

    Standardpilotduty3)

    B 150 5 30 3 3600 360

    B 300 5 30 3 15 1.5 3600 360

    B 600 5 30 3 15 1.5 7.5 0.75 6 0.6 3600 360

    E 150 0.5 1.8 0.3 216 36

    CodeDesignation1)

    Conventionalfree air thermal

    currentIth

    Max. switching duty

    125 V DCOn/Off

    250 V DCOn/Off

    310 600 V DCOn/Off

    600 V DCOn/Off

    A A A A VA

    Auxiliary switches inDC circuits

    Heavypilotduty2)

    N 150 10 2.2 275

    N 300 10 2.2 1.1 275

    N 600 10 2.2 1.1 0.4 275

    Standardpilotduty3)

    P 150 1.1 138

    P 300 5 1.1 0.55 138

    P 600 5 1.1 0.55 0.2 138

    Q 150 2.5 0.55 69

    Q 300 2.5 0.55 0.27 69Q 600 2.5 0.55 0.27 0.1 69

    R 150 1 0.22 28

    R 300 1 0.22 0.11 28

    Continuouscurrent

    Rating data4)

    200 V/60 Hz 230 V/60 Hz 460 V/60 Hz575 V/60 Hz

    Highestpermissible

    A HP HP HP A

    Three-phasecontactors to NEMA

    00 9 1 1 2 110 18 3 3 5 21

    1 27 7 7 10 32

    2 45 10 15 25 52

    3 90 25 30 50 104

    4 135 40 50 100 156

    5 270 75 100 200 311

    6 540 150 200 400 621

    7 810 300 600 932

    8 1215 450 900 1400

    9 2250 800 1600 2590

    Notes 1) The values 150, 300 and 600indicate the maximum voltagefor which an auxiliary switchcan be used.

    2)

    3)

    Heavy Pilot Duty= high switching capacityStandard Pilot Duty= normal switching capacity

    4) Rating data for 3-phasecontactors, for single-speedmotors, without inching,reversing or plugging.PS = HP

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    17/44

    A1/17

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Switchgear for North AmericaSelection and usage of fuses

    Type1) constrution1)in

    Trippingcharac-teristic1)

    Switchingcapacity

    Applications1) For use in

    USA Canada kAeff

    H Fast 10 Primarily domestic USA,Canada

    Types H, K and No. 59 Codefit the same bases and are thereforeinterchangeable. In the USA,

    the K types are therefore beingincreasingly replaced by the RKtypes.Rated current: 1 600 A

    No. 59

    Code

    Fast 10 Primarily domestic Canada,USA

    K K1/K5 Fast 100 200 Protection of circuits for heating, lighting andfeeders and outgoers for mixed loads.

    USA

    Slow 100 200 Protection of circuits for motors, transformers,heating and lighting.

    USA

    J Fast 200 See item 2 above USA,Canada Compact design. Types J andHRCI-J fit the same bases, all otherfuse types do not fit into thesebases.Rated current: 1 600 A

    Slow 200 See item 3 above. USA,Canada

    HRCI-J Fast 200 See item 2 above USA,Canada

    Slow 200 See item 3 above. USA,Canada

    RK RK1/RK5 Fast 100 200 See item 2 above USA,Canada Types RK1, RK5 and HRCI-R fit thesame bases, all other fuse types donot fit into these bases.Rated current: 1 600 A

    Slow 100 200 See item 3 above. USA,Canada

    HRCI-R Fast 100 200 See item 2 above Canada,USA

    Slow 100 200 See item 3 above. Canada,USA

    HRCII-R Slow fast 100 200 5. Protection of motor circuits Canada All other fuse types do not fit intobases for HRCII-R.

    CC(CD) Fast 200 See item 2 above USA,Canada Very compact design; all other fuse

    types do not fit into these bases.Rated current:CC 1 30 ACD 31 60 A

    Slow 200 See item 3 above. USA,Canada

    L Fast 200 See item 2 above USA,Canada Code fuses for higher ratingsRated current: 601 6000 ASlow 200 See item 3 above. USA,Canada

    Notes 1) The tripping characteristics data and the assigned applications are a rough overview only.The practice, it is always advisable to find out both this information and the required fuseltype from the North American end customer.

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    18/44

    Moeller HPL0211-2007/2008

    A1/18

    http://catalog.moeller.net

    pp

    Switchgear for North AmericaEnclosure protection types to NEC (NFPA 70), UL, CSA, NEMA

    Enclosures

    Enclosure and ingress protection marking to

    Installation site Type of protection ComparableIP rating3)

    NEC NFPA 701)NEMA No. 2501997, Appendix A2)UL 50CSA-C 22.2 No. 94

    Type 1General use

    Indoor installation Protection against accidental contact with live parts and againstalimited amount of falling dirt.

    IP20

    Type 2Drip-tight

    Indoor installation Protection against limited amounts of falling water and dirt IP 22

    Type 3Dust-tight, rain-tight,resistant to hail and ice

    Outdoor installation Protection against falling rain; undamaged by formation of ice on theenclosure

    IP54

    Type 3Rrain-tight,resistant to hail and ice, dust-tight

    Outdoor installation Protection against falling rain; undamaged by formation of ice on theenclosure

    IP54

    Type 3Sdust-tight, rain-tight,resistant to hail and ice

    Outdoor installation Protection against hail; wind-blown dust and wind-blown rain;External mechanisms remain operable while ice laden.

    IP54

    Type 4Dust-tight, water-tight, rain-tight

    Indoor or outdoorinstallation

    Protection against falling rain, splashing water and hosed water;undamaged by formation of ice on the enclosure

    IP 56

    Type 4Xdust-tight, water-tight,corrosion-resistant,rain-tight

    Indoor or outdoorinstallation

    Protection against falling rain, splashing water and hosed water;undamaged by formation of ice on the enclosure, corrosion protection

    IP 56

    Type 6Rain-tight, water-tight, immersible, resistant tohail and ice

    Indoor or outdoorinstallation

    Protection against dust and hosed water;Protection against entry of water duringtemporary limited submersion;Undamaged by formation of ice on the enclosure.

    IP67

    Type 6PRain-tight, water-tight, submersible,corrosion-resistant

    Indoor or outdoorinstallation

    Protection against entry of water during prolonged submersion atlimited depths; corrosion-resistant

    IP67

    Type 5Drip-tight, dust-tight, corrosion-resistant

    Indoor installation Protection against limited amounts of falling water and dirt;corrosion-resistant

    IP 52

    Type 12For use in industry, drip-tight, dust-tight Indoor installation Protection against dust and dripping water IP 52

    Typ 12K4)As Type 12

    Indoor installation As Type 12 IP 52

    Type 13Dust-tight, oil-tight

    Indoor installation Protection against entry of dust, splashing water,oil and non-corrosive fluids.

    IP54

    Notes 1) NEC = National Electrical Code2) NEMA = National Electrical Manufacturers Association3) The IP rating provided as an approximate comparison. A more accurate comparison is not possible, since different

    ingress protection tests and assessment criteria apply. The NEMA types cover the corresponding IP ratings but notthe other way round. In general, NEMA/UL enclosure protection testing is subject to stricter criteria.

    4) For enclosures with knockouts.

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    19/44

    A1/19

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Rating data for approved

    types1)

    UL-File No. E29184

    Pilot Duty General Use

    contactor relay

    DILER-40(31)(22)...(D)DILE

    A 600, P 300 10 A 600 V AC,0.5 A 250 V DC

    DILADILA-XHI

    A 600, P 300 15 A 600 V AC,1 A 250 V DC

    Timing relay

    DILET, ETR4 B 300 6 A 250 V AC

    Note 1)devices for world markets IEC qUL/CSA

    Circuit diagram for North America

    ETR4-11, DILET11 ETR4-69 DILET70 ETR4-70

    ON-DELAY Function: 1121214281

    ON-DELAYFLEETING CONTACT ONENERGIZATIONFLASHINGPULSE GENERATING CONTACT

    Function: 1121214281

    ON-DELAYFLEETING CONTACT ONENERGIZATIONFLASHINGPULSE GENERATING CONTACT

    ETR4-51

    ON-DELAY Function: 121622

    82

    OFF-DELAYON- and OFF-DELAYFLEETING CONTACT ONDE-ENERGIZATIONPULSE SHAPING CONTACT

    Function: 121622

    82

    OFF-DELAYON- and OFF-DELAYFLEETING CONTACT ONDE-ENERGIZATIONPULSE SHAPING CONTACT

    A1

    A2

    15

    16 18

    15

    16 18

    A1

    A2 A2

    A1

    16 18

    15

    Z1 Z2 Z1 Z2

    A1 15

    X1 A2 16 18

    25

    2826

    Z1

    A1

    Z2

    1521

    X1 A2 16 1822 24

    17

    2818

    A1

    A2

    15

    16 18A2

    A1B1 15

    16 18Y2 A2

    Y1 A1

    Z1 Z2 Z1 Z2

    A1 15 25

    28261816A2X1

    B1

    Z1 Z2

    A1B1 15

    1816A2X1

    21

    2422

    Contactor relayDILER, DILR contactor relays, DILET, ETR4 timing relays

    DIL(E)R, DILET, ETR4

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    20/44

    Moeller HPL0211-2007/2008

    A1/20

    http://catalog.moeller.net

    pp

    Display and operator units, control circuit devicesOperator panel, RMQ16, RMQ-Titan

    Rating data for approved

    types1)Function Power supply Inputs Outputs Quantity

    External Bus side Rated values Rated values Digital

    Display and

    operator units

    MI42)

    MI4-110-KC1 Text operator panel 24 V DC

    MI4-117-KC1 Text operator panel 24 V DC MI4-117-KD1 Text operator panel 24 V DC

    MI4-110-KD1 Text operator panel 24 V DC

    MI4-110-KG1 Text operator panel 24 V DC

    MI4-110-KG2 Text operator panel 24 V DC

    MI4-130-TA1 Touch operator panel 24 V DC

    MI4-137-TA1 Touch operator panel 24 V DC

    General technical data

    Maximum operating temperature 50 C (max. 45 C: MI4-150/160/450/550/570/580/590-TA1)

    Terminal cross-section 2 x1,5 mm2

    Notes 1)Devices for world markets IEC qUL/CSA2)cULus Approval

    UL-File No. 29184 Pilot Duty General Use Terminal cross-section

    Rating data forapproved types to UL/CSA 1)

    RMQ16 contact elements

    E10 C 300, Q 300 Cu cable min. AWG 18, max.AWG 14E01 C 300, R 300

    RMQ-Titan contact elements

    M22-K...M22-CK...

    A 600, Q 300,300 V ACsame polarity

    10 A 600 V AC1 A 250 V DC

    2x14 18 AWG2x12 22 AWG

    RMQ-Titan LED elements

    M22-LED...M22-CLED... 2x14 18 AWG2x12 22 AWG

    M22-LC(H)M22-AMC

    2x16 20 AWG2x16 20 AWG

    UL 508 requirements NEMA recommendation

    UL 4X NEMA 13

    Degrees of protection, RMQ-Titan

    All front elements M22(S)-... K K

    Legend plates M22S-ST... K K

    Emergency-Stop labels M22-XAK...M22-XZK...M22-XBK...M22-XYK...

    K

    K

    K

    K

    K

    K

    K

    K

    Foot and palm switches FAK-... K K

    Signal towers SL-... K

    Notes1)Devices for world markets IEC qUL/CSA For North America, the following order in flush

    mounting plates and surface mountingenclosures:

    andqe. g. M22-D-X + M22-XD-R-GB0

    qe.g. M22-D-X + M22-XD-G-GB1

    For details of degrees of protection, aPage A1/18

    START

    STOP

    START

    STOP

    START STOP

    MI4, M22, FAK, SL

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    21/44

    A1/21

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Pressure switches, Position switchesPressure switches, position switches, conduit adapter

    Rating data for approved types to UL/CSA1)

    Max. pressure Rated-iinsulation-voltageto UL/CSA

    Max motor rating HP = PS Ratedoperationalcurrent

    Part no.Article no.

    PriceSee PriceList

    Std.pack

    Ui 115 V 200V

    230V

    460V

    575 Ie

    psi2) V AC HP HP HP HP HP A

    MCS(N) pressure switches, IP55

    With transparent hood

    1-pole, for single-phase motors only 4)

    65 300 0.253) 0.53) 10 MCS4FORMCDN024457

    1 off

    160 0.253) 0.53) MCS11FORMCDN093273

    315 0.253) 0.53) MCS22FORMCDN014965

    MCS(N) pressure switches, IP55

    With transparent hood

    3 pole4)

    65 600 3 3 5 7.5 10 MCSN4FORMCDN

    064798

    1 off

    160 3 3 5 7.5 MCSN11FORMCDN036322

    230 3 3 5 7.5 MCSN16FORMCDN045814

    Notes 1) Devices for world markets: IEC q UL/CSA2) In North America, pressure is stated in pounds/inch (psi) (1 bar = 14.5 psi)3) Heavy Pilot Duty = High switching capacity4) Selection data and application notes aChapter Pressure switches

    UL-File No. E29184 Pilot Duty General Use

    Rating data for approved types to UL/CSA 1)

    Position switches

    LS... A 300, Q 300 When using a metal gland(e.g. V1/2-M20-NA), this must be earthed(not total insulation)

    Safety interlocks

    LS-ZBZ A 300, Q 300 10 A 300 V AC

    UL-approved degrees of protection

    NEMA 4 NEMA12 NEMA 13

    Position switches

    Position switches

    LS... K K K

    Safety position switches

    LS-...-...-ZB K K

    Safety interlocks

    LS-...-...-ZBZ K K K

    Notes 1) Devices for world markets IEC = UL/CSAFor details of degrees of protection aA1/18

    For use with Part no.Article no.

    PriceSee PriceList

    Std. pack Notes

    m" conduit adapter

    LSLSMfor use with american pipethread, metal

    V1/2"/M20-NA225269

    10 off The screw connection is for earthing; no totalinsulationM20

    1/2"

    MCS(N), LS

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    22/44

    Moeller HPL0211-2007/2008

    A1/22

    http://catalog.moeller.net

    pp

    ContactorsDILM contactors complete units

    Rating data for approved types1) ContactorsGENERAL USE

    Maximum ACcurrent-motor rating

    Maximummmotor-rated current

    Single-phase Three-phase IthOpen/enclosed

    NEMA size

    115 V120 V 230 V240 V 200 V208 V 230 V240 V 460 V480 V 575 V600 VHP HP HP HP HP HP A Part no.

    1 2 3 5 5 15/13,5 DILEM(4) 00

    k 1 1 2 3 5 20 DILM7 00

    1 3 3 5 7 20 DILM9 00

    1 2 3 3 10 10 20 DILM12 0

    1 3 5 10 10 20 DILM15 0

    2 3 5 7 10 15 35 DILM17 0

    2 5 7 7 15 20 35 DILM25 1

    3 5 10 10 20 25 40 DILM32 1

    3 7 10 15 30 40 55 DILM40 2

    3 10 15 20 40 50 65 DILM50 2

    5 15 20 25 40 60 80 DILM65 27 15 25 30 60 75 125 DILM80() 3

    7 15 25 40 75 100 125 DILM95 3

    10 25 40 50 100 125 160 DILM115 4

    15 30 40 60 125 125 160 DILM150 4

    50 60 125 150 225/2) DILM185 4

    60 75 150 200 250/2) DILM225 4

    75 100 200 250 350/2) DILM250 5

    100 125 250 300 350/2) DILM300 5

    125 150 300 400 450/2) DILM400 5

    150 200 400 500 550/2) DILM500 6

    200 200 400 600 630/2) DILM580 6

    200 250 500 600 700/2) DILM650 6

    250 300 600 700 800/2) DILM750 6 290 350 700 860 850/2) DILM820 6

    350 400 800 1000 1000 DILM1000

    560 640 1200 1300 1600 DILM1600

    Note 1)devices for world markets IEC UL/CSA2)please inquire

    Please enquire for approvals for:

    Elevator Control

    Refrigeration Control

    Resistance Air Heating

    Incandescent Lamps

    Electrical Discharge Lamps

    Capacitor Switching

    Set of connection terminals consisting of three individual

    terminals

    Conductor material Cross-sections For use with Part no.Article no.

    Pricesee price list

    See PriceList

    Notes

    Cu, Al 2x(AWG4 to MCM500) DILM500/22 DILM500-XK-CNA232192

    1 off incl- cover with control cableconnection

    Cu, Al 2x(AWG2 to MCM500) DILM580/22DILM650/22

    DILM650-XK-CNA232193

    incl- cover with control cableconnection

    Cu, Al 4x(AWG2 to MCM500) DILM750/22DILM820/22

    DILM820-XK-CNA232194

    Incl. terminal cover

    Cu, Al 1x(AWG6 to 350MCM) Z5-.../FF250 Z5-FF250-XK-CNA229314

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    23/44

    A1/23

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    ContactorsMotor starter combinations, DILM/Z

    Rating data for approved types1) Contactors Overload

    relays Maximum short-circuit protection for NorthAmerica

    maximum three-phase currentmotor ratingPS = HP

    Maximummmotor ratedcurrent

    FuseCEC or NEC

    Circuit-breaker2)

    200 V208 V

    230 V240 V

    460 V480 V

    575 V600 V

    Continuouscurrent

    Short-circuitrelease, non-

    delayedHP HP HP HP A Part no. Part no. 3) A A A

    1 DILEM ZE-1 3 15

    1 1.4 DILEM ZE-1,6 6 15

    1 1 2.3 DILEM ZE-2,4 6 15

    1 2 3 3.9 DILEM ZE-4 15 15

    1 1 3 6 DILEM ZE-6 20 15

    2 6.8 DILEM ZE-9 35 15

    2 2 5 5 7.8 DILEM ZE-9 35 15

    2 3 5 5 9.6 DILEM ZE-12 45

    1 DILM7 ZB-12-1 3 25 200

    o 1 1.4 DILM7 ZB-12-1,6 6 25 200

    1 1 2.3 DILM7 ZB-12-2,4 6 25 2001 1 2 3 3.9 DILM7 ZB-12-4 15 25 200

    1 1 3 6 DILM7 ZB-12-6 20 25 200

    7 9 DILM9 ZB-12-10 25 25 200

    3 5 7 9.6 DILM12 ZB-12-10 25 25 200

    7 10 11 DILM12 ZB-12-12 45 25 200

    5 10 15.2 DILM15 ZB-12-16 60 40 320

    1 DILM17 ZB-32-1 3 25 200

    o 1 1.4 DILM17 ZB-32-1,6 6 25 200

    1 1 2.3 DILM17 ZB-32-2,4 6 25 200

    1 1 2 3 3.9 DILM17 ZB-32-4 15 25 200

    1 3 6 DILM17 ZB-32-6 20 25 200

    3 5 7 9.6 DILM17 ZB-32-10 25 25 200 7 10 11 DILM17 ZB-32-12 40 30 320

    5 10 15.2 DILM17 ZB-32-16 40 30 320

    7 15 20 22 DILM25 ZB-32-24 90 100 1200

    10 20 25 32.2 DILM32 ZB-32-32 125 125 1200

    3 5 7.5 9.6 DILM40 ZB-65-10 40 40 380

    5 10 10 15.2 DILM40 ZB-65-16 60 60 760

    7 20 25 32.2 DILM40 ZB-65-24 90 90 1200

    10 20 30 34 DILM40 ZB-65-40 125 125 1200

    20 40 50 54 DILM50 ZB-65-57 200 150 2000

    20 50 50 63 DILM65 ZB-65-65 200 160 2000

    25 50 60 68 DILM80 ZB150-70 250 250 2500 30 75 100 99 DILM90 ZB150-100 400 400 3200

    40 100 100 124 DILM115 ZB150-125 500 500 4000

    60 125 125 156 DILM150 ZB150-150 600 600 4800

    50 60 125 150 156 DILM185 Z5-160 600 CLASS J 600 7200

    60 75 150 200 192 DILM225 Z5-220 800 CLASS J 800 16000

    75 100 200 250 248 DILM250 Z5-250 700 CLASS L 600

    100 125 250 300 312 DILM300 ZW7-400 1000 1000

    125 150 300 400 382 DILM400 ZW7-400 1000 1000

    150 200 400 500 480 DILM500 ZW7-540 1000 600

    Note 1)devices for world markets IEC UL/CSA2)Circuit-breaker aSection 103) On request, the ZEV can alternatively be fitted.

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    24/44

    Moeller HPL0211-2007/2008

    A1/24

    http://catalog.moeller.net

    pp

    ContactorsOverload relays

    Auxiliary contacts

    Pilot Duty General Use

    AC DC AC DCType V A V A

    DIL(E)EM-10(-01)...(D)DIL E A600 P300 600 10 250 0.5

    DILM7-10(-01)toDILM32-10(-01)

    A600 P300 600 15 250 1

    DILA-XHI...DILM32-XHI...

    A600 P300 600 15 250 1

    DILM1000-XHI11-SIDILM1000-XHI11-SADILM1000-XHI11V-SI

    A600 P600 600 10

    ETS4-VS3 B300 R300 600

    ZE D300 R300 240 1.5

    600 0.6

    ZB12, ZB32, ZB65,ZB150,Z5, ZW7

    B3001) R300

    B6002) R300

    Notes 1)at opposite polarity2)at same polarity

    Overload releasesetting range

    Contact sequence Auxiliary contacts For use with Short-circuitprotection,CEC/NEC fuse

    Part no.Article no.

    PriceSee PriceList

    Std. pack

    Ir N/O =normallyopen contact

    N/C =normallyclosedcontact

    A

    ZE overload relay

    Direct mounting Approved for North America only

    912 1 S 1 N/C DILEM 45 ZE-12014752

    1 off

    T3T2T1

    95 97

    96 98

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    25/44

    A1/25

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Rotary Switches, Switch-DisconnectorMiscellaneous switches with "disconnect function"

    Rating data for approved types1)

    UL-File No. E36332 T0-... T3-... T5B-...

    Contacts

    Rated operational voltage Ue V AC 600 600 600

    Rated uninterrupted current Iu

    Current rating A 16 25 65Pilot Duty A 600P 600

    A 600

    Switching capacity

    AC-3; max. rated power40 60 Hz AC motors

    3-phase 200 V AC HP 3 5 15

    230 V AC HP 3 7 15

    460 V AC HP 10 15 40

    575 V AC HP 10 15 50

    Single-phase 120 V AC HP 1 3

    200 V AC HP 2 3 7

    230 V AC HP 2 3 10

    Short-circuit rating

    Standard 600 V AC kA 5 5 5

    With back-upfuse

    A 50 80 CLASS J

    with Circuit-breakers Type NZMH6 NZMH6

    Current setting A 50 125

    Disconnect in motor circuits 600 V AC kA 10 10

    With back-up fuse Class 20 A/J 40 A/J

    Terminal cross-section

    Terminal cross-section

    Cu cable min. AWG 18 14 12

    max. AWG 14 10 4

    Tightening torque max. Nm 1 2 4

    Notes 1) devices for world markets IEC UL/CSA.Accessories aRotary switches for the German marketDo not use AW extension terminals where UL/CSA approval is required.

    UL-approved degrees of protection

    UL/NEMA 1 UL/NEMA 3R UL/NEMA 12

    Rotary switches

    T0-.../E; /Z; /SVB K K K

    T3-.../E; /Z; /SVB K K K

    Notes For details of degrees of protection, aPage A1/18

    T rotary switches in NA version

    In the NA version the rotary switch has an English text and/or a non-IEC terminal designation. Switches in style12 to 15 have an extra text on the front of the enclosure (e.g. part no. and degree of protection). Not possible inconnection with key operation S-T0, SVA-T3 and SVC-T3.

    An available overview found in the installation instructions 11502327.

    Type: T0 T3 T5B P1 P3-63 P3-100

    construction type

    /E; /EA; /EZ/Z; /V; /IVS

    +NA105864

    +NA105864

    /I2 +NA-I2105866

    +NA-I2105866

    /I4 +NA-I4105868

    +NA-I4105868

    /I5 +NA-I5105869

    T

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    26/44

    Moeller HPL0211-2007/2008

    A1/26

    http://catalog.moeller.net

    pp

    Rotary switches,Switch-DisconnectorsSwitch-disconnectors

    Rating data for approved types1)

    UL-File No. E36332 P1-25 P1-32 P3-63 P3-100

    Contacts

    Rated operational voltage Ue V AC 600 600 600 600

    Rated uninterrupted currentIu

    Current rating A 20 30 60 100Pilot Duty A 600

    P 600A 600P 600

    Switching capacity

    AC-3; max. rated power 40 60 Hz ACmotors

    3-phase 200 V AC HP 5 7 15 20

    230 V AC HP 5 10 15 25

    460 V AC HP 10 20 40 60

    575 V AC HP 15 25 50 75

    Single-phase 120 V AC HP 1 2 3 5

    200 V AC HP 3 3 7 10

    230 V AC HP 3 5 10 15

    Short-circuit rating

    Standard 600 V AC kA 5 5 10 10

    With back-up fuse A 110 110 150 150

    with Circuit-breakers Type NZMH6 NZMH6 NZMH6 NZMH9

    Current setting A 125 125 125 125

    Disconnect in motor circuits 600 V AC kA 10 10 10

    With back-up fuse Class 50 A/J 50 A/J 100 A 100 A

    Terminal capacity

    Terminal capacity

    Cu cable min./ AWG 14 14 14 14

    max. AWG 8 8 3 3

    Tightening torque max. Nm 1.6 1.6 3 3

    HI 11

    Auxiliary switch(1 N/O + 1 N/O contact)

    Pilot Duty P 600

    Heavy Pilot Duty A 600

    General Use 10 A 600 V AC

    Notes 1)Devices for world markets IEC UL/CSA

    UL-File-No:UL-approved degrees of protection

    E 36332 UL/NEMA 3R1) UL/NEMA 12 UL/NEMA 13

    Switch-disconnectors

    P1-.../EA /SVB K K

    P1-.../V /SVB K K

    P3-.../EA/SVB K K K

    P3-.../V/SVB K K K

    Notes Details of degrees of protection1)NEMA recommendation

    P1, P3

    For Moeller Electric Sales and Support call KMparts.com (866) 595-9616

  • 8/10/2019 Moeller Certificates

    27/44

    A1/27

    http://catalog.moel ler.net Moel ler HPL0211-2007/2008

    Approvalsforworldmarkets

    Rotary switches, Switch-DisconnectorsSwitch-disconnectors

    Rating data for approved types P5-125 P5-160 P5-250 P5-315

    UL-File No. E36332

    Contacts

    Rated operational voltage Ui V 600 600 600 600

    Rated impulse withstand voltage1) Uimp V AC 8000 8000 8000 8000

    Rated uninterrupted current2) Iu A 125 160 250 300

    Rated operational current

    Ampere-Rating On/Off switches Ie A 1252) 1602) 2502) 3002)

    Changeoverswitches

    Ie A 1252) 1602)

    Non inductive and slightly inductive loads

    rated Switching duty

    DOL-Rating (similar to AC-3)

    3-phase, 3 polig

    120 V HP 15 20 30 40

    240 V HP 30 40 60 75

    480 V HP 60 60 75 100

    600 V HP 60 60 75 100

    Short-circuit rating

    max. back-up fuse, gL characteristic A 125 160 250 315rated short-time withstand current (1-s-current) A 2500 3000 4600 5800

    Terminal capacity

    Cu cable

    Solid or stranded to boxterminal

    AWG 3/0 3/0

    MCM 350 350

    Flexible without ferrule AWG 2/0 2/0

    MCM 300 300

    Connection with cable lug or busbar M10 x M10 x M12 x M12 x

    Terminal screw mm 20 20 20 20

    max. Width mm 20 20 25 25

    max. width with terminal cover mm 25 25 34 34

    Ambient temperature open on 100 %Iu/Ith 50 C over 24 hours with peaks up to 55 C

    enclosed on 100%Ithe 35 C over 24 hours with peaks up to 40 C

    Notes 1) valid for mains with earth star point, overvoltag