Modular Cylindrical

76
1 Modular Cylindrical FM-200™ Agent Storage Container P/N 93-120XXX-001 93.120X-1 Effective: August 1999 DESCRIPTION These cylindrical agent storage containers, which are less than ten inches high and contain from 20 to 30 pounds of FM-200, are ideal for height-limited locations such as un- der-floor applications. They are equipped with a pressure gauge, a burst disc type discharge valve, a replaceable ini- tiator will assembly a screen assembly, cable assembly, mounting brackets and safety plug. Each ASC has a boss- mounted check valve which accepts and optional Pressure switch (see Fenwal Data Sheet 93.3119.0) and is used for recharging the container Initiator assemblies must be ordered for each container. See Fenwal data Sheet 93.1932.0 for information. Total pressure in a filled container is adjusted to 360 psi at 70 o F by superpressurizing with dry nitrogen. Nozzles and piping selected shall ensure a minimum dis- charge rate of 84 lbs. FM-200 agent per second at the mini- mum operating temperature. Operating temperature shall be limited to 32 o to 130 o F. Nozzles and piping must be in accordance with Fenwal FM-200 Design Manual. OPERATION The container is discharged when its initiator is actuated to rupture the burst disc valve. INSTALLATION The container must be securely mounted in position with the valve down using the integral mounting brackets. The cen- ter of four slots are located at the corners of a rectangle 8-1/ 2 in. wide by 11-11/16 in. long. Use four 5/16 in. bolts or studs to secure the container to a solid surface. The 93-120251-001 unit has mounting brackets on the bot- tom as shown at right and the 93-120253-001 unit has the mounting brackets on top. The 93-120351-001 and 93- 120353-001 units have mounting brackets on the dies. All units must be mounted with the valve at the bottom: either parallel to the floor or facing down. If not mounted in this manner, proper discharge will not be possible. After the container is secured in place, remove the safety plug and screw the screen assembly into the valve body. Then connect the rest of the piping and nozzle specified in the system drawing. Retain the safety plug for use when reconditioning the container or whenever a filled container is moved. MAINTENANCE The following inspection and/or maintenance procedures should be scheduled or performed upon the occurrence of any even which might bias the reliability of the system. A. QUARTERLY INSPECTION 1. Check the pressure gauge. If the pressure is less than 325 psig at 70 o F (22.9 Kg/cm 2 at 21 o C) the container must be removed by qualified personnel, inspected care- fully then recharge or replaced as required. Pressure will vary with temperature. In the range of 55 to 85 o F (12.8 to 29.4 o C), this change is approximately 3 psi per degree F (0.397 Kg/cm 2 per degree C). 2. Check all components supporting hardware and tighten, repair or replace as required. 3. Visually check all components for evidence of physical abuse and take whatever action is indicated. Replace any component if at all in doubt of its ability to perform properly. B. SEMI-ANNUL INSPECTION Qualified personnel are to remove and weight all agent stor- age containers. Losses in net weight of agent must not ex- ceed 5% or 10% under pressure loss adjusted for temperature. Container, and agent weight are marked on the mounting bracket. All outlet piping must be clean and free of dirt, chips, filings and other foreign material that my become hazardous pro- jectiles or cause the system to become inoperative or inef- fective at the time of discharge. NOTE: The safety plug shipped with the container must be retained and secured to the container whenever the piping is removed from a charged container. Charged containers must have safety plug in- stalled when removed from system for shipment.

description

The design and estimated calculation for FM-200 fire protection system

Transcript of Modular Cylindrical

Page 1: Modular Cylindrical

1

Modular CylindricalFM-200™ Agent Storage ContainerP/N 93-120XXX-001

93.120X-1

Effective: August 1999

DESCRIPTIONThese cylindrical agent storage containers, which are lessthan ten inches high and contain from 20 to 30 pounds ofFM-200, are ideal for height-limited locations such as un-der-floor applications. They are equipped with a pressuregauge, a burst disc type discharge valve, a replaceable ini-tiator will assembly a screen assembly, cable assembly,mounting brackets and safety plug. Each ASC has a boss-mounted check valve which accepts and optional Pressureswitch (see Fenwal Data Sheet 93.3119.0) and is used forrecharging the container

Initiator assemblies must be ordered for each container. SeeFenwal data Sheet 93.1932.0 for information.

Total pressure in a filled container is adjusted to 360 psi at70oF by superpressurizing with dry nitrogen.

Nozzles and piping selected shall ensure a minimum dis-charge rate of 84 lbs. FM-200 agent per second at the mini-mum operating temperature. Operating temperature shallbe limited to 32o to 130oF. Nozzles and piping must be inaccordance with Fenwal FM-200 Design Manual.

OPERATIONThe container is discharged when its initiator is actuated torupture the burst disc valve.

INSTALLATIONThe container must be securely mounted in position with thevalve down using the integral mounting brackets. The cen-ter of four slots are located at the corners of a rectangle 8-1/2 in. wide by 11-11/16 in. long. Use four 5/16 in. bolts orstuds to secure the container to a solid surface.

The 93-120251-001 unit has mounting brackets on the bot-tom as shown at right and the 93-120253-001 unit has themounting brackets on top. The 93-120351-001 and 93-120353-001 units have mounting brackets on the dies. Allunits must be mounted with the valve at the bottom: eitherparallel to the floor or facing down. If not mounted in thismanner, proper discharge will not be possible.

After the container is secured in place, remove the safetyplug and screw the screen assembly into the valve body.Then connect the rest of the piping and nozzle specified inthe system drawing. Retain the safety plug for use whenreconditioning the container or whenever a filled containeris moved.

MAINTENANCEThe following inspection and/or maintenance proceduresshould be scheduled or performed upon the occurrence ofany even which might bias the reliability of the system.

A. QUARTERLY INSPECTION

1. Check the pressure gauge. If the pressure is less than325 psig at 70oF (22.9 Kg/cm2 at 21oC) the containermust be removed by qualified personnel, inspected care-fully then recharge or replaced as required. Pressurewill vary with temperature. In the range of 55 to 85oF(12.8 to 29.4oC), this change is approximately 3 psi perdegree F (0.397 Kg/cm2 per degree C).

2. Check all components supporting hardware and tighten,repair or replace as required.

3. Visually check all components for evidence of physicalabuse and take whatever action is indicated. Replaceany component if at all in doubt of its ability to performproperly.

B. SEMI-ANNUL INSPECTION

Qualified personnel are to remove and weight all agent stor-age containers. Losses in net weight of agent must not ex-ceed 5% or 10% under pressure loss adjusted fortemperature. Container, and agent weight are marked onthe mounting bracket.

All outlet piping must be clean and free of dirt, chips, filingsand other foreign material that my become hazardous pro-jectiles or cause the system to become inoperative or inef-fective at the time of discharge.

NOTE: The safety plug shipped with the container must beretained and secured to the container whenever thepiping is removed from a charged container.Charged containers must have safety plug in-stalled when removed from system for shipment.

Page 2: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

RECONDITIONINGAfter a system has been actuated, it is recommended thatthe local authorized Fenwal distributor be contacted to re-condition the system.

The Reconditioning Kit for this unit is P/N 31-193005-001.This kit does not contain the initiator, which must be orderedseparately.

SPECIFICATIONSCylinder Diameter: 9-3/8” (239mm)

Overall Height: 9-7/8” (251mm)

Overall Length: 19-1/2” (495mm)

Empty Weight: 24 lbs. (10.8 Kg) approx.

Volume: .442 cu. ft. (12.52 L)

Minimum Fill: 20 lbs. (9.07 Kg)

Maximum Fill: 30 lbs. (13.61 Kg)

ARCHITECT/ENGINEER SPECIFICATIONSThe agent storage container shall be a Fenwal cylindrical(refillable) FM-200 container constructed of high strength lowHSLA alloy steel. It shall consist of: fill valve, burst disc valveassembly, initiator, safety plug, screen assembly, cable as-sembly, integral supporting flanges, 0-100 psig pressure

gauge and pressure switch assembly (optional). The con-tainers shall hold from 20 to 30 lbs. of FM-200 agent.

Container shall conform to all applicable specifications ofDepartment of Transportation.

The burst disc valve assembly shall be an integral part ofthe agent storage container and shall be operated by apply-ing electrical current to an initiator assembly which has anelectro-explosive device that provides on demand, and in-stantaneous full bore release and discharge of the agent.Valves with moving parts and seals are not acceptable.

Filled containers shall be super-pressurized with dry nitro-gen to 360 psig at 70oF to aid in rapid agent distribution,particularly at lower temperatures. It shall automatically re-lieve between 850 to 1000 psi in even of excessive pressurebuild up.

Devices and connecting leads shall be completely super-vised.

The container design shall permit on-site reconditions andrefilling.

The integral mounting assembly shall provide a means formounting to a solid vertical or horizontal surface and shallwithstand a thrust of 1000 lbs. for 5 seconds in any direc-tion.

*FM-200 is a Registered Trademark of Great Lakes Chemical Corporation

93.120X-1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A. CP

Page 3: Modular Cylindrical

1

Spherical Agent StorageContainerFM-200� Agent Storage ContainerP/N 93-11020X-001 93.1120.1

Effective: March 2000

FEATURES� 4 Convenient Sizes� 20 to 196 Pound Capacities� UL Listed, FMRC Approved� Requires No Floor Space� Electric Initiator Actuation

DESCRIPTIONFenwal Modular Spherical Agent Storage Containers storeFM-200 super-pressurized with dry nitrogen to 360 psig at70oF. These containers hold from 20 to 196 pounds of FM-200 and are equipped with a burst disc type discharge valve,a replaceable initiator well, a screen assembly, safety plugand cable assembly. Each container has two identical boss-mounted check valves which will accept a pressure gauge(standard), and an optional pressure switch (see Data Sheet93.3119.0). Either of these check valves may be used forrecharging the container.Initiator assemblies must be ordered for each container. SeeData Sheet 93.1932.0

OPERATIONThe container is discharged when the initiator is actuated torupture the burst disc valve.

INSTALLATIONThe container must be rigidly mounted in position with thevalve facing down. Fenwal mounting brackets provide a se-cure means for wall mounting containers. A lifting ring onthe container provides a means for raising the container toits mounting location.After the container is secured in place, remove the safetyplug and connect the rest of the piping and nozzles(s) speci-fied in the system drawing. Retain the safety plug for usewhen reconditioning the container and whenever a filled con-tainer is moved.

MAINTENANCEInspection and/or maintenance procedures should be sched-uled as listed below, or performed when an event occurswhich might affect the reliability of the system.

A. QUARTERLY INSPECTION1. Check the pressure gauges of each agent storage con-

tainer. If the pressure is less than 325 psig at 70oF (22.9Kg/cm2 at 21oC), the container should be removed andcarefully inspected by qualified personnel. It should thenbe reconditioned, recharged or replaced depending uponits condition. Pressure varies with temperature, and inthe range of 55oF to 85oF (12.7oC-29.4oC) this change isapproximately 3pse/oF (.38 Kg/cm2/oC)

2. Check all component supporting hardware and tighten orrepair as required.

3, Visually check all components for physical abuse andtake whatever action is necessary. Replace the compo-nent if at all in doubt as to its ability to perform properly.

B. SEMI-ANNUAL INSPECTIONQualified personnel are to remove and weigh all agent stor-age containers. Losses of agent must not exceed 5% in netweight, or 10% reduction of pressure (adjusted for tempera-ture). Container and agent weight are marked on thecontainer�s nameplate.All outlet piping must be clean and free of dirt, chips, fillingsand other foreign material that may become hazardous pro-jectiles or cause the system to become inoperative or inef-fective at the time of the discharge.NOTE: The safety lug shipped with this container should be

retained and secured to the container whenever thepiping is removed from a charge container. Chargedcontainers must have the safety plug installedwhen removed from the system for shipment.Observe proper handling procedures when in-stalling or removing the initiator.

RECONDITIONINGAfter a system has been actuated, it is recommended thatthe local authorized Fenwal Distributor be contacted for re-conditioning the system.The Reconditioning Kit for this unit is P/N 31-193005-001This kit does not contain the initiator, which must be orderedseparately.

Page 4: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

ARCHITECT/ENGINEER SPECIFICATIONSThe agent storage container shall be a Fenwal modularspherical (refillable) container constructed of high strength,low HSLA alloy steel. It shall consist of: fill check valve, burstdisc valve assembly, integral supporting flanges, 0-700 psigpressure gauge and pressure switch assembly (optional).The containers shall hold from 20 to 196 lbs. Of FM-200agent.Containers shall conform to too applicable specifications ofDept. of Transportation, Underwriters Laboratories, and Fac-tory Mutual Research Corp.The burst disc valve assembly shall be an integral part ofthe agent storage container and shall be operated by apply-ing electrical current to an initiator assembly, which has aelectro-explosive device that provides an instantaneous fullbore release and discharge of the agent on demand. Thereleasing mechanism shall contain no moving parts.Filled containers shall be super-pressurized with dry nitro-gen to 360 psig at 70oF to aid in rapid agent distribution,particularly at lower temperatures. It shall automatically re-lieve between 850 to 1000 psig in the event of excessivepressure build-up.Releasing devices and connecting leads shall be completelysupervised.The mounting bracket shall be designed for installation on awall, floor or other rigid surface and shall serve as supportfor the agent storage container, and shall be capable of with-standing a thrust of 1000 lbs. For 5 seconds in any direction.

.oNtraP

erehpS

retemaiD *thgieH **TWytpmE

NI mm NI mm BL gK

100-102011-39 2.31 433 7.02 525 5.82 9.21

100-202011-39 8.41 773 4.22 965 7.63 6.61

100-302011-39 3.71 934 9.42 436 0.25 6.32

100-402011-39 5.12 745 3.92 547 1.99 0.54

*Height is from top of lifting ring to bottom surface of flange.Flange mounting holes 5/8 in. (15.9 mm) diameter locatedon bolt circle 6-5/8 in. (162.3 mm) diameter. Flange is 1.4 in(6.4 mm) thick for all models except for 90-110204-001, whichis 3.8 in. (9.5 mm).**Average weight for shipping and mounting planning. Ac-tual weight stamped on each unit.

������������ � �� �����

�� � �� � ��

������������� ����� ������ ���� ����

������������� ��� � ���!��� ���� ����

������������� ������ ������� ��� ����

������������� ����� � ��� � �� �� � ��

*FM-200 is a Registered Trademark of Great Lakes Chemi-cal Corporation

93.1120.1 3/00 5M ©Kidde-Fenwal Inc. Printed in U.S.A. CP

Page 5: Modular Cylindrical

1

Floor Mounted SphericalFM-200™ Agent Storage ContainerP/N 93-190000-00X

93.1225.1

Effective: August 1999

FEATURES• Designed for Under Floor Installation• Contains 10 to 15 lbs. of FM-200 Agent• UL Listed/FM Approved• DOT Shipping Container

DESCRIPTIONThis FM-200 spherical agent storage container is less than10 inches in height to fit under most raised floors and con-tains from 10 to 15 pounds of FM-200 superpressurized to360 psig with dry nitrogen.

Each assembly is equipped with pressure gauge, burst disctype discharge valve, replaceable initiator well, safety plug,screen assembly, cable assembly and mounting brackets.Each ASC has a boss-mounted check valve which acceptsand optional Pressure Switch (see Fenwal Data Sheet93.3119.0) and is used for recharging the container.

Initiator assemblies much be ordered for each container. SeeFenwal Data Sheet 93.1932.0 for ordering information

OPERATIONThe container much be securely mounted to a rigid surfacewith the valve horizontal/parallel to floor or down. Four holesin the mounting brackets are drilled to accept 5/16 inchmounting bolts. The centers of the mounting holes are lo-cated at the corners of a rectangle 6.38 inches wide by 8.38inches long.

MAINTENANCEThe following inspection and/or maintenance proceduresmuch be scheduled as listed below or performed upon oc-currence of any event which might affect the reliability of asystem.

A. QUARTERLY INSPECTION

1. Check the pressure gauges of each container. If the pres-sure is less than 325 psig at 70oF (22.9 Kg/CM2 at 21o

C), the container should be removed by qualified per-sonnel and carefully inspected, then reconditioned, re-charged or replaced as its condition warrants. Pressurewill vary with temperature. In the range of from 55 to85oF (12 to 29o C) this change is approximately 3 psi perdegree F (.38 kg/cm2/oC).

2. Check all component supporting hardware and tightenor repair as required.

3. Visually check all components for evidence of physicalabuse and take whatever action is indicated. Replacethe component if at all in doubt of its ability to performproperly.

B. SEMI-ANNUAL INSPECTION

Qualified personnel are to remove and weight all agent stor-age containers. Losses in net weight of agent much not ex-ceed 5 percent. Loss in pressure (adjusted for temperature)must not exceed 10 percent. Container and agent weightare marked on the inspection tag.

All outlet piping must be cleaned and free of dirt, chips, fil-ings and other foreign material that may become hazardousprojectiles or cause the system to become inoperative orineffective at the time of discharge.

NOTE: The safety plug shipped with this container shouldbe retained and secured to the container wheneverthe piping is removed from a charge container.Charged containers much have safety plug installedwhen removed from system for shipment. Observeproper handling procedures when installing or re-moving the initiator.

RECONDITIONINGAfter a system has been actuated, it is recommended thatthe local authorized Fenwal Distributor be contacted for re-conditioning the system. Refer to, “Filling and Recondition-ing Fenwal’s FM-200 Agent Storage Containers.”

The Reconditioning Kit for this unit is P/N 31-193005-001.This kit does not container the initiator, which must be or-dered separately.

Page 6: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

SPECIFICATIONSDiameter: 9-3/8” (239mm)

Overall Height: 9-7/8” (251mm)

Overall Length: 19-7/8” (495mm)

Empty Weight: 24 lbs. (10.8 Kg) Approx.

ARCHITECT/ENGINEER SPECIFICATIONSThe agent storage container shall be a Fenwal cylindrical(refillable) FM-200 container constructed of high strengthlow HSLA alloy steel. It shall consist of: Fill Valve, burst discvalve assembly, initiator, safety plug, screen assembly, cableassembly, integral supporting flanges, 0-700 psig pressuregauge and pressure switch assembly (optional). The con-tainers shall hold from 10 to 15 lbs. of FM-200 agent.

Container shall conform to all applicable specifications ofDepartment of Transportation, Underwriters Laboratories,Inc., and the Factory Mutual System.

The burst disc valve assembly shall be an integral part ofthe agent storage container and shall be operated by apply-ing electrical current to an initiator assembly which has anelectro-explosive device that provides, on demand, and in-stantaneous full bore release and discharge of the agent.

The releasing mechanism shall contain no moving parts.

Filled containers shall be super-pressurized with dry nitro-gen to 360 psig at 70oF to aid in rapid agent distribution,particularly at lower temperatures It shall automatically re-live between 850 to 100 psig in event of excessive pressurebuild up.

Releasing devices and connecting leads shall be completelysupervised

The container design shall permit on-site reconditioning andrefilling.

The integral assembly shall provide a means or mounting toa solid vertical or horizontal surface and shall withstand athrust of 1000 lbs. for 5 seconds in any direction.Tank construction per DOT-4BA-500.

93.1225.1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A. CP

*FM-200 is a Registered Trademark of Great Lakes Chemical Corporation.

Page 7: Modular Cylindrical

1

FM-200® BOTTOM DISCHARGEAGENT STORAGE CONTAINERP/N 93-19204X-00X93.1920.1

Effective: September 1999

FEATURES� 150-350, 240-560, and 370-850-lb. Capacities� Electric Initiator Actuation� 3-inch Discharge Valve� Optional Liquid Level Indicator� Standard Low Pressure Supervisory

Pressure Switch� UL Listed� FM Approved

DESCRIPTIONFenwal FM-200 Bottom Discharge Agent Storage Contain-ers store FM-200 super-pressurized with dry nitrogen to 360psig (70oF). They are painted red and are equipped with a 3-inch burst disc type discharge valve, a replaceable initiatorwell, a screen assembly, pressure gauge, supervisory pres-sure switch with cable assembly, fill port, overpressure reliefvalve, safety cap, liquid level measuring device (optional)and lifting lugs. A 3-inch Flex Hose (P/N 29-117134-002) isavailable to facilitate piping connections. Initiator assembliesP/N 93-191001-001 must be ordered for each container.

OPERATIONThe agent storage container discharges when the initiator isactuated, causing the burst-disc valve to rupture.

INSTALLATIONThe container is installed in a vertical position with the valveassembly pointing up. Interconnection for discharge pipingis 3-inch NPT. A 3-inch flex hose is available to facilitateconnection between the container and discharge piping. A3-inch, 300-lb. malleable-iron threaded pipe union manufac-tured per ANSI B16.39 is required to mate the tank dischargeport to the flex-hose assembly.The container is secured in place by two mounting brackets(P/N 29-232334-00X) which are bolted together around thecontainer and affixed to a solid wall or a strut assembly. Two1/2-inch diameter bolts are required to secure the mountingbrackets to a vertical surface and two 1/2-inch diameter 9-inch long threaded rods are needed to hold the two mount-ing brackets together.After the container is securely mounted, it is connected todischarge piping per the system drawings. The initiator as-sembly is then installed.

MAINTENANCEAccording to NFPA standards the following inspection and/or maintenance procedure must be scheduled as listed be-low and performed upon the occurrence of any event whichmight affect the reliability of the system.

QUARTERLY INSPECTION1. Check the pressure gauges of each agent storage con-

tainer. If the pressure is less than 325 psig at 70oF (22.9kg/cm2 at 21oC), the container should be removed andcarefully inspected by certified personnel. It should thenbe reconditioned, recharged or replaced as it�s condi-tion indicates. Pressure varies with temperature. In therange of 55 to 85oF (12.8 to 29.4oC) change is approxi-mately 3 psi per degree F (0.397 kg/cm2 per degree C).

2. Check all component supporting hardware and tighten,repair, or replace as required.

3. Visually check all components for evidence of physicalabuse and take whatever action is required. Replaceany component if at all in doubt of its ability to performproperly.

Page 8: Modular Cylindrical

2

SEMI-ANNUAL INSPECTIONQualified personnel are to determine the amount of agent inall containers. The optional liquid level indicator may be usedto measure agent supply and compare it to the original netweight which is marked on the container label. If the mea-sured net weight is less than 95% of the original charged netweight the container should be tested for leakage, rechargedand reinstalled.Inspect all piping, fittings and nozzles for looseness, dirt orother damage. All outlet piping must be clean and free ofdirt, chips, fillings and other foreign material that may causethe system to become inoperative or ineffective at the timeof discharge.

RECONDITIONINGAfter a system has been discharged, it is recommended thatthe local authorized Fenwal distributor be contacted to re-condition the system.The reconditioning kit for these containers is P/N 31-193017-001. The initiator, not included, is ordered separately.

ORDERING INFORMATIONKEY TO PART NUMBERS

93-19204X-00X1: w/o Liquid Level Indicator2: w/ Liquid Level Indicator

1: 5 ft. Volume (350 lb.)

2: 12 ft. Volume (850 lb.)

3

3

0: 8 ft. Volume (560 lb.)3

ACCESSORIES

X00-140291-39 X00-040291-39 X00-240291-39

)kcalB(tekcarBderiuqeRowT()reniatnoCrep

400-433232-92 200-433232-92 000-433232-92

ILLylbmessAepaT

498382

ILLylbmessAdoR)99.tpeS-erP(

210-990491-13 A/N

SPECIFICATIONSAGENT STORAGE CONTAINERS

X00-140291-39 X00-040291-39 X00-240291-39

egnaRlliF)ILLo/w.bl(

053-051 065-042 058-073

egnaRlliF)ILL/w.bl(

053-002 065-023 058-084

thgieH).ni(

75 5.85 5.06

retemaiD).ni(

61 02 42

emuloVlanretnI).tf.uc(

5 8 21

thgieWytpmE).bl(

052 053 084

mumixaMdaoLcitatS

006 019 0331

erutarepmeTegnaR

031ot23 o 45ot0(F o )C

feileRytefaSegnaRtsruB

GISP0001ot058

noitcurtsnoCnoitacificepS

005WB4-TOD

SUPERVISORY PRESSURE SWITCHES

300-945511-60 200-945511-60

lanoitpO/deppihS sreniatnoChtiwdeppihS lanoitpO

gnitaRtcatnoC CDV42@spmA2

noitarepOerusserPrednUnepO:taesolCstcatnoC(

)GISP51±,002

erusserPrednUdesolC:tanepOstcatnoC(

)GISP51±,002

Page 9: Modular Cylindrical

3

NO LIFT NO LIFT

R R

F

B

C

INSPECTIONTAG

E

D

A

DIMENSIONAL INFORMATIONTANK AND BRACKET DIMENSIONS

������������� ������������� �������������

�� �������

���� � ������ ���� � ������ ��� � � ������

� �� ����� ���� �

� ����� ����� ��

� �� �

� �����

� �����

� ������

� ����� ����� �����

� ������ �����

� ������ ���� �����

� ����� ���� �����

BRACKET OUTLINE

G

H

J

I

AGENT STORAGE CONTAINER OUTLINE

Page 10: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

93.1920.1 9/99 ©1999 Kidde Fenwal Inc. Printed in USA

ARCHITECTURAL AND ENGINEERINGSPECIFICATIONSThe FM-200 shall be stored in vertically mounted cylindricalcontainers with a 3-inch burst disc type discharge valve. Con-tainers shall be super-pressurized with dry nitrogen to 360 psigat 70oF. This container shall be Fenwal P/N 93-19204X-00X.Containers shall be U.L. Listed and FMRC Approved.Each agent storage container shall have a fill range of 150-350, 240-560, or 370-850 lbs. and be of a construction thatcomplies with DOT-4BW500.The agent storage container shall incorporate lifting lugs, over-pressure relief, 3-inch burst-disk type discharge valve, fill port,cable assembly, pressure gauge, supervisory pressure switch,liquid-level indicator (optional), and a safety cap. Electricaldevice�s connecting leads shall be completely supervised.

A compatible flex hose shall be available to facilitate instal-lation and connection to discharge piping.The container shall be secured in place by two opposingsteel mounting brackets. These brackets shall be FenwalP/N 29-232334-00X.

Page 11: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

Initiator Assembliesfor Fire Suppression SystemsP/N 93-199932-00X

93.1932.0

Effective: August 1999

93.1932.0 8/99 ©1999 Kidde-Fenwal Inc. Printed in USA

DESCRIPTIONInitiator assemblies are used in Fenwal Fire SuppressionSystem to rupture the burst disc valve in Fenwal agent stor-age containers.

WARNING!

The initiator is a Class “C” explosive. It must behandle and stored in accordance withappropriate local regulations governing Class“C” explosives. The local Fire Marshall should

CAUTION!

Never handle, transport, store, or install theinitiator assembly unless the shorting capsupplied with the assembly is properly securedto its threaded end. Safety glasses or a faceshield must be worn when handling thesedevices. Improper handling, misuse or abuse ofthis device can cause bodily injury.

OPERATIONThe initiator assembly is activated by an electrical current of2.0 amps. The assembly is destroyed by its operation andmust be replaced whenever a system is actuated.

INSTALLATIONThe initiator assembly is inserted into a well in the agentstorage container. Consult Fenwal Publication 93-FM200M-004 and/or 93-FM200M-003 for details on the proper instal-lation and testing procedures for this device.

MAINTENANCEThe initiator assembly should be stored in an area main-tained at 70-75oF (21-24oC). The storage area must be dryand secure from unauthorized access to these units. Thecombined shelf life and service life of an initiator assemblyshall not exceed seven (7) years. The service life varies withthe maximum temperature to which it is exposed for an ap-preciable length of time. See Table 1.

Table 1

.PMETDESOPXE.XAM EFILECIVRESSRAEY

Fo Co

08 72 5

001 83 3

021 94 2

041 06 1

At the end of it’s service life or seven years, whichever oc-curs first, in initiator assembly must be removed and de-stroyed in accordance with local regulations.

If an initiator is installed in an agent storage container thathas relieved as a result of an over-pressure, both the initia-tor and well assembly should be replaced regardless of theinitiator’s age. The initiator must be destroyed in accordancewith local regulations.

SPECIFICATIONS

.oNtraP

ylbmessAthgieW

"A".miD etairporppACSA

.zO .mG .nI mm

400-139991-13 21.1 0.23 96.2 3.86 100-102011-39100-202011-39100-302011-39100-402011-39100-052011-39100-352011-39100-153011-39100-353011-39

Page 12: Modular Cylindrical

1

FM-200™ Pendant NozzlesP/N 93-1940.1

93.1940.1

Effective: August 1999

FEATURES• 180o and 360o Styles

• Six Pipe Sizes - 1/2” to 2” NPT

• Specially designed for FM-200

• Uniform Agent Distribution

• Custom Orifice Sizing

• UL Listed

• FMRC Approved

DESCRIPTIONThese nozzles are used in Fenwal FM-200 Fire Suppres-sion Systems to disperse FM-200 uniformly throughout thehazard area. Patterns direct discharged FM-200 parallel tothe ceiling. Nozzles are available to discharge in either 180o

or 360o patterns, depending on location within the hazardarea. A selection of orifices is available for each nozzle sizeto provide correct sizing for appropriate agent distribution.

Nozzles are constructed of brass, nozzle sizes are 1/2, 3/4,1/ 1-1/4, 1-1/2 and 2 inch NPT. See Ordering Information forsizes and part numbers.

DESIGN/INSTALLATIONThe nozzles are equipped with female National Pipe Threadsand provide and equal distribution of agent throughout theprotected area. Nozzles should be mounted in a downwardvertical position only. The Placement of the nozzles for ad-equate coverage to all portions of the hazard area is deter-mined by considering the indicated throw of each nozzle.When using large nozzles in an area where smaller nozzleshave a sufficient throw, care should be used to avoid anyunnecessary and unwanted turbulence.

ARCHITECT/ENGINEER SPECIFICATIONThis FM-200 Fire Suppression System shall use dischargenozzles that distributed the FM-200 uniformly throughout theprotected area. The nozzle shall be Fenwal P/N 93-1940XX-XXX.

360o Nozzle

180o Nozzle

Page 13: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

063 o ELZZON

eziSepiP A B C D

)mm2.21("2/1 )mm57.13("052.1 )mm82.73("864.1 )mm91.94("739.1 )mm57.13("052.1

)mm50.91("4/3 )mm1.83("005.1 )mm80.04("875.1 )mm79.35("521.2 )mm1.83("005.1

)mm4.52("1 )mm54.44("057.1 )mm36.34("817.1 )mm23.06("573.2 )mm54.44("057.1

)mm57.13("4/1-1 )mm51.75("052.2 )mm35.94("059.1 )mm58.96("057.2 )mm51.75("052.2

)mm1.83("2/1-1 )mm05.36("005.2 )mm08.05("000.2 )mm95.47("739.2 )mm05.36("005.2

)mm8.05("2 )mm02.67("000.3 )mm73.25("260.2 )mm73.97("521.3 )mm02.67("000.3

081 o ELZZON

eziSepiP A B C D

)mm2.21("2/1 )mm57.13("052.1 )mm57.13("052.1 )mm48.24("786.1 )mm8.05("000.2

)mm50.91("4/3 )mm1.83("005.1 )mm29.43("573.1 )mm98.84("059.1 )mm13.85(692.2

)mm4.52("1 )mm54.44("057.1 )mm76.93("265.1 )33.65("812.2 )mm48.76("176.2

)mm57.13("4/1-1 )mm51.75("052.2 )mm54.44("057.1 )mm64.76("656.2 )mm55.28("052.3

)mm1.83("2/1-1 )mm05.36("005.2 )mm98.84("059.1 )mm39.47("059.2 )mm70.29("526.3

)mm8.05("2 )mm02.67("000.3 mm89.94("869.1 )mm20.37("578.2 )mm68.29("656.3

OUTLINE DIMENSIONS (INCHES)

93.1940.1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A.

*FM-200 is a Registered Trademark of Great Lakes Chemical Corporation

Page 14: Modular Cylindrical

1

Pressure Switch AssemblyP/N 31-194133-0X

93.3119.0

Effective: January 2000

FEATURES� Easy Installation� Available Normally Open or Normally Closed� Explosion Resistant Cable Option

DESCRIPTIONThis pressure switch assembly mounts directly to a checkvalve on Fenwal spherical FM-200® agent storage contain-ers to trigger a TROUBLE condition when container pres-sure drops below 200 psig ±15 psi. Assemblies are availablewith normally open or normally closed contacts, and withstandard or explosion resistant cable assemblies.

OPERATIONNormally Open - The pressure switch contacts are closedwhen the container is pressurized in accordance with speci-fications. The contacts open when pressure drops below 200psig.Normally Closed - The pressure switch contacts are openwhen the container is pressurized in accordance with speci-fications. The contacts close when pressure drops below200 psig.

CAUTION!

Pressure in a normally filled container will dropbelow 200 psig at or below a temperature of+10oF (-12oC). Accordingly, this modification isnot recommended for low temperatureapplications.

INSTALLATIONTo install the pressure switch assembly, first unscrew theguard around the unused boss on the container and removethe safety plug from the check valve. Secure the check valvehex with a wrench to guard against loosening the check valve.Screw the pressure switch into the check valve 3 turns be-yond hand tight and then attach the cable assembly by screw-ing the housing over the threaded boss. Connect the cableassembly to the control unit in accordance with the systemschematic.

CAUTION!

Use wrench on check valve to avoid overtightening and when loosening components forremoval.

ORDERING INFORMATIONStandard Pressure Switch Assembly -Normally Open: P/N 31-194133-001

W/Explosion ResistantCable Assembly*: P/N 31-194133-002

Standard Pressure Switch Assembly -Normally Closed: P/N 31-194133-00

W/Explosion ResistantCable Assembly*: P/N 31-194133-004

SPECIFICATIONSCurrent Rating: 1 amp @ 120/240VAC,

Resistive 2 amps @ 24 VDCContacts Open: 200 ±15 psig*Explosion resistant cable assemblies for Class 1, Groups C andD; Class 2, Groups E, F and G locations.ARCHITECT/ENGINEER SPECIFICATIONSThe Pressure Switch Assembly shall be used with Fenwalspherical FM-200 agent storage containers to provide su-pervision of loss of pressure and/or extinguishing agent byindication of a Trouble signal at the Fenwal control unit. Itshall consist of a cable assembly and a pressure switch. Itshall be mounted directly on the container by means of a

Page 15: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

boss-mounted check valve to facilitate removal of the pres-sure switch without losing FM-200 agent.Normally Open - The contacts of the switch shall be closedwhen the container is pressurized in accordance with speci-fications. The contacts will open when container pressuredrops below 200 ±15 psig. This switch shall not be used forapplications where ambient temperatures could drop to 10oF(12oC) or lower as this temperature will cause normal vesselpressure to drop below 200 psig.Normally Closed - The contacts of the switch shall be openwhen the container is pressurized in accordance with speci-fications. The contacts will close when container pressuredrops below 200 ±15 psig. This switch shall not be used forapplications where ambient temperatures could drop to 10oF(12oC) or lower as this temperature will cause normal vesselpressure to drop below 200 psig.The explosion resistant cable assembly shall be designedfor hazardous locations, Class 1, Groups C and D, Class 2,Groups E, F and G. Its contacts shall be rated at 1 Amp at120/240VAC and 2 Amps at 24VDC.

93.3119.9 1/00 ©2000 Kidde-Fenwal, Inc. Printed in U.S.A.

Fenwal is a registered trademark of Kidde-Fenwal, Inc.FM200 is a registered trademark of Great Lakes Chemical Corporation

Page 16: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

Wall Mounting BracketP/N 31-194019-001

93.3119.1

Effective: August 1999

DESCRIPTIONThe Wall Bracket shown is used to mount Fenwal ModularSpherical FM-200™ Agent Storage containers.

INSTALLATIONThe bracket may be mounted with in the position shown orinverted. Six bolt holes are provided for secure mounting,using 1/2 in. (12.7 mm) hardware. The bracket also may bewelded to stanchions, beams or bulkheads. The mountingholes bust be laid out to the dimensions shown below to atolerance of 1/32 in. (.79 mm) on each hole location. Mountagainst a rigid structural member or wall.

93.3119.1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A. CP

Manufactured from0.250 in. (6.4mm) stock

Page 17: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

Floor Mounting BracketP/N 31-194023-002

93.3119.2

Effective: August 1999

93.3119.2 8/99 ©1999 Kidde-Fenwal Inc. Printed in USA

DESCRIPTIONThe floor mounting bracket shown is used to mount FenwalModular Spherical FM-200™ Agent Storage Containers.

INSTALLATIONThe bracket is fastened to the floor through six 0.625 in.(15.9 mm) holes. Use 1/2 inch (12.7 mm) lag screws or boltswith lockwashers to prevent loosening. The agent storagecontainer is then mounted on top of the bracket with thevalve extending down through the 4 inch (102 mm) hole.

*Fm-200 is a Registered Trademark of Great Lakes Chemi-cal Corporation

Page 18: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective January 2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

F-93-2010

F-93-2010 ©2000 Kidde-Fenwal, Inc. Printed in U.S.A.

• For use with UL Listed, ULC Listed & FMRC approved systems • See Kidde Manual 90-FM200M-021 for USCG Approval

Features

Cylinder and Valve Assemblies 10LB (4.5 KG) - 70LB (31.7 KG) Capacity, Vertical Mount Only

MATERIALSVALVE BODY: BRASSCYLINDER: STEEL, PAINTED RED

rebmuNtraP eziS.lyCsnoisnemiD

*A *B *C

100-010001-39 .sbL01 70.7 43.31 03.71

100-020001-39 .sbL02 70.7 10.12 79.42

100-040001-39 .sbL04 00.9 08.22 67.62

100-070001-39 .sbL07 00.9 78.43 38.83

.sehcninierasnoisnemiD*

ORDERING INFORMATION

P/N: 90-10000X0-001

CYLINDER VALVE

SAFETY CAP

SYPHON TUBE

CYLINDER

A

B

C

NOTES:1. THE SAFETY CAP MUST BE INSTALLED ON THE VALVEOUTLET AT ALL TIMES EXCEPT WHEN THE CYLINDERS ARECONNECTED TO THE SYSTEM PIPING OR BEING FILLED. THESAFETY CAP MUST NOT BE REMOVED FROM ITS CHAIN.2. SEE F-90-2070 FOR ADDITIONAL INFORMATION.3. CYLINDERS ARE VERTICAL MOUNT ONLY.

Page 19: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

F-93-2020

F-93-2020 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

• For use with UL listed, ULC listed & FMRC approved systems

ORDERING INFORMATION

Cylinder and Valve Assemblies 10 LB. (4.5 KG) - 70LB. (31.7 KG) Capacity, Horizontal Mount Only,

MATERIALSVALVE BODY: BRASSCYLINDER: STEEL, PAINTED RED

rebmuNtraP eziS.lyCsnoisnemiD

*A *B *C

100-110001-09 .sbL01 70.7 43.31 03.71

100-120001-09 .sbL02 70.7 10.12 79.42

100-140001-09 .sbL04 00.9 08.22 67.62

100-170001-09 .sbL07 00.9 78.43 38.83

.sehcninierasnoisnemiD*

P/N: 90-1000X1-001

NOTES:1. THE SAFETY CAP MUST BE INSTALLED ON THE VALVEOUTLET AT ALL TIMES EXCEPT WHEN THE CYLINDERS ARECONNECTED TO THE SYSTEM PIPING OR BEING FILLED. THESAFETY CAP MUST NOT BE REMOVED FROM ITS CHAIN.2. SEE F-90-2070 FOR ADDITIONAL INFORMATION.3. CYLINDERS ARE HORIZONTAL MOUNT ONLY.4. NOT FOR USE WITH ENGINEERED SYSTEMS

Page 20: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

Cylinder and Valve Assembly 125 LB (56.7 KG) Capacity

F-93-2030

ORDERING INFORMATION

MATERIALSVALVE BODY: BRASSCYLINDER: STEEL, PAINTED RED

NOTES:1. THE SAFETY CAP MUST BE INSTALLED ON THE VALVEOUTLET AT ALL TIMES EXCEPT WHEN THE CYLINDERSARE CONNECTED TO THE SYSTEM PIPING OR BEINGFILLED. THE SAFETY CAP MUST NOT BE REMOVED FROMITS CHAIN.2. SEE F-93-2070 FOR ADDITIONAL INFORMATION.

P/N: 93-10012X-001

CYLINDER VALVE

LIQUID LEVEL INDICATOR

LIFTING LUGS

CYLINDERNAMEPLATE

12,75” DIA

CYLINDER

VALVE OUTLET

30°

PLAN VIEW

SAFETY CAP

35.93” 31.97”

F-93-2030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

N/P NOITPIRCSED

100-121001-39100-521001-39

ILL/WDTS

Page 21: Modular Cylindrical

����������������� ������� ���� ��� ������ ���� ��������������������� ���������� ��� ���!������� ������ ��"�#������!������� �����"�������"�� ��������� ��"�������!�� ������������� ���� �������"�!������������� �������� ����� ��� �� �������� ��"��� ����� �������$����� ���" ��"������������������ �����������%��&'()'*������� ���+,&-.�--'�)&&&

�������������� ������������������������������ �����

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

��������� ���� ���� ��� ��� ��� �� ���� ��� � �� ����� ������� � ������

���������

��/0�)&1&������������������'///����������2�����"������3���������4�5���

������������ ����� ����������������������������

������������������ �������������������������������

��������� ��� �������

�������������������������������� �������� ������������������������������������� �� ��������� ������� ����������������������� ������� ����������������������������� ����������������������� ����������������!���������� ���� ������� �

������������ �

N/P NOITPIRCSED

101-002001-39101-102001-39

DTSILL/W

Page 22: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2050

F-93-2050 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSVALVE BODY: BRASSCYLINDER: STEEL, PAINTED RED

Cylinder and Valve Assembly 350 LB (158.7 KG) Capacity

NOTES:1. THE SAFTY CAP MUST BE INSTALLED ON THEVALVE OUTLET AT ALL TIMES EXCEPT WHEN THECYLINDERS ARE CONNECTED TO THE SYSTEMPIPING OR BEING FILLED. THE SAFETY CAPMUST NOT BE REMOVED FROM ITS CHAIN.2. SEE F-93-2070 FOR ADDITIONAL INFORMATION.

ORDERING INFORMATION

CYLINDER VALVE

LIQUID LEVEL INDICATOR

LIFTING LUGS

CYLINDERNAMEPLATE

16.00" DIA

CYLINDER

VALVE OUTLET

30°

PLAN VIEW

SAFETY CAP

58.36" 53.14"

P/N: 93-10035X-001

N/P NOITPIRCSED

100-053001-39100-153001-39

DTSILL/W

Page 23: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2060

F-93-2060 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSVALVE BODY: BRASSCYLINDER; STEEL, PAINTED RED

Cylinder and Valve Assembly 600 LB (272.1 KG) Capacity

CYLINDER VALVE

LIQUID LEVEL INDICATOR

LIFTING LUGS

CYLINDERNAMEPLATE

22.00" DIA

CYLINDER

VALVE OUTLET

30°

PLAN VIEW

SAFETY CAP

56.72" 50.51"

NOTES:1. THE SAFETY CAP MUST BE INSTALLED ON THEVALVE OUTLET AT ALL TIMES EXCEPT WHEN THECYLINDERS ARE CONNECTED TO THE SYSTEMPIPING OR BEING FILLED. THE SAFETY CAPMUST NOT BE REMOVED FROM ITS CHAIN.2. SEE F-93-2070 FOR ADDITIONAL INFORMATION.

ORDERING INFORMATION

P/N: 93-10060X-001

N/P NOITPIRCSED

100-006001-39100-106001-39

DTSILL/W

Page 24: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2070

F-93-2070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

Cylinder Data

(Sheet 1 of 2)

ENGINEERED SYSTEMS CYLINDER DATA

NOTE: ENGINEERED SYSTEMS HAVE A FILL DENSITY RANGE OF 30 LB/CU FT TO 70 LB/CU FT

TRAPREBMUN

EGNARLLIFYTPMETHGIEW

THGIEWSSORG

ILL/WTHGIEH RETEMAID EMULOV

LLIFNIM LLIFXAM

BL GK BL GK BL GK BL GK NI MC NI MC TF 3 M3

100-010001-39 01-5 5-3 52 11 03 41 53 61 ON 03.71 44 70.7 81 761.0 7400.0

100-020001-39 02-9 9-4 13 41 04 81 15 32 ON 79.42 46 70.7 81 682.0 1800.0

100-040001-39 04-71 81-8 83 71 55 52 87 53 ON 67.62 86 00.9 32 275.0 2610.0

100-070001-39 07-03 23-41 25 42 28 83 321 65 ON 38.83 99 00.9 32 000.1 3820.0

100-121001-39 521-45 75-52 89 54 251 96 322 101 SEY 39.53 29 57.21 33 887.1 6050.0

100-521001-39 521-45 75-52 89 54 251 96 322 101 ON 39.53 29 57.21 33 887.1 6050.0

100-002001-39 002-68 19-93 931 36 522 201 143 451 ON 53.05 821 06.31 53 958.2 0180.0

100-102001-39 002-68 19-93 141 46 722 301 343 551 SEY 53.05 821 06.31 53 958.2 0180.0

101-002001-39 002-68 19-93 331 06 912 001 333 151 ON 57.25 431 57.21 33 958.2 0180.0

101-102001-39 002-68 19-93 331 06 912 001 333 151 SEY 57.25 431 57.21 33 958.2 0180.0

100-053001-39 053-051 951-86 102 19 153 951 555 052 ON 63.85 941 00.61 14 000.5 6141.0

100-153001-39 053-051 951-86 302 29 143 061 755 152 SEY 63.85 941 00.61 14 000.5 6141.0

100-006001-39 006-852 272-411 533 251 395 072 539 524 ON 27.65 541 00.22 65 275.8 7242.0

100-106001-39 006-852 272-411 733 351 595 072 739 624 SEY 27.65 541 00.22 65 275.8 7232.0

Page 25: Modular Cylindrical

Effective June 1999FM-200 COMPONENT DESCRIPTION

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2070

(Sheet 2 of 2)

Cylinder Data

MODULAR SYSTEMS CYLINDER DATA

NOTE: MODULAR SYSTEMS HAVE A FILL DENSITY RANGE OF 40 LB/CU FT TO 70 LB/CU FT* Fill density range of 40lb/cu ft to 58.3 lb/cu ft for modular balanced systems only

F-93-2070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

TRAPREBMUN

EGNARLLIFYTPMETHGIEW

THGIEWSSORG

ILL/WTHGIEH RETEMAID EMULOV

LLIFNIM LLIFXAM

BL GK BL GK BL GK BL GK NI MC NI MC TF 3 M3

100-X10001-39 01-6 5-3 52 11 13 41 53 61 ON 03.71 44 70.7 81 761.0 7400.0

100-X20001-39 02-11 9-5 13 41 24 91 15 32 ON 79.42 46 70.7 81 682.0 1800.0

100-X40001-39 04-32 81-01 83 71 16 72 87 53 ON 67.62 46 00.9 32 275.0 2610.0

100-X70001-39 07-14 23-91 25 42 49 34 321 65 ON 38.83 99 00.9 32 000.1 3820.0

100-121001-39 521-17 75-23 89 54 961 77 322 101 SEY 39.53 29 57.21 33 887.1 6050.0

100-521001-39 521-17 75-23 89 54 961 77 322 101 ON 39.53 29 57.21 33 887.1 6050.0

100-002001-39 002-621 19-65 931 36 562 021 933 451 ON 53.05 821 06.31 53 958.2 0180.0

100-102001-39 002-621 19-75 141 46 762 121 143 551 SEY 53.05 821 06.31 53 958.2 0180.0

101-002001-39 002-621 19-75 331 06 952 811 333 151 ON 57.25 431 57.21 33 958.2 0180.0

101-102001-39 002-621 19-75 331 06 952 811 333 151 SEY 57.25 431 57.21 33 958.2 0180.0

100-053001-39 053-102 951-19 102 19 604 281 555 052 ON 63.85 941 00.61 14 000.5 6141.0

100-153001-39 053-102 951-19 302 29 804 381 755 152 SEY 63.85 951 00.61 14 000.5 6141.0

100-006001-39* 005-153 722-951 533 251 686 213 538 083 ON 27.65 541 00.22 65 275.8 7242.0

100-106001-39* 005-153 722-951 733 351 886 313 738 083 SEY 27.65 541 00.22 65 275.8 0742.0

Page 26: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2080

Cylinder Valve

WORKING PRESSURE: 360-609 PSIGPROOF PRESSURE: 1000 PSIGBURST PRESSURE 2000 PSIGTEMPERATURE RANGE: 32o TO 130o F

MATERIALSVALVE BODY: BRASSPISTON: BRASSFINISH: NATURALSEAT: RUBBER

EQUIVALENT LENGTH OF SCHEDULE 40 PIPE:1-1/2" : 16.7' OF 1-1/4"2" : 28.0' OF 2"2½" : 31.5' of 2½"

P/N: 93-1X0000-000

F-93-2080 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

24 LB

15 LB

9.9 LB

2-1/2"

2"

1-1/2"

VALVE SIZE

SAFETY

DISCHARGE

OUTLET PORT

CAP

93-160000-000

93-150000-000

93-140000-000

PART NO.

F: WEIGHT

E: SAFETY DISC REPL. P/N

D: SAFETY DISC RELIEF PRESSURE

6.61"

6.28"

5.22"

6.30"

5.32"

4.83"

10.04"

8.80"

7.63"

A B

C

C

SEAT

798-972 PSI

798-972 PSI

754-900 PSI

D

264929

264925

242461

E F

CONNECTION

PRESSURE

SUPERVISORY

SWITCH

PISTON

SAFETY CHAIN

VENT HOLE

PRESSURE

PROTECTION

CAP

GAGE

VALVE CORE, PILOT

CONNECTION

ACTUATION PORT

CONTROL HEAD

B

BODY

1/8" NPTACTUATION PORT

SAFETY

SLAVE CYLINDER

A

DISC

Page 27: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2090

Cylinder Supervisory Pressure Switch

ELECTRICAL RATING:120/240/277 V-AC 375 VA28V-AC/DC 2 AMPS

NEMA 1 ENCLOSUREACTUATION PRESSURE: 320 PSI +/- 10 PSIDEACTUATION PRESSURE: 250 PSI +/- 10 PSIOPERATING TEMPERATURE RANGE: +32oF TO +130oFOPERATION EXAMPLE: "NORMALLY CLOSED" DEVICECONTACTS ARE OPEN UNDER PRESSUREPRESSURE LOSS GREATER THAN 40 PSI WILL CAUSECONTACTS TO CLOSE P/N: 8787090X

NOITAREPO N/P

NEPO(DESOLCYLLAMRON)ERUSSERPREDNU

00907878

DESOLC(NEPOYLLAMRON)ERUSSERPREDNU

10907878

ORDERING INFORMATION

WITH VALVE CORE DEFLECTOR

1/4" SAE FEMALE PORT FITTING

1.56”

.47" CONDUIT ENTRY HOLE

2.12"

1.56"

2.93”

F-93-2090 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

Page 28: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2100

Valve Outlet Adapters

F-93-2100 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

NOTE: FOR DIRECT CONNECTION OF CYLINDER VALVE TODISTRIBUTION PIPING.MATERIAL: BRASS

P/N: 28390X

CD

A (SYSTEM PIPE CONNECTION)

B (VALVE OUTLET CONNECTION)

ORDERING INFORMATION

.ONTRAP EZIS *A *B *C *D

409382 2/1-1 TPN"2/1-1478.1JNU21

96.2 XEH05.2

509382 2 TPN"2005.2JNU21

21.3 XEH00.3

609382 2/1-2 TPN"2/1-2000.3JNU21

00.3 XEH57.3

Page 29: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2110

Liquid Level Indicator

F-93-2110 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

ORDERING INFORMATION

REDNILYC N/PEPATILL

521 186532

002 498382

053 498382

006 498382

CAP

GRADUATED TAPE

O-RINGP/N: WK-566109-160

BRASS TUBE

FM-200

EDGE OF FITTING

BRASS TUBE

TAPE INSIDE

READING TAKEN AT TOP

P/N: SEE TABLE

TAPE IN MAGNETIC INTERLOCK

POSITION READY TO TAKE

READING.

CYLINDER

LIQUID LEVELMAGNETIC END OFTAPE ENGAGESIN MAGNETIC FIELDOF FLOAT WHENTAPE IS PULLEDUP TO TAKE READING

MAGNET EMBEDDED

FLOAT - FLOATS ON SURFACE

FM-200

IN FLOAT

OF LIQUID FM-200.

FREE TO MOVE UP OR DOWN

OUTSIDE OF BRASS TUBE.

RETAINER - FLOAT RESTSHERE WHEN CYLINDER

IS EMPTY.

Page 30: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2120

Flexible Discharge Hoses

F-93-2120 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MINIMUM BURSTING PRESSURE: 2000 PSIWORKING PRESSURE: 500 PSIPROOF PRESSURE: 1000 PSI

MATERIALSHOSE: REINFORCED RUBBER HOSEFITTING: BRASS

A

HOSE

SYSTEM PIPE CONNECTION,

MALE NPT THREAD

FM-200 CYLINDER VALVE

CONNECTION, SWIVEL NUT

.ONTRAP TPNELAM A SUIDARDEB.NIM

898382 2/1-1 42 5.01

998382 2 13 5.31

009382 2/1-2 84 5.22

ORDERING INFORMATION

Page 31: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2130

Manifold El-Check

F-93-2130 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

A

B

VALVE BODY

C

C CHECK

FOR CONNECTION TO

ARROW INDICATES

SYSTEM MANIFOLD

FLOW DIRECTION

PART NO. SIZE A* B* C*

877690 2 3.93 4.88 2” NPT

2-1/2” NPT5.764.692-1/2878743

NOTE: EL-CHECKS ARE TO BE INSTALLED AT SYSTEMMANIFOLD IN VERTICAL DIRECTION AS SHOWN

NOTE: DO NOT USE AS A MAIN/RESERVE CHECKVALVE WITH MORE THAN 1 MAIN/RESERVE CYLINDER

MATERIALSVALVE BODY: ZINC PLATED STEELCHECK: STAINLESS STEELSEAT: NITRILE RUBBER

*DIMENSIONS ARE IN INCHES

Page 32: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2131

Typical Installation of El-Check

F-93-2131 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

NOTES: INSTALL EL-CHECKS SO THAT ARROW IS INDIRECTION OF FLOW

EL-CHECK MAY BE ADJUSTED AS SHOWN TO OB-TAIN A SMOOTH RADIUS IN FLEXIBLE DISCHARGEHOSE.

Page 33: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2140

360 Degree Pendant Nozzle

F-93-2140 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

A SELECTION OF ORIFICES ARE AVAILABLE FOREACH NOZZLE SIZE. CONSULT YOUR FENWALDESIGN AND INSTALLATION MANUAL FOR DETAILS P/N: 93-19402X-XXX

2.500" (63.50mm)

1.250" (31.75mm)

1.500" (38.10mm)

1.750" (44.45mm)

2.250" (57.15mm)

3.000" (76.20mm)

Pipe Size

2.250" (57.15mm)

1.750" (44.45mm)

3.000" (76.20mm)

1.250" (31.75mm)

2.250" (63.50mm)

1.500" (38.10mm)

2" (50.80mm)

1-1/2" (38.10mm)

1" (25.40mm)

1-1/4" (31.75mm)

3/4" (19.05mm)

1/2" (12.20mm)

2.937" (74.59mm)

1.937" (49.19mm)

2.125" (53.97mm)

2.375" (60.32mm)

2.750" (69.85mm)

3.125" (79.37mm)

2.000" (50.80mm)

1.950" (49.53mm)

1.718" (43.63mm)

1.578" (40.08mm)

1.468" (37.28mm)

2.062" (52.37mm)

A

A

360 DEGREE NOZZLE

B C

C

D

FE D

METAL STAMP X-XXX (HOLE DIA. SIZE)

IN .093 ± .031 HIGH

CHARACTERS ON ANY FLAT

B

Page 34: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-2150

180 Degree Pendant Nozzle

F-93-2150 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

A SELECTION OF ORIFICES ARE AVAILABLE FOREACH NOZZLE SIZE. CONSULT YOUR FENWALDESIGN AND INSTALLATION MANUAL FOR DETAILS

P/N: 93-19401X-XXX

2.875" (73.02mm)

2.656" (67.46mm)

2.218" (56.33mm)

1.950" (48.89mm)

1.687" (42.84mm)

2.950" (74.93mm)

Pipe Size

1/2" (12.20mm)

3/4" (19.05mm)

1-1/4" (31.75mm)

1" (25.40mm)

1-1/2" (38.10mm)

2" (50.80mm)

1.250" (31.75mm)

1.375" (34.92mm)

1.562" (39.67mm)

1.750" (44.45mm)

1.968" (49.98mm)

1.950" (48.89mm)

1.500" (38.10mm)

2.250" (63.50mm)

1.250" (31.75mm)

3.000" (76.20mm)

1.750" (44.45mm)

2.250" (57.15mm)

A

180 DEGREE NOZZLE

A

30° FEN

WA

L

B C

60°

B

IN .093 ±.031 HIGH CHARACTERS

METAL STAMP X-XXX (DASH NO.)

ON ANY FLAT

C

D

3.656" (92.86mm)

3.250" (82.55mm)

2.671" (67.84mm)

2.296" (58.31mm)

2.000" (50.80mm)

3.625" (92.07mm)

D

Page 35: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5010

Pressure Operated Control Head

F-93-5010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

P/N: 878737MATERIALBODY: RETAINING NUT, AND PISTON: BRASS

1.250-18

UNEF-3B

SWIVEL NUT

PISTON

1/8"-27 NPT

PRESSURE INLET

SETOPERATED

2.19"

1.50" HEX

1.00" HEX

Page 36: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5020

Pressure Operated Control Head, Stackable

F-93-5020 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALBODY, RETAINER CAP, PISTON & MTG. NUT: BRASS P/N: 878750

Page 37: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5030

Lever or Pressure Operated Control Head

F-93-5030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSLEVER: STAINLESS STEELBODY & PISTON: BRASS

P/N: 878751

Page 38: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5040

Pilot Actuation Fittings

F-93-5040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIAL: BRASS

Page 39: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5050

Nitrogen Pilot Cylinder, Bracket, and Adapter

F-93-5050 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSCYLINDER: STEEL, PAINTED BLACKVALVE: BRASSBRACKET: STEEL, PAINTED BLACKADAPTER: BRASS

GAUGE

PLUG OUTLET PORT-1/8" NPT FEMALE,

ATTACH ADAPTER HERE

SAFETY

OUTLET

1/8" NPT

MALE

5/16"-TUBING MALE

ADAPTER

P/N WK-699205-010

1-1/4"-18 NF-3

FOR CONTROL HEAD CONNECTION

CYLINDER P/N 877940-000

BRACKET P/N 877845-000

SPECIFICATIONS

CYLINDER CAPACITY-108 in (1770 CM )SAFETY OUTLET BURST RANGE: 2650-3000 PSI (183-207 BARS) AT 70°F (20°C)NITROGEN-BB-n-411 b, GRADE A, TYPE I1800 PSI (124 BARS) AT 70°F (20°C)

16"

3.56"

(406mm)

(90mm)

33

N/P noitpircseD

049778 dradnatS

100-377921-60desolCyllamroN

erusserPrednUnepO

200-377921-60nepOyllamroN

erusserPrednUdesolC

Page 40: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5070

1/4" Flexible Actuation Hoses

F-93-5070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSHOSE: WIRE BRAIDED, TEFLON LINING (CRES T304)COUPLINGS: BRASSMINIMUM BURST PRESSURE: 12,000 PSIGOPERATING PRESSURE: 3000 PSIGTEST PRESSURE: 4500 PSIGMINIMUM BEND RADIUS 2.5"

P/N: 26498x

Page 41: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5080

Master Cylinder Adapter Kit

F-93-5080 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSADAPTER & CAP: BRASSCHAIN: STAINLESS STEELLABEL: MYLAR

P/N: 844895

1.42"

1/4" MALE NPT X 5/16" TUBING

PROTECTION CAP

CAUTION

INSTALL CAP

WHEN

NOT IN

USE

LABEL

Page 42: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5090

1/4" Check Valve

F-93-5090 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

WORKING PRESSURE: 0-1800 PSI (0-124 BAR)MINIMUM BURSTING PRESSURE: 5000 PSI (345 BAR)

MATERIAL: BRASS

NOTE: INSTALL VALVE WITH ARROW POINTING INDIRECTION OF FLOW.

P/N: 264985

Page 43: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

F-93-5100

3/8" Check Valve

F-93-5100 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

TECHNICAL DATAWORKING PRESSURE: 0 TO 5000 PSI (0 TO 345 BAR)PROOF PRESSURE: 10,000 PSI (690 BAR)CRACKING PRESSURE: 2 TO 4 PSI (.14 TO .28 BAR)OPERATING TEMPERATURE: -40F TO 250F (-40F TO 121C)

MATERIALSBODY: BRASSSEAL: BUNA-N

1.00"2.35"

(60 MM) (25 MM)

HEX

3"

8NPT BOTH ENDS

INSTALL VALVE WITH ARROW POINTING

IN DIRECTION OF FLOW.

P/N: 261193

Page 44: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5110

Check Valves, 1/2" Thru 2"

F-93-5110 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

VALVE MUST BE INSTALLED WITH ARROW POINTING INDIRECTION OF FLOW

MATERIAL: BRASS

Page 45: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5120

Check Valves, 2-1/2" & 3"

F-93-5120 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

VALVE MUST BE INSTALLED WITH ARROW POINT-ING IN THE DIRECTION OF FLOW

MATERIALSVALVE BODY: BRASSGASKET: IRONFLANGES, BOLTS, & NUTS: STEEL

P/N: 870100

EGNALFKCENGNIDLEW

EVLAVKCEHCEZIS

N/PYTQ

DERIUQER

"2/1-2 617362 2

"3 0021-0186 2

ORDERING INFORMATION

Page 46: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

F-93-5130

Stop (Directional) Valves, 1/2" Thru 2"

F-93-5130 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

NOTES:1. VALVE MUST BE INSTALLED WITH ARROW POINTING INDIRECTION OF FLOW.2. VALVE MAY BE INSTALLED IN HORIZONTAL OR VERTI-CAL PIPE RUN.

MATERIALSBODY: BRASS

B

C

A

INLETVALVE SIZE

OUTLET

(NPT)

BOTH ENDS

1-1/4 - 18 NF-3 FOR CONTROL HEAD CONNECTION

TRAPREBMUN

EZISEVLAVTPN

A B C

NI MM NI MM NI MM

320078220078221078230078321078940078

"2/1"4/3

"1"4/1-1"2/1-1

"2

57.352.405.505.505.705.7

59801041041191191

05.218.226.326.357.457.4

46172929121121

86.486.578.678.634.834.8

911441571571412412

Page 47: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

F-93-5140

Stop (Directional) Valves, 2-1/2" & 3"

F-93-5140 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

VALVE MUST BE INSTALLED WITH ARROW POINTINGIN DIRECTION OF FLOW

MATERIALSVALVE BODY: BRASSGASKET: IRONFLANGES, BOLTS, & NUTS: STEEL

P/N: 890010

ORDERING INFORMATION

CONNECTION

FOR CONTROL HEAD

1 - 1/4” -18 NF-3 MALE

3/4” X 4 - 1/2”

OUTLET

(249mm)

9.81"INLET

10.5"

(267mm)

3/4” HEX NUT

P/N 1523-0800

16 REQUIRED

GASKETP/N 200973

2 REQUIRED

WELDING NECK FLANGEP/N 263716

(114mm) LG.HEX BOLT

P/N 1966-4872-16 REQUIRED

SIDE VIEW

WITHOUT

ASSEMBLED FLANGE

FLANGE - 6.62" (168mm)

BOLT CIRCLE

8.25" (210mm) DIA.

EVLAVKCEHCEZIS

N/PKCENGNIDLEW

N/PEGNALF)DERIUQER2(

"2/1-2 010098 617362

"3 010098 0021-0186

Page 48: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

F-93-5150

4" Stop (Directional) Valve

F-93-5150 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

VALVE MUST BE INSTALLED WITH ARROW POINTING INDIRECTION OF FLOWMATERIALS

VALVE BODY: BRASSGASKET: IRONFLANGES, BOLTS, & NUTS: STEEL

P/N: 890208

10.75" (273mm) DIA.

BOLT CIRCLE

FLANGE - 8.50" (216mm)

ASSEMBLED FLANGE

WITHOUT

SIDE VIEW

P/N 1966-5680-16 REQUIRED

HEX BOLT7/8” X 5" (127mm) LG.

2 REQUIRED

P/N 6810-1600WELDING NECK FLANGE

2 REQUIRED

P/N 200150GASKET

16 REQUIRED

P/N 1523-5600

7/8” HEX NUT

(308mm)

12.12"

INLET

4"

11.06"

(281mm)

OUTLET

1- 1/4” -18 NF-3 MALE

FOR CONTROL HEAD

CONNECTION

Page 49: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5160

Discharge Indicators

F-93-5160 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSBODY-967082: BRASSBODY-875553: ALUMINUMCAPS: CLEAR CELLULOSE ACETATE

EZIS N/P

)SSARB("4/3 280769

)LA("2/1 355578

ORDERING INFORMATION

NORMAL

DISCHARGE

POSITION

INDICATION

POSITION

CAP

STEM

3.25"

(83mm)

BODY

NPT MALE

1.12"(29mm) HEX

ACROSS FLATS

3"

4

P/N 967082

2.62"

(67mm)

P/N 875553BODY

NPT MALE

0.93"(24mm) HEX

ACROSS FLATS

1"2

POSITION

INDICATION

POSITION

DISCHARGE

NORMAL

STEM-RED

CAP

Page 50: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5170

Safety Outlets

F-93-5170 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSBODY & RETAINING NUT: BRASSSEAL WIRE: COPPER & LEAD

BODY

SEAL WIRE

SAFETY DISC

RETAINING NUT

NPT MALE

1.78"

(45mm)

3"4

PART

NUMBERAGENT

PRESSURE RELIEF

OPERATES AT

PSI BAR

803242 2400-2800 166-193

844346 FM-200 750-900 52-62

N2/CO2

Page 51: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5180

Pressure Operated Switch

F-93-5180 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

P/N: 486536

NOTES:1. SWITCH MAY BE MOUNTED IN ANY POSITIONBUT PREFERRED INSTALLATION IS UPRIGHT ASSHOWN.2. ANY LOAD CONNECTION TO THE SWITCH MUSTNOT EXCEED SWITCH RATING AND SHALL UTILIZEA SUITABLE PROTECTION DEVICE (ie. CIRCUITBREAKER, FUSE)3. CONTACT RATINGS (3PDT)15 AMP @ 125 VAC10 AMP @ 250 VAC3/4 HP @ 250 VAC1, 2 OR 3 PHASE

Page 52: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5190

Pressure Operated Switch, Explosion Proof

F-93-5190 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

NOTES:1. TOGGLE SWITCH MAY BE MOUNTED IN BASEFOR EITHER N.O. TO N.C. OR N.C. TO N.O. CON-TACT TRANSFER UPON OPERATION. ILLUSTRATIONSHOWS POSITION OF TOGLE WHEN SWITCH IS INSET POSITION.2. ANY LOAD CONNECTED TO THE SWITCH MUSTNOT EXCEED SWITCH RATING AND SHALL UTILIZEA SUITABLE PROTECTION DEVICE. (ie. CIRCUITBREAKER, FUSE)

3. REMOVE OPERATING HEAD TO MAKE ELECTRI-CAL CONNECTIONS TO TOGGLE SWITCH. WHENREPLACING OPERATING HEAD, ENSURE THATTOGGLE ENGAGES CLUTCH. TIGHTEN COVERSCREWS SECURELY.4. CLASS I, GROUP D CAUTION: TO PREVENTIGNITION OF HAZARDOUS ATMOSPHERES,DISCONNECT THE DEVICE FROM THE SUPPLYCIRCUIT BEFORE OPENING. KEEP ASSEMBLYTIGHTLY CLOSED WHEN IN OPERATION.

P/N: 981332

Page 53: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5200

Pressure Trip

F-93-5200 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MAXIMUM LOAD ON RING: 100 LBS. (45 KG)MINIMUM NOMINAL OPERATING PRESSURE:50 PSI (3.5 BAR)MATERIALS

BODY, BRACKET, AND PISTON: BRASSGUARD, STEM, RING AND SPRING: STAINLESSSTEEL

P/N: 874290

1.37"

SPRING

PISTON

2.50"

(64mm)

(41mm)

HEX

PRESSURE INLET½”NPT - FEMALE

1.62"

(41mm)

BODY

RING

STEM

GUARD BRACKET WITH

.375"(10mm) DIA.

MOUNTING HOLE

Page 54: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-5201

Pressure Trip Applications - Installation Detail

F-93-5201 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

Page 55: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-6010

Lever Operated Control Head

F-93-6010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSLEVER: STAINLESS STEELBODY: BRASS

P/N: 870652

Page 56: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-6020

Cable Operated Control Head

F-93-6020 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

P/N: 979469

LOCAL MANUAL RELEASE LEVER

SEAL WIRE

LOCKING PIN

DIRECTION OF

PULLTHREADED NUT -

3/8" NPS FOR PIPE

1/16" CABLE

3/8" PIPE (OR 1/2" EMTWITH ADAPTER P/N

843837 - SEE F-93-6120)SWIVEL

NUT

1.50"

(38mm)

1-1/4"-18 NF-3

FEMALE

CLOSURE

DISC

CABLE CLAMP AND WHEEL ASSEMBLY

4.25"

5.25"

(108mm)

(133mm)

Page 57: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-6021

Tandem Cable Operated Control Heads - Installation Detail

F-93-6021 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

CYLINDER CENTERS

HEAD (CLOSURE DISC REMOVED)

SLOT IN CONTROL

HOUSING FITS INTOFLARE ON CABLE

1/16” CABLE

WHEEL ASSEMBLY

SEE F-93-6030

CABLE HOUSING

3/8” PIPE OR

ADAPTER P/N

843837-SEE F-93-6120

CABLE CLAMP AND

Page 58: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-6030

Cable Housing for Cable Operated Control Heads

F-93-6030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIAL: Brass, .625" (16mm) O.D. x .049" (1.28 mm) WALL

FLARED 3/8" NPS MALE

A

TRAPREBMUN

SREDNILYCHTIWDESU

REDNILYCSRETNEC

NOISNEMID"A"

SBL GK NI mm NI mm

207062159062206362

002,521053006

7.09-7.657.8511.272

0.510.810.42

183754016

6.016.316.91

072643894

Page 59: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-6040

Pull Box, Break Glass

F-93-6040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSBody: AluminumHandle: Brass

P/N: 871403

400 Main Street - Ashland, MA 01721-2150

Tel.(508)881-2000 FAX (508)881-8920

KiddeR

FOR FIREBREAK GLASS PULL HANDLE

PULL HARD

OPTIONAL

NAMEPLATE

(BY INSTALLER)

HAMMER

PULL

4-COVER

3/8” PIPE

1/16” CABLE

SCREWS

HANDLE

2 - NAMEPLATEBRACKETS-

(SUPPLIED WITH

PULL BOX)

5.87"

5.00" 2.25"

(57mm)(127mm)

(149mm)

PULL HANDLE

CABLE FASTENER FOR

BREAK GLASS

P/N WK-928103-000

1/16” CABLE

3/8” NPT FEMALE2 - HOLES FOR 1/4”

MOUNTING SCREWS

(SCREWS NOT SUPPLIED

WITH PULL BOX)SECTION VIEW

WK-524906-080P/N

P/N WK-803246-000

P/N WK-934617-000

Page 60: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-6041

Break Glass Pull Box used with Z-Bracket - Installation Detail

F-93-6041 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

P/N 60532

Z-BRACKET

(90mm)

SEE F-93-6120ADAPTER P/N 843837

3.56"

SEE F-93-6080PULLEY-P/N 844648-

2E.M.T. CORNER

(114mm)4.50"

16

1"CABLE

E.M.T.1"

2

1"

1"

4MOUNTING BOLTS HERE

3 HOLES FOR

Z-BRACKET

P/N 60532 (90mm)3.56"

SEE F-93-6080PULLEY P/N 803808

4.50"(114mm)

WATERTIGHT CORNER

NPT NIPPLE8

3"

CABLE1"

16

Page 61: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-6100

Dual Pull Mechanism

F-93-6100 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

P/N: 840058

Page 62: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-6110

Dual Pull Equalizer

F-93-6110 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

P/N: 840051

Page 63: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-6120

Adapter, 3/8" Pipe (Male) to 1/2" EMT (Female)

F-93-6120 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIAL: ZINC PLATED STEEL

P/N: 843837

Page 64: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-7145

Cylinder Recharge Adapters

F-93-7145 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIAL: ZINC PLATED STEEL

3.624.00600878759

3.254.06200, 350878758

878757 10-125 3.22 2.50

B*A*CYL. SIZE (LB)P/N

* DIMENSIONS ARE IN INCHES

3/8" NPT (VENT

VALVE CONNECTION

"A"

3/8"-18NPT

(CHARGE CONNECTION)

O-RING

SEAL

CYLINDER VALVE

OUTLET CONNECTION

"B"

HEX

Page 65: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-8010

Electric Control Head

F-93-8010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

P/N: 8901XX

PU

ELECTRIC

CONTROL HEAD

VOLTS

AMPS

PART NO.

SET RELEASEDMADE IN U. S. A.

TO RESETUSE SCREWDRIVER

CONNECTION FOR FLEXIBLE

ELECTRIC CONDUIT-

3/4" NPT FEMALE

LOCKING PIN

LOCAL MANUAL

RELEASE LEVER

SWIVEL NUT

1.50" (38mm) HEX

1-1/4"-18 NF-3 THREAD

CONTROL HEADPART

NUMBER

890181

890149

890165

VOLTAGE

24 VDC

125 VDC

115 VAC

CURRENT

2.0A

0.3A

1.0A

KIDDE-FENWAL, INC.

400 MAIN STREET

ASHLAND, MA 01721

INDICATOR ANDRESET STEM

6.18"

4.00"

(157mm)

(102mm)

SEAL WIRE

ORDERING INFORMATION

Page 66: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-8017

Electric Control Head, Stackable Explosion Proof

F-93-8017 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

P/N: 486500-01

VOLTAGE: 24VDCCURRENT: 0.2A CONTINUOUS DRAW

5.28"

2.90"

1.25-18 UNEF-2A

1/2"-14 NPT

(3) 18 AWG-LEADS

CONDUITCONNECTION

18" LONG

CONNECTION

SWIVEL NUT

1.25-18 UNEF-2B

CONNECTION

ELECTRIC CONTROL HEAD, PART

NO. 486500-01 IS RATED FOR USE

IN HAZARDOUS (CLASSIFIED)

LOCATIONS CLASS 1, DIV. l,

GROUPS C, D AND CLASS ll, DIV. ll,

GROUPS E, F, G BETWEEN

-40F AND 140F. USE CONDUIT

SEAL WITHIN 18 IN. (45cm) OF

THIS DEVICE.

NOTE:THIS CONTROL HEAD IS POLARIZED. IMPROPERWIRING WILL RESULT IN FAILURE OF THIS DEVICE TOOPERATE

WARNINGELECTRIC CONTROL HEAD, P/N: 486500-01, IS DESIGNEDFOR INSTALLATION DIRECTLY ON 487 SERIES HALONAND MODEL 9300 FM-200 VALVES ONLY. THIS CONTROLHEAD MUST NOT BE INSTALLED ON ANY OTHER TYPEOF HALON OR FM-200 CYLINDER VALVE, NITROGENVALVE, CARBON DIOXIDE CYLINDER VALVE, FE-13 CYL-INDER VALVE OR STOP (DIRECTIONAL) VALVE. INSTAL-LATION OF THIS CONTROL HEAD TO ANY OTHER DE-VICE (E.G., PRESSURE OPERATED CONTROL HEAD) WILLRESULT IN FAILURE OF DEVICE TO OPERATE.

Page 67: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-8030

Electric And Cable Operated Control Head

F-93-8030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

7.56"

(192mm)

(138mm)

5.44"

CONTROL HEAD

895630

895628

895627

PART No.

115 VAC

125 VDC

24 VDC

VOLTAGE

1.0

0.3

2.0

AMPS

MADE IN U. S. A.

RELEASED

ASHLAND, MA 01721

400 MAIN STREET

KIDDE-FENWAL, INC.

SET

WIRE

RESET STEM

INDICATOR AND

3/4" NPT (FEMALE)

ELECTRIC CONDUIT-

CONNECTION FOR FLEXIBLE

LOCKING PIN

RELEASE LEVER

LOCAL MANUAL

ELECTRIC

PART NO.

VOLTS

CONTROL HEAD

USE SCREWDRIVER

TO RESET

AMPS

1 1/4-18NF-3 THREAD

1.50" (38mm) HEX

SWIVEL NUT

SEAL

1/2" E.M.T. CONNECTION

COMPRESSION TYPE FOR

REMOTE CABLE

1/2" E.M.T. CONNECTIONCOMPRESSION TYPE TOSECOND CONTROL HEADIF USED

PU

Page 68: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-8040

Electric and Cable Operated Control Head withExplosion Proof Solenoid

F-93-8040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

SE

TR

ELE

AS

ED

TO

RE

SE

T

US

ES

CR

EW

DR

IVE

R

FO

R

MA

INT

EN

AN

CE

SE

E

INS

TR

UC

TIO

NS

CA

BL

E

PU

LL

PU

OPERATING SOLENOID

U.L. LISTED FOR USE IN

THE FOLLOWING HAZARDOUS

LOCATIONS:

CLASS GROUP OP. TEMP.

I C

CONNECTION FOR FLEXIBLE

ELECTRIC CONDUIT 1/2" NPT

FEMALE

CONNECTING WIRES

36" (914 MM) LONG

7.375

INDICATOR AND

RESET STEM

(187 MM)

4.937(125 MM)

LOCKING PIN

SEAL WIRE

CONNECTION FOR

REMOTE PULL BOX

PIPE OR CONDUIT

3/8" NPS MALE

LOCAL MANUAL

RELEASE LEVER

SWIVEL NUT

1.500 (38 MM) HEX

1.250-18 NF-3 THREADCONNECTION FOR CABLE

HOUSING TO SECOND

CONTROL HEAD IF USED

3/8" NPS FEMALE.

USE PNEUMATIC CONTROL

HEAD CABLE HOUSINGS

SEE F-93-5020.

EL

EC

TR

IC

CO

NT

RO

LH

EA

D

PA

RT

NO

.

MA

DE

INU

.S.A

.

KID

DE

-FE

NW

AL

,IN

C.

40

0M

AIN

ST

RE

ET

AS

HL

AN

D,

MA

01

72

1

VO

LT

S

HZ

AM

PS

-13 TO +150F

(-25 TO +65C)

I D

(-40 TO +65C)

-40 TO +150F

II E,F,G -40 TO +150F

(-40 TO +65C)

PART

NUMBER

CONTROL HEAD

VOLTAGEPOWER

CONSUMPTION

897494 24 VDC 33 WATTS

897560 120 VAC 15.4 WATTS

Page 69: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-8070

Electric Main-To-Reserve Transfer Switch

F-93-8070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIALSCONDUIT BOX: STEEL WITH RED ENAMEL FINISHTOGGLE SWITCH LEVER: BAKELITE

P/N: 802398

Page 70: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-8130

Cylinder Mounting Straps

F-93-8130 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIAL: STEEL, PAINTED BLACK SAE 1020

Page 71: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-8140

Cylinder Wall Brackets

F-93-8140 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIAL: STEEL, ZINC PLATEDSAE 1010

Page 72: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-8150

Cylinder Mounting Cradle

F-93-8150 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIAL: STEEL, PAINTED GRAY AISI M1020

Page 73: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-9010

Main and Reserve Nameplates

F-93-9010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

MATERIAL: ALUMINUM WITH RED PAINT LETTERSP/N: 3103X

5.00"

1.62"(41mm)

(127mm)

RESERVE

P/N 31034 2-0.281"(7mm) DIA.

MOUNTING HOLES

MOUNTING HOLES

2-0.281"(7mm) DIA.P/N 31033

MAIN

(127mm)

(41mm)1.62"

5.00"

Page 74: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

FM-200 COMPONENT DESCRIPTION Effective June 1999

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS

F-93-9030

Warning Nameplate (FM-200)

F-93-9030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

P/N: 06-231865-739

MATERIAL: ALUMINUM TYPE 1100-H14 OR 3003-H14,.032 + .003 THICK. ALL LETTERS TO BE 48 PT.ALTERNATE GOTHIC #2. ETCHED .003 - .005 & FILLEDIN WITH RED CHIP PROOF ENAMEL COLOR NO.21105 PER FED. STC. 595FINISH: ONE COAT CLEAR LACQUER BOTH SIDES

TM

.281 .005 DIA. TYP. 4 HOLES

±.062

5.000

.340

.340 9.360

10.000 ±.063

4.360

WARNING

THIS AREA IS PROTECTED BY AFM-200 EXTINGUISHING

SYSTEM. DO NOT ENTER WITHOUTAUTHORIZATION DURING OR

AFTER DISCHARGE

Page 75: Modular Cylindrical

����������������� ������� ���� ��� ������ ���� ��������������������� ���������� ��� ���!������� ������ ��"�#������!������� �����"�������"�� ��������� ��"�������!�� ������������� ���� �������"�!������������� �������� ����� ��� �� �������� ��"��� ����� �������$����� ���" ��"������������������ �����������%��&'()'*������� ���+,&-.�--'�)&&&

�������������� ����������������������������

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.com

Protection Systems

R

��������� ���� ���� ��� ��� ��� � �� � ����� ������� � ������

���������

����������� ������

��/0�/&1&�����������������������������������'///����������2�����"������3���������4�5���

�������������

����������� ���� � ������ �������� ����� ����� � ���� ��� ������� ����

����� ���� ���� �� ������ ��� ����� ������ � ������� �� ����

3" NPT

FEMALE

8.058

3" NPT

FEMALE

9.360

53° MAX.SWING ANGLE

Page 76: Modular Cylindrical

This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000

R

KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920

www.fenwalfire.comProtection Systems

R

FEATURES• FOR USE WITH UL LISTED AND FMRC APPROVED SYSTEMS

F-93-9041

3" Swing Check ValveInstallation Detail

F-93-9041 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.

90°

NOTES:

1.INSTALL CHECK VALVE SO THAT ARROW

IS IN DIRECTION OF FLOW.

2. INSTALL BETWEEN O AND 90 DEGREES

FROM THE HORIZONTAL.

Effective: November 1999FM-200® COMPONENT DESCRIPTION