Modular Cylindrical
-
Upload
hishamsaeed -
Category
Documents
-
view
791 -
download
7
description
Transcript of Modular Cylindrical
1
Modular CylindricalFM-200™ Agent Storage ContainerP/N 93-120XXX-001
93.120X-1
Effective: August 1999
DESCRIPTIONThese cylindrical agent storage containers, which are lessthan ten inches high and contain from 20 to 30 pounds ofFM-200, are ideal for height-limited locations such as un-der-floor applications. They are equipped with a pressuregauge, a burst disc type discharge valve, a replaceable ini-tiator will assembly a screen assembly, cable assembly,mounting brackets and safety plug. Each ASC has a boss-mounted check valve which accepts and optional Pressureswitch (see Fenwal Data Sheet 93.3119.0) and is used forrecharging the container
Initiator assemblies must be ordered for each container. SeeFenwal data Sheet 93.1932.0 for information.
Total pressure in a filled container is adjusted to 360 psi at70oF by superpressurizing with dry nitrogen.
Nozzles and piping selected shall ensure a minimum dis-charge rate of 84 lbs. FM-200 agent per second at the mini-mum operating temperature. Operating temperature shallbe limited to 32o to 130oF. Nozzles and piping must be inaccordance with Fenwal FM-200 Design Manual.
OPERATIONThe container is discharged when its initiator is actuated torupture the burst disc valve.
INSTALLATIONThe container must be securely mounted in position with thevalve down using the integral mounting brackets. The cen-ter of four slots are located at the corners of a rectangle 8-1/2 in. wide by 11-11/16 in. long. Use four 5/16 in. bolts orstuds to secure the container to a solid surface.
The 93-120251-001 unit has mounting brackets on the bot-tom as shown at right and the 93-120253-001 unit has themounting brackets on top. The 93-120351-001 and 93-120353-001 units have mounting brackets on the dies. Allunits must be mounted with the valve at the bottom: eitherparallel to the floor or facing down. If not mounted in thismanner, proper discharge will not be possible.
After the container is secured in place, remove the safetyplug and screw the screen assembly into the valve body.Then connect the rest of the piping and nozzle specified inthe system drawing. Retain the safety plug for use whenreconditioning the container or whenever a filled containeris moved.
MAINTENANCEThe following inspection and/or maintenance proceduresshould be scheduled or performed upon the occurrence ofany even which might bias the reliability of the system.
A. QUARTERLY INSPECTION
1. Check the pressure gauge. If the pressure is less than325 psig at 70oF (22.9 Kg/cm2 at 21oC) the containermust be removed by qualified personnel, inspected care-fully then recharge or replaced as required. Pressurewill vary with temperature. In the range of 55 to 85oF(12.8 to 29.4oC), this change is approximately 3 psi perdegree F (0.397 Kg/cm2 per degree C).
2. Check all components supporting hardware and tighten,repair or replace as required.
3. Visually check all components for evidence of physicalabuse and take whatever action is indicated. Replaceany component if at all in doubt of its ability to performproperly.
B. SEMI-ANNUL INSPECTION
Qualified personnel are to remove and weight all agent stor-age containers. Losses in net weight of agent must not ex-ceed 5% or 10% under pressure loss adjusted fortemperature. Container, and agent weight are marked onthe mounting bracket.
All outlet piping must be clean and free of dirt, chips, filingsand other foreign material that my become hazardous pro-jectiles or cause the system to become inoperative or inef-fective at the time of discharge.
NOTE: The safety plug shipped with the container must beretained and secured to the container whenever thepiping is removed from a charged container.Charged containers must have safety plug in-stalled when removed from system for shipment.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
RECONDITIONINGAfter a system has been actuated, it is recommended thatthe local authorized Fenwal distributor be contacted to re-condition the system.
The Reconditioning Kit for this unit is P/N 31-193005-001.This kit does not contain the initiator, which must be orderedseparately.
SPECIFICATIONSCylinder Diameter: 9-3/8” (239mm)
Overall Height: 9-7/8” (251mm)
Overall Length: 19-1/2” (495mm)
Empty Weight: 24 lbs. (10.8 Kg) approx.
Volume: .442 cu. ft. (12.52 L)
Minimum Fill: 20 lbs. (9.07 Kg)
Maximum Fill: 30 lbs. (13.61 Kg)
ARCHITECT/ENGINEER SPECIFICATIONSThe agent storage container shall be a Fenwal cylindrical(refillable) FM-200 container constructed of high strength lowHSLA alloy steel. It shall consist of: fill valve, burst disc valveassembly, initiator, safety plug, screen assembly, cable as-sembly, integral supporting flanges, 0-100 psig pressure
gauge and pressure switch assembly (optional). The con-tainers shall hold from 20 to 30 lbs. of FM-200 agent.
Container shall conform to all applicable specifications ofDepartment of Transportation.
The burst disc valve assembly shall be an integral part ofthe agent storage container and shall be operated by apply-ing electrical current to an initiator assembly which has anelectro-explosive device that provides on demand, and in-stantaneous full bore release and discharge of the agent.Valves with moving parts and seals are not acceptable.
Filled containers shall be super-pressurized with dry nitro-gen to 360 psig at 70oF to aid in rapid agent distribution,particularly at lower temperatures. It shall automatically re-lieve between 850 to 1000 psi in even of excessive pressurebuild up.
Devices and connecting leads shall be completely super-vised.
The container design shall permit on-site reconditions andrefilling.
The integral mounting assembly shall provide a means formounting to a solid vertical or horizontal surface and shallwithstand a thrust of 1000 lbs. for 5 seconds in any direc-tion.
*FM-200 is a Registered Trademark of Great Lakes Chemical Corporation
93.120X-1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A. CP
1
Spherical Agent StorageContainerFM-200� Agent Storage ContainerP/N 93-11020X-001 93.1120.1
Effective: March 2000
FEATURES� 4 Convenient Sizes� 20 to 196 Pound Capacities� UL Listed, FMRC Approved� Requires No Floor Space� Electric Initiator Actuation
DESCRIPTIONFenwal Modular Spherical Agent Storage Containers storeFM-200 super-pressurized with dry nitrogen to 360 psig at70oF. These containers hold from 20 to 196 pounds of FM-200 and are equipped with a burst disc type discharge valve,a replaceable initiator well, a screen assembly, safety plugand cable assembly. Each container has two identical boss-mounted check valves which will accept a pressure gauge(standard), and an optional pressure switch (see Data Sheet93.3119.0). Either of these check valves may be used forrecharging the container.Initiator assemblies must be ordered for each container. SeeData Sheet 93.1932.0
OPERATIONThe container is discharged when the initiator is actuated torupture the burst disc valve.
INSTALLATIONThe container must be rigidly mounted in position with thevalve facing down. Fenwal mounting brackets provide a se-cure means for wall mounting containers. A lifting ring onthe container provides a means for raising the container toits mounting location.After the container is secured in place, remove the safetyplug and connect the rest of the piping and nozzles(s) speci-fied in the system drawing. Retain the safety plug for usewhen reconditioning the container and whenever a filled con-tainer is moved.
MAINTENANCEInspection and/or maintenance procedures should be sched-uled as listed below, or performed when an event occurswhich might affect the reliability of the system.
A. QUARTERLY INSPECTION1. Check the pressure gauges of each agent storage con-
tainer. If the pressure is less than 325 psig at 70oF (22.9Kg/cm2 at 21oC), the container should be removed andcarefully inspected by qualified personnel. It should thenbe reconditioned, recharged or replaced depending uponits condition. Pressure varies with temperature, and inthe range of 55oF to 85oF (12.7oC-29.4oC) this change isapproximately 3pse/oF (.38 Kg/cm2/oC)
2. Check all component supporting hardware and tighten orrepair as required.
3, Visually check all components for physical abuse andtake whatever action is necessary. Replace the compo-nent if at all in doubt as to its ability to perform properly.
B. SEMI-ANNUAL INSPECTIONQualified personnel are to remove and weigh all agent stor-age containers. Losses of agent must not exceed 5% in netweight, or 10% reduction of pressure (adjusted for tempera-ture). Container and agent weight are marked on thecontainer�s nameplate.All outlet piping must be clean and free of dirt, chips, fillingsand other foreign material that may become hazardous pro-jectiles or cause the system to become inoperative or inef-fective at the time of the discharge.NOTE: The safety lug shipped with this container should be
retained and secured to the container whenever thepiping is removed from a charge container. Chargedcontainers must have the safety plug installedwhen removed from the system for shipment.Observe proper handling procedures when in-stalling or removing the initiator.
RECONDITIONINGAfter a system has been actuated, it is recommended thatthe local authorized Fenwal Distributor be contacted for re-conditioning the system.The Reconditioning Kit for this unit is P/N 31-193005-001This kit does not contain the initiator, which must be orderedseparately.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
ARCHITECT/ENGINEER SPECIFICATIONSThe agent storage container shall be a Fenwal modularspherical (refillable) container constructed of high strength,low HSLA alloy steel. It shall consist of: fill check valve, burstdisc valve assembly, integral supporting flanges, 0-700 psigpressure gauge and pressure switch assembly (optional).The containers shall hold from 20 to 196 lbs. Of FM-200agent.Containers shall conform to too applicable specifications ofDept. of Transportation, Underwriters Laboratories, and Fac-tory Mutual Research Corp.The burst disc valve assembly shall be an integral part ofthe agent storage container and shall be operated by apply-ing electrical current to an initiator assembly, which has aelectro-explosive device that provides an instantaneous fullbore release and discharge of the agent on demand. Thereleasing mechanism shall contain no moving parts.Filled containers shall be super-pressurized with dry nitro-gen to 360 psig at 70oF to aid in rapid agent distribution,particularly at lower temperatures. It shall automatically re-lieve between 850 to 1000 psig in the event of excessivepressure build-up.Releasing devices and connecting leads shall be completelysupervised.The mounting bracket shall be designed for installation on awall, floor or other rigid surface and shall serve as supportfor the agent storage container, and shall be capable of with-standing a thrust of 1000 lbs. For 5 seconds in any direction.
.oNtraP
erehpS
retemaiD *thgieH **TWytpmE
NI mm NI mm BL gK
100-102011-39 2.31 433 7.02 525 5.82 9.21
100-202011-39 8.41 773 4.22 965 7.63 6.61
100-302011-39 3.71 934 9.42 436 0.25 6.32
100-402011-39 5.12 745 3.92 547 1.99 0.54
*Height is from top of lifting ring to bottom surface of flange.Flange mounting holes 5/8 in. (15.9 mm) diameter locatedon bolt circle 6-5/8 in. (162.3 mm) diameter. Flange is 1.4 in(6.4 mm) thick for all models except for 90-110204-001, whichis 3.8 in. (9.5 mm).**Average weight for shipping and mounting planning. Ac-tual weight stamped on each unit.
������������ � �� �����
�� � �� � ��
������������� ����� ������ ���� ����
������������� ��� � ���!��� ���� ����
������������� ������ ������� ��� ����
������������� ����� � ��� � �� �� � ��
*FM-200 is a Registered Trademark of Great Lakes Chemi-cal Corporation
93.1120.1 3/00 5M ©Kidde-Fenwal Inc. Printed in U.S.A. CP
1
Floor Mounted SphericalFM-200™ Agent Storage ContainerP/N 93-190000-00X
93.1225.1
Effective: August 1999
FEATURES• Designed for Under Floor Installation• Contains 10 to 15 lbs. of FM-200 Agent• UL Listed/FM Approved• DOT Shipping Container
DESCRIPTIONThis FM-200 spherical agent storage container is less than10 inches in height to fit under most raised floors and con-tains from 10 to 15 pounds of FM-200 superpressurized to360 psig with dry nitrogen.
Each assembly is equipped with pressure gauge, burst disctype discharge valve, replaceable initiator well, safety plug,screen assembly, cable assembly and mounting brackets.Each ASC has a boss-mounted check valve which acceptsand optional Pressure Switch (see Fenwal Data Sheet93.3119.0) and is used for recharging the container.
Initiator assemblies much be ordered for each container. SeeFenwal Data Sheet 93.1932.0 for ordering information
OPERATIONThe container much be securely mounted to a rigid surfacewith the valve horizontal/parallel to floor or down. Four holesin the mounting brackets are drilled to accept 5/16 inchmounting bolts. The centers of the mounting holes are lo-cated at the corners of a rectangle 6.38 inches wide by 8.38inches long.
MAINTENANCEThe following inspection and/or maintenance proceduresmuch be scheduled as listed below or performed upon oc-currence of any event which might affect the reliability of asystem.
A. QUARTERLY INSPECTION
1. Check the pressure gauges of each container. If the pres-sure is less than 325 psig at 70oF (22.9 Kg/CM2 at 21o
C), the container should be removed by qualified per-sonnel and carefully inspected, then reconditioned, re-charged or replaced as its condition warrants. Pressurewill vary with temperature. In the range of from 55 to85oF (12 to 29o C) this change is approximately 3 psi perdegree F (.38 kg/cm2/oC).
2. Check all component supporting hardware and tightenor repair as required.
3. Visually check all components for evidence of physicalabuse and take whatever action is indicated. Replacethe component if at all in doubt of its ability to performproperly.
B. SEMI-ANNUAL INSPECTION
Qualified personnel are to remove and weight all agent stor-age containers. Losses in net weight of agent much not ex-ceed 5 percent. Loss in pressure (adjusted for temperature)must not exceed 10 percent. Container and agent weightare marked on the inspection tag.
All outlet piping must be cleaned and free of dirt, chips, fil-ings and other foreign material that may become hazardousprojectiles or cause the system to become inoperative orineffective at the time of discharge.
NOTE: The safety plug shipped with this container shouldbe retained and secured to the container wheneverthe piping is removed from a charge container.Charged containers much have safety plug installedwhen removed from system for shipment. Observeproper handling procedures when installing or re-moving the initiator.
RECONDITIONINGAfter a system has been actuated, it is recommended thatthe local authorized Fenwal Distributor be contacted for re-conditioning the system. Refer to, “Filling and Recondition-ing Fenwal’s FM-200 Agent Storage Containers.”
The Reconditioning Kit for this unit is P/N 31-193005-001.This kit does not container the initiator, which must be or-dered separately.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
SPECIFICATIONSDiameter: 9-3/8” (239mm)
Overall Height: 9-7/8” (251mm)
Overall Length: 19-7/8” (495mm)
Empty Weight: 24 lbs. (10.8 Kg) Approx.
ARCHITECT/ENGINEER SPECIFICATIONSThe agent storage container shall be a Fenwal cylindrical(refillable) FM-200 container constructed of high strengthlow HSLA alloy steel. It shall consist of: Fill Valve, burst discvalve assembly, initiator, safety plug, screen assembly, cableassembly, integral supporting flanges, 0-700 psig pressuregauge and pressure switch assembly (optional). The con-tainers shall hold from 10 to 15 lbs. of FM-200 agent.
Container shall conform to all applicable specifications ofDepartment of Transportation, Underwriters Laboratories,Inc., and the Factory Mutual System.
The burst disc valve assembly shall be an integral part ofthe agent storage container and shall be operated by apply-ing electrical current to an initiator assembly which has anelectro-explosive device that provides, on demand, and in-stantaneous full bore release and discharge of the agent.
The releasing mechanism shall contain no moving parts.
Filled containers shall be super-pressurized with dry nitro-gen to 360 psig at 70oF to aid in rapid agent distribution,particularly at lower temperatures It shall automatically re-live between 850 to 100 psig in event of excessive pressurebuild up.
Releasing devices and connecting leads shall be completelysupervised
The container design shall permit on-site reconditioning andrefilling.
The integral assembly shall provide a means or mounting toa solid vertical or horizontal surface and shall withstand athrust of 1000 lbs. for 5 seconds in any direction.Tank construction per DOT-4BA-500.
93.1225.1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A. CP
*FM-200 is a Registered Trademark of Great Lakes Chemical Corporation.
1
FM-200® BOTTOM DISCHARGEAGENT STORAGE CONTAINERP/N 93-19204X-00X93.1920.1
Effective: September 1999
FEATURES� 150-350, 240-560, and 370-850-lb. Capacities� Electric Initiator Actuation� 3-inch Discharge Valve� Optional Liquid Level Indicator� Standard Low Pressure Supervisory
Pressure Switch� UL Listed� FM Approved
DESCRIPTIONFenwal FM-200 Bottom Discharge Agent Storage Contain-ers store FM-200 super-pressurized with dry nitrogen to 360psig (70oF). They are painted red and are equipped with a 3-inch burst disc type discharge valve, a replaceable initiatorwell, a screen assembly, pressure gauge, supervisory pres-sure switch with cable assembly, fill port, overpressure reliefvalve, safety cap, liquid level measuring device (optional)and lifting lugs. A 3-inch Flex Hose (P/N 29-117134-002) isavailable to facilitate piping connections. Initiator assembliesP/N 93-191001-001 must be ordered for each container.
OPERATIONThe agent storage container discharges when the initiator isactuated, causing the burst-disc valve to rupture.
INSTALLATIONThe container is installed in a vertical position with the valveassembly pointing up. Interconnection for discharge pipingis 3-inch NPT. A 3-inch flex hose is available to facilitateconnection between the container and discharge piping. A3-inch, 300-lb. malleable-iron threaded pipe union manufac-tured per ANSI B16.39 is required to mate the tank dischargeport to the flex-hose assembly.The container is secured in place by two mounting brackets(P/N 29-232334-00X) which are bolted together around thecontainer and affixed to a solid wall or a strut assembly. Two1/2-inch diameter bolts are required to secure the mountingbrackets to a vertical surface and two 1/2-inch diameter 9-inch long threaded rods are needed to hold the two mount-ing brackets together.After the container is securely mounted, it is connected todischarge piping per the system drawings. The initiator as-sembly is then installed.
MAINTENANCEAccording to NFPA standards the following inspection and/or maintenance procedure must be scheduled as listed be-low and performed upon the occurrence of any event whichmight affect the reliability of the system.
QUARTERLY INSPECTION1. Check the pressure gauges of each agent storage con-
tainer. If the pressure is less than 325 psig at 70oF (22.9kg/cm2 at 21oC), the container should be removed andcarefully inspected by certified personnel. It should thenbe reconditioned, recharged or replaced as it�s condi-tion indicates. Pressure varies with temperature. In therange of 55 to 85oF (12.8 to 29.4oC) change is approxi-mately 3 psi per degree F (0.397 kg/cm2 per degree C).
2. Check all component supporting hardware and tighten,repair, or replace as required.
3. Visually check all components for evidence of physicalabuse and take whatever action is required. Replaceany component if at all in doubt of its ability to performproperly.
2
SEMI-ANNUAL INSPECTIONQualified personnel are to determine the amount of agent inall containers. The optional liquid level indicator may be usedto measure agent supply and compare it to the original netweight which is marked on the container label. If the mea-sured net weight is less than 95% of the original charged netweight the container should be tested for leakage, rechargedand reinstalled.Inspect all piping, fittings and nozzles for looseness, dirt orother damage. All outlet piping must be clean and free ofdirt, chips, fillings and other foreign material that may causethe system to become inoperative or ineffective at the timeof discharge.
RECONDITIONINGAfter a system has been discharged, it is recommended thatthe local authorized Fenwal distributor be contacted to re-condition the system.The reconditioning kit for these containers is P/N 31-193017-001. The initiator, not included, is ordered separately.
ORDERING INFORMATIONKEY TO PART NUMBERS
93-19204X-00X1: w/o Liquid Level Indicator2: w/ Liquid Level Indicator
1: 5 ft. Volume (350 lb.)
2: 12 ft. Volume (850 lb.)
3
3
0: 8 ft. Volume (560 lb.)3
ACCESSORIES
X00-140291-39 X00-040291-39 X00-240291-39
)kcalB(tekcarBderiuqeRowT()reniatnoCrep
400-433232-92 200-433232-92 000-433232-92
ILLylbmessAepaT
498382
ILLylbmessAdoR)99.tpeS-erP(
210-990491-13 A/N
SPECIFICATIONSAGENT STORAGE CONTAINERS
X00-140291-39 X00-040291-39 X00-240291-39
egnaRlliF)ILLo/w.bl(
053-051 065-042 058-073
egnaRlliF)ILL/w.bl(
053-002 065-023 058-084
thgieH).ni(
75 5.85 5.06
retemaiD).ni(
61 02 42
emuloVlanretnI).tf.uc(
5 8 21
thgieWytpmE).bl(
052 053 084
mumixaMdaoLcitatS
006 019 0331
erutarepmeTegnaR
031ot23 o 45ot0(F o )C
feileRytefaSegnaRtsruB
GISP0001ot058
noitcurtsnoCnoitacificepS
005WB4-TOD
SUPERVISORY PRESSURE SWITCHES
300-945511-60 200-945511-60
lanoitpO/deppihS sreniatnoChtiwdeppihS lanoitpO
gnitaRtcatnoC CDV42@spmA2
noitarepOerusserPrednUnepO:taesolCstcatnoC(
)GISP51±,002
erusserPrednUdesolC:tanepOstcatnoC(
)GISP51±,002
3
NO LIFT NO LIFT
R R
F
B
C
INSPECTIONTAG
E
D
A
DIMENSIONAL INFORMATIONTANK AND BRACKET DIMENSIONS
������������� ������������� �������������
�� �������
���� � ������ ���� � ������ ��� � � ������
� �� ����� ���� �
� ����� ����� ��
� �� �
� �����
� �����
� ������
� ����� ����� �����
� ������ �����
� ������ ���� �����
� ����� ���� �����
BRACKET OUTLINE
G
H
J
I
AGENT STORAGE CONTAINER OUTLINE
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
93.1920.1 9/99 ©1999 Kidde Fenwal Inc. Printed in USA
ARCHITECTURAL AND ENGINEERINGSPECIFICATIONSThe FM-200 shall be stored in vertically mounted cylindricalcontainers with a 3-inch burst disc type discharge valve. Con-tainers shall be super-pressurized with dry nitrogen to 360 psigat 70oF. This container shall be Fenwal P/N 93-19204X-00X.Containers shall be U.L. Listed and FMRC Approved.Each agent storage container shall have a fill range of 150-350, 240-560, or 370-850 lbs. and be of a construction thatcomplies with DOT-4BW500.The agent storage container shall incorporate lifting lugs, over-pressure relief, 3-inch burst-disk type discharge valve, fill port,cable assembly, pressure gauge, supervisory pressure switch,liquid-level indicator (optional), and a safety cap. Electricaldevice�s connecting leads shall be completely supervised.
A compatible flex hose shall be available to facilitate instal-lation and connection to discharge piping.The container shall be secured in place by two opposingsteel mounting brackets. These brackets shall be FenwalP/N 29-232334-00X.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
Initiator Assembliesfor Fire Suppression SystemsP/N 93-199932-00X
93.1932.0
Effective: August 1999
93.1932.0 8/99 ©1999 Kidde-Fenwal Inc. Printed in USA
DESCRIPTIONInitiator assemblies are used in Fenwal Fire SuppressionSystem to rupture the burst disc valve in Fenwal agent stor-age containers.
WARNING!
The initiator is a Class “C” explosive. It must behandle and stored in accordance withappropriate local regulations governing Class“C” explosives. The local Fire Marshall should
CAUTION!
Never handle, transport, store, or install theinitiator assembly unless the shorting capsupplied with the assembly is properly securedto its threaded end. Safety glasses or a faceshield must be worn when handling thesedevices. Improper handling, misuse or abuse ofthis device can cause bodily injury.
OPERATIONThe initiator assembly is activated by an electrical current of2.0 amps. The assembly is destroyed by its operation andmust be replaced whenever a system is actuated.
INSTALLATIONThe initiator assembly is inserted into a well in the agentstorage container. Consult Fenwal Publication 93-FM200M-004 and/or 93-FM200M-003 for details on the proper instal-lation and testing procedures for this device.
MAINTENANCEThe initiator assembly should be stored in an area main-tained at 70-75oF (21-24oC). The storage area must be dryand secure from unauthorized access to these units. Thecombined shelf life and service life of an initiator assemblyshall not exceed seven (7) years. The service life varies withthe maximum temperature to which it is exposed for an ap-preciable length of time. See Table 1.
Table 1
.PMETDESOPXE.XAM EFILECIVRESSRAEY
Fo Co
08 72 5
001 83 3
021 94 2
041 06 1
At the end of it’s service life or seven years, whichever oc-curs first, in initiator assembly must be removed and de-stroyed in accordance with local regulations.
If an initiator is installed in an agent storage container thathas relieved as a result of an over-pressure, both the initia-tor and well assembly should be replaced regardless of theinitiator’s age. The initiator must be destroyed in accordancewith local regulations.
SPECIFICATIONS
.oNtraP
ylbmessAthgieW
"A".miD etairporppACSA
.zO .mG .nI mm
400-139991-13 21.1 0.23 96.2 3.86 100-102011-39100-202011-39100-302011-39100-402011-39100-052011-39100-352011-39100-153011-39100-353011-39
1
FM-200™ Pendant NozzlesP/N 93-1940.1
93.1940.1
Effective: August 1999
FEATURES• 180o and 360o Styles
• Six Pipe Sizes - 1/2” to 2” NPT
• Specially designed for FM-200
• Uniform Agent Distribution
• Custom Orifice Sizing
• UL Listed
• FMRC Approved
DESCRIPTIONThese nozzles are used in Fenwal FM-200 Fire Suppres-sion Systems to disperse FM-200 uniformly throughout thehazard area. Patterns direct discharged FM-200 parallel tothe ceiling. Nozzles are available to discharge in either 180o
or 360o patterns, depending on location within the hazardarea. A selection of orifices is available for each nozzle sizeto provide correct sizing for appropriate agent distribution.
Nozzles are constructed of brass, nozzle sizes are 1/2, 3/4,1/ 1-1/4, 1-1/2 and 2 inch NPT. See Ordering Information forsizes and part numbers.
DESIGN/INSTALLATIONThe nozzles are equipped with female National Pipe Threadsand provide and equal distribution of agent throughout theprotected area. Nozzles should be mounted in a downwardvertical position only. The Placement of the nozzles for ad-equate coverage to all portions of the hazard area is deter-mined by considering the indicated throw of each nozzle.When using large nozzles in an area where smaller nozzleshave a sufficient throw, care should be used to avoid anyunnecessary and unwanted turbulence.
ARCHITECT/ENGINEER SPECIFICATIONThis FM-200 Fire Suppression System shall use dischargenozzles that distributed the FM-200 uniformly throughout theprotected area. The nozzle shall be Fenwal P/N 93-1940XX-XXX.
360o Nozzle
180o Nozzle
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
063 o ELZZON
eziSepiP A B C D
)mm2.21("2/1 )mm57.13("052.1 )mm82.73("864.1 )mm91.94("739.1 )mm57.13("052.1
)mm50.91("4/3 )mm1.83("005.1 )mm80.04("875.1 )mm79.35("521.2 )mm1.83("005.1
)mm4.52("1 )mm54.44("057.1 )mm36.34("817.1 )mm23.06("573.2 )mm54.44("057.1
)mm57.13("4/1-1 )mm51.75("052.2 )mm35.94("059.1 )mm58.96("057.2 )mm51.75("052.2
)mm1.83("2/1-1 )mm05.36("005.2 )mm08.05("000.2 )mm95.47("739.2 )mm05.36("005.2
)mm8.05("2 )mm02.67("000.3 )mm73.25("260.2 )mm73.97("521.3 )mm02.67("000.3
081 o ELZZON
eziSepiP A B C D
)mm2.21("2/1 )mm57.13("052.1 )mm57.13("052.1 )mm48.24("786.1 )mm8.05("000.2
)mm50.91("4/3 )mm1.83("005.1 )mm29.43("573.1 )mm98.84("059.1 )mm13.85(692.2
)mm4.52("1 )mm54.44("057.1 )mm76.93("265.1 )33.65("812.2 )mm48.76("176.2
)mm57.13("4/1-1 )mm51.75("052.2 )mm54.44("057.1 )mm64.76("656.2 )mm55.28("052.3
)mm1.83("2/1-1 )mm05.36("005.2 )mm98.84("059.1 )mm39.47("059.2 )mm70.29("526.3
)mm8.05("2 )mm02.67("000.3 mm89.94("869.1 )mm20.37("578.2 )mm68.29("656.3
OUTLINE DIMENSIONS (INCHES)
93.1940.1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A.
*FM-200 is a Registered Trademark of Great Lakes Chemical Corporation
1
Pressure Switch AssemblyP/N 31-194133-0X
93.3119.0
Effective: January 2000
FEATURES� Easy Installation� Available Normally Open or Normally Closed� Explosion Resistant Cable Option
DESCRIPTIONThis pressure switch assembly mounts directly to a checkvalve on Fenwal spherical FM-200® agent storage contain-ers to trigger a TROUBLE condition when container pres-sure drops below 200 psig ±15 psi. Assemblies are availablewith normally open or normally closed contacts, and withstandard or explosion resistant cable assemblies.
OPERATIONNormally Open - The pressure switch contacts are closedwhen the container is pressurized in accordance with speci-fications. The contacts open when pressure drops below 200psig.Normally Closed - The pressure switch contacts are openwhen the container is pressurized in accordance with speci-fications. The contacts close when pressure drops below200 psig.
CAUTION!
Pressure in a normally filled container will dropbelow 200 psig at or below a temperature of+10oF (-12oC). Accordingly, this modification isnot recommended for low temperatureapplications.
INSTALLATIONTo install the pressure switch assembly, first unscrew theguard around the unused boss on the container and removethe safety plug from the check valve. Secure the check valvehex with a wrench to guard against loosening the check valve.Screw the pressure switch into the check valve 3 turns be-yond hand tight and then attach the cable assembly by screw-ing the housing over the threaded boss. Connect the cableassembly to the control unit in accordance with the systemschematic.
CAUTION!
Use wrench on check valve to avoid overtightening and when loosening components forremoval.
ORDERING INFORMATIONStandard Pressure Switch Assembly -Normally Open: P/N 31-194133-001
W/Explosion ResistantCable Assembly*: P/N 31-194133-002
Standard Pressure Switch Assembly -Normally Closed: P/N 31-194133-00
W/Explosion ResistantCable Assembly*: P/N 31-194133-004
SPECIFICATIONSCurrent Rating: 1 amp @ 120/240VAC,
Resistive 2 amps @ 24 VDCContacts Open: 200 ±15 psig*Explosion resistant cable assemblies for Class 1, Groups C andD; Class 2, Groups E, F and G locations.ARCHITECT/ENGINEER SPECIFICATIONSThe Pressure Switch Assembly shall be used with Fenwalspherical FM-200 agent storage containers to provide su-pervision of loss of pressure and/or extinguishing agent byindication of a Trouble signal at the Fenwal control unit. Itshall consist of a cable assembly and a pressure switch. Itshall be mounted directly on the container by means of a
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
boss-mounted check valve to facilitate removal of the pres-sure switch without losing FM-200 agent.Normally Open - The contacts of the switch shall be closedwhen the container is pressurized in accordance with speci-fications. The contacts will open when container pressuredrops below 200 ±15 psig. This switch shall not be used forapplications where ambient temperatures could drop to 10oF(12oC) or lower as this temperature will cause normal vesselpressure to drop below 200 psig.Normally Closed - The contacts of the switch shall be openwhen the container is pressurized in accordance with speci-fications. The contacts will close when container pressuredrops below 200 ±15 psig. This switch shall not be used forapplications where ambient temperatures could drop to 10oF(12oC) or lower as this temperature will cause normal vesselpressure to drop below 200 psig.The explosion resistant cable assembly shall be designedfor hazardous locations, Class 1, Groups C and D, Class 2,Groups E, F and G. Its contacts shall be rated at 1 Amp at120/240VAC and 2 Amps at 24VDC.
93.3119.9 1/00 ©2000 Kidde-Fenwal, Inc. Printed in U.S.A.
Fenwal is a registered trademark of Kidde-Fenwal, Inc.FM200 is a registered trademark of Great Lakes Chemical Corporation
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
Wall Mounting BracketP/N 31-194019-001
93.3119.1
Effective: August 1999
DESCRIPTIONThe Wall Bracket shown is used to mount Fenwal ModularSpherical FM-200™ Agent Storage containers.
INSTALLATIONThe bracket may be mounted with in the position shown orinverted. Six bolt holes are provided for secure mounting,using 1/2 in. (12.7 mm) hardware. The bracket also may bewelded to stanchions, beams or bulkheads. The mountingholes bust be laid out to the dimensions shown below to atolerance of 1/32 in. (.79 mm) on each hole location. Mountagainst a rigid structural member or wall.
93.3119.1 8/99 ©Kidde-Fenwal, Inc. Printed in U.S.A. CP
Manufactured from0.250 in. (6.4mm) stock
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must be prop-erly applied to work correctly.If you need more information on this product, or if you have a particular problem or question,contact KIDDE-FENWAL INC., Ashland, MA 01721. Telephone: (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
Floor Mounting BracketP/N 31-194023-002
93.3119.2
Effective: August 1999
93.3119.2 8/99 ©1999 Kidde-Fenwal Inc. Printed in USA
DESCRIPTIONThe floor mounting bracket shown is used to mount FenwalModular Spherical FM-200™ Agent Storage Containers.
INSTALLATIONThe bracket is fastened to the floor through six 0.625 in.(15.9 mm) holes. Use 1/2 inch (12.7 mm) lag screws or boltswith lockwashers to prevent loosening. The agent storagecontainer is then mounted on top of the bracket with thevalve extending down through the 4 inch (102 mm) hole.
*Fm-200 is a Registered Trademark of Great Lakes Chemi-cal Corporation
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective January 2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
F-93-2010
F-93-2010 ©2000 Kidde-Fenwal, Inc. Printed in U.S.A.
• For use with UL Listed, ULC Listed & FMRC approved systems • See Kidde Manual 90-FM200M-021 for USCG Approval
Features
Cylinder and Valve Assemblies 10LB (4.5 KG) - 70LB (31.7 KG) Capacity, Vertical Mount Only
MATERIALSVALVE BODY: BRASSCYLINDER: STEEL, PAINTED RED
rebmuNtraP eziS.lyCsnoisnemiD
*A *B *C
100-010001-39 .sbL01 70.7 43.31 03.71
100-020001-39 .sbL02 70.7 10.12 79.42
100-040001-39 .sbL04 00.9 08.22 67.62
100-070001-39 .sbL07 00.9 78.43 38.83
.sehcninierasnoisnemiD*
ORDERING INFORMATION
P/N: 90-10000X0-001
CYLINDER VALVE
SAFETY CAP
SYPHON TUBE
CYLINDER
A
B
C
NOTES:1. THE SAFETY CAP MUST BE INSTALLED ON THE VALVEOUTLET AT ALL TIMES EXCEPT WHEN THE CYLINDERS ARECONNECTED TO THE SYSTEM PIPING OR BEING FILLED. THESAFETY CAP MUST NOT BE REMOVED FROM ITS CHAIN.2. SEE F-90-2070 FOR ADDITIONAL INFORMATION.3. CYLINDERS ARE VERTICAL MOUNT ONLY.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
F-93-2020
F-93-2020 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
• For use with UL listed, ULC listed & FMRC approved systems
ORDERING INFORMATION
Cylinder and Valve Assemblies 10 LB. (4.5 KG) - 70LB. (31.7 KG) Capacity, Horizontal Mount Only,
MATERIALSVALVE BODY: BRASSCYLINDER: STEEL, PAINTED RED
rebmuNtraP eziS.lyCsnoisnemiD
*A *B *C
100-110001-09 .sbL01 70.7 43.31 03.71
100-120001-09 .sbL02 70.7 10.12 79.42
100-140001-09 .sbL04 00.9 08.22 67.62
100-170001-09 .sbL07 00.9 78.43 38.83
.sehcninierasnoisnemiD*
P/N: 90-1000X1-001
NOTES:1. THE SAFETY CAP MUST BE INSTALLED ON THE VALVEOUTLET AT ALL TIMES EXCEPT WHEN THE CYLINDERS ARECONNECTED TO THE SYSTEM PIPING OR BEING FILLED. THESAFETY CAP MUST NOT BE REMOVED FROM ITS CHAIN.2. SEE F-90-2070 FOR ADDITIONAL INFORMATION.3. CYLINDERS ARE HORIZONTAL MOUNT ONLY.4. NOT FOR USE WITH ENGINEERED SYSTEMS
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
Cylinder and Valve Assembly 125 LB (56.7 KG) Capacity
F-93-2030
ORDERING INFORMATION
MATERIALSVALVE BODY: BRASSCYLINDER: STEEL, PAINTED RED
NOTES:1. THE SAFETY CAP MUST BE INSTALLED ON THE VALVEOUTLET AT ALL TIMES EXCEPT WHEN THE CYLINDERSARE CONNECTED TO THE SYSTEM PIPING OR BEINGFILLED. THE SAFETY CAP MUST NOT BE REMOVED FROMITS CHAIN.2. SEE F-93-2070 FOR ADDITIONAL INFORMATION.
P/N: 93-10012X-001
CYLINDER VALVE
LIQUID LEVEL INDICATOR
LIFTING LUGS
CYLINDERNAMEPLATE
12,75” DIA
CYLINDER
VALVE OUTLET
30°
PLAN VIEW
SAFETY CAP
35.93” 31.97”
F-93-2030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
N/P NOITPIRCSED
100-121001-39100-521001-39
ILL/WDTS
����������������� ������� ���� ��� ������ ���� ��������������������� ���������� ��� ���!������� ������ ��"�#������!������� �����"�������"�� ��������� ��"�������!�� ������������� ���� �������"�!������������� �������� ����� ��� �� �������� ��"��� ����� �������$����� ���" ��"������������������ �����������%��&'()'*������� ���+,&-.�--'�)&&&
�������������� ������������������������������ �����
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
��������� ���� ���� ��� ��� ��� �� ���� ��� � �� ����� ������� � ������
���������
��/0�)&1&������������������'///����������2�����"������3���������4�5���
������������ ����� ����������������������������
������������������ �������������������������������
��������� ��� �������
�������������������������������� �������� ������������������������������������� �� ��������� ������� ����������������������� ������� ����������������������������� ����������������������� ����������������!���������� ���� ������� �
������������ �
N/P NOITPIRCSED
101-002001-39101-102001-39
DTSILL/W
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2050
F-93-2050 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSVALVE BODY: BRASSCYLINDER: STEEL, PAINTED RED
Cylinder and Valve Assembly 350 LB (158.7 KG) Capacity
NOTES:1. THE SAFTY CAP MUST BE INSTALLED ON THEVALVE OUTLET AT ALL TIMES EXCEPT WHEN THECYLINDERS ARE CONNECTED TO THE SYSTEMPIPING OR BEING FILLED. THE SAFETY CAPMUST NOT BE REMOVED FROM ITS CHAIN.2. SEE F-93-2070 FOR ADDITIONAL INFORMATION.
ORDERING INFORMATION
CYLINDER VALVE
LIQUID LEVEL INDICATOR
LIFTING LUGS
CYLINDERNAMEPLATE
16.00" DIA
CYLINDER
VALVE OUTLET
30°
PLAN VIEW
SAFETY CAP
58.36" 53.14"
P/N: 93-10035X-001
N/P NOITPIRCSED
100-053001-39100-153001-39
DTSILL/W
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2060
F-93-2060 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSVALVE BODY: BRASSCYLINDER; STEEL, PAINTED RED
Cylinder and Valve Assembly 600 LB (272.1 KG) Capacity
CYLINDER VALVE
LIQUID LEVEL INDICATOR
LIFTING LUGS
CYLINDERNAMEPLATE
22.00" DIA
CYLINDER
VALVE OUTLET
30°
PLAN VIEW
SAFETY CAP
56.72" 50.51"
NOTES:1. THE SAFETY CAP MUST BE INSTALLED ON THEVALVE OUTLET AT ALL TIMES EXCEPT WHEN THECYLINDERS ARE CONNECTED TO THE SYSTEMPIPING OR BEING FILLED. THE SAFETY CAPMUST NOT BE REMOVED FROM ITS CHAIN.2. SEE F-93-2070 FOR ADDITIONAL INFORMATION.
ORDERING INFORMATION
P/N: 93-10060X-001
N/P NOITPIRCSED
100-006001-39100-106001-39
DTSILL/W
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2070
F-93-2070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
Cylinder Data
(Sheet 1 of 2)
ENGINEERED SYSTEMS CYLINDER DATA
NOTE: ENGINEERED SYSTEMS HAVE A FILL DENSITY RANGE OF 30 LB/CU FT TO 70 LB/CU FT
TRAPREBMUN
EGNARLLIFYTPMETHGIEW
THGIEWSSORG
ILL/WTHGIEH RETEMAID EMULOV
LLIFNIM LLIFXAM
BL GK BL GK BL GK BL GK NI MC NI MC TF 3 M3
100-010001-39 01-5 5-3 52 11 03 41 53 61 ON 03.71 44 70.7 81 761.0 7400.0
100-020001-39 02-9 9-4 13 41 04 81 15 32 ON 79.42 46 70.7 81 682.0 1800.0
100-040001-39 04-71 81-8 83 71 55 52 87 53 ON 67.62 86 00.9 32 275.0 2610.0
100-070001-39 07-03 23-41 25 42 28 83 321 65 ON 38.83 99 00.9 32 000.1 3820.0
100-121001-39 521-45 75-52 89 54 251 96 322 101 SEY 39.53 29 57.21 33 887.1 6050.0
100-521001-39 521-45 75-52 89 54 251 96 322 101 ON 39.53 29 57.21 33 887.1 6050.0
100-002001-39 002-68 19-93 931 36 522 201 143 451 ON 53.05 821 06.31 53 958.2 0180.0
100-102001-39 002-68 19-93 141 46 722 301 343 551 SEY 53.05 821 06.31 53 958.2 0180.0
101-002001-39 002-68 19-93 331 06 912 001 333 151 ON 57.25 431 57.21 33 958.2 0180.0
101-102001-39 002-68 19-93 331 06 912 001 333 151 SEY 57.25 431 57.21 33 958.2 0180.0
100-053001-39 053-051 951-86 102 19 153 951 555 052 ON 63.85 941 00.61 14 000.5 6141.0
100-153001-39 053-051 951-86 302 29 143 061 755 152 SEY 63.85 941 00.61 14 000.5 6141.0
100-006001-39 006-852 272-411 533 251 395 072 539 524 ON 27.65 541 00.22 65 275.8 7242.0
100-106001-39 006-852 272-411 733 351 595 072 739 624 SEY 27.65 541 00.22 65 275.8 7232.0
Effective June 1999FM-200 COMPONENT DESCRIPTION
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2070
(Sheet 2 of 2)
Cylinder Data
MODULAR SYSTEMS CYLINDER DATA
NOTE: MODULAR SYSTEMS HAVE A FILL DENSITY RANGE OF 40 LB/CU FT TO 70 LB/CU FT* Fill density range of 40lb/cu ft to 58.3 lb/cu ft for modular balanced systems only
F-93-2070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
TRAPREBMUN
EGNARLLIFYTPMETHGIEW
THGIEWSSORG
ILL/WTHGIEH RETEMAID EMULOV
LLIFNIM LLIFXAM
BL GK BL GK BL GK BL GK NI MC NI MC TF 3 M3
100-X10001-39 01-6 5-3 52 11 13 41 53 61 ON 03.71 44 70.7 81 761.0 7400.0
100-X20001-39 02-11 9-5 13 41 24 91 15 32 ON 79.42 46 70.7 81 682.0 1800.0
100-X40001-39 04-32 81-01 83 71 16 72 87 53 ON 67.62 46 00.9 32 275.0 2610.0
100-X70001-39 07-14 23-91 25 42 49 34 321 65 ON 38.83 99 00.9 32 000.1 3820.0
100-121001-39 521-17 75-23 89 54 961 77 322 101 SEY 39.53 29 57.21 33 887.1 6050.0
100-521001-39 521-17 75-23 89 54 961 77 322 101 ON 39.53 29 57.21 33 887.1 6050.0
100-002001-39 002-621 19-65 931 36 562 021 933 451 ON 53.05 821 06.31 53 958.2 0180.0
100-102001-39 002-621 19-75 141 46 762 121 143 551 SEY 53.05 821 06.31 53 958.2 0180.0
101-002001-39 002-621 19-75 331 06 952 811 333 151 ON 57.25 431 57.21 33 958.2 0180.0
101-102001-39 002-621 19-75 331 06 952 811 333 151 SEY 57.25 431 57.21 33 958.2 0180.0
100-053001-39 053-102 951-19 102 19 604 281 555 052 ON 63.85 941 00.61 14 000.5 6141.0
100-153001-39 053-102 951-19 302 29 804 381 755 152 SEY 63.85 951 00.61 14 000.5 6141.0
100-006001-39* 005-153 722-951 533 251 686 213 538 083 ON 27.65 541 00.22 65 275.8 7242.0
100-106001-39* 005-153 722-951 733 351 886 313 738 083 SEY 27.65 541 00.22 65 275.8 0742.0
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2080
Cylinder Valve
WORKING PRESSURE: 360-609 PSIGPROOF PRESSURE: 1000 PSIGBURST PRESSURE 2000 PSIGTEMPERATURE RANGE: 32o TO 130o F
MATERIALSVALVE BODY: BRASSPISTON: BRASSFINISH: NATURALSEAT: RUBBER
EQUIVALENT LENGTH OF SCHEDULE 40 PIPE:1-1/2" : 16.7' OF 1-1/4"2" : 28.0' OF 2"2½" : 31.5' of 2½"
P/N: 93-1X0000-000
F-93-2080 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
24 LB
15 LB
9.9 LB
2-1/2"
2"
1-1/2"
VALVE SIZE
SAFETY
DISCHARGE
OUTLET PORT
CAP
93-160000-000
93-150000-000
93-140000-000
PART NO.
F: WEIGHT
E: SAFETY DISC REPL. P/N
D: SAFETY DISC RELIEF PRESSURE
6.61"
6.28"
5.22"
6.30"
5.32"
4.83"
10.04"
8.80"
7.63"
A B
C
C
SEAT
798-972 PSI
798-972 PSI
754-900 PSI
D
264929
264925
242461
E F
CONNECTION
PRESSURE
SUPERVISORY
SWITCH
PISTON
SAFETY CHAIN
VENT HOLE
PRESSURE
PROTECTION
CAP
GAGE
VALVE CORE, PILOT
CONNECTION
ACTUATION PORT
CONTROL HEAD
B
BODY
1/8" NPTACTUATION PORT
SAFETY
SLAVE CYLINDER
A
DISC
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2090
Cylinder Supervisory Pressure Switch
ELECTRICAL RATING:120/240/277 V-AC 375 VA28V-AC/DC 2 AMPS
NEMA 1 ENCLOSUREACTUATION PRESSURE: 320 PSI +/- 10 PSIDEACTUATION PRESSURE: 250 PSI +/- 10 PSIOPERATING TEMPERATURE RANGE: +32oF TO +130oFOPERATION EXAMPLE: "NORMALLY CLOSED" DEVICECONTACTS ARE OPEN UNDER PRESSUREPRESSURE LOSS GREATER THAN 40 PSI WILL CAUSECONTACTS TO CLOSE P/N: 8787090X
NOITAREPO N/P
NEPO(DESOLCYLLAMRON)ERUSSERPREDNU
00907878
DESOLC(NEPOYLLAMRON)ERUSSERPREDNU
10907878
ORDERING INFORMATION
WITH VALVE CORE DEFLECTOR
1/4" SAE FEMALE PORT FITTING
1.56”
.47" CONDUIT ENTRY HOLE
2.12"
1.56"
2.93”
F-93-2090 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2100
Valve Outlet Adapters
F-93-2100 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
NOTE: FOR DIRECT CONNECTION OF CYLINDER VALVE TODISTRIBUTION PIPING.MATERIAL: BRASS
P/N: 28390X
CD
A (SYSTEM PIPE CONNECTION)
B (VALVE OUTLET CONNECTION)
ORDERING INFORMATION
.ONTRAP EZIS *A *B *C *D
409382 2/1-1 TPN"2/1-1478.1JNU21
96.2 XEH05.2
509382 2 TPN"2005.2JNU21
21.3 XEH00.3
609382 2/1-2 TPN"2/1-2000.3JNU21
00.3 XEH57.3
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2110
Liquid Level Indicator
F-93-2110 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
ORDERING INFORMATION
REDNILYC N/PEPATILL
521 186532
002 498382
053 498382
006 498382
CAP
GRADUATED TAPE
O-RINGP/N: WK-566109-160
BRASS TUBE
FM-200
EDGE OF FITTING
BRASS TUBE
TAPE INSIDE
READING TAKEN AT TOP
P/N: SEE TABLE
TAPE IN MAGNETIC INTERLOCK
POSITION READY TO TAKE
READING.
CYLINDER
LIQUID LEVELMAGNETIC END OFTAPE ENGAGESIN MAGNETIC FIELDOF FLOAT WHENTAPE IS PULLEDUP TO TAKE READING
MAGNET EMBEDDED
FLOAT - FLOATS ON SURFACE
FM-200
IN FLOAT
OF LIQUID FM-200.
FREE TO MOVE UP OR DOWN
OUTSIDE OF BRASS TUBE.
RETAINER - FLOAT RESTSHERE WHEN CYLINDER
IS EMPTY.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2120
Flexible Discharge Hoses
F-93-2120 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MINIMUM BURSTING PRESSURE: 2000 PSIWORKING PRESSURE: 500 PSIPROOF PRESSURE: 1000 PSI
MATERIALSHOSE: REINFORCED RUBBER HOSEFITTING: BRASS
A
HOSE
SYSTEM PIPE CONNECTION,
MALE NPT THREAD
FM-200 CYLINDER VALVE
CONNECTION, SWIVEL NUT
.ONTRAP TPNELAM A SUIDARDEB.NIM
898382 2/1-1 42 5.01
998382 2 13 5.31
009382 2/1-2 84 5.22
ORDERING INFORMATION
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2130
Manifold El-Check
F-93-2130 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
A
B
VALVE BODY
C
C CHECK
FOR CONNECTION TO
ARROW INDICATES
SYSTEM MANIFOLD
FLOW DIRECTION
PART NO. SIZE A* B* C*
877690 2 3.93 4.88 2” NPT
2-1/2” NPT5.764.692-1/2878743
NOTE: EL-CHECKS ARE TO BE INSTALLED AT SYSTEMMANIFOLD IN VERTICAL DIRECTION AS SHOWN
NOTE: DO NOT USE AS A MAIN/RESERVE CHECKVALVE WITH MORE THAN 1 MAIN/RESERVE CYLINDER
MATERIALSVALVE BODY: ZINC PLATED STEELCHECK: STAINLESS STEELSEAT: NITRILE RUBBER
*DIMENSIONS ARE IN INCHES
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2131
Typical Installation of El-Check
F-93-2131 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
NOTES: INSTALL EL-CHECKS SO THAT ARROW IS INDIRECTION OF FLOW
EL-CHECK MAY BE ADJUSTED AS SHOWN TO OB-TAIN A SMOOTH RADIUS IN FLEXIBLE DISCHARGEHOSE.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2140
360 Degree Pendant Nozzle
F-93-2140 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
A SELECTION OF ORIFICES ARE AVAILABLE FOREACH NOZZLE SIZE. CONSULT YOUR FENWALDESIGN AND INSTALLATION MANUAL FOR DETAILS P/N: 93-19402X-XXX
2.500" (63.50mm)
1.250" (31.75mm)
1.500" (38.10mm)
1.750" (44.45mm)
2.250" (57.15mm)
3.000" (76.20mm)
Pipe Size
2.250" (57.15mm)
1.750" (44.45mm)
3.000" (76.20mm)
1.250" (31.75mm)
2.250" (63.50mm)
1.500" (38.10mm)
2" (50.80mm)
1-1/2" (38.10mm)
1" (25.40mm)
1-1/4" (31.75mm)
3/4" (19.05mm)
1/2" (12.20mm)
2.937" (74.59mm)
1.937" (49.19mm)
2.125" (53.97mm)
2.375" (60.32mm)
2.750" (69.85mm)
3.125" (79.37mm)
2.000" (50.80mm)
1.950" (49.53mm)
1.718" (43.63mm)
1.578" (40.08mm)
1.468" (37.28mm)
2.062" (52.37mm)
A
A
360 DEGREE NOZZLE
B C
C
D
FE D
METAL STAMP X-XXX (HOLE DIA. SIZE)
IN .093 ± .031 HIGH
CHARACTERS ON ANY FLAT
B
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-2150
180 Degree Pendant Nozzle
F-93-2150 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
A SELECTION OF ORIFICES ARE AVAILABLE FOREACH NOZZLE SIZE. CONSULT YOUR FENWALDESIGN AND INSTALLATION MANUAL FOR DETAILS
P/N: 93-19401X-XXX
2.875" (73.02mm)
2.656" (67.46mm)
2.218" (56.33mm)
1.950" (48.89mm)
1.687" (42.84mm)
2.950" (74.93mm)
Pipe Size
1/2" (12.20mm)
3/4" (19.05mm)
1-1/4" (31.75mm)
1" (25.40mm)
1-1/2" (38.10mm)
2" (50.80mm)
1.250" (31.75mm)
1.375" (34.92mm)
1.562" (39.67mm)
1.750" (44.45mm)
1.968" (49.98mm)
1.950" (48.89mm)
1.500" (38.10mm)
2.250" (63.50mm)
1.250" (31.75mm)
3.000" (76.20mm)
1.750" (44.45mm)
2.250" (57.15mm)
A
180 DEGREE NOZZLE
A
30° FEN
WA
L
B C
60°
B
IN .093 ±.031 HIGH CHARACTERS
METAL STAMP X-XXX (DASH NO.)
ON ANY FLAT
C
D
3.656" (92.86mm)
3.250" (82.55mm)
2.671" (67.84mm)
2.296" (58.31mm)
2.000" (50.80mm)
3.625" (92.07mm)
D
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5010
Pressure Operated Control Head
F-93-5010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
P/N: 878737MATERIALBODY: RETAINING NUT, AND PISTON: BRASS
1.250-18
UNEF-3B
SWIVEL NUT
PISTON
1/8"-27 NPT
PRESSURE INLET
SETOPERATED
2.19"
1.50" HEX
1.00" HEX
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5020
Pressure Operated Control Head, Stackable
F-93-5020 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALBODY, RETAINER CAP, PISTON & MTG. NUT: BRASS P/N: 878750
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5030
Lever or Pressure Operated Control Head
F-93-5030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSLEVER: STAINLESS STEELBODY & PISTON: BRASS
P/N: 878751
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5040
Pilot Actuation Fittings
F-93-5040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIAL: BRASS
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5050
Nitrogen Pilot Cylinder, Bracket, and Adapter
F-93-5050 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSCYLINDER: STEEL, PAINTED BLACKVALVE: BRASSBRACKET: STEEL, PAINTED BLACKADAPTER: BRASS
GAUGE
PLUG OUTLET PORT-1/8" NPT FEMALE,
ATTACH ADAPTER HERE
SAFETY
OUTLET
1/8" NPT
MALE
5/16"-TUBING MALE
ADAPTER
P/N WK-699205-010
1-1/4"-18 NF-3
FOR CONTROL HEAD CONNECTION
CYLINDER P/N 877940-000
BRACKET P/N 877845-000
SPECIFICATIONS
CYLINDER CAPACITY-108 in (1770 CM )SAFETY OUTLET BURST RANGE: 2650-3000 PSI (183-207 BARS) AT 70°F (20°C)NITROGEN-BB-n-411 b, GRADE A, TYPE I1800 PSI (124 BARS) AT 70°F (20°C)
16"
3.56"
(406mm)
(90mm)
33
N/P noitpircseD
049778 dradnatS
100-377921-60desolCyllamroN
erusserPrednUnepO
200-377921-60nepOyllamroN
erusserPrednUdesolC
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5070
1/4" Flexible Actuation Hoses
F-93-5070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSHOSE: WIRE BRAIDED, TEFLON LINING (CRES T304)COUPLINGS: BRASSMINIMUM BURST PRESSURE: 12,000 PSIGOPERATING PRESSURE: 3000 PSIGTEST PRESSURE: 4500 PSIGMINIMUM BEND RADIUS 2.5"
P/N: 26498x
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5080
Master Cylinder Adapter Kit
F-93-5080 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSADAPTER & CAP: BRASSCHAIN: STAINLESS STEELLABEL: MYLAR
P/N: 844895
1.42"
1/4" MALE NPT X 5/16" TUBING
PROTECTION CAP
CAUTION
INSTALL CAP
WHEN
NOT IN
USE
LABEL
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5090
1/4" Check Valve
F-93-5090 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
WORKING PRESSURE: 0-1800 PSI (0-124 BAR)MINIMUM BURSTING PRESSURE: 5000 PSI (345 BAR)
MATERIAL: BRASS
NOTE: INSTALL VALVE WITH ARROW POINTING INDIRECTION OF FLOW.
P/N: 264985
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
F-93-5100
3/8" Check Valve
F-93-5100 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
TECHNICAL DATAWORKING PRESSURE: 0 TO 5000 PSI (0 TO 345 BAR)PROOF PRESSURE: 10,000 PSI (690 BAR)CRACKING PRESSURE: 2 TO 4 PSI (.14 TO .28 BAR)OPERATING TEMPERATURE: -40F TO 250F (-40F TO 121C)
MATERIALSBODY: BRASSSEAL: BUNA-N
1.00"2.35"
(60 MM) (25 MM)
HEX
3"
8NPT BOTH ENDS
INSTALL VALVE WITH ARROW POINTING
IN DIRECTION OF FLOW.
P/N: 261193
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5110
Check Valves, 1/2" Thru 2"
F-93-5110 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
VALVE MUST BE INSTALLED WITH ARROW POINTING INDIRECTION OF FLOW
MATERIAL: BRASS
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5120
Check Valves, 2-1/2" & 3"
F-93-5120 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
VALVE MUST BE INSTALLED WITH ARROW POINT-ING IN THE DIRECTION OF FLOW
MATERIALSVALVE BODY: BRASSGASKET: IRONFLANGES, BOLTS, & NUTS: STEEL
P/N: 870100
EGNALFKCENGNIDLEW
EVLAVKCEHCEZIS
N/PYTQ
DERIUQER
"2/1-2 617362 2
"3 0021-0186 2
ORDERING INFORMATION
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
F-93-5130
Stop (Directional) Valves, 1/2" Thru 2"
F-93-5130 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
NOTES:1. VALVE MUST BE INSTALLED WITH ARROW POINTING INDIRECTION OF FLOW.2. VALVE MAY BE INSTALLED IN HORIZONTAL OR VERTI-CAL PIPE RUN.
MATERIALSBODY: BRASS
B
C
A
INLETVALVE SIZE
OUTLET
(NPT)
BOTH ENDS
1-1/4 - 18 NF-3 FOR CONTROL HEAD CONNECTION
TRAPREBMUN
EZISEVLAVTPN
A B C
NI MM NI MM NI MM
320078220078221078230078321078940078
"2/1"4/3
"1"4/1-1"2/1-1
"2
57.352.405.505.505.705.7
59801041041191191
05.218.226.326.357.457.4
46172929121121
86.486.578.678.634.834.8
911441571571412412
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
F-93-5140
Stop (Directional) Valves, 2-1/2" & 3"
F-93-5140 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
VALVE MUST BE INSTALLED WITH ARROW POINTINGIN DIRECTION OF FLOW
MATERIALSVALVE BODY: BRASSGASKET: IRONFLANGES, BOLTS, & NUTS: STEEL
P/N: 890010
ORDERING INFORMATION
CONNECTION
FOR CONTROL HEAD
1 - 1/4” -18 NF-3 MALE
3/4” X 4 - 1/2”
OUTLET
(249mm)
9.81"INLET
10.5"
(267mm)
3/4” HEX NUT
P/N 1523-0800
16 REQUIRED
GASKETP/N 200973
2 REQUIRED
WELDING NECK FLANGEP/N 263716
(114mm) LG.HEX BOLT
P/N 1966-4872-16 REQUIRED
SIDE VIEW
WITHOUT
ASSEMBLED FLANGE
FLANGE - 6.62" (168mm)
BOLT CIRCLE
8.25" (210mm) DIA.
EVLAVKCEHCEZIS
N/PKCENGNIDLEW
N/PEGNALF)DERIUQER2(
"2/1-2 010098 617362
"3 010098 0021-0186
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
F-93-5150
4" Stop (Directional) Valve
F-93-5150 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
VALVE MUST BE INSTALLED WITH ARROW POINTING INDIRECTION OF FLOWMATERIALS
VALVE BODY: BRASSGASKET: IRONFLANGES, BOLTS, & NUTS: STEEL
P/N: 890208
10.75" (273mm) DIA.
BOLT CIRCLE
FLANGE - 8.50" (216mm)
ASSEMBLED FLANGE
WITHOUT
SIDE VIEW
P/N 1966-5680-16 REQUIRED
HEX BOLT7/8” X 5" (127mm) LG.
2 REQUIRED
P/N 6810-1600WELDING NECK FLANGE
2 REQUIRED
P/N 200150GASKET
16 REQUIRED
P/N 1523-5600
7/8” HEX NUT
(308mm)
12.12"
INLET
4"
11.06"
(281mm)
OUTLET
1- 1/4” -18 NF-3 MALE
FOR CONTROL HEAD
CONNECTION
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5160
Discharge Indicators
F-93-5160 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSBODY-967082: BRASSBODY-875553: ALUMINUMCAPS: CLEAR CELLULOSE ACETATE
EZIS N/P
)SSARB("4/3 280769
)LA("2/1 355578
ORDERING INFORMATION
NORMAL
DISCHARGE
POSITION
INDICATION
POSITION
CAP
STEM
3.25"
(83mm)
BODY
NPT MALE
1.12"(29mm) HEX
ACROSS FLATS
3"
4
P/N 967082
2.62"
(67mm)
P/N 875553BODY
NPT MALE
0.93"(24mm) HEX
ACROSS FLATS
1"2
POSITION
INDICATION
POSITION
DISCHARGE
NORMAL
STEM-RED
CAP
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5170
Safety Outlets
F-93-5170 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSBODY & RETAINING NUT: BRASSSEAL WIRE: COPPER & LEAD
BODY
SEAL WIRE
SAFETY DISC
RETAINING NUT
NPT MALE
1.78"
(45mm)
3"4
PART
NUMBERAGENT
PRESSURE RELIEF
OPERATES AT
PSI BAR
803242 2400-2800 166-193
844346 FM-200 750-900 52-62
N2/CO2
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5180
Pressure Operated Switch
F-93-5180 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
P/N: 486536
NOTES:1. SWITCH MAY BE MOUNTED IN ANY POSITIONBUT PREFERRED INSTALLATION IS UPRIGHT ASSHOWN.2. ANY LOAD CONNECTION TO THE SWITCH MUSTNOT EXCEED SWITCH RATING AND SHALL UTILIZEA SUITABLE PROTECTION DEVICE (ie. CIRCUITBREAKER, FUSE)3. CONTACT RATINGS (3PDT)15 AMP @ 125 VAC10 AMP @ 250 VAC3/4 HP @ 250 VAC1, 2 OR 3 PHASE
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5190
Pressure Operated Switch, Explosion Proof
F-93-5190 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
NOTES:1. TOGGLE SWITCH MAY BE MOUNTED IN BASEFOR EITHER N.O. TO N.C. OR N.C. TO N.O. CON-TACT TRANSFER UPON OPERATION. ILLUSTRATIONSHOWS POSITION OF TOGLE WHEN SWITCH IS INSET POSITION.2. ANY LOAD CONNECTED TO THE SWITCH MUSTNOT EXCEED SWITCH RATING AND SHALL UTILIZEA SUITABLE PROTECTION DEVICE. (ie. CIRCUITBREAKER, FUSE)
3. REMOVE OPERATING HEAD TO MAKE ELECTRI-CAL CONNECTIONS TO TOGGLE SWITCH. WHENREPLACING OPERATING HEAD, ENSURE THATTOGGLE ENGAGES CLUTCH. TIGHTEN COVERSCREWS SECURELY.4. CLASS I, GROUP D CAUTION: TO PREVENTIGNITION OF HAZARDOUS ATMOSPHERES,DISCONNECT THE DEVICE FROM THE SUPPLYCIRCUIT BEFORE OPENING. KEEP ASSEMBLYTIGHTLY CLOSED WHEN IN OPERATION.
P/N: 981332
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5200
Pressure Trip
F-93-5200 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MAXIMUM LOAD ON RING: 100 LBS. (45 KG)MINIMUM NOMINAL OPERATING PRESSURE:50 PSI (3.5 BAR)MATERIALS
BODY, BRACKET, AND PISTON: BRASSGUARD, STEM, RING AND SPRING: STAINLESSSTEEL
P/N: 874290
1.37"
SPRING
PISTON
2.50"
(64mm)
(41mm)
HEX
PRESSURE INLET½”NPT - FEMALE
1.62"
(41mm)
BODY
RING
STEM
GUARD BRACKET WITH
.375"(10mm) DIA.
MOUNTING HOLE
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-5201
Pressure Trip Applications - Installation Detail
F-93-5201 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-6010
Lever Operated Control Head
F-93-6010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSLEVER: STAINLESS STEELBODY: BRASS
P/N: 870652
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-6020
Cable Operated Control Head
F-93-6020 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
P/N: 979469
LOCAL MANUAL RELEASE LEVER
SEAL WIRE
LOCKING PIN
DIRECTION OF
PULLTHREADED NUT -
3/8" NPS FOR PIPE
1/16" CABLE
3/8" PIPE (OR 1/2" EMTWITH ADAPTER P/N
843837 - SEE F-93-6120)SWIVEL
NUT
1.50"
(38mm)
1-1/4"-18 NF-3
FEMALE
CLOSURE
DISC
CABLE CLAMP AND WHEEL ASSEMBLY
4.25"
5.25"
(108mm)
(133mm)
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-6021
Tandem Cable Operated Control Heads - Installation Detail
F-93-6021 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
CYLINDER CENTERS
HEAD (CLOSURE DISC REMOVED)
SLOT IN CONTROL
HOUSING FITS INTOFLARE ON CABLE
1/16” CABLE
WHEEL ASSEMBLY
SEE F-93-6030
CABLE HOUSING
3/8” PIPE OR
ADAPTER P/N
843837-SEE F-93-6120
CABLE CLAMP AND
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-6030
Cable Housing for Cable Operated Control Heads
F-93-6030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIAL: Brass, .625" (16mm) O.D. x .049" (1.28 mm) WALL
FLARED 3/8" NPS MALE
A
TRAPREBMUN
SREDNILYCHTIWDESU
REDNILYCSRETNEC
NOISNEMID"A"
SBL GK NI mm NI mm
207062159062206362
002,521053006
7.09-7.657.8511.272
0.510.810.42
183754016
6.016.316.91
072643894
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-6040
Pull Box, Break Glass
F-93-6040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSBody: AluminumHandle: Brass
P/N: 871403
400 Main Street - Ashland, MA 01721-2150
Tel.(508)881-2000 FAX (508)881-8920
KiddeR
FOR FIREBREAK GLASS PULL HANDLE
PULL HARD
OPTIONAL
NAMEPLATE
(BY INSTALLER)
HAMMER
PULL
4-COVER
3/8” PIPE
1/16” CABLE
SCREWS
HANDLE
2 - NAMEPLATEBRACKETS-
(SUPPLIED WITH
PULL BOX)
5.87"
5.00" 2.25"
(57mm)(127mm)
(149mm)
PULL HANDLE
CABLE FASTENER FOR
BREAK GLASS
P/N WK-928103-000
1/16” CABLE
3/8” NPT FEMALE2 - HOLES FOR 1/4”
MOUNTING SCREWS
(SCREWS NOT SUPPLIED
WITH PULL BOX)SECTION VIEW
WK-524906-080P/N
P/N WK-803246-000
P/N WK-934617-000
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-6041
Break Glass Pull Box used with Z-Bracket - Installation Detail
F-93-6041 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
P/N 60532
Z-BRACKET
(90mm)
SEE F-93-6120ADAPTER P/N 843837
3.56"
SEE F-93-6080PULLEY-P/N 844648-
2E.M.T. CORNER
(114mm)4.50"
16
1"CABLE
E.M.T.1"
2
1"
1"
4MOUNTING BOLTS HERE
3 HOLES FOR
Z-BRACKET
P/N 60532 (90mm)3.56"
SEE F-93-6080PULLEY P/N 803808
4.50"(114mm)
WATERTIGHT CORNER
NPT NIPPLE8
3"
CABLE1"
16
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-6100
Dual Pull Mechanism
F-93-6100 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
P/N: 840058
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-6110
Dual Pull Equalizer
F-93-6110 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
P/N: 840051
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-6120
Adapter, 3/8" Pipe (Male) to 1/2" EMT (Female)
F-93-6120 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIAL: ZINC PLATED STEEL
P/N: 843837
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-7145
Cylinder Recharge Adapters
F-93-7145 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIAL: ZINC PLATED STEEL
3.624.00600878759
3.254.06200, 350878758
878757 10-125 3.22 2.50
B*A*CYL. SIZE (LB)P/N
* DIMENSIONS ARE IN INCHES
3/8" NPT (VENT
VALVE CONNECTION
"A"
3/8"-18NPT
(CHARGE CONNECTION)
O-RING
SEAL
CYLINDER VALVE
OUTLET CONNECTION
"B"
HEX
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-8010
Electric Control Head
F-93-8010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
P/N: 8901XX
PU
ELECTRIC
CONTROL HEAD
VOLTS
AMPS
PART NO.
SET RELEASEDMADE IN U. S. A.
TO RESETUSE SCREWDRIVER
CONNECTION FOR FLEXIBLE
ELECTRIC CONDUIT-
3/4" NPT FEMALE
LOCKING PIN
LOCAL MANUAL
RELEASE LEVER
SWIVEL NUT
1.50" (38mm) HEX
1-1/4"-18 NF-3 THREAD
CONTROL HEADPART
NUMBER
890181
890149
890165
VOLTAGE
24 VDC
125 VDC
115 VAC
CURRENT
2.0A
0.3A
1.0A
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721
INDICATOR ANDRESET STEM
6.18"
4.00"
(157mm)
(102mm)
SEAL WIRE
ORDERING INFORMATION
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-8017
Electric Control Head, Stackable Explosion Proof
F-93-8017 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
P/N: 486500-01
VOLTAGE: 24VDCCURRENT: 0.2A CONTINUOUS DRAW
5.28"
2.90"
1.25-18 UNEF-2A
1/2"-14 NPT
(3) 18 AWG-LEADS
CONDUITCONNECTION
18" LONG
CONNECTION
SWIVEL NUT
1.25-18 UNEF-2B
CONNECTION
ELECTRIC CONTROL HEAD, PART
NO. 486500-01 IS RATED FOR USE
IN HAZARDOUS (CLASSIFIED)
LOCATIONS CLASS 1, DIV. l,
GROUPS C, D AND CLASS ll, DIV. ll,
GROUPS E, F, G BETWEEN
-40F AND 140F. USE CONDUIT
SEAL WITHIN 18 IN. (45cm) OF
THIS DEVICE.
NOTE:THIS CONTROL HEAD IS POLARIZED. IMPROPERWIRING WILL RESULT IN FAILURE OF THIS DEVICE TOOPERATE
WARNINGELECTRIC CONTROL HEAD, P/N: 486500-01, IS DESIGNEDFOR INSTALLATION DIRECTLY ON 487 SERIES HALONAND MODEL 9300 FM-200 VALVES ONLY. THIS CONTROLHEAD MUST NOT BE INSTALLED ON ANY OTHER TYPEOF HALON OR FM-200 CYLINDER VALVE, NITROGENVALVE, CARBON DIOXIDE CYLINDER VALVE, FE-13 CYL-INDER VALVE OR STOP (DIRECTIONAL) VALVE. INSTAL-LATION OF THIS CONTROL HEAD TO ANY OTHER DE-VICE (E.G., PRESSURE OPERATED CONTROL HEAD) WILLRESULT IN FAILURE OF DEVICE TO OPERATE.
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-8030
Electric And Cable Operated Control Head
F-93-8030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
7.56"
(192mm)
(138mm)
5.44"
CONTROL HEAD
895630
895628
895627
PART No.
115 VAC
125 VDC
24 VDC
VOLTAGE
1.0
0.3
2.0
AMPS
MADE IN U. S. A.
RELEASED
ASHLAND, MA 01721
400 MAIN STREET
KIDDE-FENWAL, INC.
SET
WIRE
RESET STEM
INDICATOR AND
3/4" NPT (FEMALE)
ELECTRIC CONDUIT-
CONNECTION FOR FLEXIBLE
LOCKING PIN
RELEASE LEVER
LOCAL MANUAL
ELECTRIC
PART NO.
VOLTS
CONTROL HEAD
USE SCREWDRIVER
TO RESET
AMPS
1 1/4-18NF-3 THREAD
1.50" (38mm) HEX
SWIVEL NUT
SEAL
1/2" E.M.T. CONNECTION
COMPRESSION TYPE FOR
REMOTE CABLE
1/2" E.M.T. CONNECTIONCOMPRESSION TYPE TOSECOND CONTROL HEADIF USED
PU
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-8040
Electric and Cable Operated Control Head withExplosion Proof Solenoid
F-93-8040 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
SE
TR
ELE
AS
ED
TO
RE
SE
T
US
ES
CR
EW
DR
IVE
R
FO
R
MA
INT
EN
AN
CE
SE
E
INS
TR
UC
TIO
NS
CA
BL
E
PU
LL
PU
OPERATING SOLENOID
U.L. LISTED FOR USE IN
THE FOLLOWING HAZARDOUS
LOCATIONS:
CLASS GROUP OP. TEMP.
I C
CONNECTION FOR FLEXIBLE
ELECTRIC CONDUIT 1/2" NPT
FEMALE
CONNECTING WIRES
36" (914 MM) LONG
7.375
INDICATOR AND
RESET STEM
(187 MM)
4.937(125 MM)
LOCKING PIN
SEAL WIRE
CONNECTION FOR
REMOTE PULL BOX
PIPE OR CONDUIT
3/8" NPS MALE
LOCAL MANUAL
RELEASE LEVER
SWIVEL NUT
1.500 (38 MM) HEX
1.250-18 NF-3 THREADCONNECTION FOR CABLE
HOUSING TO SECOND
CONTROL HEAD IF USED
3/8" NPS FEMALE.
USE PNEUMATIC CONTROL
HEAD CABLE HOUSINGS
SEE F-93-5020.
EL
EC
TR
IC
CO
NT
RO
LH
EA
D
PA
RT
NO
.
MA
DE
INU
.S.A
.
KID
DE
-FE
NW
AL
,IN
C.
40
0M
AIN
ST
RE
ET
AS
HL
AN
D,
MA
01
72
1
VO
LT
S
HZ
AM
PS
-13 TO +150F
(-25 TO +65C)
I D
(-40 TO +65C)
-40 TO +150F
II E,F,G -40 TO +150F
(-40 TO +65C)
PART
NUMBER
CONTROL HEAD
VOLTAGEPOWER
CONSUMPTION
897494 24 VDC 33 WATTS
897560 120 VAC 15.4 WATTS
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-8070
Electric Main-To-Reserve Transfer Switch
F-93-8070 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIALSCONDUIT BOX: STEEL WITH RED ENAMEL FINISHTOGGLE SWITCH LEVER: BAKELITE
P/N: 802398
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-8130
Cylinder Mounting Straps
F-93-8130 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIAL: STEEL, PAINTED BLACK SAE 1020
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-8140
Cylinder Wall Brackets
F-93-8140 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIAL: STEEL, ZINC PLATEDSAE 1010
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-8150
Cylinder Mounting Cradle
F-93-8150 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIAL: STEEL, PAINTED GRAY AISI M1020
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-9010
Main and Reserve Nameplates
F-93-9010 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
MATERIAL: ALUMINUM WITH RED PAINT LETTERSP/N: 3103X
5.00"
1.62"(41mm)
(127mm)
RESERVE
P/N 31034 2-0.281"(7mm) DIA.
MOUNTING HOLES
MOUNTING HOLES
2-0.281"(7mm) DIA.P/N 31033
MAIN
(127mm)
(41mm)1.62"
5.00"
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
FM-200 COMPONENT DESCRIPTION Effective June 1999
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
FEATURES• FOR USE WITH UL LISTED, ULC LISTED & FMRC APPROVED SYSTEMS
F-93-9030
Warning Nameplate (FM-200)
F-93-9030 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
P/N: 06-231865-739
MATERIAL: ALUMINUM TYPE 1100-H14 OR 3003-H14,.032 + .003 THICK. ALL LETTERS TO BE 48 PT.ALTERNATE GOTHIC #2. ETCHED .003 - .005 & FILLEDIN WITH RED CHIP PROOF ENAMEL COLOR NO.21105 PER FED. STC. 595FINISH: ONE COAT CLEAR LACQUER BOTH SIDES
TM
.281 .005 DIA. TYP. 4 HOLES
±.062
5.000
.340
.340 9.360
10.000 ±.063
4.360
WARNING
THIS AREA IS PROTECTED BY AFM-200 EXTINGUISHING
SYSTEM. DO NOT ENTER WITHOUTAUTHORIZATION DURING OR
AFTER DISCHARGE
����������������� ������� ���� ��� ������ ���� ��������������������� ���������� ��� ���!������� ������ ��"�#������!������� �����"�������"�� ��������� ��"�������!�� ������������� ���� �������"�!������������� �������� ����� ��� �� �������� ��"��� ����� �������$����� ���" ��"������������������ �����������%��&'()'*������� ���+,&-.�--'�)&&&
�������������� ����������������������������
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.com
Protection Systems
R
��������� ���� ���� ��� ��� ��� � �� � ����� ������� � ������
���������
����������� ������
��/0�/&1&�����������������������������������'///����������2�����"������3���������4�5���
�������������
����������� ���� � ������ �������� ����� ����� � ���� ��� ������� ����
����� ���� ���� �� ������ ��� ����� ������ � ������� �� ����
3" NPT
FEMALE
8.058
3" NPT
FEMALE
9.360
53° MAX.SWING ANGLE
This literature is provided for informational purposes only. KIDDE-FENWAL,INC. assumes noresponsibility for the product's suitability for a particular application. The product must beproperly applied to perform as described herein.If you need more information on this product, or if you have a question, contact KIDDE-FENWAL, INC., Ashland, MA 01721; Telephone (508) 881-2000
R
KIDDE-FENWAL, INC.400 MAIN STREET, ASHLAND, MA 01721TEL: (508) 881-2000 FAX: (508) 881-8920
www.fenwalfire.comProtection Systems
R
FEATURES• FOR USE WITH UL LISTED AND FMRC APPROVED SYSTEMS
F-93-9041
3" Swing Check ValveInstallation Detail
F-93-9041 ©1999 Kidde-Fenwal, Inc. Printed in U.S.A.
90°
NOTES:
1.INSTALL CHECK VALVE SO THAT ARROW
IS IN DIRECTION OF FLOW.
2. INSTALL BETWEEN O AND 90 DEGREES
FROM THE HORIZONTAL.
Effective: November 1999FM-200® COMPONENT DESCRIPTION