Ceiling Concealed Split Systems ACC - D2- 2007 (Draft) ACC 75D/DR ACC 100D/DR Models:

Transcript of Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA...

Page 1: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

Ceiling ConcealedSplit Systems

ACC - D2- 2007 (Draft)

ACC 75D/DRACC 100D/DR

Models:

Page 2: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

CONTENTS

1. NOMENECLATURE ................................................................................................... 2

2. FEATURES ................................................................................................................ 4

3. PRODUCT LINE UP ..................................................................................................... 5

4. SPECIFICATIONS ............................................................................................... 8

5. OPERATING RANGE ......................................................................................... 22

6. SOUND DATA ................................................................................ 23

7. PERFORMANCE TABLE .................................................................... 25

8. OUTLINES AND DIMENSIONS................................................................................................ 35

9. REFRIGERANT CIRCUIT ......................................................................................................... 37

10. WIRING DIAGRAMS ....................................................................................................... 38

11. INSTALLATION ......................................................................... 40

12. SERVICING AND MAINTENANCE ............................................................................................ 43

13. TROUBLESHOOTING ......................................................................... 45

14. EXPLODED VIEW AND PARTS LIST ......................................................................... 51

Page 3: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

1. NOMENCLATURE

2

CC 75 D R A

Model Type

R : Heatpump Omitted if Cooling Only

Series

D : D Series

Capacity

75 : 75,000 Btu/h

Model Name

CC : Ceiling Concealed

Refrigerant

Blank : R22 4 : R407C

Brand

A : Acson

Electrical Characteristic

A : 50Hz / 1Ph / 220-240V

Type of Connection

Product Specification Variation

A : First Issue

- A A B A

B : For Brazed

INDOOR

Page 4: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

3

A A B F -

Model Typ

R : Heatpump Omitted if Cooling Only

Series

E : E Series D : D Series

Capacity

75 : 75,000 Btu/h

Model Name

MC : Single Split Condensing Unit

Refrigerant

Blank : R22 4 : R407C

Brand

A : Acson

Electrical Characteristic

B : For Brazed

Type of Connection

Product Specification Variation

A : First issue

F : 50Hz / 3Ph / 220-240V P : 60Hz / 3Ph / 208-230VQ : 60Hz / 3Ph / 460V

MC 75 E R A

e

OUTDOOR

Page 5: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

2. FEATURES

4

Invisible Operation The unit is installed concealed above the ceiling. ACC-D is designed to intelligently create a comfortable and healthy indoor air climate, while remaining invisible. This allows user to enjoy conditioned air without sacrificing room space or interior design creativity. Flexibility in System DesignThe unit offers fan motor that can operate up to 4 speeds, thus provide choices of external static pressure for designing ducting system. Easy Serviceability With the concept of easy serviceability in mind, ACC-D series is designed for easy access to internal components. The internal components, such as fan motor or blower, can be easily accessed for servicing through both sides or bottom of the unit. High Level of Protection The unit is incorporated with a unique safety feature, i.e. a float switch, to provide an additional protection from possible problems of condensate water over flow inside the unit. Once the condensate water reaches critical level, the level switch will be activated and signal will be sent to the microprocessor controller to stop the compressor as well as sending an error message to the wired controller, alerting the user, for further action. Wired Remote Controller The standard unit comes with the Netware III controller, which offers wide range of control features that, includes 7 days and 24 hours timer setting and more. The ACC-D series is able to communicate with the versatile NIM network control module and offers the opportunity of one centralized control for a system of multiple indoor units in a building. Auto Random RestartAuto random restart function allows the unit to automatic restart as the last setting condition when the power supply is resumed after power failure. However, the compressor will restart randomly if more than one unit is installed and sharing the same phase of power. Self Diagnosis The microprocessor provides the possibility to detect and diagnose any fault or malfunction that occurs in the system. The error will be reflected by the wired remote controller with a series of error code.

Page 6: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

3. PRODUCT LINE UP

ACC-D SERIES PRODUCT LINE UP

5

Han

dset

Con

trol

Mod

ule

Filtr

atio

n

Mar

king

NET

WA

RE

III

L2

Air

Filte

r

CE

Mar

k

Cap

. Tub

e

TXV

75D

R

ABAA X X X X X X X X

100D

R

ABAA X X X X X X X X

Classification

Hea

t Pum

p M

odel

Bui

lt-in

Filt

er R

ail

ACC

Aut

o R

ando

m R

esta

rt

Leve

l Sw

itch

NO

NM

ENC

LATU

RE

Ref

riger

ant

Con

trol

INDOOR UNIT

Page 7: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

OUTDOOR UNIT

6

Com

pres

sor

With

Con

tact

or

With

out C

onta

ctor

With

24V

ac C

ontro

l Circ

uit

With

Aut

o H

P/L

P

With

Man

ual H

P/L

P

CE

Mar

k

ETL

With

out M

arki

ng

Scr

oll-C

opel

and

TXV

With

out E

xpan

sion

Dev

ice

Riv

et "M

ade

In M

alay

sia"

With

Acc

umul

ator

With

Typ

e B

raze

d B

all V

alve

Pha

se P

rote

ctor

Gol

d Fi

n (N

A54

9)

FBAF X X X X X XFBAG X X X X X XFBAH X X X X X XFCAA X X X X X XFCAB X X X X X X XPBAB X X X X XPBAC X X X X X X XPCAA X X X X X XQBAB X X X X XQBAC X X X X X X XQCAB X X X X X X X XFBAF X X X X X XFBAG X X X X X XFBAH X X X X X XFCAA X X X X X XFCAB X X X X X X XPBAB X X X X XPBAC X X X X X X XPCAA X X X X X XQBAB X X X X XQBAC X X X X X X XQCAB X X X X X X X X

Classification

Marking

Ref

riger

ant

Con

trol

OthersController

Coo

ling

Onl

y M

odel

75D 1/2

5/8100D 1-1/8

1

Nom

encl

atur

e

AMC

Liqu

id P

ipe

Siz

e (in

)

Gas

Pip

e S

ize

(in)

Mar

king

Com

pres

sor

With

Con

tact

or

Aut

o H

P/L

P

CE

Mar

k

Scr

oll-C

opel

and

TXV

With

out E

xpan

sion

Dev

ice

For S

eque

ntia

l Con

trolle

r

With

Acc

umul

ator

With

Typ

e B

raze

d B

all V

alve

Gol

d Fi

n (N

A54

9)

FBAA X X X X X XFBAA X X X X X X XFCAA X X X X X X XFCAB X X X X X X X X XFBAA X X X X X XFBAA X X X X X X XFCAA X X X X X X XFCAB X X X X X X X X X

A4MC

Coo

ling

Onl

y M

odel

75D 1/2 1

100D 5/8 1-1/8

Classification

Nom

encl

atur

e

Con

trol

ler

Ref

riger

ant

Con

trol

Others

Liqu

id P

ipe

Siz

e (in

)

Gas

pip

e si

ze (i

n)

AMC-D Series Product Line Up

A4MC-D Series Product Line Up

Page 8: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

Outdoor Unit

7

AMC-ER Series Product Line Up

A4MC-ER Series Product Line Up

Mar

king

Com

pres

sor

With

Con

tact

or

With

Aut

o H

P/LP

CE

Mar

k

Scr

oll-C

opel

and

TXV

With

out E

xpan

sion

Dev

ice

For S

eque

ntia

l Con

trolle

r

Gol

d Fi

n (N

A54

9)

Riv

et "M

ade

In M

alay

sia"

With

Bra

zed

Type

Bal

l Val

ve

Che

ck v

alve

Pha

se S

eque

ncer

FBAA X X X X X XFBAB X X X X X X XFBAC X X X X X X XFCAA X X X X X X XFBAA X X X X X XFBAB X X X X X X XFBAC X X X X X X XFCAA X X X X X X XFBAA X X X X X XFBAB X X X X X X XFBAC X X X X X X X XFCAA X X X X X X XFBAA X X X X X XFBAB X X X X X X X XFCAA X X X X X X X

Mar

king

Com

pres

sor

With

Con

tact

or

With

Aut

o H

P/LP

CE

Mar

k

Scr

oll-C

opel

and

TXV

With

out E

xpan

sion

Dev

ice

For S

eque

ntia

l Con

trolle

r

Gol

d Fi

n (N

A54

9)

With

Acc

umul

ator

With

Bra

zed

Type

Bal

l Val

ve

FBAA X X X X X XFCAA X X X X X X XFBAA X X X X X XFCAA X X X X X X XFBAA X X X X X XFCAA X X X X X X XFBAA X X X X X XFCAA X X X X X X X

100ER

125ER

150ER

Hea

tpum

p M

odel

s

75ER

75ER

5/8

125ER 5/8

100ER 5/8

Gas

Pip

e S

ize

(in)

Liqu

id P

ipe

Siz

e (in

)

Classification

Others

Ref

riger

ant

Con

trol

Con

trol

ler

5/8

1-1/8

1-3/8

1-3/8

5/8

5/8

1

1/2 1

1-3/8

1-3/8

1-1/8

Liqu

id P

ipe

Siz

e (in

)

Classification

Gas

Pip

e S

ize

(in)

MSS

Nom

encl

atur

e

4MSS

1/2

Nom

encl

atur

e

Con

trol

ler

Ref

riger

ant

Con

trol

Others

HEA

TPU

MP

MO

DLE

S

150ER

Page 9: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

4. SPECIFICATIONS

8

General Data - Cooling Only (R22)ACC 75D ACC 100DAMC 75D AMC 100D

Btu/h 75,000 95,000

W 21,960 27,820

W 8,471 10,822

A 16.3 19.4

V/Ph/Hz

CFM / L/s 2420 / 1142 3150 / 1487

CFM / L/s 2450 / 1156 3130 / 1477

CFM / L/s 2000 / 944 2840 / 1340

CFM / L/s 1680 / 793 2240 / 1057

EXTERNAL STATIC PRESSURE (SH/H/M/L) mmAq(Pa)dBA 52 / 52 / 48 / 43 55 / 54 / 52 / 48

mm/in 430 / 16.9 430 / 16.9

mm/in 1426 / 56.1 1655 / 65.2

mm/in 826 / 32.5 826 / 32.5

mm/in 612 / 24.1 612 / 24.1

mm/in 1535 / 60.4 1765 / 69.5

mm/in 974 / 38.3 974 / 38.3

kg/lb 92 / 203 119 / 262

mm/in 25.4 / 1.0 25.4 / 1.0

CFM / L/sdBA

mm/inmm/inmm/inmm/inmm/inmm/inkg/lb 170 / 374 184 / 405

LIQUID mm/in 12.70 / 1/2 15.88 / 5/8GAS mm/in 25.40 / 1 28.57 / 1-1/8

kg/lb 6.7 / 14.77 10.5 / 23.15

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.

3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35.0°C DB / 23.9°C WB OUTDOOR

4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND

1m BELOW THE UNIT.

1150 / 45.3

1224 / 48.21175 / 46.3

BRAZING

R22 / INDOOR TXV380 - 415 / 3 / 50

IND

OO

R U

NIT

AIR FLOW

SUPER HIGH

SOUND PRESSURE LEVEL (SH/H/M/L)

HIGH MEDIUM

CONDENSATE DRAIN SIZE

20 / 14 / 10 / 7 (196 / 137 / 98 / 69)

MODELOUTDOOR UNIT

LOW

INDOOR UNIT

NOMINAL CAPACITY

NOMINAL TOTAL INPUT POWERNOMINAL RUNNING CURRENT POWER SOURCE REFRIGERANT TYPE / CONTROL

UNIT DIMENSION

SOUND PRESSURE LEVEL

PACKING DIMENSION HEIGHTWIDTHDEPTH

UNIT WEIGHT

OU

TDO

OR

UN

IT

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTHHEIGHTWIDTH

REFRIGERANT CHARGE

AIR FLOW

DEPTHUNIT WEIGHT

PIPE CONNECTIONTYPE

SIZE

UNIT DIMENSION

7000 / 3304

1041 / 40.98981 / 38.62981 / 38.62

64

Page 10: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

9

Electrical Data - Cooling Only (R22)ACC 75D ACC 100DAMC 75D AMC 100D

POWER SOURCE V/Ph/HzRATED INPUT POWER W 1061 1254

RATED RUNNING CURRENT A 4.51 5.79

MOTOR OUTPUT W 750 10004 4

POWER SOURCE V/Ph/HzRATED INPUT POWER WRATED RUNNING CURRENT AMOTOR OUTPUT W

N/A N/A

POWER SOURCE V/Ph/HzCAPACITOR µF NIL NIL

RATED INPUT POWER W 6810 8968

RATED RUNNING CURRENT A 13.6 16.3

LOCKED ROTOR AMP. A 95 125

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/230-94.

MODEL

INDOOR MOTOR

OUTDOOR MOTOR

COMPRESSOR

INDOOR UNITOUTDOOR UNITTYPEINSULATION GRADE

INSULATION GRADE

POLESTYPEINSULATION GRADE

TYPE

INDUCTION

220 - 240 / 1 / 50

INDUCTION

380 - 415 / 3 / 50CLASS F

CLASS B

380 - 415 / 3 / 50

6001.2350

SCROLL

Page 11: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

10

Components Data (R22)ACC 75D ACC 100DAMC 75D ALC 100D

2ZINC COATED STEEL ZINC COATED STEEL

DIRECT DIRECTmm/in 228.6 / 9.0 228.6 / 9.0mm/in 177.8 / 7.0 228.6 / 9.0

1N/A N/A

mm/in

N/A N/A

SONTEX 200 LT SONTEX 200 LTOIL AMOUNT cm3 2513 3253

DIAMETER mm/inTHICKNESS mm/in

ALUMINIUM ALUMINIUMTHICKNESS mm/in 0.127 / 0.005 0.127 / 0.005FACE AREA m2/ft2 0.45 / 4.89 0.55 / 5.89

412 14

DIAMETER mm/inTHICKNESS mm/in

ALUMINIUM ALUMINIUMTHICKNESS mm/in 0.127 / 0.005 0.127 / 0.005FACE AREA m2/ft2 2.29 / 24.72 2.29 / 24.72

120 16

WIDTH mm/in 665 / 26.1 780 / 30.7HEIGHT mm/in 345 / 13.9 345 / 13.9

QUANTITY pc 2MATERIALFINSIHINGCOLOUR

MATERIALFINISHINGCOLOUR

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

EPOXY POLYESTER POWDER

-

GALVANIZED MILD STEEL

WHITE

ELECTRO GALVANIZED STEEL

-

0.35 / 0.013

SEAMLESS COPPER9.52 / 3/8

0.35 / 0.013

SEAMLESS COPPER9.52 / 3/8

MATERIAL

ROWFIN PER INCH

COMPRESSORTYPEOIL TYPE

INDOOR COIL

INDEX OF PROTECTION (IP)

OUTDOOR FAN MOTOR

OUTDOOR FAN MATERIALDRIVEDIAMETERTYPE

TYPEQ'TY

LENGTH

INDOOR FAN

TYPEQ'TYINDOOR FAN

MOTOR

Q'TYMATERIALDRIVEDIAMETER

INDEX OF PROTECTION (IP)

INDOOR UNITOUTDOOR UNIT

MODEL

TYPE

OUTDOOR COIL

FIN

FIN

TUBE

TUBE

FILTRATION

CASING

INDOOR UNIT

OUTDOOR UNIT

TYPE

CENTRIFUGAL

INDUCTION

PROPELLER1

ALUMINIUM DIRECT

812.8 / 32.0INDUCTION

1

SCROLL

SIZE

WASHABLE SARANET FILTER

MATERIAL

MATERIAL

ROWFIN PER INCH

Q'TY

MATERIAL

2

1

4

2

2

Page 12: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

11

General Data - Heat pump (R22)ACC 75DR ACC 100DRAMC 75ER AMC 100ER

Btu/h 75000 100000

W 21960 29280

Btu/h 84000 110000

W 24600 32210

W 7356 10200

W 7206 9800

A 13.6 17.9

A 13.3 17.2

V/Ph/Hz

CFM / L/s 2420 / 1142 3150 / 1487

CFM / L/s 2450 / 1156 3130 / 1477

CFM / L/s 2000 / 944 2840 / 1340

CFM / L/s 1680 / 793 2240 / 1057

EXTERNAL STATIC PRESSURE (SH/H/M/L) mmAq(Pa)dBA 52 / 52 / 48 / 43 55 / 54 / 52 / 48

mm/in 430 / 16.9 430 / 16.9

mm/in 1426 / 56.1 1655 / 65.2

mm/in 826 / 32.5 826 / 32.5

mm/in 612 / 24.1 612 / 24.1

mm/in 1535 / 60.4 1765 / 69.5

mm/in 974 / 38.3 974 / 38.3

kg/lb 92 / 203 119 / 262

mm/in 25.4 / 1.0 25.4 / 1.0

CFM / L/sdBA

mm/inmm/inmm/inmm/inmm/inmm/inkg/lb 170 / 374 184 / 405

LIQUID mm/in 12.70 / 1/2 15.88 / 5/8GAS mm/in 28.58 / 1-1/8 28.58 / 1-1/8

kg/lb 6.80 / 14.99 7.50 / 16.54

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.

3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :

a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35.0°C DB / 23.9°C WB OUTDOOR

b) HEATING - 21.1°C DB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR

4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND

1m BELOW THE UNIT.

64

BRAZING

1150 / 45.3

1224 / 48.21175 / 46.3

981 / 38.62

REFRIGERANT CHARGE

AIR FLOW

380 - 415 / 3 / 50R22 / INDOOR & OUTDOOR TXV

AIR FLOW

SUPER HIGH

20 / 14 / 10 / 7 (196 / 137 / 98 / 69)

7000 / 3304

981 / 38.62

1041 / 40.98

DEPTHUNIT WEIGHT

PIPE CONNECTIONTYPE

SIZE

OU

TDO

OR

UN

IT

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTHHEIGHTWIDTH

UNIT WEIGHTCONDENSATE DRAIN SIZE

UNIT DIMENSION

UNIT DIMENSION

SOUND PRESSURE LEVEL

PACKING DIMENSION HEIGHTWIDTHDEPTH

HIGH MEDIUM

MODELOUTDOOR UNIT

POWER SOURCEREFRIGERANT TYPE / CONTROL

LOW

INDOOR UNIT

IND

OO

R U

NIT SOUND PRESSURE LEVEL (SH/H/M/L)

NOMINAL COOLING CAPACITY

NOMINAL HEATING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)NOMINAL TOTAL INPUT POWER (HEATING)NOMINAL RUNNING CURRENT (COOLING)NOMINAL RUNNING CURRENT (HEATING)

Page 13: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

12

Electrical Data - Heat pump (R22)ACC 75DR ACC 100DRAMC 75ER AMC 100ER

POWER SOURCE V/Ph/HzRATED INPUT POWER W 1061 1254

RATED RUNNING CURRENT A 4.51 5.79

MOTOR OUTPUT W 750 10004 4

POWER SOURCE V/Ph/HzRATED INPUT POWER WRATED RUNNING CURRENT AMOTOR OUTPUT W

N/A N/A

POWER SOURCE V/Ph/HzCAPACITOR µF NIL NIL

RATED INPUT POWER (COOLING) W 5695 8346

RATED INPUT POWER (HEATING) W 5545 7966

RATED RUNNING CURRENT (COOLING) A 10.9 14.8

RATED RUNNING CURRENT (HEATING) A 10.6 14.1

LOCKED ROTOR AMP. A 95 125

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.

SCROLL

380 - 415 / 3 / 50

350

6001.2

220 - 240 / 1 / 50

380 - 415 / 3 / 50

INDUCTION

INDUCTION

CLASS B

CLASS F

INSULATION GRADE

POLESTYPEINSULATION GRADE

TYPE

INDOOR UNITOUTDOOR UNITTYPEINSULATION GRADE

MODEL

INDOOR MOTOR

OUTDOOR MOTOR

COMPRESSOR

Page 14: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

13

Components Data (R22)ACC 75DR ACC 100DRAMC 75ER AMC 100ER

2ZINC COATED STEEL ZINC COATED STEEL

DIRECT DIRECTmm/in 228.6 / 9.0 228.6 / 9.0mm/in 177.8 / 7.0 228.6 / 9.0

1N/A N/A

mm/in

N/A N/A

Sontex 200 LT Sontex 200 LTOIL AMOUNT cm3 2513 3253

DIAMETER mm/inTHICKNESS mm/in

ALUMINIUM ALUMINIUMTHICKNESS mm/in 0.127 / 0.005 0.127 / 0.005FACE AREA m2/ft2 0.45 / 4.89 0.55 / 5.89

412 14

DIAMETER mm/inTHICKNESS mm/in

ALUMINIUM ALUMINIUM THICKNESS mm/in 0.127 / 0.005 0.127 / 0.005FACE AREA m2/ft2 2.29 / 24.72 2.29 / 24.72

120 16

WIDTH mm/in 665 / 26.1 780 / 30.7HEIGHT mm/in 345 / 13.9 345 / 13.9

QUANTITY pc 2MATERIALFINSIHINGCOLOUR

MATERIALFINISHINGCOLOUR

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

EPOXY POLYESTER POWDER

N/A

GALVANIZED MILD STEEL

WHITE

ELECTRO GALVANIZED STEEL

N/A

SEAMLESS COPPER9.52 / 3/8

0.35 / 0.013

SEAMLESS INNER GROOVED COPPER9.52 / 3/8

1

CENTRIFUGAL

ALUMINIUM

SCROLL

INDUCTION

PROPELLER1

DIRECT812.8 / 32.0INDUCTION

FILTRATION

CASING

INDOOR UNIT

OUTDOOR UNIT

TYPE

SIZE

INDOOR COIL

OUTDOOR COIL

FIN

FIN

TUBE

TUBE

INDOOR UNITOUTDOOR UNIT

MODEL

TYPE

LENGTH

INDOOR FAN

TYPEQ'TYINDOOR FAN

MOTOR

Q'TYMATERIALDRIVEDIAMETER

INDEX OF PROTECTION (IP)

Q'TYOUTDOOR FAN MOTOR

OUTDOOR FAN MATERIALDRIVEDIAMETERTYPE

TYPEQ'TY

COMPRESSORTYPEOIL TYPE

INDEX OF PROTECTION (IP)

WASHABLE SARANET FILTER

MATERIAL

MATERIAL

ROWFIN PER INCHMATERIAL

MATERIAL

ROWFIN PER INCH

0.35 / 0.013

2

2

4

1

2

Page 15: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

14

Safety Devices

ACC 75D ACC 100DAMC 75D AMC 100D

TYPE AUTO RESET AUTO RESET

SETTING 426 psi OFF 426 psi OFF

TYPE AUTO RESET AUTO RESET

SETTING 18 psi OFF 18 psi OFF

AVAILABLE AVAILABLE

DISCHARGE THERMOSTAT SETTING 130 oC 130 oC

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

MODEL

SAFETY DEVICE

INDOOR UNITOUTDOOR UNIT

PHASE SEQUENCER

HIGH PRESSURE SWITCH

LOW PRESSURE SWITCH

ACC 75DR ACC 100DRAMC 75ER AMC 100ER

TYPE AUTO RESET AUTO RESET

SETTING 426 psi OFF 426 psi OFF

TYPE AUTO RESET AUTO RESET

SETTING 7 psi OFF 7 psi OFF

AVAILABLE AVAILABLE

DISCHARGE THERMOSTAT SETTING 130 oC 130 oC

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

MODEL

SAFETY DEVICE

INDOOR UNITOUTDOOR UNIT

PHASE SEQUENCER

HIGH PRESSURE SWITCH

LOW PRESSURE SWITCH

Page 16: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

15

General Data - Cooling Only (R407C)ACC 75D ACC 100D

A4MC 75D A4MC 100DBtu/h 75000 100000

W 21980 29310

W 8892 10833

A 16.0 19.0

V/Ph/Hz

CFM / L/s 2520 / 1189 3070 / 1449

CFM / L/s 2320 / 1095 2620 / 1237

CFM / L/s 2095 / 989 2350 / 1109

CFM / L/s 1660 / 783 2150 / 1015

EXTERNAL STATIC PRESSURE (SH/H/M/L) mmAq(Pa)dBA 52 / 52 / 48 / 43 55 / 54 / 52 / 48

mm/in 430 / 16.9 430 / 16.9

mm/in 1426 / 56.1 1655 / 65.2

mm/in 826 / 32.5 826 / 32.5

mm/in 612 / 24.1 612 / 24.1

mm/in 1535 / 60.4 1765 / 69.5

mm/in 974 / 38.3 974 / 38.3

kg/lb 92 / 203 119 / 262

mm/in 25.4 / 1.0 25.4 / 1.0

CFM / L/sdBA

mm/inmm/inmm/inmm/inmm/inmm/inkg/lb 170 / 374 184 / 405

BRAZING BRAZINGLIQUID mm/in 12.70 / 1/2 15.88 / 5/8

GAS mm/in 25.40 / 1 28.57 / 1-1/8kg/lb 7.00 / 15.43 7.80 / 17.20

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.

3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :

COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35.0°C DB / 23.9°C WB OUTDOOR

4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND

1m BELOW THE UNIT.

1224 / 48.21175 / 46.31150 / 45.3

64

R407C / INDOOR TXV380 - 415 / 3 / 50

IND

OO

R U

NIT

AIR FLOW

SUPER HIGH

SOUND PRESSURE LEVEL (H/M/L)

HIGH MEDIUM

CONDENSATE DRAIN SIZE

20 / 14 / 10 / 7 (196 / 137 / 98 / 69)

MODELOUTDOOR UNIT

LOW

INDOOR UNIT

NOMINAL CAPACITY

NOMINAL TOTAL INPUT POWERNOMINAL RUNNING CURRENT POWER SOURCE REFRIGERANT TYPE / CONTROL

UNIT DIMENSION

SOUND PRESSURE LEVEL

PACKING DIMENSION HEIGHTWIDTHDEPTH

UNIT WEIGHT

OU

TDO

OR

UN

IT

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTHHEIGHTWIDTH

REFRIGERANT CHARGE

AIR FLOW

DEPTHUNIT WEIGHT

PIPE CONNECTIONTYPE

SIZE

UNIT DIMENSION

7000 / 3304

1041 / 40.98981 / 38.62981 / 38.62

Page 17: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

16

Electrical Data - Cooling Only (R407C)ACC 75D ACC 100D

A4MC 75D A4MC 100D

POWER SOURCE V/Ph/HzRATED INPUT POWER W 1061 1254

RATED RUNNING CURRENT A 4.51 5.79

MOTOR OUTPUT W 750 10004

POWER SOURCE V/Ph/HzRATED INPUT POWER WRATED RUNNING CURRENT AMOTOR OUTPUT W

N/A N/A

POWER SOURCE V/Ph/HzCAPACITOR µF NIL NIL

RATED INPUT POWER W 7231 8979

RATED RUNNING CURRENT A 13.34 15.82

LOCKED ROTOR AMP. A 95 125

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.

MODEL

INDOOR MOTOR

OUTDOOR MOTOR

COMPRESSOR

INDOOR UNITOUTDOOR UNITTYPEINSULATION GRADE

INSULATION GRADE

POLESTYPEINSULATION GRADE

TYPE

INDUCTION

220 - 240 / 1 / 50

INDUCTION

380 - 415 / 3 / 50

CLASS B

CLASS F

380 - 415 / 3 / 50

6001.2350

SCROLL

4

Page 18: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

17

Components Data (R407C)ACC 75D ACC 100D

A4MC 75D A4MC 100D

1ZINC COATED STEEL ZINC COATED STEEL

DIRECT DIRECTmm/in 228.6 / 9.0 228.6 / 9.0mm/in 177.8 / 7.0 228.6 / 9.0

1N/A N/A

mm/in

N/A N/A

SONTEX 200 LT SONTEX 200 LTOIL AMOUNT cm3 2513 3253

S. I. G. C. SEAMLESS COPPERDIAMETER mm/in 9.52 / 3/8 9.52 / 3/8THICKNESS mm/in 0.35 / 0.013 0.35 / 0.013

ALUMINIUM ALUMINIUM THICKNESS mm/in 0.127 / 0.005 0.127 / 0.005FACE AREA m2/ft2 0.45 / 4.89 0.55 / 5.89

412 14

S. I. G. C. SEAMLESS COPPERDIAMETER mm/in 9.52 / 3/8 9.52 / 3/8THICKNESS mm/in 0.35 / 0.013 0.35 / 0.013

ALUMINIUM ALUMINIUM THICKNESS mm/in 0.127 / 0.005 0.127 / 0.005FACE AREA m2/ft2 2.29 / 24.72 2.29 / 24.72

120 16

WIDTH mm/in 665 / 26.1 780 / 30.7HEIGHT mm/in 345 / 13.9 345 / 13.9

QUANTITY pc 2MATERIALFINSIHINGCOLOUR

MATERIALFINISHINGCOLOUR

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

EPOXY POLYESTER POWDERWHITE

GALVANIZED MILD STEEL--

ELECTRO GALVANIZED STEEL

MATERIAL

ROWFIN PER INCH

COMPRESSORTYPEOIL TYPE

INDOOR COIL

INDEX OF PROTECTION (IP)

OUTDOOR FAN MOTOR

OUTDOOR FAN MATERIALDRIVEDIAMETERTYPE

TYPEQ'TY

LENGTH

INDOOR FAN

TYPEQ'TYINDOOR FAN

MOTOR

Q'TYMATERIALDRIVEDIAMETER

INDEX OF PROTECTION (IP)

INDOOR UNITOUTDOOR UNIT

MODEL

TYPE

OUTDOOR COIL

FIN

FIN

TUBE

TUBE

FILTRATION

CASING

INDOOR UNIT

OUTDOOR UNIT

TYPE

CENTRIFUGAL

INDUCTION

PROPELLER1

ALUMINIUM DIRECT

812.8 / 32.0INDUCTION

1

SCROLL

SIZE

WASHABLE SARANET FILTER

MATERIAL

MATERIAL

ROWFIN PER INCH

Q'TY

MATERIAL

2

2

4

2

1

Page 19: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

18

General Data - Heat pump (R407C)ACC 75DR ACC 100DR

A4MC 75ER A4MC 100ERBtu/h 75000 100000

W 21980 29310

Btu/h 84000 110000

W 24620 32240

W 7827 11040

W 7827 9279

A 13.9 19.0

A 13.9 19.6

V/Ph/Hz

CFM / L/s 2520 / 1189 3070 / 1449

CFM / L/s 2320 / 1095 2620 / 1237

CFM / L/s 2095 / 989 2350 / 1109

CFM / L/s 1660 / 783 2150 / 1015

EXTERNAL STATIC PRESSURE (SH/H/M/L) mmAq(Pa)dBA 52 / 52 / 48 / 43 55 / 54 / 52 / 48

mm/in 430 / 16.9 430 / 16.9

mm/in 1426 / 56.1 1655 / 65.2

mm/in 826 / 32.5 826 / 32.5

mm/in 612 / 24.1 612 / 24.1

mm/in 1535 / 60.4 1765 / 69.5

mm/in 974 / 38.3 974 / 38.3

kg/lb 92 / 203 119 / 262

mm/in 25.4 / 1.0 25.4 / 1.0

CFM / L/sdBA

mm/inmm/inmm/inmm/inmm/inmm/inkg/lb 170 / 374 184 / 405

LIQUID mm/in 12.70 / 1/2 15.88 / 5/8GAS mm/in 28.58 / 1-1/8 28.58 / 1-1/8

kg/lb 7.00 / 15.43 7.80 / 17.20

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.

3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :

a) COOLING - 26.7°C DB / 19.4°C WB INDOOR AND 35.0°C DB / 23.9°C WB OUTDOOR

b) HEATING - 21.1°C DB INDOOR AND 8.3°C DB / 6.1°C WB OUTDOOR

4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND

1m BELOW THE UNIT.

BRAZING

64

1150 / 45.3

1224 / 48.21175 / 46.3

981 / 38.62

REFRIGERANT CHARGE

AIR FLOW

380 - 415 / 3 / 50R407C / INDOOR & OUTDOOR TXV

AIR FLOW

SUPER HIGH

20 / 14 / 10 / 7 (196 / 137 / 98 / 69)

7000 / 3304

981 / 38.62

1041 / 40.98

DEPTHUNIT WEIGHT

PIPE CONNECTIONTYPE

SIZE

OU

TDO

OR

UN

IT

HEIGHTWIDTHDEPTH

PACKING DIMENSION

HEIGHTWIDTHDEPTHHEIGHTWIDTH

UNIT WEIGHTCONDENSATE DRAIN SIZE

UNIT DIMENSION

UNIT DIMENSION

SOUND PRESSURE LEVEL

PACKING DIMENSION HEIGHTWIDTHDEPTH

HIGH MEDIUM

MODELOUTDOOR UNIT

POWER SOURCEREFRIGERANT TYPE / CONTROL

LOW

INDOOR UNIT

IND

OO

R U

NIT SOUND PRESSURE LEVEL (SH/H/M/L)

NOMINAL COOLING CAPACITY

NOMINAL HEATING CAPACITY

NOMINAL TOTAL INPUT POWER (COOLING)NOMINAL TOTAL INPUT POWER (HEATING)NOMINAL RUNNING CURRENT (COOLING)NOMINAL RUNNING CURRENT (HEATING)

Page 20: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

19

Electrical Data - Heat pump (R407C)ACC 75DR ACC 100DR

A4MC 75ER A4MC 100ER

POWER SOURCE V/Ph/HzRATED INPUT POWER W 1061 1254

RATED RUNNING CURRENT A 4.51 5.79

MOTOR OUTPUT W 750 10004 4

POWER SOURCE V/Ph/HzRATED INPUT POWER WRATED RUNNING CURRENT AMOTOR OUTPUT W

N/A N/A

POWER SOURCE V/Ph/HzCAPACITOR µF NIL NIL

RATED INPUT POWER (COOLING) W 6045 9186

RATED INPUT POWER (HEATING) W 6045 7425

RATED RUNNING CURRENT (COOLING) A 11.1 15.9

RATED RUNNING CURRENT (HEATING) A 11.1 16.5

LOCKED ROTOR AMP. A 95 125

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.

SCROLL

380 - 415 / 3 / 50

350

6001.2

220 - 240 / 1 / 50

380 - 415 / 3 / 50

INDUCTION

INDUCTION

CLASS B

CLASS F

INSULATION GRADE

POLESTYPEINSULATION GRADE

TYPE

INDOOR UNITOUTDOOR UNITTYPEINSULATION GRADE

MODEL

INDOOR MOTOR

OUTDOOR MOTOR

COMPRESSOR

Page 21: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

20

Components Data (R407C)ACC 75DR ACC 100DR

A4MC 75ER A4MC 100ER

2ZINC COATED STEEL ZINC COATED STEEL

DIRECT DIRECTmm/in 228.6 / 9.0 228.6 / 9.0mm/in 177.8 / 7.0 228.6 / 9.0

1N/A N/A

mm/in

N/A N/A

SONTEX 200 LT SONTEX 200 LTOIL AMOUNT cm3 2513 3253

S. I. G. C. SEAMLESS COPPERDIAMETER mm/in 9.52 / 3/8 9.52 / 3/8THICKNESS mm/in 0.35 / 0.013 0.35 / 0.013

ALUMINIUM ALUMINIUM THICKNESS mm/in 0.127 / 0.005 0.127 / 0.005FACE AREA m2/ft2 0.45 / 4.89 0.55 / 5.89

412 14

S. I. G. C. SEAMLESS COPPERDIAMETER mm/in 9.52 / 3/8 9.52 / 3/8THICKNESS mm/in 0.35 / 0.013 0.35 / 0.013

ALUMINIUM ALUMINIUM THICKNESS mm/in 0.127 / 0.005 0.127 / 0.005FACE AREA m2/ft2 2.29 / 24.72 2.29 / 24.72

120 16

WIDTH mm/in 665 / 26.1 780 / 30.7HEIGHT mm/in 345 / 13.9 345 / 13.9

QUANTITY pc 2MATERIALFINSIHINGCOLOUR

MATERIALFINISHINGCOLOUR

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

EPOXY POLYESTER POWDER

-

GALVANIZED MILD STEEL

WHITE

ELECTRO GALVANIZED STEEL

-

1

CENTRIFUGAL

ALUMINIUM

SCROLL

INDUCTION

PROPELLER1

DIRECT812.8 / 32.0INDUCTION

FILTRATION

CASING

INDOOR UNIT

OUTDOOR UNIT

TYPE

SIZE

INDOOR COIL

OUTDOOR COIL

FIN

FIN

TUBE

TUBE

INDOOR UNITOUTDOOR UNIT

MODEL

TYPE

LENGTH

INDOOR FAN

TYPEQ'TYINDOOR FAN

MOTOR

Q'TYMATERIALDRIVEDIAMETER

INDEX OF PROTECTION (IP)

Q'TYOUTDOOR FAN MOTOR

OUTDOOR FAN MATERIALDRIVEDIAMETERTYPE

TYPEQ'TY

COMPRESSORTYPEOIL TYPE

INDEX OF PROTECTION (IP)

WASHABLE SARANET FILTER

MATERIAL

MATERIAL

ROWFIN PER INCHMATERIAL

MATERIAL

ROWFIN PER INCH

2

2

4

1

2

Page 22: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

21

Safety Devices

ACC 75D ACC 100DA4MC 75D A4MC 100D

TYPE AUTO RESET AUTO RESET

SETTING 426 psi OFF 426 psi OFF

TYPE AUTO RESET AUTO RESET

SETTING 18 psi OFF 18 psi OFF

AVAILABLE AVAILABLE

DISCHARGE THERMOSTAT SETTING 130 oC 130 oC

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

MODEL

SAFETY DEVICE

INDOOR UNITOUTDOOR UNIT

PHASE SEQUENCER

HIGH PRESSURE SWITCH

LOW PRESSURE SWITCH

ACC 75DR ACC 100DRA4MC 75ER A4MC 100ER

TYPE AUTO RESET AUTO RESET

SETTING 426 psi OFF 426 psi OFF

TYPE AUTO RESET AUTO RESET

SETTING 7 psi OFF 7 psi OFF

AVAILABLE AVAILABLE

DISCHARGE THERMOSTAT SETTING 130 oC 130 oC

1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.

MODEL

SAFETY DEVICE

INDOOR UNITOUTDOOR UNIT

PHASE SEQUENCER

HIGH PRESSURE SWITCH

LOW PRESSURE SWITCH

Page 23: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

5. OPERATING RANGE

Ensure the operating temperature is in allowable range.

Cooling only

Heatpump

22

Caution :

The use of your air conditioneroutside the range of workingtemperature and humidity canresult in serious failure.

Out

door

tem

p. (°

CD

B)

Indoor temp. (°CWB)

-5

19

35

15

46

24

54

Standardpoint

High ambientunit

Low ambient kit

Indoor temp. (°CDB)

Heating

Out

door

tem

p. (°

CW

B)

-9

15 21

6

27

18

Standardpoint

Cooling

Out

door

tem

p. (°

CD

B)

Indoor temp. (°CWB)

-5

19

35

15

46

24

54High ambient

unit

Low ambient kit

Standardpoint

Standard operating range.

With High ambient unit. (Optional item) Please refer to local dealer for unit of this specification.

With Low ambient kit. (Optional item) Please refer to local dealer for unit of this specification.

Note :

Page 24: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

6. SOUND DATA

23

Ext. Static Speed Overall Noise (mmAq) 125 250 500 1000 2000 4000 8000 (dBA) Criteria

20 SH 52 49 49 48 45 40 33 52 4714 Hi 51 49 48 47 44 40 33 52 4610 Me 48 46 46 45 40 34 26 48 447 Lo 43 40 42 38 36 30 19 43 37

Ext. Static Speed Overall Noise (mmAq) 125 250 500 1000 2000 4000 8000 (dBA) Criteria

20 SH 60 54 51 51 49 44 37 55 5014 Hi 59 52 50 50 48 42 36 54 4910 Me 55 51 49 47 44 38 31 52 467 Lo 55 47 47 43 40 33 26 48 43

Microphone position: 1.4m below the centre of the unit.(Tested with 2m length duct at the air discharge outlet and air return inlet)

1/1 Octave sound Pressure Level (dB, reference 20Pa)ACC 75D/DR

ACC 100D/DR1/1 Octave sound Pressure Level (dB, reference 20Pa)

Page 25: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

NC CURVES

24

ACC 75D/DR NC CURVES

0

10

20

30

40

50

60

70

125 250 500 1000 2000 4000 8000

Octave-band Frequency (Hz)

Sou

nd P

ress

ure

Leve

l (dB

, ref

20µ

Pa)

NC-20

NC-25

NC-30

NC-35

NC-40

NC-45

NC-50

SH FAN

HI FAN

ME FAN

LO FAN

ACC 100D/DR NC CURVES

0

10

20

30

40

50

60

70

125 250 500 1000 2000 4000 8000

Octave-band Frequency (Hz)

Sou

nd P

ress

ure

Leve

l (dB

, ref

20µ

Pa)

NC-20

NC-25

NC-30

NC-35

NC-40

NC-45

NC-50

SH FAN

LO FAN

ME FAN

HI FAN

Page 26: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

5. PERFORMANCE TABLE 5. PERFORMANCE TABLE 7. PERFORMANCE TABLE

25

Interpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity, SC at those temperatures which are not stated out in the table. Example: Model: ACC 75D – AMC 75D Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 37°C DB Solution: Overall Based on the Performance table on Pg. 29,

1. Refer to the Indoor DB column, - 23°C is located between 20°C and 24°C (Thus, Interpolation need to be applied)

2. Refer to the Indoor WB column, - 15°C only available in the case of Indoor DB = 20°C. (Thus, Extrapolation between 16°C

WB and 17°C WB during 24°C indoor DB is required)

3. Refer to the Outdoor DB column, - 37°C is located between 35°C and 40°C. (Thus, Interpolation need to be applied)

Please follow the steps below in order to get the required capacity.

3rd Step Interpolation of Outdoor DB Find TC, SC for (a) Indoor: 23°C DB, 15°C WB Outdoor: 37°C DB

2nd Step Interpolation of Indoor DB Find TC, SC for (a) Indoor: 23°C DB, 15°C WB Outdoor: 35°C DB (b) Indoor: 23°C DB, 15°C WB Outdoor: 40°C DB

1st Step Extrapolation of Indoor WB Find TC, SC for (a) Indoor: 24°C DB, 15°C WB Outdoor: 35°C DB (b) Indoor: 24°C DB, 15°C WB Outdoor: 40°C DB

Page 27: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

26

Details: 1st Step: To obtain the Total capacity and Sensible capacity for

(a) Indoor Condition: 24°C DB, 15°C WB Outdoor Condition: 35°C DB

Outdoor DB, °C 35

Indoor DB

°C

Indoor WB

°C TC (kW) SC (kW)

15 x1 y1 16 20.229 15.040

24

17 20.744 14.517 Total capacity, TC

1x = 19.713kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)* Sensible capacity, SC Extrapolation Method:

15.040kWkW -517.14

ykW -517.14C16°°C -17C15°C -17° 1

1y = 15.563kW

(b) Indoor Condition: 24°C DB, 15°C WB Outdoor Condition: 40°C DB

Outdoor DB, °C 40

Indoor DB

°C

Indoor WB

°C TC (kW) SC (kW)

15 x2 y2 16 18.776 13.808

24

17 19.366 13.463 Total capacity, TC

2x = 18.186kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)* Sensible capacity, SC Extrapolation Method:

13.808kW13.463kW -

ykW -463.13C16°C -17°C15°C -17° 2

2y = 14.153kW

* This is due to 2 different conditions with same WB temperature, will have the same level of enthalpy. For more details, please refer to psychrometrics chart

Page 28: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

27

2nd Step: To obtain the Total capacity and Sensible capacity for

(a) Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 35°C DB

Outdoor DB, °C 35

Indoor DB

°C

Indoor WB

°C TC (kW) SC (kW)

20 15 19.173 11.110 23 15 x3 y3 24 15 19.173 15.563

Total capacity, TC

3x = 19.173kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)* Sensible capacity, SC Interpolation Method:

3ykW -563.15

11.110kWkW - 563.15C23°C - 24°C20°C - 24°

3y = 14.450kW

(b) Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 40°C DB

Outdoor DB, °C 40

Indoor DB

°C

Indoor WB

°C TC (kW) SC (kW)

20 15 18.186 9.698 23 15 x4 y4 24 15 18.186 14.153

Total capacity, TC

4x = 18.186kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)* Sensible capacity, SC Interpolation Method:

1ykW -153.14

9.698kWkW - 153.14C23C -24°C20°C -24°

4y = 13.039kW

* This is due to 2 different conditions with same WB temperature will have the same level of enthalpy. For more details, please refer to psychrometrics chart

Page 29: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

28

3rd Step: To obtain the Total capacity and Sensible capacity for

(a) Indoor Condition: 23°C DB, 15°C WB Outdoor Condition: 37°C DB

Outdoor DB, °C 35 37 40

Indoor DB

°C

Indoor WB

°C TC (kW) SC (kW) TC (kW) SC (kW) TC (kW) SC (kW)

23 15 19.713 14.450 x y 18.186 13.039 Total capacity, TC Interpolation Method:

x

18.186kW -

19.713kWkW -186.18C37°C -40°C35°C -40°

x = 19.102kW

Sensible capacity, SC Interpolation Method:

ykW -039.1314.450kWkW -039.13

C37°C -40°C35°C -40°

y = 13.886kW

Page 30: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

29

R22 MODELS(COOLING ONLY)

MODEL : ACC 75D / AMC 75D

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 24.294 15.345 22.767 13.934 21.240 12.522 19.713 11.110 18.186 9.698 16.354 8.00416 24.586 14.284 23.133 13.052 21.681 11.819 20.229 10.587 18.776 9.354 17.033 7.87516 24.586 18.738 23.133 17.505 21.681 16.273 20.229 15.040 18.776 13.808 17.033 12.32917 24.877 17.677 23.500 16.623 22.122 15.570 20.744 14.517 19.366 13.463 17.713 12.19918 25.169 16.616 23.866 15.742 22.563 14.867 21.260 13.993 19.956 13.119 18.392 12.07019 25.461 15.555 24.233 14.860 23.004 14.164 21.775 13.469 20.546 12.774 19.072 11.94020 25.750 14.484 24.572 13.887 23.393 13.290 22.215 12.693 21.036 12.096 19.622 11.38018 25.169 21.069 23.866 20.195 22.563 19.321 21.260 18.447 19.956 17.572 18.392 16.52319 25.461 20.008 24.233 19.313 23.004 18.618 21.775 17.923 20.546 17.228 19.072 16.39420 25.750 18.938 24.572 18.341 23.393 17.744 22.215 17.147 21.036 16.550 19.622 15.83321 26.038 17.860 24.893 17.308 23.748 16.755 22.603 16.202 21.459 15.649 20.085 14.98622 26.325 16.783 25.214 16.274 24.103 15.766 22.992 15.257 21.882 14.749 20.549 14.13823 26.612 15.706 25.535 15.241 24.458 14.777 23.381 14.313 22.304 13.848 21.012 13.29124 26.899 14.629 25.856 14.208 24.813 13.788 23.770 13.368 22.727 12.948 21.476 12.44320 25.750 21.164 24.572 20.567 23.393 19.971 22.215 19.374 21.036 18.777 19.622 18.06021 26.038 20.087 24.893 19.534 23.748 18.982 22.603 18.429 21.459 17.876 20.085 17.21322 26.325 19.010 25.214 18.501 24.103 17.993 22.992 17.484 21.882 16.976 20.549 16.36523 26.612 17.933 25.535 17.468 24.458 17.004 23.381 16.539 22.304 16.075 21.012 15.51824 26.899 16.855 25.856 16.435 24.813 16.015 23.770 15.595 22.727 15.174 21.476 14.670

MODEL : ACC 100D / AMC 100D

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 30.592 19.623 28.908 18.136 27.224 16.650 25.540 15.163 23.856 13.676 21.835 11.89216 31.345 18.451 29.695 17.179 28.046 15.906 26.396 14.634 24.747 13.362 22.767 11.83516 31.345 23.736 29.695 22.464 28.046 21.192 26.396 19.919 24.747 18.647 22.767 17.12017 32.098 22.565 30.483 21.507 28.868 20.448 27.253 19.390 25.638 18.332 23.700 17.06218 32.851 21.393 31.270 20.549 29.690 19.705 28.109 18.861 26.529 18.017 24.632 17.00419 33.603 20.222 32.057 19.592 30.512 18.962 28.966 18.332 27.420 17.702 25.565 16.94620 34.351 19.034 32.801 18.482 31.251 17.930 29.700 17.378 28.150 16.825 26.290 16.16318 32.851 26.679 31.270 25.835 29.690 24.991 28.109 24.146 26.529 23.302 24.632 22.29019 33.603 25.507 32.057 24.877 30.512 24.247 28.966 23.617 27.420 22.988 25.565 22.23220 34.351 24.319 32.801 23.767 31.251 23.215 29.700 22.663 28.150 22.111 26.290 21.44821 35.096 23.120 33.515 22.555 31.935 21.990 30.354 21.425 28.773 20.859 26.876 20.18122 35.841 21.922 34.230 21.343 32.618 20.765 31.007 20.186 29.396 19.608 27.462 18.91423 36.586 20.723 34.944 20.131 33.302 19.539 31.660 18.948 30.018 18.356 28.048 17.64624 37.331 19.524 35.659 18.919 33.986 18.314 32.314 17.709 30.641 17.105 28.634 16.37920 34.351 26.962 32.801 26.410 31.251 25.858 29.700 25.306 28.150 24.753 26.290 24.09121 35.096 25.763 33.515 25.198 31.935 24.632 30.354 24.067 28.773 23.502 26.876 22.82422 35.841 24.564 34.230 23.986 32.618 23.407 31.007 22.829 29.396 22.250 27.462 21.55623 36.586 23.365 34.944 22.774 33.302 22.182 31.660 21.590 30.018 20.999 28.048 20.28924 37.331 22.166 35.659 21.562 33.986 20.957 32.314 20.352 30.641 19.747 28.634 19.022

20

24

28

30

ID DB°C ID WB°COutdoor DB°C

20 25 30 35 40 46

20

24

28

30

ID DB°C ID WB°COutdoor DB°C

20 25 30 35 40 46

Page 31: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

30

R22 MODELS(HEATPUMP)

MODEL : ACC 75DR / AMC 75ERCOOLING MODE

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 24.294 15.345 22.767 13.934 21.240 12.522 19.713 11.110 18.186 9.698 16.354 8.00416 24.586 14.284 23.133 13.052 21.681 11.819 20.229 10.587 18.776 9.354 17.033 7.87516 24.586 18.738 23.133 17.505 21.681 16.273 20.229 15.040 18.776 13.808 17.033 12.32917 24.877 17.677 23.500 16.623 22.122 15.570 20.744 14.517 19.366 13.463 17.713 12.19918 25.169 16.616 23.866 15.742 22.563 14.867 21.260 13.993 19.956 13.119 18.392 12.07019 25.461 15.555 24.233 14.860 23.004 14.164 21.775 13.469 20.546 12.774 19.072 11.94020 25.750 14.484 24.572 13.887 23.393 13.290 22.215 12.693 21.036 12.096 19.622 11.38018 25.169 21.069 23.866 20.195 22.563 19.321 21.260 18.447 19.956 17.572 18.392 16.52319 25.461 20.008 24.233 19.313 23.004 18.618 21.775 17.923 20.546 17.228 19.072 16.39420 25.750 18.938 24.572 18.341 23.393 17.744 22.215 17.147 21.036 16.550 19.622 15.83321 26.038 17.860 24.893 17.308 23.748 16.755 22.603 16.202 21.459 15.649 20.085 14.98622 26.325 16.783 25.214 16.274 24.103 15.766 22.992 15.257 21.882 14.749 20.549 14.13823 26.612 15.706 25.535 15.241 24.458 14.777 23.381 14.313 22.304 13.848 21.012 13.29124 26.899 14.629 25.856 14.208 24.813 13.788 23.770 13.368 22.727 12.948 21.476 12.44320 25.750 21.164 24.572 20.567 23.393 19.971 22.215 19.374 21.036 18.777 19.622 18.06021 26.038 20.087 24.893 19.534 23.748 18.982 22.603 18.429 21.459 17.876 20.085 17.21322 26.325 19.010 25.214 18.501 24.103 17.993 22.992 17.484 21.882 16.976 20.549 16.36523 26.612 17.933 25.535 17.468 24.458 17.004 23.381 16.539 22.304 16.075 21.012 15.51824 26.899 16.855 25.856 16.435 24.813 16.015 23.770 15.595 22.727 15.174 21.476 14.670

HEATING MODE

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 15.812 15.812 17.812 17.812 18.478 18.478 25.812 25.812 29.812 29.812 31.812 31.812 33.812 33.81217 15.621 15.621 17.640 17.640 18.313 18.313 25.414 25.414 29.546 29.546 31.529 31.529 33.511 33.51119 15.431 15.431 17.468 17.468 18.147 18.147 25.017 25.017 29.280 29.280 31.245 31.245 33.210 33.21021 15.240 15.240 17.296 17.296 17.981 17.981 24.619 24.619 29.014 29.014 30.961 30.961 32.908 32.90823 15.149 15.149 17.149 17.149 17.816 17.816 24.564 24.564 28.748 28.748 30.678 30.678 32.607 32.60725 15.058 15.058 17.002 17.002 17.650 17.650 24.510 24.510 28.482 28.482 30.394 30.394 32.306 32.30627 14.967 14.967 16.855 16.855 17.485 17.485 24.455 24.455 28.217 28.217 30.110 30.110 32.004 32.004

ID DB°C ID WB°COutdoor DB°C

20 25 30 35 40 46

20

24

28

30

FROST REGION

ID DB°COutdoor WB°C

-9 -6 -5 6 12 15 18

Page 32: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

31

R22 MODELS(HEATPUMP)

MODEL : ACC 100D / AMC 100ERCOOLING MODE

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 30.592 19.623 28.908 18.136 27.224 16.650 25.540 15.163 23.856 13.676 21.835 11.89216 31.345 18.451 29.695 17.179 28.046 15.906 26.396 14.634 24.747 13.362 22.767 11.83516 31.345 23.736 29.695 22.464 28.046 21.192 26.396 19.919 24.747 18.647 22.767 17.12017 32.098 22.565 30.483 21.507 28.868 20.448 27.253 19.390 25.638 18.332 23.700 17.06218 32.851 21.393 31.270 20.549 29.690 19.705 28.109 18.861 26.529 18.017 24.632 17.00419 33.603 20.222 32.057 19.592 30.512 18.962 28.966 18.332 27.420 17.702 25.565 16.94620 34.351 19.034 32.801 18.482 31.251 17.930 29.700 17.378 28.150 16.825 26.290 16.16318 32.851 26.679 31.270 25.835 29.690 24.991 28.109 24.146 26.529 23.302 24.632 22.29019 33.603 25.507 32.057 24.877 30.512 24.247 28.966 23.617 27.420 22.988 25.565 22.23220 34.351 24.319 32.801 23.767 31.251 23.215 29.700 22.663 28.150 22.111 26.290 21.44821 35.096 23.120 33.515 22.555 31.935 21.990 30.354 21.425 28.773 20.859 26.876 20.18122 35.841 21.922 34.230 21.343 32.618 20.765 31.007 20.186 29.396 19.608 27.462 18.91423 36.586 20.723 34.944 20.131 33.302 19.539 31.660 18.948 30.018 18.356 28.048 17.64624 37.331 19.524 35.659 18.919 33.986 18.314 32.314 17.709 30.641 17.105 28.634 16.37920 34.351 26.962 32.801 26.410 31.251 25.858 29.700 25.306 28.150 24.753 26.290 24.09121 35.096 25.763 33.515 25.198 31.935 24.632 30.354 24.067 28.773 23.502 26.876 22.82422 35.841 24.564 34.230 23.986 32.618 23.407 31.007 22.829 29.396 22.250 27.462 21.55623 36.586 23.365 34.944 22.774 33.302 22.182 31.660 21.590 30.018 20.999 28.048 20.28924 37.331 22.166 35.659 21.562 33.986 20.957 32.314 20.352 30.641 19.747 28.634 19.022

HEATING MODE

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 23.133 23.133 24.838 24.838 25.406 25.406 31.659 31.659 35.069 35.069 36.775 36.775 38.480 38.48017 23.140 23.140 24.669 24.669 25.178 25.178 31.852 31.852 34.756 34.756 36.447 36.447 38.137 38.13719 23.147 23.147 24.500 24.500 24.951 24.951 32.046 32.046 34.444 34.444 36.119 36.119 37.794 37.79421 23.154 23.154 24.330 24.330 24.723 24.723 32.239 32.239 34.131 34.131 35.791 35.791 37.451 37.45123 22.720 22.720 24.051 24.051 24.495 24.495 31.455 31.455 33.818 33.818 35.463 35.463 37.108 37.10825 22.285 22.285 23.772 23.772 24.267 24.267 30.670 30.670 33.505 33.505 35.135 35.135 36.765 36.76527 21.851 21.851 23.492 23.492 24.039 24.039 29.886 29.886 33.192 33.192 34.807 34.807 36.422 36.422

ID DB°C ID WB°COutdoor DB°C

20 25 30 35 40 46

20

24

28

30

FROST REGION

ID DB°COutdoor WB°C

-9 -6 -5 6 12 15 18

Page 33: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

32

R407C MODELS(COOLING ONLY)

MODEL : ACC 75D / A4MC 75D

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 24.294 15.345 22.767 13.934 21.240 12.522 19.713 11.110 18.186 9.698 16.354 8.00416 24.586 14.284 23.133 13.052 21.681 11.819 20.229 10.587 18.776 9.354 17.033 7.87516 24.586 18.738 23.133 17.505 21.681 16.273 20.229 15.040 18.776 13.808 17.033 12.32917 24.877 17.677 23.500 16.623 22.122 15.570 20.744 14.517 19.366 13.463 17.713 12.19918 25.169 16.616 23.866 15.742 22.563 14.867 21.260 13.993 19.956 13.119 18.392 12.07019 25.461 15.555 24.233 14.860 23.004 14.164 21.775 13.469 20.546 12.774 19.072 11.94020 25.750 14.484 24.572 13.887 23.393 13.290 22.215 12.693 21.036 12.096 19.622 11.38018 25.169 21.069 23.866 20.195 22.563 19.321 21.260 18.447 19.956 17.572 18.392 16.52319 25.461 20.008 24.233 19.313 23.004 18.618 21.775 17.923 20.546 17.228 19.072 16.39420 25.750 18.938 24.572 18.341 23.393 17.744 22.215 17.147 21.036 16.550 19.622 15.83321 26.038 17.860 24.893 17.308 23.748 16.755 22.603 16.202 21.459 15.649 20.085 14.98622 26.325 16.783 25.214 16.274 24.103 15.766 22.992 15.257 21.882 14.749 20.549 14.13823 26.612 15.706 25.535 15.241 24.458 14.777 23.381 14.313 22.304 13.848 21.012 13.29124 26.899 14.629 25.856 14.208 24.813 13.788 23.770 13.368 22.727 12.948 21.476 12.44320 25.750 21.164 24.572 20.567 23.393 19.971 22.215 19.374 21.036 18.777 19.622 18.06021 26.038 20.087 24.893 19.534 23.748 18.982 22.603 18.429 21.459 17.876 20.085 17.21322 26.325 19.010 25.214 18.501 24.103 17.993 22.992 17.484 21.882 16.976 20.549 16.36523 26.612 17.933 25.535 17.468 24.458 17.004 23.381 16.539 22.304 16.075 21.012 15.51824 26.899 16.855 25.856 16.435 24.813 16.015 23.770 15.595 22.727 15.174 21.476 14.670

MODEL : ACC 100D / A4MC 100D

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 30.592 19.623 28.908 18.136 27.224 16.650 25.540 15.163 23.856 13.676 21.835 11.89216 31.345 18.451 29.695 17.179 28.046 15.906 26.396 14.634 24.747 13.362 22.767 11.83516 31.345 23.736 29.695 22.464 28.046 21.192 26.396 19.919 24.747 18.647 22.767 17.12017 32.098 22.565 30.483 21.507 28.868 20.448 27.253 19.390 25.638 18.332 23.700 17.06218 32.851 21.393 31.270 20.549 29.690 19.705 28.109 18.861 26.529 18.017 24.632 17.00419 33.603 20.222 32.057 19.592 30.512 18.962 28.966 18.332 27.420 17.702 25.565 16.94620 34.351 19.034 32.801 18.482 31.251 17.930 29.700 17.378 28.150 16.825 26.290 16.16318 32.851 26.679 31.270 25.835 29.690 24.991 28.109 24.146 26.529 23.302 24.632 22.29019 33.603 25.507 32.057 24.877 30.512 24.247 28.966 23.617 27.420 22.988 25.565 22.23220 34.351 24.319 32.801 23.767 31.251 23.215 29.700 22.663 28.150 22.111 26.290 21.44821 35.096 23.120 33.515 22.555 31.935 21.990 30.354 21.425 28.773 20.859 26.876 20.18122 35.841 21.922 34.230 21.343 32.618 20.765 31.007 20.186 29.396 19.608 27.462 18.91423 36.586 20.723 34.944 20.131 33.302 19.539 31.660 18.948 30.018 18.356 28.048 17.64624 37.331 19.524 35.659 18.919 33.986 18.314 32.314 17.709 30.641 17.105 28.634 16.37920 34.351 26.962 32.801 26.410 31.251 25.858 29.700 25.306 28.150 24.753 26.290 24.09121 35.096 25.763 33.515 25.198 31.935 24.632 30.354 24.067 28.773 23.502 26.876 22.82422 35.841 24.564 34.230 23.986 32.618 23.407 31.007 22.829 29.396 22.250 27.462 21.55623 36.586 23.365 34.944 22.774 33.302 22.182 31.660 21.590 30.018 20.999 28.048 20.28924 37.331 22.166 35.659 21.562 33.986 20.957 32.314 20.352 30.641 19.747 28.634 19.022

ID DB°C ID WB°COutdoor DB°C

20 25 30 35 40 46

20

24

28

30

ID DB°C ID WB°COutdoor DB°C

20 25 30 35 40 46

20

24

28

30

Page 34: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

33

R407C MODELS(HEATPUMP)

MODEL : ACC 75DR / A4MC 75ERCOOLING MODE

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 24.294 15.345 22.767 13.934 21.240 12.522 19.713 11.110 18.186 9.698 16.354 8.00416 24.586 14.284 23.133 13.052 21.681 11.819 20.229 10.587 18.776 9.354 17.033 7.87516 24.586 18.738 23.133 17.505 21.681 16.273 20.229 15.040 18.776 13.808 17.033 12.32917 24.877 17.677 23.500 16.623 22.122 15.570 20.744 14.517 19.366 13.463 17.713 12.19918 25.169 16.616 23.866 15.742 22.563 14.867 21.260 13.993 19.956 13.119 18.392 12.07019 25.461 15.555 24.233 14.860 23.004 14.164 21.775 13.469 20.546 12.774 19.072 11.94020 25.750 14.484 24.572 13.887 23.393 13.290 22.215 12.693 21.036 12.096 19.622 11.38018 25.169 21.069 23.866 20.195 22.563 19.321 21.260 18.447 19.956 17.572 18.392 16.52319 25.461 20.008 24.233 19.313 23.004 18.618 21.775 17.923 20.546 17.228 19.072 16.39420 25.750 18.938 24.572 18.341 23.393 17.744 22.215 17.147 21.036 16.550 19.622 15.83321 26.038 17.860 24.893 17.308 23.748 16.755 22.603 16.202 21.459 15.649 20.085 14.98622 26.325 16.783 25.214 16.274 24.103 15.766 22.992 15.257 21.882 14.749 20.549 14.13823 26.612 15.706 25.535 15.241 24.458 14.777 23.381 14.313 22.304 13.848 21.012 13.29124 26.899 14.629 25.856 14.208 24.813 13.788 23.770 13.368 22.727 12.948 21.476 12.44320 25.750 21.164 24.572 20.567 23.393 19.971 22.215 19.374 21.036 18.777 19.622 18.06021 26.038 20.087 24.893 19.534 23.748 18.982 22.603 18.429 21.459 17.876 20.085 17.21322 26.325 19.010 25.214 18.501 24.103 17.993 22.992 17.484 21.882 16.976 20.549 16.36523 26.612 17.933 25.535 17.468 24.458 17.004 23.381 16.539 22.304 16.075 21.012 15.51824 26.899 16.855 25.856 16.435 24.813 16.015 23.770 15.595 22.727 15.174 21.476 14.670

HEATING MODE

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 15.812 15.812 17.812 17.812 18.478 18.478 25.812 25.812 29.812 29.812 31.812 31.812 33.812 33.81217 15.621 15.621 17.640 17.640 18.313 18.313 25.414 25.414 29.546 29.546 31.529 31.529 33.511 33.51119 15.431 15.431 17.468 17.468 18.147 18.147 25.017 25.017 29.280 29.280 31.245 31.245 33.210 33.21021 15.240 15.240 17.296 17.296 17.981 17.981 24.619 24.619 29.014 29.014 30.961 30.961 32.908 32.90823 15.149 15.149 17.149 17.149 17.816 17.816 24.564 24.564 28.748 28.748 30.678 30.678 32.607 32.60725 15.058 15.058 17.002 17.002 17.650 17.650 24.510 24.510 28.482 28.482 30.394 30.394 32.306 32.30627 14.967 14.967 16.855 16.855 17.485 17.485 24.455 24.455 28.217 28.217 30.110 30.110 32.004 32.004

ID DB°C ID WB°COutdoor DB°C

20 25 30 35 40 46

20

24

28

30

FROST REGION

ID DB°COutdoor WB°C

-9 -6 -5 6 12 15 18

Page 35: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

34

R407C MODELS(HEATPUMP)

MODEL : ACC 100D / A4MC 100ERCOOLING MODE

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 30.592 19.623 28.908 18.136 27.224 16.650 25.540 15.163 23.856 13.676 21.835 11.89216 31.345 18.451 29.695 17.179 28.046 15.906 26.396 14.634 24.747 13.362 22.767 11.83516 31.345 23.736 29.695 22.464 28.046 21.192 26.396 19.919 24.747 18.647 22.767 17.12017 32.098 22.565 30.483 21.507 28.868 20.448 27.253 19.390 25.638 18.332 23.700 17.06218 32.851 21.393 31.270 20.549 29.690 19.705 28.109 18.861 26.529 18.017 24.632 17.00419 33.603 20.222 32.057 19.592 30.512 18.962 28.966 18.332 27.420 17.702 25.565 16.94620 34.351 19.034 32.801 18.482 31.251 17.930 29.700 17.378 28.150 16.825 26.290 16.16318 32.851 26.679 31.270 25.835 29.690 24.991 28.109 24.146 26.529 23.302 24.632 22.29019 33.603 25.507 32.057 24.877 30.512 24.247 28.966 23.617 27.420 22.988 25.565 22.23220 34.351 24.319 32.801 23.767 31.251 23.215 29.700 22.663 28.150 22.111 26.290 21.44821 35.096 23.120 33.515 22.555 31.935 21.990 30.354 21.425 28.773 20.859 26.876 20.18122 35.841 21.922 34.230 21.343 32.618 20.765 31.007 20.186 29.396 19.608 27.462 18.91423 36.586 20.723 34.944 20.131 33.302 19.539 31.660 18.948 30.018 18.356 28.048 17.64624 37.331 19.524 35.659 18.919 33.986 18.314 32.314 17.709 30.641 17.105 28.634 16.37920 34.351 26.962 32.801 26.410 31.251 25.858 29.700 25.306 28.150 24.753 26.290 24.09121 35.096 25.763 33.515 25.198 31.935 24.632 30.354 24.067 28.773 23.502 26.876 22.82422 35.841 24.564 34.230 23.986 32.618 23.407 31.007 22.829 29.396 22.250 27.462 21.55623 36.586 23.365 34.944 22.774 33.302 22.182 31.660 21.590 30.018 20.999 28.048 20.28924 37.331 22.166 35.659 21.562 33.986 20.957 32.314 20.352 30.641 19.747 28.634 19.022

HEATING MODE

TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW) TC(kW) SC(kW)15 23.133 23.133 24.838 24.838 25.406 25.406 31.659 31.659 35.069 35.069 36.775 36.775 38.480 38.48017 23.140 23.140 24.669 24.669 25.178 25.178 31.852 31.852 34.756 34.756 36.447 36.447 38.137 38.13719 23.147 23.147 24.500 24.500 24.951 24.951 32.046 32.046 34.444 34.444 36.119 36.119 37.794 37.79421 23.154 23.154 24.330 24.330 24.723 24.723 32.239 32.239 34.131 34.131 35.791 35.791 37.451 37.45123 22.720 22.720 24.051 24.051 24.495 24.495 31.455 31.455 33.818 33.818 35.463 35.463 37.108 37.10825 22.285 22.285 23.772 23.772 24.267 24.267 30.670 30.670 33.505 33.505 35.135 35.135 36.765 36.76527 21.851 21.851 23.492 23.492 24.039 24.039 29.886 29.886 33.192 33.192 34.807 34.807 36.422 36.422

ID DB°C ID WB°COutdoor DB°C

20 25 30 35 40 46

20

24

28

30

FROST REGION

ID DB°COutdoor WB°C

-9 -6 -5 6 12 15 18

Page 36: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

8. OUTLINES AND DIMENSIONS

INDOOR UNIT MODEL : ACC 75D/DR

MODEL : ACC 100D/DR

35

Note: Dimension in mm

Note: Dimension in mm

Page 37: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

OUTDOOR UNIT MODEL : AMC / A4MC 75 / 100 D/ER

36

Note: Dimension in mm

Page 38: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

. REFRIGERANT CIRCUIT 9. REFRIGERANT CIRCUIT

MODEL : ACC 75/100D - AMC / A4MC 75/100D

MODEL : ACC 75/100DR - AMC / A4MC 75/100ER

37

Page 39: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

COOLING UNITMODEL : ACC 75/100D - AMC / A4MC 75/100D

10. WIRING DIAGRAMS

38

Page 40: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

39

MODEL : ACC 75/100DR - AMC / A4MC 75/100ER

Page 41: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

PRELIMINARY SITE SURVEY Electrical supply and installation is to conform to local authority's codes and regulations. (e.g. National Electricity Board). Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply lines must be independent of welding transformers which can cause high supply fluctuation. Ensure that the location is convenient for wiring and piping. INSTALLATION OF INDOOR UNIT The indoor unit must be installed such that there is no short circuit of the cool discharge. Comply to the installation clearance recommended. Do not put the indoor unit where there is direct sunlight on unit. Make sure the location is suitable for piping and drainage. Precautions steps :

i) Use the hanger supplied with the unit. ii) Ensure the support is strong enough to withstand the weight of the unit.

11. INSTALLATION

40

800.0 800.0

800.

0

PIPINGSDo not use contaminated or damaged copper tubings. If pipings, evaporator or condenser are exposed orhad been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, donot remove plastic/rubber plugs/caps from fittings, tubings and coils until ready to connect suction or liquidline into fittings.

OPERATIONAL CHECKAfter all electrical wiring is completed and the system is charged with refrigerant, make sure unit is operatingproperly. Check that:

a) Condenser fans are running, with warm air blowing off the condenser coil.b) Evaporator blowers are running and discharging cool air.c) Suction line inside condensing unit feels cool.d) Liquid line inside condensing unit feels warm.

ELECTRICAL CONNECTIONAs wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES forfield wiring regulations and ensure that these are complied with. Besides, observe the following generalprecautions:

a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiringwork.

b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuitbreaker for over-current protection should be provided in the exclusive line.

c) The unit must be GROUNDED to prevent possible hazard due to insulation failure.d) All wiring must be firmly connected.e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan

motors.

Page 42: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

SPECIAL PRECAUTIONS WHEN DEALING WITH REFRIGERANT R40 7C UNIT

1) WHAT IS NEW REFRIGERANT R407C? R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0) and thus conformed to the Montreal Protocol regulation. It requires Polyol-ester oil (POE) oil for its compressor's lubricant. Its refrigerant capacity and performance are about the same as the refrigerant R22.

2) COMPONENTS

Mixture weight composition R32(23%), R125(25%), R134a(52%) 3) CHARACTERISTIC

R407C liquid and vapor components have different compositions when the fluid evaporates or condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerant mixture left in the system will change and subsequently affect the system performance. DO NOT add new refrigerant to leaked system. It is recommended that the system should be evacuated thoroughly before recharging with R407C.

When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or liquid phase. Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to make certain that only original composition of R407C is being charged into the system. POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22 compressor. Extra precaution must be taken not to expose the R407C system too long to moist air.

4) CHECK LIST BEFORE INSTAL LATION/SERVICING Tubing

Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure to temporarily cover the ends of the tubing prior to installation

Compressor oil No additional charge of compressor oil is permitted.

Refrigerant No other refrigerant other that R407C

Tools Tools specifically for R407C only (must not be used for R22 or other refrigerant)

i) Manifold gauge and charging hose ii) Gas leak detector iii) Refrigerant cylinder/charging cylinder iv) Vacuum pump c/w adapter v) Flare tools vi) Refrigerant recovery machine

5) HANDLING AND INSTALL ATION GUIDELINES Like R22 system, the handling and installation of R407C system are closely similar. All precautionary measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and thorough leak check and vacuuming are equally important requirements. However, due to zeotropic nature of R407C and its hydroscopic POE oil, additional precautions must be taken to ensure optimum and trouble-free system operation. a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the

contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve type. For a heat-pump system, install a two-way flow filter dryer along the liquid line.

b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to

moist air. Residual POE oil in the piping and components can absorb moisture from the air.

41

Page 43: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

c) Ensure that the compressor is not expose to open air for more than the recommended time specified byits manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor isabout to be brazed.

d) The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level ismore stringent than R22 system so as to ensure no incompressible gas and moisture in the system.

e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is toensure that only the original composition of R407C is being delivered into the system. The liquidcomposition can be different from the vapor composition.

Composition of R407C in vapour phaseis different from liquid phase.

f) Normally, the R407C cylinder or can is being equipped with a dip pipe for liquid withdrawal. However, ifthe dip pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at thebottom.

g) When servicing leak, the top up method, commonly practiced for R22 system, is not recommended forR407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,which made up of three different components, may have changed during the leak. Consequently, a topup may not ensure that the R407C in the system is of original composition. This composition shift mayadversely affect the system performance. It is recommended that the system should be evacuatedthoroughly before recharging with R407C.

42

R32/R125/R134

33% / 33% / 34%

23% / 25% / 52%

Dip-pipe

Liquidwithdrawal

Invert cylinderwithout dip-pipe

Page 44: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

12. SERVICING AND MAINTENANCE

Warning

Disconnect from Main Supply before Servicing the air conditioner

The unit is designed to give a long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention.

Components Maintenance Procedure Recommended Schedule

Air Filters 1. Clean with a vacuum cleaner, or by tapping lightly and then washing in lukewarm water (below 40°C) With neutral soap.

2. Rinse well to dry before re-installing.

3. Note : Never use petrol, thinner, benzene or any other chemicals.

Every 2 weeks.

More frequently if required.

Indoor Unit 1. Clean away dirt or dust on grille or panel by wiping with a soft cloth soaked in lukewarm (or cold) water or neutral detergent solution.

2. Note: Never use petrol, thinner, benzene or any other volatile chemicals, which may cause plastic surface to deform.

Every 2 weeks.

More frequently if required.

Condensate Drain

Pan & Pipe

1. Check and clean. Every 3 months.

Indoor Fan 1. Check for unusual noise. As necessary.

Indoor/Outdoor Coil

1. Check and remove dirt which are clogged between fins.

2. Check and remove obstacles which hinder air flow in and out of indoor/outdoor unit.

Every month.

Every month.

Electrical 1. Check voltage, current and wiring.

2. Check faulty contacts caused by loose connections, foreign matters, etc.

Every 2 months.

Every 2 months.

Compressor 1. No maintenance needed if refrigerant circuit remains sealed. However, check for refrigerant leak at joints & fittings.

Every 6 months.

Compressor Lubrication

1. Oil is factory charged. Not necessary to add oil if circuit remains sealed.

No maintenance required.

Fan Motors Lubrication

1. All motors pre-lubricated and sealed at factory. No maintenance required.

PRE-START UP MAINTENANCE (AFTER EXTENDED SHUTDOWN) - Inspect thoroughly and clean indoor and outdoor units. - Clean or replace air filters. - Clean condensate drain line. - Clean clogged indoor and outdoor coils. - Check fan imbalance before operation. - Tighten all wiring connections and panels. - Check for refrigerant leakage.

43

Page 45: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

44

The design concept of the Condensing Unit is such that all servicing can be done from the front and side of the unit.

Upon removal of front and side panel, all the electrical "terminal box", fan and motor assembly and compressor are easilyaccessible.

Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surfaces oncequarterly. However, if a unit is installed in area subjected to much oil, mist and dust, the coil must be regularly cleaned byqualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation. Otherwise, thesystems life span might be shortened.

CAUTIONWhen the compressor is to be stopped for a long time, the crankcase heater should be energized for at least6 hours before start of operation.Do not charge OXYGEN, ACETYLENE or other flammable and poisonous gases into the refrigeration cyclewhen performing a leakage test or an airtight-test. These types of gases are extremely dangerous, becauseexplosion can occur.It is recommended that nitrogen or refrigerant be charged for these types of tests.

CAUTION FOR USEBear the following points in mind to safeguard against malfunction and breakdown.

Do not stick rods or other objects through the air outlet during operation since this may result to damage or injury

The air conditioner must not re-start within 3 minutes after shutdown. (These models are equipped with a crankcaseheater with the compressor).

Make sure the air conditioner is properly grounded by checking the ground terminal.

MAINTENANCEFor superb performance and lasting durability, please do not forget to conduct proper and regular maintenance.

Cleaning The Outdoor Unit Heat ExchangerIf you use your air conditioner for prolonged period of time, the outdoor unit heat exchanger will become dirtyimpairing its function and reducing the performance of the air conditioned. Consult your local dealer about the cleaning ofthe heat exchanger.

Page 46: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

When any air-conditioner malfunction is noted, immediately switch off the power supply to the unit, and contact the local dealer, if necessary. Some simple troubleshooting tips are given below :

FAULT CAUSE

1. Fan does not work 3 minutes after starting

• Protection against the frequent starting. Wait 3 or 4 minutes.

2. The air conditioning unit does not work

Power failure or need to replace the fuse.

The power plug is disconnected.

Possibility of making a programming error in the controller.

If the fault persist after these verifications, contact your installer.

3. The air conditioning unit does not blow sufficiently

The air filter is dirty.

The doors or windows are open.

The air entrance and exit are clogged.

The regulate temperature is not high enough.

4. The remote control light is deficient •

The batteries are discharge.

The batteries are not correctly inserted.

The assembly is not good.

5. Air discharge flow has a bad odor •

This odor can be caused by cigarette smoke particles, perfume, sweat, which stick to the coil.

Check if there is any moisture on the walls, garment, other.

Check the drain pan.

6. Condensation on the air grille of indoor unit

This is due to air humidity after a long time of operation.

The unit has a lower temperature point, increase the point and operate at high speed.

7. The water flow of air conditioning unit

• Check the condensate evacuation.

8. The air conditioning unit are noisy • “Air flow noise” : refrigerant fluid admission in evaporator.

13. TROUBLESHOOTING

45

Page 47: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

FOR COOLING ONLY MODELS OR HEAT PUMP MODELS (COOLING CYCLE) DIAGNOSIS BY FLOW CHART The following chart are efficient checking procedures for troubleshooting when these fan-coil units, are coupled with the condensing units using standard wiring. For dual circuited models, perform the procedures for each circuit. No Cooling

No Cooling ( Compresor Does Not Start )

No Voltage or Low VoltageUnit Power

Supply

EvaporatorFan Motor

Fuse ForOperation

Circuit

Single-Phase

Components Shorted

Connections Loose

OvercurrentRelay For

Evaporator Fan

High Volage or Low Voltage

Single-Phase

Evaporator FanContactor

Coil Burned

Contact Faulty

Get the Right Voltage

Repair the Power Line

Repair or Replace The Components

Tighten The Connections

Get The Right Voltage

Check The Power Supply To TheMotor : Repair When Necessary

Faulty Fan Motor

Defective Operation Switch

Change The Contactor

Repair The Contacts

Repair Or Change The Motor

Repair Or Replace The Switch

CondenserFan Motor

OvercurrentRelay For

Condenser Fan

Condenser FanContactor

CompressorContactor

High Voltage or Low Voltage

Single-Phase

Coil Burnt

Contact Faulty

Fan Motor Faulty

Other Electrical Component Faulty

Coil Burnt

Contact Faulty

Open Compressor Windings

Incorrect Wiring

Get The Right Voltage

Change The Contactor

Change The Contacts

Repair or Change The Motor

Repair or Change If Necessary

Change The Contactor

Repair The Contacts

Change The Compressor

Correct The Wiring

Running

Stop

Tripped

Faulty

Faulty

Faulty

Tripped

Blown

Running

Faulty

Stop

: Faulty : Check : Cause Remedy

Check The Power Supply To TheMotor : Repair When Necessary

46

Page 48: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

INSUFFICIENT COOLING

Insufficient Cooling

High Discharge Pressure or LowSuction PressureDual Pressure

Switch

CompressorCycling

OvercurrentRelay For

Compressor

Clogged Capillary or PressureSwitch

Switch Faulty

High Voltage or Low Voltage

Discharge GasThermostat or

InternalThermostat

Single-Phase

High Discharge Pressure AndHigh Suction Pressure

High Discharge Pressure AndLow Suction Pressure

Refrigerant Short Charge orRefrigerant Leakage

See "High Discharge Pressure" or"Low Suction Pressure"

Repair Clogging and ReplaceThe Switch If Required

Repair or Change If Necessary

Get The Right Voltage

Check The Power Line To TheCompressor : Repair When Necessary

High Suction Pressure

High Discharge Pressure or LowSuction Pressure

See "High Suction Pressure"

Running

Tripping

Cycling On

Tripping

Tripping

Loose Connections

See "High Discharge Pressure"or "High Suction Pressure"

Tighten The Connections

See "High Discharge Pressure"or "Low Suction Pressure"

Add Refrigerant. RepairLeakage If Detected.

See "High Discharge Pressure"or "Low Suction Pressure"

HIGH DISCHARGE PRESSURE High Discharge

Pressure

Clogged Condenser Coil

CondenserAir Inlet

Temperature

CondenserAir Flow

Low Fan Speed

Malfunction Of Fan CyclingSystem

Circulating Air Flow

Overcharged Refrigerant

Non-Condensable Gas

High Suction Pressure

Clean The Condenser

Check The Voltage And GetThe Right Voltage

Check The System AndRepair If RequiredSecure Space ForRequired Air Flow

Purge The Refrigerant

Restricted

High

Restricted Liquid Line

Purge The Gas

Remove The Restriction

See "High Suction Pressure"

LOW DISCHARGE PRESSURE

Low DischargePressure

Malfunction Of Fan CyclingSystem

CondenserAir Flow

Low Refrigerant Charge

Low Ambient Temperature

Check The System And Repair TheComponents If Required

Add Refrigerant

See The Unit Working Range

Excessive

47

Page 49: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

HIGH SUCTION PRESSURE High Suction

Pressure

Excessive Fresh Air IntakeEvaporator

Air InletTemperature

Insufficient Duct Insulation

Defective Compressor Valve

Reduce The Fresh Air Intake

Reinforce The Duct Insulation

Change Or Repair The Compressor

Low

Overcharged Refrigerant Purge The Refrigerant

LOW SUCTION PRESSURE

Low Suction Pressure

Clogged Air Filter

EvaporatorAir Inlet

Temperature

EvaporatorAir Flow

Restricted Duct

Low Fan Speed

Short Cycling

Faulty Thermostat

Restricted Liquid LIne AndSuction Line

Low Discharge Pressure

Clean The Air Filter

Remove The Restriction

Adjust The Fan Speed

Remove Obstacles To Air Circulation

Repair Or Replace If Necessary

Restricted

Low

Low Refrigerant Charge Add Refrigerant

See "Low Discharge Pressure"

Remove The Restriction

NOISY OPERATION

Noisy Operation

Unremoved Shipping Bolt(s)

EvaporatorFan

Compressor

Overcharged Refrigerant

Low Suction Pressure

Worn Compressor Parts

Knocking Runner

Worn Bearing

Refrigerant Short Charge

Remove The Bolt(s)

Purge The Refrigerant

See "Low Suction Pressure"

Replace Or Repair The Compressor

Fix The Runner Or Casing Properly

Noisy

Partially Clogged Clean The Dryer

Add Refrigerant

Change The Bearing

Liquid Line

ShippingBolt(s)

LiquidRefrigerantBacking Up

Noisy

Noisy

Inadequate Duct Work

Loose Fixed Screws Tighten All Fixed Screws

Check Flexible Ducts

Noisy

StrainerWhistling

48

Page 50: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

FOR HEAT PUMP MODELS By means of pressure readings :

PRESSURE PROBABLE CAUSE Data Circuit To

o

Low

A

Litt

le

Low

Nor

mal

A L

ittle

H

igh

Too

H

igh

High Side Low Side

1. Overcharged with refrigerant. 2. Non-condensable gases in refrigerant circuit (e.g. oil). 3. Obstructed air-intake/discharge. 4. Short circuiting of hot air outdoor unit.

High Side Low Side

1. Poor compression/no compression (compressor defective.) 2. Check valve stick in open position. 3. Reversing valve leaking.

High Side Low Side

1. Undercharged with refrigerant. 2. Refrigerant leakage. 3. Air filter clogged/dirty (indoor unit). 4. Indoor fan locked. 5. Defective defrost control, outdoor coil freeze up (heating). 6. Outdoor fan locked (heating).

High Side Low Side

1. Outdoor fan blocked (cooling). 2. Outdoor coil dirty (cooling). 3. Indoor fan locked (heating). 4. Indoor filter clogged/dirty (heating). 5. Non-condensable gases in refrigerant circuit (e.g. air)

High Side Low Side

1. Air intake temperature of indoor unit too high.

BY MEANS OF DIAGNOSIS FLOW CHART Generally, there are two kind of problems, i.e. starting failure and insufficient cooling/heating. "Starting Failure" is caused by electrical defect while "Insufficient Cooling/Heating" is caused by improper application or defects in refrigerant circuit.

No Cooling / Heating

Unit fail to startCheck power supply- voltage- phase- frequency

Check settings of remote control box

Compressor fails to start

Check circuit breake & fuseCheck power source cord

Fan fails to start

Fan Motor Capacitor defective

Loose Connections,Contactors

Irregular motor resistance (Ω )& insulation (M Ω )

Replace Fan Motor

Compressor Motor damaged ( to replace compressor)

Thermostat setting too high

Protection Device Actuated

Reset

Compressor locked (to replace compressor)

Voltage supply not within range

Check motor resistance ( Ω ) and insulation (M Ω )

CompressorCapacitor Defective

Loose Connections,Improper wiring

Regular but failsto start Irregular

i) DIAGNOSIS OF ELECTRIC CIRCUIT

49

Page 51: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

The most common causes of air conditioner failure to “start" are: a) Voltage not within ±10% of rated voltage. b) Power supply interrupted. c) Control settings improper. d) Air conditioner is disconnected from main power source. e) Fuse blown or circuit breaker off. ii) DIAGNOSIS OF REFRIGERANT CIRCUIT / APPLICATION There might be some cases where the unit starts running but does not perform satisfactory, i.e. insufficient cooling. Judgement could be made by measuring temperature difference of indoor unit's intake and discharge air as well as running current.

Insufficient Cooling

Unit Starts

Excessive heatsource e.g. electrickettle

High heat load

Refrigerant circuit

Leakage

Restriction e.g. atstrainer, capillary,filter dryer, etc.

Compressor

Less or no compression(Low running current)

Room overcrowdedwith people

Windows / doorswide open

Check air circulation

Indoor/Outdoor coil dirty(clogged)

Air filters dirty

Fan Malfunction

Obstruction at air inlet/outletof indoor/outdoor unit

Satisfactory operation with temperature difference ofair intake & discharge of indoor unit 10°C - 15°C

Insufficient Heating

Unit Starts

High heat load

Refrigerant circuit

Leakage

Restriction e.g. atstrainer, capillary,filter dryer, etc.

Compressor

Less or no compression(Low running current)

Windows / doorswide open

Check air circulation

Indoor/Outdoor coil dirty (clogged)

Air filters dirty

Fan Malfunction

Obstruction at air inlet/outletof indoor/outdoor unit

Satisfactory operation with temperature difference ofair intake & discharge of indoor unit 16°C - 25°C

50

Page 52: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

14. EXPLODED VIEW AND PARTS LIST

MODEL: ACC 75D

No. Description Part Number1 Assy, Panel Front Base A500140760242 Panel, Back Base A010140740503 Assy, Drain Pan A500190235844 Assy, Coil Tubing CC 75D A500240782705 Cover, Coil Right A010140733696 Cover, Coil Left A010140733707 Flange, Filter Right A010140738118 Flange, Filter Left A010140738109 Rail, Filter (CC75D/DR) A12014076976

10 Drain Pan Seperator A0101407740211 Assy, Panel Top A5001407337112 Flange, Filter T/B A0101407412013 Assy, Fan Deck A5003407405314 Panel, Side Ledt A0101407336815 Panel, Header Small Right A0101407336616 Panel, Side Big Right A0101407336517 Assy, Bracket Drain Pump Cover A5001408040618 Switch, Level A0406902296619 Assy. Terminal Box A50044080388 20 Cover, Filter L/R A0101407411921 Hanger A01014032372

Control Module A04089025212Valve, TXV A05019015343

Parts Not Shown in Diagram

51

Page 53: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

52

MODEL: ACC 75DR

No. Description Part Number1 Assy, Panel Front Base A500140760242 Panel, Back Base A010140740503 Assy, Drain Pan A500190235844 Assy, Coil Tubing CC 75DR A500240740555 Cover, Coil Right A010140733696 Cover, Coil Left A010140733707 Flange, Filter Right A010140738118 Flange, Filter Left A010140738109 Rail, Filter (CC75D/DR) A12014076976

10 Drain Pan Seperator A0101407740211 Assy, Panel Top A5001407337112 Flange, Filter T/B A0101407412013 Assy, Fan Deck A5003407405314 Panel, Side Ledt A0101407336815 Panel, Header Small Right A0101407336616 Panel, Side Big Right A0101407336517 Assy, Bracket Drain Pump Cover A5001408040618 Switch, Level A0406902296619 Assy. Terminal Box A5004407698120 Cover, Filter L/R A0101407411921 Hanger A01014032372

Control Module A04089023681Valve, TXV A05019022121

Parts Not Shown in Diagram

Page 54: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

53

MODEL: ACC 100D

No. Description Part Number1 Assy, Panel Front Base A500140760252 Panel, Back Base A010140733463 Assy, Drain Pan A500190235854 Assy, Coil Tubing CC 100D A500240782715 Cover, Coil Right A010140733696 Cover, Coil Left A010140733707 Flange, Filter Right A010140738118 Flange, Filter Left A010140738109 Rail, Filter (CC100D/DR) A1201407697710 Drain Pan Seperator A0101407740211 Assy, Panel Top A5001407459412 Flange, Filter T/B A0101407381213 Assy, Fan Deck A5003407334714 Panel, Side Ledt A0101407336815 Panel, Header Small Right A0101407336616 Panel, Side Big Right A0101407336517 Assy, Bracket Drain Pump Cover A0101407718118 Switch, Level A0406902296619 Assy. Terminal Box A50044080388 20 Cover, Filter L/R A0101407411921 Hanger A01014032372

Control Module A04089025212Valve, TXV A05019015344

Parts Not Shown in Diagram

Page 55: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

54

MODEL: ACC 100DR

No. Description Part Number1 Assy, Panel Front Base A500140760252 Panel, Back Base A010140733463 Assy, Drain Pan A500190235854 Assy, Coil Tubing CC 75D A500240733515 Cover, Coil Right A010140733696 Cover, Coil Left A010140733707 Flange, Filter Right A010140738118 Flange, Filter Left A010140738109 Rail, Filter (CC75D/DR) A1201407697710 Drain Pan Seperator A0101407740211 Assy, Panel Top A5001407459412 Flange, Filter T/B A0101407381213 Assy, Fan Deck A5003407334714 Panel, Side Ledt A0101407336815 Panel, Header Small Right A0101407336616 Panel, Side Big Right A0101407336517 Assy, Bracket Drain Pump Cover A5001408040618 Switch, Level A0406900161619 Assy. Terminal Box A5004407698120 Cover, Filter L/R A0101407411921 Hanger A01014032372

Control Module A04089023681Valve, TXV A5019022122

Parts Not Shown in Diagram

Page 56: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

55

MODEL: AMC / A4MC 75D

Page 57: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

56

MODEL: AMC / A4MC 75ER

Page 58: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

57

AMC / A4MC 75D AMC / A4MC 75ERNo. Description Part Number No. Description Part Number1 Assy, Base Pan Main A50014045044 1 Assy, Base Pan Main A500140468412 Compressor 2 Compressor

AMC 75D A50049004676 AMC 75ER A50049004676A4MC 75D A50049014526 A4MC 75ER A50049014526

3 Struc. Tube Support A01014044386 3 Accumulator4 Assy, Access Valve AMC 75ER A02119004676

AMC 75D A50054028348 A4MC 75ER A02119015245A4MC 75D A50054077736 4 Struc. Tube Support A01014044386

5 Support, Tube Liquid 1/2" Tube A01014024023 5 Support, Tube Liquid 1/2" Tube A010140240236 Support, Tube Gas 1" Tube A01014024026 6 Support, Tube Gas 1" Tube A010140240267 Assy, Coil Left Main A50024044767 7 Assy, Access Valve A500540283488 Assy, Coil Right Main A50024044769 8 Assy, Coil Left Main A500240529949 Struc. Coil A01014022392 9 Assy, Coil Right Main A50024052995

10 Assy, Structure Back L A50014022910 10 Struc. Coil A0101402239211 Assy, Structure Back R A50014029795 11 Assy, Structure Back L A5001402291012 Clamp, Tube Liquid 1/2" Tube A01014024030 12 Assy, Structure Back R A5001402979513 Clamp, Tube Gas 1" Tube A01014024033 13 Clamp, Tube Liquid 1/2" Tube A0101402403014 Structure, Front Left A01014069646 14 Clamp, Tube Gas 1" Tube A0101402403315 Structure, Front Right A01014069647 15 Structure, Front Left A0101406964616 Cover, Terminal Board Back A01014044214 16 Structure, Front Right A0101406964717 Panel, Orifice A01014044211 17 Cover, Terminal Board Back A0101404421418 Motor A03039012606 18 Panel, Service Top A0101406964419 Fan Propeller, 32" A03019021351 19 Panel, Orifice A0101404421120 Fan Guard 32" A01029048691 20 Motor A0303901260621 Panel, Service Top A01014069644 21 Fan Propeller, 32" A0301902135122 Panel, Service Bottom A01014069645 22 Fan Guard 32" A0102904869123 Assy, S. Hoisting Bracket A50014022906 23 Panel, Service Bottom A01014069645

24 Assy, S. Hoisting Bracket A50014022906Pressure Switch A04109015400High Pressure Switch A04109015136 Pressure Switch A04109015400Bracket, Fan Motor 32" A01024048601 High Pressure Switch A04109015136Phase Sequencer A04089018834 Bracket, Fan Motor 32" A01024048601Assy, Discharge Thermostat A50044052922 Phase Sequencer A04089018834Filter Drier A02164034987 Assy, Discharge Thermostat A50044052922

Filter Drier A02164034987

Parts Not Shown in DiagramParts Not Shown in Diagram

Page 59: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

58

MODEL: AMC / A4MC 100D

Page 60: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

59

MODEL: AMC / A4MC 100ER

Page 61: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

60

AMC/A4MC 100D AMC / A4MC 100ERNo. Description Part Number No. Description Part Number1 Assy, Base Pan Main A50014045044 1 Assy, Base Pan Main A500140468412 Compressor 2 Compressor

AMC 100D A50049004677 AMC 100ER A50049004677A4MC 100D A50049014427 A4MC 100ER A50049014427

3 Struc. Tube Support A01014046135 3 Accumulator A021190152464 Assy, Access Valve A50054028348 4 Struc. Tube Support A010140461355 Support, Tube Liquid 5/8" Tube A01014023152 5 Support, Tube Liquid 5/8" Tube A010140231526 SupportT, Tube Gas 1-1/8" Tube A01014024027 6 SupportT, Tube Gas 1-1/8" Tube A010140240277 Assy, Coil Left Main A50024044774 7 Assy, Access Valve A500540283488 Assy, Coil Right Main A50024044776 8 Assy, Coil Left Main A500240531249 Struc. Coil A01014022392 9 Assy, Coil Right Main A50024053125

10 Assy, Structure Back L A50014022910 10 Struc. Coil A0101402239211 Assy, Structure Back R A50014029795 11 Assy, Structure Back L A5001402291012 Clamp, Tube Liquid 5/8" Tube A01014023149 12 Assy, Structure Back R A5001402979513 Clamp, Tube Gas 1-1/8" Tube A01014024034 13 Clamp, Tube Liquid 5/8" Tube A0101402314914 Structure, Front Left A01014069646 14 Clamp, Tube Gas 1-1/8" Tube A0101402403415 Structure, Front Right A01014069647 15 Structure, Front Left A0101406964616 Cover, Terminal Board Back A01014044214 16 Structure, Front Right A0101406964717 Panel, Orifice A01014044211 17 Cover, Terminal Board Back A0101404421418 Motor A03039012606 18 Panel, Service Top A0101406964419 Fan Propeller, 32" A03019021351 19 Panel, Orifice A0101404421120 Fan Guard 32" A01029048691 20 Motor A0303901260621 Panel, Service Top A01014069644 21 Fan Propeller, 32" A0301902135122 Panel, Service Bottom A01014069645 22 Fan Guard 32" A0102904869123 Assy, S. Hoisting Bracket A50014022906 23 Panel, Service Bottom A01014069645

24 Assy, S. Hoisting Bracket A50014022906Low Pressure Switch A50134056107High Pressure Switch A04109015136 Pressure Switch A50014022906Bracket, Fan Motor 32" A01024048601 High Pressure Switch A04109015136Phase Sequencer A04089018834 Bracket, Fan Motor 32" A01024048601Assy, Discharge Thermostat A50044052922 Phase Sequencer A04089018834

Assy, Discharge Thermostat A50044052922Filter Drier A02164034987

Parts Not Shown in DiagramParts Not Shown in Diagram

Page 62: Models: ACC 75D/DR ACC 100D/DR - : : Acson International · PBAB X X X X X PBAC X X X X X X X PCAA X X X X X X QBAB X X X X X QBAC X X X X X X X QCAB X X X XXXXX Classification Controller

While upmost care is taken in ensuring that all details in the publication are correct at time of going to press, we are constantly striving for improvement and therefore reserve the rights to alter model specifications and equipment without prior notice. Details of specifications and equipment are also subject to change to suit local conditions and equipments and not all models are available in every market.