REFRIGERANT RESPONSE SYSTEM
NETWORK CONTROLLED SYSTEMS3532 KATELLA AVE. SUITE 203
LOS ALAMITOS, CA 90720CONTACT:
(714) 625-8352WWW.NC2SYSTEMS.COM
MODEL# RRS - 16C
SPECIFICATIONSComponents: RRS-16C-XXX (VSC, MVS, VEO)
Override Control Allows the operator to override the system
Configurable for Latest Standards
ANSI/ASHRAE 15, CBC, CFC & CMC
System Input and Outputs Ventilation System, Fire Alarm Panel, Mechanical Equipment Shutdown Interface
Indication Lights Provides status of alarm conditions and fan operations
Horn and Strobe Integrated Audio & Visual Alert Notifications
Thermostat Integration Works with thermostat to control exhaust fan based on space temperature (Overrides in Purge Mode)
The refrigerant response system automatically
responds to unsafe conditions while giving operators clear system
status information and direct control of relevant equipment.
WWW.NC2SYSTEMS.COM
NETWORK CONTROLLED SYSTEMS
REFRIGERANT RESPONSE SYSTEM
MODEL# RRS - 16C
MASTER VENTILATION SYSTEM EMERGENCY CONTROL PANEL (RRS-16C-MVS): Presents operators with simple system status indications and control of critical equipment.
ASHRAE Standard 15-2016, Sec 8.11.2.1 “Each machinery room shall contain a detector, located in an area where refrigerant from a leak will concentrate, that actuates an alarm and mechanical ventilation. . . at a value not greater than the corresponding TLV-TWA (or toxicity measure consistent therewith).”
FUSE In the event of a power surge, the fuse protects your investment.
LEVEL 2 ALARMUnsafe conditions. In addition to the Level 1 response, enables audio & visual alert notifications, equipment shutdown and an alert to the fire alarm system.
VENTILATION SYSTEM EMERGENCY OVERRIDE PANEL (RRS-16C-VEO - optional): An emergency override to allow operators to shutdown mechanical equipment and override the exhaust fan.
ASHRAE Standard 15-2016, Sec 8.12.h“Remote control of the mechanical equipment in the refrigerating machinery room shall be provided immediately outside the machinery room door solely for the purpose of shutting down the equipment in an emergency. Ventilation fans shall be on a separate electrical circuit and have a control switch located immediately outside the machinery room door.”
PROGRAMMABLE LOGIC CONTROLLER (Inside the RRS-16C-VSC Panel) This industrial controller is customized for your particular refrigerant detection response system.
LEVEL 1 ALARM Approaching unsafe conditions. Activates the exhaust fan and purges the system.
WWW.NC2SYSTEMS.COM
NETWORK CONTROLLED SYSTEMS
RRS - 16C - MVS RRS - 16C - VSC RRS - 16C - VEO
LOCATION3532 Katella Ave, St#203Los Alamitos, CA 90720
Tel : (714) 625-8352Fax: (714) 625-8144
WEBSITEwww.nc2systems.com
NETWORK CONTROLLED SYSTEMS
REFRIGERANT RESPONSE SYSTEMCRITICAL RESPONSE FOR REFRIGERATION MACHINERY ROOMS