Technical Data Submittal Document
Project: Customer: Engineer: Pump Manufacturer:
Model GPL + GLULimited Service Full Voltage
Across the Line StartElectric Fire Pump Controller
with Automatic Power Transfer Switch
May 2019
Contents:Data Sheets
Dimensional DataWiring SchematicsField Connections
The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package.
Note:
2
Technical DataModel GPL + GLU Electric Fire Pump Controllerwith Automatic Power Transfer Switch
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without noticeMay 2019
Standard,Listings,
Approvals andCertifications
Built to NFPA 20 (latest edition)
Underwriters Laboratory (UL)• UL218 - Fire Pump Controllers• UL 1008 - Automatic power transfer switches for fire pump controllers• CSA C22.2 No. 14 Industrial Control Equipment
New York City Accepted for use in the City of New York by the Department of BuildingsSeismic Certification See page 6 for details
Enclosure
Protection Rating□ Standard: NEMA 2 Optional□ NEMA 12□ NEMA 3 □ NEMA 3R□ NEMA 4
Accessories• Wall mounting lugs• Keylock handle
Paint Specifications• Red RAL3002• Powder coating• Glossy textured finish
*Please see Disconnecting Means details on page 3.
□ NEMA 4X-304 sst painted□NEMA 4X-304 sst brushed finish□NEMA 4X-316 sst painted□ NEMA 4X-316 sst brushed finish
MT2
T1
T31M
1M
CR4
3L1 3L2
3L1
3L2
3L3From Automatic Power Transfer Switch*
May 2019 3
Technical DataModel GPL + GLU Electric Fire Pump Controllerwith Automatic Power Transfer Switch
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without notice
Shortcircuit Withstand Rating
208V to 240V- 3ph - 50/60Hz 380V to 480V- 3ph - 60Hz 600V - 3ph - 60Hz
Normal Power Alternate Power Normal Power Alternate Power Normal Power Alternate Power
Standard 65,000A 25,000A 18,000A
Optional n/a 65,000A 25,000A
Limitations
• Across the line starting only • Horsepower rating of maximum 30hp• Can only be installed where acceptable by the authority having jurisdiction • Not accepted in FM insured property
Surge Suppression Surge arrestor rated to suppress surges above line voltage
Disconnecting Means Circuit breaker (inverse time non adjustable) rated between 150% and 250% of motor full load current
Service Entrance Rating Suitable as service entrance equipment
Emergency Start Handle
• Push and slide to lock • Across the line start (direct on line)
Electrical Readings
• Voltage phase to phase (normal power)• Amperage of each phase when motor is running
Pressure Readings
• Continuous system pressure display• Cut-in and Cut-out pressure settings
Pressure and Event recorder
• Pressure readings with date stamp• Event recording with date stamp• Under regular maintained operation, events can be stored in memory for up to 5 years.• Data viewable on operator interface display screen• Downloadable by USB port to external memory device
Pressure Sensing
• Pressure transducer for fresh water application• Pressure sensing connection 1/2” Female NPT• Rated for 0-500PSI working pressure (standard display at 0-300PSI)• Internally mounted
Visual Indications
• Power available• Motor run• Periodic test• Manual start
Visual Alarms
• Alternate lock rotor current• Alternate power phase reversal• Automatic transfer switch trouble• Control voltage not healthy• Fail to start• Invalid cut-in• Lock rotor current• Loss of power• Low ambient temperature
• Deluge valve start• Remote automatic start• Remote manual start• Emergency start
• Pump on demand/Automatic start• Low discharge pressure• Pump room temperature (ºF or ºC)• Lockout• Pressure transducer fault detected• Pump on demand• Pump rrom alarm• Service required• Undercurrent• Undervoltage• Check weekly test solenoid• Weekly test cut-in not reached
• Low water level• Motor trouble• Normal power phase reversal• Overcurrent• Overvoltage• Phase loss L1• Phase loss L2• Phase loss L3• Phase unbalanced
4
Technical DataModel GPL + GLU Electric Fire Pump Controllerwith Automatic Power Transfer Switch
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without noticeMay 2019
**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.
Remote Alarm Contacts
DPDT-8A-250V.AC• Power available• Phase reversal• Motor run• Common pump room alarm
• Overvoltage • Undervoltage • Phase unbalance• Low pump room temperature • High Pump room temperature
• Common motor trouble• Overcurrent • Undercurrent• Fail to start • Ground fault
ViZiTouch V2 Operator Interface
• Embedded microcomputer with software PLC logic• 7.0” color touch screen (HMI technology)• Upgradable software• Multi-language
Communication Protocol
Capability
• Protocol: Modbus• Connection type: Shielded female connector RJ45• Frame Format: TCP/IP• Addresses: See bulletin MOD-GPx
Operation
Automatic Start • Start on pressure drop• Remote start signal from automatic device
Manual Start
• Start pushbutton• Run test pushbutton• Deluge valve start• Remote start from manual device
Stopping • Manual with Stop pushbutton• Automatic after expiration of minimum run timer ***
Timers Field Adjustable & Visual Countdown
• Minimum run timer ***(off delay)• Sequential start timer (on delay)• Periodic test timer
ActuationVisual Indication
• Pressure• Non-pressure
Mode • Automatic• Non-automatic
***Can only be used if approved by the AHJ
May 2019 5
Technical DataModel GPL + GLU Electric Fire Pump Controllerwith Automatic Power Transfer Switch
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without notice
Automatic Power Transfer Switch
Surge Suppression Surge arrestor rated to suppress surges above line voltageDisconnecting
MeansCircuit breaker (inverse time non adjustable) rated between 150% and 250% of motor full load current
Visual Indications
• Alternate (emergency) isolating switch in the OFF position• Alternate (emergency) voltage phase to phase• Transfer switch in normal position• Transition timers
Visual Alarms
• Transfer switch trouble• Alternate power phase reversal• Alternate isolating switch open/tripped• Alternate circuit breaker open/tripped
Transfer switch test pushbuttonBypass for re-transfer and generator shutdownElectrically operated and mechanically held in the normal or alternate positionProvision for manual operation
Remote Alarm ContactsSPDT-8A-250VAC
• Isolating switch in the OFF position• Transfer switch in normal position• Transfer switch in alternate (emergency) position
Time Delays• Momentary normal power outage override (factory set at 3 sec - field adjustable 1 to 3 sec)• Alternate (emergency) power available delay (factory set at 3 sec - field adjustable 1 to 3 sec)• Transfer trouble delay (factory set at 20 sec - field adjustable 1 to 60 sec)• Retransfer to normal (factory set at 5 min - field adjustable 1 to 20 min)• Generator cooldown (factory set at 5 min - field adjustable 1 to 20 min)
Voltage Sensing• Transfer to alternate (normal power dropout) 85% of nominal - field adjustable 0 to 100%• Phase reversal transfer to alternate• Retransfer to normal (normal power pickup) 90% of nominal - field adjustable 0 to 100%
Generator Start ConnectionSPDT-8A-250V.AC
6
Technical DataModel GPL + GLU Electric Fire Pump Controllerwith Automatic Power Transfer Switch
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without noticeMay 2019
Seismic Certification
Seismic Certification Company
TRU Compliance, LLCA Tobalski Watkins Affiliate TWEI Project No.: 15014
Mounting details Rigid wall mounting
Seismic Information
Building Code
Test Criteria
Seismic Parameters SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V
IBC 2015, CBC 2016
ICC-ES
AC156
ASCE 7-10 Chapter 13
2.0 1.0 1.5 3.20 2.40 1.33 0.53
3.2 0.0 1.5 3.20 1.28 2.13 0.85
0.1
1.0
10.0
0.1 1.0 10.0
Spe
ctra
l Res
pons
e A
ccel
erat
ion
(g)
Frequency, f (Hz)
RRS for Nonstructural Components Testing
Horiz. Level 1 Vert. Level 1
Notes:• Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2016. • OSHPD Special Seismic Certification Preapproval (OSP)
May 2019 7
Technical DataModel GPL + GLU Electric Fire Pump Controllerwith Automatic Power Transfer Switch
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without notice
A4 Flow switch provision
A8 Foam pump application w/o pressure transducer and run test solenoid valve.
A9 Low zone pump control function
A10 Middle zone pump control function
A11 High zone pump control function
A13 Non-pressure actuated controller w/o pressure transducer and run test solenoid valve
A16 Lockout/interlock circuit from equipment installed inside the pump room
B11
Built in alarm panel (120V.AC supervisory power) providing indication for:• Audible alarm & silence pushbutton for motor run, phase reversal, loss of phase.• Pilot lights for loss of phase & supervisory power available
B11B Built in alarm panel same as B11 but 220-240VAC supervisory power
B19A High motor temperature c/w thermoster relay and alarm contacts (DPDT)
B19B High motor temperature c/w PT100 relay and alarm contacts (DPDT)
B21 Ground fault alarm detection c/w visual indication and alarm contact (DPDT)
C1 Extra motor run alarm contact (DPDT)
C4 Periodic test alarm contact (DPDT)
C6 Low discharge pressure alarm contact (DPDT)
C7 Low pump room temperature alarm contact (DPDT)
C10 Low water reservoir level alarm contact (DPDT)
C11 High electric motor temperature alarm contact (DPDT)
C12 High electric motor vibration c/w visual indication and alarm contact (DPDT)
C14 Pump on demand / automatic start alarm contact (DPDT)
C15 Pump fail to start alarm contact (DPDT)
C16 Control voltage healthy alarm contact (DPDT)
C17 Flow meter valve loop open c/w visual indication and alarm contact (DPDT)
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
C18 High water reservoir level c/w visual indication and alarm contact (DPDT)
C19 Emergency start alarm contact (DPDT)
C20 Manual start alarm contact (DPDT)
C21 Deluge valve start alarm contact (DPDT)
C22 Remote automatic start alarm contact (DPDT)
C23 Remote manual start alarm contact (DPDT)
C24 High pump room temperature alarm contact (DPDT)
C25 Second set of standard alarm contacts (DPDT) (Typical for city of Los Angeles and Denver)
Cx Additional visual and alarm contact (Specify function) (DPDT)
D1Low suction pressure transducer for fresh water rated at 0-300PSI with visual indication and alarm contact
D1ALow suction pressure transducer for sea water rated at 0-300PSI with visual indication and alarm contact
D13AHigh withstand rating for (normal power section) • 380v to 480v=65ka • 600v = 25ka
D14 Anti-condensation heater & thermostat
D14A Anti-condensation heater & humidistat
D14B Anti-condensation heater & thermostat & humidistat
D15 Tropicalization
D18 CE Mark with factory certificate
D26 Modbus with RTU frame format and RS485 connection
D27 Motor heater connection (external single phase power source and heater on/off contact)
D27A Motor heater connection (internal single phase power source and heater on/off contact)
D28 Customized drawing set
D34A Field programmable I/O board - 5 Input / 5 output
D36 Redundant pressure transducer for fresh water rated for 0-500PSI
8
Technical DataModel GPL + GLU Electric Fire Pump Controllerwith Automatic Power Transfer Switch
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without noticeMay 2019
Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.
Additional Options:
L01 Other language and English (bilingual)
L02 French
L03 Spanish
L04 German
L05 Italian
L06 Polish
L07 Romanian
L08 Hungarian
L09 Slovak
L10 Croatian
L11 Czech
L12 Portuguese
L13 Dutch
L14 Russian
L15 Turkish
L16 Swedish
L17 Bulgarian
L18 Thai
L19 Indonesian
L20 Slovenian
L21 Danish
L22 Greek
L23 Arabic
L24 Hebrew
L25 Chinese
D36A Redundant pressure transducer for sea water rated for 0-500PSI
E1 Permanent load shedding contacts
E2 Temporary pump motor start period load shedding contacts
E3 Temporary & permanent load shedding contacts
F2 Anti condensation heater & thermostat (alternate power section)
F2A Anti condensation heater & humidistat (alternate power section)
F2B Anti condensation heater & thermostat & humidistat (alternate power section)
F6A High withstand rating for (model GLU only) :380v to 480v=65ka • 600v=25ka
May 2019 9
Technical DataModel GPL + GLU Electric Fire Pump Controllerwith Automatic Power Transfer Switch
This is a Marketing document. Please consult factory for more information. Manufacturer reserves the right to modify this information without notice
Home
®
4
1
5 6 7 89
32
PMS 295 PMS 361 Noir
ViZiTouch V2 Operator Interface
1 - Color touch screen2 - Onscreen menu • HOME page • ALARM page • CONFIGURATION page • HISTORY page • SERVICE page • MANUAL page • LANGUAGES page
3 - Screen protector 4 - Power LED (3 colors)5 - START button6 - STOP button7 - TRANSFER SWITCH TEST button 8 - RUN TEST button9 - USB port
251818 253575-600 / 60 30
GLUALT. SIDE
WITHSTAND RATING [kA] RMS
65N/A15 653200-208 / 60
3200-208 / 60
380-416 / 50-60440-480 / 50-60
230-240 / 50-6033
3
230-240 / 50-60 3
6565 N/A30
253030 25
30 652565
65 25
N/A 65
6515 65N/A
HP RATING
1 PHASEMIN
VOLT/Hz
MAXStd HIGH Std
NORMAL SIDE
N/A
N/A
6565
N/A
N/A
HIGH
5 3/8" [136]
5 1/2" [139]
18 1/2" [470] 18 1/2" [470]
1 7/8" [48]
25 1/4" [642] 24" [610]
40 3/8" [1026] 28 1/8" [715]
3 PHASESSENSING LINE CONNECTION1/4'' NPT
DRAWING No.
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
GPL-DI601NYC
Dpt of BuildingApproved
DD/MM/YYDESCRIPTIONREV.
0. First issue 17/11/16
1/2" [12]
8" [203]
Ø3/8" [Ø10] X8
1. Revised logo 18/06/18
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
Drawing number
Limited Service Pump Controller Model:GPL+GLU
WS611 /EGPL-
With Automatic Transfer Switch
0 First issue 10/11/16
3L1
3L3
3L2
17
3L2
Blac
k
Whi
te
Blac
k
Whi
te
Whi
te
Blac
k
6465
6667
6869
To J76To J2-J3-J4
3L3
3L13L2
3L1
** Contact closes when emergency start is in "ON" position
J42
J37
J39
J41
J55
Black
Red
White
3L1
3L2X1
X2
H2
H1
J76
L1
J25
IN1
TB2
TB3
TB4
TB5
TB6
* Remove jumper to use this feature
C
NC
NO
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
C
NC
NOJ40TB1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
J14 AI4
-
+
J15 AI3
-
+
J16 AI2
-
+
J17 AI1
-
+
J54LS1
DOWN
J46AB
J43SV
J45ST
J44 24V in
24V out
J47 24VAC
C
NO
NC
C
NO
NC
J4
J3
J2 L1
J53
- +Black
Red
UPJ20
J8
12
C
NC
NOC
NC
NO1
2
C
NC
NOC
NC
NO1
2
C
NC
NOC
NC
NO1
2
C
NC
NOC
NC
NO1
2
C
NC
NOC
NC
NO1
2
J36CR4
J38CR5
L2
L3
GF
L2
L3
Motor Run
Phase Reversal
Pump Room Alarm
Motor Trouble
Remote Manual Start
Lockout
Remote Automatic Start
Deluge Valve
Water Reservoir Low
(Field Programmable)
To CT1-CT2-CT3
To 3L1-3L2-3L3
2L2
2L1
SeeGLU
Drawing
2L3
SeeGLU
Drawing
Across the Line / 3 Phase
Wiring schematic Built to the latest edition of the NFPA 20 standard
3
1
J1*
LS1-2LS1-1
J2*
CR4-2CR4-1
6869
6667
6465
3L3
3L2
3L1
Legend
1M ContactorAB Alarm BellCB Circuit BreakerCR Control Relay
CT Current TransformerEB Electric I/O BoardJ Jumper
LS Limit SwitchPT Pressure TransducerSA Surge Arrester
VMB ViZiTouch Main BoardXTR Transformer
Power Available
1 Removed (fail safe) text from Power Available relay 20/02/172 Update Logo 23/04/18
DD/MM/YYDESCRIPTIONREV.NYC
Dpt of BuildingApproved
Drawing number
Automatic Transfer Switch Model:GLU
WS601 /EGLU-0 First issue 10/11/16
J45 AST
24V in
24V out
J38
24VAC2J53
24VAC1J47
J58
J7
J6
J5
J4
J3
J2
A3
A2
A1
N3
N2
N1
5354
5152
2E3
2E22E2
2E12E1
2L3
2L22L2
2L12L1
X1
X2
H2
H1
X1
X2
H2
H1
2E2
2E1
2E3
NOC
CNC
NO
CNO
J49-3
Red
Black J49-2J49-1
J49-5J49-4 Brown
J50-2J50-1
Black
CNC
NO
J50-3
Red J50-5J50-4 Brown
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
A Pos.N
Pos.AC
BG
EN
C
NC
NO
C
NO
LSE2LSE1
C
NC
NO
C
NO
LSN2
LSN1
C
NC
NOLSA3
C
NC
NOLSA2
C
NOLSA1
C
NOLSA4
J50
J49
J46
J55LN12
LN11
J52M-
M+
J54LE12
LE11
Brown
Orange
Yellow
Black
Red
Green
Brown
Red
Black
Violet
Orange
Blue
Yellow
DOWN
UPJ20
J8
2E3
2E2
2E1
2L3
2L2
2L1
3L2
3L1
3L3
J4
J3
Black
White
Yellow
Orange
Yellow
Orange
SeeGPL
Drawing
Brown
Orange
Yellow
Black
Red
For Limited Service Pump Controller3 Phase
CNO
CNC
NO
J46-1Violet
BlueOrange
J46-6J46-7
J46-2Black
CNC
NO
J46-9
RedGreen J46-10J46-8 Brown
Yellow J46-5
J5
2L2
2L1
2L3
J6
Built to the latest edition of the NFPA 20 standardWiring schematic
Normal / AlternatePower to Fire PumpSection
Normal Powerfrom Fire
Pump Section
J39
Shown in normal position
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
10
5
5
To LSE1-LSE2
To LSN1-LSN2
To LSA2-LSA3-LSA4
Legend
ACB Circuit BreakerJ Jumper
LSA Limit SwitchLSE Limit SwitchLSN Limit SwitchMA Linear Motor ActuatorSA Surge Arrester
TSB Transfer Switch I/O BoardXTR Transformer
1 Revised logo 18/06/18
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (10)
30
1x (14 to 10)
1x (14 to 10)
1x (14 to 10)
1x (12 to 10)
1x (14 to 10)
1x (14 to 10)
1x (12 to 10)
1x (10)
1x (10)
1x (14 to 10)
1x (12 to 10)
1x (8 to 2)
1x (8 to 2)
1x (8 to 2)
1x (12 to 10)
1x (10)
1x (8 to 2)
1x (6 to 2)
1x (6 to 2)
1x (10)
1x (8 to 2)
1x (8 to 2)
1x (4 to 1)
1x (4 to 1)
1x (8 to 2)
1x (8 to 2)
1x (6 to 2)
1x (4 to 1)
1x (3 to 1)
1x (8 to 2)
1x (6 to 2)
1x (6 to 1)
1x (3 to 1)
1x (2 to 1)
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (10 to 1)
30
1x (8 to 1)
3 " (76 mm)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (8 to 1)
1x (8 to 1)
1x (10 to 1)
1x (10 to 1)
1x (8 to 1)
1x (6 to 1)
1x (6 to 1)
1x (10 to 1)
1x (8 to 1)
1x (8 to 1)
1x (4 to 1)
1x (4 to 1)
1x (8 to 1)
1x (8 to 1)
1x (6 to 1)
1x (4 to 1)
1x (3 to 1)
1x (8 to 1)
1x (6 to 1)
1x (6 to 1)
1x (3 to 1)
1x (2 to 1)
Wiring Size for motor connection for Model GPL (AWG or MCM). TERMINALS T1 - T2 - T3
Voltage
Voltage
Circuit Breaker (CB) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3
BendingSpace
HP
HP
DD/MM/YYDESCRIPTIONREV. Drawing number
GPL-TD601 1/2 /E
Terminal Diagram and Sizing
Model:GPLLimited Service Pump Controller
Built to the latest edition of the NFPA 20 standard
Notes:1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC (Canada) or local code.2 - Controller suitable for service entrance in USA.3 - For more accurate motor connections refer to motor manufacturer or motor nameplate.4 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.5 - Field wiring and lug sizes are based on copper conductors only. Do not use aluminium conductors.
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
0 First issue 10/11/16
NYCDpt of Building
Approved
M
T1 T3
1M
Incoming Power3 Phase
Bonding
L1CB1
Ground
L3Power Terminals
Model : GPL 3 Phase
T2
L2
(Use Copper Conductors Only)
1 Removed (fail safe) text from Power Available relay 20/02/172 Revised logo 18/06/18
DD/MM/YYDESCRIPTIONREV. Drawing number
GPL-TD601 2/2 /E
Terminal Diagram and Sizing
Model:GPLLimited Service Pump Controller
Built to the latest edition of the NFPA 20 standard
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
0 First issue 10/11/16
NYCDpt of Building
Approved
Control Terminals (EB1)
Close to start pump
Open to start pump
Open to start pump
Alarm Inputs (EB1)
Close to block start
Remote Alarm Terminals (EB1)
0.5 Nm24 - 12 AWG
Terminals Wire Size:
0.5 Nm24 - 12 AWG
Terminals Wire Size:
0.5 Nm24 - 12 AWG
Terminals Wire Size:
C
NC
NO
C
NC
NO
1
2
Normally closedOpens to alarm
Closes to alarmNormally open
J40TB1
Motor Run
Normally closedOpens to alarm
Closes to alarmNormally open
C
NC
NO
C
NC
NO
1
2
J42TB2
Normally closedOpens to alarm
Closes to alarmNormally open
Power Available
C
NC
NO
C
NC
NO
1
2
Normally closedOpens to alarm
Closes to alarmNormally open
J37TB3
Normally closedOpens to alarm
Closes to alarmNormally open
C
NC
NO
C
NC
NO
1
2
Normally closedOpens to alarm
Closes to alarmNormally open
J39TB4
Normally closedOpens to alarm
Closes to alarmNormally open
Pump Room Alarm **
C
NC
NO
C
NC
NO
1
2
Normally closedOpens to alarm
Closes to alarmNormally open
J41TB5
Normally closedOpens to alarm
Closes to alarmNormally open
Motor Trouble **
C
NC
NO
C
NC
NO
1
2
Normally closedOpens to alarm
Closes to alarmNormally open
J55TB6
Normally closedOpens to alarm
Closes to alarmNormally open
(Field Programmable)
IN1
IN2
IN3
IN4
J1*
J2*
J25
J25
J25
J25
Close to signal alarm IN5 J25
Remote Manual Start
Lockout
Remote Automatic Start
Deluge Valve
Water Reservoir Low
Modbus TCP/IP
Network Connection (VMB1)Shielded Female Connector RJ45
Phase Reversal
** Re-assignable* Remove jumper to use this feature
Normally closedOpens to alarm
Closes to alarmNormally open
1 Removed (fail safe) text from Power Available relay 20/02/172 Revised logo 18/06/18
5 7.5 10 15 20 25
220 to 240
380 to 416
600
440 to 480
208 1x (10 to 1)
30
1x (8 to 1)
3 " (76 mm)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (10 to 1)
1x (8 to 1)
1x (8 to 1)
1x (10 to 1)
1x (10 to 1)
1x (8 to 1)
1x (6 to 1)
1x (6 to 1)
1x (10 to 1)
1x (8 to 1)
1x (8 to 1)
1x (4 to 1)
1x (4 to 1)
1x (8 to 1)
1x (8 to 1)
1x (6 to 1)
1x (4 to 1)
1x (3 to 1)
1x (8 to 1)
1x (6 to 1)
1x (6 to 1)
1x (3 to 1)
1x (2 to 1)
HP
Voltage
Circuit Breaker (CB) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3
BendingSpace
DD/MM/YYDESCRIPTIONREV.
GLU
Drawing number
GLU-TD601 /E
Terminal Diagram and Sizing
Model:Automatic Power Transfer Switch
Built to the latest edition of the NFPA 20 standardFor Limited Service Pump Controller
Notes:1 - Controller is phase sensitive. Incoming lines must be connected in ABC sequence.2 - Field wiring and lug sizes are based on copper conductors only. Do not use aluminium conductors.
Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.
0 First issue 10/11/16
NYCDpt of Building
Approved
Remote Alarm Terminals (TSB1)
Control Terminals (TSB1)
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
J39
A Pos.N
Pos.AC
BG
EN
is in OFF or trippedCloses when ACB1
is in OFF or TrippedOpens when ACB1
Closes when Tr. Sw.in Normal Position
Opens when Tr. Sw.is in normal position
Closes when Tr. Sw.in Alternate PositionOpens when Tr. Sw.
is in alternate positionTr. Sw. in alternate position
Tr. Sw. in normal position
ACB1 in OFF or tripped
J39Opens to start generator
Normally closedCloses to start generator
Normally open
Generator Set
(Use Copper Conductors Only)
AL1 AL3
ACB1
Power Terminals
Incoming Power3 Phase
BondingGround
AL2
0.5 Nm24 - 12 AWG
Terminals Wire Size:
0.5 Nm24 - 12 AWG
Terminals Wire Size:
1 Added terminal ratings 10/05/172 Revised logo 18/06/18