Model B1
19-inch RackStatic Transfer
Switch
Why choose a model B1static transfer switch?
• Increases power availability.• True solid state.• Rugged, reliable design.• Fast, Intelligent transfers.• One touch transfer.• Integrated LAN web server.• Passively cooled.• Break before make transfers.• SCR open and short circuit protection.• Preferred source selector.• Supported current up to 32A.
Features
• Fast, reliable switching• Transparent transfer – less than ¼ cycle.• Solid state devices are far superior to their electro-mechanical equivalents. • Triple redundant internal power sources.
Weight and Dimensions
Width: 483mm, 19”Height: 1RU Depth: 400mm, 15.7”Weight (typical): 5.7Kg, 13 lb
Features
• Real time monitoring• Simple LED MIMIC status.• LCD Showing
• input/output voltage and current.• List of recent events.• Ethernet Details.• override or the preferred supply being used.
• Visual and audible alarms.• Ethernet web server.
LCD
LED MIMIC
ALARM
ETHERNET CONNECTOR
ETHERNET CONNECTOR
• Multiple communications options • Ethernet (IEEE802.3 10BaseT)• Email alert.• 5 relay outputs.• 2 control inputs.
Features
REMOTE CONNECTOR
• LCD Screen functions • Status.• List of Variables.• Event list (100 events).• Ethernet options.
Liquid Crystal Display
• LCD Screen functions • Status.• List of Variables.• Event list.• Settings.• Utilisation.• Diagnostics.
Liquid Crystal Display
• Multiple communications options • From Ethernet (IEEE802.3 10BaseT)
• SNMP• MODBUS• HTTP - Web server
• 5 relay outputs•Pin 10 to 12 RLY-O/P General Alarm•Pin 6 to 8 RLY-O/P Not in Synch•Pin 2 to 4 RLY-O/P Overloaded•Pin 1 to 3 RLY-O/P ON A•Pin 5 to 14 RLY-O/P ON B
•2 control inputs.•Pin 13 to Pin 7 Remote Transfer to S1 •Pin 11 to Pin 7 Remote Transfer to S2
Features
Features
• Programmable logic control• Fast internal communication.• All variables are easily set in software.• Constantly monitors for alarm conditions.• Intelligent transfers.
Flexible configurations
Input Output2 x unterminated cords 8 x IEC C13
2 x unterminated cords 3 x IEC C19
2 x unterminated cords 4 x IEC C13 + 2 x IEC C19
2 x unterminated cords 4 x Aus GPO
2 x terminal blocks 1 x terminal block
2 x large umbilical cords 4 x IEC C13
2 x large umbilical cords 2 x IEC C19
2 x large umbilical cords 1 x large umbilical cords
*example B1s shown above
SpecificationSpecification
Type 2-pole / 1-phase
Current Rating 20A 32A
Nominal Voltage 115V to 230V +- 20%
Fault Current 2kA for 20ms, 100A Fused
Frequency 50 / 60Hz (auto detection)
Power Factor No Limit
Crest Factor 3.5:1
Overload Capacity
100A for 30 sec.400A for 1 sec.
2,000A for 20 ms.