333 CROSSPARK DRIVE PEARL, MS 39208 Phone: (601) 933-0900 Fax: (601) 933-0901 MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3

Transcript of MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T....

Page 1: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

333 CROSSPARK DRIVE PEARL, MS 39208

Phone: (601) 933-0900 Fax: (601) 933-0901

MODEL 3010 PORTABLE AUTOMATED TEST KIT

P.A.T.

OPERATIONS MANUAL

REV 1.3

Page 2: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 1

W A R N I N G

Safety is of utmost concern to Watthour Engineering Co., Inc. The operator should become familiar with the care and use of the Model 3010 PAT by reading this manual before attempting to use the device. Because of the dangers associated with exposed voltages when making "on-site" meter tests, extreme care should be taken when testing. Watthour Engineering Co., Inc. does NOT recommend the testing of 480 volt meters at a customer's location. Although the Model 3010 PAT has the capability of testing with 480 VAC output, the auto-ranging input (supply) is limited to 300 VAC max. When taking "on-site" measurements in the "READ" mode, it is very important to avoid opening a secondary current transformer (CT) circuit. High and potentially lethal voltages could be exposed, if the current circuit is opened. Read the tutorial "Read Mode Operation" carefully.

DO NOT POWER THE TEST KIT WITH VOLTAGE ABOVE 300 VAC. Also provided is a front panel safety grounding post to allow the PAT test kit chassis to be tied to a secure ground point at the meter test location.

MAKE THIS CONNECTION FIRST! Watthour Engineering Co., Inc. assumes NO liability from misuse or negligence on the part of the test kit operator. Watthour Engineering Co., Inc. Pearl, Mississippi

USE THIS EQUIPMENT SAFELY !!

Page 3: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 2

WARRANTY STATEMENT Watthour Engineering Co., Inc. warrants each of our products to be free from defects in material and workmanship. Our obligation under this warranty is to repair or replace any product or component therein which, within two (2) years after shipment, proves to be defective upon examination. If warranty service is required, write or call your local Watthour Engineering Co., Inc. representative or contact our headquarters in Pearl, Mississippi. The equipment specified is of modular construction and lends itself to ease of servicing and repair. Should a problem arise, it will be handled in the following manner: Most of the problems that arise can be effectively handled over the telephone. Once the nature of the problem is located a replacement part will sent at no cost to the customer. If for some reason the problem cannot be solved by these means then the customer must contact Watthour Engineering Co., Inc. and obtain approval and information for shipping the unit back to the factory which will be issued on a case by case basis. Watthour Engineering Co., Inc. will repair the unit at no cost to the customer. Watthour Engineering Co., Inc. will not be responsible for the cost of shipping the unit to our facilities, but will bear the cost of return shipping to the customer. The cost of premium shipping methods requested by the customer will be the customer’s responsibility. This warranty excludes ordinary wear and tear and damage due to improper handling, storage, or operation.

Page 4: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 3

CONTENTS 1. 0 PRINCIPLE OF OPERATION....................................................................................................PAGE 5 2. 0 SPECIFICATIONS .....................................................................................................................PAGE 9 3. 0 CONTROLS AND FUNCTIONS ................................................................................................PAGE 13

3.1 FRONT PANEL.....................................PAGE 15 3.8 AUDIO CONTROL BLOCK...................... PAGE 17 3.2 TEST/ELEMENT/METER BLOCK........PAGE 15 3.9 KEYPAD ................................................... PAGE 17 3.3 COM PORTS BLOCK...........................PAGE 16 3.10 INPUT BLOCK ....................................... PAGE 18 3.4 DISPLAY CONTROL BLOCK ..............PAGE 16 3.11 CONNECTION BLOCK .......................... PAGE 18 3.5 TEST CONTROL BLOCK.....................PAGE 16 3.12 MODE BLOCK ....................................... PAGE 19 3.6 GATE CONTROL BLOCK ....................PAGE 16 3.13 OPTICAL PICKUP ASSEMBLY............. PAGE 19 3.7 PULSE INPUT BLOCK.........................PAGE 17 4. 0 SETTING UTILITIES..................................................................................................................PAGE 21 5. 0 MODEL 3010 TESTING PROCEDURE TUTORIALS...............................................................PAGE 25

5.1 MANUAL TESTING...............................PAGE 27 5.7 SAVING A TEST RECORD .................... PAGE 48 5.2 AUTO-SEQUENCE TESTING ..............PAGE 33 5.8 EDITING A TEST RECORD ................... PAGE 50 5.3 READ MODE TESTING........................PAGE 37 5.9 DEMAND TESTING................................ PAGE 51 5.4 SELF CHECK .......................................PAGE 39 5.10 PULSE INITIATOR TESTING................. PAGE 53 5.5 STANDARDS COMPARE.....................PAGE 41 5.6 SETTING UTILITIES.............................PAGE 45 6. 0 SCREEN FLOW CHARTS.........................................................................................................PAGE 55 MAIN SCREENS...........................................PAGE 57 EDIT STORED TEST...................................... PAGE 64 METER SETUP.............................................PAGE 58 MANUAL TEST ENTRY ................................. PAGE 65 EDIT DEFAULTS ..........................................PAGE 59 KWH TESTING............................................... PAGE 66 EDIT AUTO-SEQUENCE..............................PAGE 60 DEMAND TESTING........................................ PAGE 7 SELF TEST ...................................................PAGE 61 STANDARDS COMPARE.............................PAGE 62 UTILITIES .....................................................PAGE 63 7. 0 APPENDIX .................................................................................................................................PAGE 69

7.1 GLOSSARY OF COMMON TERMS .....PAGE 71 7.2 MODEL 3010 OPTIONS .......................PAGE 73 7.3 PREVENTATIVE MAINTENANCE........PAGE 74 8. 0 METER HOOKUP DIAGRAMS .................................................................................................PAGE 75

Copyright 2001, Watthour Engineering Co, Inc. ALL RIGHTS RESERVED.

Page 5: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 4

BLANK PAGE

Page 6: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 5

MODEL 3010 PRINCIPLE OF OPERATION

1.0

Page 7: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 6

BLANK PAGE

Page 8: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 7

1.0 MODEL 3010 PRINCIPLE OF OPERATION The Model 3010 Meter Test System is a portable KWH comparator and KW demand testing unit. The Model 3010 is of modular construction and is designed to test both A-base meters and socket meters with the proper adapter. Refer to the block diagram on page five for additional information. The internal power supply takes the 90-300 VAC source input voltage and converts it to deliver ±25 VDC to the solid state loading board, and the power op/amp boards. It also delivers ±25, ±15, and +5 VDC to the CPU board and ±15 and +5 VDC to the solid state loading board. The solid state loading board contains the microprocessor which sends four digital signals (one for the voltage channel, one for the left current channel, one for the center current channel, and one for the right current channel) to four digital to analog generators. These generators produce stepped analog signals which are then sent through four filters ( one for each channel ) to produce a clean sine waveform. These waveforms are then sent through four magnitude DACs which produce four usable sine waveforms which are then sent to the four power amplifiers. The power amps use the ±25 VDC voltage from the power supply to produce a 0-30 VAC output. The AC output on the voltage channel is routed to a voltage power transformer. This voltage is then routed to the solid state loading board (which produces a 60-600 VAC output) and then to both the Radian standard and the meter under test. The AC outputs from the three current channels are applied to current transformers. This produces a 25-50 amp output which passes through Hall effect current sensors. The three current channels are routed to the Radian standard, and on to the meter under test. A Radian standard is used to measure the energy produced by the test kit. Depending on which standard is installed the test board can measure KW hours/ KW, KQ hours/ KQ, and KVAR hours/ KVAR. (The customer should specify which standard is needed at the time the unit is ordered.) The data output from the Hall effect sensors is sent to two analog to digital converters (ADC). One of these converters measures volts and amps, and the other measures phase angle. The digital output from the ADCs is sent along an 8 bit parallel interface path to the microprocessor and the CPU board. The CPU receives the input from the optical reflect mode probe or the solid state probe and the pulses from the Radian standard to produce an eight bit data output which is sent to the CPU. The CPU sends accuracy information to the liquid crystal display.

Page 9: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 8

MODEL 3000 / 3010

Page 10: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 9

MODEL 3010 SPECIFICATIONS

2.0

Page 11: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 10

BLANK PAGE

Page 12: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 11

2.0 MODEL 3010 SPECIFICATIONS SOURCE ...........................................................................90 to 300 VAC 450 VA Max. TEST POTENTIAL............................................................60 - 600 Volts - Programmable 1 Volt Increments TEST POWER FACTOR...................................................Selectable in 1 Degree Increments TEST CURRENTS ............................................................2.5 to 50A Programmable in .1A increments 2.5 to 9.9A Programmable 1.0A increments 10.0 to 50A Light Load is 10% of Full Load METER FORMS TESTED.................................................1S (19S, 20S, 21S), 2S (19S, 20S, 21S), 3S, 4S, 5S, 6S, 8S, 9S, 10S, 12S, 13S, 14S, 15S, 16S, 25S, 26S, 29S, 30S STANDARD ......................................................................Electronic Radian Research RM-10-01, 02 WATT, or Optional RM-10 or RM-11-06, 08 VAR Optional RM-10 or RM-11-07, 09 VAR and Q TEST REVOLUTIONS ......................................................1 to 999 OPTICS .............................................................................Modulated Visible LED pickup COMPUTER......................................................................Internal Microprocessor with LCD Display CONTACT DEVICE TESTING..........................................Form “C” and Form “A” Test Capability DEMAND TESTING..........................................................Mode 1: Revolutions from 1/999 to 99999 Mode 2: Time Run 99 Hrs, 59 Mins, 59 Secs SYSTEM ACCURACY......................................................KWH ±.05% PF=1.0 (±.02%TYP) PF=.5 (± .04% TYP) KW ±0.25% DIMENSIONS....................................................................19.86” L, 14.8’ W, 10.4’ H WEIGHT ............................................................................43 lbs HOUSING..........................................................................Fiberglass Case, Shock Resistant to 1.0 G WARRANTY .....................................................................Two Years Covering All Parts and Labor. 90 Days on Optional Barcode Reader

Page 13: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 12

BLANK PAGE

Page 14: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 13

MODEL 3010 CONTROLS AND FUNCTIONS

3.0

Page 15: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 14

BLANK PAGE

Page 16: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 15

3.0 CONTROLS AND FUNCTIONS 3.1 FRONT PANEL 3.2 TEST / ELEMENT / METER TYPE BLOCK 3.21 The TEST input key allows the operator to set up for full load, light load, power factor, or the creep test

mode of operation. To select the desired test the operator simply depresses the TEST key until the LED for the desired test is illuminated.

3.22 The ELEMENT input key allows the operator to select series, left, center, or right current elements. Only

valid current elements for the meter form set up in the Model 3010 may be selected. For example a form 5 meter does not have a center current element therefore the test board will only scroll through the series, left, and right current elements.

3.23 The METER TYPE input key will select the type meter to

be tested. The Model 3010 is normally supplied with a Radian Research RM-10-01 or -02 standard. As an option , the unit can be supplied with a Radian Research RM-10-08 or RM-10-09 standard to allow VAR and Q hour meter testing. Depressing this key selects either KWH meter testing, VAR meter testing, or Q meter testing. The normal default phase angles for power factor will be used during VAR and Q hour PF tests.

Page 17: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 16

3.3 COM PORTS BLOCK The surface mounted RJ-11 connectors

located on the front panel of the 3010 provide connection to communication ports 1 and 2. Com Port 1 allows connection to a modem/intelligent interface device. This communications port is designed to fully integrate into the total system environment provided through the WATT-Net™ local area network. With this software package, downloading meter test data as well as meter record keeping information to a host computer can be accomplished. The WATT-Net™ LAN capability provided through this port is fully hardware and software compatible with all Watthour Engineering Co., Inc. products. Com Port 2 is used to provide a serial interface to a printer or bar code reader.

3.4 DISPLAY CONTROL BLOCK This block contains the contrast and

back light controls for the LCD computer display. The solid state electro-luminescent backlight may be turned on or off at the operators discretion as ambient light requires. Likewise the contrast of the LC display may be adjusted by pressing either the up or down arrow keys. Depressing the key once will make one “step” change to the contrast.

3.5 TEST CONTROL BLOCK The functions in this block provide the ADJUST OPTICS, START, AUTO-

SEQUENCE, CANCEL, SAVE TEST AND TEST MODE selections allowing for the start and stop control of tests. The TEST MODE key selects between KWH mode of testing or demand mode testing. The key is depressed to select the desired test and indicated by the LED.

3.6 GATE CONTROL BLOCK The gate control input connector

allows connection of the optical detector for the reflect and solid state pickup probes. The external signal used to compare standards or externally gate the test board is connected here. It is a five pin connector with a blue housing color.

Page 18: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 17

3.7 PULSE INPUT BLOCK The pulse input connections allow KYZ pulse initiator checking. In the demand test mode, the operator is allowed to select either a form A or form C contact input. These are normally associated with the type of KYZ pulse initiator device to be tested. This input will accept either a dry contact or a solid state output type of contact closure. It is a 4 pin connector with a red housing color.

3.8 AUDIO CONTROL BLOCK This control block allows the operator to set an End-Of-Test audible alert

or a Pulse signal to aid in optical adjustments as desired. The audio level may be set by pressing the up or down arrow keys. A LED indicator bar displays the audio level. The audio level indicator bar must have at least one LED illuminated in order for the “beep” tone to be audible.

3.9 KEYPAD Meter test data may be entered via the

keypad. To enter a numeric character simply press the desired number. The cursor will automatically increment to the next space after an approximate ½ second delay. If the specific field can have valid alpha character entries, press the number key associated with the desired character subsequently until the desired alpha character is displayed. If the cursor increments to the next position before the desired character is input, simply use the back arrow key to correct. The space key will blank the character in the cursors position. The right and left arrow keys will move the cursor without blanking the field. The Enter key will accept data entered from any of the 9 main menu selections and also allow the scrolling/viewing of the 9 main menu selections. The MENU/TEST key enables the TEST CONTROL block and allows testing to begin.

Context sensitive help is on-line by pressing the HELP key. To exit the help screens, press the ENTER key. In the main menu portion of the test program, the operator is prompted with the on display to ENTER to scroll through the next menu. The operator may select menu numbers 1 through 9 from any main menu display screen to “jump” to the desired menu.

Page 19: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 18

3.10 INPUT BLOCK The INPUT block contains the main

power switch used to power up the test kit. A three terminal euro connector which allows the operator to connect the main input power cord to the test kit. This AC source should be between 90 and 300 VAC. The Main Power switch is a Circuit Breaker for input protection.

3.11 CONNECTIONS BLOCK This block contains the

connectors that enable the operator to connect to the meter under test. Care should be given not to exceed the burden capabilities of the PAT or the desired output current may not be obtained.

The test leads are color coded to allow easy test set up. Normally the red current leads are for connecting the left element of the meter-under-test, the white (or gray) leads are for the center element connection to the meter, and the black leads are used for the right element connections. Polarity of the paired colors is accomplished by the colored connectors on the PAT (and the corresponding colored rubber boot on the opposite end for leads to test transformer rated meters). The black end of each connection is considered the return for current and voltage. The unit is supplied with one set of potential test leads. These are the red and black leads with the smaller 18 AWG red and black “A” mode connectors.

NOTE: Due to the many and varied test adapters available for field testing of self contained meters, NO connectors are supplied with the self-contained current leads. You must furnish your own lead connectors.

Page 20: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 19

3.12 MODE BLOCK The MODE switch toggles between

READ and TEST modes of operation. In the READ mode the Model 3010 functions as a high quality voltmeter, ammeter and a phase angle meter. In the TEST mode the PAT supplies test current potential to meters under test.

In the READ mode of operation the PAT is used to read voltage, current, and phase angle. The phase angle is read as the number of degrees the current input LAGS the voltage input and indicates from 0 to 359 degrees. It is important that the test kit be powered up and switched into the READ mode BEFORE the current is connected. This is because the current circuit is open with the PAT not powered. In the READ mode, the LEFT current connection is used along with the potential connection in making phase angle measurements. It is again important to assure that the secondary of any CT circuit NOT be opened when making current readings. High and Dangerous voltages could be present in an open CT secondary condition.

The voltage measurement range is from 30 to 600 VAC and the current measurement range is from .1 to 50 amps. When switching back to the TEST mode, a prompt will be shown reminding the operator to remove all test leads and press ENTER to continue. This is because the LEFT current circuit will be OPENED as the TEST mode is entered.

3.13 OPTICAL PICKUP ASSEMBLY The optical pickup assembly has been designed to easily slip on and

off the meter-under-test while maintaining a sure grip on the meter cover. The elastic band provides a positive hold on the meter glass for the optic probe during meter tests. There is a visible red LED to aid in aligning the probe to the meter disk. The wide pickup range of the probe should allow for ease of adjustment for most meters. Should adjustment be required, a sensitivity control is located on the top of the probe (marked SENS) and may be adjusted with the small screwdriver supplied with the PAT. This is a one turn sensitivity control and can easily be damaged if forced past its limits in either direction. In most applications, the sensitivity control should not require adjustment as it has been preset at the factory.

Page 21: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 20

BLANK PAGE

Page 22: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 21

MODEL 3010 SETTING UTILITIES

4.0

Page 23: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 22

BLANK PAGE

Page 24: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 23

4.0 SETTING UTILITIES The following are step by step instructions for the initial default settings of the Model 3010. These default settings include: Date, Time, Decimal Precision, and setting the Unit ID for the WATT-Net™ option. ( 1 ) Power up the unit using the red Main Power Switch located on the left side panel. • The following front panel LED status LEDs should be illuminated: TEST: Full Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on METER TYPE: Watt LED on ( 2 ) Press the ENTER key to scroll through the menu selections. NOTE: Press on either end of the Enter key and not in the center. ( 3 ) Press the 6 key to select the Utilities program.

• It is not necessary to have the Utilities program displayed to select it, the operator only needs to press the appropriate key while on the menu screen.

( 4 ) From the Utilities menu screen Press the 1 key to set the Time and Date.

• Enter the correct Time and Date using the key pad • Press ENTER to save the information and return to the Utilities menu.

( 5 ) Press the 2 key to set the precision of the test results and if the results are to be displayed as % error or % registration and the number of decimals to display in the calculated test results.

• Enter the preferred information using the key pad. • Press ENTER to save the information and return to the Utilities menu.

( 6 ) Press the 3 key to set the Unit ID ( for WATT-Net™ option ) and baud rate.

• Enter the preferred information using the key pad. • The unit serial number is displayed on this screen along with the factory supplied standard serial number. • Press ENTER to save the information and return to the Utilities menu.

( 7 ) Press the 4 key to enter the type of standard i.e. a 150 amp standard or a 200 amp standard. The Ke of the standard for the 150 amp version is 0.00001 and 0.00002 for the 200 amp version.

• Press the ENTER key to return to the Utilities menu. ( 8 ) Press the 0 key to clear any untransmitted test records in the 3010. For non-networking applications, this is the only way to clear any stored data. The screen displays an operator prompt to confirm the choice. ( 9 ) Press the ENTER key again to return to the main menu screen.

Page 25: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 24

BLANK PAGE

Page 26: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 25

MODEL 3010 TESTING PROCEDURES

5.0

Page 27: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 26

BLANK PAGE

Page 28: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 27

5.1 TUTORIAL FOR MANUAL TESTING In this example, the step by step instructions for a manual test are shown for a Form 2 meter 240 volt, 30 test amps, and kh of 7.2: (Assure that the meter under test has no voltage or current applied from any other source.) 1. Connect the A and C phase current leads as required by the meter form to be tested. Refer to Section 8.0 for the meter current and potential internal meter wiring diagrams. 2. Connect the potential leads as required by the meter form to be tested. Refer to Section 8.0 for the meter current and potential internal meter wiring diagrams. 3. Connect the ground lead (green boot) to the grounding post on the PAT. Connect alligator clip to a

SECURE GROUND. 4. Attach the reflect mode optics pickup or solid state pickup or K-Y or K-Z contact input depending upon

the situation to the nut located on the site of the rubber band clamp. 5. Connect the 6 pin circular connector to the GATE CONTROL 6 pin connector on the PAT. 6. Connect the line cord to the three terminal euro-connector on the PAT. If field testing, use field power

cord supplied with the PAT. (If option shop stand adapter is used then the power cord should be connected to a 120 VAC outlet.)

7. After setting the on/off switch to on, note that the following menus are displayed and status indicators

illuminated.

NOTE: A detailed flow chart can be reviewed in Section 6.0 that shows step by step instructions for this test.

The ON/OFF rocker switch is located on the right hand side of the PAT above the fan guard and fan chimney. Pressing this switch will power the unit on. Note that the fan will start and the LCD display will show the following sign-on message followed by the first main menu.

Watthour Engineering Portable Rev X.X Automated Test Kit

After a slight delay following the sign-on screen, the PAT displays the following operator main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

Page 29: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 28

The following front panel LED status lights should be illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Full Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on 8. Check meter form by pushing 1 (METER SETUP) on the main menu. For this example the KWH meter

setup is confirmed by the menu:

KWH METER SETUP Form: 2 Volts: 240 Kh: 7.2 Amps: 30

NOTE: If changes need to be made on this menu, use the right and left arrow keys in the keypad block to move the cursor to the desired field to edit. By over-writing the old values with the new changes, field selections may be changed as required.

Pressing the ENTER key returns to the first main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

9. Revolutions are set by pressing 2 EDIT DEFAULTS and then selecting number 3 EDIT TEST REVS as

shown on the following menu: Meter Default Screen

EDIT DEFAULTS 1 EDIT KWH DEFAULTS 2 EDIT KW DEFAULTS 3 EDIT TEST REVS

SERIES REVS ELEM FL 1 FL 1 LL 1 LL 1 PF 1 PF 1

Press the ENTER key to return to the first main menu: 10. The optic pickup assembly should be placed so that the probe is in the same horizontal plane as the

meter disk. Some top to bottom adjustment has been provided to aid the operator in the optic set-up. Loosen the thumb screw and position the assembly so that the red LED spot is centered on the meter disk.

11. Pressing the MENU/TEST key will enable the TEST CONTROL block and change the menu to the

following:

As Found As Left FL . . LL . . PF . .

Page 30: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 29

Pressing the ADJUST OPTICS key will set the unit to the adjust optics mode. The PAT displays the following operator prompt after setting these internal voltage and current set points:

Adjusting Optics Volts: 240 Amp: 30.0 Phase: 0 Rev: CANCEL to stop

12. To perform a manual full load series test, the following front panel LED status lights should be

illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Full Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on To initiate the test, press the START key. This key may be pressed without canceling the adjust optics mode. After the test has started the unit displays the following:

Energized for Test Volts: 240 Amp: 30.0 Phase: 0 Rev: CANCEL to stop

Following an approximate 3 second delay to allow the meter standard to stabilize, the test menu is displayed during the actual test as shown:

Test in Progress Volts: 240 Amp: 30.0 Phase: 0 Rev: 0 CANCEL to stop

As the test progresses, actual voltage, current, phase angle, and revolutions are displayed on this screen. At the conclusion of the test, the test results screen is displayed as follows:

As Found As Left FL 100.00 100.00 LL . . PF . .

Page 31: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 30

From this point, choices include viewing internal standards count, clearing test results, or saving the test record. These choices are shown on the following menu after the HELP key is pressed.

2 SHOW STD COUNT 3 CLEAR RESULTS

NOTE: It is not necessary to have this screen displayed for the key choices to be effected. The operator may press the 2 or 3 key after the test completes.

13. To perform a manual Light Load series test, press the TEST key until the Light Load LED is on and the

following front panel LED status lights are illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Light Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on To initiate the test press the START key.

Energized for Test Volts: 240 Amp: 3.0 Phase: 0 Rev: CANCEL to stop

Following an approximate 3 second delay to allow the meter standard to stabilize, the test menu is displayed during the actual test as shown:

Test in Progress Volts: 240 Amp: 3.0 Phase: 0 Rev: 0 CANCEL to stop

As the test progresses, actual voltage, current, phase angle and revolutions are displayed on this screen. At the conclusion of the test, the test results screen is displayed as follows:

As Found As Left FL 100.00 100. 00 LL 99.99 99.99 PF . .

Page 32: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 31

From this point, choices include viewing standard counts and clearing or saving the test. These choices are shown on the following menu after the HELP key is pressed.

2 SHOW STD COUNT 3 CLEAR RESULTS

14. To perform a manual Power Factor series test, press the TEST key until the Power Factor LED is on

and the following front panel LED status lights are illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Power Factor LED on TEST MODE: KWH LED on ELEMENT: Series LED on To initiate the test, press the START key.

Energized for Test Volts: 240 Amp: 30.0 Phase: 60 Rev: CANCEL to stop

Following an approximate 3 second delay to allow the meter standard to stabilize, the test menu is displayed during the actual test as shown:

Test in Progress Volts: 240 Amp: 30.0 Phase: 60 Rev: 0 CANCEL to stop

As the test progresses, actual voltage, current, phase angle, and revolutions are displayed on this screen. At the conclusion of the test, the test results screen is displayed as follows:

As Found As Left FL 100.00 100.00 LL 99.99 99.99 PF 100.03 100.03

From this point, choices include viewing standards counts and clearing or saving the test. These choices are shown on the following menu after the HELP key is pressed.

2 SHOW STD COUNT 3 CLEAR RESULTS

After the initial test(s), subsequent meter tests would update the results as the meter is adjusted in the As Left column on the display.

Page 33: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 32

15. To perform a Creep test (Voltage Only applied to the Meter), press the TEST key until the CREEP LED

is on and the following front panel LED status lights are illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Creep LED on TEST MODE: KWH LED on ELEMENT: Series LED on To initiate the test, press the START key.

Energized for Creep Volts: 240 Amp: 0.0 Phase: 0 Rev: CANCEL to stop

To begin a Test from Creep, simply press the TEST and/or ELEMENT key until the desired test is displayed. Press the START key to start the test. When the test has completed the voltage will remain on the meter. The accuracy will be displayed and “CR” shown on the screen to indicate voltage is still applied.

CR As Found As Left FL 100.01 100.01 LL PF

Page 34: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 33

5.2 TUTORIAL FOR AUTO SEQUENCE TESTING In this example, the step by step instructions for setting up an automatic sequence and performing the test are shown for a Form 2 meter 240 volt, 30.0 test amps, and Kh of 7.2: (Assure that the meter under test has no voltage or current applied from any other source.) 1. Connect the A and C phase current leads as required by the meter form to be tested. Refer to Section 8.0 for the meter current and potential internal meter wiring diagrams. 2. Connect the potential leads as required by the meter form to be tested. Refer to Section 8.0 for the meter current and potential internal meter wiring diagrams. 3. Connect the ground lead (green boot) to the grounding post on the PAT. Connect Alligator clip to a

SECURE GROUND. 4. Attach the reflective mode optics pickup or solid state pickup or K-Y or K-Z contact input depending

upon the situation to the meter. 5. Connect the 5 pin circular connector (Blue) to the GATE CONTROL 5 pin connector on the PAT. 6. Connect the line cord to the three terminal euro-connector on the PAT. If field testing, use field power

cord supplied with the PAT. 7. After setting the on/off switch to on, note that the following menus are displayed and status indicators

illuminated. The ON/OFF rocker switch is located on the right hand side of the PAT above the fan guard and fan chimney. Pressing this switch will power the unit on. Note that the fan will start and the LCD display will show the following sign-on message followed by the first main menu.

Watthour Engineering Portable Rev X.X Automated Test Kit

After a slight delay following the sign-on screen, the PAT displays the following operator main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

The following front panel LED status lights should be illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Full Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on

Page 35: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 34

8. Check meter form by pushing 1 (METER SETUP) on the main menu. For this example the KWH meter

setup is confirmed by the menu:

KWH METER SETUP Form: 2 Volts: 240 Kh: 7.2 Amps: 30.0

NOTE: If changes need to be made on this menu, use the right and left arrow keys in the keypad block to move the cursor to the desired field to edit. By over-writing the old values with the new changes field selections may be changed as required.

Pressing the ENTER key returns to the first main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

9. The optic pickup assembly should be placed so that the probe is in the same plane as the meter disk.

Some top to bottom adjustment has been provided to aid the operator in the optic set-up. Loosen the thumb screw and position the assembly so that the red LED spot is centered on the meter disk.

10. Pressing key 3 (EDIT AUTO SEQUENCE) will change the menu to the following (see Section 6.0

Screen Flow Charts):

ENTER AUTO SEQUENCE #: _ (1-9) ENTER 0 to EXIT

After entering sequence #1 in the sequence number field, the meter test steps for this sequence may be viewed and/or edited as follows:

Sequence 1 Step 1 ELEMENT: S --BLANK TEST: FL TO 0 ANGLE: 0 EXIT

Sequence 1 Step 2 ELEMENT: S --BLANK TEST: PF TO 0 ANGLE: EXIT

Sequence 1 Step 3 ELEMENT: S --BLANK TEST: LL TO 0 ANGLE: 0 EXIT

Page 36: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 35

Sequence 1 Step 4 ELEMENT: --BLANK TEST: TO 0 ANGLE: EXIT

Up to 12 sequences may be entered in any order that the operator desires. If less than 12 sequences are required, then the operator must enter a blank in the element field to terminate the sequence. Programmable phase angles may be entered from -89 to +89 degrees. If a current is chosen for a non-existent element on that form, the unit displays the error message and continues. Valid entries for the field entries for the previous screens are displayed by pressing the HELP key from the sequence entry screens. The resultant screen help is:

ELEMENT FIELD S,L,C, or R TEST FIELD FL, LL, PF, or CR

An ENTER key will return the display to the first main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

11. Pressing the MENU/TEST key enables the TEST CONTROL block and will return the results screen:

As Found As Left FL . . LL . . PF . .

Pressing the AUTO SEQUENCE key will prompt the operator for the sequence number desired. After the operator inputs the desired sequence number ( in this example 1) the following screen is displayed:

ENTER AUTO SEQUENCE #: 1 (1-9) ENTER 0 to EXIT

NOTE: If the unit is entergized for Creep, an Autosequence can be started. When the test is finished Creep (Voltage) will remain on the Meter.

Page 37: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 36

The PAT displays the following operator prompt after setting these internal voltage and current set points:

Energized for Test Volts: 240 Amp: 30.0 Phase: 0 Rev: CANCEL to stop

Following an approximate 3 second delay to allow the meter standard to stabilize, the test menu is displayed during the actual test as shown:

Test in Progress Volts: 240 Amp: 30.0 Phase: 0 Rev: CANCEL to stop

As the test progresses through each sequence, actual voltage, current, phase angle, and revolutions are displayed on this screen. At the conclusion of each test, the test results screen is momentarily displayed, and that test point result is displayed on screen as follows:

As Found As Left FL 100.00 100.00 LL 99.99 99.99 PF 100.06 100.06

This screen and the previous test in progress screen toggle as each of the test sequences is completed. The operator may determine which sequence point is being run by observing the front panel LEDs. After all the sequences have completed, the PAT will display the test result screen. Test results may be reviewed for series or element test (if applicable) by pressing the element key successively. From this point, choices include, saving the data for statistics, showing standard counts, and clearing or saving the test. These choices are shown on the following menu after the HELP key is pressed.

2 SHOW STD COUNT 3 CLEAR RESULTS

Page 38: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 37

5.3 TUTORIAL FOR READ MODE TESTING (OPTIONAL BURDEN TESTING) In this example, the step by step instructions are given for reading voltage, current, and phase angles: 1. Connect the ground lead (green boot) to the grounding post on the PAT. Connect Alligator clip to a

SECURE GROUND. 2. Connect the line cord to the three terminal euro-connector on the PAT. If field testing, use field power

cord supplied with the PAT. 3. After setting the on/off switch to on, note that the following menus are displayed and status indicators

illuminated. The ON/OFF rocker switch is located on the right hand side of the PAT above the fan guard and fan chimney. Pressing this switch will power the unit on. Note that the fan will start and the LCD display will show the following sign-on message followed by the first main menu.

Watthour Engineering Portable Rev X.X Automated Test Kit

After a slight delay following the sign-on screen the PAT displays the following operator main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

The following front panel LED status lights should be illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Full Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on 4. Press the MODE button and note that the READ LED is on. The maximum limits on the inputs are 600

volts ac on the potential and 50.0 amps AC on the current. For this example, the read setup is confirmed by the menu:

READ MODE

Volts: 0.0 Amps: .00 0 Angle:

NOTE: If current and voltage are not present, the phase angle meter does not display phase.

Page 39: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 38

5. Connect the "A" phase (left) current lead to the current to be measured. WARNING: The current circuit is not a closed circuit until the PAT is powered on and in the READ mode. Care should be made to assure that any CT secondary current path is not opened causing the possibility of exposed high voltage. 6. Connect the potential leads as required to measure the voltage point to be tested. When measuring voltage, current, and phase, the display would appear as follows for the 5 A and 120 volt 60 degree lagging example:

READ MODE Volts: 120.0 Amps: 5.0 0 Angle: 60.0

7. The READ mode may be terminated by again pressing the READ button and observing the following

display message:

Disconnect ALL Test Leads

then Press Enter

8. After removing the test leads and pressing the ENTER key, the PAT will return to the TEST mode and

display the main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

5.3.1 BURDEN OPTION If your Model 3010 is equipped with the CT burden option it may be selected when in the read mode. While reading and observing the CT secondary current on the display, the following keys and associated Ohms burden can be pressed and applied:

1 - 0.1 Ohm 2 - 0.2 Ohms 3 - 0.5 Ohms 4 – 1 Ohm 5 – 2 Ohms

The associated burden will be applied for approximately 5 seconds and automatically be removed. It can manually be removed prior to 5 seconds by pressing the associated key again. Changes in the current magnitude are observed to determine possible CT problems.

Page 40: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 39

5.4 TUTORIAL FOR SELF CHECK In this example, the step by step instructions are given for a system self check. This test will test elements of the real time clock and standard measuring system (see Section 6.0 Screen Flow Charts). 1. Connect the line cord to the three terminal euro-connector on the PAT. If field testing, use field power

cord supplied with the PAT. 2. After setting the on/off switch to on, note that the following menus are displayed and status indicators

illuminated. The ON/OFF rocker switch is located on the right hand side of the PAT above the fan guard and fan chimney. Pressing this switch will power the unit on. Note that the fan will start and the LCD will show the following sign-on message followed by the first main menu.

Watthour Engineering Portable Rev X.X Automated Test Kit

After a slight delay following the sign-on screen the PAT displays the following operator main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

The following front panel LED status lights should be illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Full Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on 6. Press the ENTER button again and note that the menu scrolls through to the next menu in the main

menu series. For this example, the self test is confirmed by the menu:

4 SELF TEST 5 STANDARDS COMPARE 6 UTILITIES ENTER for next menu

Page 41: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 40

NOTE: It is not necessary to be in this menu to select the self test, only that the operator press key 4 to enter the self test mode.

7. After pressing key 4 for this example, the self test setup is confirmed by the menu:

SELF CHECK SHORT Current Leads

ENTER to Continue

8. Short all three current leads together by clipping the like colored wires together. Pressing the ENTER

key will initiate the self test. Pressing any number key will exit to one of three main menus. First the LCD segments are tested one row at a time. As the test is running, the PAT will display the following menu and check a calculated vs actual standard count to determine if the unit is functioning normally. As the test proceeds, each individual element is checked and confirmed on the following menus:

SELF CHECK Running Testing Left Element

SELF CHECK Running

LEFT ELEMENT OK Testing Right Element

The test continues until all elements have been tested.

SELF CHECK Running LEFT ELEMENT OK RIGHT ELEMENT OK CENTER ELEMENT

ENTER to exit

LEFT ELEMENT OK RIGHT ELEMENT OK CENTER ELEMENT OK

9. After pressing the ENTER key, the PAT will return to the TEST mode and show the main menu that was

last displayed:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

NOTE: The Self Check may be canceled at any time during the test by pressing the CANCEL

key.

Page 42: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 41

5.5 TUTORIAL FOR STANDARDS COMPARE In this example, the step by step instructions are given internal standard comparison with an external standard (see Section 6.0 Screen Flow Charts): 1. Connect the A, B and C phase current leads to the current coil of the standard to be measured. The

current circuit is not a closed circuit until the PAT is powered on and in the appropriate TEST or READ mode.

2. Connect the potential leads as required to the external standard to be tested. 3. Connect the ground lead (green boot) to the grounding post on the PAT. Connect Alligator clip to a

SECURE GROUND. 4. Connect the line cord to the three terminal euro-connector on the PAT. If field testing, use field power

cord supplied with the PAT. 5. After setting the on/off switch to on, note that the following menus are displayed and status indicators

illuminated. The ON/OFF rocker switch is located on the right hand side of the PAT above the fan guard and fan chimney. Pressing this switch will power the unit on. Note that the fan will start and the LCD display will show the following sign-on message followed by the first main menu.

Watthour Engineering Portable Rev X.X Automated Test Kit

After a slight delay following the sign-on screen, the PAT displays the following operator main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

The following front panel LED status lights should be illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Full Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on 6. Press the ENTER button again and note that the menu scrolls through to the next menu in the main

menu series. For this example, the Standards Compare is confirmed by the menu:

4 SELF TEST 5 STANDARDS COMPARE 6 UTILITIES ENTER for next menu

Page 43: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 42

NOTE: It is not necessary to be in this menu to select the Standards Compare, only that the operator press key 5 to enter the standards compare mode.

7. After pressing Key 5 for this example, the standards compare test mode is confirmed by the menu:

STANDARDS COMPARE Connect Standard as

Form 9 ENTER to Continue

8. After pressing the ENTER key, the operator is prompted to select whether to generate with this unit. 9. After selecting "yes" to generate with that unit, the option is given to test a single or a multiple number of

standards.

STANDARDS COMPARE 1 Single Standard 2 Multiple Standards

ENTER to Exit 10. Assuming a single standard selection, the potential and the current leads are connected to the external

electronic standard. The tester is prompted to enter the test time in seconds to be used for the test. 11. The external standard pulse output is connected to the gate of the PAT with the cable provided.

Pressing the ENTER key will allow the menu entry to set the voltage, current, and proper Ke for the external standard for the comparison test. Pressing the MENU/TEST key will exit the check.

STANDARDS COMPARE

Volts: 120 0 Angle: 0 Amps: 5 Ext STD Ke: .00001

The HELP key may be pressed to show the help screen for the standards compare. Pressing the ENTER key will exit the help screens.

HELP for Compare STD START to run MENU to EXIT

Pressing the START button will initiate the standards compare. While this test is executing, the following menus will be displayed:

STANDARDS COMPARE WAITING FOR CONTROL

Page 44: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 43

STANDARDS COMPARE

RUNNING TEST

X.XX The test continues for the entered test time. The test may be terminated with the CANCEL key after the run screen is displayed. At the conclusion of the comparison test, the results menu will display the accuracy as shown:

STANDARDS COMPARE Internal REF 100.001 External REF 99.999

ENTER to Continue 11. After pressing the ENTER key, the PAT will return to the standards compare screen to allow the entry of

an additional test point to be checked. Pressing MENU/TEST will exit to the MAIN MENU.

4 SELF TEST 5 STANDARDS COMPARE 6 UTILITIES ENTER for next menu

MULTIPLE STANDARDS COMPARISON To test multiple standards, the standards must have the reset/gate coax input lines bussed and the optional switch/adapter installed. This may be accomplished by using a coax "tee" connector for each standard. Coaxial jumpers should be used to jumper the gate signal from one standard to the other. After the connections have been made for the standards, the START key is pressed and the display will show a waiting for control message. Once the setpoints have been found and the countdown timer is running, the reset/gate push button switch should be pressed to start the internal and external standards. The reset gate switch should be pressed again before the time out period to ensure an accurate test interval. At the end of the test the PAT display will read out in kwh directly to allow comparison of the standards. The optional switch and adapter allow up to 7 Radian standards to be tested at once.

Page 45: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 44

MODEL 3010 P.A.T. STANDARDS COMPARE CABLE DIAGRAM

Page 46: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 45

5.6 TUTORIAL FOR SETTING UTILITIES In this example, the step by step instructions are given for setting up the internal defaults. These include Date and Time, Decimal Precision, and setting the Unit ID for the WATT-Net™ option. 1. Connect the cables and connectors as in previous examples for testing a meter. 2. Connect the ground lead (green boot) to the grounding post on the PAT. Connect Alligator clip to a

SECURE GROUND. 3. Connect the line cord to the three terminal euro-connector on the PAT. If field testing, use field power

cord supplied with the PAT. 4. After setting the on/off switch to on, note that the following menus are displayed and status indicators

illuminated. The ON/OFF rocker switch is located on the right hand side of the PAT above the fan guard and fan chimney. Pressing this switch will power the unit on. Note that the fan will start and the LCD will show the following sign-on message followed by the first main menu.

Watthour Engineering Portable Rev X.X Automated Test Kit

After a slight delay following the sign-on screen, the PAT displays the following operator main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

The following front panel LED status lights should be illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Full Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on 5. Press the ENTER button again and note that the menu scrolls through to the next menu in the main

menu series. For this example, the Utilities menu is confirmed by:

4 SELF TEST 5 STANDARDS COMPARE 6 UTILITIES ENTER for next menu

NOTE: It is not necessary to be in this menu to select the Utilities, only that the operator press key 6 to enter the Utilities menu from any of the three main menus.

Page 47: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 46

6. After pressing key 6 for this example, setting the default parameters is confirmed by the menu (see

Section 8.0 Meter Hookup Diagrams):

1 SET TIME AND DATE 2 SET RESULTS DSPLAY 3 SET UNIT ID 4 SET STANDARD TYPE

7. Press Key 1 to set the time and date. Pressing the ENTER key will allow the operator to accept the

present values displayed on screen. The PAT will display the following menu:

TIME and DATE TIME: 21:22:01 DATE: 05/01/90

Pressing the ENTER key will exit the Time and Date screen. 8. Press Key 2 to set precision of the test results and the results displayed in % error or % registration.

Pressing the ENTER key will allow the operator to accept the present values displayed on screen. The PAT will display the following menu:

1 - % ERROR 2 - % REGISTRATION Results: 2 Decimals: 2 (1 or 2)

Pressing the ENTER key will exit the Results screen. 9. Press Key 3 to set the Unit ID of the PAT for networking. This screen also displays the unit serial

number and the factory supplied RM-10 serial number. The internal PAT serial number (SN) is not changeable, but the standard serial number can be changed. Pressing the ENTER key will allow the operator to accept the present values displayed on screen. The PAT will display the following menu:

UNIT SETUP

UNIT ID: 1 (1-254) BAUD: 9600 SN xxxxxxx STD xxxx

Pressing the ENTER key again will return the PAT to the previous main menu screen. 10. Press Key 4 to enter a different standard serial number. Selection is also available to enter either a 150

amp or 200 amp standard:

SETUP FOR STANDARD STANDARD SN: 3331 FULL SCALE AMP: 200 AMP=150 OR 200

Page 48: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 47

Pressing the ENTER key will return to the previous menu. 11. Press Key 0 to clear any un-transmitted test records in the PAT. For non-networking applications, this is

the ONLY way to clear any stored data. The screen displays an operator prompt to confirm this choice:

Do you want to clear UnXmitted records 1 YES 2 NO

Pressing the ENTER key will exit the Unit ID screen. Pressing the ENTER key again will return the PAT to the previous main menu screen.

Page 49: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 48

5.7 TUTORIAL FOR SAVING A TEST RECORD 1. After performing a meter test, the operator may have results similar to the following:

As Found As Left FL 100.00 100.00 LL 99.99 99.99 PF 100.06 100.06

The operator may save the test record by pressing the SAVE TEST key within the Test Control area. After entering SAVE TEST key and if not entered prior to starting the test, the PAT will prompt the operator to enter the meter data:

Do you want to Enter Meter Setup Data 1 YES 2 NO

Answering this screen with a key 1 will allow the meter test parameters to be stored in memory. If your unit is equipped with the WATT-Net™ option, the actual data storage format will vary according to your company record format specifications. The operator will be prompted for the following information:

Enter MFG Serial # (10 DIGITS) XXXXXXXXXX

Enter MFG Code (2 CHARS) XX

Enter TEST CODE (2 CHARS) XX

Enter Fnd KWH (5 DIGITS) XXXXX

Enter Lft KWH (5 DIGITS) XXXXX

Page 50: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 49

After entering the previous data, the PAT responds with the menu screen:

Holding 1 Records

This screen indicates a test record was saved, and the PAT is storing the indicated number of records.

Clear Test Results 1 YES 2 NO

Pressing 1 (YES) will clear the test data from the display. The results are still saved.

Page 51: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 50

5.8 TUTORIAL FOR EDITING A TEST RECORD NON-NETWORKING EXAMPLE 1. After entering selection No. 8 from the main menu, the operator will be prompted for the following

information (see Section 6.0 Screen Flow Charts):

Enter MFG Serial # (10 DIGITS) XXXXXXXXXX

Enter Amps (3 DIGITS) XXX

Enter MFG Code (2 CHARS) XX

Enter As Lft KWH (5 DIGITS) XXXXX

Enter Test Code (2 CHARS) XX

As Found As Left FL 100.05 100.00 LL 99.95 100.01 PF 100.08 099.99

Enter As Fnd KWH (5 DIGITS) XXXXX

“A” As Found As Left FL 100.05 100.00 LL 99.95 100.01 PF 100.08 099.99

Enter Form No. (2 DIGITS) XX

“B” As Found As Left FL 100.05 100.00 LL 99.95 100.01 PF 100.08 099.99

Enter Kh (5 DIGITS) XXXXX

“C” As Found As Left FL 100.05 100.00 LL 99.95 100.01 PF 100.08 099.99

Enter Voltage (3 DIGITS) XXX

TEST DATE TIME: hh:mm:ss DATE: mm/dd/yy

Edit Record

1 = Next 2 = Previous 3 = Quit

Page 52: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 51

5.9 DEMAND TESTING TUTORIAL In this example, the step by step instructions for a manual test is shown for a form 9 meter 120 volt, 5.0 test amps, and Kh of 1.8: 1. Connect the A, B, and C phase current leads as required by the meter form to be tested. Refer to Section 8.0 for the meter current and potential internal meter wiring diagrams. 2. Connect the potential leads as required by the meter form to be tested. Refer to Section 8.0 for the meter current and potential internal meter wiring diagrams. 3. Connect the ground lead (green boot) to the grounding post on the PAT. Connect Alligator clip to a

SECURE GROUND. 4. Connect the line cord to the three terminal euro-connector on the PAT. If field testing, use field power

cord supplied with the PAT. 5. After setting the on/off switch to on, note that the following menus are displayed and status indicators

illuminated. The ON/OFF rocker switch is located on the right hand side of the PAT above the fan guard and fan chimney. Pressing this switch will power the unit on. Note that the fan will start and the LCD display will show the following sign-on message followed by the first main menu.

Watthour Engineering Portable Rev X.X Automated Test Kit

After a slight delay following the sign-on screen, the PAT displays the following operator main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

The following front panel LED status lights should be illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Full Load LED on TEST MODE: KWH LED on ELEMENT: Series LED on 6. Check meter form by pushing 1 (METER SETUP) on the main menu. For this example the kwh meter

setup is confirmed by the menu:

KWH METER SETUP Form: 9 Volts: 120 Kh: 1.8 Amps: 5.0

Page 53: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 52

NOTE: If changes need to be made on this menu, use the right and left arrow keys in the keypad block to move the cursor to the desired field to edit. By over-writing the old values with the new changes, field selections may be changed as required.

Pressing the ENTER key returns to the first main menu:

1 METER SETUP 2 EDIT DEFAULTS 3 EDIT AUTO SEQUENCE ENTER for next menu

7. To perform a demand test, press the TEST MODE button to select the demand mode of operation. The

following front panel LED status lights should be illuminated: MODE: Test LED on METER TYPE: Watt LED on TEST: Full Load LED on TEST MODE: DEMAND LED on ELEMENT: Series LED on Pressing the MENU/TEST Key enables the TEST CONTROL block and displays the following:

DEMAND TEST MULT: AMPS: MP: REVS TIME: : : 0

To initiate the warm-up, press the ADJUST OPTICS key. This key allows application of the potential only to the meter. To stop press CANCEL. Following any required warm up time, the test may be initiated by pressing the START key. After the test has started the unit displays the following:

DEMAND RUN KYZ KW . EXP DI . ACT REVS:

Page 54: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 53

5.10 PULSE INITIATOR TESTING ( 1 ) Power up the unit using the main power switch located within the Input Power area on the front panel.

• Enter demand test mode by pressing the TEST MODE key until the Demand LED is illuminated. ( 2 ) Press the MENU/TEST key to display the Demand Test set up screen.

• Use Return or Arrow keys to move the cursor to the Mp field and enter the value of the contact device.

( 3 ) Enter the proper Contact Form in the FRM field. Make certain the proper Contact Form LED(either A or C) is on within the KYZ block. Use the SETUP screen to make a change during entry. ( 4 ) Enter desired Test Time or Test Revolutions ( 5 ) Start the Test with the START key in the TEST CONTROL block.

• The expected pulses will be displayed and actual pulses received will be shown with the count being updated every second. • If a continuous test is selected, then the expected pulses will be blank but will indicate the proper value when the test is complete.

TEST COMPLETE Press (CANCEL)

Page 55: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 54

BLANK PAGE

Page 56: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 55

MODEL 3010 SCREEN FLOW CHARTS

6.0

Page 57: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 56

BLANK PAGE

Page 58: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 57

MAIN SCREENS

1 METER SETUP2 EDIT DEFAULTS3 EDIT AUTO SEQUENCE

4 SELF TEST5 STANDARDS COMPARE6 UTILITIES

7 RESERVED

9 MANUAL TEST ENTRY8 EDIT STORED TEST

ENTER

ENTER

ENTER

ENTER FOR NEXT MENU

ENTER FOR NEXT MENU

ENTER FOR NEXT MENU

WATTHOUR ENGINEERINGPORTABLE

AUTOMATEDTEST KIT

(POWER UP SCREEN)

REV 1.2

Page 59: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 58

METER SETUP

MAIN SCREENS

KWH METER SETUPFORM:Kh:

VOLTS:AMPS: HELP

1

VALID FORM1-6, 8-10, 12-16,

25, 26, 29

ENTER"ENTER CURRENT

PARAMETERS"

KWH METER SETUPFORM: 2Kh: 7.2

VOLTS: 240AMPS: 30

ENTER

METER

Page 60: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 59

EDIT DEFAULTS

MAIN SCREENS

ENTER

2

DEMAND SETUPTIMING INT: 15 MINKYZ FORM: A (A,C)

FORM:Kh:

VOLTS:AMPS:

1 KWH DEFAULTS2 KW DEFAULTS3 EDIT TEST REVS

ENTER TO EXIT

21 3

EDIT KWH DEFAULTS

EOT: 3

ENTER

END OF TEST HELP

1=NEITHER2=VOLTAGE

3=CURRENT4=BOTH

DE-ENERGIZE

FF 1LL 1PF 1

SERIES REVS ELEMSFF 1LL 1PF 1

ENTER

HELP

ENTER ENTER

Page 61: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 60

EDIT AUTO SEQUENCES

MAIN SCREENS

HELP

3

ENTER

ENTER AUTO SEQUENCE#: ___ (1-9)

ENTER 0 TO EXIT

1

SEQUENCE 1

TEST: FLBLANK

TOELEMENT: S

ENTER

ENTER

0

ENTER AUTO SEQUENCE# 0 : (1-9)

ENTER 0 TO EXIT

ENTER AUTO SEQUENCE#: 1 (1-9)

ENTER 0 TO EXIT

STEP 1

EXIT

ELEMENT FIELD:

TEST FIELD:FL, LL, PF, or CR

S, L, C, OR R

ENTER

SEQUENCE 1

TEST: PFBLANK

TOELEMENT: S

STEP 2

EXIT

SEQUENCE 1

TEST: LLBLANK

TOELEMENT: S

STEP 3

EXIT

ENTER

0 ANGLE:

0 ANGLE:

0 ANGLE:

SEQUENCE 1

TEST:--BLANK

TOELEMENT: __

STEP 4

EXIT

ENTER

0 ANGLE:

ENTER

Page 62: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 61

SELF TEST

MAIN SCREENS

4

START

SEGMENT CHECK

SELF CHECK RUNNINGTESTING LEFT ELEM.

CANCEL

SELF CHECKSHORT CURRENT LEADS

START TO CONTINUE

SELF CHECK RUNNINGLEFT ELEMENT OK

TESTING RIGHT ELEM.

SELF CHECK RUNNINGLEFT ELEMENT OKRIGHT ELEMENT OK

TESTING CENTER ELEM.

ENTER TO EXITLEFT ELEMENT OKRIGHT ELEMENT OK

CENTER ELEMENT OK

CANCEL

CANCEL

CANCEL

CANCEL PRESS CANCEL TO EXIT

Page 63: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 62

STANDARDS COMPARE

MAIN SCREENS

5

ENTER

STANDARDS COMPARE

STANDARDS COMPARE1 - SINGLE STANDARD

ENTER

STANDARDS COMPARESTART to RESET

STANDARDS COMPAREVOLTS: 240AMPS: 30

EXIT STD Ke .00001

CONNECT STANDARD ASFORM 9

STANDARDS COMPAREGENERATE WITH THISUNIT? 1=YES 2=NO

1 2

1 2

2 - MULTIPLE STANDARDS

STANDARDS COMPAREVOLTS: 240AMPS: 30

STANDARDS COMPARE

STANDARDS COMPARE

START

STANDARDS COMPAREWAITING FOR CONTROL

STANDARDS COMPAREINTERNAL STANDARD

ENTER TO CONTINUE

0 ANGLE: 0 0 ANGLE: 0

WAITING FOR CONTROL

RUNNING TEST

00:00

STANDARDS COMPAREINTERNAL REF 100.001EXTERNAL REF 99.999

ENTER TO CONTINUE720000

CANCEL

CANCEL

CANCEL

START

CANCEL

ENTER TEST TIME(3 DIGITS)XXX SECONDS

ENTER TEST TIME(3 DIGITS)XXX SECONDS

ENTERENTER

CANCEL

CANCELCANCEL

ENTER

STANDARDS COMPARERUNNING TEST

00:00

CANCEL

CANCEL

Page 64: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 63

UTILITIES

MAIN SCREENS

6

ENTER

1 SET TIME AND DATE

1 - % ERROR2 - % REGISTRATION

UNIT SETUPUNIT ID: _ 1 (1-254)

BAUD: 9600

DO YOU WANT TO CLEARUN XMITTED RECORDS?

1=YES2=NO

2 SET RESULTS DSPLAY3 SET UNIT ID4 SET STANDARD TYPE

TIME AND DATE

DATE: 02/10/90TIME: 11:31:16

ENTER

0

RESULT: 2DECIMALS: 2 (1 OR 2)

SETUP FOR STANDARD

FULL SCALE AMP: 200STANDARD SN: 3331

DO YOU WANT TO CLEARALL MEMORY?

2=NO1=YES

1 2 3 4

SN 9001051 STD 6073 AMP = 150 OR 200

ENTER ENTER

21

21

POWER ON MESSAGE"ALL MEMORY

ITEMS CLEARED"

ENTER

Page 65: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 64

EDIT STORED TEST

MAIN SCREENS

8

ENTER

EDIT STORED RECORDSX RECORDS STOREDENTER RECORD # TOEDIT: X (P TO PRT)

Any stored tests may be viewed and edited from this menu. All meter information except the test results and the test date and time may be edited and/or viewed prior to uploading to the polling PC. These screens are customized per your WATT-Net™ record.

Page 66: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 65

MANUAL TEST ENTRY

MAIN SCREENS

9

Manual entry allows WATT-Net™ record entry of all meter data including test accuracy’s into the test kit. This menu selection allows tests from, for example, a manual field test kit to be stored in the PAT and can later be uploaded to the polling PC.

Page 67: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 66

KWH TESTING

MAIN SCREENS

AS FOUND

ENERGIZED FOR TESTVOLT

PHASE

ENTER AUTO SEQUENCE#: _0_ (1-9)

ENTER 0 TO EXIT

AS LEFTFL . .LL . .

ENTER1

TEST IN PROGRESS

PHASEVOLT

ENERGIZE FOR TEST

AMP AMP

1

"TEST MODE SET TO KWH"

PF . .

AUTOSEQUENCE STARTADJUST

OPTICS

REV REV

AS FOUNDFL 100.03 100.03

AS LEFT

LLPF

CANCEL

ADJUSTING OPTICS

PHASE: 0VOLT: 240

ENTER AUTO SEQUENCE#: __1 (1-9)

ENTER 0 TO EXIT

AMPS: 30REV: 0

ENTER AUTO SEQUENCE#: _1_ (1-9)

ENTER 0 TO EXIT

ENTERSTART AUTOSEQUENCE

PHASE: 0VOLT: 240 AMPS: 30

REV: 0 START

TEST IN PROGRESS

PHASE: 0VOLT: 240 AMPS: 30

REV: 0

AS FOUND AS LEFTFL 100.01 100.01LL . .PF . . HELP

2 SHOW STD COUNT3 CLEAR MEMORY

2 3

EXPECTED XXXXXXACTUAL XXXXXXACCURACY .001PRESS ENTER TO EXIT

ENTER

CLEAR TEST RESULTS

1=YES2=NO

DO YOU WANT TO ENTERMETER SETUP DATA

1=YES2=NO

1

2

"CUSTOMIZE RECORD"

1 2

AS FOUND AS LEFTFL . .LL . .PF . .

ENTER

MENUTEST

MENUTEST

CANCEL

CANCEL

CANCEL

SAVETEST

ENTER

HELP

HELP

SAVE TEST*

** **

*Shows on Initial Test of Meter ONLY **If the Creep Test LED is selected, the start key will energize the meter with potential only. From that point an individual test can be performed by selecting the appropriate test desired or an Auto Sequence may be started. When the test(s) are finished the Creep (Voltage) will Remain on the Meter.

Page 68: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

Rev 1.3 67

DEMAND TESTING

MAIN SCREENS

DEMAND TEST

DEMAND TEST POTMULT: 10

DEMAND RUN KYZKW .00001DI

MULT: 1Mp: ___

Mp:AMPS: 30

EXP ___

"TEST MODE SET TO DEMAND"

MENUTEST

TIME: : : _____

STARTADJUSTOPTICS

TIME: : : _____

ACT ___REVS

CANCEL

TEST COMPLETE KYZKW 7.1903

PRESS CANCEL POT*

CANCEL

AMPS: 30REVS

EXPACT 0DI .0865

"APPLIES POTENTIAL ONLY"

REVS30

30

START CANCEL

DEMAND HELPADJUST OPTICS FOR

POTENTIAL ONLY

HELP

ENTER

*Shows either Potential, Current or Both to indicate what is still applied to the

meter at the end of the test.

Page 69: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

BLANK PAGE

Page 70: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

69

APPENDIX

7.0

Page 71: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

70

BLANK PAGE

Page 72: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

71

7.1 GLOSSARY OF COMMON TERMS Accuracy- The extent to which a given measurement agrees with the defined value. Ampere- The practical unit of electric current. One ampere is the current caused to flow through a resistance of 1 ohm by 1 volt. Calibration- Comparison of the indication of the instrument under test, or registration of meter under test, with an appropriate standard. Class Designation- The maximum of the watt-hour meter load range in amperes. Constant, KYZ Output (Ke)- Pulse constant for the KYZ outputs of a solid state meter, programmable in unit-hours per pulse. Constant, Watt-hour-(A) For an electromechanical meter (Kh): The number of watt-hours represented by one revolution of the disk. Determined by the design of the meter and not normally changed. Also called Disk Constant. ( B ) For solid state meters ( Kh or Ke ) : The number of watt-hours represented by one increment ( pulse period ) of serial data. Example: Kh or Ke = 1.8 watt-hours/pulse. Creep- For mechanical meters, a continuous motion of the rotor of the meter with normal operating voltage applied and the load terminals open-circuited. For electronic meters, a continuous accumulation of data in a consumption register when no power is being consumed. Demand- The average value of power or related quantity over a specified interval of time. Demand is expressed in kilowatts, kilovolt-amperes, kilovars, or other suitable units. An interval may be 1, 5, 10, 15, 30, or 60 minutes. Energy- The integral of active power with respect to time. Kilo- A prefix meaning one thousand of a specified unit. ( Kilovolt, Kilowatt ) . 1000 watts = 1 Kilowatt. KVA-The common abbreviation for kilovolt-ampere ( equal to 1000 volt-amperes ). KYZ Output- A three-wire pulse output from a metering device to drive external control or recording equipment. Each pulse or transition represents a predetermined increment of power or other quantity. Load Factor- The ratio of average load over a designated time period to the maximum demand occurring in that period. Optical Probe- An interface device which mates with the optical port of the meter, to read data or to program the meter. Phase Angle- The phase angle or phase difference between a sinusoidal voltage and a sinusoidal current is defined as the number of electrical degrees between the beginning of one cycle of voltage and the beginning of the cycle of current. Pulse Initiator- Any device, mechanical or electrical, used with a meter to initiate pulses, the number of which are proportional to the quantity being measured. It may include an external amplifier or auxiliary relay or both.

Page 73: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

72

Q-Hour Meter- An electricity meter that measures the quantity obtained by lagging the applied voltage to a watt-hour meter by 60 degrees, or for electronic meters by delaying the digitized voltage samples by a time equivalent to 60 electrical degrees. Var- The term commonly used for volt-amperes reactive. Varhour Meter-An electricity meter that measures and registers the integral, with respect to time, of the reactive power of the circuit in which it is connected. The unit in which this integral is usually measured the kilovarhour. Watt- The practical unit of active power which is defined as the rate at which energy is delivered to a circuit. It is the power expended when a current of one ampere flows through a resistance of one ohm. Watt-hour- The practical unit of electric energy which is expended in one hour when the average power during the hour is one watt. Watt-hour Meter- An electricity meter that measures and registers the integral, with respect to time, of the active power of the circuit in which it is connected. The power integral is the energy delivered to the circuit during the interval over which the integration extends, and the unit in which it is measured is usually the kilowatt-hour.

Page 74: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

73

7.2 MODEL 3010 OPTIONS 1 BARCODE READER The optional barcode reader package comes with a COMPSEE 5312 laser scanner. The scanner is a low output type ( less than 1 mW ) approved for commercial use. The Barcode Reader can decode the various meter forms based on the modified AEP barcode standard or customer provided barcode labels. Scan distance is 2 to 6 inches from the barcode label. After pulling the trigger a successful scan will be indicated by a tone, and by two LEDs on the end of the gun labeled “SCAN” and “ DECODE”. Proper handling should be followed when using this equipment. 2 OPTIONAL STANDARDS The Model 3010 may be fitted with different standards to better the customers needs. The Model 3010 normally comes with RM-10-02 WATT standard installed. The following test standards are available with the Model 3010 test kit. RM-10 or RM-11 –02/01............................................WATT -08/06 ............................................WATT VAR -09/07 ............................................WATT VAR Q

Page 75: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

74

7.3 PREVENTATIVE MAINTENANCE OVERVIEW In an effort to properly maintain and extend the life of our test equipment, routine maintenance is recommended. Although environmental conditions may dictate more frequent attention to some of these items, under normal conditions these recommendations should be adequate. It is the desire of Watthour Engineering Co., Inc. to provide quality equipment that when properly maintained will assure long and dependable service. 9.1 DAILY / WEEKLY CHECKS

• Check cooling fan for operation. • Check to ensure that the unit is keep free of dirt or moisture.

9.2 QUARTERLY CHECKS

• Perform standards compare as instructed in the operating manual with the standards compare adapter provided. • Check all current connections including the mercury relays. • Check all circuit boards to ensure that they are secure and tighten if necessary. • Using compressed air, clean all dust and debris from the unit. • Visually inspect the unit for any other loose screws or connections.

Page 76: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N

WATTHOUR ENGINEERING CO., INC.

75

METER HOOKUP DIAGRAMS

8.0

Page 77: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 78: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 79: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 80: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 81: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 82: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 83: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 84: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 85: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 86: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 87: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 88: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 89: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 90: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 91: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 92: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 93: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 94: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 95: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 96: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 97: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 98: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 99: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 100: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 101: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 102: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 103: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 104: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 105: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N
Page 106: MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. … · MODEL 3010 PORTABLE AUTOMATED TEST KIT P.A.T. OPERATIONS MANUAL REV 1.3 . WATTHOUR ENGINEERING CO., INC. Rev 1.3 1 W A R N I N