Fire Resistance Design for WoodFire-Resistance Design for Wood Construction - BCD 220-1James B. Smith, P.E.Midwest Regional ManagerAmerican Wood Council
Copyright
This presentation is protected by US and International Copyright laws. Reproduction,
distribution, display and use of the presentation without written permission of
AWC is prohibitedAWC is prohibited.
© American Wood Council 2016
2
DescriptionDetermining the proper code application for wood-framefi bli b h ll i d i ft f thfire assemblies can be challenging and is often furthercomplicated with increases in a project’s size and scale.In a building environment where the ability to maximizeheight and area is key to cost effectiveness, designersmust understand the gamut of fire protectiong pconsiderations applicable to mid- and low-rise woodstructures. This presentation will include coderequirements, compliance options and nuances relatedto assembly selection for required fire-resistance-ratedfloor/ceiling assemblies exterior walls fire barriers firefloor/ceiling assemblies, exterior walls, fire barriers, firepartitions, and fire walls. Topics will include distinctionsbetween fire-resistive elements for separation vs. classof construction. 3
Learning Objectives
1. Apply code requirements and intent for wood-f fi i d bliframe fire-resistance rated assemblies.
2. Discuss the differences in exterior walls, fire walls, fire barriers, and fire partitions considering performance expectations, code requirements and appropriate applicationrequirements, and appropriate application.
3. Understand the paths to achieving code-compliant, fire-resistance rated wood-frame assemblies as outlined by the 2015 IBC.
4. Recognize important nuances in the various methods for demonstrating fire-resistance including: tested assemblies, prescriptive designs, calculations, and engineering analysis. 4
Outline
• Code Overview• Code Overview• Background• Fire-resistance
building elementsbuilding elements• Achieving Fire-
Resistance
5
International Building Code
The IBC• Controls building size• Regulates types of
materialsmaterials• Stipulates fire-
resistance
6
International Building Code
Allowable heights & areas determined by
• Tabular values• Factors allowing• Factors allowing
increases• Frontage• Sprinkler Systems
Special Provisions IBC• Special Provisions IBC 510
7
Allowable Heights & AreasAllowable area is based uponupon
• Use of building• Type of construction• Frontage• Existence of sprinkler
systemsTabular areas establishminimum allowable building areas that can be increased byareas that can be increased by added fire safety features -frontage and/or frontage.
8
Allowable Heights & Areas
Each occupancy groupEach occupancy group presents a different level of fire and life safety risk:
N b f t• Number of occupants• Capability of occupants• Fuel load
9
Allowable Heights & AreasAllowable heights and areas are based on a concept of equivalent risk, involving three p q , ginterdependent considerations
• level of fire hazard likely to be associated with the occupancy
• nature of contents associated with the use• nature of contents associated with the use• level of overall fire protection provided by the
• Type of construction• Setbacks of the building from other structures
(exposure)• Sprinklers and life safety systems• Other code trade-offs 10
Table 601 Fire-Resistance Rating Requirements For Building Elements (hours)
Building Elements
Building Elements (hours)
BUILDING ELEMENTTYPE I TYPE II TYPE III
TYPE
IVTYPE V
A B Ad B Ad B HT Ad B
Primary structural frameg
( )(see Section 202)
3a 2a 1 0 1 0 HT 1 0
Bearing walls, Exteriorf, g
Interior 3
3a2
2a1
1
0
0
2
1
2
0
2
1/HT
1
1
0
0
11
Nonbearing walls and
partitions, ExteriorSee Table 602
Nonbearing walls and
partitions, Interiore
0 0 0 0 0 0See
Section 0 0
Exterior Walls
12
• Define separate buildings for allowable building size (706)
Fire Walls (706)
size (706)• Not fire barriers (707)• Not fire partitions (708)• Not smoke barriers, smoke partitions or horizontal
assembliesassemblies• Table 706.4 gives required ratings based on occupancy
13
• Type V construction
Fire Walls (706.3)
• Fire walls may be wood frame
• Types I, II, III and IV construction• Fire walls must be of noncombustible materials
in accordance with Section 706.3
14
• A fire-resistance-rated wall assembly of materials
Fire Barrier (707)
designed to restrict the spread of fire in which continuity is maintained
• Of materials permitted by the building type of construction
• Fire-resistance rating 707.3 - specific ratings as indicated for shaft enclosures, interior exit stairways and ramp, enclosed exit access stairways, exit passageway, horizontal exit, atriums, incidental uses, control areas, separated occupancies fire areasseparated occupancies, fire areas
15
Fire-resistance rating for separation of fire
Fire Barrier (707)
areas per table 707.3.10
16
Separation of Occupancies
17
• A vertical assembly of materials designed to restrict the spread of fire in which openings are
Fire Partition (708)
restrict the spread of fire in which openings are protected.
• Wall assemblies for:• Separation walls for Group I-1, R-1, R-2 and R-3 per section
420 2420.2• Walls separating tenant spaces in covered and open mall
buildings per section 402.4.2.1• Corridor walls per section 1020.1
El t l bb ti ti 3006 2• Elevator lobby separation per section 3006.2• Egress balconies per section 1019.2
18
• A vertical assembly of materials designed to restrict the spread of fire in which openings are
Fire Partition (708)
restrict the spread of fire in which openings are protected. cont.
• Of materials permitted by the building type of construction
• Fire-resistance rating 708.3 not less than 1 hour.
• See exceptions for corridor walls, dwelling unit separations, and sleeping unit separations
19
• A continuous membrane, either vertical or
Smoke Barriers (709)
horizontal, such as a wall, floor or ceiling assembly, that is designed and constructed to restrict the movement of smoke.
• Vertical and horizontal smoke barrierse t ca a d o o ta s o e ba e s• Of materials permitted by the building type of
construction• 1 hour fire-resistance rating Exception: Smoke barriers
constructed of minimum 0.10- inch-thick (2.5 mm) steel in b ld ( )Group I-3 buildings. (709.3)
20
• A fire-resistance-rated floor or roof assembly of
Horizontal Assemblies (711)
materials designed to restrict the spread of fire in which continuity is maintained.
• Of materials permitted by the building type of construction
• Fire-resistance rating - specific ratings as indicated 711.2.4 but not less than that for building type of construction : separating mixed occupancies, fire areas, dwelling units and sleeping units,
k t t i id t l th tismoke compartments, incidental uses, other separations.
21
Outline
• Code Overview• Code Overview• Background• Fire-resistance
building elementsbuilding elements• Achieving Fire-
Resistance
22
1 Tested fire assembly (ASTM E 119 or UL 263)
Methods for Determining Fire-Resistance (703)
1. Tested fire assembly (ASTM E 119 or UL 263)2. Fire-resistance designs documented in approved
sources 3. Prescriptive assemblies using of fire-resistance-rated
designs in Section 721designs in Section 7214. Calculation of fire-resistance per Section 7225. Engineering analysis based on a comparison of
building element, component or assembly designs that have been tested
6. Alternative protection methods per Section 104.117. Fire-resistance designs certified by an approved
agency23
Fire TestsTested fire assembly (ASTM E 119)
http://www.awc.org/Code-Officials/2012-IBC-Challenges/# 24
Fire TestAmerican Wood CouncilASTM E119 Fire Endurance Half-lapped –Test• 5-Ply CLT (approx. 7” thick)• 5/8” Type X GWB each side• Sought 2 hour rating• RESULTS: 3 hours 6 minutes
ppmiddle of panel
25
• Based on testing to the ASTM E 119 or UL 263 d d
Documented in Approved Source
standard• Choose listed assemblies from fire-resistance
publications or directories
26
Documented in Approved SourceFire-resistance designs - AWC Design for Code Acceptance Pubs -Acceptance Pubs
27
Documented in Approved Source
DCA 3DCA 3Fire-Resistive Wood Wall and Floor/Ceiling Assemblies• ASTM E 119 or UL 263• NFPA 251
28
Documented in Approved Source
29
Documented in Approved Source
30
Documented in Approved Source
31
Fire-resistance of certain wood assemblies is prescribed in Section 721 based on testing using ASTM E 119 or UL 263
Prescriptive Fire-Resistance Rated Assemblies
32
Prescriptive Fire-Resistance-Rated Assemblies
Fire-resistance of certain wood assemblies is ib d i S ti 721 b d t ti iprescribed in Section 721 based on testing using
ASTM E 119 or UL 263
• Fire-resistance of wood frame assemblies
Calculated Resistance (703.3)
also may be calculated based on the known fire-resistance of the components, using the provisions of Section 722.6
• 1.0 hour maximum0 ou a u
34
Calculated Fire Resistance (722.6)
DCA 4DCA 4 Component Additive Method (CAM) for Calculating and Demonstrating AssemblyDemonstrating Assembly Fire Endurance
35
CAM
Calculated Fire Resistance (722.6)
Membrane Table
Time AssignedTime Assigned to Protective Membranes
•IBC Table 722 6 2(1)722.6.2(1)
36
CAM Wood Component Table
Calculated Fire Resistance (722.6)
CAM Wood Component TableAssigned Times for Wood ComponentsIBC Table 722.6.2(2)
37
CAM Wall Membranes
Calculated Fire Resistance (722.6)
Membranes on Exterior Face of WallsIBC Table 722.6.2(3)
38
CAM Cavity Insulation Table
Calculated Fire Resistance (722.6)
yAssigned Times for Insulation of Cavity
•IBC Table 722.6.2(5)
39
Interior Wall
CAM Example 1
Interior Wall
40
Floor/Ceiling with Wood Joists
CAM Example 2
41
Floor/Ceiling with I-joists
CAM Example 3
/ g j
42
Columns within Wall Assembly
IBC 704.2 and 704.3 No addition
43
al fireproofing required for the co
lumnin the assembly
• 704.2 Column protection (IBC 2018 text)
Columns within Wall Assembly
• “Exception: Columns that meet the limitations of Section 704.4.1”
• 704.4.1 Light-frame construction (IBC 2018 text)• “Studs columns and boundary elements that• Studs, columns, and boundary elements that
are integral elements in walls of light-frame construction, and are located entirely between the top and bottom plates or tracks shall be permitted to have required fire-resistance ratings provided by the membrane protection provided for the wall.”
44
Structural Stability 705.6
2 hour wall
1 hour floor
2 hour wall
45
Calculated Fire-Resistance
Fire-resistance up to two hours
• Columns
• Beams
• Tension Members…
e s o e be s
• ASD only
Products
• Lumber
Gl l
46
• Glulam
• SCL
• Decking
• CLT
Fire Design of Exposed Wood Members
Beam Fire Test ASTM E 119
47
Calculated Fire-Resistance (722)
Chapter 16 of the National Design Specification® (NDS®)
48
Effective char rate
Fire Design of Exposed Wood Members
lid l l d l i d f d l i dsolid sawn, structural glued laminated softwood, laminated veneer lumber, parallel strand lumber, and laminated strand lumber
49
Effective char depth
Fire Design of Exposed Wood Members
C16.2.1.2 Using Equation 16.2-1 and assuming nominal char rate, n or 1.5 inches/hr:
50
Fire Design of Exposed Wood Members
51
CLT manufactured with laminations of equal thickness
Fire Design of Exposed Wood Members
CLT manufactured with laminations of equal thickness
52
Technical Report No. 10 (TR10)
Calculated Resistance (722)
(TR10)• contains background and
examples for the method
53
TR-10 Design Example
TR10 containsTR10 contains:• decking• beam
l• column• CLT• etc
54
Fire-Resistance of Exposed Wood
16 3 Wood Connections16.3 Wood Connections• Where fire endurance is required,
connectors and fasteners shall be protected from fire exposure
• Wood• Fire-rated gypsum board
55
Connections
Beam-to-column(Protection provide(Protection provided by membrane)
Source: AWC TR-10 56
Connections
Concealed
Source: AWC TR-10
Concealedbeam-to-column
57
Connections
Source: AWC TR-10
Beam supporting one hour rated ceiling58
Connections
Covered column connection
Source: AWC TR-10 59
Connections
Concealed beam-to-
girder connection
Source: AWC TR-10 60
Fire Design of Exposed Wood Members
722.6.3 deleted
Limited to 1-Hour – IBC 722.6.1.1Si lifi d h
722.6.3 deleted NOT INCLUDED IN 2015 IBC
61
Simplified approachOnly Beams/Columns
Fire Design of Exposed Wood Members
DCA 2Design of Fire-Resistive Exposed Wood Members• Glued-laminated
timber, sawn lumber, & timber decking
• 1 1 5 & 2 hours• 1, 1.5 & 2 hours
62
May be used in almost all occupancies.
Wood Interior Finish (Chapter 8)
63
Wood Interior Finish Classification System
Nonsprinklered Buildings: Minimum Interior FinishNonsprinklered Buildings: Minimum Interior Finish Classification by Occupancy
Location Minimum Interior Finish Classification
Ab B CAb B C
Exit enclosures and exit
passagewaysc
A, B, E, I, M, R-1, R-4
F, S, R-2 R-3
64
Corridors Ad, I-2, I-3,
I-4
B, E, M, S,I-1, R-1, R-2, R-4
F, R-3
(Table 803.11)
Wood Interior Finish Classification System
Sprinklered Buildings: Minimum Interior FinishSprinklered Buildings: Minimum Interior Finish Classification by Occupancya, b
Location Minimum Interior Finish Classification
A B CA Bc C
Exit enclosures and exit
passagewaysd
I-3 A, B, E, M, R-1,R-4, I-1, I-2, I-4
F, R-2, R-3, S
65
Corridors I-3 A, I-2, I-4B, E, F, M,R, S, I-1
A
(Table 803.11)
Wood Interior Finish (803)• Most wood species
lif Cl Cqualify as Class C or Class B.
• Wood boards and panels may meet Class A criteria whenA criteria when pressure treated with a fire-retardant chemical.
• AWC’s DCA-1
66
• AWC s DCA-1 documents the performance.
Flame Spread
Class I or A 0 ‐ 25
Class II or B 26 ‐ 75
fire retardant treated wood
redwoodcedard l f
pine (other than lodge pole, ponderosa & red)
most other wood speciessoftwood plywood
Class III or C 76 ‐ 200
douglas‐firhem‐fir
spruce
softwood plywoodhardwood plywoodparticleboard
67
Flame Spread
E84 T l• E84 Tunnel Apparatus
68
Smoke Developed Index
A smoke-developed pindex was also measured for some of the wood products listed in DCA 1. None of the products testedof the products tested exceeded the limiting value of 450 commonly used in building code regulationsregulations.
69
Wood Interior Finish – Exceptions
• Traditional wood floor covering is exempt from interior floor finish requirements (804.1).
• Exposed portions of Type IV structural members also
70
members also exempt (803.3).
Design for Code Acceptance Pubs.
71
Available for free download www.awc.org
• Special occupancies
2015 Code Conforming Wood Design
• Fire-resistance• Building features• Wood in noncombustible
construction types• Structural considerations• Precautions during
construction• Also available for 2009 and
2012 IBC2012 IBC• http://awc.org/codes-
standards/buildingcodes/ccwd 72