ABB Network Partner Operator’s Manual REF 54_ Protection, Monitoring and Control

description

asdaS

Transcript of MMI_maen

  • ABB Network Partner

    Operators Manual REF 54_Protection, Monitoring

    and Control

  • StationAutomation

    1 MRS750500-MUM EN

    Issued 23.12.1997Version CChecked S.H.Approved T.K.

    Data subject to change without notice

    REF 54_Operators Manual

    1 Safety Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 REF 54_ Protection Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Graphical MMI/MIMIC Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    3.1 A Display idle mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53.1.1 Display backlight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53.1.2 Display contrast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63.1.3 Selecting language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63.1.4 Main window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.1.5 Assisting window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.1.6 Display test at power up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    3.2 Button introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83.3 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    3.3.1 Object control in the MIMIC view . . . . . . . . . . . . . . . . . . . . . . . 113.4 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    4 MMI Operation Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124.1 User level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    4.1.1 MIMIC view (Configuration picture) . . . . . . . . . . . . . . . . . . . . . . 134.1.2 Measurement view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134.1.3 Operation events (EVENT view) . . . . . . . . . . . . . . . . . . . . . . . . 134.1.4 Control alarms (ALARM view) . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    4.2 Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144.3 Technical level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    4.3.1 Menu system of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 164.3.2 Special situations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174.3.3 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174.3.4 Parameter menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174.3.5 Moving in the menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    4.4 Setting a parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184.5 Saving parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194.6 Acknowledgement and resetting of indicators, outputs and registers 19

    5 Protection Relay Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205.1 Priority of indication and help messages . . . . . . . . . . . . . . . . . . . . . 20

    5.1.1 Help messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205.1.2 Indication messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    5.2 Protection indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215.3 Self supervision (IRF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215.4 Supervision indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225.5 Test modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    5.5.1 Function test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235.5.2 Control test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235.5.3 MIMIC test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235.5.4 I/O test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    5.6 Green indicator LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235.7 Yellow indicator LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245.8 Red indicator LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245.9 Interlocking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

  • Page 3

    1MRS750500-MUM Operators Manual REF 54_

    1. Safety In-structions

    Dangerous voltages can occur on the connectors, even though the auxiliary volt-age is disconnected.

    National and local electrical safety regulations must always be followed.

    The frame of the protection relay has to be carefully earthed.

    Only a competent electrician is allowed to carry out the electrical installation.

    !

    !!

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 4

    2. REF 54_ Pro-tection Relay

    The REF 54_ type protection relay is designed to be used for the protection, control, meas-uring and supervision of medium voltage networks. It can be used with any type of switch-gear including single busbar, double busbar and duplex systems. The protection relayincludes energizing inputs for conventional current and voltage transformers and currentand voltage sensors.

    The REF 54_ protection relay is based on a multiprocessor environment that increases per-formance. Digital signal processing combined with a powerful CPU and distributed I/O han-dling facilitates parallel operations and improves response times and accuracy. The MMIincluding an LCD display with different views makes the local use of the REF 54_ safe andeasy. The MMI instructs the user how to proceed.

    The REF 54_ protection relay is part of the PYRAMID substation automation for Distri-bution Automation and extends the functionality and flexibility of the concept further. Thisis possible due to the state-of-the-art technology used in PYRAMID.

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 5

    3. Graphical MMI/MIMIC Features

    The front panel of the protection relay includes:

    a graphical LCD display, with the resolution 128 x 160 pixels, consisting of 19 rows dividedinto two windows

    a main window (17 rows) providing detailed information on MIMIC, objects, events, meas-urements, control alarms, and parameters of the protection relay

    an assisting window (2 rows) for protection, relay-dependent indications/alarms and helpmessages

    three push-buttons for object control eight freely programmable alarm LEDs with different colours according to the configuration

    (off, green, yellow, red) indication LED for control interlocking and test mode three protection indication LEDs an MMI push-button section with four arrow buttons and buttons for Clear and Enter an optically isolated serial communication port backlight and contrast control freely programmable button (F) a button for remote/local control (Control position button)

    Fig. 3.-1. Front view of the protection relay

    3.1. A Display idle mode

    In idle mode the MIMIC configuration picture is shown in the main window.

    3.1.1. Display backlight

    The backlight of the display is normally off. When a button on the MMI is pressed, the back-light automatically turns on. After the preset time-out (backlight time), the backlight goesout if there has been no activity on the panel. At power up, the backlight turns on for thedisplay test and then goes out again (delayed by time-out).

    R

    REF 541

    Uaux = 80...265 Vdc/acfn = 50 HzIn = 1/5 A (I)

    1MRS xxxxxx98150Un = 100/110 V (U)

    Uon = 100/110 V (Uo)

    Ion = 1/5 A (Io)

    9509

    C

    E

    R

    L

    A B B N e t w o r k P a r t n e r

    F

    I

    0

    RL

    21 kV

    CB OK

    Protection indication LEDs:Left: Ready, IRF, Test modeCenter: Start, BlockRight: Trip, CBFP

    AROFF

    Programmable LEDs

    GraphicalLCD display

    Object Control push-buttons:Select,Open,Close

    Control position button

    Optical PCconnector

    MMI push-button section

    Freely programmablebutton

    Control test &Interlocking LED

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 6

    The backlight can also be switched on via a digital input of the REF 54_. When the digitalinput has been activated, the backlight is lit. For this kind of function, the MMIWAKE func-tion must be included in the relay configuration.

    3.1.2. Display contrast

    To obtain optimum readability the contrast can be adjusted in the MIMIC view on the userlevel and in the Main Menu on the technical level.

    Press the E button and the arrow button UP to increase contrasts or the arrow buttonDOWN to decrease contrasts.

    Fig. 3.1.2-1. Adjusting display contrast

    The contrast tuning value selected is stored in a non-volatile memory and thus after powercycling of the protection relay, the contrast is automatically adjusted according to set value.

    3.1.3 Selecting language

    Fig. 3.1.3-1.Selection of language

    Press the E button for 2 seconds and enter the password, if required, to access the technicallevel. Select Configuration in the Main Menu (last item) and Languages in the Group Menu(first item). Move the cursor to the desired language and confirm the selection by pressingthe E button. After that the cursor automatically returns to the main menu.

    Push

    increase

    decrease

    E AND

    PARAMETER MENUGROUP MENUMAIN MENU

    Cancel

    Conf irm

    E

    C

    LANGUAGESEngl ish

    Suomi

    CONFIGURATIONLanguages

    MAIN MENUStatusProtection lib.Control lib.Cond. Monit. libMeasurements lib.Communic. libStandard lib.TestsInformationConf igurat ion

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 7

    3.1.4 Main win-dow

    The main window informs the user via different views and menus, for example:

    MIMIC configuration, CB status, disconnector status, etc. events measurements alarms parameter settings

    Fig. 3.1.4-1. Display

    In idle mode, the MIMIC picture shows the status of the CB(s) and the disconnectors.

    3.1.5 Assisting window

    The assisting window assists the user. It indicates two kinds of messages with detailed dataof the protection relay itself, protection functions, etc.:

    1. user help messages during operation2. indication messages

    The assisting window is always visible, totally independent of the main window.

    3.1.6 Display test at power up

    When auxiliary voltage is connected to the protection relay, the backlight goes on and ashort display test is run. This display test includes the LEDs and the display:

    First the nine alarm LEDs are activated simultaneously with different colours (red --> green --> yellow - OFF). At the same time the three protection indication LEDs and the remote/local/disabled/logic LEDs are activated simultaneously for a short time (3 cycles for the indicationLEDs).

    The LCD display is tested by inverting the display for a short time.

    After the display test, the display panel turns to the normal state (a default MIMIC view) andthe backlight turns off after the preset time-out. The test can be stopped at any time by press-ing a key.

    R

    L

    F

    I

    0

    RL

    21 kV

    CB OK

    AROFF

    Assistingwindow2 rows

    Main window17 rowsGraphical

    LCD display

    Main windowDetailed information on:

    - objects- events- measurements- alarms- parameters

    Assisting windowInformation on:

    - indicators- help messages

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 8

    3.2. Button intro-duction

    The MMI includes push-buttons for manipulating the protection relay.

    A quick touch on the up or down arrow button (less than 1 second) is interpreted as one stepupwards or downwards in a menu and as the minimum step up or down in the setting modeof parameter (digit, character, enumerator etc.).

    If the cursor is on the topmost row, pressing the up button moves the cursor to the last row. If the cursor is on the last row, pressing the down button moves the cursor to the topmost row

    of the view.

    Fig. 3.2.-1. Buttons to be used for navigation

    The table below gives a short explanation of the push-buttons and their functions.

    Up/Down These buttons are used for:

    moving the cursor either up or down in order to select the desired item of a menu (Main, Group, Subgroup or Parameter).

    entering the setting mode of a parameter, or when entering a parameter/password the "active" digit/character is scrolled.

    Left/Right These buttons are used for:

    moving between views (left/right) and to select the appropriate hierarchy level (Main, Group, Subgroup or Parameter).

    moving from right to left or vice versa when setting a parameter.

    Clear/Cancel On the user level this button is used for:

    clearing any active indication message. clearing events or alarms according to the

    selected view.

    On the technical level the button is used for:

    cancelling the setting mode. clearing all kinds of indication messages.

    Note! If there is an indication message in the assisting window, pressing of the C button for at least two seconds clears the window.

    C

    E

    Navigation push-buttons

    left right

    down

    clear/cancel

    Clear and Enter buttons

    enter/return

    up

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 9

    3.3. Control but-tons

    The control position button is used for selecting a control mode according to the followingtable. For password handling, see Passwords on page 14.

    When the control mode is changed with the control position button, the selected control po-sition is stored and the text --Storing-- is shown on the display. See also Saving param-eters on page 19.

    Enter On the user level this button is used for:

    entering the MAIN MENU on the technical level from the MIMIC view on the user level. This is done by pressing the E button for at least 2 seconds and by entering the password if required.

    On the technical level this button is used for:

    entering the MIMIC view on user level from the MAIN MENU on the technical level, by pressing the button for 2 seconds.

    activating parameter setting in the parameter group.

    Table 3.2.-1 Push button functions

    LOCAL To be able to control an object with the push-but-tons OPEN and CLOSE, the control position has to be LOCAL indicated by the yellow LED marked L. In this position, any remote control signal via the serial interface is inhibited. Binary inputs and logic controls are valid.

    REMOTE To be able to select and control an object remotely via the serial communication, the REMOTE mode has to be selected. REMOTE mode is indicated by a yellow LED R. All local push-buttons are inhibited. Binary inputs and logic controls are valid.

    DISABLED Local and remote operations are inhibited.

    Binary controls are valid.

    DISABLED mode is indicated with all LEDs being dark.

    DISABLED (LOGIC) mode

    DISABLED (LOGIC) mode is enabled.

    Binary inputs and PLC logic are used to select between LOCAL, REMOTE and DISABLED modes (Binary controls are valid.)

    LOGIC mode is indicated with the unmarked LED being lit.

    R

    L

    RL

    R

    L

    RL

    R

    L

    RL

    R

    L

    RL

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 10

    Protection relay configuration has to contain the Control position function ele-ment (COLOCAT) to allow LOGIC position to be selected with the control posi-tion button.

    Fig. 3.3.-1. Control position selection sequence, when logic position is selectable (COLOCAT function used in configuration).

    Fig. 3.3.-2. Control position selection sequence, when logic position is not selectable(COLOCAT function not used in configuration).

    LOCAL (LOGIC) mode

    LOCAL mode is enabled

    REMOTE mode is disabled

    REMOTE (LOGIC ) mode

    REMOTE mode is enabled

    LOCAL mode is disabled

    Table 3.3.-1 Control buttons

    R

    L

    RL

    R

    L

    RL

    !

    RL

    RL

    RL

    RL

    Local LogicDisabledRemote

    RL

    RL

    Local DisabledRemote

    RL

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 11

    3.3.1. Object con-trol in the MIMIC view

    Push the SELECT button to step through the available objects until the desired controllableobject is inverted. The object remains inverse until a control command is given or the time-out has elapsed. The time-out can be adjusted. The status of corresponding object during theinterlocking sequence is shown in the assisting window.

    The close and open commands are given with the O (OPEN) and I (CLOSE) push-buttons.Depending on the status of the interlocking function, the command is either executed or theInterlocking LED is lit if the commmand is not allowed.

    The length of the control pulses can be adjusted.

    3.4. Program-ming

    The front panel of the protection relay is provided with an optical serial communication con-nector for connecting a PC via a special RS 232 optolink cable, type 1MKC950001-1, to therelay. Additionally, a special PC program is needed for communication between the PC andthe protection relay.

    Select Push the push-button to step through the availa-ble objects until the desired object is highlighted.

    Close Push the push-button to close the object selected if it is open.

    Open Push the push-button to open the object selected if it is closed.

    Freely pro-grammable

    This button can be programmed for different purposes.

    Table 3.3.1.-1 Object control

    I

    O

    F

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 12

    4. MMI opera-tion levels

    The MMI/MIMIC has two main levels: the user level and the technical level. The user levelis for measurements and monitoring whereas the technical level is used for protection relayprogramming and parameterization.

    Fig. 4.-1. Menu level structure.

    4.1. User level On the user level, data is received in four different views:1. MIMIC view2. MEASUREMENT view3. EVENT view4. ALARM view

    21 kV

    CB OK

    AROFF

    StatusDisturb. record.Protection lib.Control lib.Cond. Monit. libMeasurements lib.Communic. libStandard lib.TestsInformationConfiguration

    SETTING GROUP 1

    M EASUREMENT

    EVENT view ALARM view

    USER LEVEL (LEVEL 1)

    TECHNICAL LEVEL (LEVEL 2)

    MIMIC view MEASUREMENT view

    EVENTS

    Note!Password 3can be used, i fwanted, whenenter ing theMain Menu

    I L 1 - A 8 0 0I L 2 - A 8 0 3I L 3 - A 8 0 0I 0 0I 0 b 0U 1 2 k V 2 0U 2 3 k V 2 0U 3 1 k V 2 0U 1 k V 1 1 . 5U 2 k V 1 1 . 5U 3 k V 1 1 . 5U 0 - V o l t s 0k W L 1 7 3 6 0k W L 2 7 3 6 0

    N O C 3 L o w : S t a r t9 5 - 1 2 - 2 41 8 : 3 5 : 1 2 ; 2 3 0

    N O C 3 L o w : S t a r t R E S9 5 - 1 2 - 2 41 8 : 3 5 : 1 2 ; 3 3 0

    N O C 3 H i g h : S t a r t9 5 - 1 2 - 2 41 4 : 2 5 : 5 2 ; 7 2 0

    N O C 3 H i g h : T r i p9 5 - 1 2 - 2 41 4 : 2 5 : 5 2 ; 7 6 0

    E v e n t l i s tM E A S A L A R M

    CB spring ready

    SF6 gas density

    Temperature

    Inter locking

    PARAMETER MENU

    GROUP MENUMAIN MENU

    MAIN MENU

    2 Sec 1 Sec

    PROTECTION

    NOC3Low

    SUBGROUP MENU

    O p e r a t i o n m o d e= D e f i n i t e t i m eS t a r t c u r r e n t= 3 . 1 x I nO p e r a t i o n t i m e= 0 4 1 . 0 3 sT i m e m u l t i p l i e r= 0 . 7 8

    C c l e a r s A l a r m sE V E N T M I M I C

    U p d a t i n g v a l u e s M I M I C E V E N T

    A c t u a l s e t t i n g sS e t t i n g g r o u p 1S e t t i n g g r o u p 2C o n t r o l s e t t i n g sI n p u t d a t aO u t p u t d a t aR e c o r d e d d a t a 1R e c o r d e d d a t a 2R e c o r d e d d a t a 3

    CUB3LowDEF2Low DEF2HighDEF2InstFreq1Freq2Freq3Freq4Freq5Inrush3NEF1LowNEF1High NEF1InstNOC3LowNOC3HighNOC3Inst

    men

    upic

    t

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 13

    The left and right arrow buttons are used for opening the desired view in the main window.Manipulation of the arrow buttons does not affect indications, control of objects or panel sta-tus. The views are described closer in the following chapters.

    4.1.1. MIMIC view When the MIMIC view is opened in the main window, the configuration picture of the con-trol unit is shown on the display. The MIMIC view gives the real-time status of objects (dis-connectors, circuit breakers, etc.) according to the status of the predetermined binary inputs.The MIMIC view is the default view of the protection relay (at power up, after time-out,etc.).

    C button functions in the MIMIC view Press the C button for 2 s to reset indications. Press the C button to cancel password inquiry.

    Fig. 4.1.1-1. MIMIC view.

    4.1.2. MEASURE-MENT view

    When the measurement view is opened to the main window, the values measured by the pro-tection relay will be shown on the display. The up and down arrow buttons are used forscrolling up and down the list in the window.

    The assisting window gives general information of how to scroll the display.

    C button functions in the MEASUREMENT view If there are active indications, press the C but-

    ton for 2 s to reset. When there are no active indications, press the

    C button 2 s to reset accumulated energymeasurements.

    Fig. 4.1.2-1. Measurement view.

    4.1.3. EVENT view The operation event contains the application name, channel number, code, date and time ofthe last 100 operations. The most recent recorded event is stored on top of the event list.

    R

    C

    E

    R

    L

    F

    I

    0

    RL

    21 kV

    CB OK

    AROFF

    load

    view

    C

    E

    R

    L

    F

    I

    0

    R L

    MeasurementIL1-A 800IL2-A 803IL3-A 800I0 0I0b 0U12 kV 20U23 kV 20U31 kV 20U1 kV 11.5U2 kV 11.5U3 kV 11.5U0-V 0kW L1 7360kW L2 7360kW L3 7360

    Updat ing values

    MIMIC EVENT

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 14

    C button functions in the EVENT view if there are active indications, press the C but-

    ton for 2 s to reset. when there are no active indications press C

    button 2 s to reset events recorded.

    Fig. 4.1.3-1.EVENT view

    4.1.4. ALARM view The ALARM view shows all the configured alarms with alarm texts. Active (not acknowl-edged) control alarms are distinguished from non-active alarms by LEDs and user-definedalarm texts.

    C button functions in the ALARM view If there are active indications, press the C but-

    ton for 2 s to reset. When there are no active indications, press the

    C button for 2 s to acknowledge alarms. The acknowledgement proceeds according to

    configuration made by the user.

    Fig. 4.1.4-1. ALARM view.

    4.2. Passwords Three passwords can be used: Password 1 (MIMIC) inhibits local/remote/disabled/logic selection.

    Settable: password enabled/non-enabled. Default 100000. Password 2 (parameter) inhibits parameter setting.

    This password is always enabled. Default 200000. Password 3 (level) inhibits access to the technical level.

    Settable: password enabled/non-enabled. Default 300000.

    When using the control position button password 1 has to be given (if enabled). To enter thesetting mode, a second password (password 2) is required. This password applies as long asthe user stays on the technical level.

    C

    E

    R

    L

    F

    I

    0

    R L

    even

    tvie

    EventsNOC3Low: 31/E1

    95-12-2418:35:12:230

    NOC3Low: 31/E095-12-2418:35:12:330

    NOC3High: 32/E195-12-2414:25:52:720

    NOC3High: 32/E395-12-2414:25:52:760

    Event l ist

    MEAS ALARM

    R

    L

    F R L

    C

    E

    I

    0

    alar

    mvi

    e

    C c l e a r s a l a r m s

    E V E N T M I M I C

    CB spring ready

    SF6 gas density

    Temperature

    Inter locking

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 15

    To enter the read-only-state of the technical level, the user has to give password 3. The useris able to change all three passwords or just one of them in the Main menu configuration.The maximum length of a password is six characters.

    Passwords 1 and 2 are reset after the preset time-out and must therefore be re-entered beforeusing the control position button or setting parameters.

    Fig. 4.2.-1. Setting a password.

    4.3. Technical level

    The menus of the technical level contain information for the programming of the protectionrelay. The technical level is accessed from the MIMIC view on the user level by pressingthe E button for 2 seconds and by entering the password if required. To return to the userlevel, press the E button for 1 second in the MAIN MENU.

    E C

    Confirm Cancel

    Select digi twi th lef t / r ightarrow button

    Select valuefor digi t wi thup/down arrowbutton

    E

    Press the E button.The system asks forthe password

    Setting group 1

    ENTER PASSWORD

    ******

    Setting group 1

    ENTER PASSWORD

    ******

    Setting group 1

    ENTER PASSWORD_ _ _ _ _ H

    OR

    Operation mode= Definite timeStart current= 3.1 x InOperation time= 041.03 sTime multiplier= 0.78

    Operation mode= Definite timeStart current= 3.1 x InOperation time= 041.03 sTime multiplier= 0.78

    Operation mode= Definite timeStart current= 3.1 x InOperation time= 041.03 sTime multiplier= 0.78

    pasw

    ord

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 16

    Fig. 4.3.-1. Moving between user level and technical level.

    4.3.1. Menu sys-tem of pa-rameters

    The interactive communication between the operator and the MMI is based on menus. Pressthe E button for 2 seconds to activate the MAIN MENU.

    The views are used for reading setting parameters, recorded values, etc. The menu systemis divided into three or four levels (depending on the access level):

    MAIN menu GROUP menu SUBGROUP menu PARAMETER menu.

    The buttons for object control have no functions in the menu system.

    21 kV

    CB OK

    AROFF

    1 Sec2 Sec

    Main menu

    Note ! Password 3can be used, ifwanted, whenentering the Mainmenu (see chapter4.2)

    Changing level

    MIMIC view

    User level

    Technical levelStatus

    MAINMENU

    Protection lib.Control lib.Cond. Monit. libMeasurements lib.Communic. libStandard lib.TestsInformationConfiguration

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 17

    Fig. 4.3.1-1. Menu structure on technical level.

    4.3.2. Special sit-uations

    If the user is setting a password in the assisting window when a message of high priorityappears (other than help messages), the password programming is automatically cancelledand the high-priority message is displayed. Then a new attempt to open the password has tobe done. When the password has been opened (or failed), the message reappears in the as-sisting window. Messages are cleared by pressing the C button for 2 seconds

    When the C button is pressed during the setting of a password, the setting proce-dure will be cancelled. In other situations, the C button is used to clear the assistingwindow.

    When a message of high priority is indicated in the assisting window, no help messages aredisplayed until the window has been cleared.

    4.3.3. Menus The main menu is the main view of the technical level, where the first row is always dedi-cated for the header text of the main level. The main menu is followed by the group menuand the subgroup menu which form the hierachical structure.

    4.3.4. Parametermenu

    One parameter on this level consists of 2 rows:

    row 1: parameter text row 2: "=" sign and setting value including the unit when specified (numeric value, character

    string, enumerator).

    On the parameter level the cursor moves two rows at a time

    tech

    lev

    MENU STRUCTURE (LEVEL 2)

    SETTING GROUP 1

    PARAMETER MENU

    GROUP MENUMAIN MENU

    MAIN MENU

    Navigat ion

    PROTECTION LIB

    NOC3Lo w

    SUBGROUP MENU

    O p e r a t i o n m o d e= D e f i n i t e t i m eS t a r t c u r r e n t= 3 . 1 x I nO p e r a t i o n t i m e= 0 4 1 . 0 3 sT i m e m u l t i p l i e r= 0 . 7 8

    A c t u a l s e t t i n g sS e t t i n g g r o u p 1S e t t i n g g r o u p 2C o n t r o l s e t t i n g sI n p u t d a t aO u t p u t d a t aR e c o r d e d d a t a 1R e c o r d e d d a t a 2R e c o r d e d d a t a 3

    CUB3LowDEF2Low DEF2HighDEF2InstFreq1Freq2Freq3Freq4Freq5Inrush3NEF1LowNEF1High NEF1InstNOC3LowNOC3HighNOC3Inst

    StatusDisturb. record.Protection lib.Control lib.Cond. Monit. libMeasurements lib.Communic. libStandard lib.TestsInformationConfiguration

    !

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 18

    As on the main level and group level, the first row of the display is dedicated for the headertext. The header text is advisory and shows the position of the parameter menu in the menusystem in the form of a path (Main menu/Group menu/Subgroup menu/Parameter menu)

    If the parameter to be entered is password-protected, the procedure for opening the param-eter menu is the same as for the main menu.

    4.3.5. Moving in the menus

    The arrow buttons up and down are used for moving in the parameter menu. When the ap-propriate parameter is highlighted, the setting mode is activated by pressing the E button.

    4.4. Setting a pa-rameter

    When the setting mode has been activated by pushing the E button, the first digit or characterof the setting value/text of the concerned parameter is blinking (in the case of an enumerator,the entire text is blinking). Now the digit/character can be set by using the up/down buttons.

    The next digit/character to be set is activated by pressing the arrow buttons right or left(when setting an enumerator type parameter, the left and right arrows have no function).

    Fig. 4.4.-1. Parameter setting

    The setting is confirmed by pressing the E button. Before confirming, the previous settingvalue can be restored by pressing the C button.

    If an illegal setting value is confirmed in the setting mode, a message tells the user that thesetting is out of range. The previous parameter value remains unchanged.

    E

    para

    mes

    Operation mode= Definite timeStart current= 3.1 x InOperation time

    Operation mode= Definite timeStart current= 3.1 x InOperation time

    Select parameter

    Setting group 1

    E

    C

    If parameter withnumeric value selectdigi t

    Confirm

    selection

    Scrol l forwanted valuefor digi t

    I f text parameter,select texttype

    ConfirmGive

    password

    2

    if

    need

    Cancel

    OR

    Setting group 1

    Setting group 1

    Operation mode= Definite timeStart current= 3.1 x InOperation time

    Operation mode= Definite timeStart current= 4.1 x InOperation time

    Operation mode= Definite timeStart current= 3.1 x InOperation time= 041.03 sTime multiplier= 0.78

    Operation mode= Definite timeStart current= 3.1 x InOperation time= 041.03 sTime multiplier= 0.78

    Operation mode= Definite timeStart current= 3.1 x InOperation time= 041.03 sTime multiplier= 0.78

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 19

    4.5. Saving pa-rameters

    Parameters can be saved in three different ways:

    1. by executing the following sequence select parameter Store located in Configuration/General (select Restore if you dont want to

    save the changes, see note below) enter password select Store/Progress with the arrow buttons confirm operation by pressing the E button, the assisting display confirms the storage

    2. automatically automatically after eight (8) hours counted from last storage. Then the feeder terminal saves

    the latest changes.3. moving from Main menu to the MIMIC view, if a parameter has been changed

    when changing view SAVE CHANGES E = yes, C = No appears in the assisting window Confirm or wait for the time-out to elapse to save changes automatically if Cancel is selected the saving procedure is cancelled momentarily. To restore the previous

    values the Restore parameter has to be used (described above). If not, the parameters will besaved according to item 2.

    Storage of data is indicated by the text --Storing-- in the assisting window.

    Note! At restoring, the relay is reset and restarted.

    4.6. Acknowl-edgement and reset-ting of indi-cators, outputs and registers

    The C button is used for acknowledging and resetting of indicators, outputs and registers asfollows.

    Indicators and outputs of protection functions are acknowledged by pressing the C buttonand the E button simultaneously for at least 2 seconds. A message in the assisting windowconfirms the acknowledgement.

    Indicators, outputs of functions and registers are acknowledged by pressing the C and the Ebutton simultaneously for at least 5 seconds. A message in the assisting window confirmsthe acknowledgement.

    Fig. 4.6.-1. Acknowledgement and resetting.

    View dependentreset

    Non-resetindications

    2 sec.2 sec.2 sec.

    Clears messagesaccording to viewMIMIC, MEAS,EVENT, ALARM,Main Menu

    Resetsindications

    Resets outputsand indications

    Resets registers,outputs,indications and waveform memory

    Reset/Clear operation done

    CCC

    E

    5 sec. totC

    E

    kuits

    equ

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 20

    5. Protection re-lay indications

    There are two different kinds of indication messages available in the assisting window:

    information about the protection relay functions and the condition of the protection relay (self-diagnosis) together with a LED indication.

    a text message without LED indication. This type of message is generally related to e.g. con-dition monitoring, alarms and warnings.

    Fig. 5.-1. Protection indicators

    5.1. Priority of indication and help messages

    The messages in the assisting window have a certain priority. If different type of indicationsare activated simultaneously, the message with the highest priority appears on the display.The priority of the messages:

    1. Internal fault2. Trip, CBFP3. Start, Block, Supervision 4. Help messages

    The first latched and active indication (concerns messages 1 and 2) is shown in the assistingwindow according to the predetermined priority. The latest latched and active indication(concerns messages 3 and 4) is shown in the assisting window according to the predeter-mined priority

    5.1.1. Help mes-sages

    Help messages (priority 4) assist the user by displaying hints of the following actions.

    R

    Uaux = 80...265 Vdc/acfn = 50 HzIn = 1/5 A (I)

    1MRS xxxxxx98150Un = 100/110 V (U)

    Uon = 100/110 V (Uo)

    Ion = 1/5 A (Io)

    9509

    C

    E

    R

    L

    F R L Assisting window

    Protection indication LEDs:Left: Ready, IRF, Test modeCenter: Start, BlockRight: Trip, CBFP

    U s e C - b u t t o n t o

    c l e a r E v e n t s

    assistvi

    C c l e a r s a l a r m s

    E V E N T M I M I C

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 21

    5.1.2. Indication messages

    Indication messages (priorities 1-4) automatically gives an overview of indications of pro-tection and condition monitoring operations and internal protection relay faults. The indica-tions are shown in a priority order in the assisting window and the indication messages willbe active until acknowledged by pressing the C button for two seconds.

    5.2. Protection indications

    When one of the protection functions of the protection relay starts, the name of the corre-sponding protection function and the text ":START" are displayed in the assisting window.In the case of three-phase and two-phase protection functions, also the faulted phases aredisplayed. Also a yellow indicator LED is lit.

    When the protection function started is blocked, the name of the corresponding function andthe text ":BLOCK" are displayed in the assisting window. Also a yellow indicator LED isblinking.

    When the protection function trips, the name of the function and the text ":TRIP" are dis-played in the assisting window. Also a red indicator LED is lit. In the case of three-phaseand two-phase protection functions also the faulted phases are displayed.

    When the protection function delivers a delayed trip for circuit-breaker failure protection,the name of the function and the text ":TRIP" are displayed in the assisting window. Also ared indicator LED is blinking. In the case of three-phase and two-phase protection functions,also the faulted phases are displayed.

    N O C 3 L o w : S T A R T

    L 1 , L 2 , L 3

    N O C 3 L o w : B LOCK

    N O C 3 L o w : T R I P

    L 1 , L 2 , L 3

    N O C 3 L o w : T R I P

    L 1 , L 2 , L 3

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 22

    5.3. Self supervi-sion (IRF)

    The REF 54_ is provided with an extensive self-supervision system. The self-supervisionsystem handles run-time fault situations in the REF 54_ and informs the user about an ex-isting fault via an MMI and a LON/SPA communication.

    The green READY indicator starts to blink when a fault has been detected. At the same timethe protection relay delivers a fault signal to the self-supervision output relay of the REF54_. Additionally, a fault indication text appears on the MMI of the REF 54_. Also, an eventE57 is generated to the serial communication (channel 0).

    The fault indication text on the MMI consists of two constant rows as shown in the next ex-ample.

    Fault indication has the highest priority on the MMI. Other MMI indications cannot overrunthe IRF indication. When the display panel has received a fault indication, the fault indica-tion text remains on the MMI. By pressing the C button for 2 seconds the fault indicationtext is cleared from the display, but the green LED remains still blinking. Blinking of thegreen READY indicator cannot be stopped.

    In case an internal fault disappears, the fault indication text stays on the display, if it has notbeen cleared by the C button. The green READY indicator stops blinking and an alarm out-put IRF is released to normal service state. Also, an event E56 is generated to serial commu-nication (channel 0).

    The fault code is stored and can be read from the main menu protection relay Status/General/IRF code. The IRF code includes the code of the first internal fault detected by the self-su-pervision system.

    The fault code describes the type of internal fault in the REF 54_. When a fault appears, thecode should be recorded and given to the authorized repair shop when overhaul is ordered.

    5.4. Condition monitoring indication

    If the protection relay includes condition monitoring functions that are not directly relatedto any protection functions of the protection relay or to the internal condition of the protec-tion relay, they are indicated in the assisting window by the message SUPERVISION andan explanatory text.

    Example:

    S E L F S U P E R V I S I O N

    * I N T E R N A L F A U LT *assisupv

    C M T C S 1 : S U P E R V

    T r i p c i r c u i t s u passisupi

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 23

    5.5. Test modes There are various test modes for each of the following four categories: Function Control MIMIC I/O test

    5.5.1. Function test

    It is possible to activate the outputs of the function locally from the MMI or externally viathe serial communication. The outputs are activated by using control parameters of the func-tion.

    For further details of functions, read the manual Technical Description of Functions.

    5.5.2. Control test The system provides a general interlocking bypass mode (parameter Control/General/Inter/bypass) that overrides all interlocking signals. Activation of interlocking bypass mode acti-vates the interlocking enable signals of all control objects. Thus all control actions are pos-sible and enable signals of the controllable objects are not checked while the objects arecommanded. As long as the mode is active the interlocking LED in the MMI is red andblinking. Additionally the assisting window of the MIMIC view will indicate the specialcondition.

    5.5.3. MIMIC test The test mode for MIMIC is entered by setting the Panel test parameter to start (1) in Mainmenu/ Tests/ Mimic [17] directory. The test can be interrupted by pressing any button. Ac-cordingly, the same Panel test is done as at power up (see chapter Display test at power up).

    5.5.4. I/O test The test mode is for testing binary inputs and outputs and their effect on the function of theprotection relay. Entering the test mode for the inputs or outputs is done by setting the pa-rameter Test mode to Active in Tests/General at technical level. The user has to enter thetest mode before testing or else the changes will not be valid. The test mode can be cancelledby setting the Test mode parameter to Not Active or by power up.

    Note! If the user forgets to cancel the test mode, it remains on and the READY LED remainsblinking.

    5.6. Green indi-cator LED

    Three different functions are embedded in the READY indicator.

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 24

    5.7. Yellow indi-cator LED

    Steady LED: READY The LED is lit when the protection relay is in normal operation, i.e. no internal faults have occurred and an auxiliary voltage is available to the protection relay.

    Blinking LED: IRF An internal protection relay fault (IRF) has occurred but an auxiliary voltage is connected. Also, if the pro-tection relay is in test mode, the LED is blinking. When an internal fault occurs, a message is received in the assisting window, provided the MMI/MIMIC panel is operative.

    Non-active LED: OFF The auxiliary voltage supply to the protection relay has been disconnected

    Check that the auxiliary voltage is discon-nected before taking any further action.

    Table 5.6.-1 Green indicator LED functions

    !

    Non-active LED: OFF Normal operation mode. No function has started.

    Steady LED: START A protection function is activated and the display shows the reason for starting. The start indication can be selected to be latching/non-latching. A non-latching type indicator automatically goes out when the fault disappears (the protection stage resets). A latching type indicator remains lit, although the fault disappears, until cleared by pressing the C button for two seconds.

    Should several protection stages/functions start in a short time, the last start is indicated on the display.

    Blinking LED: BLOCK The start LED goes on blinking as long as a protection function of the protection relay is blocked. The block-ing indication disappears when the blocking is removed or when the protection function in question is no longer started. Should the function still be started when the blocking signal is eliminated, the start indication will be activated. A message telling, which function has been blocked appears on the display. If several protec-tion functions are blocked at the same time, the most recent blocking is indicated on the display. If a protec-tion function is blocked when other protection func-tions are started, but not blocked, the LED remains blinking (Blocking has higher priority than start)

    Table 5.7.-1 Yellow indicator LED functions

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 25

    5.8. Red indica-tor LED

    5.9. Interlocking Interlocking is used to inhibit the close or open command for a controllable object in certainsituations. The interlocking program of the REF 54_ operates according to the permissionprinciple, i.e. any control operations not enabled by interlocking are inhibited.

    When an object is selected with the Select button, the assisting window shows the status ofthe interlocking program. The downmost LED of the programmable LEDs is reserved forthe interlocking function.

    Non-active LED: OFF Normal operation mode. No trip function has operated.

    Steady LED: TRIP A protection function has tripped. The trip indication is latching, i.e. the trip indication must be reset by press-ing the C button (or via the serial communication). If several protection stages/functions trip in a short time, the first tripping remains on the display.

    Blinking LED: TRIP (CBFP) If the tripping is due to the CBFP (circuit breaker fail-ure protection), the red indication LED is blinking. The indication is reset by pressing the C button for 2 sec-onds.

    Table 5.8.-1 Red indicator LED functions

    Non-active LED: OFF Neither interlockings nor active test mode

    Blinking LED: red Control test mode active (interlocking bypass)

    Steady LED: yellow Control command has been inhibited (interlocked)

    Table 5.9.-1 Green indicator LED functions

  • Operators Manual REF 54_ 1MRS750500-MUM

    Page 26

  • ABB Transmit OyRelays and Network ControlP.O. Box 699FIN-65101 VaasaFinlandTel. +358 10 22 4000Fax. +358 10 224 1094

    1 M

    RS

    7505

    00-M

    UM

    EN

    97.

    12

    Communications

    Services

    Meter & LoadManagementInformation

    Management

    NetworkManagement

    StationAutomation

    Panorama is the standard for a comprehensive range of integrated solutions for the efficient and reliable management of power networks. Using innovative information technology , Panorama delivers total control of the power process, from generation to consumption. The Panorama standard covers six application areas, each offering specific solutions.