    Minimum Clearance in Substation:

    Voltag

    e

    Highe

    st

    Voltag

    e

    Lighting

    Impulse

    Level

    (Kvp)

    Switchin

    g

    Impulse

    Level

    (Kvp)

    Minimum Clearance Safety

    Clearance(

    Mt)

    Ground

    Clearance(

    Mt)Phase

    -Earth

    Phase-

    Phase

    11KV 12KV 70 0.178 0.229 2.600 3.700

    33KV 36KV 170 0.320 0.320 2.800 3.700

    132KV 145KV 550 1.100 1.100 3.700 4.600

    650 1.100 1.100 2.700 4.600

    220KV 245KV 950 1.900 1.900 4.300 5.500

    1050 1.900 1.900 4.300 5.500

    400KV 420KV 1425 1050(P-

    E)

    3.400 4.200 6.400 8.000

    Electrical Clearance in Substation:Voltage Height of I

    Bay From

    Ground

    (Mt)

    Height

    of II

    Bay

    From

    Ground

    (Mt)

    Bay Width

    (Mt)

    Phase-

    Phase

    (Mt)

    BetweenEquipm

    ent

    Earth

    Wire

    From

    Ground

    132KV

    (Single)

    8.0 - 11.0 3.0 3.0 10.5

    220KV

    (Single)

    12.5 - 18 4.5 4.5 15.5

    220KV

    (Double)

    18.5 25 25 4.5 4.5 28.5

    400KV 15.6 22 22.0 7.0 >6.0 30.0

    Standard Bay Widths in Meters:

    Voltage Bay Width (Meter)

    11KV 4.7 Meter

    33KV 4.7 Meter

    66KV 7.6 Meter

    132KV 12.2 Meter

    220KV 17 Meter

    400KV 27 Meter

    Standard Bus and Equipment Elevation

    Voltage Equipment live Terminal

    Elevation (Meter)

    Main Bus Take of

    Elevation

    (Meter)Low High

    11 KV/33KV 2.8To 4 5.5 To6.5 9 6.5To8.5

    66KV 2.8To 4 6To8 9To 10.5 9.5

    132KV 3.7To5 8To9.5 13.5To14.5 12To12.5

    220KV 4.9To5.5 9To13 18.5 15To18.5400KV 8.0 15.5 - 23

  • 8/10/2019 Minimum Clearance in HV

    2/3

    Phase spacing for strung Bus:

    Voltage Clearance

    11KV 1300 mm

    33KV 1300 mm

    66KV 2200 mm

    132KV 3000 mm

    220KV 4500 mm

    400KV 7000 mm

    Minimum Clearance of Live Parts from Ground:

    Voltage Minimum Clearance to Ground (Mt) Section Clearance (Mt)

    11KV 3.700 2.600

    33KV 3.700 2.800

    66KV 4.600 3.000

    132KV 4.600 3.500

    220KV 5.500 4.300400KV 8.000 7.000

    Insulator String:

    Voltage No of Suspension

    String

    Length (mm) No of Disc for Tension

    String

    Length i

    66KV 5 965 6 1070

    132KV 9 1255 10 1820

    220KV 14 1915 15 2915

    400KV 23 3850 2 X 23 5450

    Nominal Span:

    Minimum Ground Clearance:

    Voltage Ground (Meter)

    66KV 5.5

    132KV 6.1220KV 7.0

    400KV 8.0

    800KV 12.4

    Voltage Normal Span (Meter)

    66KV 240-250-275

    132KV 315-325-335

    220KV 315-325-335

    400KV 315-325-335

    Voltage Tower

    Type

    Vertical Space

    (Mt)

    Horizontal

    Space(Mt)

    Total Height From

    Ground(Mt)

    66KV A 1.03 4.0 15.91

    B 1.03 4.27 15.42

    C 1.22 4.88 16.24

    132KV A 7.140 2.17 23.14

    B 4.2 6.29 22.06

  • 8/10/2019 Minimum Clearance in HV

    3/3

    Indoor Substation Minimum Clearances

    Distance Descriptions

    0.9 Meter Horizontally between any item of equipment and thesubstation wall

    0.6 Meter Horizontally between any Two items of equipment

    1.2 Meter Horizontally in front of any HV switchgear

    Clearance of Conductor on Tower

    NORMS OF PROTECTION FOR EHV CLASS POWER TRANSFORMERS

    The bottom most portion of any insulator or bushing in service should be at a

    minimum height of 2500 mm above ground level.Location of L.A (From T.C Bushing):

    Voltage BIL KV Peak Distance (Mt)

    11KV 75 12

    33KV 200 15

    66KV 325 24

    132KV 550 35

    220KV 900 To 1050 Close To T.C

    C 4.2 7.15 22.68

    D 4.2 8.8 24.06

    220KV A 5.2 8.5 28.55

    B 5.25 10.5 29.08

    C 6.7 12.6 31.68D

    Voltage ratio & capacity HV Side LV Side Common relays

    132/33/11KV up to 8MVA

    3 O/L relays + 1 E/Lrelay

    2 O/L relays + 1 E/Lrelay

    Buchholz, OLTCBuchholz, OT, WT

    132/33/11KV above 8

    MVA and below 31.5

    MVA

    3 O/L relays + 1 dir.

    E/L relay

    3 O/L relays + 1 E/L

    relay

    Differential,

    Buchholz, OLTC

    Buchholz, OT, WT

    132/33KV, 31.5 MVA &

    above

    3 O/L relays + 1 dir.

    E/L relay

    3 O/L relays + 1 E/L

    relay

    Differential, Over

    flux,Buchholz, OLTC

    PRV, OT, WT

    220/33 KV, 31.5MVA &

    50MVA 220/132KV, 100

    MVA

    3 O/L relays + 1 dir.

    E/L relay

    3 O/L relays + 1 dir.

    relay

    Differential, Over

    flux,Buchholz, OLTC

    PRV, OT, WT400/220KV 315MVA 3 directional O/L

    relays (with dir. High

    set) +1 directional

    E/L relays. Restricted

    E/F relay + 3

    Directional O/L

    relays for action

    3 directional O/L

    relays (with dir. High

    set)+1 directional

    E/L relays. Restricted

    E/F relay

    Differential, Over

    flux,Buchholz, OLTC

    PRV, OT, WT and

    overload (alarm)

    relay