Minilec Microprocessor Based Alarm Annunciators aredesigned to keep an alert & watchful eye on your plant &processes. The entire range has been designed with an
insight into the modern day manufactur ing plant & its futurerequirements. Minilec Alarm Annunciators are equipped
with microprocessor-based design, super bright LED faciawindows, site selectable, programmed sequences as perISA standard & thoughtful provisions for troubleshooting &maintenance. Dynamic, Aler t & Responsive These unique
advantages have helped the Minilec Annunciators to be anicon in the power T & D industry & engineeringestablishments in India. The world class Minilec
Annunciator has made its presence felt in Overseasmarkets.
MODELS
MICROWARN 0600,MBAS 0600,MBAS 9700,MBAS 09,MBAS 08,Annunciation Panels, Microfacia
Ordering InstructionsProduct Family NameModel Name
Aux. Supply / Controlsupply voltageNo. of Inputs (Windows)Operating sequence
FEATURES 4 windows to 128 windows Integral & Split models Microprocessor based
Super bright LEDs for facia Standard operating sequences Any other custom- made sequences NO-NC & Trip Non-Trip site
selectable Repeat relays Supply fail annunciation / Indication Choice of 3 window sizes Choice of five colours RS 232 / RS 485 Output Port
51
ALARM ANNUNCIATORS
FUNCTIONS Continuous monitoring of input
parameters Control of process through outputs &
software Data acquisition & communication Data Storage & records through PC
-
8/10/2019 minilecAlarm Annunciators
2/10
MBAS 0600
MBAS 0600 is a improved version of earlier MBAS 9400 and is available for 4 to 32 windows
52
The Design Features
Single chip microcontroller logic Opto isolated inputs and outputs
Super Bright LED window illumination High Noise immunity / isolation Switch mode power supply
Self surveillance watchdog LED
The Constructional Flexibili ty
Conforming to DIN panel cutouts Replaceable snap-on window capsules
Two different window size Moulded enclosures
The Functional Features
Fixed Sequence ( S1/S2/S3/S4)
Potential free dry contact inputs
NO/NC inputs selectable configuration
Relay output for external Audiblerd
Hooter 3 Relay (optional) for either of
below m entioned features
a) Ring back hooter
b) Supervisory control
M in i lec Standard CommunicationProtocol
Optional Features Fault Follower contact output
Any custom built operating per fault Input (NO or NC)sequences Supply fail indication /
Manned / Unmanned function annunciation Built- in M ODBUS RTU/ ASCII Protocol Built- in control push buttons
System Enclosur esThe MBAS 0600 annunciation systems is configured in multiples
of four basic ABS moulded enclosures
Size 1 D Size 2 D Size 3 D Size 4 D
Basic Standard Enclosures
*
A L A R M A N N U N C I A T O R S
10B8SPO
1D
10B6SP0
1D
22B10SP0
2D
20B16SPO
2D
14B0SPO
1D
28B0S0O
2D
Back view showing Terminal details
PowerSupply
DIPfor
SequenceSelection
Switches
OutputRelays
Fuse
RepeatRelay
Terminal
Fault InputTerminals
RS 232Port
DIP forNO/NC &Grouping
Manned /Unmanned
PC Side software
Functional Block Diagram
-
8/10/2019 minilecAlarm Annunciators
3/10
-
8/10/2019 minilecAlarm Annunciators
4/10
A L A R M A N N U N C I A T O R S
M INILEC offers its unique alarmAnnunciator based on the latest single
chip micro-controller technology with serialcommunication facility. Available in 19 rack type
enclosure. MBAS 9700 annunciators have split architecturefor 16, 24, 32, 40, 48, 64, 80 ,96 ,112 & 128 windows. 24, 32,
48, 64, 80, 96,112, & 12 8 window m odels are housed in 19 racktype enclosures, separate for MCU & for PSU. Here choice of facia
(DFU) is of 3 types (a) Sm all size i.e. 30 x 30 m m and (b ) Big size is 30x 65 m m ( c) 5 0 x 70 mm. (on request) Facia is available in multiples of16 windows. In addition to all other standard features, MBAS 9700has additional facility of computer linking. A serial port(RS232/RS485) o utput is available which c an be supported by an
IBM compatible PC of minimum 386 configuration. Minilec cansupply the standard software with every model or can
develop suitable softw are as per custom er requirementsor can provide source coding / protocol details to
enable client to develop their own suitablesoftware.
STANDARD FEATURESS ingle chip micro-control ler log ic . Super
bright LED's for window illumination. Siteselectable NO/NC type fault con tacts. Siteselectable trip /Non trip (Grouping) . Easy cardreplacement & hence fault diagnosis. SwitchMo de Power Supply. (Suitable for Both AC/DCSupply) High noise imm unity and wide inputsupply variation. Opto-isolated Inputs andOutputs. Site Selectable sequences. Potentialfree dry input contacts. Two different windowsizes. Replaceable window lens & windowlegends. Computer linking for fault logging withprinter facility for report. Self-surveillance watchdog LED. Relay output for external audible
hooter. D iagnost ics Menu Redundant PowerSupply CPU fail & PSU fail indicatio n w ith relayoutput contact (Only in 19 Rack)
User Friendlyterminal Connectors
CONSTRUCTIONAL DETAILSMBAS 9700 consist of fourbasic sections1) The Power Supply Unit (PSUModule).2) The Main Control Unit (CPU +IOU Mo dule).3) The Display Facia Unit(DFU Mo dule).4) Computer interface.
THE MAIN CONTROLUNIT (MCU)CPU module is the MainProcessing Unit of MBAS9700 which scans andprocesses the incoming faults i g n a l s f r o m t h e v a r i o u spotential free field contactsthrough IOU module, and drivesthe corresponding LED window s
and the audible device in order toannunciate the fault through IOUmodule. The IOU module is theinput & output interfacing unit.To each IOU mo dule 16 inputcontacts (potential free) & 16w i n d o w L E D ' s c a n b econnected.
THE DISPLAY FACIAUNIT (DFU)
T h e F a c i a b l o c k i saccessible from front (in
moulded enclosure) andc o n s t i t u t e s o f w i n d o w
capsules. The sandwichedphoto film window inscriptionsare press fitted on the windowcapsules.
For 16 to 12 8 points system theDFUs are g iven sep arately.
OPTIONAL FEATURES Different colored LED's in eachwindow for easy differentiationof c ritical faults. Customized preprogramm ed
operating sequence. M u l t i c h a n n el s e r ia l
c o m m u n i c a t i o n(8 Annunciators & singlecomputer) Repeat Relay Card
THE POWER SUPPLY UNIT (PSU)PSU converts the available power source into aregulated and filtered DC output, which is fed tothe MCU Module & DFUs. The pow er supply canaccept Specified AC or DC I/P supply, dependingupon the application. Redundant Power supply isavailable.
MBAS 9700
MCU RackPSU Rack
54
-
8/10/2019 minilecAlarm Annunciators
5/10
A L A R M A N N U N C I A T O R S
16 Pt. DFU : Small Windows
16 Pt . DFU Big Windows 16 Pt . DFU Big Windows 16 Pt . DFU Big Windows
Dimensional Details for Facia
288
14 4
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
F14
F15
F16
28 2
13 816 Pts. FaciaBig Windows
Panel Cutout
14 4 13 8
13 814 4 16 Pts. FaciaSmall Windows
F1 F2 F9 F10
F3 F4 F11 F12
F5 F6 F13 F14
F7 F8 F15 F16
Panel Cutout
COMPUTER INTERFACE
The MCU unit transmits fault information to computer serially.
RS232/RS485 standard is used for ser ial communicat ion.
Communication protocol modbus ASCII / RTU can be offered. In
computer user-friendly software is written. This software offers on-
line Date & Time setting, Legend setting, Display window & also it
gives fault repor t with o n demand p rinting facility.
TECHNICAL SPECIFICATIONS:
1.0 Supply voltage 20-60 VDC, 90 - 270VAC/DC
2.0 Supply frequency 50 / 60 Hz. ( 3%)for AC
3.0 Input
3.1 Fault Alarm Inputs. Actuation Through Fault Contacts
3.2 Fault contacts. Potential free (volt free) type
3.3 Inpu t inter ro gatio n vo ltage + 1 2V DC( ISO)
3.4 Input isolation Opto isolating device.(2 KV)
3.5 Response Time 40 msec.
3.6 Site selectable DIP for
Fault type NO/NCGrouping Trip/Non Trip
Sequence selection M anual/Auto/ Ring b ac k (o ptional)/ Firstup
4.0 Output
4.1 Output contacts 1NO+ 1NO + 1NO (optional)
4.2 Output con tact fo r CPU & PSU fai l 1NC
4.3 Contact Rating 5 amp at 240 VAC (Resistive)
5.0 No. of windows 16/24/32/40/48/64/80/96/112/128
5.1 Window s dim ensions 30 mm x 30 mm For small w indow s
30 mm x 65 mm For big windows
5.2 Window Colours Red/Yellow /Amber/Green/White/Blue
5.3 Flash rates Fast f lash- 50-60 flashes / MinSlow flash - 25-30 flashes / Min.
5.4 Pow er Consumption 1.5 W per Window. (Max)
6.0 Sequence Manual, Auto,Ring back (optional), Firstup
(Any Other Sequences On Request)
7.0 Serial communication RS232/RS485 (w ith modbus ASCII/RTU)
optional
MBAS 9700
55
Note: Mention specific voltage( Fixed/wide range ) in order
-
8/10/2019 minilecAlarm Annunciators
6/10
55
EXTERNAL WIRING DIAGRAM WITH REPEAT RELAY
COMPUTER
CON1
IOU-1
CON2A
IOU-2
CON3A
CON3ACON3
DFU2
CON3
IOU-3
CON4A
IOU-4
CON5A
CON5ACON5
DFU4
CON5
CON4ACON4
DFU3
CON4
IOU-5
CON6A
IOU-6
CON7A
CON7ACON7
DFU6
CON7
IOU-7
CON8A
IOU-8
CON9A
CON9ACON9
DFU8
CON9
CON8ACON8
DFU7
CON8
CON6ACON6
DFU5
CON6
CON2ACON2
DFU1
CON2
PSU-1 PSU-2 P SU -3 P SU -4
ON ON ON ON
MCU MODULE
OFF OFF OFF OFF
CON10
PSU-5
PSU MODULE
CON10
ON
OFF
REPEAT RELAYCARD - 1
REPEAT RELAYCARD - 2
REPEAT RELAYCARD - 3
REPEAT RELAYCARD - 4
REPEAT RELAYCARD - 5
REPEAT RELAYCARD - 6
REPEAT RELAYCARD - 7
REPEAT RELAYCARD - 8
TOMAINS
FOR CUSTOMERFAULT INPUTS
FFFFFFFF
56
A L A R M A N N U N C I A T O R S - M B A S 9 7 0 0
MODELS MOUNTING DIMENSIONS (mm) OVERALL DIMENSIONS (mm)
A B C D E F G
128 POINTS 57.15 465.10 292.38 482.60 132.50 309.88
112 POINTS 57.15 419.38 292.38 436.88 283.00 132.50 309.88
96 POINTS 57.15 373.66 241.58 391.16 283.00 132.50 259.58
80 POINTS 57.15 327.94 241.58 345.44 283.00 132.50 259.58
64 POINTS 57.15 434.62 -- -- -- -- 452.12 283.00 132.50 --- -- -- -
48 POINTS 57.15 388.90 -- -- -- -- 406.40 283.00 132.50 --- -- -- -
40 POINTS 57.15 388.90 -- -- -- -- 406.40 283.00 132.50 --- -- -- -
32 POINTS 57.15 292.38 -- -- -- -- 309.88 283.00 132.50 --- -- -- -
24 POINTS 57.15 292.38 -- -- -- -- 309.88 283.00 132.50 --- -- -- -16 POINTS 57.15 246.66 -- -- -- -- 264.16 283.00 132.50 --- -- -- -
283.00
MODELS MOUNTING DIMENSIONS (mm) OVERALL DIMENSIONS (mm)
A B C D E F G
128 POINTS 57.15 465.10 393.98 482.60 132.50 411.48
112 POINTS 57.15 419.38 393.98 436.88 283.00 132.50 411.48
96 POINTS 57.15 373.66 292.38 391.16 283.00 132.50 309.88
80 POINTS 57.15 327.94 292.38 345.44 283.00 132.50 309.88
64 POINTS 57.15 327.94 241.58 345.44 283.00 132.50 259.58
48 POINTS 57.15 439.70 -- -- -- -- 457.20 283.00 132.50 --- -- -- -
40 POINTS 57.15 439.70 -- -- -- -- 457.20 283.00 132.50 --- -- -- -
32 POINTS 57.15 343.18 -- -- -- -- 360.68 283.00 132.50 --- -- -- -24 POINTS 57.15 343.18 -- -- -- -- 360.68 283.00 132.50 --- -- -- -
16 POINTS 57.15 246.66 -- -- -- -- 264.16 283.00 132.50 --- -- -- -
283.00
DIMENSIONAL DETAILS - MCU & PSU
MCU & PSU for 16 to 64 w indows are housed in one 19 rack.
20 - 60 V DC
128
112
PANEL CUTOUT DETAILS - DFU
96
80
FPSU
SIDE VIEW
E
APSU
FRONT VIEW
C
G
FMCU
SIDE VIEW
E
AMCU
FRONT VIEW
D
B
64
48
32
QRQRQRQRQRQRQRQ
24S
16
P
P Q R
Small Window 138mm 138mm 6mm
Big Window 138mm 282mm 6mm
W L D
Small Windows
Big Windows
Overall Dimensions ( DFU )
MODELS
128 POINT 144m.m. 1152m.m . 70m.m.112 POINT 144m.m. 1008m.m . 70m.m.96 POINT 144m.m. 864m.m . 70m.m.80 POINT 144m.m. 720m.m . 70m.m.64 POINT 144m.m. 576m.m . 70m.m.48 POINT 144m.m. 432m.m . 70m.m .40 POINT 144m.m. 432m.m . 70m.m .32 POINT 144m.m. 288m.m . 70m.m .24 POINT 144m.m. 288m.m . 70m.m .16 POINT 144m.m. 144m.m . 70m.m .
128 POINT 144m .m . 2304m.m. 70m.m.
112 POINT 144m .m . 2016m.m. 70m.m.
96 POINT 144m .m . 1728m.m. 70m.m.
80 POINT 144m .m . 1440m.m. 70m.m.
64 POINT 144m .m . 1152m.m. 70m.m.
48 POINT 144m .m . 864m.m. 70m.m.40 POINT 144m.m . 720m.m . 70m.m .32 POINT 144m.m. 576m.m. 70m.m.24 POINT 144m.m. 432m.m. 70m.m.
16 POINT 144m.m. 288m.m. 70m.m.
24B
7.0 mm
10.0 mm
-
90 - 270 VAC/ DC
-
8/10/2019 minilecAlarm Annunciators
7/10
MBAS 08
A L A R M A N N U N C I A T O R S
Most compact alarm Annunciator with improved window design and all major features of MBAS 0600Annunciator. Models with built -in Buzzer & Push buttons also available.
Supply Voltage
Supply Frequency [FOR AC]
Windows
Display (Window)
Window DimensionsSmallBig
Power Consumptions
Flash Rate
Operating Sequence
Other Features
Optional Features
Input Signal
Input Interrogation Voltage
Window Colours
Output Contacts
Output Contact Rating
Inbuilt Push Buttons
Communication
Operational Temp. Lim it
Humidity
Enclosure
Unit DimensionsOverall (L x W x D)Cutout (L x W)
Weight
90 to 27 0 VAC/DC
24 VDC /30 VDC /48VDC50 / 60 Hz 3%
4 / 6 / 7 / 8 [m ax]
Window lenses replaceableLegends replaceable.
37 X 17 mm.37 X 27 mm. for 4 Windows m odel only
50 - 6 0 Flash per min. in fast flashing
20 - 30 Flash per min. in slow flashing
S1, S2, S3, S4 (Site Selectable)
NO / NC and Grouping (Trip/Non trip) Selection Supervisory Contact output.
Any other operating sequence. RS232 / RS485 Output Man / Unmanned Feature. Supply fail Annunciation
Potential Free contacts
+ 12 VD C
Red, Green, Yellow, Amber, Blue, White.
1 NO + 1 NO [For Hooter]1NO For Ring back or Supervisor y contact ( Optional)
5 Amp, 24 0V AC (Resistive)
4 NOS. (Test, Mute, Accept, Reset) Mem brane type (Optional)
RS232 / RS485 (MODBUS RTU/ASCII) (Optional)
-5C to 60 C
Upto 95% Rh
ABS moulded enclosure
96 x 96 x 76 mm92 x 92 mm
350gm
1.5 Watts per Window (M ax)
M
A1
U/M
A2
SW
I2
C2RLY-2
VE~ /+
- VE~ /
E
AUX. SUPPLY
F1
F2
F3
F4
F5
F6
F7
F8
C
TEST
MUTE
ACK
RST
C
TPB
RPB
APB
MPB
RC N/W
I3
C3RLY-3 RC N/W
I1
C1RLY-1 RC N/W
E
RS 485 OUTPUT
SR. NO. KEY OPERATION MODE OF OPERATION WINDOW STATUS WDL STATUS
1 --- Normal Run Mode As per operation Flashing @ 1 flash/sec.
2 TEST + ACK Sequence selection Windows Flashing @ 1 flash/sec.
Pressed (for 5 Sec.) fast flashes for
2 to 3 sec.
W1 - ON - S1
W2 - ON - S2
W3 - ON - S3
W4 - ON - S4
3 TEST + ACK NO / NC selection W - ON - NO Off
Pressed (for 5 Sec.) W - OFF- NC
4 TEST + ACK Grouping selection W - ON - Group 1 Steady On
Pressed (for 5 Sec.) W - OFF- Group 2
5 TEST + ACK Device ID selection As per char t in Fast Flashing
Pressed (for 5 Sec.) Manual
6 Auto exit af ter 10 Seconds
PROGRAMMING OF MBAS 08
96
96
80
96
OVERALL DIMENSIONS
CUT OUT DIMENSIONS
92
92
CONNECTION
DIAGR
AM
4 Windows PB + 2 Buzzer 6 Windows PB + 2 Buzzer 7 Windows + PB 8 Windows
57
Note: Mention specific voltage
( Fixed/wide range ) in order
-
8/10/2019 minilecAlarm Annunciators
8/10
-
8/10/2019 minilecAlarm Annunciators
9/10
-
8/10/2019 minilecAlarm Annunciators
10/10
A L A R M A N N U N C I A T O R S
The MINILEC Annunciation systems are programmed tooperate as per following operating sequences confirming to ISAstandards. Other sequences / non standard sequences are given
as per customers requirement.
MinilecSequence Code
OperatingSequence Title
ISA Std. Code
S1 Manual Reset M1S2 Auto Reset A1S3 Ringback R1-12S4 First UP F2M-1
P NORMAL
V OFF
A SILENT
P ABNORMAL
/ NORMAL
V STEADY
A SILENT
P ABNORMAL
/ TEST
V FLASHING
A AUDIBLEP ABNORMAL
/ NORMAL
V FLASHING
A SILENT
ACCEPT
ACCEPT
RESET WHILENORMAL
TO ABNORMAL
SILENCE MUTE
SEQUENCE S1 : Manual Reset (M1) 1. Test, Silence Accept,Reset Push Buttons areexternal.
2. Audible alarm can besilenced by pressingSilence (Mute) Pushbutton.
3. Manual reset of Accepted
faults after processconditions return tonormal.
4. Operation test provided.
P NORMAL
V OFF
A SILENT
P ABNORMAL
V STEADY
A SILENT
P ABNORMAL
/ TEST
V FLASHING
A AUDIBLEP ABNORMAL
/ NORMAL
V FLASHING
A SILENT
ACCEPT
ACCEPT
RETURN TONORMAL
TO ABNORMAL
SILENCE / MUTE
SEQUENCE S2 : Auto Reset (A1) 1. Test, Silence Accept,Reset Push Buttons areexternal.
2. Audible alarm can besilenced by pressingSilence (Mute) Pushbutton.
3. Automatic reset ofAccepted faults afterprocess conditions returnto normal.
4. Operation test provided.
P NORMAL
V OFF
A OFF
RB SILENTP ABNORMAL
V SLOW
FLASH
A OFF
RB AUDIBLE
P ABNORMAL
V FAST FLASH
A AUDIBLE
RB SILENT
P ABNORMAL
V STEADY
A SILENT
RB SILENT
RETURNTO NORMAL
RETURN TO NORMAL
ACCEPT WHILENORMAL
TO ABNORMAL
ACCEPTWHILE ABNORMAL
SEQUENCE S3 : Ringback (R1-12) 1. Test, Silence Accept,Reset Push Buttons areexternal.
2. Alarm & ringback Audibledevices.
3. Audible device orringback alarm can besilenced by pressingSilence (Mute) Pushbutton.
4. Ringback visual &audible alarm whenprocess status returns tonormal.
5. Operation test provided.
RETURN TO ABNORMAL
P NORMAL
V OFF
A SILENT
P ABNORMAL
V STEADY
A SILENT
P ABNORMAL
/ TEST
V FLASHING
A AUDIBLEP ABNORMAL
V STEADY
A AUDIBLEACCEPT
MUTE
ACCEPT (FIRST-OUT RESET)
ACCEPT (FIRST-OUT RESET)
RESET WHILENORMAL
FIRST TOABNORMAL
SILENCE / MUTE
SEQUENCE S4 : First Out Manual Reset (F2M-1) 1. Test, Silence Accept,Reset Push Buttons areexternal.
2. First-out flashing andsubsequent steady.
3. Manual reset of Acceptedfaults when processstatus return to normal.
4. Operation test provided.
P ABNORMAL
V FLASHING
A SILENT
Note:
P :Process Status, V :Visual Alarm Status,A :Audible Alarm Status, RB :Ringback audible alarm status.
/ TEST
SUBSEQUENT TOABNORMAL
STANDARD OPERATING SEQUENCES
Repeat Relay Card
External Repeat Relay Cards can be connected for remote annunciation or
interfacing with SCADA or DCS hardware. These cards are connected byplug- in type pre-fab c ables. Repeat Relay Card is suitable for NO type Fault
contacts o nly.
4- 3.0
25
85
180
50
5
190
510
Manned / Unmanned Facility
This feature allows disabling the audio
& visual indication on fault occ urrence ift h e s t a t i o n i s u n m a n n e d . T h e
annunciator registers & records all
faults occurring during unmanned
mode and displays again manned
mode.
M
A1
U/M
A2
S
RS 232 / 485 Convertor
This is a universal convertor for conver ting RS 232 serial
por t to RS 485 serial port or vice versa. It operates on 2 30
AC supply and is to be used with Minilec make
interconnecting cables for Minilec annunciators & for PC.
Electronic / Industrial Hooter
Electronic Hooters w ith tone & volume c ontrol are supplied. Suitable for
AC or DC supply Standard 96 x 9 6 enclosure.
OPTIONAL ACCESSORIES
ANNUNCIATOR PANELS
60
Often Alarm Annunciators are required to be housed in a suitablecubical and many tim es such control panel consists of only Alarm Annunciators.Minilec offers Alarm Annu nciators along with contro l panels. This includes design ofcontrol panel, fabrication, painting, assembly of Alarm Ann unciators and assistanceduring installation and c omm issioning.Retrofitting work by replacing old annunciation system with latest design and forexpansion in power stations, substations, process plants as also standardAnnunciation Panels for plants and equipments c an be catered to.
The Minilec Panel Advantages Complete in-house design, assembly
of Annunci ator Panels.
Sof tware capabi li ty for automisat ionto meet project specification s.
Component layout as per standards &safety requirements.
Powder coa ted MS or A luminum RackPanels with quality panel wiring.