Microsoft Word - EEPB383 Final Sem 2 1112 With Solution (1)
-
Upload
muhammad-hafiz -
Category
Documents
-
view
237 -
download
4
Transcript of Microsoft Word - EEPB383 Final Sem 2 1112 With Solution (1)
EEPB383, Semester2 2011/2012
Page 1 of 17
COLLEGE OF ENGINEERING
PUTRAJAYA CAMPUS
FINAL EXAMINATION
SEMESTER 2 2011 / 2012
PROGRAMME : Bachelor of Electrical Power Engineering (Honours) SUBJECT CODE : EEPB 383 SUBJECT : Electrical Power System II DATE : December 2011 TIME : 2 ½ hours
INSTRUCTIONS TO CANDIDATES:
1. This paper contains FIVE (5) questions in SEVEN (7) pages.
2. Answer ALL questions.
THIS QUESTION PAPER CONSISTS OF 7 PRINTED PAGES INCLUDING THIS
COVER PAGE.
EEPB383, Semester2 2011/2012
Page 2 of 17
QUESTION 1 [15 MARKS] The 9 – bus power system network of an electric utility company is shown in the Figure 1
below. Plant 3 and 5 are shut-down for maintenance leaving plant 1, 2 and 7 generating
power to feed the loads at each of the buses shown in the Figure 1. The production costs for
plant 1, 2 and 7 in $/h is given as follows:
2111 009076240 PPC .. ++=
2222 005016220 PPC .. ++=
2777 008056240 PPC .. ++=
where P1, P2 and P7 are in MW.
Figure 1
Without considering power losses in network, answer the following questions.
a) Find the incremental costs for power plant 1, 2 and 7 in terms of its power generated.
[3 marks]
b) Assuming all three power plants 1, 2 and 7 generate within its power generation limits;
determine the optimum dispatch of generation. [8 marks]
c) If the power generation limit for plant no.1 is between 80 MW and 300 MW, determine
the new optimum dispatch of generation. [4 marks]
EEPB383, Semester2 2011/2012
Page 3 of 17
QUESTION 2 [15 MARKS]
a) Draw the equivalent circuit for sub-transient period of a synchronous generator. Label all
components of the circuit. [5 marks]
b) A 100-MVA, 20-kV synchronous generator is connected through a transmission line to a
100-MVA, 20-kV synchronous motor. The per unit transient reactances of the generator
and motor are 0.25 and 0.20, respectively. The line reactance on the base of 100 MVA is
0.1 per unit. The motor is taking 50 MW at 0.8 power factor leading at a terminal voltage
of 20 kV. A three-phase short circuit occurs at the generator terminals. Determine the
transient currents in each of the two machines and in the short circuit. [10 marks]
QUESTION 3 [25 MARKS]
12
3
G1G2
T1T2
4
CB1 CB2
Figure 2
EEPB383, Semester2 2011/2012
Page 4 of 17
A 4-bus power system network above is represented as a Thevenin equivalent network in
terms of its impedance values. Detailed values are as follows (all values are in pu):
Item Base MVA Voltage
Rating X0 X1 X2
G1 100 20kV j0.08 j0.25 j0.25
G2 100 20kV j0.07 j0.2 j0.2
T1 100 20/275kV j0.09 j0.1 j0.1
T2 100 20/275kV j0.09 j0.1 j0.1
L12 100 275kV j0.4 j0.12 j0.12
L13 100 275kV j0.6 j0.14 j0.14
L23 100 275kV j0.7 j0.16 j0.16
L34 100 275kV j0.8 j0.18 j0.18
The neutral for each generator is connected to ground via a current limiting reactor of j0.3 per
unit. The Generators are operating at no-load, producing voltages at rated values at a
frequency of 50 Hz. The system voltages are at rated values. All values are expressed in per
unit on a common 100 MVA base. Circuit Breaker 1 (CB1) and Circuit Breaker 2 (CB2) are
in the OPEN position. A bolted 3 phase to ground fault occurred at Bus 4. Please do the
following:
a) Determine the Admittance Matrix [2 marks]
b) Calculate the fault current at Bus 4 in per unit [4 marks]
c) Determine the voltages at Bus 1, Bus 2, Bus 3 and Bus 4 during fault
[10 marks]
d) Calculate the fault current flowing in line 2 – 3, 1 – 3 and 3-4 [6 marks]
e) A tree falls down and shorts all 3 phases in a transmission line to ground. Is this a
bolted or non-bolted fault? Explain why? [3 marks]
EEPB383, Semester2 2011/2012
Page 5 of 17
QUESTION 4 [25 MARKS]
Refer to the power system shown in Figure 3 and the parameters given.
Figure 3
Generators G1 and G2: 1.021 jXX == p.u; 05.00jX = p.u; Voltage: 11 kV
Transformers T1 and T2: 15.0021 jXXX === p.u; Voltage: 11/275 kV
Line: 05.021jZZ == p.u, 1.00
jZ = p.u ; Voltage: 275 kV
All per unit values are on a base of 100 MVA, and pre-fault voltage is 1.0 per unit.
a) Draw the positive, negative and zero sequence impedance networks for the power system.
State in your drawing the numerical values of all the impedance. [2 + 2 + 2 marks]
b) Determine the fault current in per unit for a bolted single –line-ground fault at bus B.
[4 marks]
c) Determine the current in per unit flowing in the faulted phase of the overhead line for a
bolted single-line-ground fault at busbar B. [10 marks]
d) Determine the current flowing in the neutral of T1 and T2 for a single-line-ground fault at
bus B given the fault impedance is j0.5 per unit. [5 marks]
EEPB383, Semester2 2011/2012
Page 6 of 17
QUESTION 5 [20 MARKS]
Figure 3
A 50Hz, H = 5MJ/MVA generator is connected through parallel transmission lines to a grid
system. The machine is delivering 1.0pu power and both the terminal voltage and the
infinite-bus are 1.0pu. The values of the reactance on a common system base are given as in
the diagram. The transient reactance of the generator is 0.20pu as indicated.
Determine:
a) The power-angle equation during steady state condition. [15marks]
b) Find the initial operating angle. [2marks]
c) A temporary fault occurs at a distance of 20% of the line length away from the
sending end terminal of the line. When the fault is cleared by an auto-reclose
protection, both lines are intact. Determine the critical clearing angle and the critical
fault clearing time. [3marks]
END OF QUESTION PAPER
EEPB383, Semester2 2011/2012
Page 7 of 17
Formula Sheet
∑=
−=
n
i i
iDP
1 2γ
βλ;
∑
∑
=
=
+
=n
i i
n
i i
iDP
1
1
2
1
2
γ
γ
β
λ
02
2
0
=∆+∆
+∆
δδδ
π SPdt
dD
dt
d
f
H
em PPdt
d
f
H−=
2
2
0
δ
π
( )θωξ
δδδ ξω +
−
∆+= −
te dtn sin
1 2
00
te dtn n ω
ξ
δωωω ξω sin
1 2
00
−
−
∆−=
SHP
fD 0
2
πξ =
Sn PH
f0πω =
21 ξωω −= nd ξθ 1cos−=
f
aaaa
ZZZZ
EIII
3021
210
+++=== : Single line to ground fault
f
aaa
ZZZ
EII
++=−=
21
21 : Line-Line fault
f
aaa
ZZ
IZEI
30
110
+
−−= : Double Line to Ground Fault
2
112
Z
IZEI aa
a
−−= : Double Line to Ground Fault
EEPB383, Semester2 2011/2012
Page 8 of 17
f
f
ZZZ
ZZZ
aa
Z
EI
3
31
1
02
02
++
+
+
= : Double Line to Ground Fault
=
2
1
0
2
2
1
1
111
a
a
a
c
b
a
V
V
V
aa
aa
V
V
V
( ) add t
dd
t
dd
t
dd
asy eX
Et
Xe
XXe
XXEti
τττ δδω −−− ++
+
−+
−= sin2sin
111112)(
''0
''''0
'''
B
puS
SS = ,
B
puV
VV = ,
B
puI
II = ,
B
puZ
ZZ = ,
( )
B
BB
S
VZ
2
= , B
BB
V
SI
3=
kk
B
X
SSCC =
2
=
newB
oldB
oldB
newBold
punewpu
V
V
S
SZZ
EEPB383, Semester2 2011/2012
Page 9 of 17
Solution
Question 1[15 marks] a)
11
11 018.07.6 P
dP
dC+==λ $/MWh
22
22 010.01.6 P
dP
dC+==λ $/MWh
77
77 016.05.6 P
dP
dC+==λ $/MWh
b) Neglecting losses, total power demand,
MW
PPPPPD
345
100801060401025200
...... 9321
=
++++++++=
++++=
∑
∑
=
=
+
=
7,2,1
7,2,1
2
1
2
i i
i i
iDP
γ
γ
β
λ =
)008.0(2
1
)005.0(2
1
)009.0(2
1
)008.0(2
5.6
)005.0(2
1.6
)009.0(2
7.6345
++
+++
= 7.95 $/MWh
Solve for P based on optimal dispatch,
95.7018.07.6 1 =+ P
44.691 =P MW
95.7010.01.6 2 =+ P
1852 =P MW
95.7010.05.6 7 =+ P
625.907 =P MW
c)
Set 801 =P MW, optimise 2P and 7P
EEPB383, Semester2 2011/2012
Page 10 of 17
)008.0(2
1
)005.0(2
1
)008.0(2
5.6
)005.0(2
1.680345
+
++−
=λ = 7.885 $/MWh
885.7010.01.6 2 =+ P
5.1782 =P MW
885.7010.05.6 7 =+ P
56.867 =P MW
Total = 80+178.5 + 86.56 = 345 MW
Questions 2 [15 marks] a)
Xl : leakage reactance
Xad : reactance due to armature reaction
Xf : reactance due to filed winding
b)
50 36.870.625 36.87 .
0.8 100mS p u
∠ − °= = ∠ − °
×
[1 mark]
201 0 .
20mV p u= = ∠ °
[1 mark]
Before the fault,
* 000.625 36.87
0.625 36.87 .1
mm
m
SI p u
V
∠= = = ∠
[1 mark]
EEPB383, Semester2 2011/2012
Page 11 of 17
Generator emf behind transient reactance is,
' '( ) 1 0 (0.25 0.1)*0.625 36.87 0.8688 0.175 0.8862 11.39 .g m dg l m
E V j X X I j j p u= + + = ∠ + + ∠ ° = + = ∠ °
[2 marks]
Motor emf behind transient reactance is,
' '( ) 1 0 (0.2)*0.625 36.87 1.075 0.10 1.0796 5.32 .m m dm m
E V j X I j j p u= − = ∠ − ∠ ° = − = ∠ − °
[2 marks]
During fault, the generator short circuit current is,
' 0'
'
0.8862 11.393.545 78.61 .
( ) 0.25
g
g
dg
EI p u
j X j
∠= = = ∠ − °
[1 mark]
During fault, the motor short circuit current is,
' 0'
'
1.0796 5.323.5988 95.32 .
( ) 0.30m
m
dm l
EI p u
j X X j
∠ −= = = ∠ − °
+
[1 mark]
The short circuit current is
' ' ' 3.545 78.61 3.5988 95.32 7.0679 87.03 .f g m
I I I p u= + = ∠ − ° + ∠ − ° = ∠ − °
Questions 3 [25 marks]
a) Determine the Admittance Matrix [2 marks]
Converting to Admittance values Item X1 Y1
G1 j0.25 -j4
G2 j0.2 -j5
T1 j0.1 -j10
T2 j0.1 -j10
L12 j0.12 -j8.333
L13 j0.14 -j7.143
L23 j0.16 -j6.25
L34 j0.18 -j5.556
EEPB383, Semester2 2011/2012
Page 12 of 17
b) Calculate the fault current at Bus 4 in per unit [4 marks]
Calculating Z44: Item X1
G1 j0.25
G2 j0.2
T1 j0.1
T2 j0.1
L12 j0.12
L13 j0.14
L23 j0.16
L34 j0.18
Calculating Fault Current at Bus 4
c) Determine the voltages at Bus 1, Bus 2, Bus 3 and Bus 4 during fault [10
marks]
EEPB383, Semester2 2011/2012
Page 13 of 17
d) Calculate the fault current flowing in line 2 – 3, 1 – 3 and 3-4 [6 marks]
e) A tree falls down and shorts all 3 phases in a transmission line to ground. Is this a
bolted or non-bolted fault?. Explain why? [3 marks]
It is a non-Bolted Fault because the tree has impedance.
Question 4[25 marks] a)
Positive sequence network
Negative sequence network
EEPB383, Semester2 2011/2012
Page 14 of 17
Zero sequence network
b)
fBBB
aaaa
ZZZZ
EIII
3021
210
+++===
)1.015.0//()05.015.01.0(1jjjjjZB +++= = j0.1364
12BB ZZ = = j0.1364
)15.0//()1.015.0(0jjjZB += = j0.09375
009375.01364.01364.0
0.1210
+++===
jjjIII aaa = -j2.728 .pu
1844.83)( 0jIFI aB −== p.u
c) Positive sequence voltage at buses A and B,
)55.0
25.0)((*)15.01.0( 11
FIjjV BA +=∆ = 4545.0*728.2*25.0 jj = -0.31
111 )0()( AAA VVFV ∆+= = 1.0 – 0.31 = 0.69 p.u
)55.0
25.0)((*)05.015.01.0( 11
FIjjjV BB ++=∆ = -0.372
EEPB383, Semester2 2011/2012
Page 15 of 17
111 )0()( BBB VVFV ∆+= = 1.0 – 0.372 = 0.628 p.u
Negative sequence voltage buses A and B,
222 )0()( AAA VVFV ∆+= = 0.0 – 0.31 = - 0.31
222 )0()( BBB VVFV ∆+= = 0.0 – 0.372 = -0.372
Zero sequence voltage buses A and B,
)55.0
25.0)((*)15.0( 00
FIjV BA =∆ = - 0.186
000 )0()( AAA VVFV ∆+= = 0.0 – 0.186 = -0.186 p.u
)55.0
25.0)((*)1.015.0( 00
FIjjV BB +=∆ = - 0.31 p.u
000 )0()( BBB VVFV ∆+= = 0.0 – 0.31 = -0.31 p.u
−
−
−
=
2
22
1
11
0
00
012
)()(
)()(
)()(
AB
BA
AB
BA
AB
BA
AB
z
FVFV
z
FVFV
z
FVFV
I =
−−−
−
−−−
05.0
)372.0(31.005.0
628.069.01.0
)31.0(186.0
j
j
j
=
−
−
−
24.1
24.1
24.1
j
j
j
p.u
EEPB383, Semester2 2011/2012
Page 16 of 17
)()( 012FAIFI AB
abcAB = =
−
−
−
24.1
24.1
24.1
1
1
111
2
2
j
j
j
aa
aa
)24.1(3 jIaAB −= = -j3.72 p.u
°+°−∠+°+−∠+°−∠= 1209024.12409024.19024.1bABI = 0.0 p.u
°+°−∠+°+−∠+°−∠= 2409024.11209024.19024.1cABI = 0.0 p.u
Question 5[20 marks]
At infinite node H = α The reactance between 1 and 3, X = j(0.1+ 0.5/2) = j0.35pu Output power of generator Power angle equation:
, which is equivalent to Vt angle relative to the infinite bus
The terminal voltage: Vt = 1∠20.5° pu = 0.94 + j0.35pu The output current of the generator:
The transient internal voltage:
1mar
2mar
1mar
2mar
2mar
EEPB383, Semester2 2011/2012
Page 17 of 17
The total series resistance:
The power angle equation relating E’ and V:
b) & c) The initial operating angle is given by:
Since both lines are intact when the fault is cleared, the power-angle equation before and after the fault remains the same:
2mar
1mar
2mar
2mar
2mar
1mar