Micronik Application

download Micronik Application

of 81

Transcript of Micronik Application

  • 8/9/2019 Micronik Application

    1/81

    Honeywell

    MicroniK 200Application

  • 8/9/2019 Micronik Application

    2/81

    HONEYWELL MICRONIK 200 APPLICATION

    1 EN3C-0161 0698R0-MA

    CONTROLLER APPLICATION OVERVIEW

    GENERAL

    CONTROL OF HOT WATER HEATING COIL OR CHILLED WATER COOLING COIL

    FOR FULL OUTSIDE AIR PLANTS

    CONTROL OF HOT WATER HEATING COIL OR CHILLED WATER COOLING COIL

    IN RECIRCULATION AIR VENTILATION SYSTEMS

    SEQUENCE CONTROL OF AN ENERGY RECOVERY SYSTEM WITH

    A HOT WATER HEATING COIL

    SEQUENCECONTROL OF AN ENERGY RECOVERY SYSTEM WITH

    A CHILLED WATER COOLING COIL

    SEQUENCE CONTROL OF HOT WATER HEATING COIL AND CHILLED WATER

    COOLING COIL AND TWO POSITION (OPEN/CLOSED) DAMPER CONTROL

    SEQUENCE CONTROL OF ENERGY RECOVERY SYSTEM, HOT WATER HEATING

    AND CHILLED WATER COOLING COILS

    SEQUENCE CONTROL OF MIXED AIR DAMPERS AND HOT WATER HEATING COIL

    SEQUENCE CONTROL OF MIXED AIR DAMPERS AND CHILLED WATER COOLING COIL

    SEQUENCE CONTROL OF MIXED AIR DAMPERS, HOT WATER AND

    CHILLED WATER VALVES

    CONTROL OF ELECTRIC AIR HEATER BATTERY OR DIRECT EXPANSION

    COOLING SYSTEM (UP TO 6-STAGES/STEPS)

    SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

    SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER

    COOLING COIL AND TWO POSITION (OPEN/CLOSE) DAMPER CONTROL

    SEQUENCE CONTROL OF ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

    SEQUENCE CONTROL OF ENERGY RECOVERY SYSTEM, ELECTRIC AIR HEATER AND

    CHILLED WATER COOLING COIL

    SEQUENCE CONTROL OF ENERGY RECOVERY SYSTEM, ELECTRIC AIR HEATER AND

    CHILLED WATER COOLING COIL

    SEQUENCE CONTROL OF MIXED AIR DAMPERS, ELECTRIC AIR HEATER AND

    CHILLED WATER COOLING COIL

  • 8/9/2019 Micronik Application

    3/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA 2

    R1 ROOM/CONTROL WITH LOW LIMIT DISCHARGE AIR TEMPERATURE CONTROL OR ROOM/RETURN

    AIR DISCHARGE AIR TEMPERATURE CASCADE CONTROL OF A HOT WATER HEATING COIL OR

    CHILLED WATER COOLING COIL FOR FULL OUTSIDE AIR PLANTS

    R1-1

    R2 ROOM/CONTROL OF HOT WATER HEATING COIL OR CHILLED WATER COOLING COIL IN

    RECIRCULATION AIR VENTILATION SYSTEMS

    R2-1

    R3 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF AN

    ENERGY RECOVERY SYSTEM WITH A HOT WATER HEATING COIL

    R3-1

    R4 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF

    AN ENERGY RECOVERY SYSTEM WITH A CHILLED WATER COOLING COIL

    R4-1

    R5 ROOM/DISCHARGE AIR CASCADE SEQUENCE CONTROL OF HOT WATER HEATING COIL AND

    CHILLED WATER COOLING COIL AND TWO POSITION (OPEN/CLOSED) DAMPER CONTROL

    R5-1

    R6 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ENERGY RECOVERYSYSTEM, HOT WATER HEATING AND CHILLED WATER COOLING COILS

    R6-1

    R7 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS

    AND HOT WATER HEATING COIL

    R7-1

    R8 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS

    AND CHILLED WATER COOLING COIL

    R8-1

    R9 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS,

    HOT WATER AND CHILLED WATER VALVES

    R9-1

    R10 ROOM/CONTROL WITH LOW LIMIT DISCHARGE AIR TEMPERATURE CONTROL OR ROOM/RETURN

    AIR - DISCHARGE AIR TEMPERATURE CASCADE CONTROL OF ELECTRIC AIR HEATER BATTERYOR DIRECT EXPANSION COOLING SYSTEM (UP TO 6-STAGES/STEPS)

    R10-1

    R11 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR

    HEATER AND CHILLED WATER COOLING COIL

    R11-1

    R12 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR

    HEATER AND CHILLED WATER COOLING COIL AND TWO POSITION (OPEN/CLOSE) DAMPER

    CONTROL

    R12-1

    R13 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ELECTRIC AIR

    HEATER AND CHILLED WATER COOLING COIL

    R13-1

    R14 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ENERGY RECOVERYSYSTEM, ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

    R14-1

    R15 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF ENERGY RECOVERY

    SYSTEM, ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

    R15-1

    R16 ROOM/DISCHARGE AIR TEMPERATURE CASCADE SEQUENCE CONTROL OF MIXED AIR DAMPERS,

    ELECTRIC AIR HEATER AND CHILLED WATER COOLING COIL

    R16-1

  • 8/9/2019 Micronik Application

    4/81

    HONEYWELL MICRONIK 200 APPLICATION

    3 EN3C-0161 0698R0-MA

    W1 OUTSIDE AIR TEMPERATURE COMPENSATED SUPPLY WATER FLOW TEMPERATURE CONTROL W1-1

    W2 OUTSIDE AIR TEMPERATURE COMPENSATED HOT WATER FLOW TEMPERATURE CONTROL

    WITH HIGH OR LOW LIMIT RETURN FLOW TEMPERATURE CONTROL

    W2-1

    W3 ROOM TEMPERATURE - SUPPLY HOT WATER TEMPERATURE CASCADE CONTROL W3-1

    The R7426A controller provides one output with one mode of operation, heating or cooling, and is suitable for the followingapplications:

    Space or return air temperature control

    Discharge air temperature control

    Space or return air temperature control with low limit discharge air temperature control

    Cascade control of space or return air and discharge air temperature

    Cascade control of space air and supply water temperature

    Outside air compensated supply water temperature control with or without low or high limit return watertemperature control

    Constant supply water temperature control with or without return water temperature limit control

    The R7426B,C controllers provide three outputs for sequence control of heating, mixed air dampers or energy recoverysystems and cooling and are suitable for the following applications:

    Space or return air temperature control

    Discharge air temperature control

    Cascade control of space or return air and discharge air temperature

    Additional control function:

    Compensation by outside air temperature of main setpoint, e.g. compensated space, return or discharge airtemperature

  • 8/9/2019 Micronik Application

    5/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA 4

    Remote Control Point Adjustment (CPA).The controller control point can be remotely adjusted through a range of 5K usinga control point adjustment potentiometer in discharge air applications or a room sensor with control point adjustment

    potentiometer in room control applications connected to terminals 2&4. The configuration parameter C.05 (CPATYP) has to beset to 1, 2 or 4 in accordance to the used potentiometer resistance range.

    Remote Setpoint Adjustment (RSA).The controller setpoint can be remotely adjusted through a range of 15...30C using aroom sensor with setpoint adjustment potentiometer connected to terminals 2&4. The configuration parameter C.05 (CPATYP)has to be set to 3.

    Comfort/Standby Mode.The controllers provide occupied and unoccupied temperature setpoints. Connecting a roomtemperature sensor with occupied/unoccupied switch or a presence sensor to the controller occupancy input terminals 1&4allows to change the controller into Comfort (closed contact) or Standby (open contact) mode.

    Summer/Winter Compensation.When an outside air temperature sensor (T3) is connected to terminals 7&8 winter and/orsummer compensation of the main setpoint can be performed.

    Summer/Winter Changeover.The occupancy input, terminals 1&4 on the R7426A controllers can alternatively be used toswitch the controller between summer (cooling) and winter (heating) operation in applications using a common valve for heatingand cooling control. In summer operation the controller provides a direct acting output (Y1), with an increase in the controlledvariable, i. e. room temperature increases, the output increases. In winter operation the controller output (Y1) is reverse acting,with a decrease in the controlled variable the output increases. Summer/Winter changeover function is activated by setting theconfiguration parameter C.15 (Y1CTRF) to 2. A potential free contact or strap-on thermostat connected to terminals 1&4 isused to switch the controller mode to cooling (contact closed) or heating (contact open) control.

    Controller ON/OFF Operating Mode.Connecting an external time clock or manual switch to the controller Plant/SystemON/OFF input terminals 9&10, the controller can be switched ON or OFF. In the OFF operating mode the controllerautomatically generates zero position output signals on all outputs to drive the valve and damper actuators into the fully closedposition. In mixed air damper applications the outdoor and exhaust air dampers are closed and the return air damper is fullyopen. The time clock also switches the fan(s) OFF and drives the damper actuators (6) in full outside air applications into theclosed position by an external installed relay, if the dampers are not controlled by the controller. In full outside air applicationsthe fan(s) switch ON after a time delay to allow the dampers time to open.

    NOTE: For Terminals 9&10 see the following Figure

    Day/Night Setpoint Operation.An external time clock connected to the controller occupancy input terminals 1&4 providesday/night main temperature setpoint control determined by the programmed offset parameter value P.16 (SOFFS) for thoseheating or ventilation systems operating 24 hour per day.

    Safe Operation of Electric Heater Battery.The high limit thermostat (7) installed close to the electric heater battery switchesthe electric air heater OFF at temperatures above its adjustable setpoint.The air flow switch (10) also switches the electric heater battery OFF in the event of fan failure (no air flow). Alternatively, thedifferential air pressure switch (9) across the discharge air fan can be used for the same function.

    Filter Monitoring. The differential air pressure switch (8) closes a contact to issue an alarm at a differential pressure above itsadjustable setpoint to indicate that the filter is dirty and in need of maintenance.

    Fan Monitoring.The differential air pressure switch (9) switches the fan motor OFF at a differential pressure below itsadjustable setpoint to indicate no air flow. An external time delay relay overrides the fan monitoring function for a short periodduring start-up to avoid false alarms. The monitoring function is re-established after the adjustable time delay period.

    Plant /System

    9

    10

    ON/OFF

    without Real Time Clock

  • 8/9/2019 Micronik Application

    6/81

    HONEYWELL MICRONIK 200 APPLICATION

    5 EN3C-0161 0698R0-MA

    See functional diagram and wiring connections of option 1 for electric heating.

    25 65 70 100 %30

    off

    on

    Step1 on

    Step2 onPower

    out2out1

    Y1

    R7426A

    Y1

    20 21 22

    open/OUT2

    close/OUT1

    24V

    ~

    2 1Stage

    24Vac Relays

    off

    25 7570 100 %20 5045

    Step1 on

    Step2 on

    Step3 on

    on

    Power

    Y1

    out2out1

    R7426A

    Y1

    20 21 22

    open/OUT2

    close/OUT1

    24V

    ~

    2 1Stage

    24Vac Relays

    3

    The diagram shows as example, 60% Output Signal withMotor RuntimeY1set to 50 sec:

    30 50 70 80 100 secY1

    off

    onout1/out2

    R7426A

    Y1

    20 21 22

    open/OUT2

    close/OUT1

    24V

    ~

    A2

    RN1L40M25

    A1

    Solid State Relay

    L2L1

    100...440Vac

    Note:OUT1 or OUT2or both can beused to driveSolid State Relays

  • 8/9/2019 Micronik Application

    7/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA 6

    25 65 70 100 %30

    off

    on

    Step1 on

    Step2 onPower

    out2out1

    Y3

    R7426B

    Y3

    26 27 28

    open/OUT2

    close/OUT1

    24V

    ~

    2 1Stage

    24Vac Relays

    off

    25 7570 100 %20 5045

    Step1 on

    Step2 on

    Step3 on

    on

    Power

    Y3

    out2out1

    R7426B

    Y3

    26 27 28

    open/OUT2

    close/OUT1

    24V

    ~

    2 1Stage

    24Vac Relays

    3

    The diagram shows as example, 60% Output Signal withMotor RuntimeY3set to 50 sec:

    30 50 70 80 100 secY3

    off

    onout1/out2

    R7426B

    Y3

    26 27 28

    open/OUT2

    close/OUT1

    24V~

    A2

    RN1L40M25

    A1

    Solid State Relay

    L2L1

    100...440Vac

    Note:OUT1 or OUT2or both can beused to driveSolid State Relays

  • 8/9/2019 Micronik Application

    8/81

    HONEYWELL MICRONIK 200 APPLICATION

    7 EN3C-0161 0698R0-MA

    4-stage On/Off sequence control of cooling (Output Y1 & Y3) and 2-stage On/off sequence control of electric heating (OutputY2). The wiring connections are the same as shown in application example no. 10.

    4-stage On/Off sequence control of cooling (Output Y1 & Y3) and modulating control of heating valve. The wiring connectionsare the same as shown in application example no. 11.

    25 65 70 100 %30

    off

    on

    Step1 on

    Step2 onPower

    out2out1

    Y3

    R7426B

    Y2

    23 24 25

    open/OUT2

    close/OUT1

    24V

    ~

    2 1Stage

    24Vac Relays

  • 8/9/2019 Micronik Application

    9/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA 8

    1

    2

    3

    4

    5

    6

    7

    8

    12

    T

    MicroniK 200Controller

    T

    Freeze Protection orHigh Limit Thermostat inElektric HeatingApplications

    T

    Duct Temperature SensororOutside Air Sensor,Duct Mounting

    T Room Air Sensor

    TOutdoor Air Sensor,Wall Mounting

    Immersion TemperatureSensor

    Remote SetpointAdjustment Potentiometer

    TRoom Air Sensorwith Remote SetpointAdjustment

    T

    9

    Room withe. g. Room Air SensorandRemote SetpointAdjustment Potentiometer

    10

    11

    Supply Air FanorReturn Air Fan

    13

    14

    15

    Cooling Coil

    Recirculation Pump

    16

    A

    B

    AB

    Valve/Actuator3 - Way

    17

    18

    Valve/Actuator2 - Way

    19

    20

    Electric Heater

    24Vac/230Vac RelaysorSolid State Relay(Electric Current Valve)

    21

    Heating Coil

    Energy Recovery Coil

    22

    23

    Differential PressureSwitch

    p

    VAir Flow Switch

    Filter

    Radiator

    M MDamper Actuator

    AB

    A

    NOTE: Connections shown with dotted lines are options.

  • 8/9/2019 Micronik Application

    10/81

    HONEYWELL MICRONIK 200 APPLICATION

    D1-1 EN3C-0161 0698R0-MA

    A heating and ventilation system with constant discharge air temperature control is used where the base heating load is met byradiators and the ventilation system provides the supply of fresh outside air.

    In cooling applications it is also used to supply fresh outside air using a constant supply air temperature control system.

    EA

    0A

    M

    p

    p

    T

    p

    M6

    63

    9

    17

    9

    4

    T

    8

    11

    5

    T

    Y1

    Temperature Control.The discharge air temperature sensor (1) measures theactual value and the controller (4) compares this value with the desiredsetpoint. If a deviation between the two values exists, the controller generates a3-position control signal to reposition the valve (5) to maintain the desireddischarge air temperature. In heating applications the controller output isreverse acting and direct acting for cooling applications.

    Freeze Protection.The freeze protection thermostat (7) switches the heatingcoil pump ON - if OFF - at temperatures below its adjustable setpoint. In parallelit provides a digital input signal to the controller (4) to switch the fan(s) OFF andclose the dampers by an external installed relay logic and fully open the heatingvalve (5) to prevent the heating coil from freezing.

    Time Control.Depending on the programmed time schedule of the internalcontroller real time clock the different operating control modes Comfort,Standby, Night or OFF are selected. In the OFF operating mode the controllerautomatically fully closes the heating valve (5), switches the fan(s) OFF andthereby closes the dampers (6) by an external installed relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damperactuators can be used to start the fan.

    Y1 (%)

    100

    0

    Cooling

    Heating0

    CTRP1

    YstartXp

    T1

    X w

  • 8/9/2019 Micronik Application

    11/81

  • 8/9/2019 Micronik Application

    12/81

    HONEYWELL MICRONIK 200 APPLICATION

    D2-1 EN3C-0161 0698R0-MA

    Recirculation air systems with outside air compensated discharge air temperature control are used for ventilation in factories,storage areas, department stores, etc. or for ventilation of machinery such as computers.

    T

    1

    4

    5

    11

    Y1

    3T

    Temperature Control.The discharge air temperature sensor (1) measuresthe actual value and the controller (4) compares this value with the actualcontrol point. The control point comprises the setpoint value which iscontinuously compensated by the outside air temperature sensor (3) value.If a deviation between the two values exists, the controller (4) generates a3-position control signal to reposition the valve (5) to maintain the desireddischarge air temperature. In heating applications the controller output isreverse acting and direct acting for cooling applications.

    Time Control.Depending on the programmed time schedule of the internalcontroller real time clock the different operating control modes Comfort,Standby, Night or OFF are selected. In the OFF operating mode thecontroller automatically fully closes the heating valve (5) and switches the fan

    OFF.If the controller switches from OFF to ON mode the Plant/System On/Offoutput switches the fan ON and the controller provides automatic control.

    Y1 (%)

    100

    0

    Cooling

    Heating0

    CTRP1Ystart

    Xp

    T1

    X w

  • 8/9/2019 Micronik Application

    13/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D2-2

    Trans-former

    5 ML6420A Heating orCooling

    1 2

    2 1

    24V

    24V

    24Vac

    230Vac

    3 - Way Valve

    2 - Way Valve

    11 T7411B

    1 T7411A/T7416A

    1 23 T7416A

    15 16 17

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    Y1

    close/OUT1

    24V

    24V

    4 R7426A

    1 2

    4 6

    Item Quantity Part Number Description1 1 T7411A1001 or

    T7411A1019Duct Temperature Sensor 135mm length or

    300mm length

    3 1 T7416A1006 Outside Air Temperature Sensor, Wall Mounting

    4 1 R7426A1016 orR7426A1008

    Temperature Controller with clock orwithout clock

    5 1 ML6420A3007 andV5.....A.....

    Valve Actuator andValve

    Item Quantity Part Number Description11 1 T7411B1057 or

    43182690-001Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    14/81

    HONEYWELL MICRONIK 200 APPLICATION

    D3-1 EN3C-0161 0698R0-MA

    For use with ventilation systems comprising of an energy (heat) recovery system and a heating coil.

    EA

    0A

    T T

    p3 17

    p

    p

    9

    9

    4

    T

    8 5a

    6

    6

    M

    M

    5b

    p10

    11

    Y3

    Y1

    Temperature Control.The discharge air temperature sensor

    (1) measures the actual value and the controller (4) comparesthis value with the desired setpoint. If a deviation between thetwo values exists, the controller generates a 3-position controlsignal on output Y1or Y3 to reposition either the energyrecovery valve (5b) or the heating valve (5a) in sequence tomaintain the desired discharge air temperature.In an air-glycol-air heat recovery system it is important, to avoidicing of the exhaust air coil. This is achieved by the differentialpressure switch (10). If the differential pressure switchindicates icing of the coil, the control valve (5b) will be closedby an additional field mounted relay. Return air and warm waterwill be circulated through the exhaust air heat recovery coil tomelt the ice deposits.

    Freeze Protection.The freeze protection thermostat (7)switches the heating coil pump ON, - if OFF - at temperatures below its adjustable setpoint. In parallel it provides a digital inputsignal to the controller (4) to fully open the heating valve (5a), to switch OFF the fan(s) and close the dampers (6) by anexternal installed relay logic to protect the heating coil from freezing.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damperactuators can be used to start the fan.

    Heating Y3

    Y (%)

    1/4 Xp

    0

    100

    Y1

    0 00 Xwh/Xw

    T1

    CTRP1CTRPH

    XpH Xp

    EnergyRecovery

  • 8/9/2019 Micronik Application

    15/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D3-2

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    XWrh

    24V 24V 24V

    11 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    NC C7 T6046A

    4 R7426B

    Trans-former

    5b ML6420A Energy Recovery

    24Vac

    230Vac

    1 2

    2 1

    24V

    24V

    3 - Way Valve

    2 - Way Valve1 2

    2 1

    24V

    24V

    3 - Way Valve

    2 - Way Valve

    5a ML6420A Heating Valve

    24V

    Y1 Y2 Y3

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5a+5b 2 ML6420A3007 andV5....A....

    Valve Actuator andValve

    6 2 ML6184E1009 orML6684E1008

    Damper Actuator 24Vac, 17Nm or230Vac, 17Nm

    7 1 T6046A1006 orFT015 or FTB015 Freeze Protection Thermostat

    8+9+10 4 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    16/81

    HONEYWELL MICRONIK 200 APPLICATION

    D4-1 EN3C-0161 0698R0-MA

    For use with ventilation systems comprising of an energy (heat/cool) recovery system and a cooling coil.

    EA

    0A

    T

    p 1p

    p

    9

    9

    4

    8

    6

    6

    M

    M

    5b

    p10

    11

    T

    35a

    Y2

    Y1

    Temperature Control.The discharge air temperature sensor

    (1) measures the actual value and the controller (4)compares this value with the desired setpoint. If a deviationbetween the two values exists, the controller generates a3-position control signal on output Y1 or Y2 to repositioneither the energy recovery valve (5b) or the cooling valve (5a)in sequence to maintain the desired discharge airtemperature.If the actual temperature is below the setpoint, the controllermodulates via output Y1 the heat recovery valve (5b) into theopen position.If the actual temperature exceeds the setpoint by more than25% of the throttling range (Xp1) - dead band betweenheating and cooling - the controller starts to open the energyrecovery valve (5b) to reclaim cooling energy. If thetemperature continues to increase and the energy recovery

    valve is fully open, the controller (4) generates an output signal via Y2 to open the cooling coil valve (5b).In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differentialpressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5b) will be closed by anadditional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt theice deposits.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damperactuators can be used to start the fan.

    Y (%)

    0

    MINPOS

    100

    Y1

    0 00 Xwc/Xw

    T1

    CTRPCCTRP1

    Xp XpC

    Y2Cooling

    EnergyRecovery

  • 8/9/2019 Micronik Application

    17/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D4-2

    11 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    Trans-former

    24Vac

    230Vac

    5b ML6420A Energy Recovery 1 2

    2 1

    24V

    24V

    2 - Way Valve

    3 - Way Valve

    5a ML6420A Cooling Valve 1 2

    2 1

    24V

    24V

    3 - Way Valve

    2 - Way Valve

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    24V 24V 24V

    Y1 Y2 Y3

    XWrh

    4 R7426B

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5a+5b 2 ML6420A3007 andV5....A....

    Valve Actuator andValve

    6 2 ML6184E1009 orML6684E1008

    Damper Actuator 24Vac, 17Nm or230Vac, 17Nm

    8+9 3 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Temperature Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    18/81

  • 8/9/2019 Micronik Application

    19/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D5-2

    11 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    NC C7 T6046A

    4 R7426B

    Transformer

    5b ML6420A Cooling Valve 1 2

    2 1

    24V

    24V

    24Vac

    230Vac

    3 - Way Valve

    2 - Way Valve

    1 2

    2 1

    24V

    24V

    3 - Way Valve

    2 - Way Valve

    5a ML6420A Heating Valve

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 23 24 25 26 27 28

    24V 24V

    Y1 Y2 Y3open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    o en/OUT2

    close/OUT1

    XWrh24V 24V 24V

    WhiteBrown Green6 ML6184E Damper open/closed

    24V

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5a+5b 2 ML6420A3007 andV5....A....

    Valve Actuator andValve

    6 2 ML6184E1009 Damper Actuator 24Vac, 17Nm

    7 1 T6046A1006 orFT015 or FTB015 Freeze Protection Thermostat

    8+9 3 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Temperature Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    20/81

    HONEYWELL MICRONIK 200 APPLICATION

    D6-1 EN3C-0161 0698R0-MA

    For use with ventilation system comprising of an energy (heat/cool) recovery system, heating and cooling coils.

    M

    EA

    0A

    M

    6

    6

    10

    7

    5b

    4

    3

    11

    5a

    p8

    p

    9

    p

    T1

    T

    Y2Y3

    Y1

    9

    p

    5c

    T

    Temperature Control.The discharge air temperature sensor

    (1) measures the actual value and the controller (4) comparesthis value with the desired setpoint. If a deviation between thetwo values exists, the controller generates a 3-position controlsignal to reposition either the energy recovery valve (5c) or theheating valve (5a) or the cooling valve (5b) in sequence tomaintain the desired discharge air temperature.If the actual temperature is below the setpoint, the controllermodulates first via output Y1 the heat recovery valve (5c) intothe open position and if fully open, the heating valve (5a) isopened in sequence via output Y3. If the actual temperatureincreases the sequence of operation is reversed.If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating andcooling - the controller starts to open the energy recovery valve (5c) to reclaim cooling energy. If the temperature continues toincrease and the energy recovery valve is fully open the controller (4) generates an output signal via Y2 to open the cooling coilvalve (5b).

    In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differentialpressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by anadditional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt theice deposits.

    Freeze Protection.The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below itsadjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a), to switchOFF the fan(s) and thereby to close the damper actuators by an external installed relay logic to protect the heating coil fromfreezing.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe valves (5a, 5b and 5c) and switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damperactuators can be used to start the fan.

    Heating Y3

    Y (%)

    0

    100

    Y1

    0 00 Xwh/Xwc/Xw

    T1

    CTRP1CTRPH

    XpH Xp

    Energy

    Recovery

    XpC

    CTRPC

    Cooling Y2

  • 8/9/2019 Micronik Application

    21/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D6-2

    11 T7412A

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    NC C7 T6046A

    4 R7426B

    Transformer

    5b ML6420A Cooling Valve 12 24V

    24Vac

    230Vac

    2 124V5c ML6420A Heating Valve

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 23 24 25 26 27 28

    24V 24V

    Y1 Y2 Y3

    open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    24V 24V 24V

    5c ML6420A Energy Recovery

    24V

    24V2 1

    XWrh

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5a+5b+5c 3 ML6420A3007 andV5....A....

    Valve Actuator andValve

    6 2 ML6184E1009 orML6684E1008

    Damper Actuator 24Vac, 17Nm or230Vac, 17Nm

    7 1 T6046A1006 orFT015 or FTB015 Freeze Protection Thermostat

    8+9+10 4 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    22/81

    HONEYWELL MICRONIK 200 APPLICATION

    D7-1 EN3C-0161 0698R0-MA

    For use with ventilation systems comprising of mixed air dampers and a heating coil.

    EA

    0A

    T

    p3 17 p

    p

    9

    9

    4

    T

    8 5

    6

    6

    M

    M

    11

    Y3Y1

    6M

    T

    Temperature Control.The discharge air temperature sensor

    (1) measures the actual value and the controller (4) comparesthis value with the desired setpoint. If a deviation between thetwo values exists, the controller generates two 0(2)10Vdccontrol signals in sequence via outputs Y1 and Y3corresponding to the 0100% correctional signal to repositionthe mixed air dampers or the heating valve to maintain thedesired discharge air temperature.

    The minimum outside air damper position adjustment(MINPOS) on the controller determines the position to whichthe outside air damper will be driven even though thetemperature input condition demands that it should drive to thefully closed position.

    Freeze Protection.The freeze protection thermostat (7)switches the heating coil pump ON - if OFF - at temperatures

    below its adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5),to close the outside and exhaust air dampers (6) and to switch OFF the fan(s) to protect the heating coil from freezing.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe heating valve (5) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)OFF.

    If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controllerprovides automatic control.

    Y (%)1/4 Xp

    0

    MINPOS

    100Damper

    0 00 Xwh/Xw

    T1

    CTRPCCTRP1

    XpXpH

    Y1HeatingY3

    CTRPH

  • 8/9/2019 Micronik Application

    23/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D7-2

    11 T7412A

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    NC C7 T6046A

    4 R7426C

    Transformer

    24Vac

    230Vac

    3 15 ML7420A Heating Valve

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 26 27 28

    24V 24V

    Y1 Y3

    0..10V2..10V

    24V 24V

    6 ML7284E Mixed Air Dampers

    24V

    XWrh

    23 24 25

    2

    WhiteBrownGreen

    24V 24V0..10V2..10V

    Y2

    24V 24V0..10V2..10V

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426C1012 orR7426C1004

    Temperature Controller with clock orwithout clock

    5 2 ML7420A3006 andV5....A....

    Valve Actuator 0(2)...10Vdc andValve

    6 3 ML7284E1006 orML7174E2007

    Damper Actuator 24Vac, 17Nm24Vac, 8Nm

    7 1 T6046A1006 orFT015 or FTB015 Freeze Protection Thermostat

    8+9 3 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Temperature Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    24/81

    HONEYWELL MICRONIK 200 APPLICATION

    D8-1 EN3C-0161 0698R0-MA

    Used with ventilation system comprising of mixed air dampers and a cooling coil.

    EA

    0A

    T

    p3 1p

    p

    9

    9

    4

    8 5

    6

    6

    M

    M

    11

    Y2

    Y1

    6M

    T

    Temperature Control.The discharge air temperature sensor

    (1) measures the actual value and the controller (4) comparesthis value with the desired setpoint. If a deviation between thetwo values exists, the controller generates two 0(2)10Vdccontrol signals in sequence via outputs Y1 and Y2corresponding to the 0100% correctional signal to repositionthe mixed air dampers (6) or cooling valve (5) to maintain thedesired discharge air temperature.If the actual temperature is below the setpoint, the controllermodulates via output Y1 the mixed air dampers up to theminimum position.If the actual temperature exceeds the setpoint by more than25% of the throttling range (Xp1) - dead band between heatingand cooling - the controller starts to close the outside andexhaust air dampers and opens the return air damper. If thetemperature continues to increase and the mixed air dampers

    reach the minimum position, the controller (4) generates an output signal via Y2 to open the cooling coil valve (5).The minimum outside air damper position adjustment (MINPOS) on the controller determines the position to which the outsideair damper will be driven even though the temperature input condition demands that it should drive to the fully closed position.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe cooling valve (5) and the outside and exhaust air dampers (6), opens the return air damper (6) and switches the fan(s)OFF.

    If the controller switches from OFF to ON mode the Plant/System On/Off output switches the fan(s) ON and the controllerprovides automatic control.

    Y (%)1/4 Xp

    0

    MINPOS

    100Damper Y1

    CoolingY2

    0 00 Xwc/Xw

    T1

    CTRPCCTRP1

    Xp XpC

  • 8/9/2019 Micronik Application

    25/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D8-2

    11 T7412A

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    4 R7426C

    Transformer

    24Vac

    230Vac

    3 15 ML7420A Cooling Valve

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 26 27 28

    24V 24V

    Y1 Y2

    0..10V2..10V

    24V

    6 ML7284E Mixed Air Dampers

    24V

    XWrh

    23 24 25

    2

    WhiteBrownGreen

    24V 0..10V2..10V

    24V 24V

    Y3

    24V 24V0..10V2..10V

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426C1012 orR7426C1004

    Temperature Controller with clock orwithout clock

    5 1 ML7420A3006 andV5....A....

    Valve Actuator 0(2)...10Vdc andValve

    6 3 ML7284E1006 orML7174E2007

    Damper Actuator 24Vac, 17Nm24Vac, 8Nm

    8+9 3 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Temperature Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    26/81

  • 8/9/2019 Micronik Application

    27/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D9-2

    11 T7412A

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    NC C7 T6046A

    4 R7426C

    Transformer

    24Vac

    230Vac

    3 15a ML7420A Heating Valve

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    6 ML7284E Mixed Air Dampers

    24V

    2

    WhiteBrownGreen

    5b ML7420A Cooling Valve 3 1 2

    15 16 17 18 19 20 21 22 26 27 28

    24V 24VXWrh

    23 24 25

    Y1 Y3

    0..10V2..10V

    24V 24V24V 24V0..10V2..10V

    Y2

    24V 24V0..10V2..10V

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426C1012 orR7426C1004

    Temperature Controller with clock orwithout clock

    5a+5b 2 ML7420A3006 andV5....A....

    Valve Actuator 0(2)...10Vdc andValve

    6 3 ML7284E1006 orML7174E2007

    Damper Actuator 24Vac, 17Nm24Vac, 8Nm

    7 1 T6046A1006 orFT015 or FTB015 Freeze Protection Thermostat

    8+9 3 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Temperature Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    28/81

    HONEYWELL MICRONIK 200 APPLICATION

    D10-1 EN3C-0161 0698R0-MA

    Used with ventilation system using electric air heating, where the base heating load is met by a radiator heating system andthe ventilation system is used to ensure the supply of outside air.

    Instead of electric heating, the controller can be used to control up to 6-stages of direct expansion cooling. The controller can

    be configured to provide sequence control of electric heating and cooling as follows:- Heating mode: 4 stages, sequentially switched steps to operate external relays or

    4 binary coded switching outputs to provide up to 15 load steps.- Cooling mode: 2 stages, sequentially switched steps to operate external relays.

    EA

    0A

    7

    4

    3

    11

    p

    8

    9

    p

    T1

    T

    9

    p

    T

    6

    6

    M

    M V

    5

    Y1/Y2/Y3

    10

    Temperature Control.The discharge air temperature sensor (1) measures theactual value and the controller (4) compares this value with the desired setpoint.If a deviation between the two values exists, the controller selects the number ofstages/steps required to maintain the desired discharge air temperature.

    When configured for heating and cooling sequence operation, the controller willfirst select the heating or cooling mode and than the number of stages/stepsrequired.

    Time Control. Depending on the programmed time schedule of the internalcontroller real time clock the different operating control modes Comfort, Standby,Night or OFF are selected. In the OFF operating mode the controllerautomatically switches OFF the selected number of stages/steps and the fan(s)and thereby closes the dampers (6) by an external installed relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a timedelay by an external installed time delay relay. This allows the dampers time toopen. As alternative to the time delay relay the end-position switches of thedamper actuators can be used to start the fan.

    100

    Y1/Y2/Y3 (%)

    0

    Cooling

    Heating0

    CTRP1YstartXp

    T1

    X w

    off

    15 100 %10Y3/Y2/Y1

    2530

    Step1 on

    Step2 on

    Step5 on

    on

    PowerStep6 on

    6 signal sequence of

    70 85 9075

    Y3/Y2/Y1 out1/out2

  • 8/9/2019 Micronik Application

    29/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D10-2

    11 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    Transformer

    24Vac

    230Vac

    5 24Vac Relays

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    24V 24V 24V

    Y1 Y2 Y3

    XWrh

    4 R7426B

    Heating or Cooling 6 5 4 3 2 1

    Heating: 4 Linear or 15 Binary Plus 2 Cooling

    4 3 2 1

    2 1Stage

    Stage

    Stage

    Stage

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5 1 or6

    RY6 Auxiliary Relay Module with 6 relays or24Vac coil

    6 2 ML6184E1009 orML6684E1008

    Damper Actuator 24Vac, 17Nm or230Vac, 17Nm

    7 1 L4064K1006 High Limit Thermostat8+9+10 4 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    30/81

    HONEYWELL MICRONIK 200 APPLICATION

    D11-1 EN3C-0161 0698R0-MA

    Use with ventilation system comprising of an electric air heater and a cooling coil.

    EA

    0A

    7

    4

    3

    11

    p

    8

    9

    p

    T1

    9

    p

    T

    6

    6

    M

    M

    5a

    5b

    V10

    T

    Y2Y1/Y3

    Temperature Control.The discharge air temperature sensor (1)

    measures the actual value and the controller (4) compares thisvalue with the desired setpoint. If a deviation between the twovalues exists, the controller selects the corresponding number ofstages/steps (up to 4 stages linear or 15 stages binary) forheating or generates a 3-position control signal to reposition thecooling valve to maintain the desired discharge air temperature.

    If the temperature is below the heating setpoint the heatingstages are switched via output Y3 and Y1 and if the temperatureis above the cooling setpoint, the cooling valve (5b) is modulatedvia output Y2.

    Time Control.Depending on the programmed time schedule ofthe internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. Inthe OFF operating mode the controller automatically switches

    OFF the selected number of heating stages/steps or closes thecooling valve (5b), switches the fan(s) OFF and thereby closesthe dampers (6) by an external installed relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switchON after a time delay by an external installed time delay relay.This allows the dampers time to open. As alternative to the timedelay relay the end-position switches of the damper actuatorscan be used to start the fan.

    Heating

    Y (%)

    0

    100

    Cooling

    0 00 Xwh/Xwc

    T1

    CTRPCCTRP1CTRPH

    XpH Xp XpC

    Y1/Y3 Y2

    off

    Y3 out2

    25 8580 100 %20 Y3/Y140 45

    Step1 on

    Y3 out1

    Step2 on

    Step3 on

    on

    Power

    6065

    Y1 out2

    Y1 out1

    Step4 on

  • 8/9/2019 Micronik Application

    31/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D11-2

    11 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    Transformer

    24Vac

    230Vac

    5a 24Vac Relays

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    24V 24V 24V

    Y1 Y2 Y3

    XWrh

    4 R7426B

    Heating: 4 Linear or 15 Binary 4 3 2 1

    5b ML6420A Cooling Valve 1 2

    2 1

    24V

    24V

    3 - Way Valve

    2 - Way Valve

    Stage Stage

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5a 1 or4

    RY4 Auxiliary Relay Module with 4 relays or24Vac coil

    5b 1 ML6420A3007 andV5...A....

    Valve Actuator andValve

    6 2 ML6184E1009 orML6684E1008

    Damper Actuator 24Vac, 17Nm or230Vac, 17Nm

    7 1 L4064K1006 High Limit Thermostat

    8+9+10 4 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    32/81

    HONEYWELL MICRONIK 200 APPLICATION

    D12-1 EN3C-0161 0698R0-MA

    For use with ventilation system comprising of an electric air heater and a cooling coil with full outside air dampers.

    EA

    0A

    7

    4

    3

    11

    p8

    9

    p

    T1

    T

    9

    p

    T

    6

    6

    M

    M

    5a

    5b

    V10

    Y2Y3Y1

    Temperature Control.The discharge air temperature sensor(1) measures the actual value and the controller (4) comparesthis value with the desired setpoint. If a deviation between the

    two values exists, the controller generates a pulse widthmodulated output signal on output Y3 to control the solid staterelay (5a) or a 3-position control signal on output Y2 toreposition the cooling valve (5b) to maintain the desireddischarge air temperature.

    If the temperature is below the heating setpoint the solid staterelay(s) (5a) is modulated via output Y3 and if the temperatureis above the cooling setpoint the cooling valve (5b) ismodulated via output Y2.

    Damper Control.If the controller switches from OFF to ONmode (Comfort, Standby or Night) the controller drives thedamper actuators to the open position via output Y1.If the controller switches to the OFF mode, it drives thedampers and valves automatically to their closed positions.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically generateson all outputs a 0% output signal to switch OFF the electric air heater, to fully close the cooling valve (5b) and dampers (6)and to switch OFF the fan(s).

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a 3 minute time delay to allow the dampers time toopen. As alternative the end-position switches of the damper actuators can be used to start the fan.

    Heating

    Y (%)

    0

    100

    Cooling

    0 00 Xwh/Xwc

    T1

    CTRPCCTRP1CTRPH

    XpH Xp XpC

    Y3 Y2

    30 50 70 80 100 sec Y3

    off

    onout1/out2

  • 8/9/2019 Micronik Application

    33/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D12-2

    11 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    Transformer

    24Vac

    230Vac

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    24V 24V 24V

    Y1 Y2 Y3

    XWrh

    4 R7426B

    5b ML6420A Cooling Valve 1 2

    2 1

    24V

    24V

    3 - Way Valve

    2 - Way Valve

    5a RN1L40M25 Solid State Relay (Current Valve)

    WhiteBrown Green6 ML6184E Damper open/closed

    A1

    L1 T1

    A2

    100...440Vac

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5a up to 3 RN1L40M25 Solid State Relay (Current Valve)

    5b 1 ML6420A3007 andV5...A....

    Valve Actuator andValve

    6 2 ML6184E1009 Damper Actuator 24Vac, 17Nm

    7 1 L4064K1006 High Limit Thermostat

    8+9+10 3 or 4 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    34/81

    HONEYWELL MICRONIK 200 APPLICATION

    D13-1 EN3C-0161 0698R0-MA

    Used with ventilation system comprising of an electric air heater and a cooling coil.

    EA

    0A

    7

    4

    3

    11

    p

    8

    9

    p

    T1

    9

    p

    T

    6

    6

    M

    M

    5a

    5b

    V10

    Y2

    Y3

    T

    Temperature Control.The discharge air temperature sensor

    (1) measures the actual value and the controller (4)compares this value with the desired setpoint. If a deviationbetween the two value exists, the controller generates two0(2)...10Vdc control signals in sequence via outputs Y2 andY3 corresponding to the 0...100% correctional signal to drivethe electric current valve (5a) for proportional control of theelectric air heater or to reposition the cooling valve (5b) tomaintain the desired discharge air temperature.

    If the temperature is below the heating setpoint the controllergenerates a control signal on output Y3 to control the electriccurrent valve (5a) and if the temperature is above the coolingsetpoint, the controller generates a control signal on outputY2 to position the cooling valve (5b).

    Time Control.Depending on the programmed time schedule

    of the internal controller real time clock the different operating control modes Comfort, Standby, Night or OFF are selected. Inthe OFF operating mode the controller automatically generates 0% output signals on Y2 and Y3 to switch OFF the electricheater, to close the cooling valve (5b) and to switch OFF the fan(s) by the Plant/System On/Off output and thereby close thedampers (6) by an external installed relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damperactuators can be used to start the fan.

    Heating

    Y (%)

    0

    100

    Cooling

    0 00 Xwh/Xwc

    T1

    CTRPCCTRP1CTRPH

    XpH Xp XpC

    Y3 Y2

  • 8/9/2019 Micronik Application

    35/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D13-2

    11 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    4 R7426C

    Transformer

    24Vac

    230Vac

    85a R7425A/B Current Valve

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    24V

    10

    5b ML7420A Cooling Valve 3 1 2

    15 16 17 18 19 20 21 22 26 27 28

    24V 24VXWrh

    23 24 25

    Y1 Y3

    0..10V2..10V

    24V 24V24V 24V0..10V2..10V

    Y2

    24V 24V0..10V2..10V

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426C1012 orR7426C1004

    Temperature Controller with clock orwithout clock

    5a 1 R7425A/B Electric Current Valve

    5b 1 ML7420A3006 andV5....A....

    Valve Actuator andValve

    6 2 ML6184E1009 or

    ML6684E1008

    Damper Actuator 24Vac, 17Nm or

    230Vac, 17Nm7 1 L4064K1006 High Limit Thermostat

    8+9+10 3 or 4 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    36/81

    HONEYWELL MICRONIK 200 APPLICATION

    D14-1 EN3C-0161 0698R0-MA

    For use with ventilation system comprising of an energy (heat/cool) recovery system, an electric air heater and a cooling coil.

    10

    M

    EA

    0A

    M

    6

    6 7 5b

    4

    3

    12

    p

    8

    p

    9

    p

    T1

    T

    9

    p

    5c

    T

    5a

    11

    V

    Y2Y3

    Y1

    Temperature Control.The discharge air temperature sensor (1)measures the actual value and the controller (4) compares thisvalue with the desired setpoint. If a deviation between the twovalues exists, the controller generates the corresponding controlsignals to maintain the desired discharge air temperature.

    If the actual temperature is below the setpoint the controller (4)generates first a 3-position control signal via output Y1 toreposition the energy recovery valve (5c) to reclaim heatingenergy. If the temperature continues to decrease and the energyrecovery valve is fully open, the controller generates a pulsewidth modulated output via output Y3 to drive the solid state relay(5a) for proportional control of the electric air heater. If thetemperature increases the sequence of operation is reversed.

    If the actual temperature exceeds the setpoint by more than 25%of the throttling range (Xp1) - dead band between heating andcooling - the controller starts to open the energy recovery valve

    (5c) to reclaim cooling energy. If the temperature continues toincrease and the energy recovery valve is fully open the controller (4) generates an output signal via Y2 to open the cooling coilvalve (5b).

    In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differentialpressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by anadditional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt theice deposits.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe valves (5b and 5c) and switches the electric air heater and the fan(s) OFF and thereby close the dampers (6) by an externalinstalled relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damper

    actuators can be used to start the fan.

    30 50 70 80 100 sec Y3

    off

    onout1/out2

    Heating Y3

    Y (%)

    1/4 Xp

    0

    100

    Y1

    0 00 Xwh/Xwc/Xw

    T1

    CTRP1CTRPH

    XpH Xp

    EnergyRecovery

    XpC

    CTRPC

    Cooling Y2

  • 8/9/2019 Micronik Application

    37/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D14-2

    12 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    Transformer

    24Vac

    230Vac

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    15 16 17 18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    open/OUT2

    close/OUT1

    24V 24V 24V

    Y1 Y2 Y3

    XWrh

    4 R7426B

    5b ML6420A Cooling Valve 1 2

    2 1

    24V

    24V

    3 - Way Valve

    2 - Way Valve

    5a RN1L40M25 Solid State Relay (Current Valve)

    5c ML6420A Energy Recovery Valve 1 224V

    A1

    L1 T1

    A2

    100...440Vac

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5a up to 3 RN1L40M25 Solid State Relay (Current Valve)

    5b + 5c 2 ML6420A3007 andV5....A....

    Valve Actuator andValve

    6 2 ML6184E1009 orML6684E1008

    Damper Actuator 24Vac, 17Nm or230Vac, 17Nm

    7 1 L4064K1006 High Limit Thermostat

    8+9+10 4 DPS-Series Differential Air Pressure Switch

    11 1 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

    12 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    38/81

    HONEYWELL MICRONIK 200 APPLICATION

    D15-1 EN3C-0161 0698R0-MA

    For use with ventilation system comprising of an energy (heat/cool) recovery system, an electric air heater and a cooling coil.

    M

    EA

    0A

    M

    6

    6

    10

    7 5b

    4

    3

    12

    p

    8

    p

    9

    p

    T1

    9

    p

    5c

    T

    5a

    11

    VT

    Y2Y3

    Y1

    Temperature Control.The discharge air temperature sensor(1) measures the actual value and the controller (4) comparesthis value with the desired setpoint. If a deviation between the

    two values exists, the controller generates in correspondenceto the 0...100% correctional signal 0(2)...10Vdc control signalsin sequence via outputs Y1, Y2 and Y3 to position the energyrecovery or cooling valves or to drive the electric current valveto maintain the desired discharge air temperature.

    If the actual temperature is below the setpoint, the controllergenerates first a 0(2)...10Vdc control signal via output Y1 toreposition the energy recovery valve (5c) to reclaim heatingenergy. If the temperature continues to decrease and theenergy recovery value is fully open, the controller generates a0(2)...10Vdc control signal via output Y3 to drive the electric current valve (5a) for proportional control of the electric air heater.If the temperature increases the sequence of operation is reversed.

    If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating and

    cooling - the controller starts to open the energy recovery valve (5c) to reclaim cooling energy. If the temperature continues toincrease and the energy valve is fully open, the controller (4) generates a 0(2)...10Vdc control signal via Y2 to position thecooling valve (5b).

    In an air-glycol-air heat recovery system it is important to avoid icing of the exhaust air coil. This is achieved by the differentialpressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5c) will be closed by anadditional, field mounted relay. Return air and warm water will circulate through the heat recovery exhaust air coil to melt theice deposits.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe valves (5b and 5c) and switches the electric air heater and the fan(s) OFF and thereby close the dampers (6) by an externalinstalled relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damperactuators can be used to start the fan.

    Heating Y3

    Y (%)

    1/4 Xp

    0

    100

    Y1

    0 00 Xwh/Xwc/Xw

    T1

    CTRP1CTRPH

    XpH Xp

    Energy

    Recovery

    XpC

    CTRPC

    Cooling Y2

  • 8/9/2019 Micronik Application

    39/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D15-2

    12 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    4 R7426C

    Transformer

    24Vac

    230Vac

    85a R7425A/B Current Valve

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    24V

    10

    5b ML7420A Cooling Valve 3 1 2

    15 16 17 18 19 20 21 22 26 27 28

    24V 24VXWrh

    23 24 25

    Y1 Y3

    0..10V2..10V

    24V 24V24V 24V0..10V2..10V

    Y2

    24V 24V0..10V2..10V

    5c ML7420A Energy Recovery Valve 3 1 2

    Item Quantity Part Number Description1 1 T7411A1001 or

    T7411A1019Duct Temperature Sensor 135mm length or

    300mm length

    4 1 R7426C1012 orR7426C1004

    Temperature Controller with clock orwithout clock

    5a 1 R7425A/B Electric Current Valve

    5b + 5c 2 ML7420A3006 andV5....A....

    Valve Actuator 0(2)...10Vdc andValve

    6 2 ML6184E1009 orML6684E1008

    Damper Actuator 24Vac, 17Nm or230Vac, 17Nm

    7 1 L4064K1006 High Limit Thermostat

    8+9+10 4 DPS-Series Differential Air Pressure Switch

    11 1 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

    12 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    40/81

    HONEYWELL MICRONIK 200 APPLICATION

    D16-1 EN3C-0161 0698R0-MA

    For use with ventilation system comprising mixed air dampers, an electric air heater and a cooling coil.

    9

    9

    p

    p

    EA

    0A

    5b

    4

    3

    11

    p

    8

    T1

    T

    6

    6

    M

    M

    6M

    10

    V

    5a

    Y2Y3

    Y1

    7

    T

    Temperature Control.The discharge air temperature sensor(1) measures the actual value and the controller (4) comparesthis value with the desired setpoint. If a deviation between thetwo values exists, the controller generates in correspondence to

    the 0...100% correctional signal 0(2)...10Vdc control signals insequence via outputs Y1, Y2 and Y3 to position the mixed airdampers or cooling valve or to drive the electric current valve tomaintain the desired discharge air temperature. If the actualtemperature is below the setpoint, the controller generates firsta 0(2)...10Vdc control signal via output Y1 to reposition themixed air damper (6). If the temperature continues to decreaseand the mixed air dampers reached the minimum position(MINPOS), the controller generates a 0(2)...10Vdc controlsignal via output Y3 to drive the electric current valve (5a) forproportional control of the electric air heater. If the temperatureincreases the sequence of operation is reversed.

    If the actual temperature exceeds the setpoint by more than 25% of the throttling range (Xp1) - dead band between heating andcooling - the controller starts to close the mixed air damper (6). If the temperature continues to increase and the mixed airdampers reached the minimum position (MINPOS), the controller (4) generates a 0(2)...10Vdc control signal via Y2 to positionthe cooling valve (5b).

    The minimum outside air damper position adjustment (MINPOS) on the controller determines the position to which the outsideair damper will be driven even though the temperature input condition demands that it should drive to the fully closed position.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically generates0Vac (0%) control signals via output Y1, Y2 and Y3 to fully close the outside and exhaust air dampers (6) and the cooling valve(5b), open the return air damper and to switch OFF the electric air heater via the current valve (5a). In addition the fans areswitched OFF by the Plant/System On/Off output.

    If the controller switches from OFF to ON mode, the Plant/System On/Off output switches the fans ON and the controllerprovides automatic control.

    Heating Y3

    Y (%)1/4 Xp

    0

    MINPOS

    100Damper Y1

    CoolingY2

    0 00 Xwh/Xwc/Xw

    T1

    CTRPCCTRP1CTRPH

    XpH Xp XpC

  • 8/9/2019 Micronik Application

    41/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA D16-2

    11 T7412B

    1 T7411A 1 2

    1 23 T7411A/T7416A

    4 6

    4 R7426C

    Transformer

    24Vac

    230Vac

    85a R7425A/B Current Valve

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    24V

    10

    5b ML7420A Cooling Valve 3 1 2

    15 16 17 18 19 20 21 22 26 27 28

    24V 24VXWrh

    23 24 25

    Y1 Y3

    0..10V2..10V

    24V 24V24V 24V0..10V2..10V

    Y2

    24V 24V0..10V2..10V

    WhiteBrown Green6 ML7284E Mixed Air Dampers

    Item Quantity Part Number Description

    1 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length or300mm length

    4 1 R7426C1012 orR7426C1004

    Temperature Controller with clock orwithout clock

    5a 1 R7425A/B Electric Current Valve

    5b 1 ML7420A3006 andV5....A....

    Valve Actuator 0(2)...10Vdc andValve

    6 3 ML7284E1006 orML7174E1006

    Damper Actuator 24Vac, 0...10Vdc, 17Nm or24Vac, 0...10Vdc, 8Nm

    7 1 L4064K1006 High Limit Thermostat

    8+9 3 DPS-Series Differential Air Pressure Switch10 1 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

    11 1 T7412B1057 or43182690-001

    Remote Setpoint Adjustment Potentiometer, Wall Mounting orFront Panel Mounting

  • 8/9/2019 Micronik Application

    42/81

    HONEYWELL MICRONIK 200 APPLICATION

    R1-1 EN3C-0161 0698R0-MA

    A heating and ventilation system with room/return air temperature control and low limit discharge air or cascade control is usedwhere the base heating load is met by radiators and the ventilation system provides the supply of fresh outside air.In cooling applications it is also used to supply fresh outside air using the same temperature control system as for heatingcontrol.

    EA

    0A

    M

    p

    p

    T

    p

    M6

    63

    9

    279

    4

    T

    8

    1c

    5

    T

    Y1

    T

    TT 1b1a

    Temperature Control With Low Limit Control.The return or room airtemperature sensor (1a, b or c) and the discharge air temperature sensor (2)measure the actual values and the controller (4) compares these values with thedesired setpoints (W1) and (Wlim). If a deviation between these values exists, thelowest deviation signal of both is selected by the controller. Depending on thisdeviation signal the controller generates a 3-position control signal to repositionthe valve (5) to maintain the desired room or discharge air temperature. Inheating applications the controller output is reverse acting and direct acting forcooling applications.

    Cascade Temperature Control.The return or room air temperature sensor (1a, bor c) measures the actual value and the controller (4) compares this value with the desired setpoint (W1) of the master loop.Depending on the deviation an internal setpoint for the submaster loop, the discharge air temperature, is calculated. At zerodeviation the discharge air temperature is controlled at the programmed setpoint (Wcas) and if a deviation exists, the dischargeair setpoint is altered. The reset span of the discharge air setpoint is limited by the reset span adjustment (Rcas) and the limit

    setting (Wlim).The discharge air temperature sensor (2) measures the actual value and the controller compares this value with the desiredinternal calculated setpoint. If a deviation exists, the controller generates a 3-position control signal to reposition the valve (5) tomaintain the desired discharge air temperature. In heating applications the controller output is reverse acting and direct actingfor cooling applications.

    Freeze Protection.The freeze protection thermostat (7) switches the heating coil pump ON - if OFF - at temperatures below itsadjustable setpoint. In parallel it provides a digital input signal to the controller (4) to switch the fan(s) OFF and close thedampers by an external installed relay logic and fully open the heating valve (5) to prevent the heating coil from freezing.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe heating valve (5), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damperactuators can be used to start the fan.

    Y1 (%)

    100

    0

    Cooling

    Heating0

    CTRP2Ystart

    Xp

    T2

    X w

  • 8/9/2019 Micronik Application

    43/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA R1-2

    Transformer

    5 ML6420A Heating or Cooling 1 2

    2 1

    24V

    24V

    24Vac

    230Vac

    3 - Way Valve

    2 - Way Valve

    1c T7412C

    1b T7412A

    1 23 T7411A/T7416A NC C

    7 T6046A

    4 R7426A

    1 2

    15 16 17

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    Y1

    close/OUT1

    24V

    24V

    1 2

    1c T7412B

    2 T7411A

    1a T7411A

    64 3

    5 34 6

    Item Quantity Part Number Description1a or1b or1c

    1 T7411A1001 orT7412A1018 orT7412B1057T7412C1030

    Duct Temperature Sensor 135mm length orRoom Temperature Sensor orRoom Temperature Sensor with CPARoom Temperature Sensor with CPA and Occupancy Switch

    2 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length orDuct Temperature Sensor 300mm length

    4 1 R7426A1016 orR7426A1008

    Temperature Controller with clock orwithout clock

    5 1 ML6420A3007 andV5.....A.....

    Valve Actuator andValve

    6 2 ML6184E1009 or

    ML6684E1008

    Damper Actuator 24Vac, 17Nm or

    230Vac, 17Nm

    7 1 T6046A1006 orFT015 or FTB015

    Freeze Protection Thermostat

    8+9 3 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

  • 8/9/2019 Micronik Application

    44/81

    HONEYWELL MICRONIK 200 APPLICATION

    R2-1 EN3C-0161 0698R0-MA

    Recirculation air systems with room or return air temperature control are used for ventilation in factories, storage areas,department stores, etc.

    4

    1c

    5

    Y1

    T

    TT 1b1a

    Temperature Control.The return or room air temperature sensor (1a, b or c)measures the actual value and the controller (4) compares this value with thedesired setpoint. If a deviation between the two values exists, the controller(4) generates a 3-position control signal to reposition the valve (5) to maintainthe desired room or return air temperature. In heating applications thecontroller output is reverse acting and direct acting for cooling applications.

    Time Control.Depending on the programmed time schedule of the internalcontroller real time clock the different operating control modes Comfort,Standby, Night or OFF are selected. In the OFF operating mode thecontroller automatically fully closes the heating valve (5) and switches the fanOFF.

    If the controller switches from OFF to ON mode the Plant/System On/offoutput switches the fan ON and the controller provides automatic control.

    Y1 (%)

    100

    0

    Cooling

    Heating0

    CTRP1Ystart

    Xp

    T1

    X w

  • 8/9/2019 Micronik Application

    45/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA R2-2

    Transformer

    5 ML6420A Heating or Cooling 1 2

    2 1

    24V

    24V

    24Vac

    230Vac

    3 - Way Valve

    2 - Way Valve

    4 R7426A

    1c T7412C

    1b T7412A

    1c T7412B

    1a T7411A

    1 2

    64 3

    5 34 6

    15 16 17

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    Y1

    close/OUT1

    24V

    24V

    Item Quantity Part Number Description1a

    1b or1c

    1 T7411A1001T7411A1019T7412A1018 orT7412B1057T7412C1030

    Duct Temperature Sensor 135mm length300mm length

    Room Temperature Sensor orRoom Temperature Sensor with CPARoom Temperature Sensor with CPA and Occupancy Switch

    4 1 R7426A1016 orR7426A1008

    Temperature Controller with clock orwithout clock

    5 1 ML6420A3007 andV5.....A.....

    Valve Actuator andValve

  • 8/9/2019 Micronik Application

    46/81

    HONEYWELL MICRONIK 200 APPLICATION

    R3-1 EN3C-0161 0698R0-MA

    For use with ventilation systems comprising of an energy (heat) recovery system and a heating coil.

    EA

    0A

    M

    p

    p

    T

    p

    M6

    63

    9

    27

    9

    4

    T

    8

    1c

    5a

    T

    Y3

    T

    TT 1b1a

    5b

    p11

    Y1

    Temperature Control.The return or room air temperaturesensor (1a, b or c) measures the actual value and the controller(4) compares this value with the desired setpoint (W1) of themaster loop. Depending on the deviation an internal setpoint forthe submaster loop, the discharge air temperature, iscalculated. At zero deviation the discharge air temperature iscontrolled at the programmed setpoint (Wcas) and if adeviation exists, the discharge air setpoint is altered. The resetspan of the discharge air setpoint is limited by the reset spanadjustment (Rcas) and the limit setting (Wlim).The discharge air temperature sensor (2) measures the actualvalue and the controller (4) compares this value with the desired internal calculated setpoint. If a deviation between the twovalues exists, the controller generates a 3-position control signal on outputs Y1 and Y3 to reposition either the energy recoveryvalve (5a) or the heating valve (5b) in sequence to maintain the desired discharge air temperature.

    In an air-glycol-air heat recovery system it is important, to avoid icing of the exhaust air coil. This is achieved by the differentialpressure switch (10). If the differential pressure switch indicates icing of the coil, the control valve (5b) will be closed by anadditional, field mounted relay. Return air and warm water will be circulated through the exhaust air heat recovery coil to meltthe ice deposits.

    Freeze Protection.The freeze protection thermostat (7) switches the heating coil pump ON, - if OFF - at temperatures belowits adjustable setpoint. In parallel it provides a digital input signal to the controller (4) to fully open the heating valve (5a), toswitch OFF the fan(s) and close the dampers (6) by an external installed relay logic to protect the heating coil from freezing.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damperactuators can be used to start the fan.

    Heating Y3

    Y (%)

    1/4 Xp

    0

    100

    Y1

    0 00 Xwh/Xw

    T2

    CTRP2CTRPH

    XpH Xp

    EnergyRecovery

  • 8/9/2019 Micronik Application

    47/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA R3-2

    Transformer

    5b ML6420A Energy Recovery

    1 2

    2 1

    24V

    24V

    230Vac 3 - Way Valve

    2 - WayValve

    1 23 T7411A/T7416A NC C

    7 T6046A

    4 R7426B

    1 22 T7411A

    1 2

    2 1

    24V

    24V

    3 - Way Valve

    2 - Way Valve

    24Vac

    5a ML6420A Heating Valve

    1c T7412C

    1b T7412A

    1c T7412B

    1a T7411A

    1 2

    64 3

    5 34 6

    open/OUT2

    Y2

    close/OUT1

    24V

    15 16 17

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    Y1

    close/OUT1

    24V

    24V

    open/OUT2

    Y3

    close/OUT1

    24VX

    Wrh

    Item Quantity Part Number Description1a or1b or1c

    1 T7411A1001 orT7412A1018 orT7412B1057T7412C1030

    Duct Temperature Sensor 135mm length orRoom Temperature Sensor orRoom Temperature Sensor with CPARoom Temperature Sensor with CPA and Occupancy Switch

    2 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length orDuct Temperature Sensor 300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5a+5b 2 ML6420A3007 andV5.....A.....

    Valve Actuator andValve

    6 2 ML6184E1009 or

    ML6684E1008

    Damper Actuator 24Vac, 17Nm or

    230Vac, 17Nm

    7 1 T6046A1006 orFT015 or FTB015

    Freeze Protection Thermostat

    8+9+10 3 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

  • 8/9/2019 Micronik Application

    48/81

    HONEYWELL MICRONIK 200 APPLICATION

    R4-1 EN3C-0161 0698R0-MA

    For use with ventilation systems comprising of an energy (heat/cool) recovery system and a cooling coil.

    EA

    0A

    M

    p

    p

    T

    p

    M6

    63

    9

    2

    9

    4

    8

    1c

    5a

    T

    Y2

    T

    TT 1b1a

    5b

    p11

    Y1

    Temperature Control.The return or room air temperaturesensor (1a, b or c) measures the actual value and thecontroller (4) compares this value with the desired setpoint(W1) of the master loop. Depending on the deviation aninternal setpoint for the submaster loop, the discharge airtemperature, is calculated. At zero deviation the discharge airtemperature is controlled at the programmed setpoint (Wcas)and if a deviation exists, the discharge air setpoint is altered.The reset span of the discharge air setpoint is limited by thereset span adjustment (Rcas) and the limit setting (Wlim).

    The discharge air temperature sensor (2) measures theactual value and the controller (4) compares this value withthe desired internal calculated setpoint. If a deviationbetween the two values exists, the controller generates a 3-

    position control signal on output Y1or Y2 to reposition eitherthe energy recovery valve (5b) or the cooling valve (5a) in sequence to maintain the desired discharge air temperature.

    Time Control.Depending on the programmed time schedule of the internal controller real time clock the different operatingcontrol modes Comfort, Standby, Night or OFF are selected. In the OFF operating mode the controller automatically fully closesthe valves (5a and 5b), switches the fan(s) OFF and thereby closes the dampers (6) by an external installed relay logic.

    If the controller switches from OFF to ON mode, the fan(s) switch ON after a time delay by an external installed time delayrelay. This allows the dampers time to open. As alternative to the time delay relay the end-position switches of the damperactuators can be used to start the fan.

    Y (%)

    0

    MINPOS

    100

    Y1

    0 00 Xwc/Xw

    T2

    CTRPCCTRP2

    Xp XpC

    Y2Cooling

    EnergyRecovery

  • 8/9/2019 Micronik Application

    49/81

    HONEYWELL MICRONIK 200 APPLICATION

    EN3C-0161 0698R0-MA R4-2

    Transformer

    5b ML6420A Energy Recovery

    1 2

    2 1

    24V

    24V

    230Vac3 - Way

    Valve

    2 - WayValve

    1 23 T7411A/T7416A

    4 R7426B

    1 22 T7411A

    1 2

    2 1

    24V

    24V

    3 - Way Valve

    2 - Way Valve

    24Vac

    5a ML6420A Cooling Valve

    1c T7412C

    1b T7412A

    1c T7412B

    1a T7411A

    1 2

    64 3

    5 34 6

    15 16 17

    1 2 3 4ON/OFF

    5 6 7 8 9 10 11 12CPA/SPA T1 T2 T3

    13 14

    18 19 20 21 22 23 24 25 26 27 28

    24V 24V open/OUT2

    Y1

    close/OUT1

    24V

    24V

    open/OUT2

    Y2

    close/OUT1

    24V open/OUT2

    Y3

    close/OUT1

    24VX

    Wrh

    Item Quantity Part Number Description1a or1b or1c

    1 T7411A1001 orT7412A1018 orT7412B1057T7412C1030

    Duct Temperature Sensor 135mm length orRoom Temperature Sensor orRoom Temperature Sensor with CPARoom Temperature Sensor with CPA and Occupancy Switch

    2 1 T7411A1001 orT7411A1019

    Duct Temperature Sensor 135mm length orDuct Temperature Sensor 300mm length

    4 1 R7426B1014 orR7426B1006

    Temperature Controller with clock orwithout clock

    5a+5b 2 ML6420A3007 andV5.....A.....

    Valve Actuator andValve

    6 2 ML6184E1009 or

    ML6684E1008

    Damper Actuator 24Vac, 17Nm or

    230Vac, 17Nm

    8+9 3 DPS-Series Differential Air Pressure Switch

    Item Quantity Part Number Description

    3 1 T7411A1027 orT7416A1006

    Outside Air Sensor, Duct Mounting orWall Mounting

  • 8/9/2019 Micronik Application

    50/81

  • 8/9/2019 Micronik Application

    51/81

  • 8/9/2019 Micronik Application

    52/81

    HONEYWELL MICRONIK 200 APPLICATION

    R6-1 EN3C-0161 0698R0-MA

    For use with ventilation system comprising of an energy (heat/cool) recovery system, heating and cooling coils.

    EA

    0A

    p

    T

    p3

    9

    2p

    9

    4

    8

    1c

    7

    TT 5b

    Y2

    T

    TT 1b1a

    M6

    M6

    5a

    Y3Y1

    p10

    5c

    Temperature Control.The return or room air temperaturesensor (1a, b or c) measures the actual value and the controller(4) compares this value with the desired setpoint (W1) of the

    master loop. Depending on the deviation an internal setpoint forthe submaster loop, the discharge air temperature, iscalculated.The discharge air temperature sensor (2) measures the actualvalue and the controller (4) compares this value with thedesired internal calculated setpoint. If a deviation between thetwo values exists, the controller generates a 3-position controlsignal to reposition either the energy recovery valve (5c) or theheating valve (5a) or the cooling valve (5b) in sequence to maintain the desired discharge air temperature. If the actualtemperature is below the setpoint, the controller modulates first via output Y1 the heat recovery valve (5c) into the openposition and if fully open, the heating valve (5a) is opened in sequence via output Y3. If the actual temperature increases thesequence of operation is re