Microcomputer Protection Relays and Monitoring Device for Line Protection
-
Upload
eagle-technology -
Category
Documents
-
view
441 -
download
29
description
Transcript of Microcomputer Protection Relays and Monitoring Device for Line Protection
Zhuhai Wanlida Electric Co., Ltd. http://www.zhwld.com
User’s manual of MLPR-610Hb microcomputer
protection and monitoring device for line
Prepared by:
Proofed by:
Approved by:
Document No.: WLD [K]-JY-222-2010 Version No.: V2.03.01
Date of publication: Oct. ,2010
Copyright: Zhuhai Wanlida Electric Co., Ltd.
Note: Our company reserves the right to modify this manual. For any inconsistency
between the product and this manual, please contact us for relevant services.
Technical support hotline: 0756-3395398 Fax: 0756-3395500
Foreword
1
F o r e w o r d
1. Model description
The structural type of the MXPR-600Hb series protection is Hb. MLPR-610Hb
supports A, B, C three-phase current protection, also supports A, C two-phase
current protection. When ordering, please specify.
2. Standards referenced
General specification for static protection, security and automatic equipment, DL
478-2001
Technical code for relaying protection and security automatic equipment
GB/T 14285-2006
Protective relay and automatic equipment design rules of power eequipment
GB50062-92
3. Caution
Negative sequence voltage involved in this series of protection is combined with
phase voltage, all of low voltage component depend on line voltage in compound
voltage block, if one of the three line voltages is lower than low voltage setting, low
voltage component will operates and unblock over current protection.
There are 4 standard curves of inverse protection involved in this series of protection,
if the fault current is higher than 15 times of rated current, the inverse protection
component as if the current is 15 times of rated current.
The appearance should be inspected before power is applied, to ensure that the
panel is OK without scratch, the screws are tightened, the device is grounded firmly,
all screws of plug-ins are tightened and in good contact.
When power is applied, the ―Run‖ indicator on the panel should flash, digital tube
displays primary measuring result in cycle, protection and measuring data are
displayed on the lcd in cycle.
The terminal D25~D28 are measuring circuit of 4~20mA DC signal, when
2
testing(Can be selected or not)
signal should be supplied by special equipment, direct apply signal of relay protection
tester is prohibited.
When the device is equipped with ungrounded system, terminal D07,D08 are zero
sequence small current input terminal, the ac current input should be limited to within
2A, the measuring current input should be limited to 6A, pay attention to the signal
input when testing to avoid large signal applied so as to avoid damage to
components.
Operating circuit inside the device is only applicable to DC power supply, if AC power
is used, it should be applied with rectifier and filter.
It is prohibited to plug or unplug the plug-ins, in order to avoid damage to the device.
It is prohibited to do digital output test when the device is running with primary
equipments.
Foreword
3
1. Product description
1.1 Scope of application
The MLPR-600Hb microcomputer line protection and monitoring device applies to the
line protection and monitoring in ungrounded systems or systems grounded via resistor
with voltage ratings of below 66kV. It can also be used as a current voltage protection and
monitoring device in 110kV grounded systems.
1.2 Function and specification
1.2.1 Protective function
3-step compounded voltage block directional overcurrent protection(Three-step OC)
Inverse time overcurrent protection(IT Overcurrent)
3-phase zero sequence voltage block zero sequence overcurrent directional
protection (ZS Overcurrent)
Zero sequence overvoltage protection(ZS Overvoltage)
Overload protection(Overload)
Under frequency unloading protection(Under-frequency)
Auto reclosing
Later Instantaneous Trip(Later Inst.Trip)
PT failure
Under voltage protection(Undervoltage)
Bus charging protection
Non-electric quantity protection(2-way)(Non-electric)(Can be selected or not)
Synchronous Closing(Sync. Closing)
1.2.2 Auxiliary function
Harmonic spectrum analysis
Phase display
Low current line selection
Fault recorder
Integral energy and pulse energy(Pulse energy can be selected or not)
Self-checking fault alarm of device
Remote calling and modification of protection’s settings
Fault recorder
One or two ways programmable output of 4~20mA
Provide ethernet print function(manual print setting value, manual/auto print reports)
(Can be selected or not).
1.2.3 Monitoring function
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
4
Electric quantity(remote measuring quantity):voltage, current, active power, reactive
power, active energy, reactive energy, power factor, grid frequency, non-electric
quantity measuring(Can be selected or not), etc.
Remote binary quantity: the device has 15-way binary input, in which: 12-way for
external gathering, and 3-way for internal gathering.
1.2.4 Communication capability
2 standard RS485 multipoint communication ports
2 industrial ethernet ports (Can be selected or not)
Supports single, dual network communication, it is fully qualified for network
redundancy and backup
IEC-60870-5-103(RS485 communication mode)、 IEC-60870-5-104( industrial
ethernet mode) standard communication protocol(Can be selected or not)
1.2.5 GPS clock synchronization function(Can be selected or not)
The device is able to receive GPS clock minute synchronization (or second
synchronization) through RS485 differentiate voltage, and it can be done with
monitoring system to accomplish GPS precise clock synchronization.
1.2.6 Device specifications
32-bit DSP microprocessor
Real-time multi-task operating system and C++ program techniques, realizing online
programming
Double-screen display (LCD Chinese display and nixie tube display), easy for
inspection
One or two ways 4~20mA DC quantity output, which can be set flexibly as any
corresponding electric quantity (such as current, voltage, power, frequency, etc.)
Collecting 4 ways of 4~20mA DC quantities for measurement of non-electric
quantities, such as temperature, pressure, and realizing online monitoring(Can be
selected or not)
Having the electric energy quality analysis function and perfect harmonic analysis
function
Integrating perfect metering functions
Excellent hardware interchangeability, easy user maintenance and reduced quantity
of spare parts
Protection output relays can be configured flexibly for user convenience
With remote/local changeover switch and trip/closing buttons, reducing the number of
elements on the board/cabinet panel and simplifying wiring
Using a 6U, 19/3‖ standard enclosure in a rear plug-in structure; the device can be
installed in site on a switchboard or combined in a centralized manner
1.2.7 Main technical specifications
Rated data
Power supply: DC/AC 86~265V
Operating voltage: DC 220V or DC 110V
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
5
AC voltage: 100/ 3 V or 100V
AC current: 5A or 1A
Frequency: 50Hz
Power consumption
DC circuit: <10W (normal operation); <15W (protection operation)
AC voltage circuit: <0.5VA/phase
AC current circuit: <1VA/phase (In = 5A); <0.5VA/phase (In = 1A).
Overload capability
AC voltage circuit: 1.2Un, continuous operation
Current measuring circuit: 1.2 In, continuous operation
Protective current circuit: 2In, continuous operation
10In, allowing 10s
40In, allowing 1s
Range and error of setting value
Maximum range of setting value:
Voltage element: 1V~120V
Current element: 0.1In~20In
Frequency: 45.00Hz~55.00Hz
Timing element: 0.00s~100.00s
Error of setting value:
Current and voltage setting value: ≤±3% of setting value
Frequency setting value: ≤±0.02Hz
Slip setting value: ≤±5% of setting value
Angle setting value: ≤±2°
Whole-group operation time (including relay’s intrinsic time):
Intrinsic operating time of current instantaneous overcurrent protection:
not greater than 40ms at 1.5 times the setting value
Intrinsic operating time of Difference instantaneous overcurrent
protection: not greater than 30ms at 2 times the setting value
Measuring accuracy
AC current: Class 0.2
AC voltage: Class 0.2
4~20mA DC quantity input: ≤±1%
Power: Class 0.5
Integral energy: Class 1 (active), Class 2 (reactive)
Frequency: ≤±0.02Hz
SOE resolution: ≤2ms
Pulse width of pulse quantity: ≥10ms
4~20mA DC quantity output: ≤±1%
Capacity of trip/closing output contact
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
6
Can be connected to DC 250V, 8A for prolonged periods.
GSP clock synchronization error
clock synchronization error≤2ms
Environmental conditions
Ambient temperature:
Operating:-20℃~+55℃。
Storage:-25℃~+70℃, rainproof and snow-proof rooms with relative humidity not
greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas;
no excitation quality is applied at the limits, the device shall not have any irreversible
change; after temperature restoration, the device shall operate properly.
Relative humidity: The average relative humidity of the most humid month shall not
be greater than 90%, the average minimum temperature of this month not lower than 25℃
and there shall be no surface condensation; at the highest temperature of +40℃, the
average maximum humidity shall not exceed 50%. Atmospheric pressure: 80kPa~110kPa (below relative altitude of 2wc)
1.2.8 Hardware structure
The device uses a 6U, 19/3‖ standard enclosure, with aluminum alloy casing and installed by overall embedding. The display panel is mounted in the front, and the other plug-in modules are rear mounted. From the rear view, the power, I/O, CPU and AC plug-in modules are from the left to the right.
External dimensions and boring diagram
Structural and dimensional diagram Boring diagram for installation
Devices fabricated on-screen steps: first release on-screen stents unfastening screws,
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
7
Compounded voltage lock
≥
&
&
&
&
On/Off
TglTrip
output
Ia>Igl
Direction judgement
Direction judgement
Direction judgement
Direction judgment On/Off
Ib>Igl
Ic>Igl
Protection On/OFF
remove the stents; installed the device on the screen from the front and push until close to
the fixed plate; install the stent 2, and then stent 1, and then use fastening screw to
insertion hole from rear of stent1, and then screwed into stent 2 and tighten screw; the
stents from up and down are installed in the same way; use grounding screws to connect
grounding line.
2. Function of device
2.1 3-step compound voltage block directional overcurrent protection
(Three-step OC)
Each step can be set that it is blocked by compound voltage(the negative sequence
voltage is synthesized from the phase voltages, and minimum line voltage is used for
undervoltage block)and direction. The operation logic diagram of the compound voltage
block directional overcurrent protection is shown in Figure 2-1. When the ―Overcurrent
negative direction‖ is switched on, the operation zone of overcurrent step III is opposite
to that only when overcurrent step III direction is switched on.
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
8
U
I45
º
90º
10º
10º
160º
Figure 2-1 Operation logic of compound voltage block directional overcurrent
The inter-phase directional component uses 90°wiring mode and it is started by
phase.The current component of any phase can only be controlled by directional
component which are in the Table 2-1.
Table 2-1
Inter-phase directional
component
Iφ Uφφ
A Ia Ubc
B Ib Uca
C Ic Uab
Arg(Uφφ/Iφ)=-125°~35°,the boundary value is not very exact and the error is less
than ±2°.
Figure 2-2 Operation zone of inter-phase directional component
2.2 Inverse time limit overcurrent protection(IT Overcurrent )
In the heat accumulation mode, the time limit of the protection output shall not be less
than 40ms, and the inverse time limit characteristic can be:
a.Standard inverse time limit; curve equation: t = 0.14τ/[(I/Ip)0.02
-1]
b.Unusual inverse time limit; curve equation: t = 13.5τ/[(I/Ip) -1]
c.Extreme inverse time limit; curve equation: t = 80τ/[(I/Ip)2 -1]
d.Long inverse time limit; curve equation: t = 120τ/[(I/Ip) -1]
Where: I is the fault current, Ip is the setting value of the inverse time limit starting
current, τ is the time constant (0.01-1.00s).
The operation logic diagram of the Inverse time limit overcurrent protection is shown
in Figure 2-3.
Figure 2-3 Operation logic of inverse time limit overcurrent
2.3 3-step directional Zero sequence overcurrent protection(ZS Overcurrent)
IT overcurrent On/Off
Output sequence
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
9
In major grounding systems, the ground current is relatively high, the zero sequence
overcurrent protection of Step I, II trips directly, and that of Step III can be set as alarm or
trip for ungrounded systems. All the 3 steps of the zero sequence overcurrent protection
can be set to block in the direction of the zero sequence voltage. For ungrounded systems,
the zero sequence current is directly collected from the low current signal of the special zero
sequence CT.
The zero sequence Step III can switch on either alarm or trip. When both are
switched on, the trip function is enabled, the alarm function is released automatically.
For ungrounded systems, when a ground fault occurs in the system, the zero
sequence current of the ground fault point is basically a capacitive current with small
amplitude. If a zero sequence overcurrent relay is used to protect it from ground faults, its
selectivity can hardly be guaranteed. The device uploads the amplitude and direction of
the zero sequence current by communication, and the upper computer performs low
current ground wire selection.
The directional zero sequence overcurrent operation logic is shown in Figure 2-4.
Figure 2-4 Operation logic of directional zero sequence overcurrent
Zero sequence directional components set the operation zone separately for
grounding directly(grounding via low resistance),grounding via medium resistance(or
grounding via extinguishing coil), ungrounding(grounding via high resistance).The zero
sequence voltage which is related to direction judgment uses zero sequence voltage
calculation for direction judgment when PT wiring is YY or there is no PT failure (PT
failure function should be switched on).To use the external open-delta voltage for
direction judgment when PT wiring is VV or there is a PT failure (PT failure function
should be switched on).
Grounding directly: Arg(3U0/3I0)= -30 º~-190 º
Grounding via medium resistance: Arg(3U0/3I0)= 100 º~260 º
Ungrounding: Arg(3U0/3I0)= 10º~170 º
2.4 Zero sequence Overvoltage protection(ZS Overvoltage)
A one-step definite time limit zero sequence overvoltage protection is provided, which
can be set as trip or alarm. When the trip function is switched on, the alarm function is
released automatically. The zero sequence overvoltage operation logic is shown in Figure
Trip output/alarm output
I0>I0gl
Zero-sequence over-current direction judgment
Zero-sequence over-current direction judgment On/Off
&
Zero-sequence over-current
protection On/Off TU0>U0bsZero-sequence voltage lock On/Off
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
10
2-5.
Figure 2-5 Operation logic of zero sequence overvoltage
2.5 Overload protection
A one-step definite time limit overload protection is provided, which can be set as trip
or alarm. When the trip function is switched on, the alarm function is released
automatically. The overload operation logic is shown in Figure 2-6.
Figure 2-6 Overload operation logic
2.6 Under-frequency unloading protection(Under-frequency)
The frequency is derived from software calculation, calculate frequency using voltage
UAB. The unloading protection is blocked by undervoltage block, under-current block or
slip block, in which slip block can be switched On/Off. The operation logic of
under-frequency unloading is shown in Figure 2-7.
Figure 2-7 Operation logic of under-frequency unloading
2.7 3-phase primary reclosing
The reclosing delay can be set, the whole operation process is completed in a single
charge(15s);
There are 2 starting modes for reclosing: non-corresponding start and protection start
(overcurrent protection and zero sequence overcurrent protection); the software has
On/Off control words;
Condition of reclosing block: manual trip, remote controlled trip, external input block,
etc.
After closing the reclosing output for 600ms, the reclosing control signal will return.
Reclosing operation logic is shown in Figure 2-8. Reclosing synchronization check
doesn’t judge the frequency difference when PT is failure.
Trip/alarm output&Tgdy
Zero sequence
over-voltage On/off
U0>Ugdy
Circuit breaker at
closed position
Low-frequency unloading
On/Off Low-frequency
unloading protection
output sequence
Protection On/Off Output sequence
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
11
Figure 2-8 Reclosing operation logic
2.8 Post-acceleration
A one-step overcurrent post-acceleration and zero sequence overcurrent
post-acceleration protection is provided, which can be closed manually or remotely and
started by reclosing, with an opening time of 3s. The overcurrent acceleration and zero
sequence acceleration can be switched On/Off separately, and their current and delay can
be set separately. The operation logic of post-acceleration is shown in Figure 2-9.
Figure 2-9 Operation logic of post-acceleration
2.9 PT failure
The judgment criterion of PT failure depends on the wiring mode. When the PT failure
block function is switched on, if PT failure occurs, the undervoltage protection will block
the compound voltage component and current directional component. The judgment
criterion of PT failure is as follows:
V-V wiring mode
The current value of the phase with the maximum current is less than the maximum
load current (using the setting value of the overload current).
Automatic reclosing
output
Reclosing start
Switch open position
Reclosing charging indication =1
&
&
&
Reclosing On/Off
Tzdchz
Synchronization
check On
UL< synchronization check setting value
Frequency difference <0.5Hz
UL>80%Un
15s Reclosing charging indication =1Circuit breaker at closed position
Voltage difference <10V
Reclosing lock
Phase difference < setting value
Reclosing lock
&
Maximum phase current < 0.1In
&
≥
Au
tom
atic
reclo
sing
No-voltage
check On
Post-accel eration start
Po st -accel eration st art d el ay <3s
Post-accel eration input On/Off
Post-accel eration
operation message
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
12
① Maximum inter-phase voltage < 30V, and current of any phase > 0.1In;
② Negative sequence voltage > 8V
If any of the above conditions is met, the delay (settable) will report PT failure, and will
return when failure disappears.
Y-Y wiring mode
The current value of the phase with the maximum current is less than the maximum
load current (using the setting value of the overload current).
① When |Ua+Ub+Uc|>7V, and the modulus difference between the maximum and
minimum line voltages is greater than 18V, it is thought one or 2 phases have PT failure;
② |Ua+Ub+Uc∣> 7V, the minimum line voltage is less than 18V, used for detecting
2-phase failure.
③ When MAX{Uab,Ubc,Uca}<7V,and the current of any phase > 0.1In, it is regarded
as PT 3-phase failure.
If any of the above conditions is met, the delay (settable) will report PT failure, and will
return when failure disappears.
Figure 2-10 Operation logic of PT failure
2.10 Undervoltage protection(Undervoltage)
The inter-phase maximum voltage is taken as the voltage component for
undervoltage splitting. If the maximum line voltage is less than the undervoltage setting
value, it will trip after a delay. PT failure block low voltage protection should be set to
prevent PT failure from the wrong operation of low voltage. The operation logic of the
undervoltage protection is shown in Figure 2-11.
PT failure information
&
TPT
PT failure On/Off
|MaxU-MinU|>18V
&MinU<18V
&
MaxU<7VMaxU=Max(Uab,Ubc,Uca)MinU=Min(Uab,Ubc,Uca)
&
MaxU<30V
U2>8V
≥
&V-V wiring
Max{Ia,Ib,Ic}>0.1*In
≥
Max{Ia,Ib,Ic}<Igfh
&
≥
&
Max{Ia,Ib,Ic}>0.1*In
7V|cUbUaU|
7V|cUbUaU|
PT failure component
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
13
Figure 2-11 Operation logic of undervoltage protection
2.11 Non-electric quantity protection(4-20mA input.This function can be
selected or not. If it is not be selected , the contents related to DCS input in the
terminal figure have no meaning.)
The device has the 2-way non-electric quantity protection function, switched on/off by
control word.
2.12 Bus charging protection(Bus Charging)
The maximum current of phase is taken as current component for bus charging
protection. The bus charging protection starts for 3s when it is switched by manual or
telecontrol. If fault current is greater than setting value of bus charging in 3s and reaches
the delay, the bus charging protection will operate.
Figure 2-12 Operation logic of bus charging protection
2.13 Synchronization closing(Sync. Closing)
Synchronization closing function has two modes: manual synchronization closing
and remote control synchronization closing.
Synchronization closing function can check synchronous date and no-voltage
automatically. When the voltage of any side of line is less than the setting value of
no-voltage, the device will send closing pulse directly. When the voltage of two ends both
are greater than 80% of rated voltage (line voltage: 100V, voltage of phase: 100/ 3 V), it
will check synchronization and it will switch on if the synchronous conditions are met. If
synchronization time is up and it is not successful, the device will report ―synchronizat ion
closing failure‖.
Manual closing for synchronization is reclosing output.
Remote control closing for synchronization is remote closing output.
Output sequence
I>Iset
Remote closure
&
Bus charging On/Off
TManual closure
≥
3s opening time
Protection output
sequence&TddyLow-voltage On/Off
Umax>30V
PT breakPT break lock
Umax<Uddy
Circuit breaker at closed position
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
14
Manual closure input from
opening to closingManual closure
synchronization On
Remote controlling
closure commond
Remote closure
synchronization On
&
Frequency difference < setting value
Angle difference < setting value
Voltage difference <setting value
Synchronization time<setting value
Remote controlling closure output
≥
Voltage at this side < no-voltage
setting valueVoltage at opposite side < no-voltage
setting value
≥
With voltage at two sides
Reclosure output
&
&
Synchronization closing logic is as follows:
Figure 2-13 Synchronization closing function logic figure
2.14 Pulse energy/integral energy
Pulse energy(Can be selected or not)
The pulse circuit of the device uses an internal power supply, passive energy pulses
are input from the outside; and accumulation of pulse energy is finished by the software.
Integral energy
The software accumulates active and reactive powers into active and reactive energy
in real time.
2.15 Fault recorder
See the communication coding table for the protection voltage and current waveform
data collected by the recording unit.
3. Setting of parameters and setting values of the device
3.1 System parameters
Parameter Range Description
Setting of basic parameters
Ratting Current 0-1 Set step:1(factory default 0)00:5A;01:1A
PT Ratio 1-1500 Set step:1(factory default 1)
CT Ratio 1-5000 Set step:1(factory default 1)
CT wiring mode 0-1 Set step:1(factory default 0)00:3-phase;01:2-phase
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
15
Parameter Range Description
PT wiring mode 0-1 Set step:1(factory default 0)00:Y-Y;01:V-V
Harmonic Channel 0-12
For harmonic calculation, select the corresponding reference
quantity:
0:exit from harmonic calculation function
1:Ia,2:Ib,3:Ic,4:I0,5:IA,6:IB,7:IC,8:Ua,9:Ub,10:Uc,11:U0,12:UL
Wave Record 0-1 Set step:1(factory default 0)00:Off;01:On
Earth Mode 0-2 00:No Earth, 01:Earth(major grounding),
02:Res.Earth(grounding via resistor)
Bus Voltage 0-5 0:Ua、1:Ub、2:Uc、3:Uab、4:Ubc、5:Uca
D/A channel settings
DA1~2 channel
selection 0-14
Select DA1~2 to output corresponding reference quantities:
0:No D/A output
1:IA,2:IB,3:IC,4:Ua,5:Ub,6:Uc,7:Uab,8:Ubc,9:Uca,10:P,11:Q
Voltage reference quantity: 0-120V corresponding to
4mA-20mA,
Rating 5A:
Current reference quantity: 0—6A corresponding to
4mA—20mA,
Power reference quantity: 0—1000W corresponding to
4mA—20mA。
Rating 1A:
Current reference quantity: 0—1.2A corresponding to
4mA—20mA,
Power reference quantity: 0—200W corresponding to
4mA—20mA。
DA1~2 adjustment
Factor 0.5-1.5 Adjust parameters of D/A Channels 1~2 (4-20mA)
3.2 List of setting values
Setting value Range Description
Pro
tectio
n o
n/o
ff word
Instantaneous Protect On/Off
(Inst.PROT) 1/0 1/0:On/Off (factory default Off)
Delay Instantaneous Protect
On/Off
(Delay Inst.PROT)
1/0 1/0:On/Off (factory default Off)
Definite Time Overcurrent On/Off
(DT Overcurrent) 1/0 1/0:On/Off (factory default Off)
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
16
Setting value Range Description
Instantaneous Overcurrent
Directional On/Off
(Inst.OC Dir.)
1/0 1/0:On/Off (factory default Off)
Delay Instantaneous Directional
On/Off
(Delay Inst.Dir.)
1/0 1/0:On/Off (factory default Off)
Definite Time Overcurrent
Directional On/Off
(DT OC Dir.)
1/0 1/0:On/Off (factory default Off)
Definite Time Overcurrent Negative Directional On/Off
(DT OC Neg.Dir.)
1/0 1/0:On/Off (factory default Off)
Instantaneous Compound
Voltage Lock On/Off
(Inst.CV Lock)
1/0 1/0:On/Off (factory default Off)
Delay Compound Voltage Lock
On/Off (Delay CV Lock) 1/0 1/0:On/Off (factory default Off)
Definite Time Overcurrent
Compound Voltage Lock On/Off
(DT OC CV Lock)
1/0 1/0:On/Off (factory default Off)
Inverse Time Overcurrent
(IT Overcurrent ) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overcurrent 1
Protect (ZS OC 1 PROT) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overcurrent 2
Protect (ZS OC 2 PROT) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overcurrent 3
Alarm (ZS OC 3 Alarm) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overcurrent 3
Trip (ZS OC 3 PROT) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overcurrent 1
Directional (ZS OC 1 Dir.) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overcurrent 2
Directional (ZS OC 2 Dir.) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overcurrent 3
Directional (ZS OC 3 Dir.) 1/0 1/0:On/Off (factory default Off)
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
17
Setting value Range Description
Zero Sequence Overcurrent 1 U0
Lock (ZS OC 1 U0 Lock) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overcurrent 1 U1
Lock (ZS OC 2 U0 Lock) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overcurrent 1 U2
Lock (ZS OC 3 U0 Lock) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overvoltage
Alarm (ZS OV Alarm) 1/0 1/0:On/Off (factory default Off)
Zero Sequence Overvoltage Trip
(ZS OV PROT) 1/0 1/0:On/Off (factory default Off)
Overload alarm 1/0 1/0:On/Off (factory default Off)
Overload Protect (Overload PROT)
1/0 1/0:On/Off (factory default Off)
Undervoltage Protect (Undervoltage)
1/0 1/0:On/Off (factory default Off)
Under-frequency unloading (Under-frequency)
1/0 1/0:On/Off (factory default Off)
Slip block 1/0 1/0:On/Off (factory default Off)
Protect Start Auto Reclosing
(PROT Start ARC) 1/0
Inconsistent Start Auto Reclosing
(Incon.Start ARC) 1/0
Synchronous Start Auto
Reclosing (Sync.Start ARC) 1/0 1/0:On/Off (factory default Off)
Dead Line Start Auto Reclosing
(Dead L Start ARC) 1/0 1/0:On/Off (factory default Off)
Overcurrent Later Instantaneous (OC Later Inst.)
1/0 1/0:On/Off (factory default Off)
Zero Sequence Later Instantaneous (ZS Later Inst.)
1/0 1/0:On/Off (factory default Off)
PT failure alarm 1/0 1/0:On/Off (factory default Off)
PT failure lock () 1/0 1/0:On/Off (factory default Off)
Non-electric quantity 1 (Non-electric 1)
1/0 1/0:On/Off (factory default Off)
Non-electric quantity 2 (Non-electric 2)
1/0 1/0:On/Off (factory default Off)
Bus charging protection
(Bus Charging) 1/0 1/0:On/Off (factory default Off)
Manual synchronization On/Off
(Manual Sync.) 1/0 1/0:On/Off (factory default Off)
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
18
Setting value Range Description
Remote control synchronization
On/Off
(Remote Sync.)
1/0 1/0:On/Off (factory default Off)
3-phase definite time limit overcurrent protection
Compound voltage block undervoltage
(Undervoltage)
60.00-90.00V Set step:0.01V(factory default 90V)
Negative sequence voltage (NS Voltage)
5.00-30.00V Set step:0.01V(factory default 10V)
Instantaneous current (Inst.Current)
(0.1-20)In Set step:0.01A(factory default 20In)
Delay instantaneous current (Delay Inst.C)
(0.1-20)In Set step:0.01A(factory default 20In)
Definite time overcurrent (DT Overcurrent)
(0.1-20)In Set step:0.01A(factory default 20In)
Instantaneous time (Inst.Time)
0.00-100.00s Set step:0.01s(factory default 100s)
Delay instantaneous time (Delay Inst.Time)
0.00-100.00s Set step:0.01s(factory default 100s)
Definite time overcurrent time (DT OC Time)
0.00-100.00s Set step:0.01s(factory default 100s)
Inverse time limit overcurrent protection
Inverse time trait curve
(IT Trait Curve) 1-4 Set step:1(factory default 1)
Inverse time time contant
(IT Time Contant) 0.01-1.00s Set step:0.01(factory default 1.00)
Inverse time start current
(IT Start Current) (0.1-2)In Set step:0.01A(factory default 1In)
Zero sequence overcurrent protection
Zero sequence voltage Lock
(ZS Voltage Lock) 30.00-100V Set step:0.01V(factory default 90V)
Zero sequence overcurrent 1 (ZS Overcurrent 1)
0.1-2A Set step:0.01A(factory default 2A)
(Using a system with neutral point
ungrounded as an example)
Zero sequence overcurrent 2 (ZS Overcurrent 2)
0.1-2A
Zero sequence overcurrent 3 (ZS Overcurrent 3)
0.1-2A
Zero sequence overcurrent 1 Time (ZS OC 1 Time)
0.00-100.00s Set step:0.01s(factory default 100s)
Zero sequence overcurrent 2
Time (ZS OC 2 Time) 0.00-100.00s Set step:0.01s(factory default 100s)
Zero sequence overcurrent 3 Time (ZS OC 3 Time)
0.00-100.00s Set step:0.01s(factory default 100s)
Zero sequence overvoltage
Zero sequence overvoltage 2-100V Set step:0.01V(factory default 100V)
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
19
Setting value Range Description
(ZS Overvoltage)
Zero sequence overvoltage
Time (ZS OV Time) 0.00-100.00s Set step:0.01s(factory default 100s)
Overload protection
Overload current
(Overload Current) (0.1-20)In Set step:0.01A(factory default 20In)
Overload time
(Overload Time) 0.00-100.00s Set step:0.01s(factory default 100s)
Undervoltage protection
Undervoltage value (Undervolt. Value)
30-100V Set step:0.01V(factory default 50V)
Undervoltage time (Undervolt. Time)
0.50-100.00s Set step:0.01s(factory default 100s)
Under-frequency unloading
Under-frequency unloading (Under-freq.Value)
45.00-50.00Hz Set step:0.01Hz(factory default 48Hz)
Under-frequency time (Under-freq.Time)
0.50-100.00s Set step:0.01s(factory default 100s)
Low current lock 0.2-5A Set step:0.01A(factory default In)
Undervoltage lock (Undervolt. Lock)
10.00-90.00V Set step:0.01V(factory default 90V)
Slip block 0.5-8.00Hz/s Set step:0.01Hz/s(factory default 3Hz/s)
Reclosing
Auto reclosing time (ARC Time)
0.00-10.00s Set step:0.01s(factory default 1s)
Auto reclosing sync-angle (ARC Sync-Angle)
0.00-50.00° Set step:0.01°(factory default 20°)
Auto reclosing dead line Voltage (ARC Dead Line V)
10.00-50.00V Set step:0.01V(factory default 60V)
Post-acceleration
Overcurrent later instantaneous current
(OC Later Inst.C)
(0.02-20)In Set step:0.01A(factory default 20In)
Zero sequence later instantaneous current
(ZS Later Inst.C)
0.1-2A Set step:0.01A(factory default 1A)
Overcurrent later instantaneous time (OC Later Inst.T)
0.00-3.00s Set step:0.01s(factory default 3s)
Zero Sequence later instantaneous time
(ZS Later Inst.T)
0.00-3.00s Set step:0.01s(factory default 3s)
PT failure setting value
PT failure delay 0.50-10.00s Set step:0.01s(factory default 10s)
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
20
Setting value Range Description
Non-electric quantity protection
Non-electric 1 value (Non-elec.1 Value)
4.00-20.00mA Set step:0.01mA(factory default 20mA)
Non-electric 1 time (Non-elec.1 Time)
0.00-100.00s Set step:0.01s(factory default 0s)
Non-electric 2 value (Non-elec.2 Value)
4.00-20.00mA Set step:0.01mA(factory default 20mA)
Non-electric 2 time (Non-elec.2 Time)
0.00-100.00s Set step:0.01s(factory default 0s)
Bus charging protection
Bus charging current
(Bus Char.Current) 0.1-100.00A Set step:0.01A(factory default 100A)
Bus charging time
(Bus Char.Time) 0.00-3.00s Set step:0.01s(factory default 0s)
Synchronization closing
Synchronization voltage
difference
(Udiff-SyncClose)
0.03-10V Set step:0.01V(factory default 10V)
Synchronization frequency
difference
(Fdiff-SyncClose)
0.1-2Hz Set step:0.01HZ(factory default 2Hz)
Synchronization angle
difference
(Adiff-SyncClose)
10-30° Set step: 0.01°(factory default 10°)
Synchronization time
(T-SyncClose) 1-100s Set step:0.01s (factory default 100s)
Synchronization no-voltage
check (No-Voltage-Sync)
5-90V Set step:0.01V(factory default 10V)
4. Description of binary input, output and analog quantity
4.1 Monitoring of analog quantities
Analog quantities can be monitored under the [Protection Data Display], [Measured
Data Display] and [Pulse Energy] menus in the [State Display] menu, press the ――,
―― keys to flip over. The factory precision of the device has been calibrated. The
protection current is calibrated at double the rated current and the measuring current at a
single rated current. The list is as follows:
Note: for protection CT 3-phase, PT Y-Y wiring; due to the under-frequency
unloading protection of this device, the frequency display is put in the protection data.
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
21
Analog quantity
terminal
Analog quantity
name Test method
Terminals D01、D02 Protective Phase A
current (Ia)
Add double the rating, displayed deviation not
exceeding 1%
Terminals D03、D04 Protective Phase B
current (Ib)
Add double the rating, displayed deviation not
exceeding 1%
Terminals D05、D06 Protective Phase C
current (Ic)
Add double the rating, displayed deviation not
exceeding 1%
Terminals D07、D08 Zero sequence
current (I0) Add 1A, displayed deviation not exceeding 0.2%
Terminals D09、D10 Measured Phase A
current (IA) Add rating, displayed deviation not exceeding 0.2%
Terminals D11、D12 Measured Phase B
current (IB)
Add a single rating, displayed deviation not exceeding
0.2%
Terminals D13、D14 Measured Phase C
current (IC)
Add a single rating, displayed deviation not exceeding
0.2%
Terminals D15、D16 Phase A voltage
(Ua) Add 50V, displayed deviation not exceeding 0.5%
Uab System frequency F Add 50V 50Hz, displayed deviation not exceeding
±0.02Hz
Terminals D17、D18 Phase B voltage
(Ub) Add 50V, displayed deviation not exceeding 0.5%
Terminals D19、D20 Phase C voltage
(Uc) Add 50V, displayed deviation not exceeding 0.5%
Terminals D21、D22 Zero sequence
voltage (U0) Add 50V, displayed deviation not exceeding 0.5%
Terminals D23、D24 Line voltage (UL) Add 50V, displayed deviation not exceeding 0.5%
Terminals D23、D24 Line frequency(F) Add 50V 50Hz, displayed deviation not exceeding
±0.02Hz
Terminals D25、D26 4~20mA DC Input
1 Add 10mA, displayed deviation not exceeding 3%
Terminals D27、D28 4~20mA DC Input
2 Add 10mA, displayed deviation not exceeding 3%
Terminals D09、D10;
D13、D14 add current
by polarity;D15、D16;
D17、D18;D19、D20
add voltage by polarity
3-phase active
power
Add a single rating to current and 100V to line voltage
Alter phase angle, displayed power deviation not
exceeding 0.5%
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
22
Analog quantity
terminal
Analog quantity
name Test method
Terminals D09、D10;
D13、D14 add current
by polarity;D15、D16;
D17、D18;D19、D20
add voltage by polarity
3-phase reactive
power
Add a single rating to current and 100V to line voltage
Alter phase angle, displayed power deviation not
exceeding 2%
Terminals C12 and
C16(common terminal
of pulse +24V)
Pulse 1(MC1) Connect each point once, add 1 to the count
Terminals C13 and
C16(common terminal
of pulse +24V)
Pulse 2(MC2) Connect each point once, add 1 to the count
Terminals C14 and
C16(common terminal
of pulse +24V)
Pulse 3(MC3) Connect each point once, add 1 to the count
Terminals C15 and
C16(common terminal
of pulse +24V)
Pulse 4(MC4) Connect each point once, add 1 to the count
4.2 Monitoring of binary input
Binary input can be monitored under the [Binary input] menu in the [State Display]
menu, press the ――, ―― keys to flip over.
Binary input
terminal
Binary input name Test method
B01 Common terminal of binary
input -
(Should be connected to
DC220V or DC110V
negative terminal of external
power supply)
External power supply of 220V or 110V
DC can be applied, connect the
negative terminal to terminal B01,
positive terminal to terminal B02~B13,
in [Binary input] menu in the [State
Display], the status of binary input can be
seen.
The device also has a 24V DC
supply, if it is used, terminal B14 can be
connected to terminal B02 ~ B13, in
[Binary input] menu in the [State Display],
the status of binary input can be seen.
B02 Breaker position
B03 Trolley run position
B04 Trolley test position
B05 Earth switch position
B06 Spring is not energized
B07 Input 6
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
23
B08 Input 7 Please note about the binary input
voltage upon ordering, it is set to
DC220V by default.
B09 ARC Lock
B10 Input 9
B11 Input 10
B12 Input 11
B13 Chk.Sync.Manu.
B14 Positive terminal of internal
24V power supply
4.3 Monitoring of binary output
Binary output can be monitored under the [Binary output] menu, press the ――,
―― keys to flip over.
Binary output terminals Binary output name Test method
B15-B16 Device Failure
Select open and close menu, use ―+‖,
―-‖ key to operate and test the
corresponding terminals. B31-B32
and B34-B35 are common open
terminals that should close.
B17-B18 Trip Signal
B19-B20 Alarm Signal
B21-B22 Chk.Sync.Manu.
B23-B24 Output 5
B25-B26 PROT Output 1
B27-B28 PROT Output 2
B29-B30 Reclose Output
B31-B32(Common
open) Output 9
B32-B33
B34-B35(Common
open) Output 10
B35-B36
A22-A23 Remote Close
A22-A24 Remote Trip
5. Operation instructions
5.1 Control panel of device
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
24
128*64 matrix LCD (The LCD will go off after a period of absence of keyboard operation;
the LCD will be illuminated automatically when any key is pressed or in case of
protection trip or alarm.)
Signal indicator: operation, communication, operation, alarm, reclosure, fault (of the
device)
Circuit breaker state indication: indicating the current state of the circuit breaker (―Open‖,
―Close‖ position indication)
Remote/local selection signal, local opening/closing button
Key pad: , , , , Cancel, -, +, Enter, Revert
The 6-bit nixie tube displays the primary measured values in real time: IA, IB, IC, Uab,
Ubc, Uca, P, Q, Cosφ. (Please set the PT, CT transformation ratios properly in the System
Parameters menu). The maximum display range of the power on the nixie tube is: 99999. Note: Measurement IA: AA, measurement IB: bA, measurement
IC: CA,
voltage Uab: AbKV, voltage Ubc: bCKV, voltage Uca: CAKV,
active power: PKW, reactive power: qKVar, power factor: H
5.2 Instructions for use of key pad and LCD display
During the device’s normal operation, it will display the measuring current, power,
time and statue (indicating whether reclosure charging is finished) in cycle. Press the
―Enter‖ key to enter the main menu, which is a multi-level tree menu. Press the ――,
―― keys to move the cursor to the desired entry, press the ―Enter‖ key to enter this entry,
and press the ―Cancel‖ key to return to the next higher level of screen. If this screen is still
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
25
Main menu
1·State Display
2·Signal Revert
3·Report Display
4·Output Test
5·SYS Parameters
6·Setting Value
7·Clock Setting
8·Password
9·Version Info
a menu, continue to press the ――, ―― key to select the desired entry, press the ―Enter‖
key to enter the next level of screen, and press the ―Cancel‖ key to return to the next
higher level of menu. If there is no menu screen, be sure to press the ―Cancel‖ key to
return to the next higher level of menu. The main menu is shown at the center of the
following figure, with the corresponding submenus on both sides.
The main interface displays the primary operating parameters in turn. The maximum
displayed value of the primary is 6000.0A. For systems with a rated current of 5A, the set
CT transformation ratio shall not exceed 2000. If the primary power is greater than
1000kW, the display unit is MW, otherwise is kW.
Note 1: For the Setting menu, see the description of each device.
State Display
5.Parameters
Setting Zero No.
Comm. Setting
B. Parameters
D/A Setting
Pulse Energy
Trip Times Clear
Channel Coef.
7.Clock setting
Date:□□-□□-□□
Time:□□:□□:□□
8. Password
□□□□
Model:M□PR-600Hb
Version:V□.□□.□□
Date:20□□-□□-□□
CRC:□□□□□□□□H
1.State Disp
Protection Data
Measuring Data
Binary Input
Pulse Energy
Phase Angle
Harmonic Data
DC Input Data
Trip Times
2.Signal Revert
Enter
3.Report Dis.
Trip Report
Binary Report
Event Report
Report Clear
4.Output Test
Device Failure
Trip Signal
Alarm Signal
Chk.Sync.Manu.
Output 5
PROT Output 1
PROT Output 2
Reclose Output
Output 9
Output 10
Remote Close
Remote Trip
6.Settings(Note 1)
Protect On/Off
。。。。。。
Note: See protection
setting table for detailed
setting menus
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
26
The [State Display] menu contains 8 submenus, including protection data, measuring
data, binary input, pulse energy, angle display, harmonic data, DC measurement and trip
statistics. It is described as follows:
Note: In the standard configurations, the input circuit has the connection to an
external 220VDC control power supply. When no DC control power supply or control
system is available on site, but a 110VDC control power supply is available, a 110VDC
control power supply may be used for direct connection through local hardware
Protection Data ↑ ↓
Ia = □□□·□□ A
Ib = □□□·□□ A
Ic = □□□·□□ A
Uab = □□□·□□ V
Ubc = □□□·□□ V
Uca = □□□·□□ V
U2 = □□□·□□ V
U0 = □□□·□□ V
I0 = □□□·□□ A 。。。。。。
Protection CT secondary current value
PT secondary line voltage value
Zero sequence current
Zero sequence voltage
Measuring Data ↑ ↓
IA = □□□·□□ A
IB = □□□·□□ A
IC = □□□·□□ A
Ua = □□□·□□ V
Ub = □□□·□□ V
Uc = □□□·□□ V
P = □□□□·□ W
Q = □□□□·□ var
Cosφ = □·□□□ 。。。。。。
Measuring CT secondary current value
PT secondary phase voltage value
Cosine function for included angle of voltage and
current; for -90°<φ<90°, COSφ is positive; for 90°<
φ<270°, COSφ is negative
Converted to PT, CT secondary active power
Converted to PT, CT secondary reactive power
When Closed, energy storage not completed
Binary Input ↑ ↓
Breaker: □
Trolley Run: □
Trolley test: □
Earth Switch : □
Spring: □
Input 6 : □
Input 7 : □
ARC Lock : □
Input 9 : □
Input 10 : □
。。。。。。
Description varies with model, see corresponding terminal
diagram for details
At Closed, breaker is at closed position; at Open, breaker is at open
position. Note: The position of the breaker relates to protection logic,
with fixed position.
When Closed, trolley at running position
When Closed, earth switch at closed position
When Closed, trolley at test position
Negative seque.voltage
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
27
adjustment, or the 24V power supply of the device may be used as the input power supply
(when the input common terminal is +24V, terminal number: B14, Terminal B01 is kept
float). However, this must be specified upon ordering.
Trip Times
Total □□□□ times
Phase Angle ↑ ↓
Ua:□□□·□□°
Ub:□□□·□□°
Uc:□□□·□□°
Ia:□□□·□□°
Ib:□□□·□□°
Ic:□□□·□□°
IA:□□□·□□°
IB:□□□·□□°
IC:□□□·□□°
UL:□□□·□□° 。。。。。。
Phase angle relative to Ua, Ua as 0° by default.
When wiring method is VV, it displays line voltages
relative to Uab, the same as follows
Phase angle of protection current relative to Ua
Phase angle of measuring current relative to
Ua
Pulse Energy ↑ ↓
MC1:□□□□□□□□□□
MC2:□□□□□□□□□□
MC3:□□□□□□□□□□
MC4:□□□□□□□□□□
+□□□□□□□·□□□kWh
+□□□□□□□·□□□kvh
-□□□□□□□·□□□kWh
-□□□□□□□·□□□kvh
External pulse energy input counting (4-way)
DC Input ↑ ↓
DC1:□□□·□□mA
DC2:□□□·□□mA External DC input 4~20mA (2-way)
Accumulation of the device’s real-time active and reactive
calculations over time, + for positive direction, - for negative
direction.
Harmonic ↑ ↓
I2: □□□·□□%
I3: □□□·□□%
I4: □□□·□□%
I5: □□□·□□%
。。。。。。
I11: □□□·□□%
2~31st harmonics for which analog channels have been
selected in system
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
28
Signal revert
In the [Signal Revert] menu, press the ―Enter‖ key, the signal relay and the ―Operation‖
indicator on the panel will be reset.
Report Display
The [Report Display] menu includes 4 submenus, including trip report, binary report, event report and report clear. Event recording includes: device self-check fault, device setting value modification, system parameter modification and setting zone number modification, etc. Trip report can be record for the last 50 events, binary report for 100, event report for 30 at most. Beyond this, the latest report will overwrite the earliest one. Press the ―Enter‖ key to enter the corresponding [To view xx report, please enter report
number: 00 ] menu, and enter any figure within storage volume, press the ―Enter‖ key to display the contents of that report. The screen is as follows:
Press key to see the specific operation value. Press and keys to flip over.
Operation values
Output test
After entering the [Output Test] menu, the correct password is required to enter the
[Output Test] menu. It displays the following:
Press ―Enter‖ key
——————>
<——————
Press ―Cancel‖ key
(Note: When the test is performed on the 6 protection outputs, the starting relay will
be in the ―Closed‖ state automatically. The ―+‖, ―-‖ keys are used for switching between the
―Close/Open‖ control.)
System parameters
After entering the [SYS Parameters] menu, the correct password is required to enter
the [SYS Parameters] menu. It displays the following:
4.Output test ↑ ↓ Device Failure
Trip Signal Alarm Signal Chk. Sync. Manu Output 5 PRO Output1 PRO Output2
。。。。。。
Operate All
Device Failure
Close Open
Report No.:□□ ↓
20□□-□□-□□
□□:□□:□□:□□□
□□□□□□
Report No. of this report
Year, month, day, hour, minute, second and
millisecond when it took place
报告内容描述
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
29
Setting Zone No.: range 00~07.
Comm. setting
Setting of basic parameters (see the description of the protection device for basic
parameters)
5.Parameters ↑↓
Setting Zone No.
Comm. Setting
Basic Parameters
D/A setting
Pulse Energy
Trip Time Clear
Channel Coef.
Comm. setting ↑ ↓
RS485 Address
□□ RS485 Baud rate
□□
Pulse Input Time
□□□□ms
IP Address
□□□. □□□. □□□. □□□ Subnet Mask
□□□. □□□. □□□. □□□ K W Default
□□□. □□□. □□□. □□□
Communication address of device 01~99
00:2.4KB;01:4.8KB;02:9.6KB;03:
19.2KB;04:38.4KB;05:115.2KB
Confirmation time of 4-way pulse
energy, >10mS, < impulse width of
kilowatt-hour meter
For Ethernet communication
Setting the CT secondary current rating 00: 5A; 01: 1A
Setting the PT transformation ratio: 1~1500
Setting the CT transformation ratio: 1~5000
B. Parameters: ↑↓
Rating Current
□□ PT Ratio
□□□□
CT Ratio
□□□□ CT Wiring Mode
□□ PT Wiring Mode
□□ Harmonic Channel
□□
□ 。。。。。。
Setting the CT secondary wiring mode00: 3-phase; 01: 2-phase
Setting the PT secondary wiring mode00: Y-Y; 01: V-V
Setting analog quantity channels 0~12 for harmonic monitoring,
select 0 to exit from the harmonic calculation function
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
30
D/A setting
The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to
adjust the accuracy of the channel output. The DA1~DA2 channel selection is used to
select the corresponding analog quantity channel (see the description of the protection
device for specific reference quantities). In the accuracy test, make sure the field ground is
in good contact; otherwise the accuracy might be affected.
Pulse energy setting
Energy base numbers can be set, including Pulse 1, Pulse 2, Pulse 3, Pulse 4,
positive active energy, positive reactive energy, negative active energy and negative
reactive energy.
Clear trip times
It is used to clear the trip times.
Settings
After entering the password, you can enter the [Setting Value] menu. See the settings
description of the protection device for the detailed description.
Clock setting
A battery-back real-time clock is provided in the device, which can perform time
adjust remotely via the communication network or in-site time adjust in the [Time Setting]
menu.
Enter this menu and press the ―Enter‖
key, the clock will stop refreshing and a
cursor will appear. Move the cursor to the
desired position for modification by pressing
the ――, ―― keys, modify to the desired
value with the ―+‖, ―-‖ keys. Press the
―Enter‖ key to complete setting. If the
―Cancel‖ key is pressed, the setting will be
cancelled and the screen continues to
refresh the clock.
Password
The [Password] menu is used to modify the password for entry into the Settings,
System parameters and Output Test submenus. The initial password is provided by the
factory. The universal password is ―1000‖.
Move the cursor to the desired
position for modification by pressing the
――, ―― keys, modify to the desired
password with the ―+‖, ―-‖ keys. Press the
7.Clock setting
Date:20□□-□□-□□
Time: □□:□□:□□
Input password
0 0 0 0
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
31
Figure 6-1
MLPR-610Hb
D1(3,5)
D2(4,6) A01
D15
D17
D19 A02
D16(18,20)
14(16,18)
Ia’(Ib’、Ic’)
Ia(Ib、Ic)
Ua
Ub Power supply
Uc
Ua’(Ub’、Uc’)
Figure 6-1
―Enter‖ key to enter the new password
setting menu as above; press the
―Cancel‖ key to cancel the setting.
GPS clock synchronization
The GPS clock synchronization signal is input as rs485 differential voltage, the device
is able to receive GPS clock minute synchronization(or second synchronization). If there is
GPS signal, there will be and flashing on the bottom of cycle menu; otherwise
won’t.
The principle of GPS clock synchronization: The second pulse or minute pulse act
with the monitoring system, the time base with second precision is sent by monitoring
system, when the GPS second differential signal arrives, the time base is unified and the
milliseconds are cleared.
Version Info In the main menu, after entering the [9. Version Info] menu, the model, software
version and date of the device will be displayed.
Note: For a corresponding nonstandard model, the device’s displayed model does not
have to be changed.
6. Check of protection function
6.1 Check of three-phase overcurrent protection(Three-step OC)
Overcurrent protection is divided to three phases which can be set and On/Off
separately. Their principle is same, now take the overcurrent phase I for example. To wire
as Figure 6-1, switch on overcurrent phase I protection and overcurrent direction, and
compound voltage is switched on.
See the following table and set. To measure operation current value and keep a
record in the following table. The measuring terminals B17-B18,B25-B26,B27-B28 should
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
32
be shorted when the instantaneous overcurrent protection operates.
Input the
current of
phase A and
add 30V to
voltage
Ubc.Take the
voltage phase
as reference
and check the
operation zone.
Setting value of
instantaneous
current (A)
1 time of
rating
2 times
of rating
5 times
of rating
10 times
of rating
Operation value
Operation zone
Input the
current of
phase B and
add 30V to
voltage
Uca.Take the
voltage phase
as reference
and check the
operation zone.
Setting value of
instantaneous
current (A)
1 time of
rating
2 times
of rating
5 times
of rating
10 times
of rating
Operation value
Operation zone
Input the
current of
phase C and
add 30V to
voltage
Uab.Take the
voltage phase
as reference
and check the
operation zone.
Setting value of
instantaneous
current (A)
1 time of
rating
2 times
of rating
5 times
of rating
10 times
of rating
Operation value
Operation zone
Instantaneous
overcurrent
setting value is
5A and input
Setting value of
under voltage(V) 20 40 60 80
Low voltage
block value
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
33
6A current. Setting value of
negative sequence
voltage (V)
5 10 15 20
Negative
sequence voltage
block value
6.2 Check inverse time overcurrent protection(IT Overcurrent)
To wire as Figure 6-1.Overcurrent protection is provided, and inverse time of
overcurrent mode is set. Select one curve in ―IT Trait Curve‖(01:standard inverse time
limit, 02:unusual inverse time limit, 03:extreme inverse time limit, 04:long inverse time
limit),the time constant τp of inverse time limit is set as 0.50s and the current Ip of
inverse time limit is set as 5A. See the following table and set and check for inverse time
limit. The measuring terminals B17-B18, B25-B26, B27-B28 should be shorted when
inverse time limit overcurrent protection operates.
Curve
selection
Operating value
of inverse time
limit
2Ip(A) 3Ip(A) 5Ip(A)
01:Standard
inverse time limit
Ip=5A,τp=0.5s
Reference
operating time
5.105s 3.15s 2.140s
Actual
operating time
02:Unusual
inverse time limit
Ip=5A,τp=0.5s
Reference
operating time
6.750s 3.375s 1.688s
Actual
operating time
03:Extreme
inverse time limit
Ip=5A,τp=0.5s
Reference
operating time
13.333s 5.000s 1.667s
Actual
operating time
04:Long inverse
time limit
Ip=5A,τp=0.5s
Reference
operating time
60.000s 30.000s 15.000s
Actual
operating time
6.3 Check of zero sequence overcurrent protection(ZS Overcurrent)
Zero sequence overcurrent protection is divided to three phases which can be set
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
34
Figure 6-2
U0
U0’
+WC
-WC
Power supply
MLPR-610Hb
D21 A01 D22 B02 A02 B01
Figure 6-3
On/Off separately. Their principle is same, now take the zero sequence overcurrent phase
I for example. To wire as Figure 6-2 and switch on zero sequence overcurrent phase I
protection and zero sequence direction. It will have zero sequence voltage block function
when zero sequence voltage block is switched on.
Power supply
See the following table and set. Measure operation current value and keep a record in
the following table. The measuring terminals B17-B18, B25-B26, B27-B28 should be
shorted when the zero sequence protection operates. (YY connection is taken for
example.)
Open U0(V) ≥15 ≥15 ≥15 ≥15
Calculate 3U0(=UA) ≥15 ≥15 ≥15 ≥15
Setting value of zero
sequence current(A) 0.20 0.50 1.00 1.50
Operation value
Operation zone
6.4 Zero sequence overvoltage protection(ZS Overvoltage)
Open-delta voltage is taken as zero sequence overvoltage protection voltage, which
can be set as trip or alarm. To wire as Figure 6-3, switch on zero sequence voltage alarm.
MLPR-610Hb
D15
D16 A01
D21
D22 A02
D07
D08
3U0
3U0’
3I0
3I0’
Ua
Ua’
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
35
Ia(Ib、Ic)
Ia’(Ib’、Ic’)
Power supply
Figure 6-4
See the following table and set. Measure operation current value and keep a record in
the following table. The measuring terminals B19-B20 should be shorted when zero
sequence voltage alarm operates.
Setting value of zero
sequence voltage(V) 10 20 30 50
Zero sequence
voltage delay(s) 1 10 50 100
Zero sequence
voltage operation value(V)
Zero sequence
voltage operation time(s)
6.5 Check of overload protection
The maximum current of phase is taken as overload protection current to check,
which can be set as trip or alarm. To wire as Figure 6-4, switch on overload alarm.
See the following table and set. Measure operation current value and keep a record in
the following table. The measuring terminals B19-B20 should be shorted when overload
alarm operates.
Setting value of overload(A) 5 10 15 20
Overload delay(s) 10 5 2 1
Overload operation value(A)
Overload operation time (s)
6.6 Check of under-frequency unloading protection(Under-frequency)
The frequency of under-frequency unloading protection is derived from the measuring
frequency of voltage Uab. It has frequency slip block (Which can be On/Off) and under
current block against load feedback. To prevent fast voltage drop from wrong operation of
MLPR-610Hb
D1(3,5) A01
D2(4,6) A02
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
36
Ia
Ia’
Ua(Ub)
Ua’(Ub’)
Power supply
Figure 6-5
Power supply
frequency protection, under frequency unloading protection provides undervoltage block.
To wire as Figure 6-5, switch on under-frequency unloading protection. If slip frequency is
needed, switch on slip block. Slip block should be switched off so as not to affect
operation accuracy when frequency operation value or operation delay is measured.
See the following table and set. Measure operation value and keep a record in the
following table. The measuring terminals B17-B18、B25-B26、B27-B28 should be shorted
when under-frequency unloading protection operates.
Setting value of under-frequency(Hz) 49.5 49 48.5 48
Setting value of under current(A) 0.5 0.5 1 1
Setting value of under voltage(V) 10 20 30 60
Setting value of slip block(Hz/s) 3 4 5 7
Setting value of under-frequency
operation delay(s) 0.5 1 2 3
Under-frequency operation value(Hz)
Under-frequency operation time(s)
Slip block value(Hz/s)
6.7 Check of auto reclosing and later instantaneous trip
To wire as Figure 6-6 and check according to the following method.
Figure 6-6
MLPR-610Hb D1
A01 D2 D15(17)
A02 D16(18)
MLPR-610Hb
D1 A01
D2 B01 A02 B02
Ia
Ia’
DL
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
37
Check of protection starting method: Protection starting reclosing method is
provided, which reclosing delay is set as 2.00s.To switch on overcurrent
post-acceleration, which post-acceleration delay is set as 0.00s.To connect terminals
B01-B02, the charging sign will come up after 15s. Add fault current to make
instantaneous or overcurrent protection operate. Remove the fault current, the reclosing
will operate after 2s. Add fault current again, the overcurrent post-acceleration protection
operates immediately.
Check of non-corresponding starting method: When circuit breaker trips, not manual
trip or remote control trip, the reclosing will be started. To switch on non-corresponding
starting reclosing, and connect terminals B01-B02, the charging sign will come up after
15s. To open terminals B01-B02 (analog breaker trip), reclosing will operate after 2s.
Reclosing has no-voltage check and synchronization check function. To switch on
no-voltage check, the reclosing will be blocked when voltage UL is greater than setting
value of no-voltage check. To switch on synchronization check and select
synchronization voltage in parameter menu, the reclosing will be blocked when the
skewing between voltage UL and synchronization voltage is greater than
synchronization check angle. Both of the voltage at two ends should be greater than
80% of rated voltage (line voltage: 100V , phase voltage: 100/ 3 V).
6.8 Check of PT failure function
Add balanced 3-phase voltage (57.7V), device should report PT failure when any one
or two phases are removed. Add protection current but no voltage, which is greater than
no-current setting value, device should report PT failure (used for YY connection).
Measuring terminals B19-B20 should be shorted.
6.9 Check of undervoltage protection function
To wire as Figure 6-7. Input the voltage of phase A,B,C, switch on undervoltage
protection and close the breaker. See the following table and set. To measure operation
voltage value and keep a record in the following table. The measuring terminals
B17-B18、B25-B26、B27-B28 should be shorted when undervoltage protection operates.
Undervoltage protection will be blocked when PT is failure and PT failure lock
undervoltage is switched on.
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
38
Power supply
Figure 6-7
Setting value of
undervoltage(V) 30 50 70 90
Operation value
6.10 Check of bus charging protection
To wire as Figure 6-8, port 1 and 2 are current input of phase A, port 3 and 4 are
current input of phase B, port 5 and 6 are current input of phase C. Switch on bus charging
protection. Terminal A19 is connected with –WC, +WC and terminal A15 are shorted
immediately, using analog manual closing. Bus charging protection should operate when
input fault current in 3s. And bus charging protection should not operate when input fault
current after 3s. See the following table and set. Measure operation current value and
keep a record in the following table. The measuring terminals B17-B18、B25-B26、
B27-B28 should be shorted when bus charging protection operates.
Figure 6-8
Setting value of
bus charging current
(A)
1In 2In 5In 10In
Operation value
MLPR-610Hb D15 A01 D17
D19 A02 D16 (18,20)
Power supply
Ua
Ub
Uc
Ua’(Ub’、Uc’)
MLPR-610Hb
D1(3,5) A01 D2(4,6) A19 A02 A20
Ia(Ib、Ic)
Ia’(Ib’、Ic’)
-WC
+WC
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
39
6.11 Check of synchronization closing function(Sync. Closing)
To wire as Figure 6-9, switch on manual closing synchronization function. In the
parameter menu, synchronization voltage is set as Uab, setting value of synchronization
angle is set as 20°, setting value of synchronization frequency difference is set as 1Hz,
setting value of synchronization voltage difference is set as 5V, setting value of
synchronization no-voltage closing is set as 70V, synchronization time is set as 60s.
Add 100V/50Hz AC voltage to UAB, add a voltage with less than 70V, and 50Hz of
frequency to UL. Connect B01-B13 and then open, simulate manual synchronous closure.
The device checks out no-voltage closure, after the terminals B29-B30 closed for 600ms,
it will return, and the closure pulse is provided. Increase the voltage of UL to 98V and
adjust the frequency as 49.5Hz, the device will capture synchronization in 60s. The
terminals B29-B30 will return after closure of 600ms when voltage difference, frequency
difference, phase angle difference are content with the setting value.
The remote closure synchronous function is switched on, under the background
monitoring system and after sending closure command, the device will capture
synchronously as manual closure checking synchronization. If it captures successfully in
the time of synchronization, the terminals B23-B24 are closed for 600ms and it will send
closure pulse.
Figure 6-9
MLPR-610Hb D15 D17 A01 D19 D16(18,20) D23 A02 D24
Power supply
Ua
Ub
Uc
Ua’(Ub’、Uc’)
UL
UL’
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
40
7.1 Terminal diagram of the device
Figure 7-11 Terminal diagram of MLPR-610Hb
Input 6
IC'IC
IB'IB
Ua
Uc
Ub'
Ua'
Ub
Uc'
UL'
U0'U0
UL
(+24V)
注:1.Ia,Ib,Ic are protective currents.2.I0 is zero-sequence current.3.IA,IB,IC are measuring currents.4.Ua,Ub,Uc are bus voltages.5.U0 is zero-sequence voltage.6.UL is line voltage.7.DCSIn is 2-way 4~20mA DC
input.8.Net1,Net2 are ethernet interfaces, COM1, COM2 are 485 interfaces.9.If +24V is the standard configuration or not on IO board, it is used as input power supply only when using internal 24V.
Input 7
Input 10
Input 9
D02
D04
D06
D08
D10
D12
D14
D16
D18
D20
D22
D24
I/OPOWER
B01
B02
ON B06B05
B04B03
IaD01
IbD03
IcD05
D07
OFFB10
B08B09
B12
B14
B13
B11
B07
A02
A01
I0
D09
D11
D13
D15
B17B18
B16
B19
B21B20
D17
D19
D21
D23
B23B24
B25B26
B27B28B29
B22
A04
A06A05
B15A03
B30B31
B32
B34B35
B36
B33
CPU
Ia'
Ib'
Ic'
AC
I0'
Debug
COM2
COM1
Net2
Net1
Run
C13
C17
C19
C20
C18
C16
C14C15
C12
C10C11
C08
C09
C06
C07
C02
C04C05
C03
C01
A21
A23A24
A22
A19
A20
A18
+WC
-WC
A10
A17A16A15A14
A13A12A11
A08A09
A07
DCSIn2+
DCSIn2-
DCSIn1-
DCSIn1+D25
D27D28
D26
Input 11
IA IA'
Chk.Sync.Manu.
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
41
7.2 Typical wiring diagram of the device
Figure 7-12 Typical wiring diagram of MLPR-610Hb
AC
plug-in DCSIn1+
DCSIn2+
DCSIn2-
DCSIn1-
WC
WC
MLPR-610Hb microcomputer protection and monitoring device
Debugging port
Net2
I/O plug-in unit
Operating circuit failure
Device power+
Power off
Shielded ground
Device power-
Trip position
Closed position
Closed position monitoring
Trip coil
Trip position monitoting
Closing coil
-WC
Remote control common terminalRemote control closingManual closing iniput
Device panel+WC
Remote control trip
Manual trip input
+WC
Input 7
Input 6
Spring
GEarth Switch
Trolley test
Trolley run
Breaker
Input common
terminal-
Pulse 1( )
Pulse 2( 2)
Pulse common+24V
COM A
COM A
COM B
COM B
Shielded ground
COM A
COM A
COM B
COM B
DCSOut1+
A A B B
Pulse 3( )
Pulse 4( 4)
DCSOut1-
DCSOut2+
DCSOut2-
Positive active pulse
Positive reactive pulse
Negative active pulse
Negative reactive pulse
Pulse common+24V
CC
LARC Lock
Shielded ground
Note:
1.As shown in the figure,the ZK(remote/local changeover switch) and KK(manual operating switch) are installed on
the switchboard panel.When remote/local changeover switch and manual operating switch of device panel are used,terminal A21 is connected to +KM. 2.As shown in the figure,PT secondary is star connection,when V-V wiring is present, terminals D15,D20 are connected to phase A of PT secondary,terminals D16,D17 to phase B of PT secondary,terminals D18,D19 to phase C of PT secondary.
Zero-sequence current Measuring current Line voltage
plug-in unit
Pow
er
plug-in unit
CP
U
WC
WC
PROT Output 1
PROT Output 1
Alarm signal
Alarm signal
Chk.Sync.Manu.
Reclose Output
Output 9
normally open
Output 9 normally
closed
Device Failure
signal
Device Failure
signal
Trip Signal
AC plug-in unit
ccbbaaa a b b c c
Circuit
breaker
Bus voltage Zero-sequence voltage Protective current
Input 9
Input 10
Input 11
IChk.Sync.Manu.
(+24V)
Trip Signal
Chk.Sync.Manu.
Output 5
Output 5
PROT Output 2
PROT Output 2
Output 9 common
Output 10
normally closed
Output 10 common
Output 10
normally open
Reclose Output
t
Net1
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
42
Part 8 Operating circuit of MXPR-600Hb series device
8.1 Use of external changeover and operating switches
Traditional operating circuits are started by current, while a voltage maintaining circuit
realizes electric trip prevention. An anti-trip relay will be selected depending on the current
of the trip/closing circuit of the circuit breaker. However, this has poor generality and can
hardly be realized for circuit breakers with low trip and closing currents (such as 10KV
circuit breakers from AEG Company in Germany, whose trip and closing currents are not
greater than 0.2A). To simplify wiring and design finalization, and to improve the generality
of the product, we offer a new operating circuit shown below.
Reclosing
1LP
Tn1
JnTn2
Fuse
Clo
sing c
ircuit
Small bus
DL HQ
A16
TBJ2
TBJ1
A19TBJ
Closing output
Trip
circ
uit
Protection
DLTQ
DL
A18
A14
A13HWJ
TWJ
A12
A10TWJ
HWJ
A08TWJ
Off position
On position
A15
A24
YHJ
854ZK KK
2
A22
A23YTJ
A17
Tn1
Jn
3
768
2LP
ZK KK
A20
A11
A09
Tn2
1
6
A07
ZK
HWJ
Remote
controlled
switch-on
Operation circuit
disconnected
Manual and
anti-trip
Remote
control
opening
Manual and
trip output
Closed position
output
Trip position
output
Schematic diagram of operating circuit 1
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
43
In the diagram, KK is a traditional operating switch, used for manual trip/closing
operations, ZK is a changeover switch, used for changeover of local and remote control.
When ZK is at the ―Remote‖ position, the power of the remote control circuit will be
switched on, i.e., Terminal A22 of the device is connected to +KM, and the power of the
manual operating circuit is cut off, disabling manual closing and manual trip. On the
contrary, when ZK is at the ―Local‖ position, the power of the manual operating circuit is
switched on and that of the remote control circuit is cut off.
Note: The dotted line outlines the internal circuit of the protection device. All our
devices marked with ―anti-trip circuit‖ are designed on this operating circuit.
Terminals Tn1, Tn2 corresponding to the protection relay Jn are determined by the
corresponding protection output control word. Jn can be any one or more of Protection
outputs 1-8.
Whether local or remote control, the precondition to jump is Terminal A15 of the device is
always connected to +KM. After manual or remote controlled closing, if a short-circuit fault
occurs, the protection will operate to trip the circuit breaker. Though Terminal A15 of the
device is connected to +KM, the closing circuit is disconnected by TBJ1 and will not be closed
again. In this way, circuit breaker jump is effectively prevented.
User’s manual for MLPR-610Hb microcomputer protection and monitoring device for line WLD[K]-JY-222-2010
44
8.2 Use of trip and closing buttons on the panel
Reclosing
1LP
Tn1
JnTn2
Fuse
Clo
sing
circ
uit
Small bus
DL HQ
A16
TBJ2
TBJ1
A19TBJ
Trip
circ
uit
Protection
DLTQ
DL
A18
A14
A13HWJ
TWJ
A12
A10TWJ
HWJ
A08TWJ
Off position
On position
A15
A24
YHJ
854ZK KK1
2
A22
A23YTJ
A17
Tn1
Jn
3
768
2LP
ZK KK2
A20
A11
A09
Tn2
1
6
A07
ZK
HWJ
A21
Remote
controlled
switch-on
Operation circuit
disconnected
Closing output
Manual and
anti-trip
Remote
control
opening
Manual and
trip output
Closed position
output
Trip position
output
Schematic diagram of operating circuit 2
In the diagram, KK1, KK2 and ZK are on the panel, in which KK1 and KK2 are manual
closing and manual trip buttons (the manual closing and manual trip contacts are already
connected to manual close in and manual trip in internally), ZK is a changeover switch for
switching between the local/remote positions, completely replacing the changeover and
operating switches on the board/cabinet panel.
Note: The dotted line outlines the internal circuit of the protection device. When a
control button on the panel is used, Terminal +KM A21 on the panel must be connected to
+KM.