Meter Mounting Equipment Commonwealth Edison
Transcript of Meter Mounting Equipment Commonwealth Edison
Meter Mounting Equipment
Commonwealth Edison
MIL
BA
NK
OV
ERV
IEW
MILBANK OVERVIEW2
2
Charles A. Milbank1879-1966
Bill Martin1916-1998
Robert F. Waldrop1922-2002
Robert F. Waldrop, IIChairman
Katrina Waldrop HenkeVice Chairman
Milbank–Quality Metering Products for 80 Yearsilbank ManufacturingCompany was estab-lished in 1927 byCharles A. Milbank.
Originally, the company manu-factured high voltage switches;however, by 1941 Milbank devot-ed itself primarily to the manufac-ture of sheet metal enclosuresand related equipment for theelectrical generation and distribu-tion industry. Today we are anindustry leader in the manufac-ture of electrical meter sockets.Through a national network ofmanufacturer’s representatives weprovide wholesale electrical dis-tributors with quality electricalproducts for the utility, contractor,industrial and OEM markets.
As the meter standards havechanged, Milbank has been suc-cessful in adapting its productline to these changes. Our fullscale engineering departmentdesigns products to meet cus-tomer specifications and satisfyall utility requirements.Milbank’s employee base of over1,000 workers, along with ourfive manufacturing facilities com-
prising almost 550,000 squarefeet give us the flexibility toschedule, produce, and shiporders quickly. Currently,Milbank manufactures over10,000 different catalog items,and this list continues to grow.Our unique product offeringincludes: Residential &Commercial Meter Sockets;Residential & Commercial MeterPedestals; RV/MH Power Outlets,S e r v i ce Pede s t a l s , andTransformers; Commercial &Industrial Electrical Enclosures;Circuit Breakers; Disconnects &Safety Switches; Safety Sockets;Utility & Residential SecondaryPedestals; Hubs, and relatedaccessories. If you don’t find aunit in this catalog to service yourneeds, send us your specificationsand we will be happy to workwith you.
Our success has come from aloyal customer base that can relyon us to build quality products ata fair price in a timely manner.Our willingness and ability todesign and produce new productsto meet our customer demands is
an important factor to remaincompetitive in today’s electricalmarket.
Milbank has been serving theelectric utility & wholesale distri-bution industries for 80 yearswith innovative, quality engi-neered products. So rememberus for all of your meter mountingand related requirements, andwe will be happy to serve you aswe have in the past–with depend-able service and quality products!
We take great pride in beingone of the few family-ownedbusinesses left in our industry.We are a third generation runbusiness and truly believe that...
FAMILY MAKES A DIFFERENCE!
M
3TA
BLE O
F CO
NTEN
TSTABLE OF CONTENTS
CATALOG NUMBER LOGIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
DISCONNECTSAIR CONDITIONER DISCONNECT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5AIR CONDITIONER DISCONNECT WITH GFCI RECEPTACLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6HOT TUB DISCONNECT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
SINGLE POSITION100 & 200 AMP—4 & 5 TERMINAL—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
SINGLE POSITION (LEVER BYPASS)200 AMP— 5 & 7 TERMINAL—JAW CLAMPING LEVER—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8320 AMP—4 TERMINAL—JAW CLAMPING LEVER—HEAVY DUTY—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
MULTIPLE POSITION (HORIZONTAL GANGS)100 AMP / POSITION—4 TERMINAL—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14200 AMP / POSITION—4 TERMINAL—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14200 AMP / POSITION—7 TERMINAL—JAW CLAMPING LEVER—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
CONDOMINIUM METERING BANKS125 & 200 AMP / POSITION—VERTICAL & RECTANGULAR—OVERHEAD/UNDERGROUND SERVICE . . . . . . . . . . . . . 16-17
METER MAINS100 AMP—4 TERMINAL—METER MAIN—PLUG-IN—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9200 AMP—4 TERMINAL— METER MAIN— RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9200 AMP—7 TERMINAL— METER MAIN— RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10100, 150 & 200—4 TERMINAL— METER MAIN— 22K AIC— RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-13100/200 AMP—4 TERMINAL—METER MAIN PEDESTAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19320 AMP—4 TERMINAL— MAIN PEDESTAL— LEVER BYPASS—W/ BREAKER—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . 22
PEDESTALS100 / 200 AMP—4 TERMINAL—SINGLE POSITION—RESIDENTIAL—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18100 / 200 AMP—4 TERMINAL—DOUBLE POSITION—RESIDENTIAL—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18100/200 AMP—5 & 7 TERMINAL—HEAVY DUTY—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23JOINT USE TERMINATION CABINET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24U5706 TEMP TO FINAL SERVICE PEDESTAL—RINGLESS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20-21
TRANSFORMER RATED SOCKET20 AMP—6, 8 & 13 TERMINAL—INSTRUMENT TRANSFORMED RATED SOCKET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
COMMERCIAL METER PEDESTALCOMMERCIAL METER PEDESTAL OVERVIEW, APPLICATIONS & ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-27
MISCELLANEOUSACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28-29CONDUIT AND AMPACITY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30ENERGIZATION OF ELECTRICAL EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31MATERIALS AND FINISHES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
ADDITIONAL MILBANK PRODUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3
CATALOG NUMBER LOGIC4C
ATA
LOG
NU
MB
ER L
OG
IC
4
530 &
60 AM
P–FUSIB
LE / NO
N-FU
SIBLE–A
IR C
ON
DITIO
NER
DISC
ON
NEC
TS30 & 60 AMP–FUSIBLE / NON-FUSIBLE–AIR CONDITIONER DISCONNECTS
5
U3800(No deadfront required)
Milbankʼs air conditioner disconnect has a removable hinged cover which makes wiring a breeze. Ourcompact design meets all wire bending space requirements in the NEC and, also, complies with article440-14 in the NEC. To insure the safest conditions, we designed our disconnect pullers to be remov-able or they may be reinstalled in the off position. Another safety feature is the padlock provision on thefront cover. As with all Milbank products, our enclosure is constructed of G90U galvanized steel andfinished with an attractive, light gray, baked powder coating. Our state of the art finish combines epoxyand polyester hybrid resins into a hybrid powder coating which is then electrostatically applied. Thisoffers a durable, nonfading finish.
TECHNICAL INFORMATION
AMP TYPE CATALOGNUMBER
MAXH.P.
WT.@#
30 FUSIBLE U3830 3 2.7
60 FUSIBLE U3860 10 3.3
60 NONFUSIBLE U3800 10 3.25
LINE & LOADWIRE RANGE
GROUNDWIRE RANGE DIMENSIONS WIRE RATING
CU AL CU/AL
#14-#3AWG
#14-#3AWG #14-3 AWG
#14-#3AWG
#14-#3AWG #14-3 AWG
#14-#2AWG
#12-#2AWG #14-3 AWG
D" W" H" CU °C AL °C
2-5/8 5 7 60°/75° 60°/75°
3 5 91⁄4 60°/75° 60°/75°
3 5 8 60°/75° 60°/75°
PROFILE
U/L listed as Enclosed Pullout Switch
1∅, 240 VAC
Type 3R Rainproof
Six one-inch concentric knockouts
✓
✓
✓
✓
U3801
U3860
60 NONFUSIBLE U3801 10 2.5 #14-#3AWG
#14-#3AWG #14-3 AWG 2-3/8 5 6-3/4 60°/75° 60°/75°
AC DISCONNECT / SPA BOX6A
C D
ISC
ON
NEC
T /
SPA
BO
X
6
• Meets NEC # 210.63 Requirements *• UL Listed as Power Outlet• Type 3R Enclosure• In-Use Cover**• Duplex Ground Connector• 1” Concentric Knockouts
AC DISCONNECT• 1∅, 240 Volt• 60 amp, Non-Fused
GFCI RECEPTACLE• 20 amp• Reset/Test Button• Padlock provision
Combination AC Disconnect / 20 Amp GFCI Receptacle–Together in 1 Box
To ensure the safest conditions, Milbank disconnect pullers are designed to be reversible so they may be reinstalled in the OFF position.All units are designed with a padlock provision on the cover for security.
**Note: U3822-20GR cover rated as IN-USE COVER (Cover may be closed with cords plugged into receptacle).*Reprinted with permission from NFPA 70-2002, National Electrical Code®, Copyright 2001, National Fire Protection Association, Quincy, MA 02269. This reprinted material is not the completeand official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety. National Electrical Code® and NEC® are registered trademarks of theNational Fire Protection Association, Quincy, MA.
* NEC® #210.63 Heating, Air-Conditioning and RefrigerationEquipment Outlet. ...The receptacle shall be locat-ed on the same level and within7.5 m (25 ft.) of the heating, air-conditioning and refrigerationequipment.
* NEC® #210.08 Ground-FaultCircuit– Interruptor protectionfor personnel.
U4881-O-50GB
AMP TYPE CATALOGNUMBER
WT.@#
– BREAKERPROVISION U4881-O 7
LINE & LOAD CONNECTORWIRE RANGE
GROUND CONNECTORWIRE RANGE DIMENSIONS
CU AL CU/AL
#14-1/0 #14-1/0 #14-1/0
D″ W″ H″
3 3⁄4 71⁄2 81⁄2
50
60
BREAKER
BREAKER
U4881-O-50GB
U4881-O-60GB
8
8
#14-1/0
#14-1/0
#14-1/0
#14-1/0
#14-1/0
#14-1/0
3 3⁄4
3 3⁄4
71⁄2
71⁄2
81⁄2
81⁄2
• 240 Volt ground fault protection• UL listed, Type 3R rainproof• Milbank reliability• Easy installation• 2 pole, 50 or 60 amp GFCI breaker protection• Compact size:
8-1/2” H x 7-1/2” W x 3-3/4” D• 3 or 4 wire installation• 1∅, 120 / 240 VAC• Standard package of 12• 2 extra one-pole breaker spaces• 100 amp overall rating
Sub Panel Breaker Enclosure• Use as a 100 amp, 4 circuit sub panel
enclosure• U4881-O has provision for (2) 2-pole or
(4) 1-pole small frame breakers
Hot Tub Disconnect or Sub Panel Breaker Enclosure–Type 3RSpa Box with GFCI Protection
U3822-20GR
60 amp, Non-Fused AC Disconnect
Duplex 20 ampGFCI Receptacle
Type 3REnclosure withIn-Use Cover
AMP TYPE CATALOGNUMBER
MAXH.P.
WT.@#
60 NONFUSIBLE U3822-20GR 10 6
LINE & LOAD CONNECTORWIRE RANGE
GROUND CONNECTORWIRE RANGE DIMENSIONS WIRE RATING
CU AL CU/AL
#14-#2AWG
#12-#2AWG #14-4 AWG
D″ W″ H″ CU °C AL °C
4.8 5.25 7.4 60°/75° 60°/75°
7100 / 200 AMP–4 & 5 TERMINAL–RINGLESS–600 VAC
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
7
1 2
544 3
AMP
100/200
SERVICE CATALOGNUMBER
HUB
OH U8949-RL-TG-KK H.O.
CONNECTORSCU/AL
LINE LOAD
BY-PASS
HORN
DIMENSIONS CONCENTRIC K.O.ʼS
1 2 3 4 5
21⁄2 21⁄2 21⁄2 11⁄4 1⁄4
D″ W″ H″
41⁄8 8 151⁄2#6-350 kcmil #6-350 kcmil
100 / 200 AMP—4 & 5 TERMINAL—RINGLESS—1∅—600 VAC
U8949-RL-TG-KK
HUBS: Order hubs separately–see accessory page for ordering information.FIFTH TERMINAL: For field mounted fifth terminal, order catalog number K5T to fit into square opening in the 9 oʼclock position.INSULATED NEUTRAL: For indoor service order as extra #BL1048-KK complete interior block assembly to be installed to provide
insulated neutral.
CECHAAPPROVED
100 / 200 AM
P–4 & 5 TER
MIN
AL–R
ING
LESS–600 VA
C
8949
200 & 320 AMP–4, 5 & 7 TERMINAL–LEVER BYPASS–RINGLESS–600 VAC820
0 &
320
AM
P–4,
5 &
7 T
ERM
INA
L–LE
VER
BY
PASS
–RIN
GLE
SS–6
00 V
AC
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
8
#OF
TERMS
5
PHASE CATALOGNUMBER
SERVICE
3∅3W U8624-RXL OH
CONNECTORSCU/AL
LINE & LOAD
BY-PASS
LEVER
DIMENSIONS CONCENTRIC K.O.ʼS
1 2 3 4 5
3 21⁄2 3 3 1⁄4
6
1⁄4, 1⁄2
D″ W″ H″
47⁄8 13 19#6-350 kcmil
7 3∅4W U8606-RXL OH
HUB
C.P.
C.P. LEVER 3 21⁄2 3 3 1⁄4 1⁄4, 1⁄247⁄8 13 19#6-350 kcmil
200 AMP—5 & 7 TERMINAL—RINGLESS—3∅—600 VAC
1 2
34 465
U8624-RXL
HUBS: Order hubs separately–see accessory page for ordering information.BYPASS: Lever supplies clamping action on meter spades and also operates bypass device.CONNECTORS: Units supplied with extruded aluminum connectors and bonded triplex neutral.INSULATED NEUTRAL: For insulated neutral order catalog number K1047 (for the U8606 only). U8624 can be field converted
to isolated neutral by removing the bonding link.
BYPASS: Lever supplies clamping action and also operates bypass device. CONNECTORS: Supplied with 3/8″-16 hex head nuts with Belleville washers. For connector kits, order as extra: K1539
(350kcmil) or K1540 (600 kcmil). For twin lug connectors order as extra: K1350 (350 kcmil). Separate kits are required for bothline and load.
FIFTH TERMINAL: For factory installed fifth terminal in the 6 oʼclock position add the suffix -5T6 to the catalog number. Forfactory installed fifth terminal in the 9 oʼclock position at the suffix -5T9 to the catalog number. For field installed fifth terminalorder catalog number K3865.
862486064363
U4363-X-QG-CECHA
320 AMP CONTINUOUS (400 AMP MAX)—4 TERMINAL—HEAVY DUTY—RINGLESS—1∅—600 VAC
CECHAAPPROVED
PHASE CATALOGNUMBER
SERVICE HUB BY-PASS
DIMENSIONS CONCENTRIC K.O.ʼS
1 2 3 4 5 6D″ W″ H″
1∅
TERMS
4 U4363-X-QG-CECHA C.P. 3⁄8″ x 16 STUDS LEVER 3 3 3 3 1⁄4 1⁄4, 1⁄247⁄8 13 281⁄4OH
CONNECTORSCU/AL
9100 OR 200 AMP–CIRCUIT BREAKER MAIN DISCONNECTSINGLE POSITION–METER MAIN–240 VAC
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
9
U7375-RL-KK U7607-RL-200-KK(Supplied with 200 Amp circuit breaker)
CATALOGNUMBER
U7375-RL-KK
SERVICE
OH
HUB
H.O.
CONNECTORSCU/AL
LINE LOAD
#6-2/0 C.B.
BY-PASS
HORN
DIMENSIONS CONCENTRIC K.O.ʼS
1D″ W″ H″
11⁄433⁄4 81⁄8 22
2
11⁄4
3
11⁄4
4
1⁄4,1⁄2
5
—
100 AMP–4 TERMINAL—METER MAIN (PLUG-IN)—RINGLESS—1∅
CATALOGNUMBER
U7607-RL-200-KK
SERVICE
OH
HUB
H.O.
CONNECTORSCU/AL
LINE LOAD#6-350kcmil
#1-300kcmil
BY-PASS
HORN
DIMENSIONS CONCENTRIC K.O.ʼS
1D″ W″ H″
241⁄2 81⁄8 29
2
2
3
2
4
1⁄4,1⁄2
5
—
200 AMP–4 TERMINAL—METER MAIN—RINGLESS—1∅
CIRCUIT BREAKER: Main circuit breaker not supplied with unit. For 100 amp service order Milbank catalog numberQ2100 separately. See circuit breaker chart on accessory page for other compatible models.
CIRCUIT BREAKER: 200 amp main circuit breaker factory bussed. Order Milbank catalog number UQFB-200-X1 forreplacement. Other amperages available. See Milbank circuit breaker chart on accessory page.
HUBS: Order hubs separately–see accessory page for ordering information.FIFTH TERMINAL: For field mounted fifth terminal for U7375 order catalog number 5T8K2. For field mounted fifth
terminal for U7607 order catalog number K5T. Mount in the 9 oʼclock position only.
2
3
M I L B A N K
4
1
CECHAAPPROVED
100 OR
200 AM
P–CIR
CU
IT BR
EAK
ER M
AIN
DISC
ON
NEC
T–SING
LE POSITIO
N–M
ETER M
AIN
–240 VA
C
200 AMP–7 TERMINAL–RINGLESS–METER MAIN–3Ø10
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
10
CATALOGNUMBER
U5750-RXL-200-BL-CECHA
SERVICE
OH/UG
HUB
C.P.
CONNECTORSCU/AL
LINE LOAD
#6-350 C/B
BY-PASS
LEVER
DIMENSIONS CONCENTRIC K.O.ʼS
1D″ W″ H″
11⁄4-353⁄4 173⁄8 34
2
3-4
3
1⁄2-2
7 TERMINAL–METER MAIN–RINGLESS–3Ø4W–RINGLESS
BYPASS: Lever supplies clamping action on meter spades and also operates bypass device.BREAKER: Factory installed 200 amp, 3-pole, 10,000 AIC.SIDE WIREWAY: Allows for overhead or underground installation.
200
AM
P–7
TER
MIN
AL–
RIN
GLE
SS–M
ETER
MA
IN–3
Ø
U5750-RXL-200-BL-CECHA
2
1
13
5750
CECHAAPPROVED
NEW
PRODUCT
11100, 150 & 200 AMP–4 TERMINAL–300 VAC–METER MAIN
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
11
100, 150 & 200 AMP–4 TERMINAL–METER MAIN–OVERHEAD/UNDERGROUND–22K AIC–1∅3W
AMPS CATALOGNUMBER
HUBCONNECTORS
LINE LOADBY-
PASS
DIMENSIONS CONCENTRIC K.O.ʼS
1 2 3 4 5 6D″ W″ H″
HUB: Supplied with (2) closing plates packed inside. Order hubs as a separate item. See accessory page for hub options.INTERIOR: U5168 units have 8 circuit interior.FIFTH TERMINAL: Order K5T and field install for 208Y/120 network systems. Installs in the 9 oʼclock position only. BREAKERS: Rated 22K AIC with Milbank QNR2200H main installed.INTERLOCK KIT: For generator auxiliary circuit breaker interlock, order K5815 for large QN with small frame Q; order K5820 for large
frame QN with large frame QN.*SUB-FEED LUGS: #6-350 kcmil sub-feed lugs provided on 8 circuit interior.
2
354
5
11
5
6
6
5
6
8100 U5168-XTL-100-KK-CECHA C.P. HORN 2 2 3 21⁄2 1⁄2,3⁄441⁄2 141⁄8 32#6-350 kcmil #1/0-300 kcmilBreaker*
1⁄2,3⁄4, 1
8150
200
U5168-XTL-150-KK-CECHA
U5168-XTL-200-KK-CECHA
C.P.
C.P.
HORN
HORN
2
2
2
2
3
3
21⁄2
21⁄2
1⁄2,3⁄41⁄2,3⁄4
41⁄2
41⁄2
141⁄8
141⁄8
32
32
#6-350 kcmil
#6-350 kcmil
#1/0-300 kcmilBreaker*
#1/0-300 kcmilBreaker*
1⁄2,3⁄4, 11⁄2,3⁄4, 1
U5168-XTL-200-KK
5168
NO. OFCIRCUITS
8
AMPS CUTLER-HAMMER(WESTINGHOUSE)
SIEMENS(ITE)
SIEMENSMURRAY /
CROUSE-HINDSG.E. SQ-D
125-200 HQP / BR / WBJ — MD THQ —
≤ 100 QP / BR / HQP QP MP THQ HOMELINE
Amperage
Catalog No.
100 150 200
Q2100H QN2150RH QN2200RH
PLUG-IN BREAKER COMPATIBILITY CHARTMAIN CIRCUIT BREAKER CHART
100, 150 & 200 A
MP–4 TER
MIN
AL–300 V
AC
–METER
MA
IN
CECHAAPPROVED
200 AMP–4 TERMINAL–RINGLESS–METER MAIN1220
0 A
MP–
4 TE
RM
INA
L–R
ING
LESS
–MET
ER M
AIN
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
12
SPECIFICATIONS• Listed under UL 67 as “suitable only for use as service equipment” – file number E32628 Series 1800 MS.
• 200 amp continuous duty ringless meter socket. Accepts ANSI type C12.10 watt-hour meters. Overall ampere
rating limited to main circuit breaker rating.
• For use on 120/240 volt single phase applications.
• 22K AIC as standard.
• Type 3R enclosure constructed with G90 galvanized steel.
• Light gray polyester powder coat finish.
• Service entrance overhead or underground. OH has up to 2-1/2” hub opening and UG has up to 3” knockout
• Wire terminations accept copper or aluminum conductors:
Line & Neutral: # 1/0-350 kcmil Ground: #6-350
• Plug-on main circuit breaker: 60 and 100 amp type Q small frame, 150 and 200 amp type QN large frame.
• Lockable breaker reset cover.
U5842KO CONFIGURATIONS
A 1.0” 1.25” 1.5” 2.0” 2.5” CONC. B 0.25” 0.5” CONC.C 0.25” SOLID
CECHAAPPROVED
13U
5842 OR
DER
ING
INFO
RM
ATIO
NU5842 ORDERING INFORMATION
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
13
RINGLESS METER MAIN MODELS
Catalog Number Amp Main Term Service Wt (#)
◆ U5842-RL-KK 200 2p* 4 OH 25
*2 Pole provision.
AIC RATING: All models are rated 22K AIC.
FIFTH TERMINAL: For field installable 208Y/120 network service order K5T. Installs in the 9 oʼclock position.
MAIN CIRCUIT BREAKER CHART
Amperage 60 100 150 200
10KAIC Breaker Model Q260 Q2100 QN2150 QN2200
22KAIC Breaker Model Q260H Q2100H QN2150H QN2200H
OH-112993
OH-1132161 (100A)OH-1130010 (200A)
FIFTH TERMINALK5T
(New style block with square hole)
100 & 200 AMP / POSITION–4 TERMINAL–HORIZONTAL GANG–RINGLESS–300 VAC1410
0 &
200
AM
P /
POSI
TIO
N–4
TER
MIN
AL–
HO
RIZ
ON
TAL
GA
NG
–RIN
GLE
SS–3
00 V
AC
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
14
334 5 5
211
NO.OF
POS.
2
CATALOGNUMBER
L572-XL-KK
HUB
C.P.
CONNECTOR CU/AL BY-
PASS
HORN
DIMENSIONS CONCENTRIC K.O.ʼS
1
2 2 2 21⁄21⁄4,1⁄2
2 3 4 5D″
41⁄2
W″
205⁄16
H″
16
LINE
#2-350kcmil
LOAD
#6-2/0
3 L573-XL-KK C.P. HORN 2 2 2 21⁄21⁄4,1⁄241⁄2 281⁄2 16#2-350
kcmil #6-2/0
4 L574-XL-KK C.P. HORN 2 2 2 21⁄21⁄4,1⁄241⁄2 4011⁄16 16#2-350
kcmil #6-2/0
5 L575-XL-KK C.P. HORN 2 2 2 21⁄21⁄4,1⁄241⁄2 487⁄8 16#2-350
kcmil #6-2/0
6 L576-XL-KK C.P. HORN 2 2 2 21⁄21⁄4,1⁄241⁄2 571⁄16 16#2-350
kcmil #6-2/0
AMPS
100
100
100
100
100
100 AMP / POSITION— 4 TERMINAL—RINGLESS—1∅3W—OVERHEAD
4” SIDE WIREWAYOH SERVICE
FIFTH TERMINAL: For factory installed fifth terminal in the 9 oʼclock position for the U1252 series add the suffix -5T. Forfield mounted fifth terminal, order catalog number K5T, 9 oʼclock position only. For field installed fifth terminal for theL572 series order as extra 5T8K2 for 6 oʼclock position, and K9959 for 9 oʼclock position.
BUSSING: Bussing is 5/16″ x 1″ aluminum on U1252 & U1253, 3/8”x1” aluminum on U1254-1256. Refer to the conduit &acity information page for information on ampacity of bussing.
*UNDERGROUND PEDESTALS: (U1252-U1256 only) For underground service order S2291-TO pedestal raceway. A 12″pedestal extension kit is also available. Order catalog number S2571.
*FOR OVERHEAD SERVICE: The U1254-U1256 units are factory assembled for underground service. If overhead serv-ice is desired an extension kit is required. Order catalog number K3923 for the U1254 and U1255 units and K3955 for theU1256 unit.
200 AMP / POSITION—4 TERMINAL—RINGLESS—1∅3W—OVERHEAD / UNDERGROUND*
NO.OF
POS.
CATALOGNUMBER HUB
CONNECTOR CU/AL BY-
PASS
DIMENSIONS CONCENTRIC K.O.ʼS
1 2 3 4 5D″ W″ H″LINE LOAD
2 U1252-X-KK-K1-PED C.P. HORN 21⁄2 21⁄2 21⁄23⁄8 PED51⁄8 261⁄2 14#6-350
kcmil#6-350kcmil
3 U1253-X-KK-K3-PED C.P. HORN 21⁄2 21⁄2 21⁄23⁄8 PED51⁄8 3411⁄16 14#4-600
kcmil#6-350kcmil
4 U1254-X-KK-K3-PED C.P. HORN 21⁄2 21⁄2 21⁄23⁄8 PED51⁄8 427⁄8 16#4-600
kcmil#6-350kcmil
5 U1255-X-KK-K4-PED C.P. HORN 21⁄2 21⁄2 21⁄23⁄8 PED51⁄8 547⁄8 16(2)#2-600
kcmil#6-350kcmil
6
AMPS
200
200
200
200
200 U1256-X-KK-PED C.P. HORN 21⁄2 21⁄2 21⁄23⁄8 PED51⁄8 631⁄16 183/8″-16
STUD#6-350kcmil
1 1 2
34 453 1252-6L572-6
L572-XL-KKU1252-X-KK-K1(shown without
pedestal)
CECHAAPPROVED
15200 A
MP / PO
SITION
–7 TERM
INA
L–HO
RIZ
ON
TAL G
AN
GS–JA
W C
LAM
PING
LEVER
–RIN
GLESS–600 V
AC
200 AMP / POSITION–7 TERMINAL–HORIZONTAL GANGSJAW CLAMPING LEVER–RINGLESS–600 VAC
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
15
NO.OF
POS.
2
CATALOGNUMBER
U2732-XT-PED
HUB
(2)C.P.
CONNECTOR CU/AL BY-
PASS
LEVER
DIMENSIONS CONCENTRIC K.O.ʼS
1
21⁄2 21⁄2 PED 21⁄2 1⁄4,1⁄2
2 3 4 5D″
6
W″
321⁄8
H″
251⁄4
LINE
3/8″-16STUD
LOAD
#6-350kcmil
3 U2733-XT-PED (2)C.P. LEVER 21⁄2 21⁄2 PED 21⁄2 1⁄4,1⁄26 423⁄16 251⁄4
3/8″-16STUD
#6-350kcmil
4 U2734-XT-PED (2)C.P. LEVER 21⁄2 21⁄2 PED 21⁄2 1⁄4,1⁄26 521⁄4 251⁄4
3/8″-16STUD
#6-350kcmil
5 U2735-XT-PED (2)C.P. LEVER 21⁄2 21⁄2 PED 21⁄2 1⁄4,1⁄26 625⁄16 251⁄4
3/8″-16STUD
#6-350kcmil
6 U2736-XT-PED (2)C.P. LEVER 21⁄2 21⁄2 PED 21⁄2 1⁄4,1⁄26 723⁄8 311⁄4
3/8″-16STUD
#6-350kcmil
SERV.
OH/UG
OH/UG
OH/UG
OH/UG
OH/UG
AMPS
200
200
200
200
200
200 AMP —7 TERMINAL—RINGLESS—3∅4W—OVERHEAD/UNDERGROUND*
HUBS: Units supplied with two closing plates. To order hubs as extra refer to the hub suffix chart on the accessorypage.
BYPASS: Lever supplies clamping action on meter spades and also operates bypass device.*CONNECTOR KITS: Line wire sections supplied with studs. For connector kits order K3082 (single-350 kcmil),
K3441 (single-600 kcmil), or twin K3442 (twin-350 kcmil) or K3083 (twin-600 kcmil). Line connectors can bereversed to change from “OH” to “UG” service.
*UNDERGROUND PEDESTALS: For underground service order S2291-TO pedestal raceway. A 12″ pedestal exten-sion kit is also available. Order catalog number S2571.
BUSSING: Bussing is 3/8″ x 1″ aluminum. Refer to the conduit & ampacity information page for information onampacity of bussing.
1 1 1 2
4 453
U2732-XT-PED(shown without pedestal)
CENTER WIREWAY
CECHAAPPROVED
CONDOMINIUM METERING BANKS–RINGLESS–OH/UG SERVICE–1∅3W–120/240 VAC16C
ON
DO
MIN
IUM
MET
ERIN
G B
AN
KS–
RIN
GLE
SS–O
H/U
G S
ERV
ICE–
1∅3W
–120
/240
VA
C
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
16
CATALOGNUMBER
NO.OF
POS.
2
3
MAIN BUSRATING
LINECONNECTOR
SIZE
U2852-X-KK-K1-PED 200 amp
U2853-X-KK-K1-PED 200 amp
#6-350 kcmil
#6-350 kcmil
CATALOGNUMBER
NO.OF
POS.
4
5
MAIN BUSRATING
LINECONNECTOR
SIZE
U2854-X-KK-PED 400 amp
U2855-X-KK-PED 400 amp
*3/8″-16 STUD
*3/8″-16 STUD
6 U2856-X-KK-PED 400 amp *3/8″-16 STUD
CATALOGNUMBER
NO.OF
POS.
4
5
MAIN BUSRATING
LINECONNECTOR
SIZE
U2864-X-KK-PED 400 amp
U2865-X-KK-PED 600 amp
*3/8″-16 STUD
*3/8″-16 STUD
6 U2866-X-KK-PED 600 amp *3/8″-16 STUD
CATALOGNUMBER
NO.OF
POS.
2
3
MAIN BUSRATING
LINECONNECTOR
SIZE
U2862-X-KK-K1-PED 250 amp
U2863-X-KK-K1-PED 300 amp
#6-350 kcmil
#6-350 kcmil
SIZE SUFFIX
SINGLE
TWIN
K1539-K1
-K3
-K2
-K4
K1540
K1350
K1541
U2852-56U2862-66
U2854-56U2864-66
U2854-56U2863-66
U2864-66
#6-350kcmil
#4-600kcmil
#6-350kcmil
#2-600kcmil
KITNUMBER
COMPATIBLEWITH
WIRERANGE
125 AMP/POSITION 200 AMP/POSITION
125 AMP/POSITION 200 AMP/POSITION
CONNECTOR KITS *
VERTICAL—1∅
RECTANGULAR—1∅
U2864-X-PED-KK(Order breakers and pedestal
raceway as extra)
U2866-X(Shown without pedestal)
CECHAAPPROVED
*CONNECTORS: For line wire connector kits, order separately.FIFTH TERMINALS: For field mounted fifth terminal order cata-
log number K2381. Order one per meter position (9 oʼclockposition only).
BREAKERS: Units have provision for one double pole main permeter position. Breakers not included, order as extra.
UNDERGROUND SERVICE: For underground service orderS2291-TO pedestal raceway. Order separately.
PEDESTAL EXTENSION KIT: A 12” pedestal extension kit isalso available. Order catalog number S2571.
PLUG-IN BREAKER COMPATIBILITY CHART
AMPS CUTLER-HAMMER(WESTINGHOUSE)
SIEMENS(ITE)
SIEMENSMURRAY /
CROUSE-HINDSG.E. SQ-D
125-200 HQP / BR / WBJ — MD THQ —
≤ 100 QP / BR / HQP QP MP THQ HOMELINE
17C
ON
DO
MIN
IUM
METER
ING
BA
NK
S–RIN
GLESS–O
H/U
G SER
VIC
E–1∅3W
–120/240 VA
CCONDOMINIUM METERING BANKS–RINGLESS–OH/UG SERVICE–1∅3W–120/240 VAC
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
17
29" or 41"
4-7/8"
25" or 37"
21"
E
A
18"
A A 4-7/8"
D D
E E
PED
PED
C
AA
25" or 37"
4-7/8"
31"
PED A AA A
C
29" or 41"
4-7/8"
36"
PEDE E E E EE
VERTICALwith pedestal option in bottom
RECTANGULARwith pedestal option in bottom
125 amp/pos.(2-3 position)
200 amp/pos.(2-3 position)
125 amp/pos.(4,5 & 6 position)
200 amp/pos.(4,5 & 6 position)
FIG.
A
B
C
D
E
DIMENSIONS
11⁄4 ″ CONCENTRIC K.O.
1⁄4,1⁄2″ CONCENTRIC K.O.
3″ CONCENTRIC K.O.
4″ HUB OPENING
2″ CONCENTRIC K.O.
PEDESTAL OPTIONPedestal Raceway
S2291-TO
PEDESTAL OPTIONPedestal Extension Unit
S2571
CECHAAPPROVED
CONDOMINIUM METERING BANKS
FIFTH TERMINAL # K2381(125-200 amp)
U2852-X
100 / 200 AMP–4 TERMINAL–RESIDENTIAL PEDESTALSINGLE OR DOUBLE POSITION–1∅3W–600 VAC18
100
/ 20
0 A
MP–
4 TE
RM
INA
L–R
ESID
ENTI
AL
PED
ESTA
L–SI
NG
LE O
R D
OU
BLE
PO
SITI
ON
–1∅
3W–6
00 V
AC
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
18
Extension UnitK5800
U8436-O
HANGING HOOK: Supplied with keyhole hanger for easy mounting.EXTENSION UNIT: For 24” burial applications, order extension unit S8988 for U8303-O. For 15” burial applications, order exten-
sion unit K5800 for U8436; for 30” applications, order (2) K5800 units.FIFTH TERMINAL: For field installed fifth terminal on U8436, order catalog number K5T (9 oʼclock position). For field installed
fifth terminal on U8303-O, order catalog number 5T8K2 (9 oʼclock position).BYPASS: Horn type bypass used on both units.BLOCK ASSEMBLY: For block assembly information for the U8436, see accessory section.
AMP
200
SERVICE CATALOGNUMBER
HUB
UG U8436-O BLANK
CONNECTORSCU/AL
LINE(COMPRESSION) LOAD
BY-PASS
HORN
DIMENSIONS CONCENTRIC K.O.ʼS
1 2 3 4 5
2 2 5⁄161⁄2 2
D″ W″ H″
41⁄8 9 624/0 (Line)2/0 (Neutral) #6-350 kcmil
6
—
200 2 POS-UG U8303-O BLANK HORN 11⁄4 5⁄16 21⁄2 21⁄2 21⁄241⁄2 83⁄16 744/0 (Line)2/0 (Neutral) #6-350 kcmil 1⁄4,
1⁄2
100 / 200 AMP—4 TERMINAL—CECHA APPROVED—RINGLESS—1∅3W—600 VAC
18"
Grade Line
3
Grade Line
CHECHAMILBANK
6
6
221
CHECHA
52
3
24 4
U8303-O
Extension UnitS8988
CECHAAPPROVED
GRADE LINE
1
2
2
5
32
3
4
18.00
19100 / 200 A
MP–1∅
–120 / 240 VA
C–4 TER
MIN
AL–M
ETER M
AIN
PEDESTA
L100 / 200 AMP–1∅–120 / 240 VAC–4 TERMINAL–METER MAIN PEDESTAL
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
100 / 200 AMP—1∅3W—RINGLESS–UNDERGROUND FEED
HUBCONNECTOR
CU/AL
LINE LOAD
BLANK #6-350KCMIL CB *
CATALOG NUMBER
NU8980-O-KK
NU8980-O-KK-LP BLANK #6-350KCMIL CB *
BLANK #6-350KCMIL #6-1/0NU8980-O-SF100-KK
NU8980-O-SF100-KK-LP
NU8980-O-200-KK
NU8980-O-200-KK-LP
22K10K
MAIN BREAKER
——
— —
UQFPHUQFP
Q2100HQ2100
UQFPHUQFP
UQFPHUQFP
BLANK
BLANK
BLANK
DIMENSIONS CONCENTRIC K.O.ʼS
1 2 3D″ W″ H″
21⁄2 21⁄2 —6 9 79
21⁄2 21⁄2 —6 9 70
21⁄2 21⁄2 —6 9 79
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
21⁄2
—
—
—
6
6
6
9
9
9
70
79
70
#6-350KCMIL
#6-350KCMIL
#6-350KCMIL
#6-1/0
1/0-300
1/0-300
MILBANK
1
2
Grade Line
STD = 79"-LP = 70"
STD = 36"-LP = 24"
* FIELD INSTALLED CIRCUIT BREAKER REQUIRED.MAIN CIRCUIT BREAKERS: For 10K AIC order with factory installed main. For 22K AIC order pedestal without main and order
circuit breaker separately. All main breakers are parallel connected. For series wired main order wire kit # K4714 and UQFP-Mtype circuit breaker. See Milbank circuit breaker chart on accessory page.
BRANCH CIRCUIT BREAKERS: Branch Interior accepts most manufacturers small frame plug-in type circuit breakers (Milbank,GE, Siemens, Cutler-Hammer, Murray).
SF in catalog number has small frame plug-in type circuit breaker installed on middle stabs of 4 circuit interior. Only two single polespaces available.
FIFTH TERMINAL: For field installed 5th terminal order kit # 5T8K2. Mounts in 9 o'clock position only.BYPASS: All pedestals have horn-type bypass installed for meter testing or replacement without interrupting customer service.EXTENSION KIT: Available for low profile (-LP) units only. Order kit # K4694. See accessory page.
NU8980-O-KK
CECHAAPPROVED
BY-PASS
HORN
HORN
HORN
HORN
HORN
HORN
19
U5706 TEMP TO FINAL SERVICE PEDESTAL–RINGLESS20
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
20
SPECIFICATIONS• 200 amp, 1∅, 120/240 volt, 22K AIC, underground service only.• U5706 has Ringless meter socket available with or without horn bypass (-KK). • Suitable for use as service equipment, mobile home service equipment and temporary power
service equipment.*• Provisions for up to two Type 3R in-use receptacle kits. *• Order receptacle and bridge kits separately. See ordering information.• Direct burial pedestal suitable for free standing or structure mounted installation.• Separate line and load wireways are removable, lockable and sealable for security.• Left side is for utility connection. Right side is for customer underground load exit.• Convenient knockouts in post for thru-wall load exit requirements.• Type 3R enclosure constructed with type G90 galvanized steel. • Repaintable light gray polyester powder coat finish.• Wire terminations accept copper or aluminum conductors: Line & Neutral: #6-350 Ground: (4) #14-1/0.• Main circuit breaker can be series or parallel connected. • Universal 4 circuit branch 125 amp interior (up to (2) 2-pole) accepts most manufacturers plug-in type
circuit breakers. See wiring diagram.
U5706-O-200S*(Shown with (2) K5400-520GR receptacles,
K5400-BRIDGE-2POS & line side conduc-tor installed.)
8-1/2”
13-1/4”
19”
A
A
A
A
A
30-3/16”
E
Bridge Kit(4) .173” Extr. Holes
3-1/2”
B
C
D
OPEN
Concentric KnockoutsA (4) = 1, 1-1/2, 2, 2-1/2”
B (1) = 1-1/4, 1-1/2, 2”
C (1) = 3/4”, 1”
D (1) = 1/4”, 1/2”
E (1) = 1” Solid
U57
06 T
EMP
TO F
INA
L SE
RV
ICE
PED
ESTA
L–R
ING
LESS
21U5706 TEMP TO FINAL SERVICE PEDESTAL ORDERING INFORMATION
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
21
U5706 Ringless PedestalMain Main Replacement Branch Weight
Catalog Number Amps Service By-Pass Circuit Breaker Wired Main Type* Circuits LBS.
◆ U5706-O-200S-CECHA 200 120/240 None 200a 2p Series UQFPH-M 4 79
Up to two receptacle/circuit breaker kits can be field or factory installed. See below for ordering information. Contact factory for factory installed kits.
To increase pedestal height, order field-installed post extension kit K5708.For field installed fifth terminal in the 9 oʼclock position, order kit 5T9.For field converting from parallel to series wired, order kit K5194. For field converting from series to parallel wired, order kit K5193.
Receptacle / Circuit Breaker Kits & Receptacle Bridge Kits
Catalog Number Amps/ Volts NEMA Config Circuit Breaker Conductor Configuration
◆ K5400-520GR 20a 120v 5-20R Duplex GFI 20a 1p 12 awg Fig. 1
◆ K5400-620 20a 240v 6-20R Simplex 20a 2p 12 awg Fig. 2
◆ K5400-620GB 20a 240v 6-20R Simplex 20a 240v GFI 12 awg Fig. 3
◆ K5400-1450 50a 120/240v 14-50R 50a 120/240v 8 awg Fig. 4
◆ K5400-1450GB 50a 120/240v 14-50R 50a 120/240v GFI 8 awg Fig. 4
◆ K5400-BRIDGE-1POS Self-grounded ONE position bridge with hardware and instructions. Fig. 5
◆ K5400-BRIDGE-2POS Self-grounded TWO position bridge with hardware and instructions. Fig. 6
Receptacle kits include: receptacle, circuit breaker, connected wire, cover plate, mounting screws and instructions. Contact factory for other kits.
NOTE: Receptacle grounding is provided by metal contact with bridge and pedestal. Be sure to torque all fasteners per torque requirements.
◆ Stock item – availability subject to prior sale.
Non-stock items – minimum order quantity required.
Fig. 1 Fig. 2 Fig. 3 Fig. 4K5400-520GR K5400-620 K5400-620GB K5400-1450
Fig. 5 Fig. 6 Fig. 7K5400-BRIDGE-1POS K5400-BRIDGE-2POS UQFPH-M-200
U5706 TEM
P TO FIN
AL SER
VIC
E PEDESTA
L OR
DER
ING
INFO
RM
ATIO
N
320 AMP–4 TERMINAL–METER PEDESTAL WITH LEVER BYPASS2232
0 A
MP–
4 TE
RM
INA
L–M
ETER
PED
ESTA
L W
ITH
LEV
ER B
YPA
SS
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
22
CATALOGNUMBER
U3849-O-2/200
SERVICE
UG
HUB
NONE
CONNECTORSCU/AL
LINE LOAD3/8″ X 16STUDS
C.B. #1- 300kcmil
BY-PASS
LEVER
DIMENSIONS CONCENTRIC K.O.ʼS
1D″ W″ H″
21⁄247⁄8 13 58
2
21⁄2
3
5⁄16
4
—
5
—
320 AMP–4 TERMINAL—METER MAIN WITH BREAKERS—RINGLESS—240 VAC
CATALOGNUMBER
U1748-O
SERVICE
UG
HUB
NONE
CONNECTORSCU/AL
LINE LOAD3/8″ X 16STUDS
TWIN#6-350 kcmil
BY-PASS
LEVER
DIMENSIONS CONCENTRIC K.O.ʼS
1D″ W″ H″
21⁄247⁄8 13 64
2
21⁄2
3
21⁄2
4
5⁄16
5
—
320 AMP–4 TERMINAL—WITHOUT BREAKER—RINGLESS—600 VAC
CONNECTORS: The line wire section is supplied with 3⁄8″–16 studs with hex head nuts and captive Belleville washers. Theline side connectors are to be supplied by the Utility, load side is furnished.
BYPASS: The lever supplies clamping action on the meter spade and also operates the bypass device.FIFTH TERMINAL: For field installed fifth terminal order kit #K3865.PEDESTAL EXTENSION KIT: If extension kit is required, order as extra kit # S1848. See accessory page.
BREAKERS: The U3849 is furnished with (2) 200 amp Milbank type UQFBH-200 circuit breakers.PEDESTAL EXTENSION KIT: If extension kit is required, order as extra kit # S1848. See accessory page.THIS UNIT IS RATED 22,000 AIC—SHORT CIRCUIT CURRENT RATING WITH MILBANK UQFBH SERIES CIRCUIT
BREAKER.
U3849-O-2/200U1748-O
Grade Line
1 2
3
M I L B A N K
3
3 3
Grade Line
18"
Grade Line
1
2 3
1
2
4 4
4 4
Grade Line
18"
320 AMP CONTINUOUS400 AMP MAX
4-27/32"I.D.13"
O.D.
16-15/16"15"
S1848Pedestal Extension Unit
CECHAAPPROVED
23100 / 200 A
MP–5 &
7 TERM
INA
L–LEVER
BY
PASS–H
EAV
Y D
UTY
PEDESTA
L–600 VA
C100 / 200 AMP–5 & 7 TERMINAL–LEVER BYPASS–HEAVY DUTY PEDESTAL–600 VAC
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
23
1 2 3
44
MILBANK
4 4
4 4
CATALOGNUMBER
U9108-O
SERVICE
UG
HUB
BLANK
CONNECTORSCU/AL
LINE LOAD
3/0-4/0 #6-350kcmil
BY-PASS
LEVER
DIMENSIONS CONCENTRIC K.O.ʼS
1D″ W″ H″
21⁄26 11 58
2
21⁄2
3
21⁄2
4
5⁄16
5
—
#OF
TERMS
5
100 / 200 AMP—5 TERMINAL—HEAVY DUTY—1∅-3W OR 3∅-3W
CATALOGNUMBER
U9107-O
SERVICE
UG
HUB
BLANK
CONNECTORSCU/AL
LINE LOAD
3/0-4/0 #6-350kcmil
BY-PASS
LEVER
DIMENSIONS CONCENTRIC K.O.ʼS
1D″ W″ H″
21⁄26 11 58
2
21⁄2
3
21⁄2
4
5⁄16
5
—
#OF
TERMS
7
100 / 200 AMP—7 TERMINAL—HEAVY DUTY—3∅4W
BYPASS: Lever supplies clamping action on meter spades and also operates bypass device.BOTTOM PLATE: Bottom plate is not furnished with this unit. However, plates are required on all installations within the
city of Chicago. Order catalog number S9157 as extra.NEUTRAL: The U9108-O is supplied with a center disconnect neutral. EXTENSION KIT: For direct burial applications, order kit S3488 as separate item.
U9107-O
91089107
PEDESTAL EXTENSION UNITS3488
CECHAAPPROVED
JOINT USE TERMINATION CABINET24JO
INT
USE
TER
MIN
ATI
ON
CA
BIN
ET
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
24
Grade Line
12"
58"
13" 13"
37 5/16" 33 5/16" 39"
1
3
21"2
4 6"
JOINT USE TERMINATION CABINET
CATALOGNUMBER HUB
CONNECTOR CU/AL BY-
PASS
DIMENSIONS CONCENTRIC K.O.ʼS
1 2 3 4D″ W″ H″LINE LOAD
U4329-O BLANK NONE (6)1″ (1)1⁄2″ (1)1″ (2)7⁄16″41⁄2 13 58NONE NONE
COMMUNICATION COMPARTMENT: Easily attaches to Milbank meter pedestals for use in newconstruction.
TELEPHONE AND CABLE CONDUCTORS: This unit will accommodate both telephone and cable con-ductors, eliminating the use of multiple, unsightly network interface devices on the outer structure of thehome, while providing tamper resistance to the communication modules.
SINGLE LOCATION POINT OF SERVICE: The S4329 combined with the Milbank meter pedestalprovides a single location point of service making access for utility service personnel convenient andefficient.
APPROVED: The U4329 is approved by COMMONWEALTH EDISON COMPANY and all majorWISCONSIN UTILITIES.
U4329
CECHAAPPROVED
2520 A
MP–6, 8 &
13 TERM
INA
L–INSTR
UM
ENT TR
AN
SFOR
MER
RA
TED SO
CK
ET20 AMP–6, 8 & 13 TERMINAL–INSTRUMENT TRANSFORMER RATED SOCKET
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
25
1
3 4 56
2
# OFTERMS
6
PHASE CATALOGNUMBER
1∅3W CE136
SERVICEDIMENSIONS CONCENTRIC K.O.ʼS
1 2 3 4 5
11⁄4 11⁄4 11⁄4 11⁄4 11⁄4
6
1⁄4,1⁄2
D″ W″ H″
41⁄8 12 20Bottom Feed
8 3∅3W CE138 11⁄4 11⁄4 11⁄4 11⁄4 11⁄4 1⁄4,1⁄241⁄8 12 20Bottom Feed
13 3∅4W CE1313 11⁄4 11⁄4 11⁄4 11⁄4 11⁄4 1⁄4,1⁄241⁄8 12 20Bottom Feed
20AMP—6, 8 & 13 TERMINAL—TRANSFORMER RATED SOCKET
CE1313CE136
CECHAAPPROVED
• Type 3R enclosure• One-piece sealable cover, padlock provision• Approved by COMMONWEALTH EDISON COMPANY and all major WISCONSIN UTILITIES.
COMMERCIAL METER PEDESTALS OVERVIEW26C
OM
MER
CIA
L M
ETER
PED
ESTA
LS O
VER
VIE
W
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
26
ilbank Commercial Pedestals are pad-mounted, weatherproof electricalenclosures consisting of a utility pull section with optional meter socket, anda customer section containing distribution and control equipment. Milbank
Commercial Pedestalsare an attractive, secure,easy to install and cost-effective solution whenunderground remotesite power distributionand control equipmentis required, replacingunsightly and inefficientstrut and backboardstructures.
Un-Strut
Your
Stuff...
Commercial Pedestals • Attractive • Easy to install • Secure • Cost effective
STANDARD FEATURES –COMMERCIAL PEDESTALS
• Type 3R rainproof, vandal-resistant cabinet ofpolyurethane powder-coated steel (aluminum orstainless steel also available)
• UL listed as enclosed industrial control equip-ment (UL508)
• Isolated, lockable & sealable utility metering &lug landing sections
• Lockable customer section for distribution &control equipment with internal deadfront
• Print pocket inside customer section doorcontains wiring schematicsand installation instructions
• Most load centers are UL listed for use with variousmanufacturers’ circuit breakers
• All stainless steel externalhardware (screws, bolts,hinges, handles, hasps andsealing screws)
• Meets EUSERC 308 and otherutility standards.
Ringless Socket Ring-type Socket
Utility Lug Landing Customer Interior
UL Listed as Industrial Control Equipment (File E113855).
Strut and backboard design Commercial Pedestal
27APPLICATIONS & ACCESSORIES
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
27
CP-16PDMNT-CALTPedestal mounting base for 16" pedestal CP-24PDMNT-CALTPedestal mounting base for 24" pedestal (includes mounting hardware)CP-32PDMNTPedestal mounting base for 32" pedestal (includes mounting hardware)
CP-ABK5/8Anchor bolt kit (includes four 5/8 -13 x 18" anchor bolts) CP-PE-HOA-3POS
HOA switch – for fieldinstallation
ACCESSORIES
CP-TC7D 7-day time clock kit
CP-TC24H 24-hour time clock kit
CP-TCWIRE Male four-pin connector and wiring harness for use with time clocks other than shown
K3865Fifth terminal kit foruse with ringlessmeter sockets
• Meter sockets – ring type or ringless, to 400 amp (unmeteredand dual-metered pedestals also available)
• Main and branch breakers or T fuses• Distribution – copper load centers & panel boards • Clocks / timers / relays• Photoelectric cells and controls• Power receptacles – pin & sleeve, twist lock or straight blade • Contactors – definite purpose, electrical or mechanically
held, IEC and mercury types• Surge protection & lightning arrestors• Reserve inlet generator receptacle with interlocked circuit
breakers
• Motor starters, relays • Push button controls• Thermostat controls, fans and heating strips• Power blocks and terminal blocks• Steel, aluminum and plywood back boards• Transformers• Interlock devices for circuit breakers• Available in steel, aluminum (raw painted or anodized) or
stainless steel construction with powder-coated finish avail-able in 8 standard colors or special ordered RAL colors.
• Available for applications up to 400 amp, 120V, 208V,240V, 277V, 480V – 1Ø or 3Ø.
APPLICATIONSThese units are ideal for controlling and metering:• Traffic signals• Street lighting• Irrigation / sprinkler systems• Cell towers / telephone vaults• Pump stations• Temporary power for fairgrounds, swap meets, outdoor
markets, portable offices, holiday lights, etc.• Outdoor lighting for athletic fields, tennis and basketball courts, parking lots, land-
scaping and subdivision entrances, etc.
AVAILABLE FACTORY-INSTALLED OPTIONS
105JFifth terminalkit for usewith ring-typemeter sockets
CP-16FPADFiberglass pedestal mounting basefor 16" pedestal (direct buried)
APPLIC
ATIO
NS &
AC
CESSO
RIES
DISCONNECT SLEEVE*
M5-144
ACCESSORIES28A
CC
ESSO
RIE
S
4 1⁄2 8 3⁄16 15S8988
CATALOGNUMBER
D″ W″ H″
S3488S2571S1848
6 11 15
4 1⁄8
4 7⁄8
10
13
12
15
K4694K5800
6
4 1⁄89
9
24
15
INTERCHANGEABLE UNIT HUBS
CLOSING COVERS
METAL CLOSING PLATE(for ringless sockets)
CP-21
METER CLOSING PLATE(Gray Plastic)
6003
HUBADAPTER PLATE
(Converts 4″ opening to21⁄2″ opening.)
S8324
FIFTH TERMINALS
100-200 amp “PLUG-IN” FIFTH TERMINAL
5T8K2
200 ampFIFTH TERMINAL
K5T(New style block with square hole)
HEAVY DUTY JAWCLAMPING
K3865
FOR CONDO METERING BANKS
(125-200 amp) K2381
PEDESTAL EXTENSION UNITS
HUB SUFFIX CHART
O Plain Top WL 1″ For -RL OpeningYL 11⁄4″ For -RL OpeningZL 11⁄2″ For -RL OpeningDL 2″ For -RL OpeningELF
G
H
21⁄2″ For -RL Opening
3″ For -R Opening
31⁄2″ For -R Opening
4″ For -R Opening
RL Small Hub OpeningR Large Hub OpeningXL Small Closing PlateX
RXL Large Hub Openingadapted to small Closing Plate
RRL Large Hub Openingadapted to small Hub Opening
Large Closing Plate
REMOVABLE HUBCLOSING PLATE
DESCRIPTION SUFFIX CAT. #
-XL A7551
LARGE(for -R opening)
-X A9064
1″WL
SIZESUFFIX MILBANKNO.
YLZLDLEL
A751411⁄4″ A751511⁄2″ A75162″ A7517
21⁄2″ A7518
3″F
SIZESUFFIX MILBANKNO.
GH
A811031⁄2″ A81114″ A8112
SMALL “RL"OPENING(STANDARD)
LARGE “R” OPENING(HEAVY DUTY)
STANDARD(for -RL opening)
*NOT TO BE USED WITH LEVERBYPASS SOCKETS
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
28
29ACCESSORIES
29
PLUG-IN BREAKER COMPATIBILITY CHART
AMPS MILBANK CUTLER-HAMMER(WESTINGHOUSE)
SIEMENS(ITE)
SIEMENSMURRAY /
CROUSE-HINDSG.E. SQ-D
125-200 Q / QN HQP / BR / WBJ Q / QN MD THQ —
≤ 100 Q QP / BR / HQP QP MP THQ HOMELINE
MILBANK2-POLE—LARGE FRAME—10K AIC & 22K AIC
AMPS
100 UQFP-100
125 UQFP-125
150 UQFP-150
175 UQFP-175
200 UQFP-200
10,000 AICPLUG-IN
UQFPH-100
UQFPH-125
UQFPH-150
UQFPH-175
UQFPH-200
UQFB-100
UQFB-125
UQFP-150
UQFB-175
UQFB-200
10,000 AICBOLT-ON
22,000 AICPLUG-IN
UQFP-M-100
UQFP-M-125
UQFP-M-150
UQFP-M-175
UQFP-M-200
10,000 AICPLUG-IN
UQFPH-M-100
UQFPH-M-125
UQFPH-M-150
UQFPH-M-175
UQFPH-M-200
22,000 AICPLUG-IN
UQFB-100-X1
UQFB-125-X1
UQFP-150-X1
UQFB-175-X1
UQFB-200-X1
10,000 AICBOLT-ON
UQFBH-100
UQFBH-125
UQFBH-150
UQFBH-175
UQFBH-200
22,000 AICBOLT-ON
BLOCK ASSEMBLIESCONNECTOR KITS
For use with 3/8”-16stud type units only
SINGLETWIN
K1350K2 6-350 kcmil
K1350L
K1541
K2L
K4
6-350 kcmil Non-rotating
4-600 kcmil
CATALOG #SUFFIX (3 per set) – 1 ∅
K3442K6 6-350 kcmil K3083K8 4-600 kcmil
CATALOG #SUFFIX (4 per set) – 3 ∅
K3082K5 6-350 kcmil
K3441K74-600 kcmil or
(2) 1/0-250 kcmil
CATALOG #SUFFIX (4 per set) – 3 ∅
K1539K1 6-350 kcmil
K1540
K1540L
K3
K3L
4-600 kcmil or(2) 1/0-250 kcmil
4-600 kcmil or(2) 1/0-250 kcmil
Non-rotating
CATALOG #SUFFIX (3 per set) – 1 ∅
Replaces the load side slide-in nut assembly onMilbank 200 amp sockets. Allows for a 100 amp taplocation in addition to the #6-350 kcmil load-sideconnector. K5022 Includes Safety BarrierExtensions–for applications over 300 VAC.
K4977-INT INTERNAL HEX
K5022-INT INTERNAL HEX
PERFECT FOR 100 AMP FEEDS TO:• Outdoor Lighting• Water Well Pumps• Hot Tubs and Swimming Pools• Outbuildings• Whole House Surge Suppressors
LOAD TAP CONNECTORS (3 per set)
STD.BLOCKASSEMBLY(200 amp)
K4529
LEFT & RIGHT BLOCKASSEMBLY FOR U8436
(200 amp) Z917525-AC Left
Z917526-AC Right
Utility requirements for this equipment may vary. Always consult the serving utility for their requirements before ordering orinstalling equipment in this catalog.
AC
CESSO
RIES
CONDUIT AND AMPACITY INFORMATION30C
ON
DU
IT A
ND
AM
PAC
ITY
IN
FOR
MA
TIO
N
30
TYPE
RHW & RHH(without outer covering)
THW
CONDUCTORSIZE
AWG,MCM1412108
CONDUIT TRADE SIZES (INCHES)1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 31⁄2 46441
10863
1613115
29241910
40322613
65534322
93766132
1431179549
19215712766
16385
6 1 2 3 7 10 16 23 36 48 62
3 1 1 2 4 6 10 15 23 31 40
1/02/03/04/0
250300350400500
600700750
111
1111
2111
3321
5543
8765
121097
16141210
21181513
11
11111
11111
22111
43321
65443
87654
109876
111
111
111
322
433
544
TWTHW
FEPB (6 thru 2),RHW and
RHH(without outer covering)
RH, THHW
*This table is for concentric stranded conductors only. For cables with compact conductors refer to N.E.C.
*CU
A
18161412108
64321
1/02/03/04/0
250300350400500
600700750
255285310335380
420460475
——
20✝25✝35✝50
6585100115130
150175200230
B
250300350400500
600700750
———12108
64321
1/02/03/04/0
A
AL or Cu-Clad AL
205230250270310
340375385
———
20✝30✝40
50657590100
120135155180
C
AMBIENTTEMP.C°
CORRECTIONFACTOR
AMBIENTTEMP.F°
21 - 25 1.05 70 - 7726 - 30 1.00 79 - 8631 - 35 .94 88 - 9536 - 40 .88 97 - 10441 - 45 .82 106 - 11346 - 50 .75 115 - 12251 - 55 .67 124 - 13156 - 60 .58 133 - 14061 - 65 .33 142 - 15866 - 70 — 160 - 176
* ALLOWABLE AMPACITIES OF INSULATED COPPER &ALUMINUM CONDUCTORS (3W IN CONDUIT) 75°C (167°F)
AMPACITY CORRECTION FACTORS
Overall ampere ratings of UL Listed Milbank multiple position meter sockets are based on 1993N.E.C. Manual article 220-32 and ANSI / UL-414 (except where restricted by line connector size).These requirements provide for a diversity factor / demand factor being utilized in determining the over-all (main bus / lug) rating of a gang socket. All Milbank UL Listed gang sockets meet or exceed thesediversity factor/demand factor requirements. Standard overall ampacity ratings for UL Listed and nonUL Listed gang sockets are as shown in the chart below. Ampere ratings of meter sockets are basedon the meter socket being wired with 75° C insulated wire conductor, sized in accordance with Table310-16 of the National Electric Code.
NO. OF METERPOSITIONS
100A / POS.AMPACITY
125A / POS.AMPACITY
150A / POS.AMPACITY
200A / POS.AMPACITY
23456
200A200A200A225A270A
200A225A250A285A330A
200A225A270A338A396A
200A270A360A450A528A
MAXIMUM NUMBER OF CONDUCTORS IN CONDUIT*
A = Size: AWG/MCMB = Ampere Rating forInsulation Types:
FEPW, RH, RHW,THW, THWN, XHHW,
USE, 2W.C = Ampere Rating forInsulation Types:
RH, RHW, THW,THWN, XHHW, USE
(Per NEC table 310-16)
✝ Unless otherwise permitted elsewhere in the Code, the overcurrent protection for conductor types marked with an obelisk (✝) shall not exceed 15amps for 14 AWG, 20 amps for 12 AWG, and 30 amps for 10 AWG copper: or 15 amps for 12 AWG and 25 amps for 10 AWG aluminum andcopper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.
All meter sockets are 600 Volt rated unless otherwise noted.All meter socket ampacity ratings are continuous duty unless otherwise noted.
GANG SOCKET OVERALL AMPACITIES
31ENERGIZATION OF ELECTRICAL EQUIPMENT
31
ENER
GIZ
ATIO
N O
F ELECTR
ICA
L EQU
IPMEN
T
BEFORE ENERGIZING
IMPORTANT NOTE
WHEN ENERGIZING
AFTER ENERGIZING
A. Give equipment a thorough visual examination to determine that:1) No shipping or installation damage exists.2) Proper clearances have been maintained.3) All connections have been made.4) Equipment is clean and dry.
B. Make a thorough examination to verify:1) Tightness of all bolted connections (see table below).2) Manually operate all circuit breakers, switches, relays, etc.3) Check rigidity of all mountings, bus bars and components.4) Use test equipment to check continuity of circuitry and integrity of insulation.
C. All switches and circuit breakers should be in the “off” position.D. Verify that manual meter bypass (if applicable) is in non-bypass position.E. Install cover and/or close doors.F. If installation is not being energized at this time, follow “after-energizing” steps listed below. These
steps will secure the installation in case of accidental energization.
A. Use caution and follow established safety procedures:1) Wear safety apparel.2) Use safety equipment.3) Take action to prevent injury to yourself and others in the event of failure of the installation.4) Take action to prevent/decrease damage to property in the event of failure of the installation.5) If you are unsure how to safely energize the installation, get someone who is knowledgeable to do it.
A. Secure the installation:1) To prevent accidental contact with energized parts, cover all openings with approved filler devices.2) To prevent unauthorized access, secure all covers and/or doors with approved security devices.3) Attach/post information to advise others of potential hazards associated with the installation.
NOMINALSIZE
10
10
10
12
12
1/4
1/4
5/16
JOINT DESCRIPTION
SCREW NUTBRASS
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
Brass Nut or Extruded Hole
CU or AL Busbar <1/8″Steel Nut or EH; CU or AL Busbar >1/8″
Aluminum Extruded Hole
Steel Nut or Extruded Hole
Aluminum Extruded Hole
Steel Nut or EH; CU or AL Busbar
Aluminum Extruded Hole
ALL
ALL
ALL
ALL
ALL
ALL
ALL
HEX
20-25 in. lbs.
25-30 in. lbs
30-35 in. lbs
30-35 in. lbs
40-50 in. lbs.
40-50 in. lbs.
50-60 in. lbs.
60-70 in. lbs.
5/16 STEEL Steel Nut or EH; CU or AL Busbar HEX 100-150 in. lbs.
3/8 STEEL Steel Nut HEX 150-200 in. lbs.
1/2 STEEL Steel Nut HEX 200-250 in. lbs.
HEAD TYPE TORQUE( INCH LBS. )
*Interior labels typically indicate the required torque for wire connectors and studs, and should be referenced first.EH: Extruded HoleCU: CopperAL: Aluminum
RECOMMENDED TORQUE FOR GENERAL APPLICATIONS*
In addition to national and local electrical codes, many utilities have specific requirements for metering equip-ment. Always consult the serving utility for their specifications and requirements prior to ordering or installingMilbank meter mounting equipment.
MATERIALS AND FINISHES32M
ATE
RIA
LS A
ND
FIN
ISH
ES
32
MATERIALS
STEEL SHEET
STEEL QUALITY
ALUMINUM EXTRUSION
ALUMINUM SHEET
COPPER SHEET & BUS
INSULATING MATERIALS
PROCESS
METAL FASTENERS
The meter equipment listed in this catalog is made of galvanized steel (AISI* G90) to afford thebest possible weather proofing. *American Iron and Steel Institute.
Light gray “state of the art” electrostatically applied powder paint offers a durable, non-fadingfinish. For further information concerning the chemical analysis of the weather resistant finish,please contact the factory.
Wire-Terminals: Alloy; 6061-T6, Tin-plated for CU/AL wire.Bus Bar: Alloy; 6101-o & 6063-O
3000 series aluminum sheet, H14, or 5052 series aluminum sheet, H32. Where applicable thick-nesses range from .064 — .125
Electrolytic copper with tin plating in most applications.
Zinc-coated with a chromate dip.
• In most units, support bases for current-carrying components are molded from fiberglass rein-forced high-strength, track resistant, thermoset polyester molding compounds.
• Clear or black safety shields and polarity barriers are molded from high-strength, track resistant,polycarbonate molding compounds.
• Various sheet insulating materials, as appropriate for the application are utilized in the fabrica-tion of flat, formed and punched component parts and barriers.
16 gauge, galvanized, sheet: 0.90 oz./ sq.ft. class zinc-coated.(AISI G90)14 gauge, galvanized, sheet: 0.90 oz./ sq.ft. class zinc-coated.
FINISH
NEMA RATING
All Milbank meter sockets, CT cans and meter socket / breaker units have a NEMA 3R rating.
RATING
33ADDITIONAL MILBANK PRODUCTS
33
COMMERCIAL / INDUSTRIALELECTRICAL ENCLOSURES
2008 PRICE LISTEffective June 2, 2008
Supercedes and cancels all previous Milbank lists.All prices listed within are subject to change without notice.
MILBANK MFG. CO.
Kansas City, MO 64141-6028Tel: 816.483.5314
www.milbankmfg.com
In addition to your local utility’s meter mountingequipment, Milbank also manufactures
supporting products, such as...
Air Conditioner DisconnectsHot Tub Disconnects
RV/Mobile Home Power OutletsTerminal Boxes
Temporary Power OutletsCommercial PedestalsCommercial Enclosures
CT EnclosuresCircuit Breakers
Distribution Unit SubstationsEnclosed Circuit Breakers
Safety SwitchesTest Switches
Contact your local distributor or go towww.milbankmfg.com
to find additional product literature.
Other quality products available from Milbank
AD
DITIO
NA
L MILB
AN
K PR
OD
UC
TS
INDEX34IN
DEX
34
105J . . . . . . . . . . . . . . . . . . . . . . . . . 27
6003 . . . . . . . . . . . . . . . . . . . . . . . . . 28
5T8K2 . . . . . . . . . . . . . . . . . . . . . . . 28
A7514 . . . . . . . . . . . . . . . . . . . . . . . . 28
A7515 . . . . . . . . . . . . . . . . . . . . . . . . 28
A7516 . . . . . . . . . . . . . . . . . . . . . . . . 28
A7517 . . . . . . . . . . . . . . . . . . . . . . . . 28
A7518 . . . . . . . . . . . . . . . . . . . . . . . . 28
A7551 . . . . . . . . . . . . . . . . . . . . . . . . 28
A8110 . . . . . . . . . . . . . . . . . . . . . . . . 28
A8111 . . . . . . . . . . . . . . . . . . . . . . . . 28
A8112 . . . . . . . . . . . . . . . . . . . . . . . . 28
A9064 . . . . . . . . . . . . . . . . . . . . . . . . 28
CE1313 . . . . . . . . . . . . . . . . . . . . . . 25
CE136 . . . . . . . . . . . . . . . . . . . . . . . 25
CE138 . . . . . . . . . . . . . . . . . . . . . . . 25
CP-16FPAD . . . . . . . . . . . . . . . . . . . 27
CP-16PDMNT-CALT . . . . . . . . . . . . 27
CP-21 . . . . . . . . . . . . . . . . . . . . . . . . 28
CP-24PDMNT-CALT . . . . . . . . . . . . 27
CP-32PDMNT . . . . . . . . . . . . . . . . . 27
CP-ABK5/8 . . . . . . . . . . . . . . . . . . . . 27
CP-PE-HOA-3POS . . . . . . . . . . . . . 27
CP-TC24H . . . . . . . . . . . . . . . . . . . . 28
CP-TC7D . . . . . . . . . . . . . . . . . . . . . 28
CP-TCWIRE . . . . . . . . . . . . . . . . . . . 28
K1350 . . . . . . . . . . . . . . . . . . . . . 16, 29
K1350L . . . . . . . . . . . . . . . . . . . . . . . 29
K1539 . . . . . . . . . . . . . . . . . . . . . 16, 29
K1540 . . . . . . . . . . . . . . . . . . . . . 16, 29
K1540L . . . . . . . . . . . . . . . . . . . . . . . 29
K1541 . . . . . . . . . . . . . . . . . . . . . 16, 29
K2381 . . . . . . . . . . . . . . . . . . . . . . . . 28
K3082 . . . . . . . . . . . . . . . . . . . . . . . . 29
K3083 . . . . . . . . . . . . . . . . . . . . . . . . 29
K3441 . . . . . . . . . . . . . . . . . . . . . . . . 29
K3442 . . . . . . . . . . . . . . . . . . . . . . . . 29
K3865 . . . . . . . . . . . . . . . . . . . . . . . . 28
K4529 . . . . . . . . . . . . . . . . . . . . . . . . 29
K4694 . . . . . . . . . . . . . . . . . . . . . . . . 28
K4977-INT . . . . . . . . . . . . . . . . . . . . 29
K5022-INT . . . . . . . . . . . . . . . . . . . . 29
K5800 . . . . . . . . . . . . . . . . . . . . . . . . 28
K5T . . . . . . . . . . . . . . . . . . . . . . . . . 28
L572-XL-KK . . . . . . . . . . . . . . . . . . . 14
L573-XL-KK . . . . . . . . . . . . . . . . . . . 14
L574-XL-KK . . . . . . . . . . . . . . . . . . . 14
L575-XL-KK . . . . . . . . . . . . . . . . . . . 14
L576-XL-KK . . . . . . . . . . . . . . . . . . . 14
M5-144 . . . . . . . . . . . . . . . . . . . . . . . 28
NU8980-O-200-KK . . . . . . . . . . . . . . 19
NU8980-O-200-KK-LP . . . . . . . . . . . 19
NU8980-O-KK . . . . . . . . . . . . . . . . . 19
NU8980-O-KK-LP . . . . . . . . . . . . . . 19
NU8980-O-SF100-KK . . . . . . . . . . . 19
NU8980-O-SF100-KK-LP . . . . . . . . 19
Q2100 . . . . . . . . . . . . . . . . . . . . . . . 19
Q2100H . . . . . . . . . . . . . . . . . . . . . . 19
S1848 . . . . . . . . . . . . . . . . . . . . . . . . 28
S2571 . . . . . . . . . . . . . . . . . . . . . . . . 28
S3488 . . . . . . . . . . . . . . . . . . . . . . . . 28
S8324 . . . . . . . . . . . . . . . . . . . . . . . . 28
S8988 . . . . . . . . . . . . . . . . . . . . . . . . 28
U1252-X-KK-K1-PED . . . . . . . . . . . . 14
U1253-X-KK-K3-PED . . . . . . . . . . . . 14
U1254-X-KK-K3-PED . . . . . . . . . . . . 14
U1255-X-KK-K4-PED . . . . . . . . . . . . 14
U1256-X-KK-PED . . . . . . . . . . . . . . 14
U1748-O . . . . . . . . . . . . . . . . . . . . . 22
U2732-XT-PED . . . . . . . . . . . . . . . . 15
U2733-XT-PED . . . . . . . . . . . . . . . . 15
U2734-XT-PED . . . . . . . . . . . . . . . . 15
U2735-XT-PED . . . . . . . . . . . . . . . . 15
U2736-XT-PED . . . . . . . . . . . . . . . . 15
U2852-X-KK-K1-PED . . . . . . . . . . . . 16
U2853-X-KK-K1-PED . . . . . . . . . . . . 16
U2854-X-KK-PED . . . . . . . . . . . . . . 16
U2855-X-KK-PED . . . . . . . . . . . . . . 16
U2856-X-KK-PED . . . . . . . . . . . . . . 16
U2862-X-KK-K1-PED . . . . . . . . . . . . 16
U2863-X-KK-K1-PED . . . . . . . . . . . . 16
U2864-X-KK-PED . . . . . . . . . . . . . . 16
U2865-X-KK-PED . . . . . . . . . . . . . . 16
U2866-X-KK-PED . . . . . . . . . . . . . . 16
U3800 . . . . . . . . . . . . . . . . . . . . . . . . 5
U3801 . . . . . . . . . . . . . . . . . . . . . . . . 5
U3830 . . . . . . . . . . . . . . . . . . . . . . . . 5
U3860 . . . . . . . . . . . . . . . . . . . . . . . . 5
U3822-20GR . . . . . . . . . . . . . . . . . . . 6
U3849-O-2/200 . . . . . . . . . . . . . . . . 22
U4329-O . . . . . . . . . . . . . . . . . . . . . 24
U4363-X-QG-CECHA . . . . . . . . . . . . 8
U4881-O . . . . . . . . . . . . . . . . . . . . . . 6
U4881-O-50GB . . . . . . . . . . . . . . . . . 6
U4881-O-60GB . . . . . . . . . . . . . . . . . 6
U5168-XTL-100-KK-CECHA . . . . . . 11
U5168-XTL-150-KK-CECHA . . . . . . 11
U5168-XTL-200-KK-CECHA . . . . . . 11
U5706-O-200S-CECHA . . . . . . . 20-21
U5750-RXL-200-BL-CECHA . . . . . . 10
U5842-RL-KK . . . . . . . . . . . . . . . . . . 10
U7375-RL-KK . . . . . . . . . . . . . . . . . . . 9
U7607-RL-200-KK . . . . . . . . . . . . . . . 9
U8303-O . . . . . . . . . . . . . . . . . . . . . 18
U8436-O . . . . . . . . . . . . . . . . . . . . . 18
U8606-RXL . . . . . . . . . . . . . . . . . . . . 8
U8624-RXL . . . . . . . . . . . . . . . . . . . . 8
U8949-RL-TG-KK . . . . . . . . . . . . . . . 7
U9107-O . . . . . . . . . . . . . . . . . . . . . 23
U9108-O . . . . . . . . . . . . . . . . . . . . . 23
UQFB-100 . . . . . . . . . . . . . . . . . . . . 29
UQFB-100-X1 . . . . . . . . . . . . . . . . . 29
UQFB-125 . . . . . . . . . . . . . . . . . . . . 29
UQFB-125-X1 . . . . . . . . . . . . . . . . . 29
UQFB-150 . . . . . . . . . . . . . . . . . . . . 29
UQFB-150-X1 . . . . . . . . . . . . . . . . . 29
UQFB-175 . . . . . . . . . . . . . . . . . . . . 29
UQFB-175-X1 . . . . . . . . . . . . . . . . . 29
UQFB-200 . . . . . . . . . . . . . . . . . . . . 29
UQFB-200-X1 . . . . . . . . . . . . . . . . . 29
UQFBH-100 . . . . . . . . . . . . . . . . . . . 29
UQFBH-125 . . . . . . . . . . . . . . . . . . . 29
UQFBH-150 . . . . . . . . . . . . . . . . . . . 29
UQFBH-175 . . . . . . . . . . . . . . . . . . . 29
UQFBH-200 . . . . . . . . . . . . . . . . . . . 29
UQFP-100 . . . . . . . . . . . . . . . . . . . . 29
UQFP-125 . . . . . . . . . . . . . . . . . . . . 29
UQFP-150 . . . . . . . . . . . . . . . . . . . . 29
UQFP-175 . . . . . . . . . . . . . . . . . . . . 29
UQFP-200 . . . . . . . . . . . . . . . . . . . . 29
UQFPH-100 . . . . . . . . . . . . . . . . . . . 29
UQFPH-125 . . . . . . . . . . . . . . . . . . . 29
UQFPH-150 . . . . . . . . . . . . . . . . . . . 29
UQFPH-175 . . . . . . . . . . . . . . . . . . . 29
UQFPH-200 . . . . . . . . . . . . . . . . . . . 29
UQFPH-M-100 . . . . . . . . . . . . . . . . . 29
UQFPH-M-125 . . . . . . . . . . . . . . . . . 29
UQFPH-M-150 . . . . . . . . . . . . . . . . . 29
UQFPH-M-175 . . . . . . . . . . . . . . . . . 29
UQFPH-M-200 . . . . . . . . . . . . . . . . . 29
UQFP-M-100 . . . . . . . . . . . . . . . . . . 29
UQFP-M-125 . . . . . . . . . . . . . . . . . . 29
UQFP-M-150 . . . . . . . . . . . . . . . . . . 29
UQFP-M-175 . . . . . . . . . . . . . . . . . . 29
UQFP-M-200 . . . . . . . . . . . . . . . . . . 29
Z917525-AC . . . . . . . . . . . . . . . . . . . 29
Z917526-AC . . . . . . . . . . . . . . . . . . . 29
CATALOG NO. PG NO. CATALOG NO. PG NO. CATALOG NO. PG NO.
35N
OTES
NOTES
35
Meter Mounting Equipment & More!Commercial Electrical Enclosures
Residential & Commercial Metering
Commercial Meter Pedestals
Disconnect Devices
Current Transformer Enclosures
RV/MH Pedestals
Temporary Power Outlets
Circuit Breakers
Distribution Unit Substations
Enclosed Circuit Breakers
Safety Switches
Test Switches
REPRESENTATIVECallas/Kingsley845 Lively BoulevardWood Dale, IL 60191Tel: 630-595-7887 Fax: 630-595-6922www.ckelectricalsales.com
ComEd 3/09 (1K)
www.milbankmfg.com
MILBANK MFG. CO.PO Box 419028Kansas City, MO 64141-0028Tel: 816-483-5314 Fax: 816-483-6357Toll Free: 877-483-5314www.milbankmfg.com