Medium Voltage Switchgear and Switches
Medium Voltage Switches up to 24 kVVacuum Circuit Breaker
Type: NVL
CA⋅508⋅GB⋅0710
2
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLIndex
Index
Page
Main features 3
Requirements 4Application examples 4Economic efficiency 4Reliability of supply 4High operator safety 4
Switchgear unit arrangement 5
Key to type references 6
Technical data/standards 7
Overview of modules 8
Delivery programme of vacuum circuit breakers 10
Vacuum circuit breaker equipment 11
Circuit diagram 12
Control and indicator elements 14
Notes 15
CA_508_GB_0710.book Seite 2 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLMain features
CA⋅508⋅GB⋅0710
3
Main features
Type NVL vacuum circuit breakers are type-tested switchgear devices for use throughout the world in medium voltage panels up to 24 kV.
• Compact design
• Simple and robust drive
• Long durability
• Low-maintenance
• High reliability
• High operator safety
• 10.000 mechanical switching operations
• Simple installation
• Ideally designed insulation for panel installation
• Options for customer-specific equipment
CA_508_GB_0710.book Seite 3 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLRequirements
CA⋅508⋅GB⋅0710
4
Application examples
NVL vacuum circuit breaker is suitable for use in switching stations for power generation and power distribution for:
• Utility companies• Combined heat and power stations• Power distribution at buildings• Steel industry• Heavy industry• Airport power distribution systems• Automotive industry• Chemical industry• Petro-chemical industry• Food industry• Main distribution substations• Shipbuilding• Stand-by generating supplies
Economic efficiency
The flexibility of the standardised NVL vacuum circuit breaker with its options for configuration to customer requirements allows it to be functionally matched to its application. The circuit-breaker can be extended or modified at a later date after installation.
Reliability of supply
The high quality of vacuum circuit breaker with separate compartments for busbars, switchgear and cable connections ensures a high degree of reliability in operation and supply for the application. Thus the devices can be equipped, for instance, with an auto-reclosure in order to restore availability as quickly as possible after a fault in the mains power supply.
High operator safety
The simple and clear arrangement of the operating and indicator elements and optional locking elements, e.g. key locks for actuating keys or electromechanical actuation locks, guide the user to actuate safely.
CA_508_GB_0710.book Seite 4 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLSwitch arrangement
CA⋅508⋅GB⋅0710
5
Switch arrangement
The NVL vacuum circuit breaker consists of the basic switch frame, the three switch poles and the switch mechanism. The baseframe must be earthed via a defined fixed earthing point.
The switch poles include the vacuum switching chamber with contact system, the contact pressure springs, the tripping springs, as well as cast-resin parts. The cast-resin parts are for insulation, support and protection. In addition to their insulating function, they also absorb external forces from the switching process, contacting and short-circuit forces. They also provide mechanical protection for the vacuum chamber.
A stored energy spring mechanism is used as an operating mechanism. The closing spring is charged using a crank handle or a motor drive. During the making process, the closing spring charges the contact pressure spring and closes the contacts. At the same time, the tripping springs are charged. To achieve operational capability short-time interruption, after the closing spring has been discharged it is recharged either manually or automatically if a motorised drive is mounted. By this means the necessary energy is stored for a short-time interruption, such as the switching sequence "OFF"-"ON"-"OFF".
CA_508_GB_0710.book Seite 5 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLKey to type references
CA⋅508⋅GB⋅0710
6
Key to type references NVL vacuum circuit breaker
The NVL circuit breaker can be equipped with a wide variety of standardised customer options. The types of device are differentiated in their widths, ratings and principal functions.
Example : NVL2A-12/25/1250-150A
Type of equipment:: VL = Vacuum circuit breaker
Type of insulating enclosure: 2, 3
Rated voltage: 12 = 12 kV17 = 17.5 kV24 = 24 kV
Rated short-circuit breaking current
16 = 16 kA20 = 20 kA25 = 25 kA31 = 31.5 kA
Rated current: 630 A1250 A1600 A2000 A2500 A
Distance between polecentres:
150 mm210 mm230 mm275 mm
N. . . . .A-. . . ./. . . . /. . . . -. . . .-A
CA_508_GB_0710.book Seite 6 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLTechnical data/standards
CA⋅508⋅GB⋅0710
7
Technical data for NVL vacuum circuit breaker
Standards
* in future** so far
Rated voltage Ur [kV]
12 17,5 24
Rated frequency fr Hz 50 50 50
Rated lightning impulse withstand voltage Up kV 75 95 125
Rated power-frequency withstand voltage Ud kV 28 38 50
Rated normal current Ir Optional A 630 630 630
A 1250 1250 1250
A 1600 1600
A 2000 2000
A 2500 2500
Rated short-circuit breaking current Isc Optional kA 16
kA 20 20 20
kA 25 25 25
kA 31.5 31.5
Rated peak withstand current Ip Optional kA 40
kA 50 50 50
kA 62.5 62.5 62.5
kA 80 80
Rated short-time withstand current Ikat tk = 3 s
Optional kA 16
kA 20 20 20
kA 25 25 25
kA 31.5 31.5
Ambient temperature T °C -5 to +40
Average measured over 24 h maximum °C +35
Relative humidity
Average measured over 24 h maximum % 95
Average measured over 1 month maximum % 90
Altitude maximum m 1000
Opening time ms <55
Closing time ms <45
Arcing time ms approx. 15
Rated operating sequence (for automatic reclosing) O-0.3s-CO-15s-CO
Classification M2, C2, E1
VDE 0671 part 100 IEC 62271-100
VDE 0670 part 1000 (VDE 0671 part 1*) IEC 62271-1 (IEC 60694**)
NVL vacuum circuit breaker satisfy the listed VDE standards andIEC publications:
CA_508_GB_0710.book Seite 7 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLOverview of modules
CA⋅508⋅GB⋅0710
8/9
X1 Terminal strip X0: Plug-in connector , 64-pole
K1 Anti-pumping relay
Y7 Electric closing lock-out
Stored energy spring mechanism manual winding
Q1 Auxiliary contacts/signalling switch, 10 or 20-pole M1 Stored energy spring mechanism motor Closing spring
Earthing terminal
Y6 3. Trip element OFF
S19 Signalling switch 1S,mech. push-button ON activated
S4 wipe contact, signal OFF
Y3/Y4/Y5 2. Trip element OFF
Y1 Trip element ON
Y2/Y5 1. Trip element OFF
Transport mount
S1/S2 Signalling/control switch (stored energy spring mechanism)
CA_508_GB_0710.book Seite 8 Freitag, 1. Februar 2008 8:27 08
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLOverview of modules
CA⋅508⋅GB⋅0710
8/9
X1 Terminal strip X0: Plug-in connector , 64-pole
K1 Anti-pumping relay
Y7 Electric closing lock-out
Stored energy spring mechanism manual winding
Q1 Auxiliary contacts/signalling switch, 10 or 20-pole M1 Stored energy spring mechanism motor Closing spring
Earthing terminal
Y6 3. Trip element OFF
S19 Signalling switch 1S,mech. push-button ON activated
S4 wipe contact, signal OFF
Y3/Y4/Y5 2. Trip element OFF
Y1 Trip element ON
Y2/Y5 1. Trip element OFF
Transport mount
S1/S2 Signalling/control switch (stored energy spring mechanism)
CA_508_GB_0710.book Seite 8 Freitag, 1. Februar 2008 8:27 08
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLDelivery programme
CA⋅508⋅GB⋅0710
10
Delivery programme
Rated voltage Ur: 12 kVSwitch types:1)
NVL2A-12/20/630-150ANVL2A-12/25/630-150ANVL2A-12/31/630-150ANVL2A-12/20/1250-150ANVL2A-12/25/1250-150ANVL2A-12/31/1250-150ANVL2A-12/20/630-210ANVL2A-12/25/630-210ANVL2A-12/31/630-210ANVL2A-12/20/1250-210ANVL2A-12/25/1250-210ANVL2A-12/31/1250-210ANVL3A-12/20/1600-210ANVL3A-12/25/1600-210ANVL3A-12/31/1600-210ANVL3A-12/20/2000-210ANVL3A-12/25/2000-210ANVL3A-12/31/2000-210ANVL3A-12/20/2500-210ANVL3A-12/25/2500-210ANVL3A-12/31/2500-210A1) Key to type references → page 6.
Rated voltage Ur: 17.5 kVSwitch types:1)
NVL2A-17/20/630-150A 3)
NVL2A-17/25/630-150A 3)
NVL2A-17/31/630-150A 3)
NVL2A-17/20/1250-150A 3)
NVL2A-17/25/1250-150A 3)
NVL2A-17/31/1250-150A 3)
NVL2A-17/20/630-210ANVL2A-17/25/630-210ANVL2A-17/31/630-210A NVL2A-17/20/1250-210A NVL2A-17/25/1250-210A NVL2A-17/31/1250-210ANVL3A-17/20/1600-210A 3)
NVL3A-17/25/1600-210A 3)
NVL3A-17/31/1600-210A 3)
NVL3A-17/20/2000-210A 3)
NVL3A-17/25/2000-210A 3)
NVL3A-17/31/2000-210A 3)
NVL3A-17/20/2500-210A 3)
NVL3A-17/25/2500-210A 3)
NVL3A-17/31/2500-210A 3)
Rated voltage Ur: 24 kVSwitch types:1)
NVL2A-24/16/630-210A 3)
NVL2A-24/20/630-210A 3)
NVL2A-24/25/630-210A 3)
NVL2A-24/16/630-230A 3)
NVL2A-24/20/630-230A 3) 4)
NVL2A-24/25/630-230A 3) 4)
NVL2A-24/16/1250-230A 3)
NVL2A-24/20/1250-230A 3) 4)
NVL2A-24/25/1250-230A 3) 4)
NVL2A-24/16/630-275ANVL2A-24/20/630-275ANVL2A-24/25/630-275ANVL2A-24/16/1250-275ANVL2A-24/20/1250-275ANVL2A-24/25/1250-275A
Technical data and dimensions2):
Rated voltage Ur [kV]
12 17.5 24
Distance between pole centres a mm 150 210 210 1503) 210 2103) 2103) 2303) 275
Rated normal current Ir A 630 630 1600 630 630 1600 630 630 630
1250 1250 2000 1250 1250 2000 1250 1250
2500 2500
Type of insulating enclosure 2 2 3 2 2 3 2 2 2
Dimensions mm
b 435 555 555 435 555 555 555 595 685
c 370 370 390 370 370 390 431 431 431
d 594 594 594 594 594 594 594 594 594
e 255 255 300 255 255 300 255 255 255
f 198 198 153 198 198 153 198 198 198
g 66 66 66 66 66 66 66 66 66
h 402 402 402 402 402 402 402 402 4022) Additional technical data → page 7.3) possible additional insulation plates (phase insulation) required in the panel; not included in the scope of delivery4) In development. Date of delivery on request.
aa
b
106
h
fe
g
d
16
c
164
CA_508_GB_0710.book Seite 10 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLEquipment for vacuum circuit breaker
CA⋅508⋅GB⋅0710
11
Equipment for vacuum circuit breaker
Standard equipment:
Additional equipment:
Type: NVL....A-....../......./......... - ........AExample: NVL2A-12/25/1250-150A
charged spring drive with manual actuation
1. trip element "OFF"
auxiliary contacts 5 NO + 5 NC (up to 4 NO + 5 NC free available)
mechanical switching operation counter
mechanical push-buttons "ON" and "OFF"
mechanical position indicator
mechanical spring charge indicator
64-pin plug connector with mechanical interlocking
motorised accumulator drive incl. trip element "ON", annunciator switch for spring charging, anti-pumping relay
2. trip element "OFF"
3. trip element "OFF" with auxiliary contacts, extension 5 NO + 5 NC
transformer operated trip, alternative to 1. or 2. trip element
undervoltage release, 100 V AC (non-delayed) alternative to 2. trip element
auxiliary contact extension 5 NO + 5 NC
signalling switch spring accumulator tensioned
electric closing lock-out
fleeting contact switch message "OFF"
key interlocking for mechanical OFF-push-button
key interlocking for mechanical ON-push-button
signalling switch "mech. ON-push-button activated"
Auxiliary voltages for circuit-breaker 24 V DC 48 V DC 60 V DC 110 V DC 220 V DC 110 V AC 230 V AC
Motorised drive, stored energy spring mechanism
1. trip element "Off"
2. trip element "Off"
3. trip element "Off"
trip element "On"
electric closing lock-out
CA_508_GB_0710.book Seite 11 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLCircuit diagram
CA⋅508⋅GB⋅0710
12
2119
13
14
X0 A6
X0 A5
Y2
X1 9
X1 8
Q1
X1 7
18
53
54
Y3
X0 A8
X0 A7
17
16
33
63
64
Y6
X0 D2
X0 D1
32
31
20
Y4<U
V4
X0 C6
X0 C5
Y5I>
V5
X0 A9
X0 A10
X1 22
X1 X1
X1
Q1 Q1
X1 X1
X1 X1
Y7V7
X1 30
X0 C8
X1 29
X0 C7
2
X1
X0
S2
S1
M1
1
2
1
A2
X1 2
1
X0 A1
Y1 K1
A1
A2
11/13
1422
21
K1
23
24
11
12
X1
Q1
6
X0 A4
X1
X1 3
X0 A3
4
3
5
M~
S1
Circuit diagram
Description:
X0 Plug-in connector 64-poleX1 Terminal stripQ1 Auxiliary switchY2 1. trip element OFFY3 2. trip element OFFY4 Undervoltage release OFF (alternative to Y3)V4 Rectifier for Y4Y5 Transformer operated trip OFF (alternative to Y2 or Y3)V5 Rectifier for Y5Y6 3. trip element OFFY1 Trip element ONK1 Anti-pumping relayM1 Stored energy spring mechanism motorS1 Control switch (ON release and motor)S2 Signalling/control switch (spring accumulator tensioned)S4 Fleeting contact switch, message OFFS6 Fleeting contact break (in case of local actuation)S19 Signalling switch, mech. ON-push-button activatedS5 Control switch, interlocking of el. switching on (with drawer unit only)S7 Control switch, release interlocking of el. switching on (in conjunction
with Y7 only)Y7 Electric closing lock-outV7 Rectifier for Y7
Motor ONwith anti pumping relay
OFF (1) OFF (2) OFF (3) alternative trip elementOFF (2)
alternative trip elementOFF (2) if necessary (1)
electric closinglock-out
1. trip element 2. trip element 3. trip element Undervoltage release(non-delayed)
Transformeroperated trip
with control switch S7(integrated in
„ON"-release path)
CA_508_GB_0710.book Seite 12 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLCircuit diagram
CA⋅508⋅GB⋅0710
13
26
27 2
115
16
1
4
34
11
4
3
53
54
41
42
63
64
21
22
31
32 62
61
74
73
72
71
82
81 83 91 93 101 103
84 92 94 102 104
S4
S6S19
X0
C10
C2C4
S2
X0C11
C1C3
Q1
X0 B1B4
B7B9
X0B2
B3
B5
B6B10
B8
X0 C11
A11
A13 B11
B13
B15
C13
C15 D15
X0 C12
A12 A16 B14 C14
A14 B12 B16 C16 D16
51
52
A15
X1
X1
Messages
Sprin
g ac
cu-
mul
ator
tens
ione
d
ON-p
ush-
butto
n ac
tuat
ed
Flee
ting
cont
act
switc
h m
essa
ge
"OFF
"Auxiliary contactsAvailability optionalConsider the assembled trip elements
Sign
alPl
ug-in
con
nect
or
CA_508_GB_0710.book Seite 13 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLOperating and display elements
CA⋅508⋅GB⋅0710
14
Operating and display elements
The operating and display area is located on the front side of the vacuum circuit breaker.
All functional elements, e.g. the mechanical push-buttons for switching on and off, the indicator for the switch position and the stored energy spring mechanism are clearly arranged in order to ensure simple operation.
The operating push-buttons can be equipped with optional key interlocking devices.
Optional key interlocking devices for ON/OFF push-buttons
Switch position indicator
mechanical switching operation counter
Spring charge indicator
Operation opening for manual winding up of spring accumulator
Push-button ON
Push-button OFF
CA_508_GB_0710.book Seite 14 Freitag, 1. Februar 2008 11:31 11
Medium voltage switches up to 24 kV, Vacuum circuit breaker type NVLNotes
CA⋅508⋅GB⋅0710
15
Notes
CA_508_GB_0710_04.fm Seite 15 Freitag, 22. Februar 2008 2:33 14
SF6-insulated switchgear
Type GAType GAEType CPG.0Type CPG.1
Air-insulated switchgear
Type EAType AMC
Air-insulated switches Type NVLType KL(F), T, DES
Subject to alteration
CA 508 GB 0710