Mecanical Design

24
1 Asian Region Mechanical Design ILC Mechanical & Electrical Review Masanobu Miyahara /KEK Atsushi Enomoto /KEK Masahito Huse /Nikken Sekkei 2012/3/21

description

guide

Transcript of Mecanical Design

Page 1: Mecanical Design

1

Asian Region Mechanical Design

ILC Mechanical & Electrical Review

Masanobu Miyahara /KEK

Atsushi Enomoto /KEK

Masahito Huse /Nikken Sekkei

2012/3/21

Page 2: Mecanical Design

2

Content

① Cooling Water System

② HVAC System

③ Plumbing System

Summary

ILC Mechanical & Electrical Review2012/3/21

Page 3: Mecanical Design

3

Scheme Change Image

ILC Mechanical & Electrical Review

Asian Region Mechanical Design

Previous Schemeby DRFS

Latest Scheme

2012/3/21

Page 4: Mecanical Design

4

New Scheme Kamaboko Tunnel

ILC Mechanical & Electrical Review

Asian Region Mechanical Design

Cooling Warterpipe

Chw pipe

Fan Coil Unit

Groundwater Drainage Ditch

2012/3/21

Page 5: Mecanical Design

5

Cooling Water SystemHeat Load Summary

ILC Mechanical & Electrical Review

C ooling W ater Load (M W )

LC WAH1 PM C -0 PM B-0 PXB-0 AH8 Total

Source e- 2.88 2.88

Source e+ 5.53 5.53

DR 11.86 2.09 13.95

RTM L 2.93 0.33 0.33 2.93 6.51

M L 5.59 5.59 5.59 5.59 5.03 4.65 5.59 5.59 5.59 5.59 54.42

BDS 4.60 4.60 9.20

Dum ps 39.95 39.95

IR(DH) 0.20 0.20

subTotal 0 8.52 5.59 5.59 5.59 5.03 10.46 11.86 2.09 40.15 7.81 4.65 5.59 5.59 5.59 8.52 0.00 132.64

C ryogenics 0 2.52 1.73 0.00 49.65

Total 0 14.38 2.09 41.88 0.00182.29

Air+C hwAH1 PM C -0 PM B-0 PXB-0 AH8 Total

Source e- 1.42 1.42

Source e+ 0.72 0.72

DR 0.74 0.13 0.87

RTM L 0.95 0.11 0.11 0.95 2.10

M L 1.20 1.20 1.20 1.20 1.08 1.00 1.20 1.20 1.20 1.20 11.69

BDS 0.62 0.62 1.23

Dum ps 0.00 0.00

IR(DH) 0.38 0.38

subTotal 0 2.15 1.20 1.20 1.20 1.08 1.44 0.74 0.13 0.38 2.14 1.00 1.20 1.20 1.20 2.15 0.00

Total 0 0.74 0.13 0.38 0.0018.41

200.7

2.40 3.353.35 2.40 2.52 3.14

AH6 AH7

21.48 18.55

AH2 AH3 AH4 AH5

23.45 20.42

AH6 AH7

7.37 7.37

18.55 21.48

7.37 7.37 7.96 7.96

AH2 AH3 AH4 AH5

Cooling Water Load

Total 200MW

Air + CHw Load

2012/3/21

Page 6: Mecanical Design

6

Cooling Water System3 Types of Cooling Tower

A: Closed-circuit Type (Air-cooled)

B: Closed-circuit Type (Water cooled)

C: Open Type (Water cooled)

ILC Mechanical & Electrical Review

- IN RDR, we adopted Air-cooled type Cooling tower- Makeup water Issue in Mountainous area

2012/3/21

Page 7: Mecanical Design

7

Cooling Water System3 Types of Cooling Tower

Makeup water for 200MW cooling

- WE (Evaporation)=288m3/h

- WC (Carry over) =47m3/h

- WB (Blow down) =241m3/h

Reservation of Makeup water

Groundwater

=1m3/km/min*30km*60min/h

=1,800m3/h

Total

=WE+WC+WB

=576m3/h

ILC Mechanical & Electrical Review2012/3/21

Page 8: Mecanical Design

8

Cooling Water SystemComparison of Cooling Tower Type

A B C

TYPE C losed-circuit Air-cooled Type C losed-circuit C ooling Tow er O pen Type C ooling Tow er

UNIT SIZE

(6M W UNIT)

59m ×10m 22m ×4m 12m ×4m

SPAC E

(for 200M W )

14,160m 2 5,870m 2 3,200m 2

NO ISE

(6M W UNIT)

95dB(A) 80dB(A) 75dB(A)

UNIT C O ST

(for 200M W )

9,330M \ 1,810M \ 370M \

ILC Mechanical & Electrical Review

RDR Scheme TDR Scheme2012/3/21

Page 9: Mecanical Design

9

Cooling Water System2-Loop & 3-Loop System

2 -L O O P S Y S T E M 3 -L O O P S Y S T E M

RF RF RF

RF RF RF RF

RF RF

C T C T

H E X H E X

H E X

1st Loop

To separate the 100m=1MPa water pressure to the 2nd Loop

2nd Loop

D.I. Water Stainless steel Piping

3rd Loop

D.I. Water Stainless steel Piping

2nd Loop

Galvanized steel Piping

ILC Mechanical & Electrical Review

2-Loop System 3-Loop System

2012/3/21

Page 10: Mecanical Design

10

Cooling Water SystemComparison of 2-Loop and 3-Loop

2-Loop System 3-Loop System

Cost

(AH-3)

3,423M\ 2,943M\

Water leakage If there would be some troubleat the thin pipe around accelerator, 5km(total 650m3) de ionized cooling water would be run over.

Evaluation △ ○

ILC Mechanical & Electrical Review2012/3/21

Page 11: Mecanical Design

11

Cooling Water System3-Loop LCW System (AH-3)

From ground level to access hall

L≒1000m

⊿⊿⊿⊿H≒≒≒≒100m

De-ionize filter

De-aerator

Stand-by (back-up)

ILC Mechanical & Electrical Review2012/3/21

Page 12: Mecanical Design

12

Cooling Water System3-Loop Chw System

ILC Mechanical & Electrical Review

Turbo Refrigerator2+1(standby)

2nd-Loop

3rd-Loop

In case of AH-3(5km)

2012/3/21

Page 13: Mecanical Design

13

COP (Coefficiency Of Performance) the rating point =7.0

Cooling Water SystemInverter turbo refrigerator

COP at the midterm =up to 20.0

ILC Mechanical & Electrical Review2012/3/21

Page 14: Mecanical Design

14

HVAC SystemTunnel Ventilation System in RDR

It’s difficult to make Chevron

We need to change the scheme

ILC Mechanical & Electrical Review2012/3/21

Page 15: Mecanical Design

15

HVAC SystemTunnel Ventilation System

D≒2m

ILC Mechanical & Electrical Review

Exhaust Fan Air Handling Unit

Sloped tunnelAbout 1,000m

2012/3/21

Page 16: Mecanical Design

16

HVAC SystemTunnel Ventilation System

Outside air

Heated or Cooled by Air-handling Unit

ExhaustExhaust Fan Air Handling Unit

2012/3/21ILC Mechanical & Electrical

Review

Page 17: Mecanical Design

17

HVAC SystemTunnel Ventilation System

Smoke exhaust

Quench exhaust

Exhaust Fan Air Handling Unit

Fire !!

Helium Quench !!

2012/3/21ILC Mechanical & Electrical

Review

Page 18: Mecanical Design

18

HVAC SystemTunnel Ventilation Rate

0.5m/s×16m2×3600

=28,800m3/h

28,800m3/h÷(16m2×5000m)

=0.36N/h

0.5m/s×12m2×3600

=21,600m3/h

Beam Tunnel

High velocity (>1.0m/s) cause vibration !

ILC Mechanical & Electrical Review

Velocity < 0.5 m/s

Service Tunnel

2012/3/21

Page 19: Mecanical Design

19

HVAC SystemTypical Tunnel Section Plan

400

1098

4402

5500 60

00

Mesh grounding

LCW PIPE

3300 3500

1500

4200

11000

11600

12000

Maintenance space

Chw PIPE

Fan Coil Unit

3rd Loop Cooling Water Skid

2012/3/21ILC Mechanical & Electrical

Review

Page 20: Mecanical Design

20

Plumbing SystemDrainage System

ILC Mechanical & Electrical Review

Cooling water leakage : to the DP tank for RI monitoring

Ground water : Amount of Springwater1t/km.Min. →30t/min.

43,000t/day

2012/3/21

Page 21: Mecanical Design

21

Plumbing SystemWater Supply and Drainage System

Drainage System

Ground water is running through the ditch

Leaked cooling water is pumped up to access hall

ILC Mechanical & Electrical Review2012/3/21

Page 22: Mecanical Design

22

Plumbing SystemWater Supply and Drainage System

Water Supply System

Source of potable water is city water

Source of Makeup water is ground water

ILC Mechanical & Electrical Review2012/3/21

Page 23: Mecanical Design

23

Cooling Water System

- Use the open type Cooling Tower System

- Use 3-Loop System (⊿t=11℃)

- Inverter Turbo Refrigerator is used to make CHW

HVAC System

- Air Ventilation is through the Duct in Access tunnel

- Ventilation in ML tunnel is “Duct-less”, 0.5m/s Velocity

- Fire Smoke is extracted to the surface through AH,AT.

Summary (1)

ILC Mechanical & Electrical Review

Asian Region Mechanical Design

2012/3/21

Page 24: Mecanical Design

24

Plumbing System (water supply)

- City water is used for the potable water.

- Groundwater is used for the makeup water of CT.

Drainage System

- Groundwater is flow down to the Access Hall through

the Drainage ditch under the Service Tunnel.

- Leaked Cooling Water to the DP tank for RI Monitoring

We need more detailed study by the time next meeting in Korea

Summary (2)

ILC Mechanical & Electrical Review

Asian Region Mechanical Design

2012/3/21