MDACC Project# 12-0545 - C-AIR-S PRESSURE SHUT OFF SWITCH AFMS NEW WORK EXISTING WORK FIRE/FIRE...

7
Copyright © 2017 Perkins+Will MDACC Project# 12-0545.1 4/18/2017 6:31:45 PM c:\temp\185108.000_CRB Vivarium Renovation_activation package_rf_fernandez.rvt ISSUED FOR BIDDING AND CONSTRUCTION April 18, 2017 CRB ANIMAL AREA RENOVATION - ACTIVATION PACKAGE 1515 Holcombe Blvd. Houston, TX 77030 UNIVERSITY OF TEXAS MD ANDERSON CANCER CENTER Architect Perkins + Will 1001 McKinney, Ste1300 Houston, TX 77022 P: 713.366.4000 F: 713.528.3339 MEP Engineer Shah Smith & Associates 2825 Wilcrest, Suite 350 Houston, TX 77042 P: 713.780.7563 F: 713.780.9209 MDACC PROJECT NO. 12-0545.1 INDEX OF DRAWINGS - ACTIVATION PACKAGE SHEET NUMBER SHEET NAME ACTIVATION PACKAGE - ISSUED FOR BIDDING AND CONSTRUCTION 04-Architectural - ACTIVATION PACKAGE 000 COVER SHEET A04-01 FLOOR PLANS - BASEMENT LEVEL AREA A, BA & CA A00-50 DOOR SCHEDULE AND DETAILS 07-Mechanical M11-01 MECHANICAL LEGENDS, GENERAL NOTES AND SCHEDULES M11-02 ENLARGED BASEMENT LEVEL AREA A-C M11-03 ENLARGED BASEMENT LEVEL PIPING AREA A-C M11-04 MECHANICAL CONTROLS M11-05 MECHANICAL DETAILS 10-Electrical E00-03 ELECTRICAL LEGEND SYMBOLS AND ABBREVIATIONS E03-15 POWER PLAN - BASEMENT LEVEL B-A E07-07 PANEL SCHEDULES

Transcript of MDACC Project# 12-0545 - C-AIR-S PRESSURE SHUT OFF SWITCH AFMS NEW WORK EXISTING WORK FIRE/FIRE...

Page 1: MDACC Project# 12-0545 - C-AIR-S PRESSURE SHUT OFF SWITCH AFMS NEW WORK EXISTING WORK FIRE/FIRE SMOKE DAMPER RETURN AIR DUCT SUPPLY/OUTSIDE AIR DUCT EXHAUST/RELIEF AIR DUCT ACCESS

Copyright © 2017 Perkins+Will

MDACC Project# 12-0545.1

4/1

8/2

017 6

:31

:45 P

M

c:\te

mp\ 1

8510

8.0

00_

CR

B V

ivarium

Reno

va

tion_

activation

package_rf

_fe

rnandez.r

vt

ISSUED FOR BIDDING ANDCONSTRUCTION

April 18, 2017

CRB ANIMAL AREA RENOVATION -ACTIVATION PACKAGE

1515 Holcombe Blvd.Houston, TX 77030

UNIVERSITY OF TEXAS MD ANDERSON CANCER CENTER

ArchitectPerkins + Will1001 McKinney, Ste1300Houston, TX 77022P: 713.366.4000F: 713.528.3339

MEP EngineerShah Smith & Associates2825 Wilcrest, Suite 350Houston, TX 77042P: 713.780.7563F: 713.780.9209

MDACC PROJECT NO. 12-0545.1

INDEX OF DRAWINGS - ACTIVATION PACKAGE

SHEETNUMBER SHEET NAME

ACTIVATION PACKAGE - ISSUED FORBIDDING AND CONSTRUCTION

04-Architectural - ACTIVATION PACKAGE

000 COVER SHEET ●

A04-01 FLOOR PLANS - BASEMENT LEVEL AREA A, BA & CA ●

A00-50 DOOR SCHEDULE AND DETAILS ●

07-Mechanical

M11-01 MECHANICAL LEGENDS, GENERAL NOTES AND SCHEDULES ●

M11-02 ENLARGED BASEMENT LEVEL AREA A-C ●

M11-03 ENLARGED BASEMENT LEVEL PIPING AREA A-C ●

M11-04 MECHANICAL CONTROLS ●

M11-05 MECHANICAL DETAILS ●

10-Electrical

E00-03 ELECTRICAL LEGEND SYMBOLS AND ABBREVIATIONS ●

E03-15 POWER PLAN - BASEMENT LEVEL B-A ●

E07-07 PANEL SCHEDULES ●

Page 2: MDACC Project# 12-0545 - C-AIR-S PRESSURE SHUT OFF SWITCH AFMS NEW WORK EXISTING WORK FIRE/FIRE SMOKE DAMPER RETURN AIR DUCT SUPPLY/OUTSIDE AIR DUCT EXHAUST/RELIEF AIR DUCT ACCESS

48"

48"

1 2

A

B

C

D

F

4 5 6 7

8 9 10 11

PROCEDURETB.3917A

PROC./HOLDINGTB.3911

PROC./HOLDINGTB.3907

STORAGETB.3885

CHANGINGROOMTB.3887

JANITORTB.3904

PROC./HOLD.TB.3906

ANIMALHOLDINGTB.3876

ANIMALHOLDINGTB.4271

I.P.CLINICTB.4262

O.R.PREPTB.4258

O.R.PREPTB.4250

PRO./HOLD.TB.3933

PROCEDURE/HOLDINGTB.3935

PROCEDURE/HOLDINGTB.3947

PROCEDURE/HOLDINGTB.3934

PROCEDURE/HOLDINGTB.3938

PROCEDURE/HOLDINGTB.3942

PROCEDURE/HOLDINGTB.4024

ANIMALHOLDING/BEHAVIORAL

TB.3927A

PROC./HOLDINGTB.3893

CLINICAL RESEARCHBUILDING

F.4

E.8

B.4

5.8

CHANGINGROOMTB.3874

QUARANTINETB.3891

3900

3891

3876

3942

4024

PROCEDURETB.3876A

3929

PROCEDURE/HOLDINGTB.4020

PROCEDURETB.4271A

PROC./HOLD.TB.3922

3938

3922

3933

4020 4271

3946

3947

3907 3893

4271A

CORRIDORTB.3929

CORRIDORTB.4228

CORRIDORTB.3846

CORRIDORSB.8470

CORRIDORTB.3953

CORRIDORTB.3900

3935

3939

39113919

PROC./HOLD.TB.3908

VESTIBULETB.3927

PROC./BEHAVIORAL

TB.3927B

3934

3953A

TB.3915

TB.3930

TB.3918 TB.3914TB.4025A

TB.4025

TB.3951 TB.4008

TB.4012

TB.4016

TB.4013

TB.4009 TB.4037 TB.4041 TB.4045A TB.4049 TB.4055D TB.4055E TB.4055C TB.4059A

TB.4246 TB.4242

TB.4255 TB.4247 TB.4241

TB.3872 TB.3868 TB.3868A TB.3860A TB.3860 TB.3856

TB.3863

TB.3857A

TB.3857

TB.3853

TB.3851

TB.3954

ANIMALHOLDINGTB.3919

PROCEDURETB.3919A

ANIMALHOLDINGTB.3917

3927A

3927B

3917

JANITORTB.3926

PROCEDURE/HOLDINGTB.3946

PROCEDURE/HOLDINGTB.3939

3908

WRITE-UPSTATIONTB.3902

TB.3950

CORRIDORTB.4101

3923

CR

WP

TB.3985 TB.3989

TB.3955

TB.3959

TB.3982 TB.3986 TB.3990 TB.4030

TB.4001

TB.4005

1

1

111 1

1

1

1

1

1

1

2

A00-50

1

A00-50

5

WP

WP

3

4

4

4

4

4

4

4

4

4

4

4

4

4 4 4

1

FLOOR PLAN KEYNOTED NOTES FLOOR PLAN LEGEND

EXISTING PARTITION

NOT IN SCOPE

DOOR TAG, RE:A00-5038

10EXISTING CMU PARTITION

EXISTING CONCRETEPARTITION

WP

CR EXISTING CARD READER

WAVE PLATE

1 REMOVE/COVER THE NOW OBSOLETE ROOM STAT REPORTING PANELS. INSTALL METAL CUSTOMBLANK-OFF IN CMU WALLS. PAINT COLOR IS TO MATCH EXISTING PANEL COLOR.

2DEMO EXISTING 90 MIN RATED FLUSH DOORS. DOOR FRAME IS TO REMAIN IN PLACE FOR NEWDOORS. A NEW PAIR OF 90 MIN RATED DOORS THAT INCLUDE DOOR LITES WILL REPLACE THE OLDDOORS. REUSE EXISTING DOOR HARWARE. DOORS ARE TO BE PAINTED TO MATCH EXISTING DOORPAINT COLOR.

3 CHANGE EXISTING CARD READER TO A WAVE PLATE. RE: HARDWARE GROUP NO. 04

WP EXISTING WAVE PLATE

EXISTING ROOM STATREPORTING PANELS4 PLUMBING CONNECTIONS OF THE CASEWORK MOBILE SINKS TO THE UTILITY WALL BOXES NEED TO BE

EXECUTED.

C

14

MICROSURGERYTRAININGTB.4233

4

CORRIDORSB.8470

AIRLOCKSB.8460A

AUTOCLAVEROOMSB.8468

4

KEY PLAN

A B

C D

A-A A-B B-A

A-C A-D

C-A

01/2"

1"2"

Sheet

Title

Approved

Checked

Drawn

Job Number

Date

Sheet Information

Copyright © 2017 Perkins+Will

Revisions

MEP Engineer

Shah Smith & Associates

2825 Wilcrest, Suite 350Houston, TX 77042

t 713.780.7563

f 713.780.9209

15 234

A

D

B

C

15 234

A

D

B

C

MDACC Project# 12-0545.1

4/1

8/2

017 3

:19

:27 P

M

c:\te

mp\ 1

8510

8.0

00_

CR

B V

ivarium

Reno

va

tion_

activation

package_rf

_fe

rnandez.r

vt

A04-01

FLOOR PLANS -BASEMENT LEVELAREA A, BA & CA

DR

RF

185108.000

April 18, 2017

DR

CRB ANIMAL AREARENOVATION -

ACTIVATIONPACKAGE

1515 Holcombe Blvd.Houston, TX 77030

UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER

ISS

UE

D F

OR

BID

DIN

G A

ND

CO

NS

TR

UC

TIO

N A

pri

l 18, 2017

1001 McKinneySuite 1300

Houston, TX 77002t 713.366.4000f 713.528.3339

www.perkinswill.com

1/8" = 1'-0"1 FLOOR PLAN - CRB BASEMENT LEVEL -A

NORTHTRUE NORTH

3/16" = 1'-0"2 MICROSURGERY ROOM - AREA BA

3/16" = 1'-0"3 AUTOCLAVE - AREA CA

NO ISSUE DATE

Page 3: MDACC Project# 12-0545 - C-AIR-S PRESSURE SHUT OFF SWITCH AFMS NEW WORK EXISTING WORK FIRE/FIRE SMOKE DAMPER RETURN AIR DUCT SUPPLY/OUTSIDE AIR DUCT EXHAUST/RELIEF AIR DUCT ACCESS

LAB-TRAC AIR TERMINAL CONTROL MODES

MARK

GE-BR-B-22

SD-BR-B-22

LAB-TRAC SCHEDULE GENERAL NOTES (APPLY TO ALL ROOMS/EQUIPMENT):

A.

B.

C.

D.

E.

F.

G.

H.

ROOM

SERVED

LARGE ANIMAL HOLDING TB.3950

POSITIVE (+) OFFSET INDICATES FLOW LEAVING LAB/AREA. REFER TO AIR BALANCE DIAGRAM FOR ADDITIONAL INFORMATION.

ALL TERMINALS SHALL BE PROVIDED WITH VAV CONTROL CAPABILITY DESPITE THE CONTROL MODES REQUIRED AS PART OF THIS PROJECT.

ROOM OFFSET APPLIES TO NORMAL OPERATING MODES ONLY.

"-" INDICATES MODE DOES NOT AFFECT ZONE/VALVES. "*" INDICATES FAIL TO LAST POSITION

"MODE 1" AND "MODE 2" ARE CONTROL MODES FOR PHEONIX. MATCH CONTROL MODES TO EXISTING VIVARIUM CONTROL SCHEME.

"SHED 1" SHALL BE WHEN VIVARIUM IS ON STANDBY POWER. THIS SHALL BE THE SAME AS NORMAL OPERATING MODE.

"LOSS OF POWER" SHALL BE LOSS OF ALL POWER (NORMAL AND STANDBY). ALL VALVES SHALL FAIL TO LAST POSITION.

CONTRACTOR SHALL TAB THE PROJECT AT THE NORMAL "MODE 1" SETTING. ADJUST DIFFUSER CFM AS REQUIRED. THIMBLE CONNECTIONS SHALL REMAIN AS SHOWN.

ROOM

CFM

OFFSET

100

ANIMAL HOLDING AND PROCEDURE ROOMS

15 ACH

POSITIVE

15 ACH

NEGATIVE

790

690

10 ACH

POSITIVE

10 ACH

NEGATIVE

525

425

UNOCCUPIED ("MODE 2")

4 ACH

POSITIVE

110

210

OTHER: CONSTANT

CFM

-

-

NORMAL ("MODE 1")

790

690

SHED 1

CFM

790

690

LOSS OF POWER

CFM

*

*

REMARKS

GE

NE

RA

L N

OT

ES

THESE GENERAL NOTES APPLY TO ALL MECHANICAL DRAWINGS.

IN ANY CASE WHERE A PIPE OR DUCT SHOWN ON A PLAN SHEETDIFFERS FROM THAT SHOWN IN A SCHEMATIC OR DETAIL. USETHE LARGER OF THE TWO SIZES SHOWN.

PIPING SHOWN ON EACH PLAN IS RUN ABOVE THE CEILING ONTHE FLOOR WHERE IT IS SHOWN UNLESS OTHERWISE NOTED.

ALL ELEVATIONS INDICATED IN THIS WAY (8'-0") ARE THEELEVATIONS FROM THE FINISHED FLOOR DIRECTLY BELOW TO THEBOTTOM OF THE BARE PIPE OR DUCT.

MOUNT TEMPERATURE AND HUMIDITY SENSORS 44 INCHES ABOVEFINISHED FLOOR AND CENTERED ABOVE THE LIGHT SWITCHESWHERE BOTH OCCUR IN THE SAME LOCATION. UNLESSOTHERWISE NOTED.

PROVIDE FIRE DAMPER, ACCESS DOOR IN ALL DUCTWORKPIERCING FLOORS, AND 2 HOUR FIRE RATED WALLS.

COORDINATE LOCATION OF CEILING DIFFUSERS AND GRILLES WITHLIGHTING. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS.

DUCT RUN-OUTS TO DIFFUSERS SHALL BE THE SAME SIZE ASDIFFUSER NECK SIZE.

SUPPLY DUCT BRANCH TO TERMINAL BOXES SHALL BE SAMESIZE AS BOX INLET SIZE UNLESS OTHERWISE NOTED. REFER TOM09-02.

DUCT SIZE SHOWN ARE NET FREE AIR PASSAGE DIMENSIONS.DUCTS ARE NOT LINED, BUT ARE EXTERNALLY INSULATED.

PROVIDE AIR VENTS AT HIGH POINT OF ALL WATER SYSTEM.

COORDINATE INSTALLATION OF EQUIPMENT AND PIPING WITHELECTRICAL CONTRACTOR TO INSURE NEC CLEARANCE IN FRONTOF ALL ELECTRICAL PANELS.

ARRANGE PIPING CONNECTIONS TO ALL EQUIPMENT TO ALLOWEASY REMOVAL OF EQUIPMENT, COILS, FANS, MOTORS, FILTERS,ACCESS PANELS, ETC. PROVIDE UNIONS, FLANGES AND VALVESAT CONNECTIONS.

REFER TO ARCHITECTS DRAWINGS FOR EXACT LOCATION AND SIZEOF LOUVERS. BLANKOFF AREA OF LOUVERS NOT USED FOROUTSIDE AIR OR EXHAUST.

FVV-1-10[5000]

TERMINAL BOX NOMENCLATURE

TERMINAL BOXTYPE

TERMINAL BOXFLOOR LOCATION

MAXIMUM CFM

BOX NUMBER

LE

GE

ND

DIS

RE

GA

RD

LE

GE

ND

IT

EM

S N

OT

IN

DIC

AT

ED

ON

DR

AW

ING

S

SYMBOL DESCRIPTIONABBREV.

FD/FSD

DESCRIPTIONABBREV.SYMBOL

MVD

VD

SA/OA

RA

EA/REA

D OR DD

OR

10

1

CARBON DIOXIDE SENSOR

N.O.

HUMIDITY SENSOR

DIFFERENTIAL PRESSURE SENSOR

MOTOR STARTER

NORMALLY CLOSED

NORMALLY OPEN

N.C.

VARIABLE FREQUENCY DRIVE

FREEZE STAT

FILTER GAUGE

DIFFERENTIAL PRESSURE SWITCH

AIRFLOW MEASURING STATION

ELECTRICAL SIGNAL

DAMPER OR VALVE ACTUATOR

HIGH PRESSURE SHUT OFF SWITCH

AFMS

NEW WORK

EXISTING WORK

FIRE/FIRE SMOKE DAMPER

RETURN AIR DUCT

SUPPLY/OUTSIDE AIR DUCT

EXHAUST/RELIEF AIR DUCT

ACCESS DOOR

MOTORIZED VOLUME DAMPER

VOLUME DAMPER

SUPPLY AIR DIRECTION

OFFSET AIR QUANTITY (CFM)/EXHAUST/RETURN DIRECTION

TEMPERATURE SENSOR

THERMOSTAT

HUMIDISTAT

SMOKE DUCT DETECTOR

SMOKE DETECTOR

STATIC PRESSURE SENSOR

KEYED NOTE

REVISION TRIANGLE

DENOTES RECTANGULAR DUCTWORK

DENOTES OVAL DUCTWORK

DENOTES ROUND DUCTWORK/PIPING12"

70/22

70/22 O.

VARIABLE FREQUENCY DRIVE

ABOVE FINISHED FLOOR

BOTTOM OF DUCT

AFF

VFD

BOD

FLAT OVAL

(E)/EXIST.

FO

EXISTING

BOP BOTTOM OF PIPE

CAV CONSTANT AIR VOLUME

VARIABLE AIR VOLUMEVAV

C/C COOLING COIL

HEATING COILH/C

CFM CUBIC FEET PER MINUTE

EXHAUST FANEF

EXH EXHAUST

FAN COIL UNITFCU

GPM GALLONS PER MINUTE

NOT TO SCALENTS

SAD SOUND ATTENUATING DEVICE

AFMS AIR FLOW MEASURING STATION

VTR VENT THRU ROOF

DDC DIRECT DIGITAL CONTROL

AIR HANDLING UNITAHU

COMPRESSED AIR

CHS

CWS

CWR

HWS

CHR

CHILLED WATER SUPPLYCHS

CONDENSING WATER RETURN

CONDENSING WATER SUPPLY

CHILLED WATER RETURN

HOT WATER SUPPLY

CWS

CWR

HWS

CHR

THREE-WAY CONTROL VALVE

TWO-WAY CONTROL VALVE

BUTTERFLY VALVE

SOLENOID VALVE

VENTURI FLOW TUBE

THERMOMETER WELL

PLUG VALVE

GAGE COCK

VALVE BOX

CHECK VALVE

GLOBE VALVE

GATE VALVE

BALL VALVE

PRESSURE RELIEF VALVE

# OF STEAM RETURN

# OF STEAM SUPPLY

PRESSURE REDUCING VALVE

HOT WATER RETURN

PRV

STRAINER

ANCHOR

FLEXIBLE JOINT

GAGE

REDUCER

UNION

THERMOMETER

RV

HWR

A

#R

#S

HWR

#S

#R

A

PCR PCR PUMP CONDENSATE RETURN

CR CR CONDENSATE RETURN

HP

DP

VFD

FS

G

P

HS

CO2

S

TS

SP

H HS

T

ES

TEMPORARY WORK

MECHANICAL SYSTEMS INFORMATION

SYSTEMS DESCRIPTION

DESIGN CONDITIONS (FOR HEATING AND COOLING LOAD CALC.)

SUPPLY

EXISTING 100% OUTSIDE ARE HANDLERS WITH AND HUMIDITY CONTROL.

ALL LAB AND ANIMAL SUPPORT AREAS WILL HAVE PHOENIX LAB-TRAC AIRVALVES WITH HEATING HOT WATER COIL FOR EACH ROOM

NEW WORK WILL TIE INTO EXISTING HIGH PLUME DILUTION EXHAUST FANS WITH REDUNDANT CAPACITY.

PHOENIX LAB-TRAC AIR VALVES WILL BE PROVIDED FOR EACH ROOM. ANIMAL HOLDING/PROCEDUREROOMS WILL BE PROVIDED WITH ONE EXHAUST VALVE.

SUMMER OUTSIDE (DEG. F DB/WB)

WINTER OUTSIDE (DEG F)

SUMMER INSIDE:

ANIMAL HOLDING, PROCEDURE

FRESH (OUTSIDE) AIR (OWNER REQ)

96.0 F / 80 F

20.0 F DB

70 F DB / 15 ACH

EXHAUST

WINTER INSIDE (OCCUPIED SPACES) 70 F DB

SMALL ANIMAL VIVARIUM WITH IVCS, OCCUPIED, OPERATION (MINIMUM) 10 AIR CHANGES/HR

SMALL ANIMAL VIVARIUM WITH IVCS, OCCUPIED, DESIGN (MINIMUM) 15 AIR CHANGES/HR

LARGE ANIMAL VIVARIUM, OCCUPIED, DESIGN, OPERATION (MINIMUM) 15 AIR CHANGES/HR

GENERAL NOTES

REFER TO CONTROL MODE SCHEDULES (M-003, AND M-004) FOR FURTHER OPERATING MODE REQUIREMENTS INCLUDING ROOM OFFSETSETPOINTS. ALL PHEONIX AIR VALVES SHALL BE SIZED TO OPERATE AT ALL MODES.

REFER TO SPECIFICATIONS FOR MATERIAL REQUIREMENTS.

MAX. SP. IS THE MAXIMUM ALLOWABLE STATIC PRESSURE LOSS THROUGH THE AIR VALVE AND COIL AT SCHEDULED MAXIMUM COIL CFM.

DIVISION 26 WILL PROVIDE 120/1PH POWER AT EACH PHEONIX LAB ROOM CONTROLLER (LRC) CONTROL PANEL. LRC IN SEPARATE PANELENCLOSURE SHALL BE LOCATED ADJACENT TO LS TERMINAL UNIT. DIVISION 23 TO PROVIDE TRANSFORMER AS REQUIRED FOR CONTROLSPOWER. PROVIDE CONTROL POWER TO EACH AIR VALVE AS REQUIRED FROM THE LAB ROOM CONTROLLER.

ALL AIR VALVES SHALL BE MEDIUM PRESSURE AIR VALVES.

A.

B.

C.

D.

E.

01/

2"1"

2"

TA

S

E OF TEXAS

P RE

ENI

GNELANOISS

FO

R

EL IC E N S E D

T

JON HARPER

115708

Tx. Registration # F-2113

Sheet

Title

Approved

Checked

Drawn

Job Number

Date

Sheet Information

Copyright © 2015 Perkins+Will

Revisions

15 234

A

D

B

C

15 234

A

D

B

C

185108.000

MEP Engineer

Shah Smith & Associates

2825 Wilcrest, Suite 350Houston, TX 77042

t 713.780.7563

f 713.780.9209

MDACC Project# 12-0545.1

4/1

8/2

017 1

1:2

1:1

5 A

MC

:\E

ds_cad\P

roje

cts

\Revit_2015\1

111-0

42-0

1_M

echanic

al_

R15_E

Str

iblin

g.r

vt

4/1

8/2

017 1

1:2

1:1

5 A

M

C:\E

ds_cad

\Pro

jects

\Revit_20

15\1

11

1-0

42-0

1_

Mecha

nic

al _

R15_E

Str

iblin

g. r

vt

M11-01

MECHANICALLEGENDS,

GENERAL NOTESAND SCHEDULES

J. HARPER

E. STRIB

April 18, 2017

J. HARPER

ISS

UE

D F

OR

BID

DIN

G A

ND

CO

NS

TR

UC

TIO

N A

pri

l 18, 2017

CRB ANIMAL AREARENOVATION -

ACTIVATIONPACKAGE

1515 Holcombe Blvd.Houston, TX 77030

UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER

1001 McKinneySuite 1300

Houston, TX 77002t 713.366.4000f 713.528.3339

www.perkinswill.com

MECHANICAL SHEET LIST - ACTIVATION PACKAGESheet

Number Sheet Name

M11-01 MECHANICAL LEGENDS, GENERAL NOTES AND SCHEDULES

M11-02 ENLARGED BASEMENT LEVEL AREA A-C

M11-03 ENLARGED BASEMENT LEVEL PIPING AREA A-C

M11-04 MECHANICAL CONTROLS

M11-05 MECHANICAL DETAILS

Grand total: 5

LAB TRAC SUPPLY AIR TERMINAL BOX SCHEDULE (HEATING WATER) AP

MARK LAB SERVED

CFM RoomOffsetCFM

VALVESIZE

MAXS.P. IN.

WG

HOT WATER COIL

REMARKSMAX MIN CFMEAT(F)

LAT(F) MBH

ENTERINGWATER (F) GPM

MINROWS

GE-BR-B-22 LG ANIMAL HOLDING TB.3950 790 790 100 12 0.6 OWNER FURNISHED CONTRACTOR INSTALLED

SD-BR-B-22 LG ANIMAL HOLDING TB.3950 690 690 100 12 0.7 690 55 80 18.5 130 1.9 2 OWNER FURNISHED CONTRACTOR INSTALLED

NO ISSUE DATE

04-18-2017

Page 4: MDACC Project# 12-0545 - C-AIR-S PRESSURE SHUT OFF SWITCH AFMS NEW WORK EXISTING WORK FIRE/FIRE SMOKE DAMPER RETURN AIR DUCT SUPPLY/OUTSIDE AIR DUCT EXHAUST/RELIEF AIR DUCT ACCESS

1 2

1

LG ANIMAL HOLDING

TB.3950

[790]GE-BR-B-22

DP

[690]SD-BR-B-22

1

KEYED NOTES

REPLACE EXISTING AIR TERMINAL WITH NEWUNIT AS SCHEDULED. MATCH EXISTINGTEMPERATURE SENSOR LOCATION. VALVES AREOWNER FURNISHED CONTRATOR INSTALLED.

1

GENERAL NOTES

A. REFER TO DETAIL SHEET M11-05 FORTERMINAL BOX INSTALLATION.

B. CONTRACTOR SHALL PROVIDE CLEARANCEIN FRONT AND AT SIDES OF TERMINAL BOX UNITCONTROL PANEL AND J-BOX AS REQUIRED BYN.E.C. (36 INCHES).

C. PROVIDE DUCTWORK TRANSITIONS ASREQUIRED AT TERMINAL BOX INLET ANDDISCHARGE CONNECTIONS.

D. INSULATE EXTERIOR OF ALL SUPPLY AIRDUCTWORK AND THE TOP OF ALL SUPPLY AIRDIFFUSERS.

E. PROVIDE YOUNG REGULATORS FOR ALLDAMPERS LOCATED ABOVE INACCESSIBLECEILINGS AND NOT WITHIN THE INTERSTITIALSPACE. YOUNG REGULATORS SHALL BEPROVIDED WITH SOLID SHAFT CONNECTION;CABLE CONNECTION TO REGULATOR WILL NOT BEACCEPTED.

F. ALL AIR VALVES SHALL BE LOCATED TOALLOW FOR ACCESS TO THE CONTROLS PANELAND THE ACTUATOR.

G. CONNECT TEMP SENSOR TO LABCONTROLLER ASSOCIATED WITH EACH SPACE.REFER TO SCHEDULE FOR ASSOCIATED AIRTERMINALS.

H. PIPING AND DUCTWORK ARE NOTPERMITTED IN ELECTRICAL ROOMS, ELEVATORMACHINE ROOMS AND COMMUNICATION ROOMS.

I. EXISTING MEP DRAWINGS ARE TAKEN FROMAS-BUILT DOCUMENTS. DOCUMENTS AREGENERALLY CORRECT, HOWEVER, REVISIONSDUE TO MAINTENANCE AND MINOR RENOVATIONSHAVE OCCURRED AND MAY NOT BE REFLECTEDON THE PLANS. CONTRACTOR TO FIELD VERIFYEXISTING MEP EQUIPMENT AS REQUIRED TOACCOMPLISH WORK.

J. CONNECT NEW HOT WATER COILS TOEXISTING HOT WATER BRANCHES IN INTERSTITIALSPACE. HW PIPE TO BE 3/4" UNLESS OTHERWISENOTED.

01/

2"1"

2"

TN

0'

TA

S

E OF TEXAS

P RE

ENI

GNELANOISS

FO

R

EL IC E N S E D

T

JON HARPER

115708

Tx. Registration # F-2113

1/4" = 1'-0"

4' 8'

KEY PLAN

Sheet

Title

Approved

Checked

Drawn

Job Number

Date

Sheet Information

Copyright © 2015 Perkins+Will

Revisions

15 234

A

D

B

C

15 234

A

D

B

C

185108.000

MEP Engineer

Shah Smith & Associates

2825 Wilcrest, Suite 350Houston, TX 77042

t 713.780.7563

f 713.780.9209

MDACC Project# 12-0545.1

4/1

8/2

017 1

0:3

7:1

4 A

MC

:\E

ds_cad\P

roje

cts

\Revit_2015\1

111-0

42-0

1_M

echanic

al_

R15_E

Str

iblin

g.r

vt

4/1

8/2

017 1

0:3

7:1

4 A

M

C:\E

ds_cad

\Pro

jects

\Revit_20

15\1

11

1-0

42-0

1_

Mecha

nic

al _

R15_E

Str

iblin

g. r

vt

M11-02

ENLARGEDBASEMENT LEVEL

AREA A-C

J. HARPER

E. STRIB

April 18, 2017

J. HARPER

ISS

UE

D F

OR

BID

DIN

G A

ND

CO

NS

TR

UC

TIO

N A

pri

l 18, 2017

CRB ANIMAL AREARENOVATION -

ACTIVATIONPACKAGE

1515 Holcombe Blvd.Houston, TX 77030

UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER

A-C

1001 McKinneySuite 1300

Houston, TX 77002t 713.366.4000f 713.528.3339

www.perkinswill.com

1/4" = 1'-0"1

ENLARGED BASEMENT LEVEL -AREA A-C

NO ISSUE DATE

04-18-2017

Page 5: MDACC Project# 12-0545 - C-AIR-S PRESSURE SHUT OFF SWITCH AFMS NEW WORK EXISTING WORK FIRE/FIRE SMOKE DAMPER RETURN AIR DUCT SUPPLY/OUTSIDE AIR DUCT EXHAUST/RELIEF AIR DUCT ACCESS

PIPING GENERAL NOTES

A. REFER TO DETAIL SHEET M11-05 FOR 2-WAY CONTROL VALVE CONNECTION PIPING.

B. INSULATE ALL HOT WATER PIPING.

C. INSULATE HOT WATER COIL CASING ATEACH TERMINAL UNIT.

D. PIPING IS NOT PERMITTED ABOVEELECTRICAL AND TELECOMMUNICATIONSROOMS.

C. COORDINATE PIPING WITH CABLE TRAYINSTALLATION IN ALL SPACES. PIPING SHALLNOT INTERFERE WITH ACCESS TO CABLETRAY.

D. PROVIDE REDUCERS IN PIPING AT COILCONNECTIONS AS REQUIRED. TYPICAL AT ALLTERMINAL UNITS.

E. RUN OUTS TO TERMINAL UNITS ARE 3/4"UNLESS OTHERWISE NOTED.

F. CONTRACTOR TO PROVIDECOORDINATION DRAWINGS FOR ABOVECEILING AND INTERSTITIAL INSTALLATIONS OFDUCTWORK, FIRE PROTECTION PIPING,PLUMBING, ELECTRICAL, AND DATA.

G. COORDINATE ROOF, FLOOR, AND WALLPENETRATIONS AND CHASE DIMENSIONS WITHARCHITECTURAL AND STRUCTURAL.

KEYED NOTES

REPLACE PIPING FROM EXISTING ISOLATIONVALVES TO COIL.

1

1 2

PROCEDURE/ HOLDING

TB.3946

LG ANIMAL HOLDING

TB.3950 (1.9)SD-BR-B-22

GE-BR-B-221

01/

2"1"

2"

TN

0'

TA

S

E OF TEXAS

P RE

ENI

GNELANOISS

FO

R

EL IC E N S E D

T

JON HARPER

115708

Tx. Registration # F-2113

1/4" = 1'-0"

4' 8'

KEY PLAN

Sheet

Title

Approved

Checked

Drawn

Job Number

Date

Sheet Information

Copyright © 2015 Perkins+Will

Revisions

15 234

A

D

B

C

15 234

A

D

B

C

185108.000

MEP Engineer

Shah Smith & Associates

2825 Wilcrest, Suite 350Houston, TX 77042

t 713.780.7563

f 713.780.9209

MDACC Project# 12-0545.1

4/1

8/2

017 1

0:3

7:2

1 A

MC

:\E

ds_cad\P

roje

cts

\Revit_2015\1

111-0

42-0

1_M

echanic

al_

R15_E

Str

iblin

g.r

vt

4/1

8/2

017 1

0:3

7:2

1 A

M

C:\E

ds_cad

\Pro

jects

\Revit_20

15\1

11

1-0

42-0

1_

Mecha

nic

al _

R15_E

Str

iblin

g. r

vt

M11-03

ENLARGEDBASEMENT LEVELPIPING AREA A-C

J. HARPER

E. STRIB

April 18, 2017

J. HARPER

ISS

UE

D F

OR

BID

DIN

G A

ND

CO

NS

TR

UC

TIO

N A

pri

l 18, 2017

CRB ANIMAL AREARENOVATION -

ACTIVATIONPACKAGE

1515 Holcombe Blvd.Houston, TX 77030

UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER

A-C

1001 McKinneySuite 1300

Houston, TX 77002t 713.366.4000f 713.528.3339

www.perkinswill.com

1/4" = 1'-0"1

ENLARGED BASEMENT LEVELPIPING - AREA A-C

NO ISSUE DATE

04-18-2017

Page 6: MDACC Project# 12-0545 - C-AIR-S PRESSURE SHUT OFF SWITCH AFMS NEW WORK EXISTING WORK FIRE/FIRE SMOKE DAMPER RETURN AIR DUCT SUPPLY/OUTSIDE AIR DUCT EXHAUST/RELIEF AIR DUCT ACCESS

C

H

V-X

PXLS-Y-X PXGE-Y-X

TTE-X

SEQUENCE OF OPERATIONINSTALLATION NOTES: indicated by

1. Point summary states points required and do not excludepoints listed/specified elsewhere in the construction documents.

2. All safeties shall be hard-wired. Software interlocks are notacceptable. BAS shall monitor status of safeties as shown.Provide all safeties necessary to protect the equipment fromphysical damage.

3. BAS point names and new and/or modified graphics shall beapproved by owner prior to implementation.

4. Any removal and/or interruption of existing BAS shall bescheduled and coordinated with owner prior to starting.

5. BAS contractor to coordinate with owner for verification ofBAS devices prior to commissioning. Coordinate commissioningwith owner.

6. BAS contractor is responsible for demolition of all physicaldevices and deletion of points and programming from thedatabase.

7. All new or relocated wiring shall have typed relocation tags.Hand written tags are not acceptable.

8. A copy of the final as-built control termination drawing andrelated riser diagram layout shall reside inside of all buildingcontrollers panel enclosures.

9. Mount lab zone controller adjacent to supply valve. Mount onunistrut on hand rail in interstitial or wall mount as appropriate foraccess.

10. All valves shall fail to last position.

11. Coordinate all required points to be monitored by EdstromSystem. This shall be a minimum differential pressure,temperature, and humidity.

POINT DESCRIPTORPOINT NAME

POINT TYPE

DI AI DO AO VP

TYPICAL POINTS LIST

REMARKS

:GEF GENERAL EXHAUST FLOW X

:RT ROOM (ZONE) TEMP XACTUAL ZONE TEMP SET POINT X ACTUAL PHOENIX ZONE TEMP SET POINT FEEDBACK TO SIEMENS

:TSF TOTAL SUP FLOW X SUM OF ALL SUPPLIES:TEF TOTAL EXH FLOW X SUM OF ALL GENERAL

TOTALS 6 10 1 12

:OCC 15 OCC SUPPLY FLOW 15ACH SET POINT XREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TO PHOENIX;SIEMENS SUPERVISORY CONTROL

:UnocMnSAF UNOCC SUPPLY FLOW MIN SET POINT XCFM (RELATED T0 4 ACH); AO FROM SIEMENS TO PHOENIX;SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)

:OccStpt OCC/UNOCC COMMAND SET POINT X SIEMENS SUPERVISORY CONTROL

Control Qty ProductNumber Manufacturer Document DescriptionDevice Number

Field Mounted Devices

BILL OF MATERIAL

PXGE-Y-X 1 EXHAUST AIR VALVE

PXLS-Y-X SUPPLY AIR VALVE WITH REHEAT

TTE-X ROOM (ZONE) TEMPERATURE SENSOR

RTR-X ROUTER/POWER PANEL

V-X SEE CONTROL VALVE SUBMITTAL

NOTES: Y = ROOM NUMBER; X = NUMBER

:OccSta OCC/UNOCC COMMAND STATUS X

OCC COOLING ZONE TEMP SET POINT XOCC HEATING ZONE TEMP SET POINT XUNOCC COOLING ZONE TEMP SET POINT XUNOCC HEATING ZONE TEMP SET POINT X

:SAF SUPPLY AIRFLOW X:SPA STATIC PRESSURE ALARM X:JAM JAM ALARM X:RVA HCLO REHEAT VALVE HEATING COIL LOOPOUT X AI TO SIEMENS FROM PHOENIX

:ROStpt ZONE AIRFLOW OFFSET SET POINT X SIEMENS SUPERVISORY CONTROL:RO ZONE AIRFLOW OFFSET X

NOTE: DI AND AI ARE CONTROL POINTS THAT PHOENIX SENDS VALUES TO SIEMENS. DO AND AO ARE CONTROL POINTS THATSIEMENS SENDS VALUES TO PHOENIX.

The laboratory zone consists of a building automation system that controls venturi-type air valves (supply and general exhaust), and reheat coil valve actuator.

OCCUPIED/UNOCCUPIED MODES:Enable mutiple occupied and unoccupied mode capabilities. SIEMENS shall sendan occupancy mode signal (adjustable) to Phoenix. SIEMENS shall receive fromPhoenix the status of occupancy mode.

SIEMENS shall send signal (adjustable) for minimum occupied supply air flow setpoint to Phoenix system. SIEMENS shall send signal (adjustable) for minimumunoccupied supply air flow set point to Phoenix system.

ZONE AIR CHANGE PER HOUR RATE CONTROL:The Lab Zone Controller (LZC) receives the general exhaust CFM value from thegeneral exhaust air valve(s). The LZC total zone exhaust CFM is the zone generalexhaust CFM. Using a proportional, integral, and derivative (PID) closed loopcontrol algorithm, the LZC modulates the zone supply and general exhaust airvalves to ensure that the zone does not go below the minimum required zone airchanges per hour (ACH) rate (occupied and unoccupied).

ZONE PRESSURIZATION CONTROL:The total exhaust air volume and the total supply air volume for the zone ismonitored and controlled to maintain a negative or positive zone airflow offset setpoint (" refer to M-400 series") relative to the exhaust air flow. SIEMENS shallsend the ZONE AIRFLOW OFFSET CFM set point (adjustable) to Phoenix to use.SIEMENS shall receive from Phoenix the actual monitored zone airflow CFMoffset.

The LZC calculates the required ZONE SUPPLY AIR CFM necessary bysubtracting the zone airflow offset CFM set point from the total zone exhaustCFM. The LZC modulates the ZONE SUPPLY AIR CFM using the supply airvalve to ensure that the zone airflow offset CFM (flow tracking differential CFM) isalways maintained by a proportional, integral, and derivative (PID) closed loopcontrol algorithm.

ZONE TEMPERATURE CONTROL:The LZC measures the temperature in the zone by means of the ZONETEMPERATURE SENSOR and maintains the zone temperature at the set point byadjusting the supply airflow and modulating the NORMALLY CLOSED (N.C.)HEATING VALVE using a proportional, integral, and derivative (PID) closed loopcontrol algorithm.

If the ZONE SUPPLY AIR is at its minimum limit, the zone has general exhaust airvalve(s), and the zone requires increased cooling beyond the amount of ZONESUPPLY AIR CFM necessary to maintain the required ZONE AIRFLOW OFFSET, theLZC increases the ZONE SUPPLY AIR CFM as well as the ZONE GENERALEXHAUST CFM to maintain the zone temperature set point and the ZONE AIRFLOWOFFSET.

Occupied Mode-SIEMENS shall send zone temperature occupied cooling set point (adjustable) andzone temperature occupied heating set point (adjustable) to Phoenix system formaintaining zone temperature set point during occupied mode.

Unoccupied Mode-SIEMENS shall send zone temperature unoccupied cooling set point (adjustable) andzone temperature unoccupied heating set point (adjustable) to Phoenix system formaintaining zone temperature band during unoccupied mode.

CONTROL PRIORITY:A priority structure applies to the above control applications to ensure that safety ismaintained as the highest control priority when HVAC systems or individualcomponents cannot meet all demands placed upon the system.

1. ZONE PRESSURIZATION is first highest priority.2. ZONE MINIMUM AIR CHANGE PER HOUR RATE is the second level of priority.3. ZONE TEMPERATURE CONTROL is the third level of priority.

NCHWS

HWR

1

:ActRTStpt:CSP:HSP:UnoccCSP:UnoccHSP

1

1

1

1

X

X

ROOM DIFFERENTIAL PRESSURE X:DIFF PRESSUREPROVIDE ALARMS FOR HIGH AND LOW DIFFERENTIAL PRESSURE. PROVIDE ONROOMS SHOWN ON M-400 SERIES. DIFFERNTIAL PRESSURE SHALL DISPLAY IN THEDDC, NOT A MONITOR IN THE ROOM/PLENUM.

MONITOR ROOM RELATIVE HUMIDITY X:RHANIMAL HOLDING, PROCEDURE ROOM, CLINIC, GEM ROOMS, ASSOCIATED CORRIDORSONLY. MONITOR ONLY. NO CONTROL ASSOCIATED.

:OCC 10 OCC SUPPLY FLOW 10ACH SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)

:OCC SANITIZE OCC SUPPLY FLOW SANITIZE SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)

X

X:OCC SHED 1 OCC SUPPLY FLOW SHED 1 SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)

X:OCC SHED 2 OCC SUPPLY FLOW SHED 2 SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)

X:OCC EMER OCC SUPPLY FLOW EMER SET POINTREFER TO M-003 FOR SETPOINTS; AO FROM SIEMENS TOPHOENIX; SIEMENS SUPERVISORY CONTROL (AS APPLICABLE)

HMT-X

FOR ROOMS WITH A HUMIDITYSENSOR AND A TEMPERATURESENSOR (SHOULD BE A SINGLE UNIT)

RTR-X

OUT

IN

120V POWERBY DIV 26

TO BAS

FOR ROOMS WITH ONLY ATEMPERATURE SENSOR.

DP

FOR ROOMS INDICATED.RE: FLOORPLANS

HMT-X COMBINATION TS AND HS1

DP-XDIFFERENTIAL PRESSURE SENSOR AND ASSOCIATEDSENSING PROBES/COVER PLATES

1

* (NOTE: 1 PER VALVE)* (NOTE: 1 PER VALVE)

CALCULATED ACH X:ACH CALCULATED ACH BASED ON MEASURED AIRFLOW

01/

2"1"

2"

TA

S

E OF TEXAS

P RE

ENI

GNELANOISS

FO

R

EL IC E N S E D

T

JON HARPER

115708

Tx. Registration # F-2113

Sheet

Title

Approved

Checked

Drawn

Job Number

Date

Sheet Information

Copyright © 2015 Perkins+Will

Revisions

15 234

A

D

B

C

15 234

A

D

B

C

185108.000

MEP Engineer

Shah Smith & Associates

2825 Wilcrest, Suite 350Houston, TX 77042

t 713.780.7563

f 713.780.9209

MDACC Project# 12-0545.1

4/1

8/2

017 1

0:3

7:2

7 A

MC

:\E

ds_cad\P

roje

cts

\Revit_2015\1

111-0

42-0

1_M

echanic

al_

R15_E

Str

iblin

g.r

vt

4/1

8/2

017 1

0:3

7:2

7 A

M

C:\E

ds_cad

\Pro

jects

\Revit_20

15\1

11

1-0

42-0

1_

Mecha

nic

al _

R15_E

Str

iblin

g. r

vt

M11-04

MECHANICALCONTROLS

J. HARPER

E. STRIB

April 18, 2017

J. HARPER

ISS

UE

D F

OR

BID

DIN

G A

ND

CO

NS

TR

UC

TIO

N A

pri

l 18, 2017

CRB ANIMAL AREARENOVATION -

ACTIVATIONPACKAGE

1515 Holcombe Blvd.Houston, TX 77030

UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER

1001 McKinneySuite 1300

Houston, TX 77002t 713.366.4000f 713.528.3339

www.perkinswill.com

NO ISSUE DATE

NO SCALE1

LAB ZONE (ROOM) CONTROLWITHOUT HOOD

04-18-2017

Page 7: MDACC Project# 12-0545 - C-AIR-S PRESSURE SHUT OFF SWITCH AFMS NEW WORK EXISTING WORK FIRE/FIRE SMOKE DAMPER RETURN AIR DUCT SUPPLY/OUTSIDE AIR DUCT EXHAUST/RELIEF AIR DUCT ACCESS

THERMOMETER (TYPICAL)

PRESSURE GAUGE (TYPICAL)

REDUCER (TYPICAL)

SUPPLY

STRAINER WITH BALL VALVE AND CAPPEDHOSE ADAPTER

2-WAY MODULATINGCONTROL VALVE

RETURN

AIR

3/4" BALL VALVE WITH CAPPEDHOSE ADAPTE

BALANCING VALVE(MEMORY STOPS)

3/4" AUTO AIRVENT PIPED TOF.D. (NOTE 4)

PRESSURE/TEMPERATURETEST PORT (TYPICAL )BUTTERFLY VALVE

WHERE PIPE SIZE IS 2" OR SMALLER, PROVIDE BALL VALVE IN LIEU OF BUTTERFLY VALVE.

INSTALL UNIONS OR FLANGES IN PIPE LOCATIONS OUT OF WAY TO PERMIT COIL REMOVAL.

FOR TERMINAL AND FAN COIL UNITS PIPING PROVIDE PRESSURE/TEMPERATURE TEST

PLUGS ONLY. PRESSURE GAUGES AND THERMOMETERS NOT REQUIRED.

PROVIDE MANUAL AIR VENT AT TERMINAL UNITS.

PROVIDE REDUCERS AT TERMINAL UNIT COIL CONN. AS REQUIRED.

CONNECT COILS IN COUNTER FLOW ARRANGEMENT.

PROVIDE UNIONS OR FLANGES IMMEDIATELY UPSTREAM AND DOWNSTREAM OFCONTROL VALVE.

3/4" BALL VALVE WITH CAPPED HOSE ADAPTOR CAN BE OMITTED IF STRAINER IS AT LOWPART OF PIPING.

NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

ACID RESISTANTGASKET MATERIAL(TYPICAL)

316L STAINLESSSTEEL FLANGE(TYPICAL)

TRANSITIONAS REQUIRED

ALL THREAD ROD(SUPPORT FROMSTRUCTURE)

1.

2.

3.

4.

PROVIDE PIPE TYPE GASKET EQUAL TOSEALEX BY THERMOSEAL INC.

SUPPORT ARE VALVE INDEPENDENT OFATTACHED DUCTWORK.

PROVIDE 24" ACCESS TO CONTROL PANEL.

BASED ON PHOENIX VALVES.

NOTES:

STAINLESS STEEL EZJOINT CONNECTORBY UNION MADEPRODUCT FORROUND FLANGECONNECTIONS

18" ADD TRANSITION ASREQUIRED FOR DUAL,TRIPLE AND QUADCONNECTIONS.

LAB/GENERALEXHAUST VALVE

TRANSITION ASREQUIRED

DUCT INSULATION

WRAP VAPOR BARRIERAROUND DUCTBOARDAND SEAL VAPORTIGHT

DUCTBOARD INSULATION

DUCT

VAPOR BARRIER3" MIN.

SHEETMETALDUCTWORK

UNISTRUT SUPPORT

SEE DETAIL "A" DUCTBOARD INSULATIONWITH VAPOR BARRIER

INSULATION INACCORDANCE WITHSPECIFICATIONS

THREADED ROD

DETAIL "A"

2" MIN.

DUCT INSULATION SHIELD

15-DEG.MAX

30-DEG.MAX

A x B A x B

A x

B

TWO-SIDEDTRANSITION

ONE-SIDEDTRANSITION

REDUCE DUCTSIZE IN ONEDIMENSIONONLY, IFPOSSIBLE.

NOTE: 1. FLAT ON ONE SIDE AND/OR FLAT ON BOTTOM PREFERRED.

A x

B

ACCESS DOOR

ACCESS DOOR

HEATING COILS MAY BE DIRECTLY CONNECTEDTO DUCT.INSULATE COIL U-BENDS.PROVIDE EXTENSION HANDLES FORACCESS DOOR CLOSERS.

HEATING COILS

FLOW

30-DEG. MAX

45-DEG. MAX

FLOWA.D.

NOTE:

1.

2.3.

1'-0" MAXLENGTHFLEX DUCTCONNECTION

ACCESS DOOR

MAX 15 DEG. ANGLEUPSTREAM OF COIL

MAXIMUM 30 DEG. ANGLEDOWNSTREAM OF COIL

HEATING COIL

LOW PRESSUREDUCTWORK(SIZE PER PLAN)

1.

2.

3.

4.

REFER COIL PIPING DETAILS.

INSULATE HEATING COIL AND TUBE ENDS SAMEAS ADJACENT DUCTWORK.

SUPPORT LAB SUPPLY VALVE INDEPENDENTLYFROM DUCTWORK.

BASED ON PHOENIX VALVES.

NOTES:

LAB SUPPLY VALVE

36" ACCESS TOCONTROL PANEL

01/

2"1"

2"

TA

S

E OF TEXAS

P RE

ENI

GNELANOISS

FO

R

EL IC E N S E D

T

JON HARPER

115708

Tx. Registration # F-2113

Sheet

Title

Approved

Checked

Drawn

Job Number

Date

Sheet Information

Copyright © 2015 Perkins+Will

Revisions

15 234

A

D

B

C

15 234

A

D

B

C

185108.000

MEP Engineer

Shah Smith & Associates

2825 Wilcrest, Suite 350Houston, TX 77042

t 713.780.7563

f 713.780.9209

MDACC Project# 12-0545.1

4/1

8/2

017 1

0:3

7:3

4 A

MC

:\E

ds_cad\P

roje

cts

\Revit_2015\1

111-0

42-0

1_M

echanic

al_

R15_E

Str

iblin

g.r

vt

4/1

8/2

017 1

0:3

7:3

4 A

M

C:\E

ds_cad

\Pro

jects

\Revit_20

15\1

11

1-0

42-0

1_

Mecha

nic

al _

R15_E

Str

iblin

g. r

vt

M11-05

MECHANICALDETAILS

J. HARPER

E. STRIB

April 18, 2017

J. HARPER

ISS

UE

D F

OR

BID

DIN

G A

ND

CO

NS

TR

UC

TIO

N A

pri

l 18, 2017

CRB ANIMAL AREARENOVATION -

ACTIVATIONPACKAGE

1515 Holcombe Blvd.Houston, TX 77030

UNIVERSITY OF TEXAS MDANDERSON CANCER CENTER

1001 McKinneySuite 1300

Houston, TX 77002t 713.366.4000f 713.528.3339

www.perkinswill.com

NO ISSUE DATE

NO SCALE1

2-WAY CONTROL VALVE COILCONNECTION DETAIL

NO SCALE3

LAB AND GENERAL EXHAUSTVALVE CONNECTION DETAIL

NO SCALE4

RECTANGULAR DUCT SUPPORTEDBY UNISTRUT DETAIL

NO SCALE5

TYPICAL ONE & TWO SIDEDRECTANGULAR DUCT TRANSITIONDETAIL

NO SCALE6

REMOTE HEATING COIL DUCTINSTALLATION DETAIL

NO SCALE2

PHOENIX LAB SUPPLY VALVECONNECTION DETAIL_AP

04-18-2017