Company: April 30, 2012MCQUAY INTERNATIONAL (421088)
DOUBLE TREE
2305 HOTEL PLAZA BLVD
ORLANDO, FL 32830
Contact:
904-866-7733
Your Representative:
LIOCE, Mr. PAUL A (PAUL)
STEVE WANDTKE
(407) 9341000
Cooling Water Advanced DoubleTree
City WaterMake-UpSample:
RECORD
189
Cond
RECORD
80.0
Calcium
RECORD
92.00
Total Alk
RECORD
8.17
pH
STATUS
Make-up water is normal for this time of year.
ACTIONS
No action required at this time.
Cooling TowerTower
1.32
Sample:
Conductivity Cycles:
750-950
249
Cond
200-500
88.0
Calcium
250-450
114.00
Total Alk
RECORD
8.47
pH
.25-.50
0.03
Molybdenum
<2
0.02
Iron
<.5
0
Copper
STATUS
System is still in the passivation process.
ACTIONS
Passivation of new towers has been in process since Feb 5th. I will cease passivation in the middle of may. System residuals
are low due to the passivation process of running 1-2 cycles for 60-90 days. Once passivation is completed, system will return to
normal operating limits.
Irving, TX ¦ Monmouth Junction, NJ ¦ Jacksonville, FL ¦ Macon, GA ¦ Las Vegas, NV ¦ Brampton, ON
Page 1 of 2April 30, 2012 FSR.3.0
Chem-Aqua Headquarters 1-800-527-9921 ANCO Headquarters 1-800-476-4262
![Page 2: Mcquay International Fsr238 4-30-2012](https://reader035.fdocuments.in/reader035/viewer/2022080209/5535921c4a795936258b45fa/html5/thumbnails/2.jpg)
Company: April 30, 2012MCQUAY INTERNATIONAL (421088)
DOUBLE TREE
2305 HOTEL PLAZA BLVD
ORLANDO, FL 32830
Contact:
904-866-7733
Your Representative:
LIOCE, Mr. PAUL A (PAUL)
STEVE WANDTKE
(407) 9341000
Main ChillClosed Chilled WaterSample:
1000-3000
2647
Cond
8.5-11
10.98
pH
600-1000
1400
Nitrite
<2
0.12
Iron
<.5
0.16
Copper
STATUS
Nitrite is higher than necessary to protect the system from corrosion.
ACTIONS
I have flushed the system to reduce the amount of nitrite throughout the system. Having nitrite slightly above recommended limits
will not negatively affect the system.
Pumps
ID StrokeSpeed
Controllers
TimerMeter CntrpHCondID
Name Quantity
.::.
Customer Signature Rep. Signature
Irving, TX ¦ Monmouth Junction, NJ ¦ Jacksonville, FL ¦ Macon, GA ¦ Las Vegas, NV ¦ Brampton, ON
Page 2 of 2April 30, 2012 FSR.3.0