MCP Call Point Data Sheet

2
 Tom Cribb Road, Thamesmead, London SE28 0BH Tel: +44 (0)20 8316 4477 or (0)20 8317 1717 Fax: +44 (0)20 8317 2400 Email: [email protected] Web Site: www.cliffordandsnell.com Break Glass and Push Button Call Point Station Light Weight Glass Reinforced Polyester (GRP) Ex d Enclosure Dual 20mm gland entries, one fitted with approved stopping plug (2 * M20 holes located at the top of the Call Point. Glands supplied separately)  Monitoring facility (DC only) Weather resistant high performance red paint finish as standard High intensity Red LED can be fitted as an optional extra to indicate operation. Available up to 24Vdc Meets the requirements of BS EN 54-11 Break Glass version - Optional stainless steel Lift Flap Test Key provided as standard Push Button version - Push to operate - Reset Key provided. Protection Flap as standard Stainless steel fixings TECHNICAL SPECIFICATION IP 66 rated Weight Approx. 1Kg Relative Humidity 95% @ 40 degC Cetified Temp –55ºC to +70ºC Voltage Up to 250V Switch Ratings DC 12 - 30V 5A (resitive) or 3A (Inductive) 30 - 50V 1A resitive or inductive  AC 12 - 250V 5A resistive or ind uctive Suitable for Zones 1 & 2 Up to 4 cable entries. Top Entries 2 * as standard. Internal earth continuity provided as standard 7 way 2.5mm terminal block mounted on a PCB. Single Pole change over switch supplied as standard and fitted directly onto the 7 way connector. MAIN FEATURES Controlled document No.D7489-01-02 (CN100301) \\My Documents\SALES DATA\data MOUNTING Via holes through the Back Box. See Installation Instructions. Unit type  APPROVAL SPECIFICATION C l i f f o r d & S n e l l DIMENSIONS (mm) ATEX Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation Ma nual Call Point s Yodalex Break Glass Switches  Single Pole Double Pole  Ad di ti on al Options (User to specify resistor & diode values) Lift FLap End Of Line Resistor In line Resistor IN Line & EOL resistor Push Button CONFIGURATOR Break Glass (BG) Push Button (PB) Explosion Proof   132.5 (5.2”) 74 (2.9”) 132.5 (5.2”) 98 (3.9”)  A B C D Duty Label (Customer to specify wording)  Tag Label (Customer to specify wording)  LED Labels Entries 2 * M20 top entries A+Bstandard (Suffix A = AC or D = DC. Example SPD = single pol e dc switch ) (For other options select position of entries required and list Finish Red (standard). ( Other options upon application)  Standards for Manual Call Points European Standards (ATEX) EN60079-0:2006 & EN60079-1:2007 EN61241-0:2004 & EN61241-1:2004 Break Glass Baseefa08ATEX02 69 Ex II2 GD Ex tD A21 (Tamb –55°C to +70°C) Push Butto n Baseefa08ATEX0269 Ex II2 GD EX tD A21 (Tamb –55°C to +70°C) International Standards (IECEx) IEC600 79-0:2004 Edition 4 & IEC60079-1 :2007 Editio n 6 IEC61241-0:2004 Edition 1 & IEC61241-1: 2004 Edition 1 Break Glass IECEx BAS 08.0089 Ex II2 GD Ex tD A21 (Tamb –55°C to +70°C) Push Butto n IECEx BAS 08.0089 Ex II2 GD Ex tD A21 (Tamb –55°C to +70°C)

description

Clifford Snell MCP Call Point Data Sheet

Transcript of MCP Call Point Data Sheet

  • Tom Cribb Road, Thamesmead, London SE28 0BH

    Tel: +44 (0)20 8316 4477 or (0)20 8317 1717 Fax: +44 (0)20 8317 2400

    Email: [email protected] Web Site: www.cliffordandsnell.com

    Break Glass and Push Button Call Point Station Light Weight Glass Reinforced Polyester (GRP) Ex d Enclosure Dual 20mm gland entries, one fitted with approved stopping plug (2 * M20 holes located at the top of the Call Point. Glands supplied separately) Monitoring facility (DC only) Weather resistant high performance red paint finish as standard High intensity Red LED can be fitted as an optional extra to indicate

    operation. Available up to 24Vdc Meets the requirements of BS EN 54-11 Break Glass version - Optional stainless steel Lift Flap Test Key provided as standard Push Button version - Push to operate - Reset Key provided. Protection Flap as standard Stainless steel fixings

    TECHNICAL SPECIFICATION IP 66 rated Weight Approx. 1Kg Relative Humidity 95% @ 40 degC Cetified Temp 55C to +70C Voltage Up to 250V Switch Ratings DC 12 - 30V 5A (resitive) or 3A (Inductive) 30 - 50V 1A resitive or inductive AC 12 - 250V 5A resistive or inductive Suitable for Zones 1 & 2 Up to 4 cable entries. Top Entries 2 * as standard. Internal earth continuity provided as standard 7 way 2.5mm terminal block mounted on a PCB. Single Pole change over switch supplied as standard and fitted directly onto the 7 way connector.

    MAIN FEATURES

    Controlled document No.D7489-01-02 (CN100301) \\My Documents\SALES DATA\data

    MOUNTING Via holes through the Back Box. See Installation Instructions.

    Unit type APPROVAL SPECIFICATION

    C l i f f o r d & S n e l l

    DIMENSIONS (mm)

    ATEX

    Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation

    Manual Call Points Yodalex

    Break Glass

    Switches Single Pole

    Double Pole

    Additional Options (User to specify resistor & diode values)

    Lift FLap End Of Line Resistor In line Resistor IN Line & EOL resistor

    Push Button

    CONFIGURATOR

    Break Glass (BG)

    Push Button (PB)

    Explosion Proof

    132.5 (5.2)

    74 (2.9)

    132.5 (5.2)

    98 (3.9)

    A B

    C D

    Duty Label (Customer to specify wording) Tag Label (Customer to specify wording)

    LED

    Labels

    Entries 2 * M20 top entries A+Bstandard

    (Suffix A = AC or D = DC. Example SPD = single pole dc switch)

    (For other options select position of entries required and list

    Finish Red (standard). (Other options upon application)

    Standards for Manual Call Points European Standards (ATEX) EN60079-0:2006 & EN60079-1:2007 EN61241-0:2004 & EN61241-1:2004 Break Glass Baseefa08ATEX0269 Ex II2 GD Ex tD A21 (Tamb 55C to +70C) Push Button Baseefa08ATEX0269 Ex II2 GD EX tD A21 (Tamb 55C to +70C) International Standards (IECEx) IEC60079-0:2004 Edition 4 & IEC60079-1:2007 Edition 6 IEC61241-0:2004 Edition 1 & IEC61241-1: 2004 Edition 1 Break Glass IECEx BAS 08.0089 Ex II2 GD Ex tD A21 (Tamb 55C to +70C) Push Button IECEx BAS 08.0089 Ex II2 GD Ex tD A21 (Tamb 55C to +70C)