Tom Cribb Road, Thamesmead, London SE28 0BH
Tel: +44 (0)20 8316 4477 or (0)20 8317 1717 Fax: +44 (0)20 8317 2400
Email: [email protected] Web Site: www.cliffordandsnell.com
Break Glass and Push Button Call Point Station Light Weight Glass Reinforced Polyester (GRP) Ex d Enclosure Dual 20mm gland entries, one fitted with approved stopping plug (2 * M20 holes located at the top of the Call Point. Glands supplied separately) Monitoring facility (DC only) Weather resistant high performance red paint finish as standard High intensity Red LED can be fitted as an optional extra to indicate
operation. Available up to 24Vdc Meets the requirements of BS EN 54-11 Break Glass version - Optional stainless steel Lift Flap Test Key provided as standard Push Button version - Push to operate - Reset Key provided. Protection Flap as standard Stainless steel fixings
TECHNICAL SPECIFICATION IP 66 rated Weight Approx. 1Kg Relative Humidity 95% @ 40 degC Cetified Temp 55C to +70C Voltage Up to 250V Switch Ratings DC 12 - 30V 5A (resitive) or 3A (Inductive) 30 - 50V 1A resitive or inductive AC 12 - 250V 5A resistive or inductive Suitable for Zones 1 & 2 Up to 4 cable entries. Top Entries 2 * as standard. Internal earth continuity provided as standard 7 way 2.5mm terminal block mounted on a PCB. Single Pole change over switch supplied as standard and fitted directly onto the 7 way connector.
MAIN FEATURES
Controlled document No.D7489-01-02 (CN100301) \\My Documents\SALES DATA\data
MOUNTING Via holes through the Back Box. See Installation Instructions.
Unit type APPROVAL SPECIFICATION
C l i f f o r d & S n e l l
DIMENSIONS (mm)
ATEX
Clifford & Snell a division of Signature Industries Ltd part of the Digital Angel Corporation
Manual Call Points Yodalex
Break Glass
Switches Single Pole
Double Pole
Additional Options (User to specify resistor & diode values)
Lift FLap End Of Line Resistor In line Resistor IN Line & EOL resistor
Push Button
CONFIGURATOR
Break Glass (BG)
Push Button (PB)
Explosion Proof
132.5 (5.2)
74 (2.9)
132.5 (5.2)
98 (3.9)
A B
C D
Duty Label (Customer to specify wording) Tag Label (Customer to specify wording)
LED
Labels
Entries 2 * M20 top entries A+Bstandard
(Suffix A = AC or D = DC. Example SPD = single pole dc switch)
(For other options select position of entries required and list
Finish Red (standard). (Other options upon application)
Standards for Manual Call Points European Standards (ATEX) EN60079-0:2006 & EN60079-1:2007 EN61241-0:2004 & EN61241-1:2004 Break Glass Baseefa08ATEX0269 Ex II2 GD Ex tD A21 (Tamb 55C to +70C) Push Button Baseefa08ATEX0269 Ex II2 GD EX tD A21 (Tamb 55C to +70C) International Standards (IECEx) IEC60079-0:2004 Edition 4 & IEC60079-1:2007 Edition 6 IEC61241-0:2004 Edition 1 & IEC61241-1: 2004 Edition 1 Break Glass IECEx BAS 08.0089 Ex II2 GD Ex tD A21 (Tamb 55C to +70C) Push Button IECEx BAS 08.0089 Ex II2 GD Ex tD A21 (Tamb 55C to +70C)