MBS Gateways 

MANUAL 

pico|nano|micro|XL|XXL|compact|maxi|19”

Version:06/05/2015

Page 2: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

Contents 

1. Foreword.............................................................................................................................................................................................1

2. References...........................................................................................................................................................................................2

2.1Registeredtrademarks.........................................................................................................................................................2

2.2Copyright....................................................................................................................................................................................2

3. MBS Gateway.....................................................................................................................................................................................3

3.1Typelabel...................................................................................................................................................................................3

3.2Numberofdatapoints..........................................................................................................................................................3

4. Commissioning..................................................................................................................................................................................4

4.1MS/TPorRS485networkinstallation...........................................................................................................................4

4.2Connectiontowebserver....................................................................................................................................................5

4.3..........................................................................................................................................................................................................6

4.4CallinguptheMBSGatewaywebserver.......................................................................................................................7

4.5Webbrowsersupport...........................................................................................................................................................7

4.5..........................................................................................................................................................................................................7

5. User interface and functions........................................................................................................................................................8

5.1Start...............................................................................................................................................................................................8

5.2Generalmenu–overview....................................................................................................................................................9

5.3Generalmenu–information............................................................................................................................................10

5.4Generalmenu–IPnetwork..............................................................................................................................................10

5.5Generalmenu–systemtime............................................................................................................................................11

5.6Generalmenu–dropbox....................................................................................................................................................12

5.7Generalmenu–webservices..........................................................................................................................................13

5.8Generalmenu–password.................................................................................................................................................13

5.9Generalmenu–databack‐up..........................................................................................................................................14

5.10Generalmenu–update....................................................................................................................................................14

5.10.1Requestingnewlicences.............................................................................................................................................15

5.10.2Upgradingnewlicences...............................................................................................................................................16

5.10.2Universalgatewaysoftwareupdate.......................................................................................................................16

5.11Generalmenu–restarting..............................................................................................................................................17

5.12Drivermenuitems.............................................................................................................................................................18

Page 3: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

5.13UGW‐Cdrivermenu...........................................................................................................................................................18

5.13.1Status....................................................................................................................................................................................19

5.13.2Settings................................................................................................................................................................................19

5.14LONTalkdrivermenu.......................................................................................................................................................20

5.14.1Status....................................................................................................................................................................................20

5.14.2Settings................................................................................................................................................................................20

5.14.3Datapoints.........................................................................................................................................................................21

5.14.4Configurationfiles..........................................................................................................................................................22

5.15BACnetdrivermenu..........................................................................................................................................................22

5.15.1Status....................................................................................................................................................................................22

5.15.2Settings................................................................................................................................................................................23

5.15.3BACnetdeviceobject.....................................................................................................................................................27

5.15.4BACnetobjects.................................................................................................................................................................28

5.15.5Configurationfiles..........................................................................................................................................................30

5.15.6EDEfile................................................................................................................................................................................30

5.16M‐Busdrivermenu............................................................................................................................................................31

5.16.1Status....................................................................................................................................................................................31

5.16.2M‐BUS|counterscan....................................................................................................................................................31

5.16.2.1Searchingusingaprimaryaddress.....................................................................................................................31

5.16.2.2Searchingusingasecondaryaddress................................................................................................................31

5.16.2.3Scanprocedure............................................................................................................................................................32

5.16.3Settings................................................................................................................................................................................36

5.16.4Configurationfiles..........................................................................................................................................................36

5.17Helpmenu.............................................................................................................................................................................37

5.18Helpmenu–diagnosis.....................................................................................................................................................37

5.19Helpmenu–diagnosis–deviceinfo..........................................................................................................................37

5.20Helpmenu–diagnosis–systemimage....................................................................................................................38

5.21Helpmenu–diagnosis–logfiles................................................................................................................................39

5.22Helpmenu–diagnosis–ping.......................................................................................................................................39

5.23Helpmenu–diagnosis–traceroute..........................................................................................................................40

5.24Helpmenu–diagnosis–processinformation......................................................................................................40

6. Protocol properties and data points........................................................................................................................................41

6.1Controlviaconfigurationdata.........................................................................................................................................41

Page 4: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

6.2Classificationofprotocols.................................................................................................................................................43

6.3Termdefinitionandpropertiesofdatapoints.........................................................................................................43

6.4Client‐serverrelationship,datapoints........................................................................................................................43

6.5Actualvalues–setvalues,datapoints.........................................................................................................................43

6.6Analogue–binary–multi‐level–morecomplextypes,datapoints..............................................................44

6.7Abstractdatapointindatapointsystem....................................................................................................................44

6.7Structuringtechnicaladdresses.....................................................................................................................................44

6.9Routingaddress.....................................................................................................................................................................44

6.10Datapointtypeaspartofaddress..............................................................................................................................45

6.11Datapointtypes..................................................................................................................................................................45

6.12Addressidentificationaspartofaddress................................................................................................................45

6.13Protocol‐specificaddresses...........................................................................................................................................45

6.14Mappingpossibilities........................................................................................................................................................45

7. Configuration...................................................................................................................................................................................47

7.1Datapointfiles.......................................................................................................................................................................47

7.2Configurationfiles................................................................................................................................................................47

7.3Schematicfile..........................................................................................................................................................................48

7.4StatusLED................................................................................................................................................................................48

7.5Typicaldatapointschemata............................................................................................................................................49

8. FAQs.....................................................................................................................................................................................................51

 

 

 

 

Page 5: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 1

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

1. Foreword 

Thank you for using an MBS Gateway. 

This manual describes the pico | nano | micro | XL | XXL | compact | maxi | 19” product family 

GATEWAY A gateway is used to enable communication between devices that use different communication protocols. Its 

typical  area  of  application  is  for  technical  building  service  equipment.  Communication  partners  are,  for 

example,  control  systems, DDC  systems,  control  systems  for  refrigeration  and  heat  power  stations,  room 

controller, safety equipment such as fire or burglar alarm systems,  lighting controls and others. For various 

reasons, these systems use different communication protocols. They differ  in speed, complexity, number of 

connectible devices, range and the type of information transmitted.  

 

SCHEMATIC DESIGN OF A GATEWAY (FUNCTIONS AND MODULES) 

 

Centraldispatcher

Specialdrivers,e.g.mathematicalconnections

Interfaceconfiguration

Driver,e.g.BACnetserver

Driver,e.g.profibus

Driver,e.g.counter

Page 6: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 2

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

2. References 

2.1 REGISTERED TRADEMARKS 

Trademarks and product names of various companies will be used in this book. The following names are the 

registered trademarks of their respective manufacturers and will not be mentioned separately in this book: 

Microsoft and Windows are registered trademarks of the Microsoft Corporation 

BACnet and ASHRAE are registered trademarks of the American Society of Heating, Refrigerating and Air‐

Conditioning Engineers, INC. (ASHRAE) 

Intel and Pentium are registered trademarks of the Intel Corporation 

BACstac is a registered trademark of Cimetrics, Inc. 

ARCnet is a registered trademark of the Datapoint Corporation 

IBM‐PC and IBM‐AT are registered trademarks of the International Business Machines Corporation (IBM) 

LONTalk is a registered trademark of Echelon, Inc. 

 

2.2 COPYRIGHT 

©2012MBS GmbH | Römerstraße 15 | D‐47809 Krefeld 

Telephone: +49 2151 72 940 

Fax: +49 2151 72 9450 

 

email: info@mbs‐software.de 

Internet: http://www.mbs‐software.de 

All rights reserved. It is not permissible to reproduce or, by using electronic systems, to edit, copy or otherwise 

disseminate this manual on any part thereof in any form whatsoever (print, photocopy or any other process) 

without prior written approval by MBS GmbH. 

 

Page 7: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 3

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

3. MBS Gateway 

3.1 TYPE LABEL     

The label contains the name of the gateway, the comprised protocols including the corresponding interface, 

project ID, MAC address, standard IP address, part number and serial number. 

 

3.2 NUMBER OF DATA POINTS 

The number of data points available is determined by the device type and licence. It counts the number of 

the different registered addresses in the dispatch.txt file with the keyword target =. 

Page 8: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 4

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

4. Commissioning 

To install the MBS Gateway, you will need the following tools: 

These instructions (included with delivery) 

Computer 

Installed web browser (a list of tested browsers can be found at the end of this chapter) 

Installed PDF reader  

Network cable 

The concept of the MBS Gateway configura on 

The MBS Gateway provides a conveniently built‐in web server that allows for easy configuration. This manual 

describes the steps required to access the web server. 

All documents necessary for further settings, including the user manual, can be found in the help directory of 

the web server. These can be viewed using the Adobe Acrobat Reader and printed on demand. 

Electrical installa on 

Connect the MBS Gateway to a power supply according to the technical specifications within this document. 

An  international  power  supply  is  optionally  available  if  required.  The warranty  becomes  void  if  the MBS 

Gateway is connected to an inadequate power supply or the casing is opened. There are no controls inside the 

casing. 

Ethernet network installa on 

Connect the Ethernet network cable (RJ‐45 connector) to the MBS Gateway. Use CAT5 UTP or STP cable (or 

equivalent). Avoid laying cables parallel to power lines, e.g. to motors, frequency inverters, etc. 

Do not connect to a network before the MBS Gateway has been fully configured. Use the network cable for 

configuration. 

 

4.1 MS/TP OR RS485 NETWORK INSTALLATION 

Connect the MS/TP or RS485 network to the orange plug. Observe the instructions for connecting MS/TP or 

RS485 networks according to 135‐2004 (BACnet standard). The MBS Gateway network will provide bias and 

termination resistors if necessary. 

 

 

 

 

 

Page 9: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 5

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

MS/TP – RS485 wiring  

 

 

 

4.2 CONNECTION TO WEB SERVER Overview 

An  IP connection between the computer and the MBS Gateway must be established  in order to access the 

internal web server. The web server provides the configuration settings in the form of websites. 

Ac va ng the DHCP server (op onal) 

On request, the DHCP (Dynamic Host Configuration Protocol) automatically provides IP addresses to clients. If 

your computer is set as a DHCP client (the default), you can use the DHCP server of the gateway to provide an 

IP address. Press and hold the gateway reset switch for at least 10 but not more than 15 seconds. When the 

status LED flashes green/red alternately, the DHCP server is enabled. Then connect the network cable to your 

computer, the IP address will be assigned automatically. 

Using a manual IP address 

If you plan to use an IP address manually, please set your PC to the following settings: 

IP address: 169.254.0.2 (or higher) 

Subnet mask: 255.255.0.0 

Standard gateway: Not entered 

 

 

Page 10: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 6

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

4.3CONNECTION CHECKThe standard IP address of the MBS Gateway is 169.254.0.1; to test the connection, use the ping command. 

Open a command prompt, and type in the following command:  

Ping 169.254.0.1 <ENTER>  

The MBS Gateway responds with an output of the time period:  

Reply from 169.254.0.1: Bytes=32 time<1ms TTL=64 

 

If there is no answer or an error is indicated in the connection, please check the network settings using the 

command: ipconfig / ALL <ENTER>  

This command displays the list of NICs and assigned IP configuration.  

 

 

Page 11: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 7

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

 

4.4 Calling up the MBS Gateway web server 

To access the configuration pages of the MBS Gateway web server,  launch your preferred web browser and 

type the IP address 169.254.0.1 into the address field. Then enter your username and password. 

Default setting on delivery: 

Username: gw 

Password: GATEWAY 

The password can be changed in the menu item Setup.  

 

4.5 Web browser support 

The  integrated web  server  has  been  tested with  various  browsers  and  operating  systems  and  has  been 

approved. If you have problems with your preferred browser, please notify MBS Support. Please indicate the 

exact browser version, the exact version of the operating system and a brief description of the problem for the 

diagnosis. 

 

4.5INTERFACE MAPPING FOR SERIAL INTERFACES Assigning gateway serial interfaces to device drivers. 

pico | nano | micro | XL | XXL S232 Terminal (1) 

Com1  4‐pole  RS232  /dev/ttyS3 

pico | nano | micro | XL | XXL RS485 Terminal (1) 

Com1 4‐pole  RS485  /dev/ttyS3 

compact  

Sub‐D (1) Com1  Com2 Com3 

9‐pole 

5‐pole 

3‐pole 

RS232  

RS232 

RS485 

/dev/ttyS1 

/dev/ttyS2 

/dev/ttyS3 

maxi  

Sub‐D (1)  Sub‐D (3)  

Com4  

Com5  

9‐pole 

9‐pole 

8‐pole 

8‐pole 

RS232 

RS232 

RS485 

RS485 

/dev/ttyS0 

/dev/ttyS2 

/dev/ttyS3 

/dev/ttyS4 

19” 

Sub‐D (1) Com1  

Sub‐D (2) Com2  

9‐pole 

9‐pole 

RS232 

RS232 

/dev/ttyS0 

/dev/ttyS1 

 

 

Page 12: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 8

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5. User interface and functions 

5.1 START It is necessary to login in order to access the MBS Gateway configuration via the web server.  

 

  

Please enter your username and password here and confirm by pressing Enter or clicking on the login button. Please pay attention to upper‐ and lower‐case letters. 

The default username is:  gw The default password is: GATEWAY 

When you have successfully logged in, you will see the MBS Gateway configuration software overview page. 

The upper menu bar is for the main navigation of the MBS Gateway configuration area. 

 

  

The menu items “General” and “Help” are always available. The remaining menu items are determined by the universal gateway drivers installed. The name of the MBS Gateway is also displayed. This can be changed. All MBS Gateway settings and functions can be found in the “General” menu. These are independent of the drivers installed. Documents and diagnosis functions can be accessed via the “Help” menu. 

The current username is displayed on the right. The meanings of the symbols are as follows: 

  To logout please press this key. 

 To display this manual in an individual browser window. You can switch to the manual and the MBS Gateway configuration at any time within your web browser. 

  Changing language 

 

Page 13: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 9

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.2 GENERAL MENU – OVERVIEW The first page displayed is the “Overview” page. 

 

 

 

Type:  The universal gateway type is displayed here. 

Name, installation 

location, description: 

This information is displayed to identify the universal gateway. They can be set for the individual MBS Gateway or a particular project. The name also appears in the upper menu area and is displayed for you to check when backing‐up data. 

Status LED:  This describes the current state of the status LED on the front of the universal gateway. 

System start:  Displays the last time the universal gateway was started. 

Data points:  Displays the number of data points used in relation to the licensed number of data points. 

CPU load:  Displays CPU load in %. This should not be greater than 50% in the long‐term. 

RAM:  Displays the size of the used and total RAM in Mbytes. Too little free space can lead to operational problems. 

Driver status:  The current status of a driver  is  listed depending on the  installed drivers.  If a driver is not online, this suggests a problem starting or with the configuration of a driver. Other information can be found using the diagnosis tools in the Help menu. 

 

Page 14: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 10

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.3 GENERAL MENU – INFORMATION Information for identifying the universal gateway is entered here. This can be set as chosen and created for a particular project. The information is saved on the universal gateway. 

 

 

This information is not required for operating the gateway, but serves solely for improved identification,

particularly when using several universal gateways in a project.

 

5.4 GENERAL MENU – IP NETWORK The current setting of the IP address appears. To alter this setting, change the relevant fields and save the settings. 

 

 

Page 15: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 11

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

The new IP addresses are activated upon saving. It is necessary to login again after the IP address has been changed. If IP network services with an IP name resolution are required, it is necessary to enter at least one IP name server. The secured HTTPS protocol can also be used to access the web server. To do this, enter “https://” before the IP address to activate the universal gateway configuration. 

 

If there are communication protocols installed on this gateway that operate via the network, please restart

the system afterwards. This is necessary because the drivers only assume the settings of such protocols when

starting the system.

For the precise IP settings, please ask the network administrator. If the IP network is not required for gateway

operation, leave the standard settings. This makes it easier to access the gateway later.

5.5 GENERAL MENU – SYSTEM TIME 

The universal gateway has a battery‐powered real‐time clock. Several protocols require the current time. The system time must therefore be synchronised. Automatic time synchronisation  is advisable. However, this  is not possible for every system. 

The network time protocol (NTP)  is a standard for synchronising clocks  in  internet protocol communication 

networks. 

 

The  time zone can be set  in order  to  localise  the system. Adjustments are made automatically  for daylight 

saving hours based on this time zone. The time display can be adjusted using the configuration software. A 

complete system restart is required to activate the settings. 

Time synchronisation via BACnet can only be used if the BACnet driver is installed and if there is a time

synchronisation master in the BACnet network. Please clarify this with the BACnet network coordinator.

Page 16: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 12

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

For time synchronisation via the NTP, it must be possible to access an NTP server from the IP network. Please

ask the system administrator. 

5.6 GENERAL MENU – DROPBOX The dropbox function can be activated optionally – please contact us or use the MBS web server to order this option. 

 

  

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 17: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 13

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.7 GENERAL MENU – WEB SERVICES The MBS Gateway offers web services, e.g. to read data point lists or change data points. These services can 

be activated or deactivated here. The configuration files for the data point lists can also be edited directly. 

 

 

5.8 GENERAL MENU – PASSWORD The password for the user “gw” can be changed here. For security purposes, it is necessary to enter the previous password and re‐enter the new password. 

 

 

 

 

Page 18: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 14

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.9 GENERAL MENU – DATA BACK‐UP The entire universal gateway configuration can be backed up. The back‐up consists of a zip file archive and is 

transmitted to your system’s web browser. 

 

This archive can then be exported at a later point in time. To do this, first select the archive on your computer. 

For  purposes  of monitoring,  the  archive  is  transmitted  to  the  gateway  and  the  content  displayed.  After 

confirmation, the data back‐up is unzipped and activated after restarting. 

 

It is only possible to export data back-ups that are intended for the universal gateway. It may only be possible

to export parts of faulty or defective data back-ups.

5.10 GENERAL MENU – UPDATE Here you can: 

Request a licence upgrade 

Conduct a licence upgrade 

Update the universal gateway system software 

Page 19: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 15

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.10.1 REQUESTING NEW LICENCES The current licence is displayed. When requesting a new universal gateway licence, the following options are 

offered: 

 

Press the email key to open your email program. The email will be automatically generated with the required 

information  from  your  selection  and  the universal  gateway,  and  the  address  “support@mbs‐software.de” 

entered as recipient. The email should not be altered and will only be sent when you click the send button in 

your email program. 

 

 

 

 

 

 

 

Page 20: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 16

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.10.2 UPGRADING NEW LICENCES You will receive a licence file from the manufacturer of the universal gateway. This licence file must be stored 

on your computer and must be selected to upgrade. The licence file is only valid for the device the request was 

sent from. The licence file cannot be transferred to other devices. 

 

The licence file is transmitted to the universal gateway and checked. The new licence is then updated. 

5.10.2 UNIVERSAL GATEWAY SOFTWARE UPDATE Software additions and fixes mean that  it  is sometimes necessary to update the universal gateway. You will 

receive an update file from the manufacturer. This must be stored on your computer and must be selected to 

update. Please only select files that you have received from the manufacturer for the update. 

 

 

Page 21: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 17

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.11 GENERAL MENU – RESTARTING After configuration changes, it is often necessary to restart the MBS Gateway communication software. This is 

displayed  in the upper menu bar. You can restart by clicking the Restart button  in the menu bar or clicking 

“General – Restart”  in  the menu selection. The current universal gateway configuration  is checked and  the 

result displayed. You can view the restart page by clicking “Continue”. 

 

 

 

 

Page 22: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 18

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

In the case of some system settings, a complete system restart is necessary. This is automatically selected when 

the dialogue box  is opened. A  simple  restart of  the  communication  software  takes approx. 10  seconds;  a 

complete restart takes approx. 1 minute. A restart for a software update may take up to 4 minutes. 

“Delete historical data” deletes all data collected, e.g. “historical BACnet Trendlog data”. This is necessary to 

conduct a smooth restart without collected test data during commissioning. 

A complete system restart and deleting the historical data is advisable after the gateway has been

completely configured. You should then check if everything has started properly. This ensures that the

gateway restarts properly even in the event of a power failure.

5.12 DRIVER MENU ITEMS 

Every  installed  communication  driver  is  listed  as  a  separate menu  item  in  the  upper menu  bar.  The  first 

submenu item always displays the current data point status for a driver. Some selected drivers also have their 

own submenu, using which special settings can be made for the communication driver. Each data point has a 

unique address and name, as well as a current time, flags and value. 

The meanings of the data point flags are as follows: 

Valid value V  

Sensor fault F  

Incorrect data point E  

Local operator value L  

Set value/actual value automatic mode ‐  

Locked, cannot be changed at the moment O  

Upper limit warning W  

Upper limit alarm A  

Upper range of values S 

Lower limit warning w  

Lower limit alarm a  

Lower value range s  

Historical value H  

Value has changed c  

Definition of new data point N  

Definition of deleted data point D  

Definition of changed data point C  

 

Time stamps and values speak for themselves. 

Some data points can be changed. These data points therefore have two values. The first value is the actual 

value. The second value is the set (nominal) value, i.e. the last value assigned to the driver. Use the key to open 

a dialogue box to adjust the new set value and send it to the driver as a command. 

5.13 UGW‐C DRIVER MENU 

This communication driver is found on every MBS Gateway. This driver’s data points provide information on 

the gateway’s internal system status. Like all other data points, these data points can be edited via data point 

mappings and mapped onto BACnet and/or LON objects, for example. 

 

 

 

Page 23: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 19

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.13.1 STATUS 

The current status of MBS Gateway data points are displayed and can be edited here. 

  

5.13.2 SETTINGS 

The following settings can be made for this driver: 

  

IgnoreFailure:  

There  are  “failure”  data  points  in  communication  with  communication  devices.  These  show  whether 

communication with a device is working (value 0) or if communication with the device is faulty (value 1). These 

data points are considered in the gateway status LED display. This can be switched off with this setting.

Page 24: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 20

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.14 LONTALK DRIVER MENU 

If the LONTalk driver is installed on the universal gateway, the LON menu is active. 

5.14.1 STATUS 

This page displays the current status of all LON data points. LON values can also be edited. These data points 

can be used for data point mapping. 

 

 

5.14.2 SETTINGS 

The following settings can be made for this driver: 

 

 

Page 25: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 21

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.14.3 DATA POINTS 

 

The LON data point configuration is displayed here. Data points for more categories can be displayed via the 

upper menu bar. “nivBindings” and “nvoBindigs” are the LON data points that can be used via the LON binding 

mechanism. This can be edited by clicking on the name. 

“Explicit Neuron‐ID” are the data points that can be polled regularly via the LON Neuron‐ID. The poll interval 

can be adjusted under “Settings”. 

 

“Explicit Subnet.Node” are the data points that can be polled regularly via the LON subnet and node entries. 

The poll interval can be adjusted under “Settings”. 

Page 26: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 22

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

 

5.14.4 CONFIGURATION FILES 

 

The entire LON configuration is saved in files. These can be transmitted here from and to the universal gateway. 

You can edit the file directly without transmitting the file using the “Edit” button. 

5.15 BACNET DRIVER MENU 

If the BACnet driver is installed on the universal gateway, the BACnet menu is active. 

5.15.1 STATUS 

This page displays the current status of all BACnet data points. BACnet values can also be edited. These data 

points can be used for data point mapping. 

 

Page 27: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 23

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.15.2 SETTINGS 

General settings for the BACnet driver and settings for the BACnet datalinks can be made here. 

 

 

Start delay:  A  start  delay  for  BACnet  failure  detection  can  be  set  here. When  restarting  the 

universal gateway, BACnet communication will only be switched on after this time has 

elapsed. This allows a remote station to recognise if the universal gateway has been 

restarted by  the  absence of BACnet  requests. The  setting  “0”  initiates  a  “BACnet‐

Restart‐Notification” report as a “Global Broadcast” and to the registered recipient. 

DCC/RD 

password: 

The BACnet services “Device‐Communication‐Control” and “Reinitialize Device” can 

be password protected. 

Datalinks  The BACnet datalinks to be used can be set here. The following are supported: BACnet 

IP and BACnet MS/TP. They can be activated simultaneously. 

BACnet PTP  In addition to “BACnet Datalinks”, communication can be activated via the BACnet half 

router “Point‐To‐Point”. This is necessary for BACnet operation with a modem. 

 

Page 28: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 24

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

BACnet IP: 

The following operating types are possible for BACnet IP connection: Normal, BACnet BBMD (BACnet Broadcast 

Management Device) and BACnet Foreign Device 

BACnet  BBMD  and  FD  configuration  is  necessary  for  operation  of  the  entire  IP  network. Ask  the  BACnet 

coordinator about the settings for your project. 

 

 

Page 29: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 25

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

BACnet MS/TP: 

BACnet MS/TP is a connection for BACnet devices via the RS485 (dual cable) interface. The necessary settings 

can be made here. Ask the BACnet coordinator about the settings for your project. 

 

 

 

 

Page 30: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 26

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

BACnet PTP: 

BACnet Point‐To‐Point is designed for communication via modem. BACnet PTP is a half‐router. Together with 

the  other  part  (dial‐up  part),  it  comprises  a  BACnet  router  for  a  complete  BACnet  network.  The  BACnet 

networks must be correspondingly configured. The network number serves to identify a BACnet network. This 

must be unique throughout the BACnet network. 

 

Connect timeout:  Timeout for the establishment of a modem connection. If no connection is established within this time, it counts as a connection attempt. There are maximum “APDU‐Retries” (connection attempts). 

IDLE timeout:  If no “relevant” data  is  transmitted within  this  time during a connection,  the connection  is terminated. 

Automatic dial‐up:  Determines which BACnet services are  the subject of a connection attempt. This  is a  list of “confirmed” and “unconfirmed” items with the BACnet enumeration of services. 

C2 – Confirmed Event Notification U3 – Unconfirmed Event Notification C15 – Confirmed Write Property (triggered via MBS Gateway) C16 – Confirmed Write Property Multiple (via MBS Gateway) 

Incoming password:  BACnet PTP password for dialling‐up the universal gateway. 

External networks:  The networks that can be accessed externally via BACnet PTP are configured here. The network number specifies the accessible BACnet network. Up to three telephone numbers under which the  BACnet  counterpart  station  can  be  reached  can  be  specified.  These  are  dialled consecutively  as  part  of  the  “Connect  timeout”.  The  password  is  used  to  login  to  the counterpart station. 

 

Page 31: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 27

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.15.3 BACNET DEVICE OBJECT 

The BACnet universal gateway device object has a specific role as regards  the other BACnet objects. APDU 

parameters for BACnet transmission are set here. The device instance and device name can also be set. These 

properties are for BACnet device identification and must be unique throughout the entire BACnet network. For 

more detailed settings, ask the BACnet coordinator. 

 

Page 32: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 28

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.15.4 BACNET OBJECTS 

The BACnet object configuration is displayed here. Data points can be filtered according to object type via the 

upper menu bar. 

 

 

 

The BACnet “Object name” and “Description” can be directly edited by clicking on them. The object‐specific 

properties can be called up and edited by clicking on the Properties button. By clicking on the Trend button, 

you can directly create a new trendlog object with this object as an input reference. 

 

 

 

Page 33: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 29

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

Example of BACnet binary value object: 

The dialogue box for editing a BACnet binary value object is shown here. The status of the values “0” and “1” 

can be changed. 

For this object type, BACnet allows a “change‐of‐state counter” to be activated. The object  is automatically 

extended to all object properties necessary for this purpose. This  includes the elapsed active timer. BACnet 

alarming is activated for this object with “intrinsic reporting”. The “time delay” property determines the report 

delay in seconds. All further information can be taken from the BACnet standard. 

 

 

 

Page 34: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 30

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.15.5 CONFIGURATION FILES 

 

The entire BACnet configuration is saved in files. These can be transmitted from and to the universal gateway. 

You can edit the file directly without transmitting the file using the “Edit” button. 

5.15.6 EDE FILE 

The BACnet objects and functions projected  in the gateway can be shared with other partner companies  in 

projects in the form of a specified Excel table. These EDE (engineering data exchange) files are automatically 

generated and can be accessed on the universal gateway. 

 

Page 35: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 31

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

 

5.16 M‐BUS DRIVER MENU 

If the M‐Bus driver is installed on the universal gateway, the M‐Bus menu is active. 

5.16.1 STATUS  

This page displays the current status of all M‐Bus counters and the corresponding data points. These data points 

can be used for data point mapping and for mapping BACnet objects. 

 

5.16.2 M‐BUS | COUNTER SCAN 

The MBS Gateway offers the option of an M‐Bus scan. This searches for M‐Bus counters on the bus. Using the 

identified counters, configuration files for the M‐Bus and BACnet objects are then automatically generated. 

There are two M‐Bus search options available. The identified counters are then polled in a later process as they 

were identified, i.e. a counter found in a primary address scan is also polled with the primary address. A counter 

in a secondary address scan is then polled via the secondary address. 

5.16.2.1 SEARCHING USING A PRIMARY ADDRESS 

In the M‐Bus, every counter can be given a unique primary address between 0 and 252. This must be set for 

every  counter  during  commissioning.  During  scanning,  the  addresses  in  the  specified  area  are  polled 

individually. The identified counters are then listed. Counters that answer are identified. 

Advantage of counter polling via primary address: 

Counter polling is faster. 

Changing counters simply involves resetting the same primary address for the counter (this is only true as 

long as the same counter is installed). 

5.16.2.2 SEARCHING USING A SECONDARY ADDRESS  

Each M‐Bus counter has a unique identification, comparable to the Ethernet MAC address. To communicate 

with a counter via this address, this identification must be selected using a special M‐Bus command. Only then 

is it possible to communicate with the counter. This must take place before any attempt to communicate with 

Page 36: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 32

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

the counter. Advantage of counter polling via secondary address: No configuration of addresses in the counters 

necessary.  

5.16.2.3 SCAN PROCEDURE  

There are four steps to the M‐Bus scan. 

1. Make scan settings and start scan 

2. Selection and designation of identified counters 

3. Selection of necessary data points for each counter 

4. Creation of M‐Bus configuration and BACnet objects for the MBS Gateway. Only in this step is the gateway 

configuration changed. 

You can switch between the various steps by clicking on the tabs. 

Step 1 – Scan se ngs 

You can set the scan mode and several other parameters for conducting the M‐Bus scan here. You can then 

start the scan. 

 

Contrary to many other communication buses, the M‐Bus is permitted to operate counters with different baud 

rates (transmission speeds). There is hence a selection of different Baud rates. The progress with the actual 

scan status is displayed in a dialogue box. 

Page 37: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 33

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

Step 2 – Selec on and designa on of iden fied counters 

When the scan ends, the scan results are displayed. The counter list is combined with a previous scan result. 

Counters  that  have  been  re‐identified  are  given  the  status  “OK”,  new  counters  “new”  and  non‐identified 

counters “‐”. 

The “Use” checkbox allows you to determine whether the counter is to be used on the universal gateway or no 

longer considered. You can remove a counter from the list or call up all the information on a particular counter. 

For the counter to be used further, it must be given a unique name. 

 

 

 

 

Page 38: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 34

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

Step 3 – Data point selec on 

Finally, the data points to be used for every ticked counter are polled. To improve recognition, the data point 

values and units from the previous scan are displayed. 

 

 

 

Under the “Data point status” tab there is a “Failure” data point. This indicates whether communication with 

the counter is successful or if there is an error. 

 

Page 39: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 35

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

Step 4 – Configura on 

The last step is to create the configuration files and add new counters. 

There is also the opportunity to map the M‐Bus data points as BACnet objects. This also creates and adds the 

BACnet object configuration. 

 

 

 

 

Page 40: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 36

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.16.3 SETTINGS 

The following settings can be made for the M‐Bus driver: 

 

 

 

5.16.4 CONFIGURATION FILES 

 

 

The entire M‐Bus configuration is saved in files. These can be transmitted from and to the universal gateway. 

You can edit the file directly without transmitting the file using the “Edit” button. 

 

 

Page 41: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 37

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.17 HELP MENU 

Information on the universal gateway is displayed here. 

Information on: 

Displays information on the manufacturer of the universal gateway. 

Online help:  You can view the Universal Gateway Manual as a PDF document here. You can search and even print the manual via the PDF viewer on your web browser. 

BACnet PICS:  The BACnet PICS  (protocol  implementation conformance statement) document  lists all supported BIBBs, object types, character sets and BACnet communication options.  

To display the file, your web browser must have a PDF viewer. This is usually standard. If you have any

questions, please contact your system administrator. 

5.18 HELP MENU – DIAGNOSIS 

Communication with connected systems often does not function immediately. The problem can be diagnosed 

using these tools. 

5.19 HELP MENU – DIAGNOSIS – DEVICE INFO 

Displays general information on the Gateway. 

 

Gateway type:  Manufacturer’s internal hardware designation. 

Protocol ID:  Manufacturer’s internal protocol ID. 

Version:  Universal gateway software version. 

System start:  Displays the last time the universal gateway was started. 

Data points:  Displays the number of data points used in relation to the licensed number of data points. 

RAM:  Displays the size of the used and total RAM in Mbytes. Too little free space can lead to operational problems. 

Operating system:  Operating system version. 

Page 42: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 38

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

 

5.20 HELP MENU – DIAGNOSIS – SYSTEM IMAGE 

 

  

All important information concerning the MBS Gateway is displayed under the System Image menu item. This 

gives you a compact overview of the system’s status and all installed and configured properties. This output is 

a snapshot at the time you activated the link. The output is not automatically updated. 

 

 

 

 

 

 

 

 

 

Page 43: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 39

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.21 HELP MENU – DIAGNOSIS – LOG FILES 

The  log  output  can  be  activated  for  every  communication  driver.  These  are  outputs  that  can  provide 

information on how the program is running and any communication problems. The historical log outputs can 

be viewed under “Display mapping”. “Start for 60 sec” provides the current log outputs within 60 seconds of 

pressing the button. This process can be ended by pressing “Stop” at any time. 

 

5.22 HELP MENU – DIAGNOSIS – PING 

The universal gateway IP connection can be checked via this menu item. The output presented after pressing 

the  start button provides  information on  the  accessibility of other network nodes. You must enter  the  IP 

address of the node you want to check in the field. 

 

Page 44: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 40

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

5.23 HELP MENU – DIAGNOSIS – TRACE ROUTE 

The universal gateway IP connection can be checked via this menu item. The output presented after pressing 

the start button provides  information on the network path to other network nodes. You must enter the  IP 

address of the node you want to check in the field. 

 

 

5.24 HELP MENU – DIAGNOSIS – PROCESS INFORMATION 

The  status  of  all  operating  system  processes  are  provided  here.  The  “Mem”  (memory  usage)  and  “CPU” 

(processor utilization) columns provide important information on the process status. 

 

Page 45: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 41

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

6. Protocol properties and data points 

This is a general description only and independent of the existing gateway. With a gateway, different systems 

(e.g. Ethernet, RS485, ...) are connected to the building automation system for data exchange. Since each bus 

system works with its own data formats (protocols) (e.g. BACnet, EIB, MS/TP ...), data conversion is performed 

within the gateway. In order to convert the input format to the output format, an internal intermediate format 

is used. This makes it possible to convert between any two or more formats. The internal intermediate format 

consists of individual data points that are to be regarded as the smallest amount of information. A data point 

classically consists of an address and a value.  

Example: Analogue actual value (measured value) and an address which makes measured value selectable.  

940.Y bac 34.AV 55 

 

Routing address 940 

Data point type Y  

Analogue value 

Address type bac 

BACnet address 34.AV 55 

In addition, there may be other properties, such as plain text or special identifiers, which can for example report 

that the measuring sensor is out of order. To facilitate data exchanges between different protocols, various data 

point  types  are  provided  in  the  gateway.  These  data  point  types meet  the  specific  requirements of  each 

protocol. 

6.1 CONTROL VIA CONFIGURATION DATA 

The configuration of the gateway occurs via text files. There  is one file per driver with protocol  information 

(e.g. baud rate) with the extension .cfg and a file containing the definition of data points with the extension 

.txt. The file named dispatch.txt contains the mappings of the data points of the protocols to each other. 

Examples of configuration files 

 

The files all have the same basic structure: there are so‐called sections (areas) that begin with a line containing 

a name in square brackets. The lines following belong to such a section up to the next section or to the end of 

the file. The lines following the section name have the structure Keyword = value. 

The files can also include blank and comment lines at any point – introduced by the # character. Upper and 

lower case are distinguished. 

Page 46: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 42

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

Example 4.1.1 Example of file format 1 

# Comment first line of file 

 # First data point 

 [address1] 

name = first sample data point 

further_properties = 7 

[address2] 

# Another comment 

name = second sample data point 

# Comment last line 

 

 

Comment line 

Begin Section with the address address1 

Key name with value of first sample data point 

Key further_properties with value 7 

Begin section with the address address2 

Example 4.1.2 Example of file format 2 

# Data point list 

[S 2000.BI 1] 

name = Failure Slave 1 

query = pe 

writecache = yes 

bac_polarity = 0 

bac_time_delay = 0 

bac_alarm_value = 1 

bac_notify_type = event 

bac_event_enable = (1,1,1) 

bac_inactive_text = available 

bac_active_text = error 

[Y 2000.AI 1001] 

name = Slave 1 Value 1 

query = pe 

writecache = yes 

bac_units = 95 

bac_cov_increment = 0 

bac_resolution = 0.1 

Comment line 

Begin section 1 

Key name with value of first sample data point 

 

 

 

 

 

 

Begin section with 2 

 

Key name with value of second sample data point 

 

 

 

Page 47: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 43

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

6.2 CLASSIFICATION OF PROTOCOLS 

Protocols can be classified according to several criteria. These properties must be considered part of using the 

gateway. 

Protocol proper es table 

Topology 

 

Point‐to‐point connection  

A  point‐to‐point  connection  is  the  connection between  two  communication  partners. Compared  to  a  connection  with  several participants,  the  protocol  can  be  simple,  since addressing different participants is not necessary. 

Bus  With  bus  systems,  multiple  participants  can access  a  transmission  medium  jointly.  The opportunity  to  connect  several  devices  is laborious: the devices must be uniquely defined, and access to the common transmission medium must be coordinated. 

Communication control 

 

MasterSlave   

PeerToPeer  

Transmission control  Event‐controlled   

Polled 

Transmission medium    

 

6.3 TERM DEFINITION AND PROPERTIES OF DATA POINTS 

Data points are differentiated according to different categories. The data points behave differently depending 

on their classification and must be treated differently according to the gateway configuration. 

6.4 CLIENT‐SERVER RELATIONSHIP, DATA POINTS 

In a client‐server  relationship, a  server  is available  to  connected clients. The  server accepts  requests  from 

clients, and then sends the requested data to the client. This  is similar with regards to the relation of data 

points to each other. 

Example: A field device controls an actuator with feedback. An automation station is intended to set the control 

variable and evaluate the feedback. The data points control values and feedback are within the field device, 

which is then the server. Through reading and writing, the automation station accesses these data points and 

is thus the client in this communication. Normally, all data points of a device are client as well as server data 

points. For some protocols, it can also happen that both client and server data points are in one device. 

6.5 ACTUAL VALUES – SET VALUES, DATA POINTS 

Actual values are values that are measured or calculated by the server, and the results are transferred to the 

client. Set values are values  that are meant  to affect  the behaviour of  the server through  the client.  In set 

values, another  important distinction  is whether the value  is transferred only by the client to the server, or 

whether the actual value of the set value must also be reported back to the client. Example: A typical example 

Page 48: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 44

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

of  an actual  value  is  the mapping of a  temperature  sensor. A  typical  set  value would be  a nominal  room 

temperature set value in a room controller. 

6.6 ANALOGUE – BINARY – MULTI‐LEVEL – MORE COMPLEX TYPES, DATA POINTS 

Data points also differ as to which values are allowed. 

We distinguish:  

Analogue values (e.g. temperature reading sensor)  

Binary values (e.g. relay output)  

Multi‐level values (e.g. status data point with the operating conditions: Normal operation, Off, Economy mode, Failure). 

In some protocols there are more, sometimes complex data points. 

Example: An example of this is utilization times. At times, such values can not or only indirectly be shown in 

the gateway. These include attributes that can detect whether data points contain a valid value. With set values, 

there is an automatic value, which causes the server to take over control of the data point itself.  

6.7 ABSTRACT DATA POINT IN DATA POINT SYSTEM 

For  the processing  and  forwarding of data points within  the  gateway,  information  that  is  exchanged by  a 

protocol is shown in a generalized internal data point within the gateway. The properties of these internal data 

points allow the mapping of the most commonly used data points in building automation. The linkage between 

different data points occurs via  these  internal data points. Due  to  the decoupled  internal data points,  it  is 

possible to simply add more protocols to the gateway without needing to change the complete configuration. 

Thus, the extension of the gateway system by adding another communication protocol in combination with all 

previously available protocols becomes possible. 

6.7 STRUCTURING TECHNICAL ADDRESSES 

Within the gateway, data points are identified on the basis of a unique technical address. A complete data point 

address consists of a routing address, a data point type character, an address type character and a protocol‐

specific address. 

Example: 

940.Y bac 34.AV 55 

 

Routing address 940 

Data point type Y analogue value 

Address type bac 

BACnet address 34.AV 55 

6.9 ROUTING ADDRESS 

With the routing address, called unit, the communication port of the gateway is selected. The routing address 

is defined for each communication port in the fabrication of the gateway. If a gateway has multiple connections 

of the same type, the unit typically increases by one. Example: If a gateway has FMS Profibus twice, the routing 

addresses are 250 and 251. 

Page 49: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 45

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

6.10 DATA POINT TYPE AS PART OF ADDRESS 

In order to be able to use the address to derive specified information concerning possible uses, the address 

may contain a code letter. With this, the direction of data flow and the type of values are determined. The four 

main types are briefly presented here. For special purposes, other types come into consideration, which will 

be explained when used. 

6.11 DATA POINT TYPES 

X analogue value that is transmitted from the communication partner to the gateway. 

Y analogue value that can be transmitted in both directions. 

M binary or multi‐level value that is transmitted from the communication partner to the gateway. 

S binary or multi‐level value that can be transmitted in both directions. 

A en on: There may be several meaningful ways to assign a data point type to a data point. The selected data 

point type must be used consistently. A frequent source of error in the configuration is to use the same data 

point for different data point types. 

6.12 ADDRESS IDENTIFICATION AS PART OF ADDRESS 

In order  to be able  to  correctly  interpret  the protocol‐specific part of  the address, an abbreviation of  the communication protocol is used. Examples:  

mod for MODBUS addresses 

pbfms for Profibus FMS addresses  

bac for BACnet addresses 

6.13 PROTOCOL‐SPECIFIC ADDRESSES 

The last part of the address is determined by the communication protocol.  

Example for data point addresses in the gateway system 

70.M eib 4/5 

 

Routing address 70 

Data point type M 

Address type eib 

EIB group address 4/5 

940.Y bac 34.AV 55 

 

Routing address 940 

Data point type Y analogue value 

Address type bac 

BACnet address 34.AV 55 

6.14 MAPPING POSSIBILITIES 

A mapping basically consists of a source data point and a target data point. Changes in the value of the source 

data point are transmitted to the target data point. This transfer can additionally be modified by configuration 

entries. The address of the source data point is entered as a section in the dispatch file. The address of the 

target data point is registered on another line under the keyword target =. 

Page 50: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 46

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

Example of a dispatch.txt 

# Mapping of 1 bit value from Profibus FMS on MODbus 

[250.M fms 22.2.4] 

target = 60.S mod 3 coil 4 

# Mapping of an analogue value from Profibus FMS on MODbus 

[250.X fms 23.4] 

target = 60.Y mod 7 holding 30 

Page 51: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 47

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

7. Configuration 

7.1 DATA POINT FILES 

Which data points are to be used and which properties these data points should have is determined in the data 

point file of each protocol. The file name is derived from a protocol‐specific part of the name, a serial number, 

which is numbered in the event of multiple connections for the same protocol, and the extension .txt.  

Example of a gateway with two EIB connections: eib1.txt and eib2.txt.  

The name of the protocol‐specific part is mentioned in the description of the designated protocol. The address 

of the data point serves as the section’s name. An abbreviation of the address is used. Since the routing address 

and the data point type have already been determined by the file, they are not indicated again. This means 

that the full address 60.X eib 2/3/5 is written in the data point list as X 2/3/5. 

The use of the following key words is standard: 

name  

Optionally, you can specify a plain text for the data point here. The text is usually only used for commentary purposes within the gateway.  In some protocols, e.g. BACnet, the text  is used  in  the  protocol.  This  is  especially mentioned  separately  each  time  in  the  protocol description.  

format  

Optionally, protocol‐related properties of the data point are described here which cannot be derived solely from the address. For example, it is common to transfer analogue values of many  protocols  using  a  scaling  factor.  This  scaling  factor must  then  be  specified  in  the configuration,  so  the  gateway  can  interpret  this  value  correctly.  The  available  data  are protocol‐dependent and are described in the respective chapters. 

writecache  

Optional, possible values YES or NO  (default). This parameter only has meaning  for those parameters whose value  is described by the gateway. If the option has the value YES, the gateway remembers a value during a failed entry and repeats  its entry attempt when, for example, the connection to the device has been restored.  If this option  is missing or your value is NO, the value is discarded after a failed entry. A scenario for a meaningful application of this option would be to make a binary fault visual via EIB. If the EIB bus is not connected to the gateway at the time of occurrence of the failure, the gateway naturally cannot report the failure. When the connection has been restored, the fault condition should generally at least be transmitted afterwards. A scenario where this behaviour is not desired would be the switching of room lighting. If at the time of the switching the EIB does not work, it is generally not desired that the switching takes place after the event (e.g. after several days). 

query  

Specifies how the data point should be picked up via the corresponding protocol. Except for a few exceptions, which are described separately, the value permanent, abbreviated as pe, is used here. This value is standard. 

Other options  For some protocols,  there are other options  that need  to be projected at  this point. The description can be found in each of the protocol chapters. 

 

7.2 CONFIGURATION FILES 

The file name is derived from a protocol‐specific part of the name, a serial number, which is numbered in the 

event of multiple connections for the same protocol, and the extension .cfg.  

Page 52: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 48

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

Example of a gateway with two EIB connec ons: 

eib1.cfg and eib2.cfg.  

The name of the protocol‐specific part is mentioned in the description of the designated protocol. 

General parameters for each connection are established in the configuration file for each connection. Typically, 

information such as baud rate, individual addresses or poll rates should be indicated. The content consists of a 

section with a protocol‐specific description and configuration entries. 

Example 5.1.  Modbus sample configura on file modslave1.cfg 

# Modbusconfiguation 

[MOD] 

baudrate = 9600 

mode = RS485 

# Individual slave address 

address = 12 

7.3 SCHEMATIC FILE 

In  this  file,  the  allocations between  the data points  are defined. With  the  keyword  value,  a  value  can be 

specified  to represent the source data point value which  is  to be  transmitted  to  the  target data point. The 

keyword threshold, depending on the data point type of the source data point, has two different meanings. If 

the source data point is an analogue value (data point type X or Y), then the specified value has the effect of a 

threshold, which means that only changes in value where the change is greater than the specified threshold 

are transferred. If the source data point is an integer value (M or S), the target data point is changed only when 

the value of the source data point is equal to the specified value. 

7.4 STATUS LED 

The gateway provides quick orientation of the current operational state via a three‐colour status LED. The LED 

has the colours green and red and as a mixed colour orange. During system  initialization, the LED  lights up 

orange. After the initialization, the status LED flashes green. 

Table: status LED during normal operation 

Colour code  Definition  Data point Green flashing  Normal state   Alternately orange/green flashing  Projected indicator  S LED info Alternately red/green flashing  Usually a failure parameter on defect  S LED warning 

Red flashing  All failure parameters on defect  S LED error Permanent red light  At least one driver does not start properly   

The data points determine the LED colour code with ascending priority. The warning and error parameters are 

set automatically by the gateway in accordance with the projected failure parameters. The info parameter is 

available for the normal dispatch mechanism and may be used for optical signalling of a collective defect, for 

example. 

 

Page 53: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 49

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

7.5 TYPICAL DATA POINT SCHEMATA 

This section shows schematically, how typical data point mappings are constructed. In the examples, pseudo 

addresses are used. 

Example of actual analogue value 

Entry in file protA.txt[X address1]name = outside temperature of 

protocol Aquery = pe

Entry in file protB.txt[Y parameter 16]name = outside temperature to 

protocol Bquery = pe

Entry in file dispatch.txt# Mapping of the outside 

temperature[110.X protA address1]target = 140.Y protB parameter 16

 

Example of actual binary value 

Entry in file protA.txt[M address7] name = pump failure of protocol 

Aquery = pe 

Entry in file protB.txt[S parameter 23]name = pump failure in protocol Bquery = pe 

Entry in file dispatch.txt# Mapping of pump failure[110.M protA address1]target = 140.S protB parameter 23 

 

Example of mul ‐level set value without feedback 

Entry in file protA.txt[M address8]name = operating status of 

protocol Aquery = pe 

Entry in file protB.txt[S parameter 29]name = operating status in 

protocol Bquery = pe 

Entry  in  file  dispatch.txt#  Mapping  of  pump  failure[110.M  protA  address8]target = 140.S protB parameter 29 

 

Example of mul ‐level set value with feedback 

Entry in file protA.txt[S address8]name = operating status of 

protocol Aquery = pe

Entry in file protB.txt[S parameter 29]name = operating status in 

protocol Bquery = pe

Entry  in  file  dispatch.txt# Mapping of the operational status[110.S  protA  address8]target = 140.S protB parameter 29[140.S  protB  parameter  29]target = 110.S protA address8

Page 54: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 50

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

Sample mapping of a two‐stage actual value (1 = day, 2 = night on two binary values.) 

Entry in file protA.txt[M address83]name = operating status of 

protocol Aquery = pe 

Entry in file protB.txt[S parameter 129]name = day mode in protocol Bquery = pe[S parameter 130]name = night mode in protocol Bquery = pe 

Entry in file dispatch.txt# Mapping of the operational status[110.S protA address83]threshold = 1value = 1target = 140.S protB parameter 129[110.S protA address83]threshold = 1value = 0target = 140.S protB parameter 130[110.S protA address83]threshold = 2value = 0target = 140.S protB parameter 129[110.S protA address83]threshold = 2value = 1target = 140.S protB parameter 130 

 

Example of projec ng MBus to BACnet  

File: bac1.txt

[Y 2000.AI 1001]name = Slave 1 Value 1query = pewritecache = yesbac_units = 95bac_cov_increment = 0bac_resolution = 0.1 

File: dispatch.txt# Slave 1 Value 1[60.X mbus P26 value 1]target = 940.Y bac 2000.AI 1001 

File: mbus1.txt[X P26 value 1]name = Slave 1 Value 1query = pe 

 

Page 55: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 51

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

8. FAQs 

Problem: You want to access MBS Gateway and do not know the IP address.  

Solution 1: 

If your computer  is set as a DHCP client (the default), you can use the DHCP server of the MBS Gateway to 

provide an IP address. Press and hold the compact reset switch for at least 10 but not more than 15 seconds. 

When the status LED  flashes green/red alternately, the DHCP server  is enabled. Then connect the network 

cable to your computer, the IP address will be assigned automatically. To access the configuration pages of the 

MBS Gateway web server,  launch your preferred web browser and type the IP address 169.254.0.1  into the 

address field. Then enter your username and password. Default setting on delivery: 

Username: gw Password: GATEWAY The password can be changed in the menu item Setup. The MBS Gateway home page is polled and displayed.  

Solution 2: (computer skills and an installed BACnet protocol required) 

When BACnet is installed on the gateway (see sticker on the casing of the device), it can be combined with the 

Wireshark program (freeware, available at: http://www.wireshark.org) to sniff the network traffic and to read 

out on the basis of the reports. Start by selecting the Wireshark program and choose Capture Options. Check 

the settings in the next window and press the Start button. The Capture window will appear. Set the filter to 

bacnet. Then start the MBS Gateway, and wait for the output shown in the picture. 

The IP is shown below:  

Source: 169.254.0.1 (in this example) 

Network protocol: BACnet  

Info: I–Am–Router‐To‐Network 

  

Problem: You do not know the password to log on to the web console. 

Page 56: MBS Gatewaysdownload.mbs-solutions.de/handbuecher/en/MBS_Gateways_Manual… · MBS Gateways – MANUAL 7 MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de

MBS Gateways – MANUAL 52

MBS GmbH | Römerstraße 15 | 47809 Krefeld | Tel. +49 21 51 72 94‐0 | info@mbs‐software.de 

 

Solution: In this case, you can only revert the MBS Gateway back to the factory settings.  

A en on: In this case, you will lose all se ngs and parametriza ons of the compact 

To set the MBS Gateway back to the default setting, press and hold the reset button for longer than 15 seconds. 

The status LED flashes orange, and after copying the factory configuration a restart will be made. 

Then the gateway should be reset to the default settings: 

IP address:169.254.0.1Username:gwPassword: GATEWAY 

Problem: RS485 connection problems 

Solution:  For  RS485  connections,  if  possible,  do  not  connect  the GND,  especially  not  between  switching 

cabinets with different GND potentials. 

Problem: RS485 A B wires reversed. 

Solution: With swapped A B data lines, a connection does not take place. The yellow LED lights up constantly.