Maytag Restrictor Bore Size

download Maytag Restrictor Bore Size

of 16

Transcript of Maytag Restrictor Bore Size

  • 7/28/2019 Maytag Restrictor Bore Size

    1/16

  • 7/28/2019 Maytag Restrictor Bore Size

    2/16

    2

    1. Regularly:

    a. Clean or replace the indoor air lter at thestart of each heating and cooling season,and when an accumulation of dust and dirtis visible on the air lter.

    b. Remove any leaves and grass clippingsfrom the coil in the outdoor unit, beingcareful not to damage the aluminum ns.

    c. Check for any obstruction, such as twigs,sticks, etc.

    d. Certain models have external panelsfabricated from a premium grade ofstainless steel designed to inhibit cor-rosion. For such units, if the unit islocated in a coastal region or other areasubjected to high concentrations of salt,then the unit should be hosed off afterstorms and monthly otherwise to maintain

    its new appearance.

    2. Before Each Cooling Season:

    If the furnace/air handler blower motor and theoutdoor unit fan motor(s) have oil tubes at themotor bearings, apply 10 drops of SAE No. 20motor oil to each oil tube.

    CAUTION:Do not over-oil, or oil motors notfactory-equipped with oil tubes. Thecompressor is hermetically sealedand does not require lubrication.

    3. Before Calling a Service Technician, BeCertain:

    a. The unit thermostat is properly setsee To Operate Your Air Conditionerfor Cooling and To Operate Your Furnacefor Heating.

    b. The unit disconnect fuses are in goodcondition, and the electrical power to theunit is turned on.

    1. GENERAL INFORMATIONRead the following instructions completely beforeperforming the installation.

    To Operate Your Furnace forHeating

    1. Set the thermostat system switch to HEATor AUTO and the thermostat fan switch toAUTO. (See Figure 1)

    2. Set the thermostat temperature to thedesired temperature level using the

    temperature selector. Please refer tothe separate users manual for completethermostat programming instructions. Thefurnace and indoor blower will cycle on andoff to maintain the indoor temperature atthe desired heating level.

    To Shut Off Your Air Conditioner

    Set the thermostat system switch to OFFand the thermostat fan switch to AUTO. (SeeFigure 1)

    The system will not operate, regardless of thethermostat temperature setting.

    To Operate the Indoor BlowerContinuously

    Set the thermostat fan switch to ON (SeeFigure 1)

    The indoor blower will start immediately, andwill run continually until the fan switch is resetto AUTO.

    The continuous indoor blower operation can beobtained with the thermostat system switch setin any position, including OFF.

    The continuous indoor blower operation istypically used to circulate the indoor air toequalize a temperature unbalance due to a sunload, cooking, or replace operation.

    To Maintain Your Air Conditioner

    CAUTION:Be certain the electrical power tothe outdoor unit and the furnace/ air handler is disconnected beforedoing the following recommendedmaintenance.

  • 7/28/2019 Maytag Restrictor Bore Size

    3/16

    3

    Condensing Unit Section Each condens-ing unit is shipped with a refrigerant chargeadequate to operate the outdoor section withan indoor matching coil or air handler, and 15feet of refrigeration line.

    NOTE: DO NOT USE ANY PORTION OFTHE CHARGE FOR PURGING OR LEAKTESTING.

    Matching coils and air handlers are shippedwith a small pressurized holding charge topressurize them to keep out contaminants. Torelease the pressure, carefully read the instal-lation instructions provided with the indoor coilor air handler.

    Liquid and Suction Lines Refrigerant gradecopper tubing should be used when installing thesystem. Refrigerant suction line tubing shouldbe fully insulated.

    Field Connections for Electrical PowerSupply All wiring must comply with currentrevisions of the National Electrical Code(ANSI/NFPA 70) and with applicable localcodes having jurisdiction. The minimum size ofelectrical conductors and circuit protection mustbe in compliance with information listed on theoutdoor unit data label.

    2. SAFETY CONSIDERATIONS

    Pressures within the System Split systemair conditioning equipment contains liquid andgaseous refrigerant under pressure. Installationand servicing of this equipment should be per-formed by qualied, trained personnel thoroughlyfamiliar with this type of equipment. Under nocircumstances should the Homeowner attemptto install and/or service the equipment.

    Labels, Tags, Precautions When workingwith this equipment, follow all precautions in theliterature, on tags, and on labels provided with

    the equipment. Read and thoroughly understandthe instructions provided with the equipmentprior to performing the installation and opera-tional checkout of the equipment.

    Brazing Operations Installation of equipmentmay require brazing operations. Safety codesmust be complied with. Safety equipment (e.g.;safety glasses, work gloves, re extinguisher,etc.) must be used when performing brazingoperations.

    WARNING:Ensure all electrical power to the unitis off prior to installing or servicingthe equipment. Failure to do so maycause personal injury or death.

    3. SITE PREPARATION

    Unpacking Equipment Remove the card-board carton and Users Manual from theequipment. Take care not to damage the tubingconnections when removing the carton.

    Inspect for Damage Inspect the equipmentfor damage prior to installing the equipment atthe job site. Ensure coil ns are straight and, ifnecessary, comb ns to remove attened andbent ns.

    Preferred Location of the Outdoor Unit at theJob Site Conduct a survey of the job site todetermine the optimum location for mountingthe outdoor unit. Overhead obstructions, poorlyventilated areas, and areas subject to accumula-tion of debris should be avoided. The outdoorunit should be installed no closer than 18 inchesfrom the outside walls of the facility and in anarea free from overhead obstructions to ensureunrestricted airow through the outdoor unit.

    Facility Prerequisites Electrical powermust be supplied to the equipment. Electricalpower supplied must be adequate for properoperation of the equipment. The system mustbe wired and provided with circuit protection inaccordance with local building codes and theNational Electrical Code.

    Minimum Circuit Ampacity Electrical wiringto the equipment must be compatible and incompliance with the minimum circuit ampacitylisted on the outdoor unit data label.

    Maximum Fuse/Circuit Breaker Size Circuitprotection for the outdoor unit must be compat-ible with the maximum fuse/circuit breaker sizelisted on the outdoor unit data label.

    4. INSTALLING THE OUTDOOR UNIT

    Slab Mount The site selected for a slab mountinstallation requires a stable foundation and one

  • 7/28/2019 Maytag Restrictor Bore Size

    4/16

    4

    not subject to erosion. The slab should be leveland anchored (if necessary) prior to placing theequipment on the slab.

    Cantilever Mount The cantilever mountshould be designed with adequate safety factorto support the weight of the equipment, and forloads subjected to the mount during operation.Installed equipment should be adequately se-cured to the cantilever mount and levelled priorto operation of the equipment.

    Roof Mount The method of mounting shouldbe designed so as not to overload roof structuresnor transmit noise to the interior of the structure.Refrigerant and electrical line should be routedthrough suitably waterproofed openings to pre-vent water leaking into the structure.

    5. INSTALLING THE INDOOR UNIT

    The indoor section should be installed beforeproceeding with routing of refrigerant piping.Consult the installation instructions of the indoorunit (i.e.: air handler, furnace, etc.) for detailsregarding installation.

    6. CONNECTING REFRIGERANTTUBING BETWEEN THE INDOORAND OUTDOOR UNIT

    General Once outdoor and indoor unit place-ment has been determined, route refrigeranttubing between the equipment in accordance withsound installation practices. Refrigerant tubingshould be routed in a manner that minimizes thelength of tubing and the number of bends in thetubing. Refrigerant tubing should be supportedin a manner that the tubing will not vibrate orabrade during system operation. Tubing shouldbe kept clean of foreign debris during installationand installation of a liquid line lter drier is rec-

    ommended if cleanliness or adequacy of systemevacuation is unknown or compromised. Everyeffort should be made by the installer to ensurethat the eld installed refrigerant containingcomponents of the system have been installedin accordance with these instructions and soundinstallation practices so as to insure reliablesystem operation and longevity. The maximumrecommended interconnecting refrigerant linelength is 75 feet, and the vertical elevation dif-

    ference between the indoor and outdoor sectionsshould not exceed 20 feet.

    Filter Dryer Installation A lter dryer isprovided with PS series models only and mustbe installed in the liquid line of the system. If theinstallation replaces a system with a lter dryeralready present in the liquid line, the lter dryermust be replaced with the one supplied with the

    unit. The lter dryer must be installed in strictaccordance with the manufacturers installationinstructions.

    For all other series models, installing a lterdryer is optional. However, it is good installationpractice to install a lter dryer when replacingthe evaporator and/or condenser of a system.When installing, the lter dryer must be installedin strict accordance with the manufacturersinstallation instructions.

    Optional Equipment Optional equipment(e.g.: liquid line solenoid valves, etc.) should beinstalled in strict accordance with the manufac-turers installation instructions.

    7. MAKING ELECTRICALCONNECTIONS

    WARNING:Turn off all electrical power at the maincircuit box before wiring electricalpower to the outdoor unit. Failure tocomply may cause severe personnelinjury or death.

    Wiring Diagram/Schematic A wiring dia-gram/schematic is located on the inside coverof the electrical box of the outdoor unit. Theinstaller should become familiar with the wiringdiagram/schematic before making any electricalconnections to the outdoor unit.

    Outdoor Unit Connections The outdoorunit requires both power and control circuitelectrical connections. Refer to the unit wiringdiagram/schematic for identication and locationof outdoor unit eld wiring interfaces.

    Control Circuit Wiring The outdoor unit isdesigned to operate from a 24 VAC Class ll controlcircuit. Control circuit wiring must comply with

  • 7/28/2019 Maytag Restrictor Bore Size

    5/16

    5

    the current provisions of the National ElectricalCode (ANSI/NFPA 70) and with applicable localcodes having jurisdiction.

    Thermostat Connections Thermostat con-nections should be made in accordance with theinstructions supplied with the thermostat, andwith the instructions supplied with the indoorequipment.

    Electrical Power Wiring Electrical powerwiring shall comply with the current provisionsof the National Electrical Code (ANSI/NFPA 70)and with applicable local codes having jurisdic-tion. Use of rain tight conduit is recommended.Electrical conductors shall have minimum circuitampacity in compliance with the outdoor unit rat-ing label. The facility shall employ electrical circuitprotection at a current rating no greater than thatindicated on the outdoor unit rating label.

    Disconnect Switch An electrically compatibledisconnect switch must be within line of sight ofthe outdoor unit. This switch shall be capable ofelectrically de-energizing the outdoor unit.

    Optional Equipment Optional equipmentrequiring connection to the power or controlcircuits must be wired in strict accordance withcurrent provisions of the National Electrical Code(ANSI/NFPA 70), with applicable local codes hav-ing jurisdiction, and the installation instructionsprovided with the equipment. Optional Equip-

    ment (e.g.: liquid line solenoid valves, hard startkits, low suction pressure cutout switch kit, highpressure cutout switch kit, refrigerant compres-sor crankcase heater, etc.) should be installedin strict accordance with the manufacturersinstallation instructions.

    8. STARTUP AND CHECKOUT

    WARNING:Ensure electrical power to the unit is offprior to performing the following steps.Failure to do so may cause personalinjury or death.

    Air Filters Ensure air lters are clean and inplace prior to operating the equipment.

    Thermostat Set the room thermostat functionswitch to OFF, fan switch to AUTO, and move

    temperature setpoint to its highest setting. Priorto applying electrical power to the outdoor unit,ensure that the unit has been properly andsecurely grounded, and that power supply con-nections have been made at both the facilitypower interface and outdoor unit.

    Outdoor Unit Ensure the outdoor coil andtop of the unit are free from obstructions and

    debris, and all equipment access/control panelsare in place.

    Using extreme caution, apply power to the unitand inspect the wiring for evidence of open,shorted, and/or improperly wired circuits.

    Functional Checkout:

    CAUTION:If equipped with a compressorcrankcase heater, wait 24 hours priorto performing a function checkout toallow for heating of the compressorcrankcase. Failure to comply mayresult in damage and could causepremature failure of the system.

    Indoor Blower Set the thermostat functionswitch to COOLING and the fan switch to ON.Verify that the indoor blower is operating andthat airow is not restricted. Set the fan switchback to AUTO.

    Positive Temperature Coefcient Resistor(PTCR) (select models) A PTCR is factoryinstalled and located on the control panel of theoutdoor unit. The PTCR is a soft start device foruse with reciprocating compressors. If a hardstart kit is needed on this model the soft start(PTCR) must be removed rst.

    Low-Pressure Switch A low-pressureswitch is factory-installed in select models only.If provided, this switch is located in the suctionline internal to the outdoor unit. The switch isdesigned to protect the compressor from a lossof charge. Under normal conditions, the switch isclosed. If the suction pressure falls below 5 psig,then the switch will open and de-energize theoutdoor unit. The switch will close again once thesuction pressure increases above 20 psig.

  • 7/28/2019 Maytag Restrictor Bore Size

    6/16

    6

    Comfort Alert TM Diagnostics (Select Models) The Comfort Alert TM diagnostics is a break-through innovation for troubleshooting heatpump and air conditioning system failures. Themodule installs easily in the electrical box ofthe outdoor unit near the compressor contac-tor. By monitoring and analyzing data from theCopeland Scroll compressor and the thermostatdemand, the module can accurately detect the

    cause of electrical and system related failureswithout any sensors. A ashing LED indicatorcommunicates the ALERT code and guides theservice technician more quickly and accuratelyto the root cause of a problem.

    NOTE: This module does not provide safetyprotection! The Comfort Alert module is amonitoring device and cannot shut down thecompressor directly.

    LED Description (See Figure 2)

    POWER LED (Green): indicates voltage is pres-ent at the power connection of the module.

    ALERT LED (Yellow): communicates anabnormal system condition through a uniqueash code. The ALERT LED will ash a numberof times consecutively, pause and then repeatthe process. The number of consecutiveashes, dened as the Flash Code, correlatesto a particular abnormal condition. Detaileddescriptions of specic ALERT Flash Codes areshown in Table 1 of this manual.

    TRIP LED (Red): indicates there is a demandsignal from the thermostat but no current to thecompressor is detected by the module. The TRIPLED typically indicates the compressor protectoris open or may indicate missing supply powerto the compressor.

    The scroll compressors run (R), common (C) andstart (S) wires are routed through the holes in the

    Comfort AlertTM

    module marked R, C and S.The common (C) wire need not be routed throughthe module for it to operate properly.

    24 VAC Power Wiring The Comfort Alert TM module requires a constant nominal 24 VACpower supply. The wiring to the modules R andC terminals must be directly from the indoor unitor thermostat. The module cannot be powered bythe C terminal on a defrost board or other controlboard without experiencing nuisance alerts.

    Figure 2. Comfort Alert TM Diagnostics Module

    Figure 3. 24VAC Comfort Alert TM Wiring Diagram

    24 Volt FieldConnections

    LPS

    CC

    C R Y

    C

    R

    Y

    Comfort AlertL

    L

  • 7/28/2019 Maytag Restrictor Bore Size

    7/16

    7

    NOTE: Factory installed modules may havedifferent thermostat demand signal wiring,follow manufacturers wiring installationswhen replacing module.

    NOTE: After the thermostat demand signal isconnected, verify Y is phased properly withC by measuring 24 VAC across Y and C whendemand is present.

    TROUBLESHOOTINGInterpreting The Diagnostic LEDs When anabnormal system condition occurs, the ComfortAlert TM module displays the appropriate ALERTand/or TRIP LED. The yellow alert LED will asha number of times consecutively, pause andthen repeat the process. To identify a FlashCode number, count the number of consecutiveashes. Every time the module powers up, thelast ALERT Flash Code that occurred prior toshut down is displayed for one minute.

    Cooling Gradually lower the thermostattemperature setpoint below the actual roomtemperature and observe that the outdoor unitand indoor blower energize. Feel the air beingcirculated by the indoor blower and verify thatit is cooler than ambient temperature. Listenfor any unusual noises. If present, locate anddetermine the source of the noise and correctas necessary.

    Heating If provided with heating equipment,lower the thermostat setpoint temperature to thelowest obtainable setting and set the thermostatfunction switch to HEATING. The indoor blowerand outdoor unit should stop running. Increasethe setpoint temperature of the thermostat tothe maximum setting. Verify that the heatingequipment has been energized (i.e., fossil fuelburner operating, etc.) and that the indoor blowerenergizes after a short period of time. Feel theair being circulated by the indoor blower andverify that it is warmer than ambient temperature.Listen for any unusual noises. If present, locateand determine the source of the noise and cor-rect as necessary.

    NOTE: Other sources for heating (i.e.: electricfurnace, fossil fuel furnace, air handler withelectric heat options, etc.) that interface withthe unit should be functionally checked to verify

    system operation and compatibility. Refer to theinstallation instructions for this equipment andperform a functional checkout in accordancewith the manufacturers instructions.

    Adjustment of Refrigerant Charge:

    CAUTION:Split system air conditioner equipmentcontains liquid and gaseous refrigerantunder pressure. Adjustment ofrefrigerant charge should only beattempted by qualified, trainedpersonnel thoroughly familiar with theequipment. Under no circumstancesshould the homeowner attempt toinstall and/or service this equipment.Failure to comply with this warningcould result in equipment damage,personal injury, or death.

    NOTE: The following Refrigerant ChargingCharts are applicable to matched assembliesof our equipment and at listed airows for theindoor coil. Assemblies of indoor coils andoutdoor units not listed are not recommendedand deviations from rated airows or non-listedequipment combinations may require modica-tions to the expansion device(s) and refrigerantcharging procedures for proper and efcientsystem operation.

    Refrigerant Charging Chart Refer toRefrigerant Charging Charts for correct systemcharging, and to Orice Usage Chart for correctrestrictor sizes.

    NOTE: Linesets over 15 feet in length mayrequire additional refrigerant charge. NORDYNErecommends 0.6 oz. of refrigerant per foot forany lineset over 15 feet.

    Optional Equipment A functional checkoutshould be performed in accordance with thecheckout procedures supplied with the equip-ment.

  • 7/28/2019 Maytag Restrictor Bore Size

    8/16

    8Table 1. Interpreting the Diagnostic LEDS

    Status LED Status LED Description Status LED Troubleshooting InformationGreen POWER Module has power Supply voltage is present at module terminals

    Red TRIP Thermostat demand signal 1. Compressor protector is openY is present, but the 2. Outdoor unit power disconnect is opencompressor is not 3. Compressor circuit breaker or fuse(s) is openrunning 4. Broken wire or connector is not making contact

    5. Low pressure switch open if present in system6. Compressor contactor has failed open

    Yellow ALERT Long Run Time 1. Low refrigerant chargeFlash Code 1 Compressor is 2. Evaporator blower is not running

    running extremely 3. Evaporator coil is frozenlong run cycles 4. Faulty metering device

    5. Condenser coil is dirty6. Liquid line restriction (filter drier blocked if present in system)7. Thermostat is malfunctioning8. Comfort Alert Failure9. Comfort Alert Failure

    Yellow ALERT System Pressure Trip 1. High head pressureFlash Code 2 Discharge or suction 2. Condenser coil poor air circulation (dirty, blocked, damaged)

    pressure out of limits or 3. Condenser fan is not runningcompressor overloaded 4. Return air duct has substantial leakage

    5. If low pressure switch present in system, check FlashCode 1 information

    Yellow ALERT Short Cycling 1. Thermostat demand signal is intermittentFlash Code 3 Compressor is running 2. Time delay relay or control board defective

    only briefly 3. If high pressure switch present go to Flash Code 2 information4. If low pressure switch present go to Flash Code 1 information

    Yellow ALERT Locked Rotor 1. Run capacitor has failedFlash Code 4 2. Low line voltage (contact utility if voltage at disconnect is low)

    Check wiring connections3. Excessive liquid refrigerant in compressor4. Compressor bearings are seized

    Measure compressor oil level

    Yellow ALERT Open Circuit 1. Outdoor unit power disconnect is openFlash Code 5 2. Compressor circuit breaker or fuse(s) is open

    3. Compressor contactor has failed open Check compressor contactor wiring and connectors Check for compressor contactor failure (burned, pitted or

    open) Check wiring and connectors between supply and

    compressor

    Check for low pilot voltage at compressor contactor coil4. High pressure switch is open and requires manual reset5. Open circuit in compressor supply wiring or connections6. Unusually long compressor protector reset time due to

    extreme ambient temperature7. Compressor windings are damaged

    Check compressor motor winding resistance

    Yellow ALERT Open Start Circuit 1. Run capacitor has failedFlash Code 6 Current only in run circuit 2. Open circuit in compressor start wiring or connections

    Check wiring and connectors between supply and thecompressor S terminal

    3. Compressor start winding is damaged Check compressor motor winding resistance

    Yellow ALERT Open Run Circuit 1. Open circuit in compressor run wiring or connectionsFlash Code 7 Current only in start circuit Check wiring and connectors between supply and the

    compressor R terminal2. Compressor run winding is damaged

    Check compressor motor winding resistance

    Yellow ALERT Welded Contactor 1. Compressor contactor has failed closedFlash Code 8 Compressor always runs 2. Thermostat demand signal not connected to module

    Yellow ALERT Low Voltage 1. Control circuit transformer is overloadedFlash Code 9 Control circuit < 17VAC 2. Low line voltage (contact utility if voltage at disconnect is low)

    Check wiring connections

    Flash Code number corresponds to a number of LED flashes, followed by a pause and then repeated. TRIP and ALERT LEDs flashing at same time means control circuit voltage is too low for operation.

  • 7/28/2019 Maytag Restrictor Bore Size

    9/16

    9

    Table 2. Module Wiring Troubleshooting

    Miswired Module Indication Recommended Troubleshooting Action

    Green LED is not on, Determine if both R and C module terminals aremodule does not power up connected. Verify voltage is present at modules R and

    C terminals. Review 24VAC Power W iring (page 4) forR and C wiring.

    Green LED intermittent, Determine if R and Y terminals are wired in reverse.module powers up only Verify modules R and C terminals have a constantwhen compressor runs source. Review 24VAC Power W iring (page 4) for R

    and C wiring.

    TRIP LED is on but system Verify Y terminal is connected to 24VAC at contactorand compressor check OK coil. Verify voltage at contactor coil falls below 0.5VAC

    when off.

    TRIP LED and ALERT LED Verify R and C terminals are supplied with 19-28VAC.flashing together

    ALERT Flash Code 3 Verify Y terminal is connected to 24VAC at contactor coil.(Compressor Short Cycling) Verify voltage at contactor coil falls below 0.5VAC whendisplayed incorrectly off.

    ALERT Flash Code 5, 6 or 7 Check that compressor run and start wires are through(Open Circuit, Open Start Circuit modules current sensing holes. Verify Y terminal isor Open Run Circuit) displayed connected to 24VAC at contactor coil. Verify voltage atincorrectly contactor coil falls below 0.5VAC when off.

    ALERT Flash Code 6 (Open Check that compressor run and start wires are routedStart Circuit) displayed for Code 7 through the correct module sensing holes.(Open Run Circuit) or vice versa

    ALERT Flash Code 8 Determine if modules Y terminal is connected. Verify Y(Welded Contactor) terminal is connected to 24VAC at contactor coil. Verifydisplayed incorrectly 24VAC is present across Y and C when thermostat demand

    signal is present. If not, R and C are reverse wired. V erifyvoltage at contactor coil falls below 0.5VAC when off.

    Refrigerant Metering Devicefor 13 SEER Split System Air Conditioner

    ModelNumber

    Restrictor BoreSize (inches)

    System ChargeR-22 (oz.)

    1.5 ton 0.053 782.0 ton 0.060 94

    2.5 ton 0.065 99

    3.0 ton 0.075 110

    3.5 ton 0.078 122

    4.0 ton 0.089 126

    5.0 ton 0.099 160

  • 7/28/2019 Maytag Restrictor Bore Size

    10/16

  • 7/28/2019 Maytag Restrictor Bore Size

    11/16

    11

    Restrictor Refrigerant Charging Charts

    2.5 OUTDOOR TEMPERATURE (F)TON 70 75 80 85 90 95 100 105Suct.

    Press.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.72 159 13474 161 139 175 13876 163 144 178 143 192 143

    78 166 149 180 148 194 147 208 14780 169 152 182 153 196 152 211 152 225 15182 186 156 199 156 213 156 227 156 242 15684 203 160 216 160 229 160 244 160 258 16086 219 164 232 164 246 164 260 164 274 16488 223 167 236 168 249 168 262 168 276 16790 239 172 252 172 266 172 278 17192 256 176 269 176 282 17694 273 181 286 18096 289 18598

    3 OUTDOOR TEMPERATURE (F)TON 70 75 80 85 90 95 100 105Suct.

    Press.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.74 156 13976 158 145 172 14378 161 150 175 148 189 14780 163 154 177 153 191 151 205 15082 167 157 180 157 193 156 207 155 221 15484 183 160 196 160 209 159 223 158 237 15786 200 163 212 163 225 162 239 161 253 16088 216 167 229 166 241 165 256 164 270 16390 219 170 232 170 245 169 258 168 272 16792 235 174 248 173 261 173 274 17194 252 178 265 177 277 17696 268 181 281 180

    98 284 185100

    3.5 OUTDOOR TEMPERATURE (F)TON 70 75 80 85 90 95 100 105Suct.

    Press.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.73 174 13875 176 143 186 14277 178 149 188 147 198 14679 181 153 190 152 200 151 210 150

    81 185 156 193 156 202 156 212 155 222 15483 197 159 205 160 214 159 224 158 234 15885 209 163 217 163 226 163 236 162 246 16287 221 167 229 167 238 166 248 166 258 16589 224 170 233 171 242 170 250 170 260 16991 236 174 245 174 254 174 262 17393 248 178 257 178 266 17795 260 182 269 18297 272 18699

  • 7/28/2019 Maytag Restrictor Bore Size

    12/16

    12

    Restrictor Refrigerant Charging Charts

    4 OUTDOOR TEMPERATURE (F)TON 70 75 80 85 90 95 100 105Suct.

    Press.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.72 150 12574 153 130 167 13176 155 135 169 136 184 138

    78 155 144 171 141 186 143 200 14480 159 147 172 148 188 148 202 149 217 15182 176 151 190 153 204 154 219 155 233 15784 193 156 207 158 221 159 235 161 249 16286 210 162 224 164 237 165 251 166 266 16888 213 165 227 167 241 169 253 170 268 17290 230 171 244 173 257 175 270 17692 247 177 261 179 274 18194 264 183 278 18596 281 19098

    5 OUTDOOR TEMPERATURE (F)TON 70 75 80 85 90 95 100 105Suct.

    Press.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.Liq.

    Press.Dis.

    Temp.68 149 14170 151 146 166 14672 154 151 168 151 183 15174 154 160 171 156 185 156 200 15676 158 163 172 163 187 161 202 160 217 16078 175 166 189 166 204 165 219 165 234 16580 193 169 207 170 221 169 236 169 251 16982 210 173 224 173 238 173 253 173 267 17384 213 177 227 177 241 177 255 177 269 17786 231 181 245 181 259 181 271 18088 248 185 262 186 276 18590 265 190 279 190

    92 283 19494

  • 7/28/2019 Maytag Restrictor Bore Size

    13/16

    13

    TXV Refrigerant Charging Charts

    1.5 Ton AC TXV Charging Chart

    2.0 Ton AC TXV Charging Chart

    140

    160

    180

    200

    220

    240

    260

    280

    300

    320

    340

    360

    380

    400

    75 80 85 90 95 100 105 110 115 120 125 130 135

    Liquid Temperature (F)

    L i q u

    i d P r e s s u r e

    ( p s

    i g )

    Add refrigerant when below curve

    Remove refrigerant when above curve

    140

    160

    180

    200

    220

    240

    260

    280

    300

    320

    340

    360

    380

    400

    75 80 85 90 95 100 105 110 115 120 125 130 135

    Liquid Temperature (F)

    L i q u

    i d P r e s s u r e

    ( p s

    i g )

    Add refrigerant when below curve

    Remove refrigerant when above curve

  • 7/28/2019 Maytag Restrictor Bore Size

    14/16

    14

    TXV Refrigerant Charging Charts

    140

    160

    180

    200

    220

    240

    260

    280

    300

    320

    340

    360

    380

    400

    75 80 85 90 95 100 105 110 115 120 125 130 135

    Liquid Temperature (F)

    L i q u

    i d P r e s s u r e

    ( p s

    i g )

    Add refrigerant when below curve

    Remove refrigerant when above curve

    2.5 Ton AC TXV Charging Chart

    3.0 Ton AC TXV Charging Chart

    140

    160

    180

    200

    220

    240

    260

    280

    300

    320

    340

    360

    380

    400

    75 80 85 90 95 100 105 110 115 120 125 130 135

    Liquid Temperature (F)

    L

    i q u

    i d P r e s s u r e

    ( p s

    i g )

    Add refrigerant when below curve

    Remove refrigerant when above curve

  • 7/28/2019 Maytag Restrictor Bore Size

    15/16

    15

    3.5 Ton AC TXV Charging Chart

    140

    160

    180

    200

    220

    240

    260

    280

    300

    320

    340

    360

    380

    400

    75 80 85 90 95 100 105 110 115 120 125 130 135

    Liquid Temperature (F)

    L i q u

    i d P r e s s u r e

    ( p s

    i g )

    Add refrigerant when below curve

    Remove refrigerant when above curve

    TXV Refrigerant Charging Charts

    4.0 Ton AC TXV Charging Chart

    140

    160

    180

    200

    220

    240

    260

    280

    300

    320

    340

    360

    380

    400

    75 80 85 90 95 100 105 110 115 120 125 130 135

    Liquid Temperature (F)

    L

    i q u

    i d P r e s s u r e

    ( p s

    i g )

    Add refrigerant when below curve

    Remove refrigerant when above curve

  • 7/28/2019 Maytag Restrictor Bore Size

    16/16

    140

    160180

    200

    220

    240

    260

    280

    300

    320

    340

    360

    380

    400

    75 80 85 90 95 100 105 110 115 120 125 130 135

    Liquid Temperature (F)

    L i q u

    i d P r e s s u r e

    ( p s

    i g )

    5.0 Ton AC TXV Charging Chart

    TXV Refrigerant Charging Charts

    INSTALLER: PLEASE LEAVETHESE INSTALLATION INSTRUCTIONS

    WITH THE HOMEOWNER.

    7085600 Specications and illustrations subject to change

    without notice and without incurring obligations.Printed in U.S.A. (06/06)708560&