Duct burners - APX® Burner 4 - 21.9 - 7E - i - 5/08
Specifications of APX® burners
APX® Burner - STRAIGHT - packaged blower [1]
[1] Not for EC-market - see “Available APX® versions and options” page 4-21.9-12 and page 4-21.9-13.[2] Burner data displayed assume blower(s) operating on 60 Hz electrical supply. Max. burner capacity will be reduced by 17 % if operated on
50 Hz. Fuel and air pressure should be reduced by 30 % while motor power will reduce 40 % with 50 Hz operation.[3] sg (specific gravity) = relative density to air (density air = 0.0763 lbs/ft³(st).[4] Burner size corresponds with the straight burner length in ft.[5] Pressure differential between burner test connection and combustion chamber for natural gas to be used for burner commissioning -
LP burner (Low Pressure drillings). Actual pressure differential at burner gas inlet is 5 % higher.[6] Fresh air firing. When firing in low oxygen environment, max. capacity should be downrated.[7] Differential combustion air pressure between burner air test connection and combustion chamber for commissioning.[8] When firing in balanced combustion chamber.[9] Expected flame length in fresh air firing. Flame length may vary in function of process air flow distribution, velocity, temperature, oxygen level
etc. Contact MAXON for more information.
Typical burner data [2]Fuel: natural gas with 1000 Btu/ft³ HHV - sg = 0.6 [3]
Combustion air: 60° F - 21 % O2 - 50 % humidity - sg = 1.0 [3]
Stated pressures are indicative. Actual pressures are a function of air humidity, altitude, type of fuel and gas quality.
Burnersize [4]
Differentialgas pressure
Standarddrilling [5]
“wc
Differentialgas pressurelow pressure
drilling [5]“wc
Maximumcapacity [6]
Btu/h
Differentialair pressure
[7]
“wc
Nominalair flow [8]
scfm
Min.Capacity
Btu/h
Flame length [9]
in
Blowerhorsepower
hp
Numberof
blowers
0.5 5.5 400,000 1.5 80 12,500 30-40 1/12 1
1 16.5 9 1,000,000 4 172 25,000 30-40 0.5 1
1.5 16.5 9 1,500,000 4 260 37,500 30-40 0.5 1
2 16.5 9 2,000,000 4 345 50,000 30-40 1 1
2.5 16.5 9 2,500,000 4 430 62,500 30-40 1 1
3 16.5 9 3,000,000 4 510 75,000 30-40 1 1
3.5 16.5 9 3,500,000 4 600 87,500 30-40 1.5 1
4 16.5 9 4,000,000 4 690 100,000 30-40 1.5 1
5 16.5 9 5,000,000 4 860 125,000 30-40 3 1
6 16.5 9 6,000,000 4 1030 150,000 30-40 1 2
7 16.5 9 7,000,000 4 1200 175,000 30-40 1.5 2
8 16.5 9 8,000,000 4 1380 200,000 30-40 1.5 2
9 16.5 9 9,000,000 4 1550 225,000 30-40 3 2
10 16.5 9 10,000,000 4 1720 250,000 30-40 3 2
11 16.5 9 11,000,000 4 1900 275,000 30-40 3 2
12 16.5 9 12,000,000 4 2060 300,000 30-40 3 3
13 16.5 9 13,000,000 4 2240 325,000 30-40 3 3
14 16.5 9 14,000,000 4 2400 350,000 30-40 3 3
15 16.5 9 15,000,000 4 2600 375,000 30-40 3 3
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 8E- i - 5/08 Duct Burners - APX® Burner
APX® burner - H - external blower conversion table to corresponding straight lengths of burner in feet
Example:APX® 2 x 2.5 H corresponds with 6.5 ft straight burner length.
Use table page 4-21.9-7 and page 4-21.9-8 for typical burner data per foot of burner.
Burner size Burner dimension(ft)
Corresponding straight length
(ft)
APX 1 x 1 H 1 x 1 3
APX 1 x 1.5 H 1 x 1.5 3.5
APX 1 x 2 H 1 x 2 4
APX 1 x 2.5 H 1 x 2.5 4.5
APX 2 x 1 H 2 x 1 5
APX 2 x 1.5 H 2 x 1.5 5.5
APX 2 x 2 H 2 x 2 6
APX 2 x 2.5 H 2 x 2.5 6.5
APX 3 x 1 H 3 x 1 7
APX 3 x 1.5 H 3 x 1.5 7.5
APX 3 x 2 H 3 x 2 8
APX 3 x 2.5 H 3 x 2.5 8.5
APX 3 x 3.5 H 3 x 3.5 9.5
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 9E - i - 5/08
APX® burner firing on natural gas - modulated combustion air [1] - STRAIGHT and H - external blower
[1] If an APX® burner is used with constant combustion air, select the required combustion air pressure from above table for required maximum capacity per foot.
[2] sg (specific gravity) = relative density to air (density air = 0.0763 lbs/ft³(st).[3] 34120 Btu/h is the minimum capacity for natural gas (1 control valve per burner, SP drillings see [4]). The maximum capacity is set at
1.36 MBtu/h. Overfiring in fresh air heating application is possible (up to 20 %). For low oxygen recirculating applications we advise to limit the max. capacity per foot to 1 MBtu/h, with n = 1.3
[4] Pressure differential between burner test connection and combustion chamber for natural gas to be used for burner commissioning - SP burner (Standard Pressure drillings).Actual pressure differential at burner gas inlet is 5 % higher.
[5] Pressure differential between burner test connection and combustion chamber for natural gas to be used for burner commissioning - LP burner (Low Pressure drillings).Actual pressure differential at burner gas inlet is 5 % higher.
[6] Differential combustion air pressure between burner air test connection and combustion chamber for commissioning.[7] Typical differential combustion air pressure for 5 ft APX® to be used for blower selection.[8] Advised combustion air flow and air factor "n" for best burner performance. For recirculating air heating with low oxygen, advised air factor is
20 % higher (n >= 1,1 for fresh air firing, n >= 1,3 for recirculating processes).[9] Typical flame length for shown air amount and capacity. Flame length may vary in function of process air flow distribution, velocity, tempera-
ture, oxygen level etc. Contact MAXON for more information.
Typical burner dataFuel: natural gas with 1000 Btu/ft³ HHV - sg = 0.6 [1]
Combustion air: 60° F - 21 % O2 - 50 % humidity - sg = 1.0 [1]
Stated pressures are indicative. Actual pressures are a function of air humidity, altitude, type of fuel and gas quality.
APX® natural gas firing - Capacity per foot [3]MBtu/h(HHV) 0.03 0.17 0.34 0.68 1.0 1.36
Differential natural gas pressureSP burner [4] "wc 0.015 0.5 1.9 7.6 16.5 30.5
Differential natural gas pressure LP burner [5] "wc 0.01 0.26 1.04 4.16 9 16.6
Fres
h ai
r firi
ng
Differential combustion air pressure for fresh air firing [6] "wc 0.45 0.45 0.45 1.8 4 7.1
Differential combustion air pressure at bloweroutlet for fresh air firing [7] "wc 0.7 0.7 0.7 2.8 6 11
(Optimal) combustion air flow for fresh air firing [8] scfh 3500 3500 3500 7000 10300 14035
(Optimal) combustion air factor for fresh air firing .[8] n 11 2.2 1.1 1.1 1.1 1.1
Flame length (fresh air firing) [9] ft NA 0.98 1.6-2.7 2.7-3.6 3.6-4.6 4.6-5.6
Rec
ircul
atio
n ai
r with
low
O2
and
high
er u
pstre
am te
mpe
ratu
re Differential combustion air pressurefor recirculating air firing (low O2. n>=1.3) [6] "wc 0.45 0.45 0.67 2.68 5.35 10
Differential combustion air pressure at bloweroutlet for recirculating air firing (low O2. n>=1.3) [7] "wc 0.63 0.63 1.0 3.68 7.4 15
(Optimal) combustion air flow for recirculating air firing (low O2. n>=1.3) [8] scfh 3531 3531 4238 8476 12360 NA
(Optimal) combustion air factor for recirculating air firing (low O2. n>=1.3) [8] n 11 2.2 1.3 1.3 1.3 NA
Flame length(recirculating air firing (low O2. n>=1.3) [9] ft NA 1.6-2.6 4-5 6.5-8.2 9.2-10 (11.5)
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 10E- i - 5/08 Duct Burners - APX® Burner
APX burner firing on propane - modulated combustion air flow [1] - STRAIGHT and H - external blower
[1] If an APX® is used with constant combustion air, select the required combustion air pressure from above table for required maximum capacity per foot.
[2] sg (specific gravity) = relative density to air (density air = 0.0763 lbs/ft³(st)[3] 68303 Btu/h is the minimum capacity for propane/butane-firing (1 control valve per burner, SP drillings see [4]). The maximum capacity is set
at 1.36 MBtu/h. Overfiring in fresh air heating application is possible (up to 20 %). For low oxygen recirculating applications we advise to limit the max.capacity per foot to 1 MBtu/hr, with n = 1.3
[4] Pressure differential between burner test connection and combustion chamber for propane/butane to be used for burner commissioning - SP burner (Standard Pressure drillings).Actual pressure differential at burner gas inlet is approx. 5 % higher.
[5] Pressure differential between burner test connection and combustion chamber for natural gas to be used for burner commissioning - LP burner (Low Pressure drillings).Actual pressure differential at burner gas inlet is 5 % higher.
[6] Differential combustion air pressure between burner air test connection and combustion chamber for commissioning.[7] Typical differential combustion air pressure for 5 ft APX® to be used for blower selection.[8] Advised combustion air flow and air factor "n" for best burner performance. For recirculating air heating with low oxygen, advised air factor is
20 % higher (n >= 1,1 for fresh air firing, n >= 1,3 for recirculating processes).[9] Typical flame length for shown air amount and capacity. Flame length may vary in function of process air flow distribution, velocity,
temperature, oxygen level etc. Contact MAXON for more information.
Typical burner dataFuels: propane with 2592 Btu/ft³ HHV - sg = 1.57 [2] butane with 3364 kBtu/ft³ HHV - sg = 2.07 [2]
Combustion air: 15° C - 21 % O2 - 50 % humidity - sg = 1.0 [2]
Stated pressures are indicative. Actual pressures are a function of air humidity, altitude, type of fuel and gas quality.
APX® natural gas firing - Capacity per foot [3]MBtu/h(HHV) 0.07 0.17 0.34 0.68 1.0 1.36
Differential natural gas pressureSP burner [4] "wc 0.03 0.19 0.75 3 6.52 12
Differential natural gas pressure LP burner [5] "wc 0.02 0.14 0.58 2.3 5 9.2
Fres
h ai
r firi
ng
Differential combustion air pressure for fresh air firing [6] "wc 4 4 4 4 4 7.1
Differential combustion air pressure at bloweroutlet for fresh air firing [7] "wc 6 6 6 6 6 11
(Optimal) combustion air flow for fresh air firing [8] scfh 10300 10300 10300 10300 10300 14035
(Optimal) combustion air factor for fresh air firing .[8] n 33 6.6 3.3 1.6 1.1 1.1
Flame length (fresh air firing) [9] ft NA 0.98 1.6-2.7 2.7-3.6 3.6-4.6 4.6-5.6
Rec
ircul
atio
n ai
r with
low
O2
and
high
er u
pstre
am te
mpe
ratu
re Differential combustion air pressurefor recirculating air firing (low O2. n>=1.3) [6] "wc 4 4 4 4 5.35 (10)
Differential combustion air pressure at bloweroutlet for recirculating air firing (low O2. n>=1.3) [7] "wc 6 6 6 6 7.4 (15)
(Optimal) combustion air flow for recirculating air firing (low O2. n>=1.3) [8] scfh 10300 10300 10300 10300 12360 NA
(Optimal) combustion air factor for recirculating air firing (low O2. n>=1.3) [8] n 33 6.6 3.3 1.6 1.3 NA
Flame length(recirculating air firing (low O2. n>=1.3) [9] ft NA 1.6-2.6 4-5 6.5-8.2 9.2-10 (11.5)
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 11E - i - 5/08
Materials of construction
1) Air/gas mixing body Aluminium
2) Mixing plates AISI 430 (1.4016)
3) Endplate Cast iron or AISI 304 (1.4301)
4) Sideplate Galvanized or AISI 430 (1.4016)
1
2
4
3
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 12E- i - 5/08 Duct Burners - APX® Burner
Selection criteria
Application details
The MAXON APX® nozzle-mix line burner has been especially designed for low temperature air heating applications, where standard raw gas line burners (MAXON "NP" AIRFLO®) are not suitable.
Thanks to its unique single-piece air/gas mixing body, APX® strongly differentiate from the regular "box burner", with excellent flame stability and flexibility, also in high modulating and/or low oxygen process air flows.
Basically, APX® is available in two main versions.
A wall-mounted APX® to be externally mounted on the oven - or dryer wall. Thanks to the flame that exits the mixing chamber more than 0.5 ft downstream from the burner mounting flange, it is possible to penetrate oven panels up to 0.5 ft thickness without risking damage to oven structure from flame impingement.
The in-duct APX® is installed inside the dryer or make-up air unit to heat-up low temperature process air flows.
Available APX® versions and options
The two basic APX® versions, wall-mounted and in-duct, are available in several variations. Below tables give an overview of the different options of each version.
Note that wall-mounted APX® burners are always mounted on suction side of circulating fans, or in balanced ducts.
Whether slot or continuous flange mounted burner should be selected depends upon the desired amount of cooling/purge air around the burner.
The packaged blower option is not available on the EC-market - for EC-market, same execution can be achieved by selecting the external blower option, and mounting an appropriate European blower direct onto the air inlet connection of the burner.
To comply with local codes and directives, special provisions may be required to correctly safeguard the minimum combustion air pressure in case multiple blowers are mounted on the burner.
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 13E - i - 5/08
[1] All burners are available with constant or modulated combustion air flow.All burners are available with SP and LP drillings (standard pressure / low pressure - see tables page 4-21.9-7 and page 4-21.9-8).
[2] Available with incremental of 0.5 ft (0.5 / 1 / 1.5 / 2 ….ft).[3] Not available on EC-market. [4] H-style burners. Contact MAXON for other grid-configurations.
Example: "APX® SM-EB-SP-7.5 ft STRAIGHT"= wall-mounted APX® of 7.5 ft straight, slot mounted for external blower, with standard pressure drillings.
[1] All burners are available with constant or modulated combustion air flow.All burners are available with SP and LP drillings (standard pressure / low pressure - see tables page 4-21.9-7 and page 4-21.9-8)
[2] Available with incremental of 0.5 ft (0.5 / 1 / 1.5 / 2 ….ft)[3] Not available on EC-market.[4] H-style burners. Contact MAXON for other grid-configurations.[5] In-duct APX® "Slide-in-units" with mounting plug or plate to be flanged onto the duct.
Example: "APX® ID-SU-LP-14 ft STRAIGHT"= in-duct APX® burner slide-in-unit of 14 ft with low pressure drillings.
Wall-mounted APX® "WM" [1]
Slot-mounted "SM" Continuous flange mounted "CF"Packaged blower "PB" External blower "EB" Packaged blower "PB" External blower "EB"
0.5 ft to 5 ft Straight [2] [3] 1 ft to 5 ft Straight [2] 0.5 ft to 5 ft Straight [2] [3] 1 ft to 5 ft Straight [2]
5.5 ft to 15 ft Straight [2] [3] 5.5 ft to 15 ft Straight [2] 5.5 ft to 15 ft Straight [2] [3] 5.5 ft to 15 ft Straight [2]
NA (1 x 1) to (1 x 2.5) ft H [2] [4] NA (1 x 1) to (1 x 2.5) ft H [2] [4]
NA (2 x 1) to (2 x 2.5) ft H [2] [4] NA (2 x 1) to (2 x 2.5) ft H [2] [4]
NA (3 x 1) to (3 x 3.5) ft H [2] [4] NA (3 x 1) to (3 x 3.5) ft H [2] [4]
In-duct APX® "ID" [1]
Packaged blower "PB" External blower "EB" Slide-in-unit "SU"
0.5 ft to 5 ft Straight [2] [3] 0.5 ft to 5 ft Straight [2] 0.5 ft to 5 ft Straight [5]
5.5 ft to 15 ft Straight [2] [3] 5.5 ft to 15 ft Straight [2] 5.5 ft to 15 ft Straight [5]
NA (1 x 1) to (1 x 2.5) ft H [2] [4] NA
NA (2 x 1) to (2 x 2.5) ft H [2] [4] NA
NA (3 x 1) to (3 x 3.5) ft H [2] [4] NA
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 14E- i - 5/08 Duct Burners - APX® Burner
Endplate set options
Different types of endplates are available for MAXON APX® burners. Refer to the table below for selection of the most appropriate pilot endplates.
[1] Refer to tables on page 4-21.9-17 and page 4-21.9-18 for information on SI and flame rods included in each endplate.[2] Use this pilot endplate set on stable back-pressure application only. When fluctuating oven pressures can be expected, use FIG.4.[3] Select these endplate sets when externally mounted SI and FR/UV are required, or to prevent the use of ignition and/or ionization cable
inside the duct (internally mounted SI and FR). To be used together with the external mounting plate sets EXT-MTG.[4] Direct ignition endplate set to accommodate SI and FR/UV on 1 single endplate set (standard not possible for wall-mounted burners - contact
MAXON).[5] To be selected together with NP-EP SI FR/UV.
Overview Endplate set options MAXON APX® burners
Description Designation [1] Wall-mount In-duct 3D-View
Raw gas pilot endplate set with air by-pass(incl. SI, pilot gas connection, FR or provision for UV-scanner)
[2]
FIG1-FR yes no
FIG1-UV yes no
Endplate set with FR only FIG2-FR yes yes
Endplate set with sight glass only FIG2-SG yes yes
Plain endplate set FIG2-PLN yes yes
Endplate set for direct ignition(with SI only) FIG3-SI yes yes
Raw gas pilot endplate set (incl. SI, FR or provision for UV-scanner)
FIG4-FR yes no
FIG4-UV yes no
In-duct raw gas pilot endplate set(incl. SI, FR or provision for UV-scanner)
FIG5-FR no yes
FIG5-UV no yes
In-duct feed through raw gas pilot endplate set [3]
FIG6-FR no yes
FIG6-UV no yes
External mounting plate kit for external UV/FR and external SI EMP-EXT no yes
External mounting plate kit for external UV/FR and external SI EMP-INT no yes
In-duct endplate set for direct ignition(incl. SI, FR and provision for UV) [4] NP-EP SI FR/UV no yes
In-duct plain endplate set [5] NP-EP PLN no yes
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 15E - i - 5/08
APX® endplate accessories (included in the endplate assembly)
[1] Only applicable for US-supplies (spark excitation)[2] Select correct flame rod from table "Feed thru flame rods" on page 4-21.9-18.[3] Select correct spark ignitor from table "Feed thru spark ignitors" on page 4-21.9-17.[4] These endplate sets include a pilot nozzle and air shutter to adjust the bypass pilot air.[5] Feed thru endplate sets FIG6 do not include SI/FR. For fresh air applications, standard spark ignitor (SI-APX-4 in.) and standard flame rod
(FR-APX) can be selected. Both the standard SI/FR or the feed thru SI/FR have to be added separately.[6] This endplate set allows direct ignition on induct APX® burners; SI and flame detection can be mounted on this endplate.[7] For EC-market only.
Process temperature
Special attention should be paid when selecting the burner to avoid downstream process air temperatures above 570° F at low fire. Higher temperatures at minimum burner capacity may dramatically reduce life-time of the burner. At higher capacity, the burner parts are better cooled by the air- and gas flow, and allow much higher downstream temperatures.
The slide-in-units APX® can accept in specific circumstances higher process temperatures, both upstream and downstream of the burner. Contact MAXON for more information.
Combustion air requirements
MAXON APX® burners are fed with clean fresh combustion air containing 21 Vol % oxygen and a maximum temperature of 120° F.
In some installations, the use of higher temperature combustion air, or combustion air containing slightly lower oxygen levels, may be possible. This should be considered case by case. Contact MAXON for more information.
Accessories included in the endplate sets, except not when explicitly written
Endplate set Flame rod UV-tube [1] Spark ignitor Adjustable orifice Gas test port
FIG1-FR [4] FR-APX NA SI-APX-10mm AO-3/8" NPT NA
FIG1-UV [4] NA NA SI-APX-10mm AO-3/8" NPT NA
FIG2-FR FR-APX NA NA NA 1/8" NPT
FIG2-SG NA NA NA NA 1/8" NPT
FIG2-PLN NA NA NA NA 1/8" NPT
FIG3-SI NA NA SI-APX-14mm-L NA 1/8" NPT
FIG4-FR FR-APX NA SI-APX-1/2-14 AO-3/8" NPT NA
FIG4-UV NA UVT-1 [1] SI-APX-1/2-14 AO-3/8" NPT NA
FIG5-FR FR-APX NA SI-APX-14mm-S AO-3/8" NPT 1/8" NPT
FIG5-UV NA UVT-2 [1] SI-APX-14mm-S AO-3/8" NPT 1/8" NPT
FIG6-FR [5] [2] [5] NA [3] [5] AO-3/8" NPT 1/8" NPT
FIG6-UV [5] NA UVT-2 [1] [3] [5] AO-3/8" NPT 1/8" NPT
NP-EP SI FR/UV [6][7] NA NA SI-APX-14mm-L NA 1/8” NPT
NP-EP PLN [7] NA NA NA NA NA
Max. upstream process air temperature 480° F
Max. downstream process air temperature at low fire 570° F
Max. downstream process air temperature at high fire 750° F
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 16E- i - 5/08 Duct Burners - APX® Burner
Modulated or constant combustion air
All MAXON APX® burners can operate with constant or fixed air flow, as well as with modulated air flow.
At constant air flow, the required differential combustion air pressure (refer to table on page 4-21.9-9, page 4-21.9-10 and page 4-21.9-11) is set by a fixed air damper (burner air inlet or fan) and the combustion air flow through the burner is constant for all burner firing rates (always maximum air flow).
At modulating air flow, an additional air control valve is adjusting the combustion air in function of burner capacity.
The choice whether constant or modulated air flow should be selected highly depends on the application and the desired emissions on CO and NOx. Refer to "Emissions" on page 4-21.9-19 for more details.
Ratio control
In case the burner is operated with modulated air flow, best performance is realized when the burner is adjusted with ratio's as indicated in the table on page 4-21.9-9 and page 4-21.9-10. This can be achieved with MAXON MICRO-RATIO® valves or SMARTLINK® MRV.
Changes of combustion air temperature, system back pressure variations, and other parameters could influence gas/air-ratio if the control system is not designed for compensation. Contact MAXON for more information.
Process air flow velocity and oxygen content
[1] A minimum parallel process flow for in-duct burners, and cross process flow for wall-mounted burners is required. Burners shall not fire without process flow. Advised minimum velocity shall be above 6 ft/s.
[2] Optimal burner performance of in-duct APX® burners will be realized with a uniform process air velocity around the flame between 6 ft/s and 26 ft/s. Higher process air velocities are possible (up to 65 ft/s), however may influence emissions of CO (see page 4-21.9-19).
[3] (Higher cross-velocities (up to 9 m/s) will quench the flame and affect emissions (CO)). The use of a flame protection shield is advised to limit CO. Contact MAXON for more information.
[4] Depending on temperature, capacity and excess air, MAXON APX® burners can fire in almost inert process air environment.
Process back pressures
[1] Wall mounted burners can only fire in ducts under suction or in balanced atmospheres. Ducts in overpressure should be avoided.[2] All in-duct burners, except the slide-in-unit design. Special considerations to be taken for the design of combustion air fan in case of higher
back-pressures.[3] Higher back-pressures are possible when the plug and airbox are reinforced. Contact MAXON for more information.
IN-DUCT(parallel velocity)
WALL-MOUNTED
(cross velocity)
Min. process air velocity [1] 6 ft/s 6 ft/s
Max. process air velocity 26 (65) ft/s [2] 20 (30) ft/s [3]
Min. process air oxygen level [4] 3 - 6 Vol % 3 - 6 Vol %
Max. process back-pressure - wall-mounted APX
[1] -2" wc to balanced
Max. process back-pressure - in-duct APX
[2] -40" wc to +40" wc
Max. process back-pressure - in-duct APX slide-in unit
[2] -12" wc to +12" wc
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 17E - i - 5/08
Piloting & ignition
APX® burners, equipped with one of the raw gas pilot endplate set (see table on page 4-21.9-14), will generate a stable pilot flame, used to ignite the burner on main flame. After the main burner is ignited, the pilot shall be interrupted. Permanent pilot is not advised. Use the main burner at minimum capacity for continuous operation.
Direct ignition of APX® burners is also possible, if accepted by local codes. Note that only in-duct APX® burners offer direct ignition endplates which accommodate spark ignitor and flame detection in the same endplate set. Direct ignition wall-mounted burners need 1 endplate set for the SI and another endplate set to mount the flame detector.
For both pilot and direct ignition, use ignition transformers min. 5000 V - 200 mA.
Available spark ignitors
Spark ignitors are included into the pilot endplate sets, except for FIG6 endplates. Refer to table on page 4-21.9-14 for exact information.
Below table will help you with the selection of the appropriate feed thru spark ignitors (in combination with FIG6 endplate set and external mounting plate (EMP).
Typical ignition sequence (with pilot)
Pre-purge of burner and combustion chamber, according to the applicable codes and the installation's requirements.Gas control valve shall be in the minimum position.APX burners with modulated combustion air shall have the combustion air valve (linked with the gas control valve) also in the corresponding minimum position to allow minimum combustion air flow to the burner.Pre-ignition (typically 2 s sparking in air).Open pilot gas and continue to spark the ignitor (typically 5 s to 10 s depending on local code requirements).Stop sparking, continue to power the pilot gas valves and start flame check. Trip burner if no flame detected from here on.Check pilot flame stability (typically 5 s to 10 s to prove stable pilot).Open main gas valves and allow enough time to have main gas in the burner (typically 5 s + time required to have main gas in the burner).Close the pilot gas valves.Release to modulation (allow modulation of the burner).
Above sequence shall be completed to include all required safety checks during the start of the burner (process & burner safeties). We advise to position 1 pilot gas valve as close as possible to the pilot burner gas inlet for fast ignition of the pilot burner.
Feed thru ignitors with carbon steel tube
Feed thru ignitors with stainless steel tube
Spark ignitors only(without tube)
12" CS QI 12" CS quartz ignitor 12" SS QI 12" SS quartz ignitor 12" QI L/T 12" quartz ignitor
18" CS QI 18" CS quartz ignitor 18" SS QI 18" SS quartz ignitor 18" QI L/T 18" quartz ignitor
24" CS QI 24" CS quartz ignitor 24" SCS QI 24" SS quartz ignitor 24" QI L/T 24" quartz ignitor
30" CS QI 30" CS quartz ignitor 30" SS QI 30" SS quartz ignitor 30" QI L/T 30" quartz ignitor
36" CS QI 36" CS quartz ignitor 36" SS QI 36" SS quartz ignitor 36" QI L/T 36" quartz ignitor
48" CS QI 48" CS quartz ignitor 48" SS QI 48" SS quartz ignitor 48" QI L/T 48" quartz ignitor
Select your spark ignitor in function of the required length (12" to 48" in steps of 6").
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 18E- i - 5/08 Duct Burners - APX® Burner
Flame supervision
The flame of APX® burners can be supervised with a flame rod or UV-scanner.
Depending on the application, different versions of endplate sets accommodating different types of flame rods can be selected. Refer to table page page 4-21.9-14 (Overview endplate set options) and table page 4-21.9-15 (APX® accessories) for more information.
For poor quality propane, LPG or butane, we advise to use UV-scanners only.
Only use the appropriate positions on the MAXON endplate sets for correct and safe flame supervision. Every other position is not acceptable and may cause unsafe situations.
Refer to the user manual of the UV-scanner for correct installation and operating instructions.
Available flame rods
Also flame rods are included into the pilot endplate sets, except for FIG6 endplates. Refer to table page 4-21.9-14 for exact information.
Below table will help you with the selection of the appropriate feed thru flame rods (in combination with FIG6 endplate set and external mounting plate (EMP).
Flame development
Tables page 4-21.9-9, page 4-21.9-10 and page 4-21.9-11 are giving typical flame length of MAXON APX® burners for the shown combustion air amount, burner capacity and application (fresh air versus recirculating air).
Note that flame length is influenced by different factors, such as:
Excess air factor (higher excess air will reduce flame length)Process air velocity (higher velocity will reduce flame length)Type of fuel (butane flames will typically be longer than natural gas flames)Burner length (shorter burners will give shorter flame lengths)Air distribution at the burner inlets - see "Piping" below etc.
In case the burner is fired with low excess air in low oxygen environment, flame may become quite radiant. Take this into consideration for the design of combustion chambers (choice of materials, distance to the wall, expansion allowance...).
Contact MAXON for more information.
Feed thru ignitors with carbon steel tube
Feed thru ignitors with stainless steel tube
Spark ignitors only(without tube)
12" CS FR 12" CS quartz flame rod 12" SS FR 12" SS quartz flame rod 12" FR L/T 12" quartz flame rod
18" CS FR 18" CS quartz flame rod 18" SS FR 18" SS quartz flame rod 18" FR L/T 18" quartz flame rod
24" CS FR 24" CS quartz flame rod 24" SCS FR 24" SS quartz flame rod 24" FR L/T 24" quartz flame rod
30" CS FR 30" CS quartz flame rod 30" SS FR 30" SS quartz flame rod 30" FR L/T 30" quartz flame rod
36" CS FR 36" CS quartz flame rod 36" SS FR 36" SS quartz flame rod 36" FR L/T 36" quartz flame rod
48" CS FR 48" CS quartz flame rod 48" SS FR 48" SS quartz flame rod 48" FR L/T 48" quartz flame rod
Select your flame rod in function of the required length (12" to 48" in steps of 6").
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 19E - i - 5/08
Piping
Except for the slide-in-units, where the air and gas distribution is incorporated into the burner design, special attention should be paid to the execution of air and gas manifolds, feeding the air and gas inlet(s) of all the other APX® burner versions.
Common engineering practice should be followed to equally feed the burner at each air and gas connection. Prevent too high velocities which may cause unequal pressure build-up. Burner and piping shall be independently supported to allow for thermal expansion, to prevent any stress on the burner inlets and to prevent the transmission of vibrations.
Fuels
MAXON APX® burners can fire natural gas, propane, butane, LPG and is able to fire multiple fuels simultaneously, if the control system is properly designed.
Alternative fuels may be possible. Contact MAXON for more information.
Expected Emissions
The clean hot air generated by MAXON APX® burners meets most of the local requirements of make-up air systems, over the full turndown of the burners.
Also in low temperature ovens and drying systems, MAXON APX® burners are able to fire with both low NOx and CO, over its entire turndown, meeting the most stringent local emission requirements.
The production of pollutants can be highly dependant upon burner application and installation. Differing temperatures, process velocities, oxygen levels, fuels and other process related factors such as unequal process air distribution can all influence the actual level of emissions produced. No guarantee of emissions is intended or implied on the above.
Contact MAXON for evaluation of expected emissions on your typical application.
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 20E- i - 5/08 Duct Burners - APX® Burner
Dimensions and weights
0.5 ft packaged blower
This burner version includes a combustion air blower. This version is not suitable for the EC-market.
Mounting arrangements (view C-C’)
1) Combustion air blower2) Main gas inlet flange 1” NPT3) Spark ignitor4) Flame rod5) Burner mounting plane
Dimensions in inches unless stated otherwiseA B C D E F G ø H ø I K L
6.5 11.5 4.5 11.2 6.6 8.1 3.1 4.7 4 7.7 10.2
Continuous flange mounting Slot mounting
Dimensions in inches unless stated otherwiseM N O P ø Q R S ø T X [1] Y [1]
7.9 9 10.1 6 0.438 5 9.2 0.438 8.6 7
A A'
B B'
2
1
B-B'A-A'4
5
3
D
A
BC
ø H
FG
ø I
EK L
C
C'
X
YMNO
Pø
Q
X
YR
SøT
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 21E - i - 5/08
1 ft to 15 ft external blower
1) Gas inlet 1.1/2” NPT2) Air inlet + shutter3) Test connection4) Mounting surface5) Gas inlet flange
1.1/2”NPT
CL
CL
CL
CL
23
CL
CL
A
A'L
A
A A
B C
A A
B C
A A
C C
B
L
L
A AB B
C D
L
L
E E
E E
E E
E E
EE
B
F
A
B
D
E
C
A-A'K
GH
J
31
54
1
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 22E- i - 5/08 Duct Burners - APX® Burner
Dimensions in inches unless stated otherwise
burner size (ft) 1 1.5 2 2.5 3 3.5 4 5 6 7 8 9 10 11 12 13 14 15
sketch A A A A A A A A B B C C C C D E E D
A 7 7 7 7 7 7 7 7 18 18 36 36 36 36 18 18 18 21
B - - - - - - - - 25 25 29 24,9 29 29 54 54 54 63
C - - - - - - - - 18 18 29 24 29 29 54 47 47 56
E 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
F - - - - - - - - - - - - - - - 61 61 -
G 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 1.1 1.1
H 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6.5 6.5
J 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6 6.6
K 11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
L 12 18 24 30 36 42 48 60 72 84 96 108 120
132
144
156
168
180
weight (lbs) 14 21 27 34 41 49 55 68 82 95 109 123 13
6150
164
177
191
205
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 23E - i - 5/08
1 to 15 ft packaged blower (not for EC-market)
This modular straight burner includes one or more combustion air blowers. This version is not suitable for the EC-market.
The packaged burner dimensions are the same as those of the “external blower” version, see page 4-21.9-21.
Additional to the “external blower” version, the packaged version has got one or more combustion air blowers mounted directly on the back of the burner. For positions of these combustion air inlets see page 4-21.9-21.For dimensions of blowers, see page 4-21.9-36.
APX® "H" Style burners - wall mounted
1) Gas inlet 1.1/2” NPT2) Air inlet + shutter3) Test connection4) Mounting surface
1
N
B
AD
II
HH
F
LJ J
C E
GK
M
A
A
2
3
4
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 24E- i - 5/08 Duct Burners - APX® Burner
Dimensions in in. unless stated otherwise
Burner size A B C D E F G H I J K L M N Weight(lbs)
1 x 1 22.12 18.5 8.48 16.24 6.45 12.24 8.06 6 - 4.22 14 12 0.44 2.5 41
1 x 1.5 28.12 24.5 8.48 16.24 6.45 12.24 8.06 6 - 4.22 14 18 0.44 2.5 48
1 x 2 34.12 30.5 8.48 16.24 6.45 12.24 8.06 6 - 4.22 14 24 0.44 2.5 54
1 x 2.5 40.12 36.5 8.48 16.24 6.45 12.24 8.06 6 - 4.22 14 30 0.44 2.5 61
2 x 1 22.12 18.5 8.48 28.24 6.45 24.24 8.06 12 6 4.22 14 12 0.44 7.12 68
2 x 1.5 28.12 24.5 8.48 28.24 6.45 24.24 8.06 12 6 4.22 14 18 0.44 7.12 75
2 x 2 34.12 30.5 8.48 28.24 6.45 24.24 8.06 12 6 4.22 14 24 0.44 7.12 82
2 x 2.5 40.12 36.5 8.48 28.24 6.45 24.24 8.06 12 6 4.22 14 30 0.44 7.12 88
3 x 1 22.12 18.5 8.48 40.24 6.45 36.24 8.06 18 6 4.22 14 12 0.44 7.12 95
3 x 1.5 28.12 24.5 8.48 40.24 6.45 36.24 8.06 18 6 4.22 14 18 0.44 7.12 102
3 x 2 34.12 30.5 8.48 40.24 6.45 36.24 8.06 18 6 4.22 14 24 0.44 7.12 109
3 x 2.5 40.12 36.5 8.48 40.24 6.45 36.24 8.06 18 6 4.22 14 30 0.44 7.12 116
3 x 3.5 52.12 48.5 8.48 40.24 6.45 36.24 8.06 18 6 4.22 14 42 0.44 7.12 129
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 25E - i - 5/08
APX® "H" Style burners - slot fired mounting
1) Gas inlet 1.1/2” NPT2) Air inlet + shutter3) Test connection4) Mounting surface
Dimensions in in. unless stated otherwise
Burner size A B C D E F G H I ø J K N Weight(lbs)
1 x 1 26.62 18.5 8.41 16.24 6.45 12.24 8 6 6.68 0.4 12 2.5 41
1 x 1.5 32.62 24.5 8.41 16.24 6.45 12.24 8 6 6.68 0.4 18 2.5 48
1 x 2 38.62 30.5 8.41 16.24 6.45 12.24 8 6 6.68 0.4 24 2.5 54
1 x 2.5 44.62 36.5 8.41 16.24 6.45 12.24 8 6 6.68 0.4 30 2.5 61
2 x 1 26.62 18.5 8.41 28.24 6.45 24.24 8 18 6.68 0.4 12 7 68
2 x 1.5 32.62 24.5 8.41 28.24 6.45 24.24 8 18 6.68 0.4 18 7 75
2 x 2 38.62 30.5 8.41 28.24 6.45 24.24 8 18 6.68 0.4 24 7 82
2 x 2.5 44.62 36.5 8.41 28.24 6.45 24.24 8 18 6.68 0.4 30 7 88
3 x 1 26.62 18.5 8.41 40.24 6.45 36.24 8 30 6.68 0.4 12 7 95
3 x 1.5 32.62 24.5 8.41 40.24 6.45 36.24 8 30 6.68 0.4 18 7 102
3 x 2 38.62 30.5 8.41 40.24 6.45 36.24 8 30 6.68 0.4 24 7 109
3 x 2.5 44.62 36.5 8.41 40.24 6.45 36.24 8 30 6.68 0.4 30 7 116
3 x 3.5 56.62 48.5 8.41 40.24 6.45 36.24 8 30 6.68 0.4 42 7 129
A
B
HFD
I I I II
KI
N
ø J
G
C E
2
3
1
4
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 26E- i - 5/08 Duct Burners - APX® Burner
APX® Slide-in-units
.
[1] Gas inlet connection standard ISO-threaded for sizes up to and including 2". Larger sizes standard have DIN PN10 flanged connections. NPT threaded and ANSI 150lbs flanges available on request.
[2] Plug to be mounted in an opening with min. dimensions J x H
1) Gas inlet2) Pilot gas connection 1/2”3) Combustion air test connection 1/4”4) Gas test connection 1/4”5) Burner support (custom made)6) Burner mounting plug (custom made -
drawing shows typical lay-out)7) Mounting plate
to be used in case of external ignitor and flame scanner option
Dimensions in in. unless stated otherwiseBurner size 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5L 6 12 18 24 30 36 42 48 54 60 66 72 78 84 90Gas inlet [1] 1" 1" 1 1/2" 1 1/2" 1 1/2" 1 1/2" 2" 2" 2" 2" 2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2"A 16.54 16.54 16.54 16.54 16.54 16.54 16.54 16.54 16.54 16.54 16.54 16.54 16.54 20.47 20.47B 24.41 24.41 28.35 28.35 28.35 28.35 36.22 36.22 36.22 36.22 36.22 36.22 36.22 44.09 44.09J [2] 11.81 11.81 11.81 11.81 11.81 11.81 11.81 11.81 11.81 11.81 11.81 11.81 11.81 15.75 15.75H [2] 19.69 19.69 23.62 23.62 23.62 23.62 31.50 31.50 31.50 31.50 31.50 31.50 31.50 39.37 39.37weight (lbs) 129 147 157 174 185 199 242 254 268 281 294 307 389 404 422
Dimensions in in. unless stated otherwiseBurner size 8 8.5 9 9.5 10 10.5 11 11.5 12 12.5 13 13.5 14 14.5 15L 96 102 108 114 120 126 132 138 144 150 156 162 168 174 180Gas inlet [1] 3" 3" 3" 3" 3" 3" 3" 4" 4" 4" 4" 4" 4" 4" 4"A 20.47 20.47 20.47 20.47 20.47 20.47 20.47 20.47 20.47 20.47 20.47 20.47 20.47 20.47 20.47B 44.09 44.09 44.09 44.09 44.09 44.09 44.09 44.09 51.97 51.97 51.97 51.97 51.97 51.97 51.97J [2] 15.75 15.75 15.75 15.75 15.75 15.75 15.75 15.75 15.75 15.75 15.75 15.75 15.75 15.75 15.75H [2] 39.37 39.37 39.37 39.37 39.37 39.37 39.37 39.37 47.24 47.24 47.24 47.24 47.24 47.24 47.24weight (lbs) 440 455 471 572 594 616 632 651 715 735 755 775 794 815 832
A A'
B
B'
C
C'D
WE LFG
Z
D
J
HS
X
Y
A
B
C-C'
D
B-B'
A-A'
2
1
3
4
65
7
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 27E - i - 5/08
For complete burner dimension information, following application depending dimensions should be defined:
Wall mounting: opening dimensions
A = wall opening
B = burner length (refer to burner dimensions on page 4-21.9-20)
XL = endplate width mounted on left side of the burner
XR = endplate width mounted on right side of the burner
A = B + XL + XR
XL and XR depending on the endplate type, use the table below for determination.
Note that Fig. 4 endplates need a special wall opening shape if full seal is required. Contact MAXON for details.
Mounting flange dimensions
Use this sketch to determine fixing points for flange mounted burner parts.
W: internal duct width S: duct wall thicknessD: max. 2 ft (D = X + Y + Z + S) E: min. 0.5 ftX: internal insulation thickness F: min. 0.5 ftY: external insulation thickness G: default G = XZ: flange elevation (default = 4 in.)
Dimensions in in. unless stated otherwise
Endplate Fig. # X
1 2.22, 3, 4, 5, 6 1.3
4 3
Dimensions in in. unless stated otherwise
A B C D E
2.1 8.4 6 0.4 0.6
B
AX
LX
R
A C C C
B
D
E
A A
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 28E- i - 5/08 Duct Burners - APX® Burner
Slot mounting tabs
These support tabs can be mounted at various locations on the burner body at 6 in. spacings. They are suggested to be used for burners longer than 4 ft. Burners with a maximum length of 4 ft can be supported using the fixation holes in the endplates.
Universal mounting bracket
These brackets can be used to support burners in horizontal orientation (use 1 bracket per 5 ft burner) and in vertical orientations (use 1 bracket per 3 ft burner and install brackets on both sides of the burner).
1) Mounting surface to be attached to burner
Dimensions in in. unless stated otherwise
A B C D E
2 3.4 2.3 0.4 0.4
Dimensions in in. unless stated otherwise
A B C D E F
7.5 6.5 3.75 1.4 1 0.4
B
A
ø D
C
ø E
X
Y
1
A A
C
C
D
ø F
B
E
A
A-A
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 29E - i - 5/08
Endplates
[1] Clearance for flame rod removal
[1] Clearance for flame rod removal
FIG 1
1) Spark ignitor connection M10x12) UV/flame rod connection 1”NPT3) Pilot gas connection 3/4-16 UNF4) Flame rod5) Mounting surface6) Pilot air shutter
Dimensions in in. unless stated otherwise
A B C D E [1] F [1] G H J K L
1.1 1.8 3.6 0.4 10.8 9.4 3.4 6.0 0.8 2.5 6.5
FIG 2
1) Flame rod connection1.1/4”NPT2) Flame rod3) Optional sight glass4) Gas test connection 1/8” NPT5) Mounting surface
Dimensions in in. unless stated otherwise
A B C D E [1] F [1] G H J K L M N
1.1 1.8 3.6 0.4 9.3 6.9 5 2.5 1.5 2 6.5 0.8 1.4
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 30E- i - 5/08 Duct Burners - APX® Burner
[1] Clearance for spark ignitor removal
[1] Clearance for flame rod removal
FIG 3
1) Spark ignitor connection M14x1.252) Spark ignitor3) Gas test connection 1/8”NPT4) Mounting surface
Dimensions in in. unless stated otherwise
A B C D E [1] F [1] G H J K L M N
1.1 1.8 3.6 0.4 3.3 2.7 5 2.5 1.5 2 6.5 0.8 1.4
FIG 4
1) Spark ignitor connection 3/4”-162) UV/flame rod connection 1/4”NPT3) Pilot gas connection 3/8”NPT4) Flame rod5) Mounting surface6) Pilot gas adjusting needle valve
Dimensions in in. unless stated otherwise
A B C D E [1] F [1] G H J K L P
1.1 1.8 3.6 0.4 10.7 7.9 5.0 2.5 3.5 4.0 6.5 0.8
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 31E - i - 5/08
[1] Clearance for flame rod removal
[1] Clearance for flame rod removal
FIG 5
1) Spark ignitor connection M14x1.252) UV/flame rod connection 1/4”NPT3) Pilot gas connection 3/8”NPT4) Flame rod5) Mounting surface6) Gas test connection 1/8”NPT
Dimensions in in. unless stated otherwise
A B C D E [1] F [1] G H J K L M N R S T
1.1 1.8 3.6 0.4 9.3 6.9 5 2.5 1.5 2 6.5 0.8 1.4 1.5 0.5 0.6
FIG 6
1) Spark ignitor connection 3/4” - 10UNC
2) UV/flame rod connection 3/4” - 10UNC
3) Pilot gas or local flame rod connection 1/4” NPT
4) Flame rod5) Mounting surface6) Gas test connection 1/8” NPT
Dimensions in in. unless stated otherwise
A B C D E [1] F [1] G H J K L M N R S T
1.1 1.8 3.6 0.4 9.2 7.0 5.0 2.5 1.5 2.0 6.5 0.8 1.4 1.6 3.0 0.6
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 32E- i - 5/08 Duct Burners - APX® Burner
INDUCT ENDPLATE SET
1) Scanner connection Rp1/2”Flame rod connection Rp1/4” (bushed)
2) Spark ignitor connection M14x1.253) Pilot gas connection Rp 1/4”4) Gas test connection 1/8”NPT5) Combustion air test connection 1/8” NPT
A = 11.5 in.B = 6.5 in.
INDUCT PLAIN ENDPLATE SET
1) Gas test connection 1/8”NPT2) Combustion air test connection 1/8” NPT
A = 11.5 in.B = 6.5 in.
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 33E - i - 5/08
Flame rod - FR-APX
Flame rod - FR-Quartz
for use with external mounting plate kit.
Spark ignitor - SI-APX-10 mm
Spark ignitor - SI-APX-14 mm-Long
Spark ignitor - SI-APX-14 mm-Short
1) 1/4” - 18 thread
Dimensions in in. unless stated otherwiseA B øC
9.6 7.5 0.2
Dimensions in in. unless stated otherwiseSize A B12” 12 118” 18 124” 24 130” 30 136” 36 148” 48 1
1) 1/4” - 18 thread
Dimensions in in. unless stated otherwiseA B C øD
2.75 0.25 0.4 0.125
1) 14 mm thread
Dimensions in in. unless stated otherwiseA B C øD
4.09 0.51 1.87 0.08
1) 14 mm thread
Dimensions in in. unless stated otherwiseA B C øD
3.3 0.51 1.07 0.08
1
ø CB
A
A
øB
1
1
A
B
øD
C
1
B
øD
A
C
1
B
C
øD
A
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 34E- i - 5/08 Duct Burners - APX® Burner
Spark ignitor - SI-APX-1/2-14
Spark ignitor - quartz less tube
Spark ignitor - quartz with tube
Available in different sizes. Each size available in either carbon steel or stainless steel.
1) 1/2”-14 thread
Dimensions in in. unless stated otherwiseA B C D øE
6.5 5.51 1.25 0.375 0.56
Dimensions in in. unless stated otherwiseA B øC
8.4 6.5 0.472
Dimensions in in. unless stated otherwiseSize A B12” 12 118” 18 124” 24 130” 30 136” 36 148” 48 1
A
B D
C
ø E1
B
ø C
A
A
øB
1
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
Duct burners - APX® Burner 4 - 21.9 - 35E - i - 5/08
Mounting plate kits for spark ignitor and flame detection
External SI/UV
1) Gasket2) Cover plate3) Sealing plate
Dimensions in in. unless stated otherwise
A B C D E F G H I J ø K ø L M Weight (lbs)
3.74 5.51 2.48 4.72 0.80 0.58 0.47 0.31 0.26 0.32 1.12 1.12 0.77 2.60
Internal SI/UV
1) Gasket2) Cover plate
Dimensions in in. unless stated otherwise
A B C D E F G H I J ø K ø L M Weight (lbs)
3.74 5.51 2.48 4.72 0.69 0.89 0.47 0.31 0.39 0.20 Pg 9 Pg 9 0.49 2.20
1 2 3 A
A'A-A'
DB
C
A
G
HI
J
E
F
ø Lø
K
M
1 2 A
A'A-A' E
J
I
F
MG
H
ø Kø L
DB
C
A
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.
4 - 21.9 - 36E- i - 5/08 Duct Burners - APX® Burner
Blowers and accessories
Adjustable pilot gas orifice
1) Blower2) Filter3) Silencer
Dimensions in in. unless stated otherwise
Burner sizeft A B C D E ø F ø G
1 12.7 11.5 15.2 14.4 20.3 7.0 11.81.5 12.7 11.5 15.2 14.4 20.3 7.0 11.82 16.4 11.5 19.0 14.6 20.5 7.0 11.8
2.5...15 16.4 11.5 19.0 14.6 27.8 9.0 16.4
1) Gas outlet 3/8” NPT2) Gas inlet 3/8” NPT3) Protection cap:
remove to access flow adjustment screw HEX 3.8 mm
A = 1.5 in.B = 3.44 in.C = 0.75 in.
123
A
BC
DE
ø F
ø G
21
3
MAXON
GAS
A
C
B
w w w . m a x o n c o r p . c o mcombustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice. © 2005 Copyright Maxon Corporation. All rights reserved.