Masters degree project on thermal comfort with radiant heating walls

17
evds www.ucalgary.ca/evds Field Study of Thermal Comfort with Radiant Walls Susana Garcia-San Roman Supervisor Dr. James A. Love November 22, 2011 SAIT Tower Residence 24,000 m2 22 stories 445 suites for students 715 residents.

description

Field Study of Thermal Comfort with Radiant Walls on a students residence located in Calgary

Transcript of Masters degree project on thermal comfort with radiant heating walls

Page 1: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

Field Study of Thermal Comfort with Radiant Walls

Susana Garcia-San Roman

Supervisor Dr. James A. LoveNovember 22, 2011

SAIT Tower Residence 24,000 m222 stories

445 suites for students715 residents.

Page 2: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

QUESTIONS BEFORE THE RESEARCH ...

Page 3: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

KEY POINTS- OUTLINE

Page 4: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

THERMAL COMFORT: PERSONAL PARAMETERS

QUESTIONNAIRE RESPONDENTS

RESULTS – WINTER SURVEY

Page 5: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

THERMAL COMFORT: ENVIRONMENTAL PARAMETERSDRY BULB TEMPERATURE (ºC)

COOLING DESIGN T (26.6ºC)

HEATING DESIGN T (25.7ºC)

19-29ºC

14-24ºC

Page 6: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

INDOOR CLIMATE (WINTER): AIR STRATIFICATION

THERMAL COMFORT: ENVIRONMENTAL PARAMETERS

Page 7: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

THERMAL COMFORT: ENVIRONMENTAL PARAMETERSINDOOR CLIMATE: RADIANT ASYMMETRY

SURFACE TEMPERATURES (WINTER)

SURFACE TEMPERATURES (SUMMER)

COLD FLOOR

19ºC

12ºC

15ºC 27ºC

44ºC25ºC

Page 8: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

OCCUPANT COMFORT ASSESSMENT

LOCAL THERMAL DISCOMFORT

•29% COLD FLOOR•16% HIGH VERT. AIR T DIFFERENCE•RADIANT ASYMMETRY•DRAFT

Page 9: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

Predicted percentage dissatisfied: PPD 10 % + 10 %Predicted mean vote: PMV - 0.5 to + 0.5

Page 10: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

PREDICTED COMFORT INDICESCALCULATION WITH CODE ASHRAE 55 TC STANDARD FROM 6 PARAMETERS

Page 11: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

OCCUPANT COMFORT ASSESSMENT (QUESTIONNAIRE RESPONSES)

THERMAL SENSATION

ACTUAL COMFORT INDICES

VOTES IN THE 3 CENTRAL CATEGORIES 74 % ACTUAL % DISSATISFIED 26 %

Page 12: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

COMPARISON INDOOR ENVIRONMENT PARAMETERS WITH COMFORT ZONE (WINTER)

1 CLO1-1.3 METVa 0.2 m/s

COMFORT ZONE (STANDARD 55 ASHRAE 2010)

SATISFIED

DISSATISFIED

Page 13: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

THERMAL RESPONSES IN A DYNAMIC ENVIRONMENT

Page 14: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

ADAPTIVE MODEL IN THERMAL COMFORT RESEARCH

TC ASSESSMENT, A DYNAMIC ACCUMULATIVE DECISION MAKING PROCESS

Page 15: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

ADAPTIVE MODEL IN THERMAL COMFORT RESEARCH

Page 16: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

... QUESTIONS AFTER THE RESEARCH

Page 17: Masters degree project on thermal comfort with radiant heating walls

evds www.ucalgary.ca/evds

Thank you!

Questions welcome