Masterpact LV power air circuit breakers and switch disconnectors.
-
Upload
marianna-chase -
Category
Documents
-
view
246 -
download
7
Transcript of Masterpact LV power air circuit breakers and switch disconnectors.
MasterpactLV power air circuit breakers and switch disconnectors
Customer Training - Freddy Suhartono - May 2000 - English 2
Function
Masterpact circuit breaker are used to protect and control low voltage distribution system.
Masterpact circuit breaker may be installed in main LV switchboards (incoming units, main and secondary outgoers).
Customer Training - Freddy Suhartono - May 2000 - English 3
Features
Ratings from 800 to 6300 A AC, from 1000 to 8000 A DC Breaking capacity from 40 to 150 kA rms (N1, H1, H2) Operational voltages 690 V AC, 1000 V DC; 3 or 4 poles Fixed or drawout version Wide range of control units offering multiple function Comply with all the major international standards:
• International standard: IEC 947-2,• North American standard: UL489, ANSI C37-50, CSA C22-2, NEMA AB1
to SG3,• Japanese standards: JIS 160 and C 8372
Comply with national standards:• France: NF C63-120• Germany: VDE 0660• United Kingdom: BS4752• Australia AS• Italy CEI;
Customer Training - Freddy Suhartono - May 2000 - English 4
Features Mechanical endurance :
• with maintenance co cycles : 20,000 (M08 - M16); 15,000 (M20 - M32); 10,000 (M40 - M63)
• no maintenance co cycles : 10,000 (M08 - M32); 5,000 (M40 - M63) Electrical endurance :
• with maintenance co cycles (440 V) : 10,000 (M08 - M16); 9,000 (M20); 8,000 (M25); 4,000 (M32); 3,000 (M40 - M50); 2,000 (M63)
Customer Training - Freddy Suhartono - May 2000 - English 5
Front face1. Opening push-button (0)
2. Closing push-button (I)
3. Keylock for “connected”, “disconnected” or “test” position
4. Door interlock
5. Stored-energy-mechanism charging handle
6. Operations counter
7. “Open” position keylock
8. Racking handle storage
9. Functional position indicator: “connected”, “test” and “disconnected”
10. Controls on fixed chassis
11. Padlocking facilities for “connected”, “disconnected” or “test” position
12. Stored-energy-mechanism status indicator
13. Main-contact position indicator
14. Fault trip indicator/breaker reset button
Stored energy status:
Customer Training - Freddy Suhartono - May 2000 - English 6
Frame size
AC circuit breaker:• Masterpact has 4 frames size, they are
M08 up to M32, M40, M50, and M63.• Common height and depth from 800 A to
6300 A. DC circuit breaker:
• Masterpact has 5 frames size, they are M10 up to M32, M40, M50, M63, and M80.
• Common height and length from 1000 to 4000 A for operational voltages greater than 500 VDC.
Customer Training - Freddy Suhartono - May 2000 - English 7
Drawout version
1. Arc chute cover
2. Auxiliary terminal shield
3. Auxiliary connection block
4. Fixed chassis
5. Safety shutters
6. Arc chute
7. Remote control voltage release
8. Motor for electrical charging of stored energy mechanism
9. Control unit (AC system)
10. Front cover
Customer Training - Freddy Suhartono - May 2000 - English 8
Safety and reliability Reduced, simple maintenance; Double insulation from the front face; Positive contact indication; Auxiliary devices can be fitted on site without adjustment A trip interlock ensures that the circuit breaker is open during connection and
disconnection Connection to top or bottom terminal Fully tropicalised as standard
Customer Training - Freddy Suhartono - May 2000 - English 9
Stored energy operating mechanism
Masterpact circuit breakers are operated via a stored energy mechanism for instantaneous opening and closing.
The mechanism is charged either manually or electrically.
Closing and opening operations can be initiated either from the local push buttons on the circuit breaker front face, or by remote control.
Customer Training - Freddy Suhartono - May 2000 - English 10
Other possibilities
Fixed circuit breakerThe fixed circuit breaker is derived from the moving part of the drawout circuit breaker by adding a fixing bracket on each side.
1000 VAC circuit breakers. Source changeover system (two solutions) :
• Mechanical interlocking for 2 or 3 circuit breakers• Automatic source-changeover controller, easy to implement on any
two suitably equipped circuit breakers (electrically charged operating mechanism, etc)
Customer Training - Freddy Suhartono - May 2000 - English 11
Device identification
Breaking capacity :• N1 : standard;• H1 : H2 : high performance• L1 : current limiting• DC : direct currentRating :• Rated current / 100Family :• Masterpact: LV power air circuit breaker
M 20 H1
Customer Training - Freddy Suhartono - May 2000 - English 12
Conformity with standard
Ui: rated insulation voltage Ue: rated operational voltage Icu: ultimate breaking capacity, for various values of the rated
operational voltage Ue Ics: service breaking capacity Icw: short-time withstand current
Customer Training - Freddy Suhartono - May 2000 - English 13
Degree protection
Circuit breaker installed free standing: IP30-5
Circuit breaker installed in a cabinet with access to controls through a door cut-out: IP40-5
Circuit breaker installed in a cabinet behind a door with a cut-out fitted with a sealed, transparent cover: IP54-9
Customer Training - Freddy Suhartono - May 2000 - English 14
Control unit selection
Masterpact M08 to M63 circuit breakers are equipped with microprocessor based electronic control units.
All the protected functions are powered by the AC system and no auxiliary power supply is required.
Each control unit of the Masterpact range corresponds to a certain type of application (instantaneous, distribution, selective, universal).
All the STR control units measure the true rms value of the current and are therefore not affected by harmonics that may be present on the system.
Customer Training - Freddy Suhartono - May 2000 - English 16
Auxiliaries Electrical operating mechanism
Added to the manual charging mechanism, a motor charges and automatically recharges the stored-energy spring upon breaker closing making possible fast O-C-O cycles.
Operation counterWith gear-motor option only. The operation counter is read from the front and gives the total number of breaker operating cycles.
ReleasesTwo types of voltage release: undervoltage release (MN [instantaneous] & time delayed [MNR) and shunt release (MX)]. For undervoltage release, the breaker will open, If the supply voltage drops between 35% and 70% of Un. Closing is possible when release voltage reaches 85% Un.
Closing releaseThis device releases the breaker closing mechanism when the spring is charged.
Customer Training - Freddy Suhartono - May 2000 - English 17
Accesories Auxiliaries switches
Three auxiliary switch blocks are standard - 4 contacts (O), optional - 4 directly-operated double break changeover switches (OF), optional - 24 additional changeover switches (OFSUP block).
Ready to close contact (PF)This contact indicates the breaker is open, the stored-energy mechanism is charged, the mechanism is correctly reset, the breaker opening pushbutton is not locked, no opening order is present.
Spring charged contact (CH)In addition to the local mechanical indicator and the “ready to close” contact, the gear-motor limit switch changeover contact can indicate that the operating mechanism is ready (spring charged).
Fault trip indication (SDE) Safety shutters (VO)
Mounted on the fixed portion of drawout breakers, the safety shutters automatically block access to the disconnection contacts
when the breaker is in the disconnected or test position (IP20). Shutter lock (VVC)
To lock the shutters in the closed position and hold the shutters in the open position.
Customer Training - Freddy Suhartono - May 2000 - English 18
Accesories Arc chute cover (CC)
This cover eliminates the safety clearance requirement above the breaker.
Terminal shield (CB)This cover prevents access to the electrical auxiliary connection terminals.
Interphase barries (EIP)The insulated partitions for vertical installation between
connection pads to reinforce insulation at connection points and to prevent arc propagation in the event of a line side
fault Partitioning fixture (AC)
Attached to the fixed portion of drawout breakers. This fixture provides IP30 partitioning between breaker compartment and
connection zone. Door frame (CDP)
This frame provides an equipment seal function (IP405). Suitable for fixed and drawout patterns.
Transparent cover (CCP)This is designed for the door frame (CDP). It provides a
degree of protection of IP549. Suitable for fixed and drawout patterns.
Customer Training - Freddy Suhartono - May 2000 - English 19
Accessories Auxiliaries for fixed version
Connection by one or two plugs, disconnectable and accessible from the front.
Auxiliaries for fixed versionThe breaker auxiliary circuits are connected by connection
blocks that operate automatically to isolate the auxiliaries when breaker is in “disconnected” position.
Breaker mismatch protectionFor drawout version only, this systems allows only correctly matched breakers (rating, type wiring, etc.) to be inserted in a given fixed frame.
Earth protectionThe earth connection terminal (drawout pattern) is on the left
hand side of the chassis. It’s marked with the symbol . Push button locking device
This padlockable device (padlocks not supplied) prevents direct operation of the circuit breaker by covering the “on” and “off” pushbuttons.
“Off” position locking deviceA Profalux key lock locks the breaker in “off” position by holding the pushbutton in its depressed position.
Customer Training - Freddy Suhartono - May 2000 - English 21
Automatic source-changeover systems
Masterpact source-changeover systems can be used to implement various configurations involving several incoming feeders.
The two or three Masterpact CB or switch-disconnectors used are mechanically interlocked to prevent certain combinations of operations.
The devices may be arranged :• Vertically, I.e stack-mounted and interconnected by a set of rods;• Horizontally (two only), I.e side by side and interconnected by a set of
cables.
Customer Training - Freddy Suhartono - May 2000 - English 22
Automatic source-changeover systems with 2 devices
A Masterpact automatic source-changeover system with 2 devices is made up of :
• CB QN connected to the “Normal” source
• CB QR connected to the “Replacement” source
• Mechanical interlocking system by rods or cables; Automatic control of the system can be provided by
adding :
• Electrical interlocking unit IVE
• Auxiliaries control plate ACP
• Controller BA or UA Each Masterpact CB is equipped with :
• a motor mechanism
• a shunt release (MX)
• a ready to close contact (PF)
• a block of 4 changeover switches (OF)
• an additional terminal block (BS) and a block of 4 connected position switches (CE) for source-changeover systems made up of drawout breakers.
Customer Training - Freddy Suhartono - May 2000 - English 23
Automatic source-changeover systems with 3 devices
A Masterpact automatic source-changeover system with 3 devices up of :
• 2 CB QN1 and QN2 connected to the “Normal” source;
• CB QR connected to the “Replacement” source;
• Mechanical interlocking system by rods; For such applications (consult us) automatic control of the
system can be provided by adding :
• 2 electrical interlocking unit IVE
• auxiliaries control plate ACP
• controller BA or UA Each Masterpact CB is equipped with :
• a motor mechanism
• a shunt release (MX)
• a ready to close contact (PF)
• a block of 4 changeover switches (OF)
• an additional terminal block (BS) and a block of 4 connected position switches (CE) for source-changeover systems made up of drawout breakers.
Customer Training - Freddy Suhartono - May 2000 - English 24
Automatic source-changeover systemscontroller option selection
Installation Mounted directly on the auxiliaries control
plate ACP.
Used together with the auxiliaries control plate ACP, controller BA and UA initiate the automatic changeover operations according to the status of the “Normal” and “Replacement” sources.
Mounted on the front of the switchboard. The distance between the controller and the auxiliaries control plate must not exceed 2 m.
Customer Training - Freddy Suhartono - May 2000 - English 25
Automatic source-changeover systemscontroller option selection (controller BA)
Controller BA can be used with Masterpact CB to implement a straight forward automatic source-changeover system.
Electrical characteristicsPower is supplied from the auxiliaries control plate ACP. The same voltage must be used to supply the ACP plate, the IVE unit and the CB motor mechanisms. Otherwise, BC type or equivalent isolation transformer must be used.
Operationa four-position switch can be used to select: automatic operation, forced operation on source N, forced operation on source R, and stop.Adjustment of time delays in front:
• t1 = time delay before QN opens when the voltage UN of the Normal source disappears, it can be adjusted from 0.1 to 30 sec.
• t2 = time delay before QR opens when the voltage UN of the Normal source is restored, it can be adjusted from 0.1 to 240 sec.
CB status indication on the front of the controller: on, off, fault trip.
Customer Training - Freddy Suhartono - May 2000 - English 26
Automatic source-changeover systemscontroller option selection (controller UA)
Controller UA offers the following automatic functions: • switching from one source to another depending on the presence of voltage UN
on the Normal source• control of an engine generating set• shedding and reconnection of non-priority circuits• switching to the Replacement source in the event of a failure on one of the
phases of the Normal source Electrical characteristics
Power is supplied from the auxiliaries control plate ACP. The same voltage must be used to supply the ACP plate, the IVE unit and the CB motor mechanisms. Otherwise, BC type or equivalent isolation transformer must be used.
Customer Training - Freddy Suhartono - May 2000 - English 27
End presentation