MASTER^ - inis.iaea.org · Table 1. The CCW heat exchangers are one-pass, shell-and-tube heat...

45
^ / FLOW-INDUCED VIBRATION OF COMPONENT COOLING WATER HEAT EXCHANGERS* CONP-900617—1 ^ DE90 003789 Y. S. Yeh and S. S. Chen** Nuclear Engineering Department Taiwan Power Company Taiwan, Republic of China **Materials and Components Technology Division Argonne National Laboratory Argonne, Illinois USA SUMMARY This paper presents an evaluation of flow-induced vibration problems of component cooling water heat exchangers in one of Taipower's nuclear power stations. Specifically, it describes flow-induced vibration phenomena, tests to identify the excitation mechanisms, measurement of response characteristics, analyses to predict tube response and wear, various design alterations, and modifications of the original design. Several unique features associated with the heat exchangers are demonstrated, including energy-trapping modes, existence of tube-support-plate (TSP)-inactive modes, and fluidelastic instability of TSP- active and -inactive modes. On the basis of this evaluation, the difficulties and future research needs for the evaluation of heat exchangers are identified. * Paper to be submitted for presentation at the ASME Pressure Vessel and Piping Conference, Nashville, Tennessee, June 17-21, 1990. MASTER^ DISTRIBUTION OF THIS DOCUMENT IS UNLIMITED The submitted manuscript has been authored by a contractor of the U. S. Government under contract No. W-31-109-ENG-38. Accordingly, the U. S. Government retains a nonexclusive, royalty-free license to publish or reproduce the published form of this contribution, or allow others to do so, tor U. S. Government purposes.

Transcript of MASTER^ - inis.iaea.org · Table 1. The CCW heat exchangers are one-pass, shell-and-tube heat...

  • ^ /

    FLOW-INDUCED VIBRATION OF COMPONENT COOLING WATER

    HEAT EXCHANGERS*

    CONP-900617—1

    ^ DE90 003789

    Y. S. Yeh and S. S. Chen**

    Nuclear Engineering DepartmentTaiwan Power Company

    Taiwan, Republic of China

    **Materials and Components Technology DivisionArgonne National Laboratory

    Argonne, Illinois USA

    SUMMARY

    This paper presents an evaluation of flow-induced vibration problems of

    component cooling water heat exchangers in one of Taipower's nuclear power

    stations. Specifically, it describes flow-induced vibration phenomena, tests to

    identify the excitation mechanisms, measurement of response characteristics,

    analyses to predict tube response and wear, various design alterations, and

    modifications of the original design. Several unique features associated with the

    heat exchangers are demonstrated, including energy-trapping modes, existence

    of tube-support-plate (TSP)-inactive modes, and fluidelastic instability of TSP-

    active and -inactive modes. On the basis of this evaluation, the difficulties and

    future research needs for the evaluation of heat exchangers are identified.

    * Paper to be submitted for presentation at the ASME Pressure Vessel and Piping

    Conference, Nashville, Tennessee, June 17-21, 1990.

    M A S T E R ^DISTRIBUTION OF THIS DOCUMENT IS UNLIMITED

    The submitted manuscript has been authoredby a contractor of the U. S. Governmentunder contract No. W-31-109-ENG-38.Accordingly, the U. S. Government retains anonexclusive, royalty-free license to publishor reproduce the published form of thiscontribution, or allow others to do so, torU. S. Government purposes.

  • 1. Introduction

    The Maanshan Nuclear Power Station contains two trains of component

    cooling-water (CCW) heat exchangers for each of two reactors. Trains A and B of

    Unit 1 were placed in service in December 1982 and January 1983, respectively.

    Tube leakage in both heat exchangers was discovered in March 1983, after only a

    few months of operation. Damage was noticed at tube supports and midspan

    regions. This was the beginning of a series of steps taken by Taiwan Power

    Company (Taipower) to resolve the problem. A brief history is presented in

    Table 1.

    The CCW heat exchangers are one-pass, shell-and-tube heat exchangers

    with sea water in the tube side and hot demineralized water in the shellside. A

    schematic diagram of the heat exchanger is given in Fig. 1. Each exchanger

    contains 3,488 tubes contained in a 66-in. (i.d.) circular cylindrical shell. The two

    tube sheets are 1.75-in. aluminum-bronze plates, and two types of baffle plates are

    0.625-in. carbon steel plates; four are segmental baffle plates with a single

    horizontal cut, and ten are support plates with double horizontal cuts as shown in

    Fig. 1.

    A 36-in. (o.d.) circular impingement plate was installed at the inlet to

    distribute the incoming flow to the first three passes. All heat exchanger tubes

    are cupronickel with 0.75-in. o.d. and 0.049-in. wall thickness. The tubes are

    arranged in a rotated triangular pattern with a pitch of 15/16-in.

  • 2. Tube Damage

    2.1 Initial Inspection

    In March 1983, after a few months of operation, 14 tubes were found

    damaged in Train A and 4 in Train B. All damaged tubes had flat spots

    developing in the first and second baffle plates next to the inlet nozzle. These flat

    spots are 6-24 inches long. A damaged tube in Train A developed a 4-in. long

    crack along a 24-in. flat spot, and a damaged tube in Train B was severed at the

    second support plate. All damaged tubes were located in the inlet area.

    Apparently, the high flow velocity in the nozzle caused large tube motion that

    resulted in tube damage. The flat spots were caused by tubes colliding with each

    other.

    In February 1984, the manufacturer of the CCW heat exchangers, Struthers-

    Wells Corp. (SWC), completed initial modifications of both CCW heat exchangers

    in Unit 1. The modifications included removing 420 tubes from each heat

    exchanger. No damage inspection was performed when they were removed and

    placed in groups in an open field.

    In March 1984, the first five spans were inspected for flat spots between the

    supports and ring-type markings at tube supports. If no damage was found in the

    first five spans, the tube was considered undamaged. If damage was observed in

    these five spans, inspection continued to the subsequent spans until no further

    damage was found. Figure 2 shows the results of the damage inspection. Among

    396 inspected tubes in Train A and 400 in Train B, 36 tubes in Train A and 28 in

  • Train B were damaged. Twenty tubes in Train A and 16 in Train B contained flat-

    spot damage between the first two baffle plates.

    2.2 Damage Inspection of Selected Tubes

    In July 1984, 28 tubes from each heat exchanger in Unit 1 were selected for

    evaluation of the extent and distribution of tube damage. Figure 3 shows the

    location of the tubes selected from each heat exchanger. In contrast to the tubes

    near the nozzle, most damage occurred at the supports and baffles. Only one tube

    from Train A showed flat-spot damage. In general, most of the damage was in

    the first three supports. However, several tubes showed damage only at the

    middle supports, e.g., supports 5 through 9. This damage pattern shows that

    tubes located in regions other than near the nozzle are also subjected to

    unacceptable vibration.

    From the damage inspection, several general conclusions can be made:

    • Excessive flow-induced vibrations were noted in both Trains A and B.

    • Tube-to-tube impacts appear between the first two baffles.

    • Damage at supports occurs in various regions of the tube array and at

    different axial locations.

    It is apparent that the original design of the heat exchanger is inadequate

    from the standpoint of flow-induced vibration. The mechanism causing such

    large tube vibration is due to fluidelastic instability.

  • 3. Vibration Tests of CCW Heat Exchangers by Bechtel Group, Inc.

    3.1 Phase-1 Tests

    Two modifications were made in accordance with the manufacturer's

    recommendations after the initial report of tube damage: (1) removing 420 tubes

    from each train. [One hundred fourteen removed tubes were not replaced and the

    holes were left in the baffles; supports and tube sheets were plugged. The rest of

    the tubes were replaced by BWG 12 tubes (0.75-in. o.d. and 0.109-in. wall

    thickness.)]; and (2) replacing the original impingement plate at the inlet (a 36-in.

    diameter, 3/8-in. thick stainless steel plate welded to tie bars and a support plate)

    by a flow deflector. Bechtel Group, Inc. performed tests on the modified heat

    exchanger [1].

    Eighteen tubes were selected for measurement. Two accelerometers were

    embedded in each pod and inserted inside the selected tubes to measure tube

    accelerations in two perpendicular directions at midspans. Three additional

    accelerometers were placed on the outside shell.

    After properly checking all accelerometers, flow tests were performed at a

    series of flow rates, varying from zero to the rated flow of 127,000 gpm. A 14-

    channel FM-type recorder was used to store the accelerations.

    Analysis of the data includes time-domain data, frequency spectra, and

    vibration amplitude.

  • 3.1.1 Time-Domain Data

    The data on acceleration-time plots revealed that

    • Low-level background vibration of about 0.25 g peak-to-peak existed at

    zero flow due to other equipment.

    • Tube accelerations increased with flow velocity, reaching a magnitude

    of 10 g peak-to-peak (p-p) at 127,000 gpm.

    • Impact signrls were noted for flow above 7,000 gpm.

    • The impact signals, occurring right at the peak of the vibration

    waveform, indicate a direct impact at the accelerometer pod location.

    In addition, the accelerations were doubly integrated to obtain tube

    displacements. Figure 4 shows the tube displacements (p-p) as a function of flow

    rate for nine tubes.

    3.1.2 Frequency Spactra

    Typical frequency spectra are shown in Fig. 5. The following general

    characteristics are noted:

    • Tube responses at low flow rate are broadband, indicating that the

    excitation is turbulent buffeting.

  • • As the flow velocity increases, the major frequencies are located in two

    regions, i.e., at 21-24 and 26-32 Hz.

    3.1.3 Monitoring of SheU Vibration

    Three shell accelerometers were installed on the external surface of the heat

    exchanger to supplement the internally mounted accelerometers. At 6,000 gpm,

    faint impact sounds could be heard at the first baffle location. At 7,000 gpm,

    clean, but still faint, impact sounds could be heard at the second support and first

    baffle. At 8,000 gpm, sound intensities increased noticeably. At 12,000 gpm, the

    impact sounds became more frequent and much stronger.

    The heat exchanger was tested again with the flow deflector rotated 180

    degrees. The objective was to obtain vibration response under a new shellside

    inlet condition. The test was conducted in February 1984 with flow rates at 7,000,

    10,000, and 12,000 gpm. Tube responses were comparable with those of the

    original test. However, the flow deflector did change the details of tube response.

    3.1.4 Conclusions and Recommendations

    When the shellside flow rate exceeded 7,000 gpm, the modified CCW heat

    exchanger experienced severe tube vibration. Some of the tubes are subjected to

    fiuidelastic instability at the rated flow of 12,700 gpm. The modifications

    recommended by the manufacturer are inadequate. Meanwhile, it is

    recommended that the following steps be taken before a final resolution of the

    problem is reached.

  • 8

    • Operate the heat exchangers at flow rates not to exceed 6,000 gpm

    whenever possible.

    • Implement a surveillance program to detect leakage and inspect tube

    damage before final modification.

    • Investigate measures to resolve the problem, (e.g., improve flow velocity

    distribution by adding inlet and outlet nozzles, and increase tube natural

    frequencies by adding tube supports, in particular, in the inlet and outlet

    regions.

    • Evaluate the feasibility of replacing the existing units with a better

    design.

    3.2 Phase-2 Tests

    Additional modifications to the heat exchangers were made as a result of the

    Phase-1 tests. The modifications included staking the bottom 14 tube rows in

    Bays 1, 2, and 3, and installing perforated plates in Bays 2 and 3. Two large cuts

    were made to implement these modifications in June 1984.

    • The first bay was staked at midspan and the second and third bays were

    staked at the 1/3 and 2/3 points of each span. Staking strips of carbon

    steel with a width of 0.75-in. and a thickness of 60 mils were wedged

    horizontally between adjacent tube rows.

  • • A plate, 43 x 45 x 3/8 inches, with 3/8-in. diameter holes on a 13/16-in.

    staggered pitch, resulting in 19% open area, was installed in Bajr 2.

    • Two perforated plates were installed in Bays 2 and 3; a top plate

    contained 1/2-in. diameter holes on a 1-in. staggered pitch (22% open

    area) and a bottom plate contained 7/16-in. diameter holes on a 1-in.

    staggered pitch (17% open area). All plates were stainless steel sheets

    3/8-in. thick.

    The Phase-2 vibration tests were a continuation of the Phase-1 test. The test

    procedure, instrumentation, and data analysis are the same as those in Phase 1.

    Accelerometers used for Phase 1 were used, to the extent feasible, for Phase 2

    tests. Twenty-eight additional acceleronieters were procured for Phase 2 [2].

    To guide the selection of suitable locations for installing accelerometers, and

    to assist the interpretation of test results, natural frequencies of selected tubes

    were calculated.

    The test results were summarized as follows:

    • Tube impact signals are noted at high flow velocity.

    • Response of the unstaked tubes in the frequency range of 20 to 55 Hz was

    excited at flow rates of 6,100 gpm and above. The only tube that was

    instrumented and staked detected prominent tube response at 129 Hz.

    • The largest tube motion was about 15 mils.

  • 10

    Tube vibration amplitudes increase with increasing shell side flow velocity.

    At the maximum flow rate of 12,700 gpm, the peak acceleration amplitude was

    about 1.2 g, which was considerably lower than the 15 g in Phase-1 tests. The

    maximum tube displacement was about 30 mils, peak to peak; tube collision at

    midspan is unlikely. Impacts were noted for flow over 9,000 gpm. Tube wear is

    still possible, and the long-term effect is uncertain. Under the described

    conditions, it is recommended that flow rate be restricted to 9,000 gpm, a rigorous

    surveillance and maintenance program be implemented, and sources be located

    for replacement heat exchangers.

    After the Phase-2 test, Taipower decided to replace two CCW heat exchangers

    with a new design, and modify the other two trains. The new design has a 15-in.

    tube span and it is not expected to have any flow-induced vibration problems. The

    other two trains were modified as follows by Taiwan Machinery Manufacturing

    Corp. (TMMC) on the basis of a recommendation of a French consulting firm:

    • The inlet region was changed from the original three passes to seven

    passes.

    • The outer shell diameter was increased.

    The modified heat exchanger is shown in Fig. 6 After completion of the

    modification by TMMC, flow tests were conducted by Loutech Taiwan, Inc. [3].

  • 11

    4. Analysis and Vibration Tests of Modified Heat Exchangers

    4.1 Tests by Loutech Taiwan, Inc.

    To verify the severity of vibration and structural integrity, Loutech Taiwan,

    Inc., performed a flow test in September 1988. Twenty-five tubes were

    instrumented with two accelerometers each to measure the accelerations in two

    perpendicular directions. The instrumented tubes and the fisial locations are

    given in Fig. 7.

    Four types of plots were obtained from the data from each accelerometer:

    • Overall tube displacement versus time: the peak amplitudes at each of

    147 time intervals within 110 seconds.

    • Average spectra of tube displacements: average spectra for 0 to 147 Hz.

    • Peakhold spectra: the peaks of all spectra from 0 to 147 Hz.

    • Frequency spectra versus time: frequency spectra of different tubes as

    function of time.

    Figure 8 shows typical average frequency spectra for a series of flow rates

    and Figs. 9 and 10 show the frequency spectra as a function of time.

    One method to determine the response characteristics and the critical flow

    velocity is to plot tube displacement as a function of flow rate. The most frequently

  • 12

    used tube response is the rms value of *abe response (acceleration, velocity, or

    displacement). Loutech did not provide rms values of tube displacements.

    Alternatively, the peak values are presented. Figures 11 to 13 show the peak tube

    displacements as a function of flow rate in logarithmic scale for selected tubes,

    where H and V are used to indicate horizontal and vertical components

    respectively.

    4.2 Natural Frequencies: ISP-active and-inactive Modes

    The natural frequencies of the tubes are very important for the interpretation

    of tube response data. A free-vibration analysis was performed for different cases.

    CCW heat exchanger tubes, fixed to the tube sheets at the two ends, were

    supported by 14 tube-support plates (TSP), see Fig. 14. To facilitate assembly and

    relative motion caused by thermal expansion, holes in the TSP were made larger

    than the tube diameters. It is not uncommon for tube holes to be drilled 0.4 to

    0.8 mm larger than the outside diameter of the tubes. In this case, the magnitude

    of the clearance was not known. Owing to the clearance, TSP? may not provide

    support in some cases. Therefore, there are two types of modes: TSP-active and

    TSP-inactive

    Current design practices consider the heat exchanger tubes to be simply

    supported, without clearances, at the TSPs. For small clearances, this

    assumption is expected to be applicable; the tube will respond as a continuous

    beam supported by all TSPs, and anti-nodes of all modes do not appear at the

    TSPs. This type of mode is called "TSP-active." Studies show that this

    assumption is indeed applicable if the clearance is small [4-7], although there are

  • 13

    some variations of resonant frequencies. With this assumption, the simple beam

    theory can be used to predict tube natural frequencies, as well as tube responses to

    different excitations.

    When the clearance is relatively large, the tube will rattle inside some of the

    TSP holes for small-amplitude oscillations. This type of mode, in which some

    TSPs do not provide effective supports, is called "TSP-inactive.:i

    For intermediate clearances, the tube response will depend strongly on the

    excitation amplitude. For low excitations, the tube will vibrate within the

    clearance gap (TSP-inactive modes). For large excitations, the tube will be in

    contact with all TSPs most of the time (TSP-active modes). In reality, the tube

    response will be composed of both TSP-active and TSP-inactive modes.

    A typical CCW heat exchanger tube was analyzed for the TSP-active and

    -inactive modes. Table 2 shows the natural frequencies of TSP-active and -inactive

    modes for different cases. The characteristics of Tube BWG 12, presented in this

    paper, are similar to those of Tube BWG 18 except that the natural frequencies of

    Tube BWG 18 are a little lower. As an example, the natural frequencies of TSP-

    active modes of two tubes are compared in Table 3. The difference in natural

    frequencies of the two tubes for the TSP-active mode is small; this is also true for

    TSP-inactive modes.

    Two different situations are considered for TSP-inactive modes: a particular

    TSP, such as TSP 2, being inactive, and two TSPs, such as TSPs 2 and 4, being,

    inactive.

  • 14

    Figure 14 shows the tube and all TSPs. The TSP-active modes are given in

    Fig. 15 for the first five modes. The results agree well with those obtained by

    Bechtel [2]. Figure 16 shows the first five modes when TSP 2 is inactive, and Fig.

    17 shows the first two modes when two TSPs are inactive.

    Among the TSP-inactive modes, some of the modes are dominant in specific

    spans; these modes are called energy-trapping modes [8]. For example, Fig. 18

    shows the lowest TSP-inactive modes for different cases. These modes are the

    most important ones when one TSP is inactive.

    43 Tube Response Characteristics

    Among the information that is most important for the interpretation of the

    daca is the natural frequency of the tubes. Based on the results presented in Table

    2 and Figs. 15-18, we can construct frequency bands for tube BWG 12, as shown in

    Fig. 19. These frequency bands are plotted on the assumption that only one

    support is inactive. Experimental data show that those modes associated with

    more than two inactive supports are not significant. Two types of frequency

    bands, passing and stopping, can be constructed. Within a passing band, waves

    can propagate freely through each tube support; however, within a stopping band,

    waves will be attenuated as they travel from one support to the next. All natural

    frequencies are in the passing bands only. In a stopping band, since no natural

    frequencies exist within that frequency range, tube response will be very small.

    Figure 19 shows the approximate boundaries of the first two stopping and passing

    bands:

    First Stopping Band 0 - 9.5 Hz

  • 15

    First Passing Band 9.5 - 73 Hz

    Second Stopping Band 73 - 95 Hz

    Second Passing Band 95 - 176 Hz

    The first passing band is approximately between 9.5 and 73 Hz; therefore, the

    dominant tube response is expected to be in this frequency range. In addition, the

    first TSP-active mode is at 23.9 Hz; any frequencies below this are the energy-

    trapping modes associated with TSP-inactive modes. The first two stopping bands

    are approximately between 0 and 9.5 Hz and 73 and 95 Hz; in these two frequency

    bands, we expect that the tube response will be very small.

    Based on the experimental data and analytical results, some general

    observations can be made.

    TSP-inactive modes contribute significantly to tube response. It can be seen

    from the frequency spectra that TSP-inactive modes, whose frequencies are lower

    than that of the first TSP-active mode of approximately 23 Hz, contribute

    significantly to the response.

    Some of the tubes are subjected to fiuidelastic instability of TSP-inactive

    modes. For example, let us consider Tube 11C. The frequency spectra for Tube

    11C are given in Fig. 8 for various flow rates. When the flow rate is increased

    from 10,000 gpm to 145,000 gpm, the contribution of TSP-inactive modes increases;

    at 14,000 and 14,500 gpm, TSP-inactive modes are dominant. Furthermore, Fig.

    13 shows that the slope of the response curve is much larger than 2, an indication

    that the tube is subjected to fiuidelastic instability associated with TSP-inactive

    modes.

  • 16

    The response of various tubes is different and the response of each tube

    changes with flow rate. The key parameter in this case is the clearance between

    the tube and TSP holes. As flow rate changes, the tube configurations also

    change, i.e., the contact points of the tubes with TSPs changes with flow rate due

    to the change in drag and lift forces.

    The motion of Tube 5B is the largest of all instrumented tubes associated with

    TSP-active and -inactive modes; however, the TSP-inactive modes are not the

    dominant mode of the response. The large amplitudes are believed to be

    attributable to the high local flow velocity. The tube is not subjected to fluidelastic

    instability.

    Based on the frequency band presented in Fig. 19, the dominant mode of each

    tube at different flow rates can easily be identified from the spectra.

    The response of all tubes is contained in the first passing band; this is in

    agreement with the frequency band consideration. The modes include TSP-active

    and -inactive modes. In some cases, the frequencies of the active and inactive

    modes can be seen clearly in the spectra. As an example, the frequency spectra of

    Tubes 1A-H and 2A-H are given in Fig. 9, the lower frequency peaks are TSP-

    inactive modes and the higher peaks are TSP-active modes. In some other cases,

    only TSP-inactive or TSP-active modes dominate; see Fig. 10 for typical examples.

    Among the instrumented tubes, the displacements of the tubes in the first

    row in the inlet region are the largest. This can easily be seen by comparing the

    displacements of tubes in different locations.

  • 17

    The tube displacements in the inlet regions are larger than those in the outlet

    region. In addition, the spans close to the inlet nozzle (accelerometer groups B

    and C) have larger displacements than spans further av/ay from the inlet nozzle.

    The main characteristics of the tube responses are

    • TSP-inactive modes are important since some of them are subjected to

    fluidelastic instability.

    • Fluidelastic instability of TSP-active modes does not occur.

    • Tube characteristics (support conditions) change with flow rate.

    • The tubes located in the front row in the inlet region have larger

    displacements.

    • Tube wear may be important owing to the impact/sliding associated with

    fluidelastic instability of TSP-inactive modes and turbulence excitation of

    TSP-active and -inactive modes.

    4.4 Fluidelastic Instability and Wear

    From the experimental data, it is noted that fluidelastic instability may

    occur, depending on the modes. The critical flow velocities for different cases

    were calculated. The flow velocity distribution is not known. Assuming a

    uniform flow velocity distribution, the flow velocity is 1.16 ft/sec at 12,700 gpm.

  • 18

    The mass-damping parameter is 0.24, assuming a damping ratio of 1%.

    Therefore, the reduced flow velocity is 0.84 and 1.84 for TSP-active and TSP-

    inactive modes, respectively. On the basis of the existing correlations [9,10], the

    critical reduced flow velocity ranges from 1.1 to 2.2, On the basis of the existing

    correlations, we expect the tubes are not subjected to fluidelastic instability of TSP-

    active modes, but may be subjected to fluidelastic instability of TSP-inactive

    modes. This is in agreement with the experimental data.

    In the original design, the incoming fluid passes across three passes only;

    the reduced flow velocity at 12,700 gpm is 1.96 and 4.29 for TSP-active and TSP-

    inactive modes, respectively. Therefore, the tubes are subjected to fluidelastic

    instability of TSP-inactive modes and some of the tubes are subjected to fluidelastic

    instability of TSP-active modes. The instability of the TSP-active modes had

    caused tube damage in the original design.

    Once the tubes are subjected to fluidelastic instability of TSP-active modes,

    they are not acceptable from the standpoint of flow-induced vibration and it is not

    necessary to calculate wear rate because tube leaks will occur within a very short

    time of operation. On the contrary, when the tubes are subjected to fluidelastic

    instability of TSP-inactive modes, the wear rate is much smaller and its

    significance depends on many other parameters. In general, it is difficult to

    predict tube wear under such conditions. In CCW heat exchangers, several

    important parameters, such as clearance, flow velocity distribution, and wear

    rate, are not known. It is impossible to predict tube wear with confidence.

    However, as an exercise, tube wear was calculated by means of the approach

    taken by Connors [11]. If a wear coefficient of 600 and clearance of 25 mils are

    used in the calculations, it is concluded that it will take about 16 years for a tube to

  • 19

    wear through. This wear calculation is not accurate and only gives an estimate of

    order of magnitude.

    5. CONCLUSIONS

    On the basis of this evaluation, we have concluded the following:

    In the original design, the flow velocity was larger than the critical flow

    velocity; therefore, the tubes were subjected to the fiuidelastic instability of TSP-

    active modes. The original design was not acceptable and the observed damage

    was due to fluidelastic instability.

    In the extensively modified version, the tubes are not subjected to the

    fluidelastic instability associated with TSP-active modes. Therefore, occurrence of

    tube leaks caused by flow-induced vibration is not expected to occur during short-

    term operation. Based on the tube response characteristics, it is believed that the

    clearance between the tubes and support plate holes is relatively large. Because of

    the clearance, wear will result from the sliding and impacting of the surfaces due

    to the oscillations associated with turbulence excitation and instability of TSP-

    inactive modes. When the unit is put in service, a surveillance program and

    follow-up work should be conducted to ensure the safety and predict the useful life

    of a unit.

    From the experience with CCW heat exchangers, it appears that the state of

    the art is such that more work remains to be done. Specifically, the following

    items should be emphasized:

  • 20

    • Flow Velocity Distribution. An efficient computer code to compute the

    flow velocity distribution for general heat exchangers would be very

    useful. Currently, few codes can be used for CCW heat exchangers.

    Unfortunately, more time and cost will be required to use these codes.

    • Wear Prediction. The state of the art is inadequate to predict tube wear.

    Very little information is available for wear associated with TSP-inactive

    modes and data for TSP-active modes are very limited. The detailed

    dynamics of tube/support interaction are still not well understood.

    • Tube Response and Prediction of Stability. Methods are available to

    predict the critical flow velocity of fluidelastic instability and tube

    response to various excitations. However, the methods require further

    improvement.

    ACKNOWLEDGMENTS

    Tests of CCW Heat Exchangers were performed by Bechtel Group, Inc., and

    Loutech Taiwan, Inc.

    Many engineers in the Nuclear Engineering Department of Taiwan Power

    Company have contributed to various aspects of the program; among them are Y.

    H. Cheng, S. C. Cheng, T. K. Lee, P. C. Kao, F. Y. Lai, H. H. Lee, and P. F. Wang.

    This work was performed for Taiwan Power Company under an agreement

    with the U.S. Department of Energy under contract agreement 31-109-ENG-38-

    85847.

  • 21

    This work was performed for Taiwan Power Company under an agreement

    with the U.S. Department of Energy under contract agreement 31-109-ENG-38-

    85847.

    1. "Test Report: Vibration of Tubes in Component Cooling Water Heat

    Exchangers, Phase 1 Tests," Bechtel Group, Inc., San Francisco, CA,

    (September 1984).

    2. "Test Report: Vibration of Tubes in Component Cooling Water Heat

    Exchangers, Phase 2 Tests," Bechtel Group, Inc., San Francisco, CA,

    (October 1984).

    3. "Final Report on CCW Heat Exchanger Tube Vibration Test, Third Nuclear

    Power Station, Taiwan Power Company," by Loutech Taiwan, Inc.,

    (December 1988).

    4. Sebald, J. F., and Nobles, W. D., "Control of Tube Vibration in Steam

    Surface Condensers," Proc. Am. Power Conf., Vol. XXIV, 630-643 (1962).

    5. Moretti, P. M., and Lowery, R. L., "Heat Exchanger Tube Vibration

    Characteristics in a 'No Flow1 Condition," Final Report: Tubular

    Exchanger Manufacturers Association Experimental Program, Oklahoma

    State University (1973).

  • 22

    6. Shin, Y. S., Jendrzejczyk, J. A., and Wambsganss, M. W., "Effect of

    Tube/Support Interaction on the Tube Vibration of a Tube on Multiple

    Supports," Argonne National Laboratory, Technical Memorandum ANL-

    CT-77-5 (1977).

    7. Rogers, R. J., and Pick, R. J., "On the Dynamic Spatial Response of a Heat

    Exchanger Tube with Intermittent Baffle Contacts," Nucl. Eng. Des. 36, 81-

    90(1976).

    8. Chen, S. S., "Vibration of Continuous Pipes Conveying Fluid/' in Flow-

    Induced Structural Vibrations, ed. by E. Naudascher, IUTAM-IAHR

    Symposium, Karlsruhe, Germany, 1972, pp. 663-675.

    9. Pettigrew, M. J., Sylvestre, Y., and Campagna, A. O., "Vibration Analysis

    of Heat Exchanger and Steam Generator Designs," Nucl. Eng. Des. 48, 97-

    115(1978).

    10. Chen, S. S., Flow Induced Vibration of Circular Cylindrical Structures.

    Hemisphere Publishing Corp., 1987.

    11. Connors, H. J., "Flow-Induced Vibration and Wear of Steam Generator

    Tubes," Nucl. Technol., 33, 311-331 (1981).

    DISCLAIMER

    This report was prepared as an account of work sponsored by an agency of the United StatesGovernment. Neither the United States Government nor any agency thereof, nor any of theiremployees makes any warranty, express or implied, or assumes any legal liability or responsi-bility for the accuracy, completeness, or usefulness of . . , . information, apparatus, product, orprocess disclosed, or represents that its use would not infringe privately owned rights. Refer-ence herein to any specific commercial product, process, or service by trade name, trademarkmanufacturer, or otherwise does not necessarily constitute or imply its endorsement recom-mendation, or favoring by the United States Government or any agency thereof. The viewsand opinions of authors expressed herein do not necessarily state or reflect those of theUnited States Government or any agency thereof.

  • Table 1. History of CCW Heat Exchangers

    1. Trains A and B of Unit 1 were placed in service in December 1982, andJanuary 1983, respectively.

    2. Tube leakage was discovered in March 1983. Damage was found at supportsand midspans.

    3. The manufacturer's action taken after tube leakage:

    * Damage was considered to be attributable to inappropriate design of theinlet flow distributor.

    • Modifications, as follows, were recommended to alleviate the problem:

    a. Replacing the original flow impingement plate by a flow deflector.b. Replacing 306 tubes from each heat exchanger with heavier tubes (8WG

    12vs.BWG18).c. Eliminating 114 tubes from each heat exchanger and plugging the holes

    in the tubesheets and baffles.

    4. The CCW Heat Exchangers of Units 1 and 2 were placed in service in Januaryand February of 1984, respectively, after modifications were made in responseto manufacturer's recommendations.

    5. Bechtel Group, Inc. performed Phase-1 test.

    Test of Train A after modifications in February 1984. Six tubes at the inletregion and three tubes at the outlet region were instrumented.

    Train A was tested again with the flow deflector rotated 90 degrees.

    6. Additional modifications were recommended on the basis on the results of thePhase-1 test.

    Staking the bottom 14 tube rows in bays 1, 2 and 3.

    Installing perforated plates in bays 2 and 3.

  • 7. Modifications of Unit 2 were completed in June 1984, and those in Unit 1 werecompleted later.

    8. Bechtel Group, Inc. performed Phase-2 test in July 1984.

    Train B of Unit 2 and Train A of Unit 1 were tested.

    Train B of Unit 2 was retested.

    9. Taipower decided to order two new CCW heat exchangers and to modify two ofthe original CCW heat exchangers

    10. The modification of the original CCW heat exchanger was completed byTaiwan Machinery Manufacturing Corp. in 1988.

    11. Loutech Taiwan, Inc., performed tests on the modified Train B of Unit 1 inSeptember 1988.

    12. Taipower and Argonne National Laboratory performed an evaluation of CCWheat exchangers.

  • Table 2. Natural Frequencies in Hz of CCW Tubes

    All TSPsActive

    2.38B48E+012.47746E+012.61928E+012.80613E+013.02973E+013.28225E+013.55647E+013.84557E+014.14246E+014.43886E+014.72400E+014.98308E+015.19570E+015.33561E+015.416e8E+019.55004E+019.74398E+011.0O413E+02i,04170E+021.08504E+021.13254E+021.18294E+021.23513E+021.28796E+021.34005E+021.38959E+021.43402E+021.46972E+021.49222E+021.52036E+022.24451E+022.27477E+022.32095E+022.37882E+022.44457E+022.51509E+022.58773E+022.66008E+022.72974E+022.79427E+02

    TSP 2Inactive

    1.13053E+012.39328E+012.49449E+012.65018E+012.84452E+013.062Q9E+013.29786E+013.55885E+013.84635E+014.15166E+014.46243E+014.76359E+015.03460E+015.24556E+015.41605E+016.81634E+019.55977E+019.77727E+011.00993E+021.04873E+021.09095E+021.13550E+021.18346E+021.23522E+021.28941E+021.34393E+021.39611E+021.44234E+021.47717E+021.52035E+021.76043E+022.24604E+022.27996E+022.32972E+022.38855E+022.45133E+022.51733E+022.58778E+022.66092E+022.73303E+02

    TSP 3InactJve

    9.68389E+002.39275E+012.48674E+012.62322EI012.80663E+013.043B6E+013.32520E+013.63698E+013.96541E+014.28958E+014.54128E+014.72946E+014.99427E+015.22849E+015.41581E+016.49951E+019.55868E+019.76213E+011.00489E+021.04179E+021.08759E+021.14026E+021.19731E+021.25641E+021.31414E+021.35919E+021.39086E+021.43571E+021.47461E+021.52035E+021.70462E+022.24585E+022.27741E+022.32180E+022.37920E+022.44969E+022.52867E+022.61100E+022.69198E+022.76585E+02

    TSP 4Inactive

    9.53309E+002.39177E+012.47919E+012.62222E+012.B3474E+013.09982E+013.36640E+013.57155E+013.85633E+014.20758E+014.56757E+014.89305E+015.02601E+015.20820E+015.41540E+016.43080E+019.55670E+019.74738E+011.00469E+021.04707E+021.09784E+021.14751E+021.18557E+021.23706E+021.29952E+021.36271E+021.41933E+021.44225E+021.47154E+021.52034E+021.69312E+022.24553E+022.27520E+02 .?.32211E+022.38809E+022.4652BE+022.53571E+022.58937E+022.66472E+022.74758E-I-02

    9222233334445,5,5,6,9.9.1.1.1.1.1.1.1.1.1.1.1.1.1,2.2.2.2.2.2.2.2.2.

    TSP 5Inactive

    .51959E+00

    .39064E+01

    .47765E+0I

    . 63923E-I01

    .86230E101

    .05253E+01

    .29078E+01

    .6315SE+01

    .97486E+01

    .16079E+01

    . 4727IE+01

    .84508E+01

    .34234E+O1

    .19770E+01

    .41472E+01

    .41603E+01

    .55442E+0174437E+0100799E+02,05206E+0208902E+0213414E+0219654E+0225808E+0229097E+0234623E+0241092E+0246170E+0247017E+0252031E+0269085E+0224517E+0227486E+0232747E+0239495E+0244902E+0251894E+02 '61017E+0269207E40273149E+02

    TSP BInactive

    9.51825E+002.38852E+012.49456E+012.62225E+C12.85222E+013.04704E+013.34421E+013.60336E+013.90738E+014.23021E+014.48968E+014.84973E+015.01855E+015.30070E+015.40789E+016.41220E+019.55012E+019.77780E+011.OO463E+O21.05040E+021.08789E+021.14413E+021.19067E+021.24690E+021.30252E+021.35013E+021.41028E+021.44153E+021.4B675E+021.51990E+021.69032E+022.24452E+022.28015E+022.32154E+022.39318E+022.44784E+022.53491E+022.59662E+022.68039E+022.74624E+02

    TSPs 2 & l\Inactive

    B.29776E+001.25001E+012.39854E+012.50390E+012.65102E+012.85479E+01.3.11S83E+O13.38327E+013.57531E+013.85679E+014.21025E+014.57386E+014.91663E+015.19907E+015.41526E+016.05711E+017.06316E+019.57002E+019.79375E+011.01002E+021.05086E+021.10094E+021.15084E+021.1B641E+021.23711E+021.29995EH021.36372E+021.42288E+021.47022E+021.52033E+02I.63128E+021.80180E+022.24763E+022.28230E+022.32974E+022.39309E+022.468B9E+022.53823E+022.58943E+022.66510E+02

    TSPs 3 & AInactive

    4.66164E+001.32502E+012.39716E+012.49075E+012.62533E+012.83516E+013.11056E+013.42886E+013.76846E+014.C8698E+014.31113E+014.58220E+014.89624E+015.16138E+015.31758E+015.41642E+017.29944E+019.56835E+019.77076E+011.00526E+021.04718E+021.10005E+021.15936E+021.22136E+021.27918E+021.31901E+021.36535E+021.41980E+0?1.46557E+021.49476E+021.52036E+021.84664E+022.24733E+022.27853E+022.32271E+022.38848E+022.46978E+022.55829E+022.64736E+022.72761E+02

  • Table 3. Natural Frequencies ot the TSP-active Modes of Tubes BWG 12 and 18

    Modes

    123456789

    1011121314151617180920

    Tube BWG 12Hz

    23.924.826.228.130.332.835.638.541.444.447.249.851.953.454.295.597.4

    100.4104.2108.5

    Tube BWG 18Hz

    21.522.323.625.327.329.632.134.737.440.042.644.946.848.048.886.187.990.593.997.8

  • oFig. 1. Arrangement of Baffles and Support Plates

  • I ' ' I ' ' I ' 'I M i l

    I I I f f' ' I '

    ! • • 1+-»

    • ' m 11 ' i • • i ' •

    i i i i

    15 13 11 9 7

    TRAIN A

    TUBE FRETTING DAMAGEATSUPPORT

    FLATTENED TUBE SURFACE

    2/3/4 FLATTENED SURFACESFOUND ON ONE SPAN

    flff i

    Fig. 2. Damage Inspection of Removed Tubes

  • CCW HXs, Unit 1(Both Train A and B)

    Daaage Appeared at Supports as Follows:

    EX A EL-3-1£1-26-2E5-1-2/3/4/5/8£5-4-1/2/3/4/6/9E5-51-3/4/6/9£5-54-1/2/3/4/6/8E29-26-6£53-1-1

    HX B EL-3-2/4El-26-2/3E5-1-2/4/5/6/7E3-4-2/3/4/5/6/7/9/10/12/13/14E5-51-1/2/3/4/5/6/7E53-4-8/9E53-51-5E53-38-6

    El-3-2/4Row 1 (from bottom), tube 3 (fron left) at support plates 2 and 4

    Fig. 3. Location of 28 Tubes Selected from Each Heat Exchanger

  • Fiq. 4. Peak-to-Peak Displacements as Function of Flow Rate

    5000 1.000e+04 1.500e+04FLOW RATE, gpm

  • 1 0 0 200 300 400

    Frequency500 100 200 300 400 500

    Fig. 5. Frequency Spectra of Tube 1H, a Typical Tube

  • Fig. 6. CCW Heat Exchanger Modified by TMMC

  • 13

    / > A / W V A / \ / V A A A A A A y A . V ^ . A y y A^ A A/NyV̂ y V \A/W*V/**/ VVVW yVW VW\A Ay^ A ^ V A A / V W V V V W

    \ y V . y v y y ^ y \ A y V / \ y y y v

    VVVV^AyY^y^;Ay^Av^r,/^/^AAAA^AA7^y^y^y^yvX/V^/AAAXXA/A/. A/v^Ay^A/Vv^yV^yV^y•vVV^y^AAy^y^Ay^vVAAy^Ay^yvv^y^XAy\X\A,VVVV>AAyVV^AA/kyvV\Ay\AAAyNA/\/V\AAy\A/^yV^AA/VA/Vyv^A-AAy^Ay^A/\y^vv^y^y^/^V•\AyV^Ay\.AA^^y^yVV^AyV^y^ A X X A / /\.-••%Ayv\Ay^/VV

    NAyV^yV^y^y^Ay^AAy^AyVV^y^y^Ay^AAA/v^/V^AAX

    VV^AAXXAy^Ay•VVVV^AyXAyVN''

    A.AyNy^cVAAy^yVVAyVAAy^AXy^AAAAAAAAj^ «- A ~ - - ' - AAAy%* 9

    ^y\Ay\yV

    \A A * /s A X A A A \ X \ ' V V V ' - VV VV VVV V VVVN W V V W V VV ' vf v v V V V-' VV V W v V W \AyOC^XYAYAi/VY^^^ 1 ,̂ AAv^Ay^Av^A.̂ A.VVVV^AAAv^A'

    NAAA^y^AAy^y^AAAAXy^AOOOOvAA A ^ y ^ ^ ' ^ ' ^ \AAyVV^y\AA^%A/vV\AAAA^VAyV\A/Ay^WNyA^"A,A.AAA/WA-VWW\.XyVV\AAAA'WW/OO^^YXVVYV , ' w ̂ '"^Wvv^A-V\/VVVV\Ay^AyvVAA-• AAAAyV^A,rtv^y\AyVV\A.XAA/Jr ŷv̂ Aŷ A.-• •AyV^-^AAAAAAAAAAAy\AA.-.-AAA.\/V\A'5 AAAy\A_Ay\AA/\AA "AAA/

    \A/VVVV\AvT^/\Ay\yv\AA AAyAA/\AAAA/\Ay\AAAAAA/\AAAy

    \ A - - H p V ^ y

    INLET INSTRUMENTATION DEPTH

    A 25.5 !N. (TUBE 1-4 & 20, GROUP A)

    • 65 IN. (TUBE 5-9 &19, GROUP B)

    • 107 IN. (TUBE 10-15, GROUP C)

    • 149 IN. (TUBE 16-18, GROUP D)

    OUTLET INSTRUMENTATION DEPTH

    • 25 IN. (TUBE 11 & 2', GROUP E)

    X 64.25 IN. (TUBE 3'-5\ GROUP F)

    • 106 IN. (TUBES 61 & T, GROUP G)

    Fiq. 7. Instrumented Tubes

  • 11C-H

    4\; • • • ? * ! •

    TV. 1 . . : . ,

    Ullllu

    J •:

    fBjnriT

    ; i H 5 4 i

    Liiiiiillllyi'iiiiiiiiiii,

    ' . • • • • ! •

    gpm

    145,000

    11C-V

    140,000

    130,000

    120,000

    110,000

    qj...j..4...j....j 100,000

    90,000

    76,000

    •*3i:

    J : : :

    =..; (I

    iuiOl

    i! H

    yil

    T e l•••••!• •{••ii-

    !G jn?

    U : :"

    ..J....

    .!*...:

    iiiiliiibui....

    60,000

    140 0 140

    Frequency, Hz Frequency, Hz

    Fiq. 8. Frequency SDectra of Tube 11C

  • TSP-InactiveModes

    mtnu

    TSP-ActiveModes

    Tube 1A-H10,000 gpm

    140.

    TSP-InactiveModes

    ml nut

    TSP-ActiveModes

    Tube 2A-H145,000 gpm

    P-Q.

    140.

    Fig. 9. TSP-Inactive and TSP-Active Modes

  • TSP-Inactive Modes

    mlnuTube 5F-H1200 GPM

    TSP-Active Modes

    Tube 5B-V7000 GPM

    Hz. 140.

    Fig. io. Either TSP-Inactive or TSP-Active Modes Are Dominant

  • TUBE 1A-V

    0.1

    EBUJQ

    0.011000 10000

    FLOW RflTE, gpm

    100000

    0.1

    £

    LUQ=3H

    0.011000

    TUBE 1A-H

    10000

    FLO ID RflTE, gpm

    100000

    Fig. 11. Displacement of Tube 1A

  • TUBE 5B-V

    £UiQ

    t o.i-Ja.z

    0.011000 10000

    FLOW RflTE, gpm100000

    TUBE 5B-H

    ESuuQ

    to.i

    z

    0.011000 10000

    FLOW RflTE, gpm100000

    Fig. 12. Displacement of Tube 5B

  • 0.1TUBE11C-Y

    o3

    0.011000 10000

    FLOW RflTE, gpm100000

    0.1 TUBE 11C-H

    10000FLOW RflTE, gpm

    100000

    Fig. 13. Displacement of Tube 11C

  • CM

    CM

    CO

  • 1ST MODE, 23.9 HZ

    3RD MODE, 26.2 HZ

    4TH MODE, 28.1 HZ

    5TH MODE, 30.3 HZ

    TSP-flCTlUE MODES

    Fiq. 15. The First Five Modes of TSP-Active Modes

  • 1ST MODE, 11.3 HZ

    2ND MODE, 23.9 HZ

    3RD MODE, 24.9 HZ

    4TH MODE, 26.5 HZ

    5TH MODE, 28.4 HZ

    TSP 2 SNflCTlUE

    Fig. 16. The First Five Modes of TSP-Inactive Modeswhen TSP 2 is Inactive

  • 8.30 HZ

    12.5 HZ

    TSP2 RNDTSP 4 INRCTIUE

    4.66 HZ

    13.25 HZ

    TSP 3 HND TSP 4 INflCTlUE

    Fiq. 17. The Fi rs t Two Modes for TSPs 2 and 4 Inactive andTSPs 3 and 4 Inactive

  • TSP 2 INflCTlUE 11.31 HZ

    TSP 3 INflCTlUE 9.68 HZ

    TSP 4 INflCTlUE 9.53 HZ

    TSP 5 INflCTlUE 9.52 HZ

    TSP 8 INflCTlUE 9.52 HZ

    Fig. 18. The First TSP-Inactive Mode for One TSP Inactive

  • FIRST

    STOPPING

    BANDFIRST

    PASSINGBAND

    SECONDSTOPPING

    BAND

    SECONDPASSING

    BAND

    '7/777.

    OHZ 50 HZ 100 HZ 150 HZ

    Fig. 19. Frequency Bands for Tube BWG12