Master Examination Practice Drill #6 2011

102
Master Examination Practice Drill #6 2011

description

Master Examination Practice Drill #6 2011. Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at LEAST ______ inside the fountain, when measuring from the outside edges of the fountain. 2 feet 3 feet 4 feet 5 feet. 1. D 680.57(C)(1). - PowerPoint PPT Presentation

Transcript of Master Examination Practice Drill #6 2011

Page 1: Master Examination Practice  Drill #6   2011

Master Examination Practice Drill #6 2011

Page 2: Master Examination Practice  Drill #6   2011

O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at LEAST ______ inside the fountain, when measuring from the outside edges of the fountain.A. 2 feetB. 3 feetC. 4 feetD. 5 feet

Page 3: Master Examination Practice  Drill #6   2011

O 1. D

O 680.57(C)(1)

Page 4: Master Examination Practice  Drill #6   2011

O In an aircraft hanger, the area that extends upward from the floor level ________ above the upper surface of aircraft wings, power plants and fuel tanks shall be classified as a Class I, Division 2 or Zone 2 location.A. 5 feetB. 6 feetC. 8 feetD. 10 feet

Page 5: Master Examination Practice  Drill #6   2011

O 2. A

O 513.3

Page 6: Master Examination Practice  Drill #6   2011

O Conductors supplying outlets for arc and xenon motion picture projectors of the professional type shall be a MINIMUM size of __________.A. 12 AWGB. 10 AWGC. 8 AWGD. 6 AWG

Page 7: Master Examination Practice  Drill #6   2011

O 3. C

O 540.13

Page 8: Master Examination Practice  Drill #6   2011

O Where rigid polyvinyl chloride (PVC) conduit is installed underground to supply a gasoline dispensing unit, threaded rigid metal conduit (RMC) or threaded intermediate metal conduit (IMC) shall be used for the LAST ______ of the underground run to where the conduit emerges.A. 2 feetB. 4 feetC. 5 feetD. 6 feet

Page 9: Master Examination Practice  Drill #6   2011

O 4. A

O 514.8, Ex. 2

Page 10: Master Examination Practice  Drill #6   2011

O Where electrical metallic tubing (EMT) is installed under metal-corrugated sheet roofing decking, a clearance of at LEAST _____ must be maintained between the top of the tubing and the surface of the roof decking.A. 1 in.B. 1 ¼ inC. 1 ½ in.D. 2 in.

Page 11: Master Examination Practice  Drill #6   2011

O 5. C

O 300.4(E)

Page 12: Master Examination Practice  Drill #6   2011

O After applying all demand factors, the ampacity of the service-entrance conductors are required to be NOT less than _____ where both the overcurrent device and its assembly are not listed for operation at 100 percent of their rating.A. 125 percent of the loads on the branch

circuitsB. The sum of the loads on the branch

circuitsC. The sum of the noncontinuous loads

plus 125 percent of the continuous loadsD. The sum of all branch-circuit overcurrent

protection devices.

Page 13: Master Examination Practice  Drill #6   2011

O 6. C

O 230.42(A)(1)

Page 14: Master Examination Practice  Drill #6   2011

O The demand factor of any electrical system is the ratio of the maximum demand for a system to:A. The totally connected load of the

system.B. 125% of the total connected load

of the system.C. 125% of the total connected

continuous load of the system.D. 80% of the total connected

noncontinuous load plus 125% of the total connected continuous-load of the system.

Page 15: Master Examination Practice  Drill #6   2011

O 7. A

O Article 100

Page 16: Master Examination Practice  Drill #6   2011

O The accessible portion of abandoned supply circuits and interconnecting cables located in an information technology equipment room shall be removed, UNLESS _________.A. Tagged and identified as abandonedB. Identified as Type CMPC. Contained in a racewayD. Disconnected from their supply

source

Page 17: Master Examination Practice  Drill #6   2011

O 8. C

O 645.5(G)

Page 18: Master Examination Practice  Drill #6   2011

O A residential branch circuit is to supply two (2) wall-mounted ovens rated at 4 kW each and one (1) 6 kW counter-mounted cooktop. Where all the equipment is 240 volts, single-phase, the branch-circuit conductors supplying this kitchen equipment shall have an ampacity of at LEAST __________.A. 22 amperesB. 27 amperesC. 33 amperesD. 37 amperes

Page 19: Master Examination Practice  Drill #6   2011

O 9. DO T220.55 Note 4 Treat as one unitO 6kw+4kw+4kw= 14kwO 14-12=2x5=10 O 8000 x 1.10= 8800 watts/ 240V=

36.7 A

Page 20: Master Examination Practice  Drill #6   2011

O On ac circuits, an ac general-use snap switch may be used for controlling a stationary motor rated 2 hp or less, if 300 volts or less, NOT exceeding _________ of the ampere rating of the switch at its rated voltage.A. 50 percentB. 80 percentC. 115 percentD. 125 percent

Page 21: Master Examination Practice  Drill #6   2011

O 10. B

O 430.83(C)(2)

Page 22: Master Examination Practice  Drill #6   2011

O What MINIMUM size THWN copper conductors are required to supply a continuous-duty, 25 hp, 208-volt, 3-phase motor? Given: The motor is on the end of a short conduit run that contains only three (3) conductors, at an ambient temperature of 50°C. Consider the motor termination to be rated for 75°CA. 6 AWGB. 3 AWGC. 2 AWGD. 1 AWG

Page 23: Master Examination Practice  Drill #6   2011

O 11. D

O T430.250O 430.22O T 310.15(B)(16)O 74.8 x 1.25= 93.5 AO 93.5 / .75 ( Temp Correction)= 124.6

AO Use the 75C col.

Page 24: Master Examination Practice  Drill #6   2011

O Which of the following statements regarding busways is/are true? Busways shall not be installed _________.A. Where subject to severe physical

damageB. Outdoors or in wet or damp

locations unless identified for such use

C. In hoistwaysD. All of the above are true.

Page 25: Master Examination Practice  Drill #6   2011

O 12. D

O 368.12(A), (B) and (D)

Page 26: Master Examination Practice  Drill #6   2011

O Which of the following shall be installed on the critical branch of the emergency system in a health care facility?A. Exit signsB. Nurse call systemsC. Communication systemsD. Fire alarms

Page 27: Master Examination Practice  Drill #6   2011

O 13. B

O 517.33 (A)(5)

Page 28: Master Examination Practice  Drill #6   2011

O The emergency controls for attended self-service gasoline stations and convenience stores with motor fuel dispensers must be located NOT more than ________ from the motor fuel dispensers.A. 20 feetB. 50 feetC. 75 feetD. 100 feet

Page 29: Master Examination Practice  Drill #6   2011

O 14. D

O 514.11(B)

Page 30: Master Examination Practice  Drill #6   2011

O Which of the following listed wiring methods is not approved for use in assembly locations, UNLESS encased in concrete?A. EMTB. Schedule 80 PVCC. Type MC cableD. Type AC cable

Page 31: Master Examination Practice  Drill #6   2011

O 15. B

O 518.4(A)

Page 32: Master Examination Practice  Drill #6   2011

O Where transformer vaults are not protected with an automatic fire-suppression system, they shall be constructed of materials that have a MINIMUM fire-resistance rating of __________.A. 1 hourB. 2 hoursC. 3 hoursD. 4 hours

Page 33: Master Examination Practice  Drill #6   2011

O 16. C

O 450.42

Page 34: Master Examination Practice  Drill #6   2011

O What percent of electrical supplied spaces in a recreational vehicle park must have 30-ampere, 125-volt receptacle outlets provided?A. 60 percentB. 70 percentC. 90 percentD. 100 percent

Page 35: Master Examination Practice  Drill #6   2011

O 17. B

O 551.71

Page 36: Master Examination Practice  Drill #6   2011

O What is the MINIMUM bend radius of trade size 4 in. rigid metal conduit (RMC) where the bend is not made with a one-shot or full-shoe bender?A. 16 inchesB. 18 inchesC. 24 inchesD. 30 inches

Page 37: Master Examination Practice  Drill #6   2011

O 18. C

O Cpt. 9, Table 2

Page 38: Master Examination Practice  Drill #6   2011

O Type AC cable shall NOT be used _______.A. In lengths of more than 6 ft.B. In cable traysC. As concealed feedersD. Where embedded in plaster in

wet locations.

Page 39: Master Examination Practice  Drill #6   2011

O 19. D

O 320.12(5)

Page 40: Master Examination Practice  Drill #6   2011

O Where portions of a cable, raceway or sleeve are known to be subjected to different temperatures and where condensation is known to be a problem, the raceway or sleeve shall ________.A. Be filled with an approved

materialB. Have an explosionproof sealC. Be provided with a drainD. Be installed below the level of

the terminations.

Page 41: Master Examination Practice  Drill #6   2011

O 20. A

O 300.7(A)

Page 42: Master Examination Practice  Drill #6   2011

O What is the MINIMUM size 75°C copper service-entrance conductors require for a 200 ampere rated commercial service?A. 4/0 THWB. 2/0 THW C. 3/0 THHND. 3/0 THW

Page 43: Master Examination Practice  Drill #6   2011

O 21. D

O T310.15(B)(16)

Page 44: Master Examination Practice  Drill #6   2011

O Determine the MINIMUM size THWN copper feeder conductors required by the NEC® to supply the following 480-volt, continuous duty, 3-phase, induction type, Design B, motors. Motor terminations are assumed to be rated at 75 degrees C. 1 – 40 hp1 – 50 hp1 – 60 hp

A. 2/0 AWGB. 3/0 AWGC. 4/0 AWGD. 250 kcmil

Page 45: Master Examination Practice  Drill #6   2011

O 22. CO 77 x 1.25= 96+65+52= 213 A

O Use 75C column of T310.15(B)(16)

Page 46: Master Examination Practice  Drill #6   2011

O Two (2) or more motors may be installed without individual overcurrent protection devices if rated less than 1 hp each, and the full-load current rating of each motor does NOT exceed __________, if they are on a 120-volt, 20 ampere branch circuit.A. 2 amperesB. 4 amperesC. 5 amperesD. 6 amperes

Page 47: Master Examination Practice  Drill #6   2011

O 23. D

O 430.53(A)(1)

Page 48: Master Examination Practice  Drill #6   2011

O Where a listed packaged spa or hot tub is installed outdoors, the unit is permitted to be cord-and-plug connected, provided the cord is NOT longer than _______ and protected by a GFCI.A. 6 feetB. 10 feetC. 15 feetD. 20 feet

Page 49: Master Examination Practice  Drill #6   2011

O 24. C

O 680.42(A)(2)

Page 50: Master Examination Practice  Drill #6   2011

O Given: A three-phase, 480-volt, 100 ampere noncontinuous load is located 390 feet from a panelboard. What MINIMUM size THWN aluminum feeder conductors are required to limit the voltage drop to 3 percent?

(K= 21.2)A. 2 AWGB. 1 AWGC. 1/0 AWGD. 2/0 AWG

Page 51: Master Examination Practice  Drill #6   2011

O 25. CO 3% of 480V = 14.4

O 1.732KDI / Max. Allowed VD= CMO 1.732 x 21.2 x 100 x 390 / 14.4= 99446 CM

Page 52: Master Examination Practice  Drill #6   2011

Click Here to Advance to Non Timed Slides

Page 53: Master Examination Practice  Drill #6   2011

O Where a hotel has a stationary electric sign installed inside a decorative fountain, the sign shall be at LEAST ______ inside the fountain, when measuring from the outside edges of the fountain.A. 2 feetB. 3 feetC. 4 feetD. 5 feet

Page 54: Master Examination Practice  Drill #6   2011

O 1. D

O 680.57(C)(1)

Page 55: Master Examination Practice  Drill #6   2011

O In an aircraft hanger, the area that extends upward from the floor level ________ above the upper surface of aircraft wings, power plants and fuel tanks shall be classified as a Class I, Division 2 or Zone 2 location.A. 5 feetB. 6 feetC. 8 feetD. 10 feet

Page 56: Master Examination Practice  Drill #6   2011

O 2. A

O 513.3

Page 57: Master Examination Practice  Drill #6   2011

O Conductors supplying outlets for arc and xenon motion picture projectors of the professional type shall be a MINIMUM size of __________.A. 12 AWGB. 10 AWGC. 8 AWGD. 6 AWG

Page 58: Master Examination Practice  Drill #6   2011

O 3. C

O 540.13

Page 59: Master Examination Practice  Drill #6   2011

O Where rigid polyvinyl chloride (PVC) conduit is installed underground to supply a gasoline dispensing unit, threaded rigid metal conduit (RMC) or threaded intermediate metal conduit (IMC) shall be used for the LAST ______ of the underground run to where the conduit emerges.A. 2 feetB. 4 feetC. 5 feetD. 6 feet

Page 60: Master Examination Practice  Drill #6   2011

O 4. A

O 514.8, Ex. 2

Page 61: Master Examination Practice  Drill #6   2011

O Where electrical metallic tubing (EMT) is installed under metal-corrugated sheet roofing decking, a clearance of at LEAST _____ must be maintained between the top of the tubing and the surface of the roof decking.A. 1 in.B. 1 ¼ inC. 1 ½ in.D. 2 in.

Page 62: Master Examination Practice  Drill #6   2011

O 5. C

O 300.4(E)

Page 63: Master Examination Practice  Drill #6   2011

O After applying all demand factors, the ampacity of the service-entrance conductors are required to be NOT less than _____ where both the overcurrent device and its assembly are not listed for operation at 100 percent of their rating.A. 125 percent of the loads on the branch

circuitsB. The sum of the loads on the branch

circuitsC. The sum of the noncontinuous loads

plus 125 percent of the continuous loadsD. The sum of all branch-circuit overcurrent

protection devices.

Page 64: Master Examination Practice  Drill #6   2011

O 6. C

O 230.42(A)(1)

Page 65: Master Examination Practice  Drill #6   2011

O The demand factor of any electrical system is the ratio of the maximum demand for a system to:A. The totally connected load of the

system.B. 125% of the total connected load

of the system.C. 125% of the total connected

continuous load of the system.D. 80% of the total connected

noncontinuous load plus 125% of the total connected continuous-load of the system.

Page 66: Master Examination Practice  Drill #6   2011

O 7. A

O Article 100

Page 67: Master Examination Practice  Drill #6   2011

O The accessible portion of abandoned supply circuits and interconnecting cables located in an information technology equipment room shall be removed, UNLESS _________.A. Tagged and identified as abandonedB. Identified as Type CMPC. Contained in a racewayD. Disconnected from their supply

source

Page 68: Master Examination Practice  Drill #6   2011

O 8. C

O 645.5(G)

Page 69: Master Examination Practice  Drill #6   2011

O A residential branch circuit is to supply two (2) wall-mounted ovens rated at 4 kW each and one (1) 6 kW counter-mounted cooktop. Where all the equipment is 240 volts, single-phase, the branch-circuit conductors supplying this kitchen equipment shall have an ampacity of at LEAST __________.A. 22 amperesB. 27 amperesC. 33 amperesD. 37 amperes

Page 70: Master Examination Practice  Drill #6   2011

O 9. DO T220.55 Note 4 Treat as one unitO 6kw+4kw+4kw= 14kwO 14-12=2x5=10 O 8000 x 1.10= 8800 watts/ 240V=

36.7 A

Page 71: Master Examination Practice  Drill #6   2011

O On ac circuits, an ac general-use snap switch may be used for controlling a stationary motor rated 2 hp or less, if 300 volts or less, NOT exceeding _________ of the ampere rating of the switch at its rated voltage.A. 50 percentB. 80 percentC. 115 percentD. 125 percent

Page 72: Master Examination Practice  Drill #6   2011

O 10. B

O 430.83(C)(2)

Page 73: Master Examination Practice  Drill #6   2011

O What MINIMUM size THWN copper conductors are required to supply a continuous-duty, 25 hp, 208-volt, 3-phase motor? Given: The motor is on the end of a short conduit run that contains only three (3) conductors, at an ambient temperature of 50°C. Consider the motor termination to be rated for 75°CA. 6 AWGB. 3 AWGC. 2 AWGD. 1 AWG

Page 74: Master Examination Practice  Drill #6   2011

O 11. D

O T430.250O 430.22O T 310.15(B)(16)O 74.8 x 1.25= 93.5 AO 93.5 / .75 ( Temp Correction)= 124.6

AO Use the 75C col.

Page 75: Master Examination Practice  Drill #6   2011

O Which of the following statements regarding busways is/are true? Busways shall not be installed _________.A. Where subject to severe physical

damageB. Outdoors or in wet or damp

locations unless identified for such use

C. In hoistwaysD. All of the above are true.

Page 76: Master Examination Practice  Drill #6   2011

O 12. D

O 368.12(A), (B) and (D)

Page 77: Master Examination Practice  Drill #6   2011

O Which of the following shall be installed on the critical branch of the emergency system in a health care facility?A. Exit signsB. Nurse call systemsC. Communication systemsD. Fire alarms

Page 78: Master Examination Practice  Drill #6   2011

O 13. B

O 517.33 (A)(5)

Page 79: Master Examination Practice  Drill #6   2011

O The emergency controls for attended self-service gasoline stations and convenience stores with motor fuel dispensers must be located NOT more than ________ from the motor fuel dispensers.A. 20 feetB. 50 feetC. 75 feetD. 100 feet

Page 80: Master Examination Practice  Drill #6   2011

O 14. D

O 514.11(B)

Page 81: Master Examination Practice  Drill #6   2011

O Which of the following listed wiring methods is not approved for use in assembly locations, UNLESS encased in concrete?A. EMTB. Schedule 80 PVCC. Type MC cableD. Type AC cable

Page 82: Master Examination Practice  Drill #6   2011

O 15. B

O 518.4(A)

Page 83: Master Examination Practice  Drill #6   2011

O Where transformer vaults are not protected with an automatic fire-suppression system, they shall be constructed of materials that have a MINIMUM fire-resistance rating of __________.A. 1 hourB. 2 hoursC. 3 hoursD. 4 hours

Page 84: Master Examination Practice  Drill #6   2011

O 16. C

O 450.42

Page 85: Master Examination Practice  Drill #6   2011

O What percent of electrical supplied spaces in a recreational vehicle park must have 30-ampere, 125-volt receptacle outlets provided?A. 60 percentB. 70 percentC. 90 percentD. 100 percent

Page 86: Master Examination Practice  Drill #6   2011

O 17. B

O 551.71

Page 87: Master Examination Practice  Drill #6   2011

O What is the MINIMUM bend radius of trade size 4 in. rigid metal conduit (RMC) where the bend is not made with a one-shot or full-shoe bender?A. 16 inchesB. 18 inchesC. 24 inchesD. 30 inches

Page 88: Master Examination Practice  Drill #6   2011

O 18. C

O Cpt. 9, Table 2

Page 89: Master Examination Practice  Drill #6   2011

O Type AC cable shall NOT be used _______.A. In lengths of more than 6 ft.B. In cable traysC. As concealed feedersD. Where embedded in plaster in

wet locations.

Page 90: Master Examination Practice  Drill #6   2011

O 19. D

O 320.12(5)

Page 91: Master Examination Practice  Drill #6   2011

O Where portions of a cable, raceway or sleeve are known to be subjected to different temperatures and where condensation is known to be a problem, the raceway or sleeve shall ________.A. Be filled with an approved

materialB. Have an explosionproof sealC. Be provided with a drainD. Be installed below the level of

the terminations.

Page 92: Master Examination Practice  Drill #6   2011

O 20. A

O 300.7(A)

Page 93: Master Examination Practice  Drill #6   2011

O What is the MINIMUM size 75°C copper service-entrance conductors require for a 200 ampere rated commercial service?A. 4/0 THWB. 2/0 THW C. 3/0 THHND. 3/0 THW

Page 94: Master Examination Practice  Drill #6   2011

O 21. D

O T310.15(B)(16)

Page 95: Master Examination Practice  Drill #6   2011

O Determine the MINIMUM size THWN copper feeder conductors required by the NEC® to supply the following 480-volt, continuous duty, 3-phase, induction type, Design B, motors. Motor terminations are assumed to be rated at 75 degrees C. 1 – 40 hp1 – 50 hp1 – 60 hp

A. 2/0 AWGB. 3/0 AWGC. 4/0 AWGD. 250 kcmil

Page 96: Master Examination Practice  Drill #6   2011

O 22. CO 77 x 1.25= 96+65+52= 213 A

O Use 75C column of T310.15(B)(16)

Page 97: Master Examination Practice  Drill #6   2011

O Two (2) or more motors may be installed without individual overcurrent protection devices if rated less than 1 hp each, and the full-load current rating of each motor does NOT exceed __________, if they are on a 120-volt, 20 ampere branch circuit.A. 2 amperesB. 4 amperesC. 5 amperesD. 6 amperes

Page 98: Master Examination Practice  Drill #6   2011

O 23. D

O 430.53(A)(1)

Page 99: Master Examination Practice  Drill #6   2011

O Where a listed packaged spa or hot tub is installed outdoors, the unit is permitted to be cord-and-plug connected, provided the cord is NOT longer than _______ and protected by a GFCI.A. 6 feetB. 10 feetC. 15 feetD. 20 feet

Page 100: Master Examination Practice  Drill #6   2011

O 24. C

O 680.42(A)(2)

Page 101: Master Examination Practice  Drill #6   2011

O Given: A three-phase, 480-volt, 100 ampere noncontinuous load is located 390 feet from a panelboard. What MINIMUM size THWN aluminum feeder conductors are required to limit the voltage drop to 3 percent?

(K= 21.2)A. 2 AWGB. 1 AWGC. 1/0 AWGD. 2/0 AWG

Page 102: Master Examination Practice  Drill #6   2011

O 25. CO 3% of 480V = 14.4

O 1.732KDI / Max. Allowed VD= CMO 1.732 x 21.2 x 100 x 390 / 14.4= 99446 CM