Marine Low Leakage Shut Off Damper - Eindec · Marine Low Leakage Shut Off Damper ... 555S Class1...

4
Marine Low Leakage Shut Off Damper KYODO reserves the right to make changes without written notice. The actual product might differ from pictures shown. Drawings are not meant to show exact details of every aspects of the product. SD-1 Model: SD-P [Pneumatic Actuator] SD-E [Electric Actuator] SD-EM [Electric/Manual Actuator] SD-M [Manual Lever] Introduction KYODO Low Leakage Shut Off Dampers are used in ventilation systems to prevent spread of toxic smoke and hazardous gas between divisions. Description Kyodo Low Leakage Shut Off dampers satisfy UL 555S Class1 leakage standard and NORSOK (Norwegian Petroleum Industry Standard) H-001 standard requirements. The damper had passed the 60,000 cycles test according to the test method of UL555S. It complies with the test method taken from BS EN 1751:1999 which is comparable to AMCE-500 D-98. The leakage tests in BS1886, DW144 and UL555S also used the same method. Applications Marine, Oil & Gas, Process Plants and General Ventilation Systems. Features Robust construction Low casing leakage Low blade leakage Low airflow resistance Manual, pneumatic, or electric operation Dimensional Limits The minimum size is 100mm wide x 100mm high. The maximum single module size is 1,800mm wide x 1,800mm high. Construction The damper frame is welded with integral 50mm folded flanges using 2-3mm thick galvanized steel. The drive side casing section is provided with a return flange to facilitate the mounting of the actuator bracket. For cases where there is difficulty to access the bolt holes behind the control enclosure, welded nuts will be provided. The blades are double skin aerofoil type using 1.2mm thick stainless steel and are plug welded and bolted to 19mm diameter solid shafts. Mechanical bushings are fitted on the non-drive side. Damper with multiple blades are fitted with a linkage to provide an opposed motion. Robust blade links are welded to the drive shafts and connected together by flat bar. The linkage arrangement is contained within the flanges of the damper frame. Round connection available on request.

Transcript of Marine Low Leakage Shut Off Damper - Eindec · Marine Low Leakage Shut Off Damper ... 555S Class1...

Page 1: Marine Low Leakage Shut Off Damper - Eindec · Marine Low Leakage Shut Off Damper ... 555S Class1 leakage standard and NORSOK (Norwegian Petroleum Industry Standard) H-001

Marine Low Leakage Shut Off Damper

KYODO reserves the right to make changes without written notice. The actual product might differ from

pictures shown. Drawings are not meant to show exact details of every aspects of the product. SD-1

Model: SD-P [Pneumatic Actuator]

SD-E [Electric Actuator]

SD-EM [Electric/Manual Actuator] SD-M [Manual Lever]

Introduction

KYODO Low Leakage Shut Off Dampers are used in ventilation systems to prevent spread of toxic smoke and hazardous gas between divisions.

Description

Kyodo Low Leakage Shut Off dampers satisfy UL 555S Class1 leakage standard and NORSOK (Norwegian Petroleum Industry Standard) H-001 standard requirements. The damper had passed the 60,000 cycles test according to the test method of UL555S. It complies with the test method taken from BS EN 1751:1999 which is comparable to AMCE-500 D-98. The leakage tests in BS1886, DW144 and UL555S also used the same method.

Applications

Marine, Oil & Gas, Process Plants and General Ventilation Systems.

Features

• Robust construction

• Low casing leakage

• Low blade leakage

• Low airflow resistance

• Manual, pneumatic, or electric operation

Dimensional Limits

The minimum size is 100mm wide x 100mm high. The maximum single module size is 1,800mm wide x 1,800mm high.

Construction

The damper frame is welded with integral 50mm folded flanges using 2-3mm thick galvanized steel. The drive side casing section is provided with a return flange to facilitate the mounting of the actuator bracket. For cases where there is difficulty to access the bolt holes behind the control enclosure, welded nuts will be provided.

The blades are double skin aerofoil type using 1.2mm thick stainless steel and are plug welded and bolted to 19mm diameter solid shafts. Mechanical bushings are fitted on the non-drive side.

Damper with multiple blades are fitted with a linkage to provide an opposed motion. Robust blade links are welded to the drive shafts and connected together by flat bar. The linkage arrangement is contained within the flanges of the damper frame.

Round connection available on request.

Page 2: Marine Low Leakage Shut Off Damper - Eindec · Marine Low Leakage Shut Off Damper ... 555S Class1 leakage standard and NORSOK (Norwegian Petroleum Industry Standard) H-001

Marine Low Leakage Shut Off Damper

KYODO reserves the right to make changes without written notice. The actual product might differ from pictures

shown. Drawings are not meant to show exact details of every aspects of the product. SD-2

All dimensions are in mm

130 (W<250) A,B

150 (W≥250)

C,D Minimum 80, maximum 130

Leakage Rates

Testing conducted by BSRIA on standard production single module dampers has achieved a mean leakage rate of

• 0.040 m³/s/m² at a differential pressure of 2,000Pa and

• 0.002 m³/s/m² at a differential pressure of 50Pa.

0.08 m³/s/m² at a differential pressure of 2,000Pa for NORSOK standard. Lower leakage rates can be achieved upon request.

Performance Tested

The test methods were taken from BS EN 1751:1999, comparable with those used in American standard AMCA 500-D-98. Leakage tests under BS1886, DW144 and UL555S also used the same methods.

Data based on test conducted by BSRIA on a 1,000mm x 1,000mm damper.

Total pressure loss is measured across the shut-off damper when the blades are fully open.

Page 3: Marine Low Leakage Shut Off Damper - Eindec · Marine Low Leakage Shut Off Damper ... 555S Class1 leakage standard and NORSOK (Norwegian Petroleum Industry Standard) H-001

Marine Low Leakage Shut Off Damper

KYODO reserves the right to make changes without written notice. The actual product might differ from pictures

shown. Drawings are not meant to show exact details of every aspects of the product. SD-3

Actuator / Lever

Different type of control option to choose from based on customer requirement.

• Electrical Actuator [Model SD-E]

Options

1. AC 24V 50/60Hz or DC 24V 10VA 7/2W 2. AC 230V 50/60Hz 12.5VA 8/3W

The damper is fitted with an electrical control system which enables rapid opening and closing of the damper blades. Remote indication of blade fully open and fully closed status can be signaled by microswitches mounted in to the electrical actuator which is positively connected to the damper blades.

ExMax RedMax

InMax

Hazardous area under Zone 1, 2, 21, 22. Closing time is 1, 3, or 10 second (adjustable on site).

• Pneumatic Actuator [Model SD-P]

The Air Torque actuator offers the following characteristics:

� Reliability and high performance

� Wider product range permitting a more economical sizing selection

� Innovative and patented universal drive shaft and multifunction position indicator

For double action and spring return actuators the

• Minimum supply pressure is 2.5 Bar (36 PSI).

• Maximum supply pressure is 8 Bar (116 PSI).

• Manual Lever [Model SD-M]

Page 4: Marine Low Leakage Shut Off Damper - Eindec · Marine Low Leakage Shut Off Damper ... 555S Class1 leakage standard and NORSOK (Norwegian Petroleum Industry Standard) H-001

Marine Low Leakage Shut Off Damper

KYODO reserves the right to make changes without written notice. The actual product might differ from pictures

shown. Drawings are not meant to show exact details of every aspects of the product. SD-4

• SD-EM [Electric/Manual Actuator]

Model:

• ADS-B101 [Manual Reset]

• ADM-B102 [Manual / Electrical Reset] Closing : Manual / Fuse / Electrical Rated Voltage : DC 24V Operating Voltage : DC 18V - 30V Confirmation : Operation confirmation

signal from built-in microswitch

Fusible Link : 72 degree celcius

ADS-B101:

ADM-B102:

Operation Method The damper is fitted with an electrical actuator which enables rapid closing of the damper blades. It can be operated in three ways.

1. Manual Operation Mode

[ Closing ] Pull the MANUAL LEVER. This actuates the spring to release (ADS-B101/ADM-B102) causing the damper blades to close momentarily. [ Reset ] Turn the MANUAL HANDLE counterclockwise until the indicator reaches position "O" on the scale, locking the damper blades.

2. Electrical Operation Mode

The electrical actuator closes/opens the damper blades rapidly once signal (AC/DC 24V) is received from control centre. Once the damper is closed/opened, confirmation signal and reporting signal will be sent out immediately.

3. Activation by Thermal Fuse Unit

A temperature above 72°C in the damper duct causes the temperature fuse to be melt. The shaft of the fusible link unlocks the fuse arm to activate the spring in the ADS-B101/ADM-B102, thus causing the damper blades to close in 0.5sec.