    User Guide – Standard Functionality IM/CM/S–EN Rev. M

    ControlMaster CM10, CM30 and CM50Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

  • 8/18/2019 Manual usuario control ABB-CM10

    2/112

    Language

    Operator Templates

    Page 1 (4) TemplaOperator FunctionsAutoscrollSoft Key FunctionAuto Manual EnablLocal Remote EnabAlarm Ack. EnableSP Adjust Enable

    SettingsBrightnessContrast*

    Date & TimeDate FormatTime & DateDaylight SavingSP Adjust Enable

    Basic Device Setup Display

    Menu

    Exit Select Exit Select Exit S

    Initial SetupApp. TemplateLoop 1 Output Type

    Loop 1 Split O/PInstrument TagMains Freq.Config ActionCustom TemplateReset to Defaults

    Security SetupBasic PasswordAdvanced PasswordReset Passwords

    Custom Config

    Note. When in Advanced Level (configuration) mode, press and hold the key to return to the standard Operator page – see Fig. 3.1, page 5

    *Enabled for CM30 and CM50 only

    Refer to Section 7.2, page 39Refer to Section 6, page 27 Refer to Section 7.1, page 36

    Menu Menu

    Loop 1 Setpoints  Local Setpoint 1 (4)  RSP Ratio

      RSP Bias  Ramp Mode  Ramp Rate

    Loop 1 ControlOn/Off HysteresisModeAutotunePID

    Loop 1 Mot Valve  RatioBias

      Deadband  Travel Time

    Loop 1 Time PropCycle Time 1Cycle Time 2

    Alarm 1 (8)Trip

    http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/

  • 8/18/2019 Manual usuario control ABB-CM10

    3/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Contents

    1 Safety .......................................................................... 3

    1.1 Electrical Safety ..................................................... 31.2 Symbols ................................................................ 31.3 Health & Safety ..................................................... 4

    2 Introduction ................................................................ 4

    2.1 EC Directive 89 / 336 / EEC .................................. 42.2 End of Life Disposal ............................................... 4

    3 Displays, Icons and Keys .......................................... 5

    3.1 CM10 Operator Page, Icons and Keys .................. 5

  • 8/18/2019 Manual usuario control ABB-CM10

    4/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    7 Advanced Level ........................................................ 36

    7.1 Device Setup ....................................................... 367.2 Display ................................................................ 39

    7.3 Input/Output ........................................................437.4 Control ................................................................ 517.5 Process Alarm ..................................................... 637.6 Functions ............................................................ 667.7 Communication ................................................... 767.8 Diagnostics ..........................................................77

    7.8.1 Diagnostic Messages ................................ 797.9 Device Info .......................................................... 83

    8 Templates and Functionality ....................................848 1 Basic Templates 84

     Ap

     A A

     Ap

     Ap

     Ap

  • 8/18/2019 Manual usuario control ABB-CM10

    5/112

  • 8/18/2019 Manual usuario control ABB-CM10

    6/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    1.3 Health & Safety 2 This

    CM

    con

    2.1

    Health and Safety

     To ensure that our products are safe and without risk to health,the following points must be noted:  The relevant sections of these instructions must be read

    carefully before proceeding. Warning labels on containers and packages must be

    observed. Installation, operation, maintenance and servicing must

    be carried out only by suitably trained personnel and inaccordance with the information given.

    Normal safety precautions must be taken to avoid the

    possibility of an accident occurring when operating inconditions of high pressure and / or temperature.

    No

  • 8/18/2019 Manual usuario control ABB-CM10

    7/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    3 Displays, Icons and Keys

    3.1 CM10 Operator Page, Icons and Keys

     

    PV Value

    Setpoint Value

    Icons

    Output Value See Table 3.1for key functions

  • 8/18/2019 Manual usuario control ABB-CM10

    8/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    3.2 CM30 and CM50 Operator Page, Icons & Keys The ControlMaster CM30 and CM50 displays and icons are shown in

     

    PV Value

    Bargrap

    h

    Setpoint Value

  • 8/18/2019 Manual usuario control ABB-CM10

    9/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

     The ControlMaster CM30 and CM50 front panel keys are shown

    Fig. 3.3 ControlMaster CM30 / CM50 Front Panel Keys

               

  • 8/18/2019 Manual usuario control ABB-CM10

    10/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4 Installation

    4.1 Siting and Environmental Requirements

     At Eye Level Close to the Sensor 

  • 8/18/2019 Manual usuario control ABB-CM10

    11/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.2 Dimensions

    Dimensions in mm (in.)97 (3.81)

    97(3.81)

    0 030 8

    50 (1.97)

    +0 6 +0.02

  • 8/18/2019 Manual usuario control ABB-CM10

    12/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Dimensions in mm (in.)

    14

    23 (0.9)

    68

    76 (3.0)

  • 8/18/2019 Manual usuario control ABB-CM10

    13/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.3 MountingControlMaster is designed for panel mounting. For NEMA4X 

    protection, a panel thickness of 2.5 mm (0.1 in.) is required.

     To panel-mount the controller:1. Cut a hole of the correct size for the controller in the

    panel – see Section 4.2, page 9 for dimensions.

    2. Insert the controller into the panel cut-out.

    Referring to Fig. 4.4:

    3. Position the upper panel clampA at the top front of the case against the panel.

    4. Locate the panel clamp anchorB in slotC.5. Tighten the panel clamp anchor screwD until panel

    A

  • 8/18/2019 Manual usuario control ABB-CM10

    14/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.4 Jumper Links for Relay Outputs The factory-set default for relay action is N/O.

    4.4.1 Removing the Controller from its Case The ControlMaster inner assembly must be removed from its

    case to access the relay contact jumper links.

    Referring to Fig. 4.5:

    1. Insert the bezel release toolA (supplied) into the frontpanel slotB below the function keys.

    2. Press the bezel release toolA fully in and then downC  until the shoulder on the tool engages with the

    notch behind the controller front plate.3 Pull the bezel release toolA to withdraw the inner

  • 8/18/2019 Manual usuario control ABB-CM10

    15/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.4.2 Resetting Jumper Links

    1. The links associated with the relay outputs are shown

    in Fig. 4.6.

    2. If necessary, move the link to select the relay action

    required (N/O or N/C).

    Note.  The factory-set default for all jumper links is N/O.

  • 8/18/2019 Manual usuario control ABB-CM10

    16/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.5 Electrical Connections

    Warning.

     The controller is not fitted with a switch therefore a disconnecting devstandards must be fitted to the final installation.

    It must be mounted in close proximity to the controller within easy reachdevice for the instrument.

    Remove all power from supply, relay and any powered control circuits aconnections.

    Use cable appropriate for the load currents. The terminals accept cab

     Always route signal leads and power cables separately, preferably in e

    It is strongly recommended that screened cable is used for signal inpu

    The instrument conforms to Mains Power Input Overvoltage Category

  • 8/18/2019 Manual usuario control ABB-CM10

    17/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.5.1 CM10 Electrical Connections

         C    o    m    m    s     *

     Tx PSU

     Analog / DigitalOutput 1****

     Analog Input 1

     Analog Input 2

    NC

    Standard Connections Rear View

  • 8/18/2019 Manual usuario control ABB-CM10

    18/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.5.2 CM30 Electrical Connections

    Rear View

    Digital Output + Exte

    Digital Input / Outp

         C    o    m    m    s     *

     TxPSU  Analog Output 2

    Standard Connections

    Digital Input / Outpu

    Digital Input / Outp

    Relay Output 2

     AnalogInput 1

     Analog Input 2

     Analog / Digital

    Output 1****

  • 8/18/2019 Manual usuario control ABB-CM10

    19/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.5.3 CM50 Electrical Connections

    Rear View

     Analog Input 1

     Analog Input 2     C    o    m    m    s     *

    Standard Connections

    Digital Output + External

    Digital Input / Output 1

    Digital Input / Output 2

     Tx PSU*Refer to rear panel for

    MODBUS connections

    **N/O (factory default) or N/C

    contact selection made via

  • 8/18/2019 Manual usuario control ABB-CM10

    20/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.5.4 Analog Inputs

          

         

     

    THC

    CJ**

    3-lead RTD

    mA, mV, V,Digital Input

    RTD +

    RTD –

     AnalogInput 2

     AnalogInput 1

    3rd lead

      ****

  • 8/18/2019 Manual usuario control ABB-CM10

    21/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

          

         

    THC

    CJ**

    3-lead R

    RTD +

    RTD –

     AnalogInput 4

     AnalogInput 3

    3rd lead

    CM30 CM50

      ****

    mA, mV, V,Digital Input

  • 8/18/2019 Manual usuario control ABB-CM10

    22/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    4.5.5 Frequency / Pulse Input

    Note.  This input is designed primarily for use with flowmet

    Source Device

    External Voltag(Max. 30 V)

    –ve +ve

    Load*

  • 8/18/2019 Manual usuario control ABB-CM10

    23/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Digital Input/Output + ExternalCM10: Terminal 21

    CM30: Terminal 43 or 35CM50: Terminal 7 or 30

    Digital Input/OutputCM10: Terminal 22 or 23

    CM30: Terminal 44 or 45; 36, 37, 38 or 39CM50: Terminal 8 or 9; 31, 32, 33 or 34

    Digital Input/Output –CM10: Terminal 24

    CM30: Terminal 46 or 40

    CM50: Terminal 10 or 35

     Terminal Connections on Stan

  • 8/18/2019 Manual usuario control ABB-CM10

    24/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    5 Operator Level Menus

    Operator level menus are us

    select the view and to enter B To access Operator Level  me

    1. From the Operator Pag

    2. Use the / key

    3. Press to expand m

    return to the previous m

    Menu functions are described

     

    Adjust...Setpoint Loop 1

    View Select

    Enter Config. Mode

  • 8/18/2019 Manual usuario control ABB-CM10

    25/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

     Autotune Used to start or stop an autois On – see page 29.

     Adjust Enables a value to be adjust

     The icon next to a value in

    Setpoint Select Selects the local setpoint tconfigured).

     Alarm Acknowledge  Acknowledges any active bu

     View Select Selects the Operator  view to

    Enter Advanced Level Displays the Access Level  se

  • 8/18/2019 Manual usuario control ABB-CM10

    26/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    5.1 Diagnostic Status Bar 

     

    Failure

    Maintenance

     Out of Spec

     Check Function

    NAMUR (NE107) Stat

  • 8/18/2019 Manual usuario control ABB-CM10

    27/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    5.2 Diagnostic View The Diagnostic View   can be selected from the Operator   / 

    View Select  menu. All currently active diagnostic alarm states

    are displayed in the Diagnostic View .

     Alarm Icon Diagnostic Description / Alarm Tag

  • 8/18/2019 Manual usuario control ABB-CM10

    28/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    5.4 Access Level

    Level Access

    Logout Displayed after Basic  or  Advanced levels areaccessed. Logs the user out of Basic or Advanced level. If passwords are set, a passwordmust be entered to access these levels againafter selecting Logout .

    Read Only Enables all parameter settings to be viewed

    Basic Enables access to the  Basic setup level andadjustment of PID  (see page 30)  parameters,autotuning configuration and adjustment of 

    alarm trip points.

  • 8/18/2019 Manual usuario control ABB-CM10

    29/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    6 Basic Level

     The Basic menu provides access to the tunaMenuBasic

    Loop 1 Setpoints

    Local Setpoint 1 (4)  The local setpoint value required. If

    value here is also updated.

    RSP Ratio If the remote (external) setpoint issetpoint input) + bias.

    Note This parameter is available o

  • 8/18/2019 Manual usuario control ABB-CM10

    30/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Basic / …Loop 1 Setpoints

    Ramp Mode  The ramping setpoint facility can be

    used to prevent a large disturbance to

    the control output when the setpointvalue is changed. The rate set applies to

    both the local and the remote setpoints

    Ramp Rate Sets the ramp rate required in engineeri

    Note. Applicable only if Ramp Mode is

    Loop 1 Control

  • 8/18/2019 Manual usuario control ABB-CM10

    31/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Basic / …Loop 1 Control

    Mode  Turns the Autotune functionality onWhen set to On, an Autotune can b

     Autotune

     Autotune Operation

     Autotune is a user-activated feature that enables automatic se'at setpoint type' algorithm. Autotune changes the controller the optimum PID settings. Autotune uses a relay type functioprocess. New PID parameters are calculated and stored in thfrom Autotune, switch the controller to Manual  control mode (to the normal setpoint) before initiating Autotune.

    1 Set the first step

  • 8/18/2019 Manual usuario control ABB-CM10

    32/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Basic / …Loop 1 Control / …Autotune

    First Step Defines the maximum size of the first othe output step magnitude according to

    measurement of the process characterimaximum setting provides the largest o

    Dynamics Used to configure  Autotune to give opcontrolled. 

    Normal  Determines if derivative control is requaccordingly.

    Deadtime Sets the proportional and integral term(higher proportional band [lower gain] an

    PI Used for processes where it is known th

  • 8/18/2019 Manual usuario control ABB-CM10

    33/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Basic / …Loop 1 Control / …PID

    Derivative T ime 1 Set in seconds.

    Manual Reset When the Integral Time  is Off,  th

    variable is equal to the control setp 

    Note: The controller is shipped with null PID values (P=100, I

    it is connected to, these values must be tuned accordingly.

    adjustment. If the controller is tuned manually the table below

     These values are only suggested starting values and should n

    Process Type P I

     Temperature (fast)* 10 30

    T ( l )*

  • 8/18/2019 Manual usuario control ABB-CM10

    34/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Basic

    Loop 1 Mot Valve

    Example of Motorized Valve With Feedback  

    Motorized Valve Output Without Feedback (Boundless)

     A motorized valve output without feedback (boundless) process derivative of the required regulator position (the controller signals t

    in the direction to travel and how far to move) by a series of integra

    PV 

    SPT (OP x Ratio) + BiasPID

  • 8/18/2019 Manual usuario control ABB-CM10

    35/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Basic / …Loop 1 Mot Valve

    Calculation for Control Pulses (Boundless Control)

     The following calculations are for guidance when setting Dea

     The Deadband on the ControlMaster is set in engineering unitas a %, this can be calculated in the following way:

    Minimum ’ON’ time of integral action pulses (for a fixed contr

    Minimum (approximate) time between integral action pulses (

    % Deadband = Deadband (eng unitsEng Hi - Eng Lo

    = Travel Time x Deadband% (in seco% Proportional Band

    I t l A ti Ti D db d%

  • 8/18/2019 Manual usuario control ABB-CM10

    36/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Basic / …Loop 1 Mot Valve

    Deadband Example: If the valve is set to be driven4 %, the motor stops driving when the

    48 % and 52 %.

    Travel Time For motorized valve without feedback (s

    Position %

    Required Valve

  • 8/18/2019 Manual usuario control ABB-CM10

    37/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Basic

    Loop 1 Time Prop  The active time of the output pulseoutput the pulse is active for the co

    Note. Applicable only if Output Typdigital output) – see page 36.

    Cycle Time= 10 s

    50 % Output

    5 s 5 s 1 s

  • 8/18/2019 Manual usuario control ABB-CM10

    38/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    7 Advanced Level

    7.1 Device Setup

    Provides access to standard setup parameters tprovides the ability to create non-standard config

     

    MenuDevice Setup

    Initial Setup

     App Template  Application templates enable standacreated as simply as possible. Select parameters. When a template is selectemplate The inputs and function

  • 8/18/2019 Manual usuario control ABB-CM10

    39/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Device Setup / …Initial Setup

    Instrument Tag  A 16-character alphanumeric tag

    Mains Freq Used to set the internal filters to r

    Config Action  The Config Action parameter is u

    behave when the Advanced  leve

    Continue  The controller continues to ope

    normal.

    Hold  Puts the controller into Manualcontroller returns to the pre-Cooutputs are held at their value / s

    Inactive Puts the controller into Manual co

  • 8/18/2019 Manual usuario control ABB-CM10

    40/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Device Setup

    Security Setup 2 Security access levels are providalphanumeric characters.

    Note. Passwords are not set at the fa

    Basic Password Basic level provides access to the Bas

     Advanced Password Provides access to all configuration p

    Reset Passwords Resets all passwords to factory values

    Custom Config

    Loop 1 (2) PV Sets the source for the process variab

    Loop 1 (2) Split O/P Sets the source for output to the split

    L (2) V l M d S h l i d F db

  • 8/18/2019 Manual usuario control ABB-CM10

    41/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    7.2 Display

    Used to setup the operator page, displayed l

    Language Selects the language on the c

    Operator Templates Enables up to 4 operator pag

    Page 1 (4) Template  The operator template type. Tabbreviations, for example:

    Single PV, SP & OP 

    Menu

    Display

  • 8/18/2019 Manual usuario control ABB-CM10

    42/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Display

    Operator Functions  

     Autoscroll When enabled (On ), operator pagepage.

    Soft Key Function  Assigns a dedicated function to th

    Configuration Displays the Access Level  enablin

     Auto/Manual  Toggles between Auto and Manua

    Local/Remote  Toggles between Local  and Remo

    Scroll View Scrolls through each available Ope

  • 8/18/2019 Manual usuario control ABB-CM10

    43/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Display / …Operator Functions

     Auto Manual Enable  Turns on / off the ability for Au

    Local Remote Enable  Turns on / off the ability for LoLevel .

     Alarm Ack. Enable  Turns on / off the ability to ac

    SP Adjust Enable  Turns on / off setpoint adjustm

    Settings  Adjusts display settings to su

    Brightness Increases / Decreases the dis

    Contrast Increases / Decreases the dis

  • 8/18/2019 Manual usuario control ABB-CM10

    44/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Display / …Date & Time / …Daylight Saving

    DS Region

    Off Daylight saving is disabled.

    Europe Standard daylight saving start and

    USA Standard daylight saving start and

    Custom Used to create custom daylight saEurope or USA.

    Note. Enables Daylight Start Time

    DS Start Time  The start time selected from 1-hou

    N t Di l d l h th DS

  • 8/18/2019 Manual usuario control ABB-CM10

    45/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    7.3 Input/Output

    Enables analog and digital inputs / output

     Analog Inputs

     Analog Input 1 (4)*

    Input Type Input types comprise: Millivolts,

    volt-free 24V Digital Freq Input P

    MenuInput/Output

  • 8/18/2019 Manual usuario control ABB-CM10

    46/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    … Input/Output / …Analog Input 1 (4)

    Elect. Low Sets the required electrical range.

    Note. Applicable only to Millivolts, M

    Linear Inputs Standard

    Millivolts 0 toMilliamps 0 t Volts 0

    Resistance (low) 0 tResistance (high) 0 t

    Elect High Sets the required electrical range

  • 8/18/2019 Manual usuario control ABB-CM10

    47/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    … Input/Output / …Analog Input 1 (4)

    Eng Units  The selected units are used by

    Not applicable for: Pulse Input ,

    Thermocouple and RTD  inputs

     Appendix C, page 106 for anal

    Eng. Dps Engineering decimal places – svalue.

    Eng Low Specifies the engineering low (m

    For example, for an electrical in

    of 50 to 250 bar, set the Eng L

    N li bl f P l I

  • 8/18/2019 Manual usuario control ABB-CM10

    48/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    … Input/Output / …Analog Input 1 (4)

    Pulse Units Selects the unit of measure for the p

    Pulse / Unit Sets the number of pulses required Pulse Units = Kl and Pulse / Unit = 1

    10 pulses = 1 Kl.

    Broken Sensor If an input failure occurs, the input v

    None No action taken.

     Automatic If the value of failed input is below E

    minimum downscale value; otherwis

  • 8/18/2019 Manual usuario control ABB-CM10

    49/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Input/Output / … …Analog Input 1 (4)

    Filter Time  The input is averaged over the

    Fault Detect Sets a tolerance level (in % of above or below the engineering

    Zero Adjustment

    Span Adjustment

     The Zero Adjustment  and Span

    eliminate system errors. Apply

    is displayed.

    Normally,  Zero Adjustment   is

    performed by applying an offse

    close to Eng High (adjustment

  • 8/18/2019 Manual usuario control ABB-CM10

    50/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Input/Output / … …Analog Outputs

    Elect. Low*  The current output required when th

    45.

    Elect. High*  The current output required when th

    45.

     Auto Eng Range* If enabled (On ) the Eng High and En

    range values of the source automat

    Eng Low*  The minimum engineering range out

    Eng High*  The maximum engineering range ou

  • 8/18/2019 Manual usuario control ABB-CM10

    51/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Input/Output

    Digital I/O

    Digital IO 1 (6)

    Type Sets the Digital IO to operate a

    Off  No action taken.

    Output   The Digital IO operates as an o

    Volt Free High input detected when volt-

     24 Volt  Digital input low < 5 V, high > 1

  • 8/18/2019 Manual usuario control ABB-CM10

    52/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Input/Output

    Relays

    Relay 1 (4)

    Source Selects the digital signal to be assdescription of sources.

    Polarity Sets the polarity of the relay.

    Positive  The relay is energized If the source

    Negative  The relay is energized If the source

  • 8/18/2019 Manual usuario control ABB-CM10

    53/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    7.4 Control

    Enables the setpoints, control functions and

    Loop 1 Setpoints  The controller can configure independlimit the absolute values and rate of ch

    Low Limit

    High Limit

     The setpoint Low / High Limit  parame

    and / or remote setpoints. Setpoint lim

    tracking enabled. If the setpoint is ou

    value can be adjusted only towards its

    MenuControl

  • 8/18/2019 Manual usuario control ABB-CM10

    54/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control / …Loop 1 Setpoints

    Track Mode  The local (internal) setpoint can track anselected.

    Off  No tracking.

    Local  The local (internal) setpoint tracks the proc

    Remote  The local (internal) setpoint tracks the remo

    the controller is put into Manual  control mo

    Note. Available only if the template selecte

    Local and Remote Note. Available only if the template selecte

  • 8/18/2019 Manual usuario control ABB-CM10

    55/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control / …Loop 1 Setpoints

    RSP Fault Action  The action required when a fault occu

    No Action No fault action.

    Local Selects the local (internal) setpoint mo

    Local Default  Selects the local (internal) setpoint mo

    Default Setpoint Sets the value required for the local (in

    Ramp Mode See Basic Level, page 28.

    Ramp Rate  See Basic Level, page 28.

  • 8/18/2019 Manual usuario control ABB-CM10

    56/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control / …Loop 1 Setpoints / Select Sources

    LSP1 (4) Select  The source required to select local setpoin

    local setpoint. Selection is made on the r

    signal.

    Local Select  The source required to select local setpoin

    local setpoint. Selection is made on the r

    signal.

    Remote Select  The source required to select remote setpo

  • 8/18/2019 Manual usuario control ABB-CM10

    57/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control

    Loop 1 Control Configures the basic type of control req

    settings.

    Control Type Selects the basic type of controller req

    PID Standard proportional, integral and de

    On/Off  A simple 2-state control.

    Note. Loop 1 output type must be se

    Control Action If the required controller action is know

    to Unknown and Autotune (see page

  • 8/18/2019 Manual usuario control ABB-CM10

    58/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control

    Loop 1 Output Used to set the output limits, tracking raprocess variable failure.

    Limits Note. When used with split output the limit

    the split output range values are calculated

    Limit Action Selects when the output limits should be a

    Low/High Limit Sets minimum / maximum controller outpu

    Failure Actions

    Power Recovery Used to select the default power failure mo

  • 8/18/2019 Manual usuario control ABB-CM10

    59/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control / …Loop 1 Output / …Failure Actions / …Power Reco

    Man – Default  Manual  control mode with output set

     Auto Mode  Auto control mode with integral term r

     Auto – Last   Auto control mode with integral term r

    PV Fail Action Determines the controller output when

    No Action No action is taken if the PV input fails.

    Man – HoldO/P 

    Puts the controller into Manual  controthe PV failure.

    Man Default Puts the controller into Manual contro

  • 8/18/2019 Manual usuario control ABB-CM10

    60/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control / …Loop 1 Output

     A/M Select Sources  The selection of A/M ( Auto / Manual  ) cosignals; either from internal digital signals

    digital inputs (or digital communications).

     Auto Select  The source required to select Auto contro

    is made on the rising edge of the digital sig

    Manual 1 (2)Select

     The source required to select  Manua

    Selection is made on rising edge of the d

    output value is set according to Manual 1 (2

    below).

    C lM CM 0 CM30 d CM 0

  • 8/18/2019 Manual usuario control ABB-CM10

    61/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control / …Loop 1 Output

    Manual 1 (2)Config O/P

    Used when Manual 1 (2) Output  is set

     A/M Toggle  The source required to toggle between A

    modes. When the digital signal is high,

    Manual  control mode (the front panel

    other digital select signals have no effec

    low, Auto control mode is selected. Whe

    front panel controls or edge-triggered di

    put the controller into Manual  control m

    A/M Output Sets the (manual) output value when

    C lM CM10 CM30 d CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    62/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control / …Loop 1 Output

    Slew Rate  The (output) Slew Rate restricts the maximcontrol output.

    Function Selects if the output Slew Rate function is

    Off 

    Up and Down  The Slew Rate applies to increasing and d

    Up  The Slew Rate applies to increasing outpu

    Down  The Slew Rate applies to decreasing outpu

    C t lM t CM10 CM30 d CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    63/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control /…Loop 1 Output

    Tracking Configures the control output follow a

    mode, the output can be adjusted as

    switching from Manual  to Auto is bump

    setting, the output ramps to its expect

    Source is set to None , tracking is disabl

    SourceSignal Source

    Sets the source of the signal required

    If set to None, output tracking is disab

    Mode Selects the type of object tracking.

    In Auto Control output tracking signal when

    C t lM t CM10 CM30 d CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    64/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Control

    Loop 1 Split O/P*

     The split output facility enables the PID control output (seepage 30 ) to be split into 2 separate outputs. This enables

    heat / cool and other applications requiring dual outputs to

    be controlled. The linear relationship between the input from

    the PID algorithm and the 2 outputs is configured using the

    Min and Max  Input / Output  parameters (below).

    When operating with Split O/P  in Manual  control mode,

    manual adjustment is made to the input at the split output

    block (x axis). By default, the Operator page displays both

    MinMinMaxMin

    C t lM t CM10 CM30 d CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    65/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    7.5 Process Alarm

    Used to configure up to 8 independent proce

    Process Alarm

    MenuProcess Alarm

    Hysteresis

    C t lM t CM10 CM30 d CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    66/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Process Alarm

    Hi h d L L t h A

     Trip

    Point

     Alarm On

    Hysteresis

    Process Variable

     Alarm Latched

     Alarm Acknowledged by Operator AlarmOff 

    High Latch Alarm

    C t lM t CM10 CM30 d CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    67/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Process Alarm / … Alarm 1 (8)

    Hysteresis Hysteresis trip level in engineering uwhen the process variable has move

    value – see Process Alarm examplesTime Hysteresis If an alarm trip value is exceeded, the

    has expired. If the signal goes out of

    the hysteresis timer is reset.

    Display Enable Enables an alarm to be used for contthe Operator  level or Diagnostic view

     Acknowledge

    S

     The source required to acknow

    A k l d i i d

    C t lM t CM10 CM30 d CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    68/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    7.6 Functions

    Contains parameters for setting up the math b

    controller.

    Logic Equations Up to 8 logic equations can be configsignals) with 7 operators. The elements o1, Operator 1 and Operand 2 are evaluaOperand 3. This result is then combined end of the equation.

    Note. If any of the operand sources are i

    l i ti t t t t i d i

    MenuFunctions

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    69/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Functions / Logic Equations

    Equation Number Selects the logic equation (1 to 8) to

    Operand 1 (8) See Appendix A , page 100 for desc

    Invert 1 (8) Logically inverts (applies NOT  functi

    For example, if the digital signal assiof '0' before being applied to the eq

    Operator1 (7) Selects the Operator  type: OR, AND

    Select END if no more elements are

    Math Blocks Up to 8 math blocks can be configtypes (see Block Type below). Thef i bl k f l P

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    70/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Functions / …Math Blocks / …Block Type

    Equation Enables an equation with up to 4 operandassigned to any analog or digital signal (s

    either '0' or '1'. With the exception of theleft to right order, with no operator prece

     The result of a math block can be used

    complex math equations to be construct

    math block 1 is processed first, then ma

    Operand 1

    O d 2

    Operator 1

     Add, SubtractMultiply, Divide

    L S l t

     

    M

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    71/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Functions / …Math Blocks / …Block Type

    Real Time Average

    Calculates the average value of a pthe math block is updated at the e

    configured to restart the calculation  The average value is stored in case than the Average Duration (see pag

    Max Hold  The math block output represents th

    Min Hold  The math block output represents th

    Multiplexer Enables 1 of 2 analog signals or con

     A 

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    72/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Functions / …Math Blocks

    Equation Setup

    Source 1 (2)  The source of the first operand in the

    constant).

    Source 1(2) Constant Sets the constant value to be used.

    Note. Applicable only if Source 1 (2) is a

    Operator 1 (3)

    End  Add Subtract 

    M lti l

     Terminates the equation.

    St d d ith ti f ti

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    73/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Functions / …Math Blocks

    Real Time Average Setup

    Source 1

    (RTA Source)

    Selects the source for real time ave

    of sources.

    Reset Source Select the digital source required to

     This does not change the immediatenext average value – see Appendix A

     Average Duration Sets the time duration the average i

     The output value of the math block

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    74/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Functions / …Math Blocks

    Multiplexer  Setup

    Source 1 Selects the source (any analog signal [se

    into the multiplexer.

    Source 1 Constant Sets the constant value to be used.

    Note. Applicable only if Source 1 is assig

    Source 2 Select the source for the second input in

    Source 2 Constant Sets the constant value to be used.

    Note. Applicable only if Source 1 is assig

    M S l t S l t th di it l i l t b d t

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    75/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Functions / …Math Blocks

    Setup for All Math Block Types 

    Eng. Dps Selects the resolution required to be

    Eng. LowEng High

    Selects the engineering range low /

    If the math block result exceeds theblock fail state is set and its output i

    Eng Units  The selected units are displayed idescription of engineering units. 

    Fault Action  The value returned when the math b

    N F il d l l t d l i d

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    76/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Function

    Linearizer 1 (2)  A 20-breakpoint (custom) linearizer. Cust

    1. Selecting an analog source as th

    2. Selecting the custom linearizer o

     The engineering range and units of the in

    linearizer output.

    Source 1 (2) Selects the input source to be linearizedsources.

    Lin 1 (2) Breakpoints Set X  and Y  values as a % of the enginee

    Breakpoint  Selects the breakpoint to be configured.

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    77/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Functions

    Delay Timer 1 (2)  2 Delay timers are provided. The de

     An internal timer is started and, whe

    for the configured On Time. After ththe source input until the end of this

    Source 1 (2)  The source signal used to trigger thsee page Appendix A , page 100 for

    Delay Time  The delay (in seconds) between the

    On Time  The length of time in seconds the de

    Real Time Alarms 2 Independent real-time alarms can

    d i

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    78/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    7.7 Communication

    …Functions / …Real Time Alarms / …Real Time Alarm 1 (2)

    On hour  Sets the hour the alarm is activated – no

    On minute Set the minutes past the hour the alarm

    Duration Set the duration the alarm is active.

    Display enable If disabled (Off  ), the alarm state does notalarm log

    Tag  A 16-character alphanumeric tag dispDiagnostic Status Bar  and the Diagnostic

  • 8/18/2019 Manual usuario control ABB-CM10

    79/112

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    80/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    …Diagnostics

    Source Analysis

     Analog Sources Enables the current value of any analog

     Analog Source Selects the analog signal to be viewed –

     View Value Displays the value of the analog signal s

    Digital Sources Enables the current state of any digital s

    Digital Source Selects the digital signal to be viewed –

     View State Displays the state of the digital signal se

    Invalid Sources Select edit to display any invalid analog

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    81/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    7.8.1 Diagnostic Messages

    Icon Number /Message

    Possible Cause

    242.004 ADC 1 Failed

     Temporary or permanent failure of analogconverter on the main I/O board.

    240.005 ADC 2 Failed

     Temporary or permanent failure of analogconverter on the option board.

    250.000 (248.001)PV 1 (2) Failed

    Problem with Input assigned to Loop 1 (2sensor leads, defective input source or inpof permitted range.

    246.002 Problem with Input assigned to Loop 1 (2

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    82/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    230.010(228.011)

    WV 1 (2) Failed

    Problem with input assigned to Loop 1 (2) wild vBroken sensor leads, defective input source or

    signal out of permitted range.234.008(232.009)

    PFB 1 (2) Failed

    Problem with input assigned to Loop 1 (2) positfeedback. Broken sensor leads, defective inputor input signal out of permitted range.

    216.016NV Error Proc Bd

    Failure of non-volatile memory on processor / dboard or permanent corruption of its data .

    214.017NV Error Main Bd

    Failure of non-volatile memory on main board opermanent corruption of its data.

    Icon Number /Message

    Possible Cause

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    83/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    208.020NV Error

    Comm Bd

    Failure of non-volatile memory on commuboard or permanent corruption of its data

    206.021NV Error

    SW Key 1

    Failure of non-volatile memory on Softwarpermanent corruption of its data.

    Config Error The configuration contains a source that ipresent or valid.

    Icon Number /Message

    Possible Cause

    ControlMaster CM10 CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    84/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    070.040(066.041)

     Tuner 1 (2) Abort Autotune has been aborted by the user.

    094.034(090.035)

     Valve 1 (2) Sticking

    Motorized valve travel time is significantly sloweconfigured time.

    168.026 (166.027)(164.028) Tuner 1

    Phase 1..3

     Autotune is in progress. See page 29 for details phase.

    160.030(158.031)

    Icon Number /Message

    Possible Cause

  • 8/18/2019 Manual usuario control ABB-CM10

    85/112

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    86/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    8 Templates and Functionality

    8.1 Basic Templates

    8.1.1 Single Loop / Single Loop with Remote Setpoint This template provides basic feedback control using three term PID o

    the difference between the process variable and the control setpoint

    user (Local setpoint) or an input from a remote source (remote setpo

    Notes.

    Input assignments can be changed in Device Setup

    Output assignments can be changed in Input / Outp

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    87/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    PV 

    L/R

    SP

     AIN 1

     AIN 2x Ratio+ Bias

    LSPT1

    LSPT2

    LSPT3

    LSPT4

    LocalSet Point

    MO

    Loop 1PID Control1

    RSP

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    88/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    8.2 Standard Templates

    8.2.1 Auto / Manual Station (Low Signal Selection / Digi This template configures the ControlMaster as a back up for a

    ControlMaster's current output follows the master controllers output Upon detection of a fault in the Master system, which is identified b

    digital Input signal, the ControlMaster selects Manual Mode with eith

    fixed output value.

    Once the Master signal is restored or the digital input state returns to

    Mode and continues to follow the Master Controller output.

    (See Fig. 8.4, page 88 for details of parallel connection).

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    89/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    8.2.2 Analog Backup Station (Low Signal Selection / This template provides a back up for a master controller (syste

    Remote Control Mode. In this mode the output of the ControlMa

    in the Master system, either by a low signal on the Master outp

    Control Mode and the process is controlled by the PID output o The PID algorithm continuously tracks the Master Controller ou

    operation. Once the Master Controller output is restored or th

    switches back to Remote Control Mode and continues to track

    (See Fig. 8.4, page 88 for details of parallel connection).

     AIN 1PV 

    Loop 1PID Control

    LSPT1

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    90/112

    ControlMaster CM10, CM30 and CM50

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

     The auto-manual station and analog backup station templates can be

    Parallel operation is achieved by using an external relay that is triggere

    to be routed to the process. This setup allows uninterrupted control,

    or ControlMaster.

    ControlOutput

    MasterController

     AIN 2 +Output

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    91/112

    ,

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    8.2.3 Single Indicator The Single Indicator template is used to display one variable on

    8.2.4 Dual Indicator The Dual Indicator template is used to display two process varia

    Fig. 8.5 Single Indicator Template

    Ma AIN 1 PV 

    M AIN 1 PV 1

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    92/112

    ,

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    9 PC ConfigurationIn addition to local configuration via the front panel keys, the controlle

     The infrared port is activated when Advanced  level is accessed. For f

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    93/112

    ,

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    10 Specification

    Operation

    Display

    Language

    Operator keypad

    Color 1 / 4 VGA TFT, liquid crystal display (LCD) with built-inbacklight

    English, German, French, Italian and Spanish

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    94/112

    ,

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Control output types

    Current proportioning

     Time proportioning

    On / Off 

    Motorized valve with feedback 

    Motorized valve without feedback 

    Split output – with combinations of relay, digital output andcurrent outputs

    Control parameters

    Proportional band (0 to 999.9 %)

    Integral (0 to 10000 s)

    Derivative (0.0 to 999.9 s)

     Aut

    O

    Pro

    N

     T

    S

    H

     A

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    95/112

    ,

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Maths blocks

    Delay timers

    Number 8

    Operators +, –, x , /  

     Average, Maximum, Minimum

    High / Low / Median Select

    Square root

    Multiplexer

    Number 2

    Programmable Delay

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    96/112

    ,

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Other linearizations

    x, x3/2, x5/2

    Digital filter 

    Programmable 0 to 60 s

    Display range

    –9999 to 99999

    Update rate

    125 ms

    Common mode noise rejection

    >120 dB at 50 / 60 Hz with 300  imbalance resistance

    Normal (series) mode noise rejection

    >60 dB at 50 / 60 Hz

     In

    T

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    97/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    RTD Maximum Range°C (°F)

     Accuracy(% of reading)

    Pt100–200 to 600

    (–325 to 1100)0.1 % or ±0.5 °C

    (0.9 °F)

    Linear InputsStandard

     Analog Input Accuracy

    (% of reading)

    Millivolts

    Milliamps

    0 to 150 mV 

    0 to 50 mA 

    0.1 % or ±20 µV 

    0.2 % or ±4 µA 

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    98/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Outputs

    Controls / retransmission outputs Rel

    Number 2 (1 standard, 1 optional)

    Isolation Galvanically isolated from the rest of the circuitry,500 V for 1 minute

     Analog range 0 to 20 mA Programmable

    Load 750 Max.

     Accuracy 0.25 % of output or ±10 µA 

    N

     T

    C

    C

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    99/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Digital input / output

    CM10 2 (Optional)

    CM30 / CM50 6 (2 Standard, 4 optional)

     Type User-programmable as input or output

    Minimum input pulse duration – 125 ms

    Input

    – volt-free or 24 V DC

    – 1-signal: 15 to 30 V 

    – 0-signal: –3 to 5 V 

    – Conforms to IEC 61131-2

    Output

    – Open collector output

    – 30 V, 100 mA max. switched

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    100/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Safety

     Approvals and certifications

    EN61010-1

    cULus

    General safety

    Pollution category 2

    Insulation category 2

    Isolation (to inputs)

    Ele

    Sup

    1

    1

    Pow

    1

    Pow

    N

     Analog I/Ps Comms

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    101/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Physical

    Size

    Weight

    Panel cutout

    CM10 50 x 97 x 141 mm (2.0 x 3.8 x 5.5 in.)

    CM30 97 x 97 x 141 mm (3.8 x 3.8 x 5.5 in.)CM50 144 x 76 x 146 mm (5.6 x 3.0 x 5.7 in.)

    CM10 0.38 kg (0.84 lb) approx. (unpacked)

    CM30 0.5 kg (1.1 lb) approx. (unpacked)

    CM50 0.57 kg (1.27 lb) approx. (unpacked)

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    102/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

     Appendix A – Digital and Analog Sources

     A.1 Digital Sources

    Note. Numbers in brackets indicate additional parameters, for exam

    State parameters are available.

    Source Name Description [Comment]

     Alarm 1 (8) Ack. State Acknowledged alarm = 0Unacknowledged alarm = 1

     Alarm 1 (8) State Alarm State

     Analog input failure (active when the signal

    Lo

    Lo

    Lo

    So

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    103/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    Loop 1 Ctrl Track Control track state

    Math Block 1 (8) Fail Maths failure

    RTA 1 (2) State Real time alarm state

    Softkey ToggleFront panel soft key toggles the source’sstate.

    Softkey EdgeFront panel soft key sets the source activeon key press.

     T1 (2) Int Pulse Totalizer intermediate pulse. Active for1 second when the intermediate count isreached.

     Totalizer run state

    Source Name Description [Comment]

    ControlMaster CM10, CM30 and CM50

  • 8/18/2019 Manual usuario control ABB-CM10

    104/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

     Appendix B – Configuration Error CodesConfiguration errors are generated when a signal assigned as a sourc

    Configuration errors are displayed as numerical codes and a descrip

    ErrorCode

    Error Description

    1 Analog Input Value A1 (I/P 1)

    2 Analog Input Value A2 (I/P 2)

    3 Analog Input Value B1(I/P 3 – CM50)

    4 Analog Input Value B2(I/P 4 – CM50)

    13 Setpoint Actual R

    14 Setpoint SelectedLSPT Value 2

    15 Setpoint ControlSetpoint Value 2

    16 Setpoint SelectedRatio Value 2

    ErrorCode

    Error Description

  • 8/18/2019 Manual usuario control ABB-CM10

    105/112

    ControlMaster CM10, CM30 and CM501 1 1

  • 8/18/2019 Manual usuario control ABB-CM10

    106/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    98 Analog Input State C1(I/P 3 – CM30)

    99 Analog Input State C2(I/P 4– CM30)

    100 Setpoint Remote Mode State 1

    101 Setpoint LSPT 1Selected State 1

    102 Setpoint LSPT 2Selected State 1

    103 Setpoint LSPT 3Selected State 1

    ErrorCode

    Error Description

    108 Setpoint LSPT 3Selected State 2

    109 Setpoint LSPT 4Selected State 2

    110 Digital Input State

    111 Digital Input State

    112 Digital Input State

    113 Digital Input State

    114 Digital Input State

    115 Digital Input State

    ErrorCode

    Error Description

    ControlMaster CM10, CM30 and CM501 1 1

  • 8/18/2019 Manual usuario control ABB-CM10

    107/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    154 Alarm Ack State 7

    155 Alarm State 8

    156 Alarm Ack State 8

    157 Time Prop State 1

    158 Time Prop State 2

    159 Time Prop State 3

    160 Time Prop State 4

    161 Control O/P Auto State 1

    162 Control O/P Manual State 1

    ErrorCode

    Error Description

    169 Mot Valve C

    170 Mot Valve O

    171 Mot Valve S

    172 Mot Valve T

    173 Mot Valve T

    174 Mot Valve C

    175 Mot Valve O

    176 Mot Valve S

    177 Delay Timer

    ErrorCode

    Error Desc

    ControlMaster CM10, CM30 and CM501 1 1

  • 8/18/2019 Manual usuario control ABB-CM10

    108/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

     Appendix C – Analog Input (Engineering) Units

    Unit Description

    % %

    % sat % saturation

    %dO2 % dissolved oxygen

    %HCI % hydrochloric acid

    %N2 % nitrogen

    %O2 % oxygen

    %OBS % obscuration

    %RH % relative humidity

    ControlMaster CM10, CM30 and CM501/ 1/ 1/

  • 8/18/2019 Manual usuario control ABB-CM10

    109/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

    m WG meters water gauge

    m3 /d, m3 /h, m3 /m, m3 /scubic meters per day, hour, minute,second.

    mbar millibar

    mg/kg milligrams per kilogram

    Mgal/d (UK) imperial mega gallons per day

    Mgal/d (US) US mega gallons per day

    mho conductance

    Ml/d, Ml/h megaliters per day, hour.

    ml/h ml/m milliliters per hour minute

    Unit Description

    ControlMaster CM10, CM30 and CM50

    U i l ll 1/ 1/ d 1/ DIN

  • 8/18/2019 Manual usuario control ABB-CM10

    110/112

    Universal process controllers, 1 / 8, 1 / 4 and 1 / 2 DIN

     Appendix D – Output Type Assignments

    Output Type AO 1 AO 2 DIO 1 DIO 2

     Analog OP PV

     Time Proportioning PV SP

    MValve + Feedback PV SP

    MValve Boundless PV SP OP 2

    Split Output Analog / Relay

    OP 1 PV

    Split Output Analog / Digital

    OP 1 PV OP 2

    Split Output

    Refer to Section 7.6, page 66 Refer toRefer to Section 7.5, page 63

    Process Alarm

    Menu

    Functions Com

    Menu Menu

    http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/http://im_cm_s-en_m.pdf/

  • 8/18/2019 Manual usuario control ABB-CM10

    111/112

    Alarm 1 (8)TypeTagSourceTripHysteresisTime Hysteresis

    Display EnableAcknowledge Source

    Enable Source

    Process Alarm

    Exit Select

    Logic EquationsEquation NumberOperand 1 (8)Invert 1 (8)Operator 1 (7)

    Math Blocks

    Math Block NumberBlock TypeEng. DPsEng. LowEng. HighEng. UnitsFault ActionSource 1 (2)Source 1 (2) ConstantReset SourceAverage DurationOperator 1 (3)Mux Selector

    Linearizer 1 (2)Source 1 (2)Lin 1 (2) Breakpoints

    Delay Timer 1 (2)SourceDelay Time

    On TimeReal Time AlarmsReal Time Alarm 1 (2)

    Refer todetails paramete

    Functions Com

    Exit Select Exit

    CCustomer Support

    We provide a comprehensive after sales service via a Worldwide

    Service Organization. Contact one of the following offices for

    details on your nearest Service and Repair Centre.

  • 8/18/2019 Manual usuario control ABB-CM10

    112/112

    y p

    UK  ABB Limited

     Tel: +44 (0)1480 475321

    Fax: +44 (0)1480 217948

    USA 

     ABB Inc.

     Tel: +1 215 674 6000

    Fax: +1 215 674 7183

    Client WarrantyPrior to installation, the equipment referred to in this manual must be stored in a clean, dry environment, in accordance with the

    Company's published specification.

    Periodic checks must be made on the equipment's condition. In the event of a failure under warranty, the following