Manual: Distribution Substation Manual (DSM) Section 1: Customer Supply Arrangements Standard Number: HPC-5DA-07-0001-2012
DM# 3666709 Page 2 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
Document Control
Author Name: Viswa Easwaran
Position: Standards Engineer
Document Owner
(May also be the Process Owner)
Name: Justin Murphy
Position: Manager Asset & Works
Approved By * Name: Justin Murphy
Position: Manager Asset & Works
Date Created/Last Updated July 2013
Review Frequency ** 3 yearly
Next Review Date ** July 2016
* Shall be the Process Owner and is the person assigned authority and responsibility for managing the whole process, end-to-end, which may extend across more than one division and/or functions, in order to deliver agreed business results.
** Frequency period is dependent upon circumstances– maximum is 5 years from last issue, review, or revision whichever is the latest. If left blank, the default shall be 1 year unless otherwise specified.
Revision Control
Revision Date Description
0 12/07/2013 Original Issue
STAKEHOLDERS The following positions shall be consulted if an update or review is required:
Manager Assets & Works
Manager Engineering Services
Manager Engineering Systems Planning
DM# 3666709 Page 3 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
TABLE OF CONTENTS
1 PURPOSE .................................................................................................... 4
2 SCOPE ......................................................................................................... 4
3 CONTENTS .................................................................................................. 5 3.1 Index of Drawings ................................................................................................. 5
4 REFERENCE DOCUMENT .......................................................................... 6
5 REVISION INFORMATION .......................................................................... 6
DM# 3666709 Page 4 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
1 PURPOSE
This Standard specifies the connection arrangements that shall be used to meet the electricity requirements of customers supplied at either low voltage (LV) (up to 4000 kVA) or alternatively at medium voltage (MV). Connection arrangements, options for achieving higher than normal levels of reliability, together with the required high and low voltage electrical protection devices are included.
This Standard supersedes the Western Power Document (record DMS# 3254304]
previously in use by Horizon Power since disaggregation.
2 SCOPE
This Standard covers the following arrangements:
Low voltage connection arrangements to be used for customer electricity
supply up to 4000 kVA, including the maximum consumers mains sizes and electrical protection devices that shall be used;
Medium voltage connection arrangements to be used for customer electricity
supply at medium voltage supply;
District, Sole use and Customer Owned Substation arrangements, required
to provide for the customers present and future load requirements;
Arrangements available to provide higher levels of reliability to meet
customers required supply reliability requirements.
DM# 3666709 Page 5 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
3 CONTENTS
3.1 Index of Drawings
Drawing Number Drawing Title
DSM-1-01 Legend
DSM-1-02 Transformer & LV Feeder – Ground Mounted Fusing
Transformer & LV Feeder – Overhead Fusing
Isolation Transformer – Overhead and RMU Fusing
District Substations
DSM-1-03 Discrete LV Load Below 315 A
Customer’s MSB Non Contiguous
Customer Supplied From Shared LV Street Circuit
DSM-1-04 Discrete LV Load Up To 315 A
Customer’s MSB Non Contiguous
Customer Supplied From Dedicated LV Street Circuit
DSM-1-05 Discrete LV Load Up To 1310 A
Customer’s MSB Contiguous
Customer Supplied From Dedicated LV Circuit
DSM-1-06 Discrete LV Load Up To 2000 A
Customer’s MSB Contiguous
Customer Supplied From Dedicated LV Circuit
Sole Use Substations
DSM-1-07 Discrete LV Load Up To 1310 A
Customer’s MSB Contiguous
Customer Supplied From Dedicated Transformer
DSM-1-08 Discrete LV Load Up To 2625 A
Customer’s MSB Contiguous
Customer Supplied From Dedicated Transformers
DSM-1-09 Discrete LV Load Up To 5250 A
Customer’s MSB Contiguous
Customer Supplied From Dedicated Transformers
Customer Owned Substations
DSM-1-10 Customer MV Metering
Ground Mounted Overhead and Outdoor
Ground Mounted Outdoor and Indoor
DM# 3666709 Page 6 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
4 REFERENCE DOCUMENT
The following Reference Documents have been used to prepare this Standard:
Doc Ref. Document Title Record No DM#
Publisher
Distribution Substation Manual - Section 1 Customer Substation Arrangements
3246304 (Superseded)
Horizon Power
Western Australian Distribution Connections Manual
3468505 Regional Power & Electricity Networks Corporation
5 REVISION INFORMATION
(Informative) Horizon Power has endeavoured to provide standards of the highest quality and would appreciate notification if any errors are found or even queries raised.
Each Standard makes use of its own comment sheet which is maintained throughout the life of the standard, which lists all comments made by stakeholders regarding the
standard.
A comment sheet found in DM:3507040 can be used to record any errors or queries
found in or pertaining to this standard, which can then be addressed whenever the standard gets reviewed.
Date Rev No. Notes
0 12/07/2013 Original Issue
DM# 3666709 Page 7 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 8 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 9 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 10 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 11 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 12 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 13 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 14 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 15 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 16 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 17 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 18 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 19 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 20 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
DM# 3666709 Page 21 of 21 Print Date 15/07/2013
© Horizon Power Corporation – Document Number: HPC-5DA-07-0001-2012 Uncontrolled document when printed. Printed copy expires one week from print date. Refer to Document No. for current version.
.