Symmetra™ PX 160 Maintenance Bypass Enclosure Installation 05/2014 www.schneider-electric.com

Transcript of Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ......

Page 1: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Symmetra™ PX 160Maintenance Bypass Enclosure

Installation

05/2014

www.schneider-electric.com

Page 2: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Legal InformationThe Schneider Electric brand and any registered trademarks of Schneider ElectricIndustries SAS referred to in this guide are the sole property of Schneider ElectricSA and its subsidiaries. They may not be used for any purpose without the owner'spermission, given in writing. This guide and its content are protected, within themeaning of the French intellectual property code (Code de la propriétéintellectuelle français, referred to hereafter as "the Code"), under the laws ofcopyright covering texts, drawings and models, as well as by trademark law. Youagree not to reproduce, other than for your own personal, noncommercial use asdefined in the Code, all or part of this guide on any medium whatsoever withoutSchneider Electric's permission, given in writing. You also agree not to establishany hypertext links to this guide or its content. Schneider Electric does not grantany right or license for the personal and noncommercial use of the guide or itscontent, except for a non-exclusive license to consult it on an "as is" basis, at yourown risk. All other rights are reserved.

Electrical equipment should be installed, operated, serviced, and maintained onlyby qualified personnel. No responsibility is assumed by Schneider Electric for anyconsequences arising out of the use of this material.

As standards, specifications, and designs change from time to time, please ask forconfirmation of the information given in this publication.

Page 3: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure

Table of Contents

Important Safety Information.....................................................................1

Safety Precautions .....................................................................................2Electrical Safety....................................................................................4

Specifications ..............................................................................................6

Product Overview........................................................................................8

Installation..................................................................................................10

Prepare for Cables ...................................................................................10

Mount the Maintenance Bypass Enclosure to the Wall ................................. 11

Connect the Power Cables ........................................................................ 11

Connect the Communication Cables ..........................................................13

Diagram...................................................................................................13

990–4907A-001 i

Page 4: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure

ii 990–4907A-001

Page 5: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Important Safety Information Maintenance Bypass Enclosure

Important Safety InformationRead these instructions carefully and look at the equipment to become familiar withit before trying to install, operate, service or maintain it. The following safetymessages may appear throughout this manual or on the equipment to warn ofpotential hazards or to call attention to information that clarifies or simplifies aprocedure.

The addition of this symbol to a “Danger” or “Warning” safetymessage indicates that an electrical hazard exists which will result inpersonal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potentialpersonal injury hazards. Obey all safety messages with this symbolto avoid possible injury or death.

DANGERDANGER indicates a hazardous situation which, if not avoided, will result indeath or serious injury.

Failure to follow these instructions will result in death or serious injury.

WARNINGWARNING indicates a hazardous situation which, if not avoided, could result indeath or serious injury.

Failure to follow these instructions can result in death, serious injury, orequipment damage.

CAUTIONCAUTION indicates a hazardous situation which, if not avoided, could result inminor or moderate injury.

Failure to follow these instructions can result in injury or equipmentdamage.

NOTICENOTICE is used to address practices not related to physical injury. The safetyalert symbol shall not be used with this type of safety message.

Failure to follow these instructions can result in equipment damage.

Please NoteElectrical equipment should only be installed, operated, serviced, and maintainedby qualified personnel. No responsibility is assumed by Schneider Electric for anyconsequences arising out of the use of this material.

990–4907A-001 1

Page 6: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure Important Safety Information

A qualified person is one who has skills and knowledge related to the construction,installation, and operation of electrical equipment and has received safety trainingto recognize and avoid the hazards involved.

Safety Precautions

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

All safety instructions in this document must be read, understood and followed.

Failure to follow these instructions will result in death or serious injury.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

Read all instructions in the Installation Manual before installing or working on thisUPS system.

Failure to follow these instructions will result in death or serious injury.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

Do not install the UPS system until all construction work has been completedand the installation room has been cleaned.

Failure to follow these instructions will result in death or serious injury.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

• The product must be installed according to the specifications andrequirements as defined by Schneider Electric. It concerns in particular theexternal and internal protections (upstream circuit breakers, battery circuitbreakers, cabling, etc.) and environmental requirements. No responsibility isassumed by Schneider Electric if these requirements are not respected.

• After the UPS system has been electrically wired, do not start up the system.Startup must only be performed by Schneider Electric.

Failure to follow these instructions will result in death or serious injury.

2 990–4907A-001

Page 7: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Important Safety Information Maintenance Bypass Enclosure

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

The UPS System must be installed according to local and national regulations.Install the UPS according to:

• IEC 60364 (including 60364–4–41- protection against electric shock, 60364–4–42 - protection against thermal effect, and 60364–4–43 - protection againstovercurrent), or

• NEC NFPA 70

depending on which one of the standards apply in your local area.

Failure to follow these instructions will result in death or serious injury.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

• Install the UPS system in a temperature controlled environment free ofconductive contaminants and humidity.

• Install the UPS system on a non-inflammable, level and solid surface (e.g.concrete) that can support the weight of the system.

Failure to follow these instructions will result in death or serious injury.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

The UPS is not designed for and must therefore not be installed in the followingunusual operating environments:

• Damaging fumes

• Explosive mixtures of dust or gases, corrosive gases, or conductive or radiantheat from other sources

• Moisture, abrasive dust, steam or in an excessively damp environment

• Fungus, insects, vermin

• Salt-laden air or contaminated cooling refrigerant

• Pollution degree higher than 2 according to IEC 60664-1

• Exposure to abnormal vibrations, shocks, and tilting

• Exposure to direct sunlight, heat sources, or strong electromagnetic fields

Failure to follow these instructions will result in death or serious injury.

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Do not drill/punch holes for cables or conduits with the gland plates installed anddo not drill/punch in close proximity to the UPS.

Failure to follow these instructions will result in death or serious injury.

990–4907A-001 3

Page 8: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure Important Safety Information

WARNINGHAZARD OFARC FLASH

Do not make mechanical changes to the product (including removal of cabinetparts or drilling/cutting of holes) that are not described in the Installation Manual.

Failure to follow these instructions can result in death, serious injury, orequipment damage.

WARNINGHAZARD OF OVERHEATING

Respect the space requirements around the UPS system and do not cover theproduct’s ventilation openings when the UPS system is in operation.

Failure to follow these instructions can result in death, serious injury, orequipment damage.

WARNINGHAZARD OF EQUIPMENT DAMAGE

Do not connect the UPS output to regenerative load systems includingphotovoltaic systems and speed drives.

Failure to follow these instructions can result in death, serious injury, orequipment damage.

Electrical Safety

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

• Electrical equipment must be installed, operated, serviced, and maintainedonly by qualified personnel.

• The UPS system must be installed in a room with restricted access (qualifiedpersonnel only).

• Apply appropriate personal protective equipment (PPE) and follow safeelectrical work practices.

• Turn off all power supplying the UPS system before working on or inside theequipment.

• Before working on the UPS system, check for hazardous voltage between allterminals including the protective earth.

• The UPS contains an internal energy source. Hazardous voltage can bepresent even when disconnected from the mains supply. Before installing orservicing the UPS system, ensure that the units are OFF and that mains andbatteries are disconnected. Wait five minutes before opening the UPS toallow the capacitors to discharge.

• A disconnection device (e.g. disconnection circuit breaker or switch) must beinstalled to enable isolation of the system from upstream power sources inaccordance with local regulations. This disconnection device must be easilyaccessible and visible.

• The UPS must be properly earthed/grounded and due to a high leakagecurrent, the earthing/grounding conductor must be connected first.

Failure to follow these instructions will result in death or serious injury.

4 990–4907A-001

Page 9: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Important Safety Information Maintenance Bypass Enclosure

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

In systems where backfeed protection is not part of the standard design, anautomatic isolation device (backfeed protection option or other device meetingthe requirements of IEC/EN 62040–1 or UL1778 4th Edition – depending onwhich of the two standards apply to your local area) must be installed to preventhazardous voltage or energy at the input terminals of the isolation device. Thedevice must open within 15 seconds after the upstream power supply fails andmust be rated according to the specifications.

Failure to follow these instructions will result in death or serious injury.

When the UPS input is connected through external isolators that, when opened,isolate the neutral or when the automatic backfeed isolation is provided external tothe equipment or is connected to an IT power distribution system, a label must befitted at the UPS input terminals, and on all primary power isolators installedremote from the UPS area and on external access points between such isolatorsand the UPS, by the user, displaying the following text (or equivalent in a languagewhich is acceptable in the country in which the UPS system is installed):

DANGERHAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Risk of Voltage Backfeed. Before working on this circuit: Isolate the UPS andcheck for hazardous voltage between all terminals including the protective earth.

Failure to follow these instructions will result in death or serious injury.

990–4907A-001 5

Page 10: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure Specifications

Specifications

ElectricalUPS rating 96 kVA 160 kVA

Input voltage(V)

380 400 415 380 400 415

Nominal inputcurrent (A)

154 146 141 256 243 234

Maximumrated inputcurrent (340V input )(A)

169 160 155 281 267 258

Inputfrequency(Hz)

50/60

Maximumshort-circuitwithstand(kA) Icc

Rated conditional short-circuit current Icc: 30 kA symmetrical rmsRated peak withstand current Ipk: 63 kADevice: NSX400F Mic2.3 3P 320 A setting (manufacturer: Schneider Electric) for 160 kVA, orNSX250F TMD200 3P (manufacturer: Schneider Electric) for 96 kVA

Maximumshort-circuitwithstand(kA) Icw

Rated short-time withstand current Icw: 13 kA symmetrical rmsRated peak withstand current Ipk: 26 kAShort-circuit withstand time: 3 cycles

Switch SizesMains input switch Q1 (A) 400

UPS output switch Q2 (A) 250

Maintenance bypass switch Q3 (A) 250

Upstream Protection

NOTICEFor a maximum short-circuit withstand higher than 13 kA, it is mandatory toinstall a circuit breaker (NSX250F TMD200 3P or NSX400F Mic2.3 3P 320 Asetting) upstream of the maintenance bypass enclosure.

Failure to follow these instructions can result in equipment damage.

UPS rating Required protection Max input current

96 kVA NSX250F TMD200 3P 169 A

160 kVA NSX400F Mic2.3 3P 320 A setting 281 A

6 990–4907A-001

Page 11: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Specifications Maintenance Bypass Enclosure

Recommended Cable SizesNOTE: Use only copper conductors with a minimum rating for 90 °C.

NOTE: 30℃ ambient temperature, IEC standard 60364-5-52, Table A.52-4 (52-C3), "C" method of installation. If the ambient room temperature is higher than 30℃, larger conductors are to be selected in accordance with the correction factorsof the IEC.

UPS rating 96 kVA UPS 160 kVA UPS

Input cable (L1, L2, L3, N, PE)(mm2)

70 120

Output cable (L1, L2, L3, N, PE)(mm2)

50 95

Maintenance bypass to UPS inputcable (mm2)

70 120

UPS output to maintenance bypasscable (mm2)

50 95

Weights and Dimensions

Weight (kg) Height (mm) Width (mm) Depth (mm)

Without packaging 90 1200 800 300

With packaging 105 1230 830 350

EnvironmentalStorage Operation

Temperature -25 °C to 55 °C 0 °C to 40 °C

Relative humidity 0 to 95% non-condensing

Elevation 0 to 15000 m 0 to 3000 m

Protection class IP20

Color Black

Torque

Torque (Nm) Screws

Mains input terminal block 23 M8 X 25 MSC HXG STL

Mains input to UPS terminal block 23 M8 X 25 MSC HXG STL

UPS output terminal block 23 M8 X 25 MSC HXG STL

System output terminal block 23 M8 X 25 MSC HXG STL

990–4907A-001 7

Page 12: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure Product Overview

Product OverviewFront view (interior)

A. Cable entry

B. PE busbar

C. Q2 – UPS output switch

D. Q3 – Maintenance bypass switch

E. Q1 – Mains input switch

F. Q10 – LED protection breaker

G. LED H3 – OK to operate Q3 when light is ON

H. LED H2 – OK to operate Q2 when light is ON

I. Terminal block – signal connection to UPS

Site PlanningNOTE: Select a location for the maintenance bypass enclosure which provideseasy access to all breakers and internal components.

NOTE: Select a wall that is structurally sound and able to support the size andweight of the maintenance bypass enclosure.

8 990–4907A-001

Page 13: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Product Overview Maintenance Bypass Enclosure

ClearanceFollow the listed clearance requirements and consult local codes for any additionalrequirements.

The best location for the maintenance bypass enclosure is close to the UPS.

Front view

A. Minimum front clearance: 650 mm

B. Minimum enclosure–to–floor clearance: 600 mm

C. Minimum side clearance: 100 mm

990–4907A-001 9

Page 14: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure Installation

Installation

Prepare for CablesNOTE: All power cables must be connected on site. External power cables are notsupplied with the maintenance bypass enclosure.

NOTE: Schneider Electric recommends to create the necessary holes for cableaccess before mounting the maintenance bypass enclosure to the wall.

NOTE: The size of the holes and glands must be adapted to fit the size of thecables.

1. Open the front door of the enclosure.

2. Remove the front panel.

3. Remove the bottom plate.

4. Drill holes for cables in the bottom plate. Make sure that the hole locationscorrespond to the connector locations in the enclosure.

5. Reinstall the bottom plate.

Front view

10 990–4907A-001

Page 15: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Installation Maintenance Bypass Enclosure

Mount the Maintenance Bypass Enclosure to the Wall1. Measure and mark the four mounting hole locations on the wall.

2. Drill holes in each of the four marked locations and mount the anchor bolts.

3. Lift the maintenance bypass enclosure, position it against the backing and line itup with the four holes/anchor bolts. Secure the enclosure with the four bolts andflat washers.

Connect the Power Cables

NOTICEFor a maximum short-circuit withstand higher than 13 kA, it is mandatory toinstall a circuit breaker (NSX250F TMD200 3P or NSX400F Mic2.3 3P 320 Asetting) upstream of the maintenance bypass enclosure.

Failure to follow these instructions can result in equipment damage.

990–4907A-001 11

Page 16: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure Installation

1. Route the cables through the holes in the bottom plate of the maintenancebypass enclosure.

2. Connect the UPS input cables (L1, L2, L3, N) to the UPS input terminals andthe PE cable to the PE bar.

3. Connect the AC input cables (L1, L2, L3, N) to the AC input terminal block andthe PE cable to the PE bar.

4. Connect the system output cables from the UPS (L1, L2, L3, N) to the systemoutput terminals and the PE cable to the PE bar.

5. Connect the UPS output cables (L1, L2, L3, N) to the UPS output terminals andthe PE cable to the PE bar.

12 990–4907A-001

Page 17: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Installation Maintenance Bypass Enclosure

Connect the Communication CablesLocated inmaintenancebypass

Located inUPS J2

Q1

Q2

Q3

From Q10L1

H2

H3N

MBBDry contact

123456

123456

78

78

91011121314

910

Diagram

NOTICEFor a maximum short-circuit withstand higher than 13 kA, it is mandatory toinstall a circuit breaker (NSX250F TMD200 3P or NSX400F Mic2.3 3P 320 Asetting) upstream of the maintenance bypass enclosure.

Failure to follow these instructions can result in equipment damage.

990–4907A-001 13

Page 18: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure Installation

14 990–4907A-001

Page 19: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Maintenance Bypass Enclosure Installation

Page 20: Maintenance Bypass Enclosure Installation - · PDF fileUPS rating 96 kVA 160 kVA ... Recommended Cable Sizes NOTE: ... Maintenance Bypass Enclosure Installation Installation. R. Schneider

Schneider Electric35 rue Joseph Monier92500 Rueil MalmasonFrance

+ 33 (0) 1 41 29 70 00www.schneider-electric.com

As standards, specifications, and design change fromtime to time, please ask for confirmation of theinformation given in this publication.© 2013 – 2014 Schneider Electric. All rights reserved.990–4907A-001