CLEARWATER, FLSeptember 5, 2002
Mining Electrical Maintenance and Safety Association
![Page 2: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/2.jpg)
FULLY AUTOMATIC BACKUP GENERATOR
SYSTEM
Larry CassonDrummond Co. Inc.
![Page 3: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/3.jpg)
METHODS OF APPLYING POWER GENERATORS
1. STAND ALONE GENERATOR(S)• One or more generators provide all the real power
(KW) and reactive power (KVAR) required by the load. Paralleling generators require KW and KVAR sharing.
2. BASE LOADING• One or more generators providing constant real
output power (KW) and reactive power (KVAR). May be expressed as power (KW) and power factor (PF).
![Page 4: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/4.jpg)
![Page 5: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/5.jpg)
![Page 6: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/6.jpg)
![Page 7: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/7.jpg)
![Page 8: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/8.jpg)
![Page 9: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/9.jpg)
![Page 10: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/10.jpg)
![Page 11: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/11.jpg)
![Page 12: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/12.jpg)
34,500 VOLTSGENERATOR
# 1GENERATOR
# 2
OVERHEAD LINE # 1
OVERHEAD LINE # 2
4160 VOLTS
![Page 13: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/13.jpg)
UNLOADING TRAIN WITH DUAL CAR DUMPER AND POSITIONING CARS WITH A TRAIN CAR INDEXER
POWER IN KW
![Page 14: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/14.jpg)
MANUAL SWITCH TO GENERATORS
MANUAL SWITCH TO INCOMING POWER
![Page 15: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/15.jpg)
BASICS
![Page 16: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/16.jpg)
KW
KVARKVA
POWER TRIANGLE
PF = COS of included angle = KW/KVA
Included angle
![Page 17: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/17.jpg)
KW
KVAR
POWER TRIANGLEBase loading
Throttle
Voltage regulator
![Page 18: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/18.jpg)
+ KW- KW
+ KVAR
- KVAR
4 POWER QUADANTS
+ KVARProducing
REVERSE POWER PROTECTION REQUIRED
-KVAR Absorbing
![Page 19: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/19.jpg)
![Page 20: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/20.jpg)
![Page 21: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/21.jpg)
![Page 22: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/22.jpg)
![Page 23: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/23.jpg)
![Page 24: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/24.jpg)
![Page 25: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/25.jpg)
UNDERGROUND 14,400 VOLT SYSTEM
KW
KVAR
ONE GENERATOR RUNNING
![Page 26: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/26.jpg)
![Page 27: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/27.jpg)
![Page 28: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/28.jpg)
![Page 29: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/29.jpg)
![Page 30: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/30.jpg)
![Page 31: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/31.jpg)
![Page 32: M E M S A](https://reader035.fdocuments.in/reader035/viewer/2022070423/5681678c550346895ddcacbf/html5/thumbnails/32.jpg)
WHY USE GENERATORS
• BACKUP POWER SYSTEM• REDUCE POWER SYSTEM LOADING• HELP STABILIZE VOLTAGE